Rockwell Automation 1606-XLS240E, 1606-XLS240EA, 1606-XLS240EC, 1606-XLS240E-D User Manual

Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Numbers: 1606-XLS240E, 1606-XLS240EA, 1606-XLS240EC & 1606-XLS240E-D
Index
egaP
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC-Input...............................................................4
4. DC-Input...............................................................5
5. Input Inrush Current ...........................................6
6. Output .................................................................7
7. Hold-up Time.......................................................9
8. DC-OK Relay Contact ..........................................9
9. Efciency and Power Losses..............................10
10. Reliability...........................................................11
11. Functional Diagram...........................................12
12. Terminals and Wiring........................................12
13. Front Side and User Elements...........................13
14. EMC....................................................................14
15. Environment ......................................................15
16. Protection Features ...........................................16
17. Safety Features..................................................16
18. Dielectric Strength ............................................16
19. Certications......................................................17
20. Environmental Compliance...............................18
2 Physical Dimensions and Weight......................18
21.
22. Accessories
22.1.
1606-XLB Wall Mounting Bracket ............19
22.2. 1606-XLSBUFFER24 Module ....................20
22.3. 1606-XLSRED Redundancy Module .......... 20
23. Application Notes............................................. 21
23.1. Repetitive Pulse Loading ..........................21
23.2. Peak Current Capability ...........................22
23.3. Back-feeding Loads ..................................22
23.4. External Input Protection .........................22
23.5. Charging Batteries ....................................23
23.6. Output Circuit Breakers ............................ 23
23.7. Parallel Use to Increase Output Power .... 24
23.8. Parallel Use for Redundancy ....................24
23.9. Daisy Chaining of Outputs .......................25
23.10. Series Operation .......................................25
23.11. Inductive and Capacitive Loads ................25
23.12. Operation on Two Phases ........................ 26
23.13. Use in a Tightly Sealed Enclosure ............ 26
23.14. Mounting Orientations ............................ 27
...................................................... 19
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery whether it is charged (13.7V) or discharged (10V).
• 230Vac—Afigure with the unit (Vac) at the end is a momentary figure without any additional tolerance included.
• 50Hz vs. 60Hz—Unless otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
• shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 100-240V Wide-range Input Width only 60mm Efciency up to 93.5% 150% (360W) Peak Load Capability Easy Fuse Tripping due to High Overload Current Active Power Factor Correction (PFC) Negligible low Inrush Current Surge Short-term Operation down to 60Vac and up to 300Vac Full Power Between -25°C and +60°C DC-OK Relay Contact Quick-connect Spring-clamp Terminals 3 Year Warranty
Description
The most outstanding features of the 1606-XLS DIN rail power supplies are their high efciency and small sizes, which are achieved by a synchronous rectication and further design innovations. The 1606-XLS series is part of Rockwell Automation's family of power supplies, existing alongside lower featured power supplies.
With short-term peak power capability of 150% and built-in large sized output capacitors, these features help start motors, charge capacitors and absorb reverse energy and often allow a unit of a lower wattage class to be used.
High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible.
The integrated output power manager, a wide range input voltage design and virtually no input inrush current make installation and usage simple. Diagnostics are easy due to the dry DC-ok contact, a green DC-ok LED and red overload LED.
Unique quick-connect spring-clamp terminals allow a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation.
