26.3. Using the Inhibit Input ..................... 24
26.4. Troubleshooting
................................. 24
.............. 19
....................... 23
Terminology and Abbreviations
•DC UPS—Uninterruptible power supply with DC input.
•Normal mode—Describes a condition where the battery is charged, the input voltage is in range and the output is loaded within the
allowed limits..
• Buffer mode—Describes a condition where the input voltage is below the transfer threshold level, the unit is running on battery (buffering)
and the output is loaded within the allowed limits.
• Charging mode—Describes a condition where the battery is being charged, the input voltage is in range and the output is loaded within the
allowed limits.
• Inhibit mode—Describes a condition where buffering is disabled intentionally by using the inhibit input of the DC UPS (e.g. for service
actions or to save battery capacity).
•Buffer time—Equivalent to the term “hold-up time.”
• T.b.d.—To be defined, value or description will follow later.
...... 22
Bulletin 1606 Switched Mode Power Supplies
1.
Description
The 1606-XLS240-UPSD uninterruptible power
supply (UPS) controller along with a standard 24V
power supply and one 12V battery can bridge power
failures or voltage uctuations. This unit can supply
and bridge both a 24V load as well as a 12V load at
the same time. The 12V is generated by a DC/DC
converter from the 24V output. Therefore, systems that
use 24V control circuits and require 12V for e.g.
remote radio telemetry can be supplied with
only one 1606-XLS240-UPSD DC-UPS controller.
The DC-UPS includes a professional battery
management system which charges and monitors
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.
AC
24V
Power
Supply
DC-UPS
Dual
output
1606XLS240UPSD
12V Battery
24VDC
e.g.: PLC
12VDC
24V
Load
12V
Load
e.g.: radio
transmitter
DC-UPS, Dual Output
■ 24V DC-UPS With an Additional 12V Output for
Various Applications
■ Only One 12V Battery Required
■ Stable Output Voltage in Buer Mode
■ Superior Battery Management for Longest Battery Life
■ Comprehensive Diagnostic and Monitoring Functions
■ Replace Battery Signal Included
■ Electronically Overload and Short Circuit Protected
■ 50% Power Reserves
■ 3 Year Warranty
2.
Specication Quick Reference
Input voltage 24Vdc Nominal
22.5-30Vdc Input range
Output voltage
(normal mode)
12V 12V output
Output voltage
(buer mode)
Output current
(normal mode)
Output current
(buer mode)
Total output
power
0.23V lower as
input voltage
22.25V
12V
0 - 15A
0 - 5A
0 - 10A
10 – 15A for 5s
0 - 5A
360W
240W
Typ., 24V output
24V output at 10A
12V output at 5A
24V output
12V output
24V output
24V output
12V output
Normal mode
Buer mode
Allowed batteries 3.9Ah to 40Ah VRLA lead acid
Temperature range -25 to +70°C Operational
Derating 6W/°C +50 to +70°C
Dimensions 49x124x117mm WxHxD
Buer time
typ. 6’30” 7Ah battery module
24V 7A, 12V 5A
typ. 54’ 26Ah module
24V 7A, 12V 5A
3.
Catalog Numbers
DC-UPS 1606-XLS240-UPSD24V and 12V output
Accessories
2Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
1606-XLSBATASSY1
1606-XLSBATBR1
1606-XLSBATASSY2
1606-XLSBARBR2
1606-XLB
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Battery module 12V 7Ah
Mounting kit w/o battery
Battery module 12V 26Ah
Mounting kit w/o battery
Panel/Wall mount bracket
It is assumed that the input power source can deliver a sufficient output current.
4.
Certication Marks
IND. CONT. EQ.
UL 508
Marine RINA
UL 60950-1
GOST R
EMC, LVD
C-TICK
Bulletin 1606 Switched Mode Power Supplies
Intended Use
• This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
• Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or
threaten human life.
• This device is designed for use in hazardous (pending), non-hazardous, ordinary or unclassified locations.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM017A-EN-P — February 20143
Bulletin 1606 Switched Mode Power Supplies
5. Input
Input voltage
nom. DC 24V
Input voltage ranges
nom. 22.5 to 30Vdc Continuous operation, see Fig. 5-1
30 to 35Vdc Temporarily allowed, no damage to the DC-UPS *)
35Vdc Absolute maximum input voltage with no damage to the
DC-UPS
0 to 22.5Vdc The DC-UPS switches into buer mode and delivers
output voltage from the battery if the input was above
the turn-on level before and all other buer conditions
are fullled.
