Rockwell Automation 1606-XLS240F, 1606-XLS240F-D User Manual

Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Numbers: 1606-XLS240F & 1606-XLS240F-D
Index
1.
Intended Use .......................................................3
2.
Installation Requirements ...................................3
3.
4.
Input Inrush Current ...........................................6
5.
Output .................................................................7
6.
Hold-up Time .......................................................9
7.
DC-OK Relay Contact ..........................................9
8.
Efciency and Power Losses ..............................10
9.
Reliability ...........................................................11
10.
11. Functional Diagram ...........................................12
12. Terminals and Wiring ........................................12
13. Front Side and User Elements ...........................13
14. EMC ....................................................................14
15. Environment ......................................................15
16. Protection Features ...........................................16
17. Safety Features ..................................................16
18. Dielectric Strength ............................................16
19. Certications
20. Environmental Compliance ..............................18
21. Physical Dimensions and Weight ......................18
.....................................................17
22. Accessories ........................................................ 19
22.1. 1606-XLB Wall Mounting Bracket .......19
22.2. 1606-XLSBUFFER48 Module ....................20
22.3. 1606-XLSRED Redundancy Module.............20
23. Application Notes............................................. 21
23.1. Repetitive Pulse Loading .......................... 21
23.2. Peak Current Capability ...........................22
23.3. Back-feeding Loads ..................................22
23.4. External Input Protection .........................22
23.5. Charging Batteries ...............................23
23.6. Output Circuit Breakers ............................23
23.7. Parallel Use to Increase Output Power ....24
23.8. Parallel Use for Redundancy ....................24
23.9. Daisy Chaining
23.10. Series Operation .......................................25
23.11. Inductive and Capacitive Loads................25
23.12. Operation on Two Phases ........................26
23.13. Use in a Tightly Sealed Enclosure ............26
23.14. Mounting Orientations ............................ 27
egaP egaP
of Outputs .......................25
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• 3AC 400V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery whether it is charged (13.7V) or discharged (10V).
• 230Vac—Afigure with the unit (Vac) at the end is a momentary figure without any additional tolerance included.
• 50Hz vs. 60Hz—Unless otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
• shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 100-240V Wide-range Input Width only 60mm Efciency up to 92% 150% (360W) Peak Load Capability Easy Fuse Tripping due to High Overload Current Active Power Factor Correction (PFC) Negligible low Inrush Current Surge Short-term Operation down to 60Vac and up to 300Vac Full Power Between -25°C and +60°C DC-OK Relay Contact Quick-connect Spring-clamp Terminals 3 Year Warranty
Description
The most outstanding features of this 1606-XLS series DIN rail power supply are its high efciency and small size, which are achieved by a synchronous rectication and further novel design details.
With short-term peak power capability of 150% and built-in large sized output capacitors, these features help start motors, charge capacitors and absorb reverse energy and often allow a unit of a lower wattage class to be used.
High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible.
The integrated output power manager, a wide range input voltage design and virtually no input inrush current make installation and usage simple. Diagnostics are easy due to the dry DC-ok contact, a green DC-ok LED and red overload LED.
Unique quick-connect spring-clamp terminals allow a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Specication Quick Reference
Output voltage DC 48V Adjustment range 48 – 56V Output current 5 – 4.3A continuous
7.5 6.5A for typ. 4s Output power 240W continuous 360W for typ. 4s Output ripple < 100mVpp 20Hz to 20MHz Input voltage AC 100-240V ±15% Mains frequency 50-60Hz ±6% AC Input current 2.22 / 1.22A at 120 / 230Vac Power factor 0.98 / 0.92 at 120 / 230Vac AC Inrush current typ. 4 / 7A peak at 120 / 230Vac Efciency 91.2 / 92.0% at 120 / 230Vac Losses 23.2 / 20.9W at 120 / 230Vac Temperature range -25°C to +70°C operational Derating 6W/°C +60 to +70°C Hold-up time typ. 27 / 28ms at 120 / 230Vac Dimensions 60x124x117mm WxHxD
Catalog Numbers
Power Supply
1606-XLS240F
48-56V Power supply Extended DC Input
Accessories 1606-XLB Wall mount bracket
1606-XLSRED Redundancy module 1606-XLSBUFFER48 Buffer unit
Certication Marks
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
Marine
EMC, LVD
1606-XLS240F-D
Gost R C-Tick
Marine RINA
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in non-hazardous, ordinary or unclassified locations.
Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
Should damage or malfunction occur during installation or operation, turn power immediately off and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document. Please refer to section 24.14.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. AC-Input
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks AC input range min. 85-276Vac continuous operation min. 60-85Vac full power for 200ms, no damage between 0 and 85Vac min. 276-300Vac < 500ms Allowed voltage L or N to earth max. 276Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 81Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 63Vac steady-state value, see Fig. 3-1 typ. 55Vac dynamic value
AC 100V AC 120V AC 230V Input current typ. 2.65A 2.22A 1.22A at 48V, 5A, see Fig. 3-3 Power factor *) typ. 0.99 0.98 0.92 at 48V, 5A, see Fig. 3-4 Crest factor **) typ. 1.65 1.67 1.85 at 48V, 5A Start-up delay typ. 800ms 650ms 340ms see Fig. 3-2 Rise time typ. 8ms 8ms 8ms 0mF, 48V, 5A, see Fig. 3-2 typ. 15ms 15ms 15ms 5mF, 48V, 5A, see Fig. 3-2 Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
60V 300Vac276V
Shut-down
full
power
for
200ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output Voltage
Input Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
5A
0.5 1 1.5 2 2.5 3 3.5 4 4.5
0
0.4
0.8
1.2
1.6
2.0
2.4
2.8A
Output Current
Input Current, typ.
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c
Power Factor, typ.
0.5 1 1.5 2 2.5 3 3.5 4 4.5 5A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
100Vac
120Vac
2
3
0
V
a
c
4 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
1606-XLS240F:
DC input nom. DC 110-150V -20%/+25% DC input range min. 88-187Vdc continuous operation DC input current typ. 2.37A 110Vdc, at 24V, 10A
1606-XLS240F-D:
DC input nom. DC 110-300V -20%/+25% DC input range min. 88-375Vdc continuous operation DC input current typ. 2.37/ 0.85A 110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103 Turn-on voltage typ. 80Vdc steady state value Shut-down voltage typ. 55Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or similar DC source.
For other sources, please contact Rockwell Automation. b) Connect +pole to L and –pole to N. c) Connect the PE terminal to a earth wire or to the machine
ground.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
5. Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 10A
peak
10A
peak
10A
peak
over entire temperature range
typ. 5A
peak
4A
peak
7A
peak
over entire temperature range
Inrush energy max. 4A
2
s 4A2s 4A2s over entire temperature range
Inrush delay (A) typ. 650ms 520ms 250ms see (A) in Fig. 5-1
Fig. 5-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
A
A…. Inrush delay
Input: 230Vac Output: 48V, 5A Ambient: 25°C
Upper curve: Input current 2A / DIV Middle curve: Input voltage 500V / DIV Lower curve: Output voltage 40V / DIV Time basis: 100ms / DIV
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 48V Adjustment range min. 48-56V guaranteed max. 58V Factory setting typ. 48.0V ±0.2%, at full load, cold unit Line regulation max. 10mV 60-300Vac Load regulation max. 100mV static value, 0A 5A Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm Output current nom. 5A continuously available at 48V, see Fig. 6-1 nom. 4.3A continuously available at 56V, see Fig. 6-1
nom. 7.5A
nom. 6.5A
Output power nom. 240W continuously available nom. 360W BonusPower
®
time typ. 4s duration until the output voltage dips, see Fig. 6-2 min. 3s max. 5s
®
BonusPower
recovery time typ. 7s overload free time to reset power manager, see Fig. 6-3 Overload behaviour cont. current Short-circuit current min. 3A max. 7A min. 5A max. 15A max. 7.5A Output capacitance typ. 3 000μF included inside the power supply
*) BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short­term duration is hardware controlled by an output power manager. BonusPower is available repeatedly. Detailed information can be found in chapter 23.1. If the power supply is loaded longer with the BonusPower than shown in the Bonus-time diagram (see Fig. 6-2), the max. output power is automatically reduced to 240W.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 56.8V.
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specied short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.2.
