Carefully read the operating manual before commissioning the units for the first time. It contains
useful tips and notes such as hazard warnings to
prevent personal injury and material damage.
Failure to follow the directions in this manual not
only presents a danger to people, the environment
and the system itself, but will void any claims for
liability.
Keep this operating manual and the refrigerant
data sheet near to the units.
1.2
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
Safety and
usage instructions
General safety notes
Identification of notes
DANGER!
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or material and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient
and fault-free operation.
1.3
Personnel qualifications
Personnel responsible for commissioning, operation, maintenance, inspection and installation must
be able to demonstrate that they hold a qualification which proves their ability to undertake the
work.
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger, which if not avoided may be fatal or
cause serious injury.
WARNING!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury.
Dangers of failure to observe
1.4
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
In particular, failure to observe the safety notes
may pose the following risks:
n The failure of important unit functions.
n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.
1.5
Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
4
1.6
Safety notes for the operator
The operational safety of the units and components is only assured providing they are used as
intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified personnel.
n Protective covers (grille) over moving parts
must not be removed from units that are in
operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with certain unit parts or components
may lead to burns or injury.
n The units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperature.
n Spaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of
suffocation.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign
objects, fluids or gases.
n The units must be inspected by a service tech-
nician at least once annually. Visual inspections and cleaning may be performed by the
operator when the units are disconnected from
the mains.
n The local room air conditioner is designed for
flexible use in living and work spaces. Yearround operation is not recommended.
n Do not leave the appliance running for an
extended period unsupervised.
Safety notes for installation,
1.7
maintenance and inspection
n Appropriate hazard prevention measures must
be taken to prevent risks to people when performing installation, repair, maintenance or
cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
n Local regulations and laws such as Water
Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
n Mobile units must be set up securely on suit-
able surfaces and in an upright position. Stationary units must be permanently installed for
operation.
n The units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
n Safety devices must not be altered or
bypassed.
Unauthorised modification
1.8
and changes
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety. The
use of other parts may invalidate liability for
resulting consequences.
1.9
Intended use
Depending on the model, the equipment and the
additional fittings with which it is equipped is only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed room..
Different or additional use shall not be classed as
intended use. The manufacturer/supplier assumes
no liability for damages arising from an unintended
use of the equipment. The user bears the sole risk
in such cases.
Using the equipment as intended also includes
working in accordance with the operating manual
and installation instructions and complying with the
maintenance requirements.
Under no circumstances should the threshold
values specified in the technical data be exceeded.
1.10
For warranty claims to be considered, it is essential
that the ordering party or its representative complete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
Warranty
5
REMKO RKL
1.11
The devices are supplied in a sturdy shipping container. Please check the equipment immediately
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
1.12
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved
collection points.
Transport and packaging
WARNING!
Environmental protection
and recycling
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not disposed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner, e.g. using certified firms and recycling specialists or at collection points.
6
2
2.1
Technical data
Technical data
Unit data
SeriesRKL 491 DC
RKL 491 DC
Operating modeLocal inverter room air conditioner in split design
Nominal cooling output
Energy efficiency ratio,
1)
1)
Energy efficiency size SEER
Power consumption, annual, Q
1)
CE
kW4.30 (1.80 to 4.60)
B
4.6
kWh346
Application area (room volume), approx.m³120
Adjustment range indoor unit°C/%r.H.+16 to +30 / 35 to 80
Operating range outdoor unit°C/%r.H.+21 to +43 / 35 to 80
Refrigerant
R 410A
3)
Max. operating pressurekPa4200
Air volume flow per level, indoor unitm³/h380 / 520 / 600
Max. airflow volume outdoor unitm³/h1000
2)
Sound pressure level p. stage, ind. unit
dB(A)45 / 48 / 54
Sound power level max., IT/ATdB(A)59 / 64
Power supplyV/Hz230 / 1~/ 50
Enclosure class indoor unit / outdoor unitIP24 / X4
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW1.31
A5.60
Elec. starting current max., LRAA8.00
Condensate pump, flow rate, max.mm WS1800
Refrigerant, basic capacitykg1.08
Refrigerant piping, lengthmm3000, 2300 usable
Dimensions indoor unit H/W/Dmm695 / 470 / 335
Dimensions outdoor unit H/W/Dmm490 / 510 / 230
Weight indoor unitkg35.0
Weight outdoor unitkg14.0
Standard colourwhitesilver
Serial number1288...1289...
