Rockwell Automation 1606-XLS960EE User Manual

Reference Manual
egaP egaP
1.
Intended Use .......................................................3
3. AC-Input...............................................................4
4. Input Inrush Current ...........................................5
5. DC-Input...............................................................5
6. Output .................................................................6
7. Hold-up Time .......................................................8
8. DC-OK Relay Contact ..........................................9
9. Shut-down Input .................................................9
10. Remote Control of Output Voltage .................10
11. Internal Data Logging .......................................10
12. Efciency and Power Losses ..............................11
13. Lifetime Expectancy and MTBF.........................12
14. Functional Diagram ...........................................12
15. Terminals and Wiring ........................................13
16. Front Side and User Elements ...........................14
17. EMC ....................................................................15
18. Environment ......................................................16
19. Protection Features ...........................................17
20. Safety Features ..................................................17
21. Dielectric Strength ............................................18
22. Certications
.....................................................18
23. Physical Dimensions and Weight .................... 19
24. Accessories ....................................................... 20
24.1.
1606-XLC - Wall mounting bracket ......... 20
24.2.
1606-XLSBUFFER24 module ....................
20
25. Application Notes............................................ 21
25.1. Repetitive Pulse Loading .......................... 21
25.2. Peak Current Capability ...........................22
25.3. External Input Protection.........................22
25.4. Charging Batteries ...............................23
25.5. Output Circuit Breakers............................23
25.6. Parallel Use to Increase Output Power.... 24
25.7. Parallel Use for Redundancy ....................24
25.8. Series Operation .......................................25
25.9. Inductive and Capacitive Loads................25
25.10. Back-feeding Loads ..................................25
25.11. Operation on Two Phases ........................26
25.12. Use in a Tightly Sealed Enclosure ............26
25.13. Mounting Orientations ............................27
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLS960EE
Index
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230VA—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
• 230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
• 50Hz vs. 60Hz—As long as not otherwise stated, AC100V and AC230V parameters are valid at 50Hz and AC120V parameters are valid at 60HZ
mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
•shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 200-240V Input Width only 125mm, Weight only 1.8kg
94.6% Full Load and Excellent Partial Load Efciencies 50% BonusPower
, 1440W for up to 4s
110A High Peak Current for 25ms for E
asy Fuse Tripping
Safe Hiccup
PLUS
Overload Mode Active PFC (Power Factor Correction) Negligible Low Input Inrush Current Surge Full Power Between -25°C and +60°C Current Sharing Feature for Parallel Use Internal Data Logging for Troubleshooting Included. DC-OK Relay Contact Shut-down Input 3 Year Warranty
Description
The most outstanding features of the XLS family of power supplies are their extremely reliable efciency and small footprint, which are achieved by a synchonous rectication and other technological designs.
The 1606-XLS960EE is a device for 200-240V mains voltages. Large power reserves of 150% support the starting of heavy loads such as DC motors or capacitive loads. In many cases this allows you to use a unit from a lower wattage class which saves space and money.
High immunity to transients and power surges as well as low electromagnetic emission enable you to use this power supply in nearly every environment.
The integrated output power manager and input fuses as well as the near zero input inrush current make installation and usage simple. Diagnostics are easy with the DC-OK relay, a green DC-OK LED and a red overload LED.
A large international approval package for a variety of applications makes this unit suitable for nearly every application.
Specication Quick Reference
Output voltage DC 24V nominal Adjustment range 24 - 28V Output current 40 – 34.3A continuous 60 – 51.5A short term (4s) Output power 960W continuous 1440W short term (4s) Output ripple < 100mVpp 20Hz to 20MHz Input voltage AC 200-240V -15%/+10% Mains frequency 50-60Hz ±6% AC Input current 4.6A at 230Vac Power factor 0.96 at 230Vac AC Inrush current typ. 14A peak at 230Vac Efciency 94.6% at 230Vac Losses 54.8W at 230Vac Temperature range -25°C to +70°C operational Derating 24W/°C +60 to +70°C Hold-up time typ. 30ms at 230Vac Dimensions 125x124x127mm WxHxD Weight 1800g / 3.97lb
Catalog Numbers
Power Supply 1606-XLS960EE 24-8V Standard unit
Accessories 1606-XLC Wall mount bracket 1606-XLSBUFFER24 Buffer unit
Certication Marks
IND. CONT. E
Q.
