REMKO RKL 491 DC User Manual

Assembly and operating instructions
REMKO RKL 491 DC
Local inverter room air conditioner in split design
0074-2014-01 Edition 1, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety notes for the operator........................................................................................................... 5
1.7 Safety notes for installation, maintenance and inspection.............................................................. 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Warranty........................................................................................................................................ 5
1.11 Transport and packaging.............................................................................................................. 6
1.12 Environmental protection and recycling........................................................................................ 6
2 Technical data....................................................................................................................................... 7
2.1 Technical data................................................................................................................................. 7
3 Structure and function.......................................................................................................................... 8
4
Operation............................................................................................................................................... 9
5 Installation........................................................................................................................................... 11
6 Connecting line................................................................................................................................... 14
7 Electrical connection ......................................................................................................................... 17
8 Troubleshooting and customer service ........................................................................................... 18
9 Care and maintenance ....................................................................................................................... 19
10 Shut-down ........................................................................................................................................... 20
11 Exploded view and spare parts lists................................................................................................. 21
11.1 Exploded view indoor unit........................................................................................................... 21
11.2 Spare parts list - Indoor unit........................................................................................................ 22
11.3 Exploded view outdoor unit......................................................................................................... 24
11.4 Spare parts list - Outdoor unit..................................................................................................... 24
12 Index..................................................................................................................................................... 25
3
REMKO RKL
1
1.1
Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for liability.
Keep this operating manual and the refrigerant data sheet near to the units.
1.2
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.

Safety and usage instructions

General safety notes

Identification of notes

DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.
1.3

Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.
WARNING!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.
Dangers of failure to observe
1.4 the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.
1.5

Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4
1.6

Safety notes for the operator

The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grille) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with certain unit parts or components
may lead to burns or injury.
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperature.
n Spaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of suffocation.
n All housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign objects, fluids or gases.
n The units must be inspected by a service tech-
nician at least once annually. Visual inspec­tions and cleaning may be performed by the operator when the units are disconnected from the mains.
n The local room air conditioner is designed for
flexible use in living and work spaces. Year­round operation is not recommended.
n Do not leave the appliance running for an
extended period unsupervised.
Safety notes for installation,
1.7 maintenance and inspection
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Local regulations and laws such as Water
Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n Mobile units must be set up securely on suit-
able surfaces and in an upright position. Sta­tionary units must be permanently installed for operation.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices must not be altered or
bypassed.
Unauthorised modification
1.8 and changes
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety. The use of other parts may invalidate liability for resulting consequences.
1.9

Intended use

Depending on the model, the equipment and the additional fittings with which it is equipped is only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed room..
Different or additional use shall not be classed as intended use. The manufacturer/supplier assumes no liability for damages arising from an unintended use of the equipment. The user bears the sole risk in such cases.
Using the equipment as intended also includes working in accordance with the operating manual and installation instructions and complying with the maintenance requirements.
Under no circumstances should the threshold values specified in the technical data be exceeded.
1.10
For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

Warranty

5
REMKO RKL
1.11
The devices are supplied in a sturdy shipping con­tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
1.12
Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.

Transport and packaging

WARNING!

Environmental protection and recycling

Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recy­cling specialists or at collection points.
6
2
2.1