Specication Quick Reference
Output voltage DC 24V Adjustment range 24 - 28V Output current 10 – 9A continuous 15 – 13.5A for typ. 4s Output power 240W continuous 360W for typ. 4s Output ripple < 50mVpp 20Hz to 20MHz Input voltage AC 100-240V ±15% Mains frequency 50-60Hz ±6% AC Input current 2.22 / 1.22A at 120 / 230Vac Power factor 0.98 / 0.92 at 120 / 230Vac AC Inrush current typ. 4 / 7A peak at 120 / 230Vac Efciency 92.6 / 93.5% at 120 / 230Vac Losses 19.1 / 16.7W at 120 / 230Vac Temperature range -25°C to +70°C operational Derating 6W/°C +60 to +70°C Hold-up time typ. 27 / 28ms at 120 / 230Vac Dimensions 60x124x117mm WxHxD
Catalog Numbers
Power Supply
1606-XLS240E 1606-XLS240E-D 1606-XLS240EA 1606-XLS240EC
24-28V Standard unit Extended DC-input ATEX approved unit Conformal coated unit
Accessories 1606-XLB Wall mount bracket
1606-XLSRED Redundancy module 1606-XLSBUFFER24 Buffer module
Certication Marks
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
ATEX
II 3G Ex nAC II T4
Marine
EMC, LVD
GOST R
Marine RINA
C-Tick
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.
Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
Should damage or malfunction occur during installation or operation, turn power off immediately and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document. Refer to section 24.14.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. AC-Input
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks AC input range min. 85-276Vac continuous operation min. 60-85Vac full power for 200ms, no damage between 0 and 85Vac min. 276-300Vac < 500ms Allowed voltage L or N to earth max. 276Vac continuous, IEC 62103 Input frequency nom. 50–60Hz ±6% Turn-on voltage typ. 81Vac steady-state value, see Fig. 3-1 Shut-down voltage typ. 63Vac steady-state value, see Fig. 3-1 typ. 55Vac dynamic value
AC 100V AC 120V AC 230V Input current typ. 2.65A 2.22A 1.22A at 24V, 10A, see Fig. 3-3 Power factor *) typ. 0.99 0.98 0.92 at 24V, 10A, see Fig. 3-4 Crest factor **) typ. 1.65 1.67 1.85 at 24V, 10A Start-up delay typ. 800ms 650ms 340ms see Fig. 3-2 Rise time typ. 8ms 8ms 8ms 0mF, 24V, 10A, see Fig. 3-2 typ. 15ms 15ms 15ms 10mF, 24V, 10A, see Fig. 3-2 Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. **) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
60V 300Vac276V
Shut-down
full
power
for
200ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output Voltage
Input Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
10A
123456789
0
0.4
0.8
1.2
1.6
2.0
2.4
2.8A
Output Current
Input Current, typ.
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c
Power Factor, typ.
12345678910A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
100Vac
120Vac
2
3
0
V
a
c
4 Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
1606-XLS240E, 1606-XLS240EA, 1606-XLS240EC:
DC input nom. DC 110-150V -20%/+25% DC input range min. 88-187Vdc continuous operation DC input current typ. 2.37A 110Vdc, at 24V, 10A
1606-XLS240E-D:
DC input nom. DC 110-300V -20%/+25% DC input range min. 88-375Vdc continuous operation DC input current typ. 2.37/ 0.85A 110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103 Turn-on voltage typ. 80Vdc steady state value Shut-down voltage typ. 55Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or similar DC source.
For other sources, contact Rockwell Automation. b) Connect +pole to L and –pole to N. c) Connect the PE terminal to a earth wire or to the machine
ground. d) A supply from the intermediate DC-bus of a frequency
converter is not recommended and can cause a
malfunction or damage the unit.