UL 508
UL 60950-1
EMC, LVD
Marine
Gost R
C-Tick
2 Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to Mounting.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid
(e.g. cable conduits) by more than 15%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input nom. AC 200-240V suitable for TN, TT and IT mains networks AC input range min. 170-264Vac continuous operation min. 110-170Vac full power for up to 200ms min. 0-170Vac no damage to the unit 264-300Vac < 500ms Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 164Vac steady-state value, load independent, see Fig. 3-1 Shut-down voltage typ. 151Vac steady-state value, load independent, see Fig. 3-1 Input current typ. 4.6A at 24V, 40A, see Fig. 3-3 Power factor*) typ. 0.96 at 24V, 40A, see Fig. 3-4 Crest factor
**)
typ. 1.65 at 24V, 40A Start-up delay typ. 750ms see Fig. 3-2 Rise time typ. 23ms at 24V, 40A, resistive load, 0mF see Fig. 3-2 typ. 25ms at 24V, 40A, resistive load, 40mF see Fig. 3-2 Turn-on overshoot max. 200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
170V
Rated input range
V
IN
P
OUT
151V 264Vac
Shut-down
164V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output Voltage
Input Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load at 24V
40A
4 8 12 16 20 24 28 32 36
0
1
2
3
4
5
6A
Input Current, typ.
Output Current
Power Factor, typ.
4 8 12 16 20 24 28 32 36 40
A
0.75
0.80
0.85
0.90
0.95
1.00
Output Current
4 Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
4. Input Inrush Current
The power supply is equipped with an active inrush current limitation circuit, which limits the input inrush current after turn-on to a negligible low value. The input current is usually smaller than the steady state input current.
Inrush current
*)
max. 18A
peak
over entire temperature range
typ. 14A
peak
over entire temperature range
Inrush energy max. 4A
2
s over entire temperature range
Inrush delay typ. 750ms
*) The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
Fig. 4-1 Typical turn-on behaviour at nominal
load and 25°C ambient temperature
Output
50mS/DIV
Input 230Vac
24Vdc
Input Current 5A / DIV
5. DC Input
Do not operate this power supply with DC input voltage. Check the 1606-XLE480EP-D unit instead. Two 1606-XLE480EP-D units in parallel might be necessary.
All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014 5
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 24V Adjustment range min. 24-28V guaranteed max. 30V
****)
at clockwise end position of potentiometer Factory setting typ. 24.1V ±0.2%, at full load, cold unit, in “single use” mode typ. 24.1V ±0.2%, at full load, cold unit, in “parallel use” mode typ. 25.1V at no load, cold unit, in “parallel use” mode Line regulation max. 10mV 170-264Vac Load regulation max. 50mV in “single use” mode: static value, 0A 40A, see Fig. 6-1
typ. 1000mV in “parallel use” mode: static value, 0A
40A,
see Fig. 6-2 Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm Output current nom. 40A continuously available at 24V, see Fig. 6-1 and Fig. 6-2 nom. 34.3A continuously available at 28V, see Fig. 6-1 and Fig. 6-2 nom. 60A short term available BonusPower*), at 24V
for typical 4s, see Fig. 6-1 and Fig. 6-2 nom. 51.5A short term available BonusPower
*)
, at 28V
for typical 4s, see Fig. 6-1 and Fig. 6-2 typ. 110A up to 25ms, output voltage stays above 20V, see Fig.
6-4, This peak current is available once every second.
See section 25.2 for more peak current measurements. Output power nom. 960W continuously available at 24-28V nom. 1440W*) short term available BonusPower*) at 24-28V BonusPower
time typ. 4s duration until the output voltage dips, see Fig. 6-5 BonusPower recovery time typ. 7s overload free time to reset power manager, see Fig. 6-6 Overload behavior cont. current output voltage > 20Vdc, see Fig. 6-1 Hiccup
PLUS
mode
**)
output voltage < 20Vdc, see Fig. 6-1
Short-circuit current min. 60A
***)
load impedance 25mOhm, see Fig. 6-3
max. 70A
***)
load impedance 25mOhm, see Fig. 6-3
max. 23A average (R.M.S.) current, load impedance 25mOhm, see
Fig. 6-3 min. 110A up to 25ms, load impedance <10mOhm, see Fig. 6-4 typ. 125A up to 25ms, load impedance <10mOhm, see Fig. 6-4 Output capacitance typ. 10 200μF included in the power supply
*) BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short­term duration is hardware controlled by an output power manager. BonusPower is repeatedly available. Detailed information can be found in section 25.1. If the power supply is loaded longer with the BonusPower than shown in the Bonus-time diagram (see Fig. 6-5), the max. output power is automatically reduced to 960W. If the power requirement is continuously above 960W and the voltage falls below approx. 20V (due to the current regulating mode at overload), the unit shuts-off and makes periodical restart attempts. This behavior is called hiccup mode which is described below. If the voltage is above 20V, the unit continuously delivers current.