EDP no.16154901615491
1)
Air inlet temperature TK 27°C / FK 19°C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume
2)
Distance 1m free field
3)
Contains greenhouse gas per Kyoto protocol (see also information in "Connecting line" chapter)
7
2
1
4
3
5
6
7
8
LA
LA
LE
IG
AT
LE
2
1
4
3
5
LE
2
6
REMKO RKL
3
Equipment description
The device is particularly suited for flexible operation, but can also be mounted in a stationary installation. The local air conditioning unit is comprised
of an indoor unit for setting up on the floor indoors
and an outdoor unit for wall or ground installation
outdoors. In "cooling" mode, the output produced
by the compressor precisely matches itself to
requirements, and thereby regulates the nominal
temperature with minimal temperature deviations.
This "inverter-technology" results in energy savings
over conventional split systems and also reduces
noise emissions to a particularly low level. The
flexible connection pipe serves to transport the
heat outdoors. The outdoor unit discharges the
absorbed heat to the outdoor air by means of a
heat exchanger (condenser). The condensate collected during cooling operation is transported to
the outdoor unit by means of a condensate pump
integrated into the indoor unit and evaporates via
the heat exchanger. The device filters and dehumidifies the air and thereby creates a comfortable
room climate. It works fully automatically and offers
numerous additional options thanks to its microprocessor control system. The device can be conveniently operated by means of the infrared remote
control unit included.
Structure and function
Fig. 1: Front view
IG Indoor unit
AT Outdoor unit
LA Air outlet
LE Air intake
1Recessed grip
2Infrared receiver
3Ventilation louvers
4Control panel
5Carrying handle
6Conveyor rollers
7Connector pipes
8Condenser fan (back side)
Fig. 2: Rear view (indoor unit)
LE Air intake
1Connector pipes
2Mount for the outdoor unit
3Cover
4Air filter
5Condensate drain
6Mains lead with plug
8
96
758
2
1
REMOTE
DRAIN WATER
AUTO
SWING
TIMING
ON
OFF
TIMER
SET
RESET
THERMO CONTROL
COMP. ON
DEHUM.
FAN
LO
MED HI AUTO
MODE
3
4
10
11
12
13
14
15
13
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
4
Operation
The system can be operated by means of the control panel on the device or via the standard infrared remote
control unit. The functional operation of the buttons among themselves is identical, however, the designation
can vary. The batteries must be correctly inserted before the infrared remote control is used.
Fig. 3: Control panel
Legend
„ON / OFF“ button
„MODE“ button (Fan speed-mode)
The fan speed is indicated by means of LEDs in
the selected modes AUTO-HI-MED-LO or circulated air mode FAN.
LED „AUTO“ (Fan mode)
Indication of the automatic fan operation.
LED „HI“ (Fan mode)
Indication of the high fan operation.
LED „MED“ (Fan mode)
Indication of the average fan operation.
Display
The display shows the set nominal temperature or
the residual time of a programmed timer.
"ON" and "OFF" timer
The timer function can be used to switch the
device on or off automatically in hourly intervals
( „▼▲“ buttons) by means of pressing the "SET"
button. The function can be used to program the
switch-on timer when the device is off and the
switch-off timer when the device is on, for up to 24
hours. Both timers can be deleted by means of
pressing the "RESET" button.
LED „TIMING ON and OFF“
Indicator of activation (LED ON) or deactivation
(LED OFF) of the timing on and off
LED „LO“ (Fan mode)
„AUTO SWING“ button
Indication of the low fan operation.
The direction of the discharged air via the oscil-
LED „DE- HUM.“ (Dehumidifying mode)
Indication of the dehumidifying mode.
LED „FAN“ (Circulated air )
Indication of the circulated air.
LED „COMP. ON“ (Compressor operation)
The controller controls the cooling output by
means of switching the compressor on or off. Compressor operation is indicated by means of the
LED. If the LED flashes, the compressor will be
activated in max. 3 mins.
Button „▼ ▲“ Temperature setting
The desired nominal temperature can be set with
the „▼ ▲“ buttons in steps of 1°C between 16 and
30°C.
lating fins can be adjusted to fixed or oscillating by
pressing the "AUTO SWING" button.