Peak current voltage dips typ. from 48V to 42V at 10A for 50ms, resistive load typ. from 48V to 42V at 20A for 2ms, resistive load typ. from 48V to 36V at 20A for 5ms, resistive load
***)
at clockwise end position of potentiometer
*)
short term available BonusPower
at 48V, for typical 4s, see Fig. 6-1
*)
short term available BonusPower
at 56V, for typical 4s, see Fig. 6-1
*)
short term available BonusPower
**)
continuous, load impedance 200mOhm, see Fig. 6-1
**)
continuous, load impedance 200mOhm, see Fig. 6-1
**)
during BonusPower
**)
during BonusPower
**)
continuous, load impedance <10mOhm, see Fig. 6-1
*)
, load impedance 200mOhm
*)
, load impedance 200mOhm
*)
,
*)
,
*)
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 7
Bulletin 1606 Switched Mode Power Supplies
Fig. 6-1 Output voltage vs. output current,
Output Voltage
60V
50
40
30
20
10
56V
48V
typ.
c o
n t
i
n u o u s
Adjustment
Range
0
02 6810
4
s
h
o
r
t
-
t
e
r
m
Output Current
12A
Fig. 6-2 Bonus time vs. output power
Bonus Time
10s
9 8 7 6 5 4 3 2 1 0
110 120 130 140 150
Fig. 6-3 BonusPower recovery time
Limitation by
Power Demand
100%
Output Voltage
Bonus
Time
Power Manager
Recovery Time
Bonus Power disabled
t
t
m
a
x
m
i
n
Output Power
typ
160%
The BonusPower
is available as soon as power comes on and immediately after the end of an output short circuit or
output overload.
Fig. 6-4 BonusPower after input turn-on Fig. 6-5 BonusPower after output short
Input Voltage
Short of
Output
Output Voltage
Output Voltage
Output Power
100%
150%
Bonus Power
Output Power
150%
100%
Bonus Power
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
8 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 100V AC 120V AC 230V Hold-up Time typ. 51ms 53ms 55ms at 48V, 2.5A, see Fig. 7-1 typ. 26ms 27ms 28ms at 48V, 5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
0
10
20
30
40
50ms
85 120 155 190 230Vac
Input Voltage
4
8
V
,
2
.
5
A
,
m
i
n
.
4
8
V
,
2
.
5
A
,
t
yp
.
4
8
V
,
5
A
,
m
i
n
.
4
8
V
,
5
A
,
ty
p
.
Hold-up Time
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
8. DC-OK Relay Contact
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
250ms
0.9* V
ADJ
<
1ms
10%
V
OUT
= V
ADJ
>
1ms
open openclosed closed
Note: The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according
to specication. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly if the load is a battery, if the power supply is used in parallel or if the power supply is used for N+1 redundant systems.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 9
Bulletin 1606 Switched Mode Power Supplies
9. Efciency and Power Losses
AC 100V AC 120V AC 230V Efciency typ. 90.4% 91.2% 92.0% at 48V, 5A Average efciency *) typ. 89.6% 90.0% 90.3% 25% at 1.25A, 25% at 2.5A,
25% at 3.75A, 25% at 5A Power losses typ. 5.6W 5.7W 5.9W at 48V, 0A typ. 25.5W 23.2W 20.9W at 48V, 5A
*) The average efciency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time.
Fig. 9-1 Efciency vs. output current at 48V,
typ.
Fig. 9-2 Losses vs. output current at 48V, typ.
Efciency
1
86
87
88
89
90
91
92
85
93%
120Vac
100Vac
230Vac
5A234
Output Current
1.5 2.5 3.5 4.5
Power Losses
012345A
3
6
12
15
18
21
27W
120Vac
100Vac
230Vac
Output Current
9
24
Fig. 9-3 Efciency vs. input voltage at 48V,
5A, typ.
Fig. 9-4 Losses vs. input voltage at 48V, 5A,
typ.