**) Hiccup
PLUS
Mode Up to 4s of overloading, the power supply delivers continuous output current. After this, the output power is reduced to nearly zero for approx. 17s before a new start attempt is automatically performed. If the overload has been cleared, the device will operate normally. If the overload still exists, the output current will be delivered for 2 to 4s (depending on the overload) again followed by a 17s rest time. This cycle is repeated as long as the overload exists. See Fig. 6-3. During the off-period a small rest voltage and rest current is present on the output.
***) Discharge current of output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 28.5V.
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6 Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Fig. 6-1 Output voltage vs. output current in
“single use” mode, typ.
Fig. 6-2 Output voltage vs. output current in
“parallel use” mode, typ.
Output Voltage
0
010203040
4
8
12
28V
16
20
24
6050 70A
Output Current
Adjustment Range
Hiccup
mode
A
B
A
B
Short-term (4s) then switching to curve
Continuously available
A
Output Voltage
(Parallel Use, typ.)
22V
02040
23V
24V
25V
29V
26V
27V
28V
60A503010
Adjustment
Range
Factory
setting
Output Current
Continuously
allowed
Bonus
Power
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, typ. Fig. 6-4 Dynamic overcurrent capability, typ.
Output Current
0
65A
17s
17s
17s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
Output Voltage
(dynamic behavior, < 25ms)
0
0
4
8
12
28V
16
20
24
150
A
6030 90 12015 45 75 105 135
Adjustment
Range
Output Current
Fig. 6-5 Bonus time vs. output power Fig. 6-6 BonusPower recovery time
ma
x
.
Bonus Time
0
100 120 130 140 150
170%
1
2
3
4
5s
110 160
Output Power
m
i
n
.
Power Demand
100%
t
t
Limitation by Power Manager
Output Voltage
Bonus Power disabled
Bonus
Time
Recovery Time
BonusPower is available as soon as power comes on and after the end of an output short circuit or output overload.
Fig. 6-7 BonusPower after input turn-on Fig. 6-8 BonusPower after output short
100%
Output Voltage
Input Voltage
Bonus Power
Output Power
150%
Short of
Output
100%
Output Voltage
Bonus Power
Output Power
150%
All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014 7
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 230V Hold-up Time typ. 58ms at 24V, 20A, see Fig. 7-1 min. 47ms at 24V, 20A, see Fig. 7-1 typ. 30ms at 24V, 40A, see Fig. 7-1 min. 24ms at 24V, 40A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
0
10
20
30
40
60ms
170 190 210 230 250Vac
Input Voltage
Hold-up Time
24V, 20A, typ.
2
4
V
,
4
0
A
,
t
y
p
.
24V, 20A, min.
50
2
4
V
,
4
0
A
,
m
i
n
.
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
8 Rockwell Automation Publication 1606-RM029A-EN-P — April 2014
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
8. DC-OK Relay Contact
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches 90% of the adjusted output voltage. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 21.
Fig. 8-1 DC-ok relay contact behavior
V
= V
OUT
ADJ
10%
<
1ms
>
1ms
250ms
0.9* V
ADJ
open
openclosed closed
9. Shut-Down Input
This feature allows a switch-off of the output of the power supply with a signal switch or an external voltage. The shut-down function ramps down and has no safety feature included. The shut-down occurs immediately while the turn-on is delayed up to 350ms. In a shut-down condition, the output voltage is <2V and the output power is <0.5W.
The voltage between different minus pole output terminals must be below 1V when units are connected in parallel. In a series operation of multiple power supplies only wiring option “A” with individual signal switches is allowed.
Please note that option C requires a current sink capability of the voltage source. Do not use a blocking diode.
Fig. 9-1 Activation of the shut-down input
Option A:
Shut-
15
down Input
OFF: linked ON : open
16
Option B:
(via open collector)
OFF: I > 0.3mA ON : I < 0.1mA
n.c.
I
15
16
-
Shut­down Input
Option C:
(via external voltage
OFF: U < 1V ON : U = 4 -29V
n.c.
+
U
16
-
down Input
Shut-
15
All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014 9
Loading...
+ 19 hidden pages