LED „DRAIN WATER“
If the pump is unable to transport the collected
condensate then this is signalised via an acoustic
alarm in combination with the flashing "DRAIN
WATER" LED. The device will be operational again
after the container is emptied by means of the condensate drain.
Infrared receiver
The device receives the signals from the infrared
remote control via the sensor.
„FAN“ button(only on the infrared remote con-
trol)
The ventilator speed can be adjusted by means of
pressing the "FAN" button.
9
IR
2
1
10
12
14
FAN
TEMP.
ON/OFF
FUZZY
C
TIMER
MODE
17
FUZZY
REMKO RKL
Dehumidifying mode DE-HUM. ( )
Position the indoor unit and the outdoor unit in the
room that is to be dehumidified.
1.Ensure that the indoor unit cannot extract
warm air from the outdoor unit.
2.Do not hang the outdoor unit onto the indoor
unit.
3.Please observe: The condensate formed
during dehumidification may not be pumped
to the outdoor unit as otherwise it will be dissipated back into the air in the room or may
run out of the outdoor unit.
4.Take the condensate drain hose on the back
of the indoor unit out of its bracket and
remove the plug.
5.Allow the condensate to drain downwards
into a drain or container.
Fig. 4: Infrared remote control
IR Infrared transmitter
Cooling mode ( )
1.Switch the unit on by means of the "I / 0"
button.
2.Set the temperature selection switch to the
desired nominal temperature.
3.Select the desired fan mode to AUTO, HI,
MED or LO by means of the "MODE" button.
Circulated air mode ( )
1.Switch the unit on by means of the "I / 0"
button.
2.Select FAN mode by means of the "MODE"
button. (Remote control )
The outdoor unit can remain in the room in circulated air mode. However, do not hang the outdoor
unit onto the indoor unit.
Indication of the fan speed:
= high speed
= average speed
= low speed
= automatic speed
NOTICE!
Ensure that the external container does
not overflow. This could result in water
damage.
6.Switch the unit on by means of the "I / 0"
button.
7.Set the temperature selection switch to the
lowest nominal temperature.
8.Set the "MODE" button to the lowest fan
speed "LO".
10
20 cm
20 cm
5
Installation instructions
The device is supplied in a fully operational condition and is equipped as standard with a 3.0 m long
connection pipe linking the indoor and outdoor
devices, meaning that it is ready for use. The
scope of delivery includes various accessories for
mounting the outdoor unit.
Indoor unit
The indoor unit is positioned at the desired location
with the air discharge side pointing into the room.
When positioning, ensure there is a minimum gap
of 20 cm around the device.
Connector pipes
The connector pipes can be laid through a tilted
window or through a gap in the door. The connector pipe can be separated from the indoor unit,
meaning that there is the additional option of fitting
it to a wall opening (Ø min. 60 mm). Please note
the following information when laying the connector pipes:
n The connector pipes may not be jammed in or
n There may not be any tension of other
n The pipe insulation and the protective jacket
Installation
kinked.
mechanical stress exerted on the connector
pipes.
may not be damaged.
Installation on the ground
Fig. 5: Minimum clearance to wall
It is not necessary to use any mounting accessories when installing the outdoor unit on a patio or
balcony. The outdoor unit should be positioned
vertically and protected from direct sunlight. A minimum gap of 20 cm should be maintained from the
air discharge side to the wall. It must be ensured
that the air can be discharged freely (min. 50 cm
gap to any obstacles). The connecting pipe is fed
through a gap in the window (
(Fig. 7).
Fig. 5) or door
Outdoor unit
The outdoor unit expels the heat from the room
into the outside air. In order to do so, the outdoor
unit can be positioned on the ground or mounted
on an external wall.
Fig. 6: Absence of minimum gap
11
353 mm
220 mm
1
REMKO RKL
Fig. 8: Required air circulation
Fig. 7: Example assembly outdoor unit
Mounting on an external wall with wall bracket
n Fasten to the wall using the supplied wall
bracket.
n Hook the outdoor unit into the wall bracket and
secure it with the supplied M4 bolts (
Fig. 9).
The wall brackets can be fastened with the supplied fastening elements (dowel 6mm and screws).
Should this not be suitable for the characteristics of
the wall then the fastening elements should be
selected on site to ensure suitable holding force.
When mounting, ensure that the cable is not
stressed and that the insulation is not damaged in
the process. Maintain the minimum gaps. The air
outlets of the indoor and outdoor units may not be
blocked.