Allowed input voltage ripple
max. 1.5Vpp Bandwidth <400Hz
1Vpp Bandwidth 400Hz to 1kHz
Allowed voltage between input
and earth (ground)
max. 60Vdc or
42.4Vac
Turn-on voltage
typ. 22.8Vdc The output does not switch on if the input voltage does
not exceed this level.
max. 23Vdc
Input current **)
typ. 140mA Internal current consumption for the DC-UPS
typ.
1.1A Current consumption for battery charging in constant current
mode at 24V input (see Fig 8-2). ***)
External capacitors on the input
No limitation
*) The DC-UPS shows “Check Wiring” with the red LED and buering is not possible.
**) The total input current is the sum of the output current,
the current which is required to charge the battery during the
charging process and the current which is need ed to supply the DC-UPS itself. See also
Fig. 5-2 . This calculation does not apply
in overload situations where the DC-UPS limits the output current, therefore see Fig. 5-3.
***) Please note: This is the input current and not the current which ows into the battery during charging. The battery current can
be found in section 8.
Fig. 5-1 Input voltage rangeFig. 5-2 Input current, denitions
A: Rated input voltage range
B: Temp. allowed, no harm to the unit
C: Absolute max. input voltage
D: Buffer mode
V
IN
183035V22.50
AB
C
D
V
OUT
Internal
current
consumption
Current
consumption
for battery
charging
Output
Current
Input
Current
Fig. 5-3 Input current and output voltage vs.
output current, typ. (battery fully charged)
Electric output current limitation
The DC-UPS is equipped with an electronic output
current limitation. This current limitation works
in a switching mode which reduces the power
losses and heat generation to a minimum. As a
result, the output voltage drops since there is not
enough current to support the load. A positive
eect of the current limitation in switching mode
is that the input current goes down despite an
increase in the output current resulting in less
stress for the supplying source. Fig 5-3 shows the
behavior when the 12V is not loaded. Power which
is taken out from the 12V reduces the power on
the 24V side.
0
0
5
10
15
20A
O
u
t
p
u
t
C
u
r
r
e
n
t
4812
20A
Output Voltage
15
20V
Overload
I
n
p
u
t
C
u
r
r
e
n
t
10
4Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
6. Output in Normal Mode
The total output power of 360W can be shifted dynamically between the two outputs.
24V Output:
nom. DC 24V The output voltage follows the input voltage reduced by the
input to output voltage drop.
Output voltage
Voltage drop between input and
output
max.
max.
0.3V
0.45V
At 10A output current, see Fig. 6-1 for typical values
At 15A output current, see Fig. 6-1
for typical values
Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm *)
Output current nom. 0 – 15A Continuously allowed, lower if the 12V output is loaded.
min. 12.3A Output if 12V
output is loaded with 5A.
Short-circuit current min. 17.9A Load impedance 100mOhm, see Fig. 6-2 for typical values. The
12V output is o during an overload or short on the 24V.
max. 21A
Capacitive and inductive loads
No limitation
12V Output:
nom. DC 12V
Output voltage
Output voltage tolerance
±2%
Ripple and noise voltage typ. 30mVpp 20Hz to 20MHz, 50Ohm *)
nom. 0 - 5A Continuously allowed, may be lower if the 24V output is loaded
more than 12.3A
Output current
Short-circuit current min.
4A
Load impedance 100mOhm, see Fig. 7-5. for typical values.
The 24V output is on during an overload or short on the 12V.
max. 5.5A
Capacitive and inductive loads
No limitation
*) This gure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage may be
higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-2 Output voltage vs, output current in
normal mode at 24V input, typ.
Fig. 6-1 Input to output voltage drop, typ.
Input to Output
Voltage drop
0
0210
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
O
u
t
p
u
t
C
u
r
r
e
n
t
468 121416
Output Voltage
0
05101520
4
8
12
28V
16
20
24
25A
Output Current
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM017A-EN-P — February 20145
Bulletin 1606 Switched Mode Power Supplies
7. Output in Buer Mode
If the input voltage falls below the transfer threshold level, the DC-UPS starts buering without any interruption or
voltage dips. The transfer threshold level is typically 80mV higher than the 24V output voltage in buer mode.