Efciency
85 120
155
190 225 260Vac
88
89
90
91
Input Voltage
92
93
94%
Power Losses
8
12
16
20
24
Input Voltage
28
32W
85 120
155
190 225 260Vac
10 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
10. Reliability
AC 100V AC 120V AC 230V Lifetime expectancy
*) 57 000h 67 000h 81 000h at 48V, 5A and 40°C
118 000h 112 000h 118 000h at 48V, 2.5A and 40°C 161 000h*) 188 000h*) 228 000h*) at 48V, 5A and 25°C MTBF
**) SN 29500, IEC 61709 539 000h 566 000h 606 000h at 48V, 5A and 40°C
932 000h 979 000h 1 048 000h at 48V, 5A and 25°C MTBF
**) MIL HDBK 217F 342 000h 349 000h 349 000h at 48V, 5A and 40°C; Ground
Benign GB40
467 000h 478 000h 478 000h at 48V, 5A and 25°C; Ground
Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours and is calculated according to the capacitor’s manufacturer specication. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF gure is a statistical representation of the likelihood of a device to fail. A MTBF gure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the eld. However, it is impossible to determine if the failed unit has been running for 50 000h or only for 100h.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 11
Bulletin 1606 Switched Mode Power Supplies
11. Functional Diagram
Fig. 11-1 Functional diagram
+
+
-
-
DC-ok contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok Relay
Output Voltage Monitor
Output
Power
Manager
Temper-
ature Shut-
down
Overload LED
DC-ok LED
Input Fuse Input Filter Input Rectier Active Transient Filter & Inrush Current Limiter
V
OUT
L
N
12. Terminals and Wiring
Bi-stable, quick-connect spring clamp terminals. IP20 Finger safe construction. Suitable for eld- and factory installation. Shipped in open position.
Input Output DC-OK-Signal
Type
spring-clamp terminals spring-clamp terminals spring-clamp terminals Solid wire 0.5-6mm2 0.5-6mm2 0.5-6mm2 Stranded wire 0.5-4mm2 0.5-4mm2 0.5-4mm2 American Wire Gauge 20-10 AWG 20-10 AWG 20-10 AWG Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 10mm / 0.4inch Screwdriver not applicable not applicable not applicable Recommended tightening torque not applicable not applicable not applicable Pull-out force 10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E)
Fig. 12-1 Connecting a wire
Instructions:
a) Use appropriate copper cables that are designed for minimum
operating temperatures of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum. b) Follow national installation codes and installation regulations! c) Ensure that all strands of a stranded wire enter the terminal
connection! d) Up to two stranded wires with the same cross section are
permitted in one connection point (except PE wire). e) Do not use the unit without PE connection. f) Unused terminal compartments should be securely tightened. g) Ferrules are allowed.
1.
Insert the wire
2.
Close the lever
To disconnect wire: reverse the above procedure.
12 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
13. Front Side and User Elements
Fig. 13-1 Front side
A
Input Terminals (Quick-connect spring-clamp terminals)
N, L Line input
PE (Protective Earth) input
B
Output Terminals (Quick-connect spring-clamp terminals, two pins per
pole) + Positive output – Negative (return) output
C
DC-OK Relay Contact (Quick-connect spring-clamp terminals)
The DC-OK relay contact is synchronized with the DC-OK LED. See section 8 for details.
D
Output voltage potentiometer
Multi turn potentiometer; Open the ap to adjust the output voltage. Factory set: 48.0V
E
DC-OK LED (green)
On, when the output voltage is >90% of the adjusted output voltage
F
Overload LED (red)
On, when the voltage on the output terminals is <90% of the adjusted output voltage, or in case of a short circuit in the output. Input voltage is required Flashing, when the unit has switched off due to over-temperature.
Indicators, LEDs
Overload LED DC-OK LED DC-OK Contact
Normal mode OFF ON Closed During BonusPower OFF ON Closed Overload (VOUT < 90%) ON OFF Open Output short circuit ON OFF Open Temperature Shut-down Intermitted OFF Open No input power OFF OFF Open
A
B
C
D
E
F
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 13
Bulletin 1606 Switched Mode Power Supplies
14. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions.