Fig. 8 and
Fig. 9: Gaps assembly bracket
1Safety bolt M4
Mounting height
The outdoor unit (lower edge) may only be
mounted max. 1.8 m above the installation level of
the indoor unit (Fig. 10). If the outdoor unit is
mounted below the installation level of the indoor
unit, then the height difference may not exceed 1.5
m.
12
20 cm
max. 1,8 m
2
1
4
3
Fig. 10: Max. assembly height
External wall mounting with fastening straps
Fastening straps are an additional option for
mounting the outdoor unit to an external wall or
parapet wall.
n Hook the wall bracket onto the outdoor unit and
secure it with the screws (M4).
n Hook one end of the fastening strap with the
spring catch into the fastening eyelet of the
outdoor unit.
n Hook the other end of the fastening strap into
the eyelet bolt which is to be attached to the
on-site external wall or parapet wall (
Ensure sufficient stability.
NOTICE!
Depending on the weather can out of the condensate drain at the back of the outer part condensation run and cause noise. This is a
normal process. Select the installation site for
the outdoor unit in such a way as the draining
water cannot cause any form of damage or
hook up the connection to a drain.
The connecting line is connected to the indoor unit
with quick-release couplings. This provides the
facility to disconnect the connecting line from the
indoor unit for assembly purposes without losing
refrigerant.
Connecting line
DANGER!
The unit must be disconnected from the mains
supply during the entire process! It may only be
switched back on when all of the connections
have been made and checked. The fastenings
and all of the covers must be attached beforehand.
DANGER!
Suitable protective gear must be worn when
connecting or disconnecting the connection
pipe.
Instructions for disconnecting the connecting
line:
n Disconnect the units only immediately before
assembly and only leave the units disconnected for as long as is absolutely necessary.
n Before the pipes are reconnected, it is to be
ensured that there is no dirt, moisture or other
foreign bodies in the quick release couplings
which could impair their function.
n Always mount the cable strap as soon as the
pipelines are connected.
n The pipelines may only be disconnected and
connected by authorised specialist engineers.
NOTICE!
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a
lesser impact on global warming than those
with a high greenhouse potential. This device
contains refrigerant with a greenhouse potential of 1975. That means the escape of 1 kg of
this refrigerant has an effect on global warming
that is 1975 times greater than 1 kg CO2,
based on 100 years. Do not conduct any work
on the refrigerant circuit or dismantle the
device - always enlist the help of qualified
experts.
14
In doing so, the following procedure must be
2
1
2
2
1
3
4
5
adhered to:
1.Switch the unit off.
2.Pull the power plug out of the socket.
3.Remove the 2 screws from the cover on the
rear side of the unit (Fig. 12).
Fig. 12: Rear view, indoor unit
1: Cover
2: Screws
4.Remove the cover from the unit.
5.Unscrew the cable strap from the connecting
line (Fig. 13).
6.Push in the side clips on the plugged connection and pull the plug out of the socket
(Fig. 13).
7.Remove the upper section from the bracket
by means of unscrewing the two screws
(Fig. 13).
8.Pull off the condensate drainage hose
(Fig. 13).
9.Unscrew the left-hand union nut with the size
24 open-ended spanner provided. In doing
so, use the second size 21 open-ended
spanner to hold the lower coupling section
still (Fig. 14).
NOTICE!
Never twist the the fixed lower section.
NOTICE!
It is possible that residual fluid can leak
out of the the condensate hose.
10.Screw continuously until the connection is
disconnected.
11.Unscrew the right-hand union nut with the
size 24 open-ended spanner provided. In
doing so, use the second size 21 openended spanner to hold the upper coupling
section still (Fig. 15).
15
A
B
C
D
A
B
C
1
1
REMKO RKL
NOTICE!
Never twist the the fixed upper section.
12.Screw continuously until the connection is
disconnected.
NOTICE!
Do not stop screwing in the event that
refrigerant escapes and a slight hissing
sound is heard.
13.Screw the protective caps provided onto the
4 coupling halves (
14.Ensure that there is a wall opening available
of Ø 60 mm in the event that the connecting
line is to be fed through a wall.
15.After the placement or mounting of the indoor
unit and outdoor unit is complete, the connecting line can be hooked up to the indoor
unit in the opposite order.
16.After making the connections, check the
quick-release couplings for leaks.
Fig. 16).