Buering is possible even if the battery is not fully charged.
24V Output
Output voltage
nom. DC 24V Output is stabilized and independent from battery voltage.
22.45V ±1%, at no load,
22.25V ±1%, at 10A output current
Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 0 - 10A Continuously allowed, 12V output not loaded.
10 - 15A *) 12V output not loaded.
min. 7.0A If 12V output is loaded with 5A.
Short-circuit current min. 17.9A Load impedance 100mOhm **); the 12V output is o during an
overload or short on the 24V.
max. 21A
12V Output
Output voltage
nom. DC 12V Output is stabilized and independent from battery voltage.
Output voltage tolerance
±2%
Ripple and noise voltage typ. 30mVpp 20Hz to 20MHz, 50Ohm ;
nom. 0 - 5A Continuously allowed, may be lower if the 24V output is loaded
more than 7.0A
Output current
Short-circuit current min. 4A Load impedance 100mOhm, see Fig. 7-5 for typical values.
Continuous constant; the 24V output is on during an overload
or short on the 12V as long as the battery delivers current.
max. 5.5A
*) If the output current is in the range between 10A and 15A (Bonus Power) for longer than 5s, a hardware-controlled
reduction of the maximal output current to 10A occurs. If the 10A are not sucient to maintain the 24V, buering stops at
both outputs after another 5s. Buering is possible again as soon as the input voltage recovers.
**) If the nominal output voltage cannot be maintained in buer mode, the DC-UPS switches o after 5s to save battery
capacity.
Fig. 7-1 Buering transition, denition
Fig. 7-2 Transfer behavior, typ.
Buer mode
Output
voltage
24V
28V
Input
voltage
t
t
Transfer
threshold
5
0
0
m
s
/
D
I
V
0
V
O
u
t
p
u
t
V
o
l
t
a
g
e
I
n
p
u
t
V
o
l
t
a
g
e
2
4
V
2
2
.
2
5
V
a
t
1
0
A
2
4
V
6Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Bulletin 1606 Switched Mode Power Supplies
Fig. 7-4 24V Output voltage vs. output current
in buer mode, typ.
Fig. 7-3 Available output current in buer mode
Output Voltage
A
B
C
Continuously available
Available for 5s then auto switching to curve
Buering will stop after 5s
D
0
0
5101520
5
10
15
25V
20
25
Output
Current
AB
CD
D
Buering will stop after 5s
Output
Current
0
05 Sec.
15A
10A
Time
5A
BonusPower
Fig. 7-5 12V Output voltage vs. output current
in normal or buer mode, typ.
Output Voltage
Output Current
01 2 3
0
2
4
6
14V
8
10
12
45 6 A
A
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM017A-EN-P — February 20147
Bulletin 1606 Switched Mode Power Supplies
8.Battery Input
The DC-UPS requires one 12V VRLA battery to buer the 24V and 12V output.
Battery voltage nom. DC 12V Use one maintenance-free 12V VRLA lead acid battery or
one battery module which is listed in the Accessories
section.
9.0 – 15.0V Continuously allowed, except deep discharge protection
Battery voltage range
max. 35Vdc Absolute maximum voltage with no damage to the unit
typ. 7.4V Above this voltage level battery charging is possible.
Allowed battery sizes min. 3.9Ah
max. 40Ah
Internal battery resistance max. 100mOhm See individual battery datasheets for this value
Battery charging method
CC-CV Constant current, constant voltage mode
Battery charging current (CC-mode) nom. 1.5A Independent from battery size,
max. 1.7A Corresponding 24V input current see Fig. 8-2
End-of-charge-voltage (CV-mode)
13.4-13.9V Adjustable, see section 14
Battery charging time typ. 5h *) For a 7Ah battery
typ. 17h *) For a 26Ah battery
typ. 21A Buer mode, 240W output, 11.5V on the battery
terminal of the DC-UPS, see
Battery discharging current **)
Fig. 8-1 for other parameters
typ. 0.3A Buer mode, 0A output current
max. 50μ
A
At no input, buering had switched o, all LEDs are o
typ. 310mA At no input, buering had switched o, yellow LED
shows “buer time expired” (max. 15 minutes)
Deep discharge protection ***) typ. 10.5V At 0% output load
typ. 9.0V At 100% output load
*) The charging time depends on the duration and load current of the last buer event. The numbers in the table represent a
fully discharged battery. A typical gure for a buer current of 10A at 24V output is 3h 20Min. for a 7Ah battery.