The CE Mark indicates conformance with the EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC and the RoHS directive 2011/65/EC. A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 contact discharge
air discharge
8kV 15kV
Criterion A
Criterion A Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 input lines
output lines DC-OK signal (coupling clamp)
4kV 2kV 1kV
Criterion A
Criterion A
Criterion A Surge voltage on input EN 61000-4-5
L
N
L PE, N PE
2kV 4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + -
+ / -
PE
1kV 1kV
Criterion A
Criterion A Surge voltage on DC-OK EN 61000-4-5 DC-OK signal PE 1kV Criterion A Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac 70% of 100Vac 0% of 200Vac 40% of 200Vac 70% of 200Vac
0Vac, 20ms 40Vac, 200ms 70Vac, 500ms 0Vac, 20ms 80Vac, 200ms 140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C Voltage sags SEMI F47 0706 dips on the input voltage according to SEMI F47 standard 80% of 120Vac (96Vac)
70% of 120Vac (84Vac) 50% of 120Vac (60Vac)
1000ms 500ms 200ms
Criterion A
Criterion A
Criterion A Powerful transients VDE 0160 over entire load range 750V, 1.3ms Criterion A
Criteria: A: Power supply shows normal operation behavior within the dened limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. The power supplu will incur no damage
or hazard.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Conducted emission output lines **)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 limits for DC power port
according EN 61000-6-3 fullled Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 fullled for class A equipment Voltage uctuations, icker EN 61000-3-3 fullled *) This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
*) tested with constant current loads, non pulsing. **) for information only, not mandatory for EN 61000-6-3.
14 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Switching Frequencies
The power supply has three converters with three different switching frequencies
included. Two are nearly constant. The other one is input voltage and load dependent. Switching frequency 1 35kHz nearly constant Switching frequency 2 105kHz nearly constant Switching frequency 3 40kHz to 220kHz input voltage and load dependent
15. Environment
Operational temperature
*) -25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 15-1
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation Output de-rating 6W/°C 60-70°C (140°F to 158°F) Humidity
**) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions 2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II Altitude de-rating 15W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 15-2 Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient temperature and is dened as the air temperature 2cm below the unit. **) Do not energize in the presence of condensation.
Fig. 15-1 Output current vs. ambient temp. Fig. 15-2 Output current vs. altitude
Allowed Output Current at 48V
2.5
5
7.5A
c
o
n
t
i
n
u
o
u
s
0
-25 0 20 40
70°C60
Ambient Temperature
f
o
r
t
y
p
.
4
s
Allowed Output Current at 48V
0
0 2000 4000 6000m
2.5
5
7.5A
c
o
n
t
i
n
u
o
u
s
Altitude
f
o
r
t
y
p
.
4
s
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
A
B
C
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 15
Bulletin 1606 Switched Mode Power Supplies
16. Protection Features
Output protection Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ. 58Vdc
max. 60Vdc
In case of an internal power supply defect, a redundant circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart. Degree of protection IP 20 EN/IEC 60529 Penetration protection > 3.5mm e.g. screws, small parts Over-temperature protection yes Output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor) Internal input fuse T6.3A H.B.C. not user replaceable
*) In case of a protection event, audible noise may occur.
17. Safety Features
Input / output separation
*) SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 double or reinforced insulation Class of protection I PE (Protective Earth) connection required Isolation resistance > 5MOhm input to output, 500Vdc PE resistance < 0.1Ohm Touch current (leakage current) typ. 0.19mA / 0.44mA 100Vac, 50Hz, TN-,TT-mains / IT-mains typ. 0.29mA / 0.65mA 120Vac, 60Hz, TN-,TT-mains / IT-mains typ. 0.53mA / 1.04mA 230Vac, 50Hz, TN-,TT-mains / IT-mains < 0.25mA / 0.54mA 110Vac, 50Hz, TN-,TT-mains / IT-mains < 0.38mA / 0.79mA 132Vac, 60Hz, TN-,TT-mains / IT-mains < 0.74mA /1.29mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
18. Dielectric Strength
The output voltage is oating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the eld using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 18-1 Dielectric strength
A B C D
Type test 60s 2500Vac 3000Vac 500Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac 500Vac
Cut-off current setting > 10mA > 10mA > 20mA > 1mA
DA
C
B
B
N
L
Input DC-ok
Output
-
Earth, PE
+
To meet the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur.
16 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
19. Certications
EC Declaration of Conformity
Complies with CE EMC and CE Low Voltage Directives.
UL 508
IND. CONT. EQ.