Fig. 15: Unscrew the right-hand union nut
A: Hold to prevent turning
B: Tighten
C: Loosen
Fig. 16: Screw on protective caps
1: Protective caps
Fig. 14: Unscrew the left-hand union nut
A: Hold to prevent turning
B: Tighten
C: Loosen
D: Remove cable strap
16
7
Electrical connection diagram
Electrical connection
Fig. 17: Electrical connection diagram
PCB1Control board
PCB2Main board
SMSwing motor
FM1Vaporiser fan
FM2Condenser fan
WMCondensate pump
CMCompressor
OLPCompressor excessive temperature protec-
tion
CX1Condenser, vaporiser fan
CX2Condenser, condenser fan
CX3Condenser compressor
RTSensor circulating air temperature
The unit has been manufactured using state-of-the-art production methods and tested several times to
ensure its correct function. If malfunctions should occur, please check the unit as detailed in the list below. If
all functional checks have been carried out and the device still fails to operate properly, then please notify
your nearest specialist dealer.
Functional trouble
Fault descriptionCauseRemedy
The unit does not startMains failureCheck voltage and if necessary wait
The unit is running with Reduced
ventilation output
Timer mode activeWait for timer period to expire or press
Used air or outlet openings
soiled or blocked by foreign
bodies
until power is back on
Arrange to have exchanged
Insert mains plug
Empty container via condensate drain
hose
"I / 0" button again
Clean the openings Remove foreign
bodies
Filter soiledClean the filter in accordance with the
instructions
Outdoor unit soiledClean the fins on the inside of the out-
door unit
Cooling load of the room
excessive
Condensate leaks out of the unitDevice standing at an anglePosition vertically, ensure stable posi-
Plugs missing from condensate drain hose
Error codes
Error codesFault description / note
01I/O PCBA error communication
02Air intake sensor defective
03Evaporator sensor defective
32Liquid line sensor defective
Reduce the thermal load
tioning
Seal the hose so that it is watertight
again
33Hot gas sensor compressor defective
35Compressor speed is not correct
36Compressor over temperature
37Liquid line heat exchanger is too high
18
Error codesFault description / note
1
38Low power AC
39High power AC(A)
40AC(PCON) overcurrent active
41IPM board error communication
42IPM board general error
43IPM board DC overcurrent
44PFC overcurrent
45Over-/undervoltage
46IPM board current error
47PFC over temperature
9
Regular care and observation of some basic points
will ensure trouble-free operation and a long
service life of the unit.
The device should be checked and thoroughly
cleaned after each prolonged use, but in any case
at least once per year.
The entire plant may only be maintained or
repaired by specialist authorised firms.
Care and maintenance
DANGER!
Prior to performing any work, ensure the equipment is disconnected from the voltage supply
and secured to prevent accidental switch-on!
n Clean the equipment using a damp cloth. Do
not use a jet of water.
n Do not use any caustic, abrasive or solvent-
based cleaning products.
n Only use suitable cleaning agents, even in the
event of severe soiling.
n Empty the condensate container and check if
the diameter of the condensate lines have
tapered as a result of soiling prior to and after
each operating season. If this is the case, they
must be cleaned.
NOTICE!
Check the level of dirt on the on the exchanger
fins.
n Clean the air filter on the indoor unit at regular
intervals, and more frequently if necessary.
n It is recommended that you take out a mainte-
nance contract with an appropriate specialist
firm.
This enables you to ensure the operational reliability of the plant at all times!
Fig. 18: Remove filter
1Filter
19
NOTICE!
Never operate the indoor unit without the original filter. The heat exchanger fins on the
indoor unit with soil up if operated without a
filter and the device will suffer performance
loss.
REMKO RKL
Air filter for indoor unit
Clean the air filter at intervals of no more than 2
weeks. Reduce this interval if the air is especially
dirty.
Cleaning the filter on the indoor unit
Please proceed as follows in order to clean the
unit:
1.Remove the mains plug.
2.Pull the filter out of the unit (Fig. 18).
3.Clean the filter of dust. Use a vacuum
cleaner in the event of slight soiling.
4.In the event of more severe soiling, carefully
clean in lukewarm water.
5.Subsequently allow the filter to dry in the air.
6.Insert the filter back into the device.
10
Never switch off the equipment by pulling out
the mains plug.