**) The current between the battery and the DC-UPS is more than twice the 24V output current. This is caused by boosting the 12V
battery voltage to a 24V level.
This high current requires large wire gauges and short cable length for the longest possible
buer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the
battery terminals which increases the discharging current. See also section 24 for additional installation instructions.
***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops
buering when the voltage on the battery terminals of the DC-UPS fall below a certain value.
Fig. 8-1 Battery discharging current
vs. 24V output current, typ.
(12V not loaded)
Fig. 8-2 Required input current vs. input
voltage for battery charging
(12V not loaded)
Battery Current
0
0
10
20
5
15
25
30A
2.57.5105.21A515
Output Current
Voltage on
battery terminal
of the DC-UPS:
A:
10.5V
B:
11V
C:
12V
A B C
Input Current
0
23
0.5
1.0
0.25
0.75
1.25
1.5A
Input Voltage
24252628V
m
a
x
.
(
b
a
t
t
e
r
y
c
ha
r
g
i
n
g
c
u
r
r
e
n
t
1
.
7
A
)
27
t
y
p
.
(
ba
t
t
e
r
y
c
h
a
r
g
i
n
g
c
ur
r
e
n
t
1
.
5
A
)
8Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Bulletin 1606 Switched Mode Power Supplies
9.Buer Time
The buer time depends on the capacity and performance of the battery as well as the load current. The diagram
below shows the typical buer times of the 24V output with the standard battery modules at 20°C.
Buer time with battery module 1606-XLSBATASSY1 min. 18’30’’ At 5A output current *)
min. 5’30’’ At 10A output current *)
typ. 20’50’’ At 5A output current, see
Fig. 9-1 **)
typ. 6’30’’ At 10A output current, see Fig. 9-1 **)
Buer time with battery module 1606-XLSBATASSY2 min. 96’30’’ At 5A output current *)
min. 37’50” At 10A output current *)
typ. 126’ At 5A output current, see Fig. 9-1 **)
typ. 53’20” At 10A output current, see Fig. 9-1 **)
*) Minimum value includes 20% aging of the battery and a cable length of 1.5m with a cross section of 2.5mm2 between the
battery and the DC-UPS and requires a fully charged (min. 24h) battery.
**) Typical value includes 10% aging of the battery and a cable length of 0.3m with a cross section of 2.5mm
2
between the battery
and the DC-UPS and requires a fully charged (min. 24h) battery.
Fig. 9-1 Buer time vs. 24V output current with the battery modules 1606-XLSBATASSY1 and 1606-XLSBATASSY2
Buer Current
515
2
4
6
8
10A
201025 30 3545 504055 60 65 70 75 80 85
Buer Time (Minutes)
1606-XLSBATASSY2 typ.
1606-XLSBATASSY1 typ.
.
12
V
7
A
h
b
a
t
t
er
y
1
2
V
2
6
A
h
b
a
t
t
e
r
y
120 150210 240
300
Min.
18027090
1606-XLSBATASSY1 typ.
1606-XLSBATASSY2 typ.
90
The buer time is reduced if the 12V output is loaded. This can be calculated according to the following
example:
Step 2: Add the computed current to the actual 24V current:
2.15A+ 5A = 7.15A
Step 3: Determine the buer time by using the standard buer time curve
(
)
Fig. 9-1
:
7.15A load with 1606-XLSBATASSY2: Approx. 12 minutes buer time.
The battery capacity is usually specied in amp-hours (Ah) for a 20h discharging event. The battery discharge is nonlinear (due to the battery chemistry). The higher the discharging current, the lower the appropriable battery capacity.
The magnitude of the reduction depends on the discharging cu rrent as well as on the type of battery. High current
battery types can have up to 50% longer buer times co mpared to regular batteries when batteries will be
discharged in less than 1 hour. High discharging currents do not necessarily mean high power losses as the
appropriable battery capacity is reduced with such currents. When the battery begins to recharge after a discharging
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM017A-EN-P — February 20149
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.