LISTED E56639 for use in the U.S.A. (UL 508) and Canada (C22.2 No. 14-95) Industrial Control Equipment
UL 60950-1
RECOGNIZED for use in the U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950) Information Technology Equipment, Level 3
CSA C22.2 No. 107-1, 60950-1
CSA Certied under File Number 240020
Marine
GL (Germanischer Lloyd) classied for marine and offshore applications.
Environmental category: C, EMC2 See below for link to the Certicate.
GOST R
GOST R certication is applicable for products intended for sal and use within Russia. See below for link to Certicate.
Marine RINA
RINA (Registro Italiano Navale) certied. See below for link to the Certicate.
C-Tick
C-tick compliance is for products intended for sale and use within the Australian market. Dee below for link to the C-tick Declarations of Conformity.
Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certification.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 17
Bulletin 1606 Switched Mode Power Supplies
20. Environmental Compliance
The unit does not release any silicone and is suitable for use in paint shops. The unit conforms to the RoHS directives 2002/95/EC and 2011/65/EC. Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated. The production material within our production does not include following toxic chemicals:
Polychlorized Biphenyl (PCB), Polychlorized Terphenyl (PCT), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrom Biphenyll (PBB), Polybrom Bipheny-oxyd (PBO), Polybrominated Diphenylether (PBDE), Polychlorinated Diphenylether (PCDE), Polydibromphenyl Oxyd (PBDO), Cadmium, Asbestos, Mercury, Silicia
21. Physical Dimensions and Weigth
Weight 900g / 1.98lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN rail height must be added to the unit depth (117mm) to calculate the total required installation depth.
Installation Clearances See section 2.
Fig. 22-1 Front view Fig. 22-2 Side view
48-56V
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
18 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
22.1. 1606-XLB Wall Mounting Bracket
This bracket is used to mount the power supply onto a at surface without a DIN rail.
22. Accessories
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 19
Bulletin 1606 Switched Mode Power Supplies
22.2. 1606-XLSBUFFER48 Buffer Module
er
t.
ures.
This buffer unit is a supplementary device for DC 48V power supplies. It delivers power to bridge typical mains failures
or extends the hold-up time after turn-off of the AC power. In times when the pow supply provides sufcient voltages, the buffer unit stores energy in integrated electrolytic capacitors. In case of mains voltage fault, this energy is released again in a regulated process. One buffer module can deliver 20A additional curren
DC
Buffer
Unit(s)
Power
Supply
Load
AC
+
-
The buffer unit does not require any control wiring. It can be added in parallel to the load circuit at any given point. Buffer units can be added in parallel to increase the output ampacity or the hold-up time.
Note: The image on the left is for representational purpose only.
22.3. 1606-XLSRED Redundancy Module
L N PE
+ +
- -
1606­XLS240F
Power Supply
Adj
Overload
DCok
24V,10A
Failure
Monitor
24V,10A
Load
optional
I I
L N
PE
L N PE
+ +
- -
1606­XLS240F
Power Supply
Adj
Overload
DCok
24V,10A
XLSRED
Redundancy Module
+
-
OUT
+
-
IN 1
+
-
IN 2
The 1606-XLSRED is a dual redundancy module, which includes two
diodes as decoupling devices. It can be used for various purposes. The most popular application is to congure highly reliable and true redundant power supply systems. Another interesting application is the separation of sensitive loads from non-sensitive loads. This avoids the distortion of the power quality for the sensitive loads which can cause controller fail
1606-
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
20 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
23. Application Notes
23.1. Repetitive Pulse Loading
Typically, a load current is not constant and varies over time. This power supply is designed to support loads with a higher short-term power demand (=BonusPower). The short-term duration is hardware-controlled by an output power manager and is available on a repeated basis. If the BonusPower load lasts longer than the hardware controller allows it, the output voltage will dip and the next BonusPower is available after the BonusPower recovery time has elapsed (see section 6).
To avoid this, the following rules must be met: a) The power demand of the pulse must be below 150% of the nominal output power. b) The duration of the pulse power must be shorter than the allowed BonusPower time (see Output section). c) The average (R.M.S.) output current must be below the specied continuous output current.
If the R.M.S. current is higher, the unit will respond with a thermal shut-down after a period of time. Use the maximum duty cycle curve (Fig. 23-2) to check if the average output current is below the nominal current.