Temporary shut-down
If it is planned to shut down the equipment for
longer periods e.g. during the winter, proceed as
follows:
1.Allow the equipment run for 2-3 hours in cir-
2.Shut down the equipment by pressing the "I /
3.Empty the internal condensate container via
4.Make sure that there is no condensate in the
5.Clean the filter and the plastic surfaces.
6.Hang the outdoor unit onto the indoor unit.
7.Cover the equipment with a synthetic tar-
Shut-down
NOTICE!
culation mode. This extracts any residual
humidity from the unit.
0" button on the operating panel. Only then
should you pull out the mains plug and wind
up the cable.
the condensate drain hose on the rear side of
the indoor unit.
outdoor unit before storing the indoor and
outdoor unit indoors. To drain the condensate, remove the plug from the outdoor unit.
paulin to protect it against dust.
8.Store the equipment in a cool and dry location away from direct sunlight.
Permanent shut-down
The entire system should only be dismantled by a
specialist firm familiar with all environmental
aspects involved. REMKO GmbH & Co. KG or your
sales partner will be be pleased to provide details
of refrigerant specialists in your area.
20
11
11.1
Exploded view and spare parts lists
Exploded view indoor unit
Fig. 19: Exploded view indoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
21
REMKO RKL
11.2
Please contact REMKO GmbH & Co. KG directly to order spare parts. All of the spare parts numbers for your
unit can be found in the download area at www.remko.de.
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. DesignationRKL 491 DC
1Front panel
2Recessed grip
3Cover, top
4Exhaust grille
5Fins
6Shift lever for fins
7Back wall
8Air filter
Spare parts list - Indoor unit
IMPORTANT!
RKL 491 DC
9Cover for connecting line
10Unit base
11Base plate, cpl.
12Conveyor rollers
13Side cover, right / left
14Condensate container
15Partition wall
16Sound absorption plate
17Bracket for microswitch
18Microswitch, (container full)
19Microswitch, (pump on / off)
20Float, (container full)
21Float, (pump on / off)
22Swing motor for fins
23Coupling for swing motor
24Condensation pump cpl.
On request by providing the serial number
25Electrical terminal block
26Capacitor, evaporator fan
27Capacitor, condenser fan
28Frame, rear right
29Fan, cpl.
22
No. DesignationRKL 491 DC
30Evaporator fan
31Compressor, cpl.
32Evaporator
33Coupling, set (1x m / 1x w)
34Connecting line, cpl.
35Fastening block, cpl.
36Condensate drain hose
37Keypad board
38Keypad foil
39Control board
40IPM protection board
41Mains cable with plug
42Motherboard
43Capacitor board
44Covering for fan
On request by providing the serial number
RKL 491 DC
45Ambient air probe
46Anti-freeze protection probe
When ordering spare parts, please quote the serial no., unit number and type (see name plate)!
23
REMKO RKL
11.3
Fig. 20: Exploded view outdoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
Exploded view outdoor unit
11.4
No. DesignationRKL 491 DC
50Back wall
51Front panel
52Unit base
53Covering for fan
54Condenser fan
55Fastening for condenser fan
56Condenser fan, motor
57Condenser
58Seal
Spare parts list - Outdoor unit
Spare parts not illustrated
Remote control
Capacitor, compressor
Fastening set for outdoor unit, cpl.
On request by providing the serial number
On request by providing the serial number
RKL 491 DC
Wall bracket
When ordering spare parts, please quote the serial no., unit number and type (see name plate)!
24
12
A
Assembly
C
Care and maintenance ...................................... 19
D
Disposal of equipment......................................... 6
Thanks to intensive training,
our consultants are always
completely up-to-date in terms
of technical knowledge. This has
given us the reputation of being
more than just an excellent,
reliable supplier:
REMKO, a partner
helping you find solutions to
your problems.
Distribution
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highlyqualified sales specialists.
REMKO field staff are more than
just sales representatives: above
all, they must act as advisers to
our customers in air conditioning
and heating technology.
SFlbCustomer Service
Our equipment operates
precisely and reliably. However,
in the event of a fault, REMKO
customer service is quickly at
the scene. Our comprehensive
network of experienced dealers
always guarantees quick and
reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood!
Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG
Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage
Postfach 1827 D-32777 Lage
Telephone +49 5232 6 06-0
Telefax +49 52 32 606-2 60
E-mail info@remko.de
Website www.remko.de
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.