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
5. Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 10A
peak
10A
peak
10A
peak
over entire temperature range
typ. 5A
peak
4A
peak
7A
peak
over entire temperature range
Inrush energy max. 4A
2
s 4A2s 4A2s over entire temperature range
Inrush delay (A) typ. 650ms 520ms 250ms see (A) in Fig. 5-1
Fig. 5-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
A
A…. Inrush delay
Input: 230Vac Output: 24V, 10A Ambient: 25°C
Upper curve: Input current 2A / DIV Middle curve: Input voltage 500V / DIV Lower curve: Output voltage 20V / DIV Time basis: 100ms / DIV
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6 Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 24V Adjustment range min. 24-28V guaranteed max. 30V Factory setting typ. 24.1V ±0.2%, at full load, cold unit Line regulation max. 10mV 60-300Vac Load regulation max. 100mV static value, 0A 10A Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm Output current nom. 10A continuously available at 24V, see Fig. 6-1 nom. 9A continuously available at 28V, see Fig. 6-1
nom. 15A
nom. 13.5A
Output power nom. 240W / 252W continuously available at 24V / 28V nom. 360W / 378W *) short term available BonusPower
®
BonusPower
time typ. 4s duration until the output voltage dips, see Fig. 6-2 min. 3s max. 5s
®
BonusPower
recovery time typ. 7s overload free time to reset power manager, see Fig. 6-3 Overload behaviour cont. current Short-circuit current min. 8A max. 12.5A min. 21A max. 27A max. 15A Output capacitance typ. 7 000μF included inside the power supply
*) BonusPower, short term power capability (up to typ. 4s)
The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short­term duration is hardware controlled by an output power manager. BonusPower is repeatedly available. Detailed information can be found in section 23.1. If the power supply is loaded longer with the BonusPower than shown in the Bonus-time diagram (see Fig. 6-2), the max. output power is automatically reduced to 240/252W.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee this value can be achieved. The typical value is about 28.6V.
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specied short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves are provided in section 23.2.
Peak current voltage dips typ. from 24V to 20.5V at 20A for 50ms, resistive load typ. from 24V to 18V at 50A for 2ms, resistive load typ. from 24V to 14V at 50A for 5ms, resistive load
***)
at clockwise end position of potentiometer
*)
short term available BonusPower
at 24V, for typical 4s, see Fig. 6-1
*)
short term available BonusPower
at 28V, for typical 4s, see Fig. 6-1
**)
continuous, load impedance 100mOhm, see Fig. 6-1
**)
continuous, load impedance 100mOhm, see Fig. 6-1
**)
during BonusPower
**)
during BonusPower
**)
continuous, load impedance <10mOhm, see Fig. 6-1
*)
, load impedance 100mOhm
*)
, load impedance 100mOhm
*)
,
*)
,
*)
at 24V / 28V
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014 7
Bulletin 1606 Switched Mode Power Supplies
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Bonus time vs. output power
c on
t i
n uo
u s
Output Voltage
0
0 5 10 15 20
4
8
12
28V
16
20
24
25
A
Output Current
s
h
or
t
-
t
e
r
m
Adjustment
Range
Bonus Time
0
110 120 130 140 150
160%
1
2
3
7
4
5
6
8
9
10s
m
i
n
m
a
x
typ
Output Power
Fig. 6-3 BonusPower recovery time
Power Demand
100%
t
t
Limitation by Power Manager
Output Voltage
Bonus Power disabled
Bonus
Time
Recovery Time
BonusPower is available as soon as power comes on and immediately after the end of an output short circuit or output overload.
Fig. 6-4 BonusPower after input turn-on Fig. 6-5 BonusPower after output short
100%
Output Voltage
Input Voltage
Bonus Power
150%
Output Power
Short of
Output
100%
Output Voltage
Bonus Power
Output Power
150%
8 Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 100V AC 120V AC 230V Hold-up Time typ. 51ms 53ms 55ms at 24V, 5A, see Fig. 7-1 typ. 26ms 27ms 28ms at 24V, 10A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
10
20
30
40
50
60ms
85 120 155 190 230Vac
Input Voltage
2
4
V
,
5
A,
m
i
n
.
2
4
V
,
5
A
,
t
y
p
.
2
4
V
,
1
0
A
,
m
i
n
.
2
4
V
,
1
0
A,
t
y
p
.
Hold-up Time
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
8. DC-OK Relay Contact
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in parallel to the power supply output.
Contact closes As soon as the output voltage reaches the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. Contact re-closes As soon as the output voltage exceeds 90% of the adjusted voltage. Contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. permissible load Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
250ms
0.9* V
ADJ
<
1ms
10%
V
OUT
= V
ADJ
>
1ms
open openclosed closed
Note: The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according
to specication. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly if the load is a battery, if the power supply is used in parallel or if the power supply is used for N+1 redundant systems.
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014 9
Loading...
+ 19 hidden pages