Fig. 23-1 Repetitive pulse loads, denitions Fig. 23-2 Max. duty cycle curve
DutyCycle
1.0
P
max.
150%
100%
PEAKTPEAK
P
0
T
0
0.8
0.6
0.4
0.2
P
0
0
110 120 130 140
T
T
peak -
=
peak
T
peak + T0
(D
D
utyCycle
utyCycle
x T
peak
P
Base load (W)
0
Pulse load (above 100%)
P
PEAK
Duration between pulses (s)
T
0
Pulse duration (s)
T
PEAK
D
utyCycle
T0 =
Example: A load is powered continuously with 120W (= 50% of the rated output load). From time to time a peak
power of 360W (= 150% of the rated output load) is needed for 1 second.
The question is: How often can this pulse be supplied without overloading the power supply?
- Make a vertical line at P
= 150% and a horizontal line where the vertical line crosses the P0 = 50%
PEAK
curve. Read the max. duty cycle from the duty cycle-axis (= 0.37)
- Calculate the required pause (base load) length T
- Result: The required pause length = 1.7s
- Max. repetition rate = pulse +pause length = 2.7s
:
0
T0=
T
peak -
(D
utyCycle
D
utyCycle
More examples for pulse load compatibility:
P
P
PEAK
T
0
PEAK
T0 P
P0 T
PEAK
PEAK
T0 360W 240W 1s >25s 360W 120W 0.1s >0.16s 360W 0W 1s >1.3s 360W 120W 1s >1.6s 300W 120W 1s > 0.75s 360W 120W 3s >4.9s
P
1
=
0
%
0
P
5
=
0
%
0
P
=
5
7
%
0
1
=
0
%
0
P
PEAK
150%100
)
x T
peak
)
1s - (0.37 x 1s)
==1.7s
0.37
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 21
Bulletin 1606 Switched Mode Power Supplies
23.2. Peak Current Capability
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when starting a capacitive load.
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe operation of subsequent circuit breakers.
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following two examples show typical voltage dips:
Fig. 23-3 Peak load with 2x the nominal
current for 50ms, typ.
Fig. 23-4 Peak load with 4x the nominal
current for 5ms, typ.
Peak load 10A (resistive) for 50ms Output voltage dips from 48V to 42V.
Peak load 20A (resistive) for 5ms Output voltage dips from 48V to 36V.
Please note: The DC-OK relay triggers when the voltage dips more than 10% for longer than 1ms.
23.3. Back-feeding Loads
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (E
lectro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off.
The maximum allowed feed-back-voltage is 58Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitor which is specied in section 6.
23.4. External Input Protection
The unit is tested and approved for branch circuits up to 20A. An external protection is only required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations might apply.
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6A B- or 4A C-Characteristic breaker should be used.
22 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
23.5. Charging Batteries
The power supply can be used to charge lead-acid or maintenance free batteries. (Four 12V batteries in series)
Instructions for charging batteries:
a) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge
voltage.
End-of-charge voltage 55.6V 55.0V 54.3V 53.6V
Battery temperature 10°C 20°C 30°C 40°C
b) Use a 10A circuit breaker (or blocking diode) between the power supply and the battery. c) Ensure that the output current of the power supply is below the allowed charging current of the battery. d) Use only matched batteries when putting 12V types in series. e) The return current to the power supply (battery discharge current) is typ. 4mA when the power supply is switched
off (except if using a blocking diode).
23.6. Output Circuit Breakers
Standard miniature circuit breakers (MCBs or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 48V branches.
MCBs are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 24V branches which are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to the ride-through time of PLCs. This requires power supplies with higfh current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufciently small in order for the current to actually ow. The best current reserve in the power supply does not help if Ohm’s law does not permit current ow. The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length.
Fig. 24-5 Test circuit
Maximal wire length
*)
for a fast (magnetic) tripping:
0.75mm² 1.0mm² 1.5mm² 2.5mm²
C-2A
58m 64m 104m 143m
C-3A
41m 53m 73m 124m
C-4A
18m 31m 54m 94m
C-6A
10m 14m 21m 33m
C-8A
4m 6m 8m 13m
C-10A
3m 4m 7m 10m
B-6A
19m 28m 39m 75m
B-10A
8m 12m 16m 29m
MCB
Power Supply
AC
DC
+
-
Load
+
-
B-13A
7m 9m 13m 23m
Wire length
S1... Fault simulation switch
S1
*) Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire).
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 23
Bulletin 1606 Switched Mode Power Supplies
23.7. Parallel Use to Increase Output Power
Power supplies from the same series (XLS) can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (±100mV) with the same load conditions on all units, or the units can be left with the factory settings.
If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 6A or 10A is requird on each output. Alternatively, a diode or redundancy module can also be used.
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals on bottom and output terminals on the top of the unit) or in any other condition where a derating of the output current is required (e.g. altitude, above 60°C, …).
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.
23.8. Parallel Use for Redundancy
Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. Redundant systems for a higher power demand are usually built in a N+1 method. E.g. ve power supplies, each rated for 5A are paralleled to build a 20A redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also section 23.7.
L N PE
+ +
- -
1606­XLS240F
Power Supply
Adj
Overload
DCok
48V,5A
Failure
Monitor
24V,10A
Load
optional
I I
L
N
PE
L N PE
+ +
- -
1606­XLS240F
Power Supply
Adj
Overload
DCok
48V, 5A
1606­XLSRED
Redundancy Module
+
-
OUT
+
-
IN 1
+
-
IN 2
Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defective unit becomes a load for the other power supplies and the output voltage can not be maintained any more. This can be avoided by using decoupling diodes which are included in the 1606-XLSRED redundancy module.
Recommendations for building redundant power systems: a) Use separate input fuses for each power supply.
b) Monitor the individual power supply units. Therefore, use the DC-OK relay contact of the 16060-XLS power supply. c) It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting.
24 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
23.9. Daisy Chaining of Outputs
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as shown in Fig. 23-7.
Fig. 23-6 Daisy chaining of outputs Fig. 23-7 Using distribution terminals
Power
+ +
- -
Supply
Input
Output
Load
+
-
max 25A!
Power
+ +
- -
Supply
Input
Output
Load
+
-
Distribution Terminals
Power
+ +
- -
Supply
Input
Output
Power
+ +
- -
Supply
Input
Output
23.10. Series Operation
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth (see notes)
Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc are no longer SELV and can be dangerous. Such voltages must be installed with a protection against touching.
Earthing of the output is required when the sum of the output voltage is above 60Vdc.
Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals.
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation (input terminals on bottom and output terminals on the top of the unit).
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.
23.11. Inductive and Capacitive Loads
The unit is designed to supply any kind of load, including unlimited inductive of capacitive loads.
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 25
Bulletin 1606 Switched Mode Power Supplies
23.12. Operation on Two Phases
240V
+15%
max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
The power supply can also be used on two phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+15%. Use a fuse or a circuit breaker to protect the N input. The N input is internally not protected and is in this case connected to a hot wire. Appropriate fuses or circuit breakers are specied in section 23.4, “External Input Protection”.
23.13. Use in a Tightly Sealed Enclosure
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature denes the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box Enclosure: Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm
Load: 24V, 8A; (=80%) load is placed outside the box Input: 230Vac Temperature inside enclosure: 47°C (in the middle of the right side of the power supply with a distance of 2cm) Temperature outside enclosure: 27°C Temperature rise: 20K
26 Rockwell Automation Publication 1606-RM045A-EN-P — March 2014
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
23.14. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction inuences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current. Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 23-8 Mounting Orientation A
(Standard orientation)
Power Supply
OUTPUT
Output Current
0
10 20 30 40
60°C
2.5
5
7.5
10A
INPUT
50
A
1
Ambient Temperature
Fig. 23-9 Mounting Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2.5
5
7.5
10A
50
A
2
Ambient Temperature
A
1
Fig. 23-10 Mounting Orientation C
(Table-top mounting)
Output Current
0
10 20 30 40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A
1
A
2
Fig. 23-11 Mounting Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A
1
A
2
Fig. 23-12 Mounting Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A
1
A
2
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM045A-EN-P — March 2014 27
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://
www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums,
software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer Tech Co nn ec t representative, or visit http://www.rockwellautomation.com/support/
SM
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wo rldw ide Locat or at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Publication 1606-RM045A-EN-P — March 2014
, available at http://
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...