Technical data

Technical data

Unit data
Series RKL 491 DC
RKL 491 DC
Operating mode Local inverter room air conditioner in split design
Nominal cooling output
Energy efficiency ratio,
1)
1)
Energy efficiency size SEER
Power consumption, annual, Q
1)
CE
kW 4.30 (1.80 to 4.60)
B
4.6
kWh 346
Application area (room volume), approx. 120
Adjustment range indoor unit °C/%r.H. +16 to +30 / 35 to 80
Operating range outdoor unit °C/%r.H. +21 to +43 / 35 to 80
Refrigerant
R 410A
3)
Max. operating pressure kPa 4200
Air volume flow per level, indoor unit m³/h 380 / 520 / 600
Max. airflow volume outdoor unit m³/h 1000
2)
Sound pressure level p. stage, ind. unit
dB(A) 45 / 48 / 54
Sound power level max., IT/AT dB(A) 59 / 64
Power supply V/Hz 230 / 1~/ 50
Enclosure class indoor unit / outdoor unit IP 24 / X4
Electr. rated power consumption
Electr. rated current consumption
1)
1)
kW 1.31
A 5.60
Elec. starting current max., LRA A 8.00
Condensate pump, flow rate, max. mm WS 1800
Refrigerant, basic capacity kg 1.08
Refrigerant piping, length mm 3000, 2300 usable
Dimensions indoor unit H/W/D mm 695 / 470 / 335
Dimensions outdoor unit H/W/D mm 490 / 510 / 230
Weight indoor unit kg 35.0
Weight outdoor unit kg 14.0
Standard colour white silver
Serial number 1288... 1289...
EDP no. 1615490 1615491
1)
Air inlet temperature TK 27°C / FK 19°C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume
2)
Distance 1m free field
3)
Contains greenhouse gas per Kyoto protocol (see also information in "Connecting line" chapter)
7
2
1
4
3
5
6
7
8
LA
LA
LE
IG
AT
LE
2
1
4
3
5
LE
2
6
REMKO RKL
3
Equipment description
The device is particularly suited for flexible opera­tion, but can also be mounted in a stationary instal­lation. The local air conditioning unit is comprised of an indoor unit for setting up on the floor indoors and an outdoor unit for wall or ground installation outdoors. In "cooling" mode, the output produced by the compressor precisely matches itself to requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter-technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The flexible connection pipe serves to transport the heat outdoors. The outdoor unit discharges the absorbed heat to the outdoor air by means of a heat exchanger (condenser). The condensate col­lected during cooling operation is transported to the outdoor unit by means of a condensate pump integrated into the indoor unit and evaporates via the heat exchanger. The device filters and dehu­midifies the air and thereby creates a comfortable room climate. It works fully automatically and offers numerous additional options thanks to its micro­processor control system. The device can be con­veniently operated by means of the infrared remote control unit included.

Structure and function

Fig. 1: Front view
IG Indoor unit AT Outdoor unit LA Air outlet LE Air intake 1 Recessed grip 2 Infrared receiver 3 Ventilation louvers 4 Control panel 5 Carrying handle 6 Conveyor rollers 7 Connector pipes 8 Condenser fan (back side)
Fig. 2: Rear view (indoor unit)
LE Air intake 1 Connector pipes 2 Mount for the outdoor unit 3 Cover 4 Air filter 5 Condensate drain 6 Mains lead with plug
8
9 6
758
2
1
REMOTE
DRAIN WATER
AUTO
SWING
TIMING
ON
OFF
TIMER
SET
RESET
THERMO CONTROL
COMP. ON
DE­HUM.
FAN
LO
MED HI AUTO
MODE
3
4
10
11
12
13
14
15
13
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
4

Operation

The system can be operated by means of the control panel on the device or via the standard infrared remote control unit. The functional operation of the buttons among themselves is identical, however, the designation can vary. The batteries must be correctly inserted before the infrared remote control is used.
Fig. 3: Control panel
Legend
„ON / OFF“ button
„MODE“ button (Fan speed-mode)
The fan speed is indicated by means of LEDs in the selected modes AUTO-HI-MED-LO or circu­lated air mode FAN.
LED „AUTO“ (Fan mode)
Indication of the automatic fan operation.
LED „HI“ (Fan mode)
Indication of the high fan operation.
LED „MED“ (Fan mode)
Indication of the average fan operation.
Display
The display shows the set nominal temperature or the residual time of a programmed timer.
"ON" and "OFF" timer
The timer function can be used to switch the device on or off automatically in hourly intervals ( „▼▲“ buttons) by means of pressing the "SET" button. The function can be used to program the switch-on timer when the device is off and the switch-off timer when the device is on, for up to 24 hours. Both timers can be deleted by means of pressing the "RESET" button.
LED „TIMING ON and OFF“
Indicator of activation (LED ON) or deactivation (LED OFF) of the timing on and off
LED „LO“ (Fan mode)
„AUTO SWING“ button
Indication of the low fan operation.
The direction of the discharged air via the oscil-
LED „DE- HUM.“ (Dehumidifying mode)
Indication of the dehumidifying mode.
LED „FAN“ (Circulated air )
Indication of the circulated air.
LED „COMP. ON“ (Compressor operation)
The controller controls the cooling output by means of switching the compressor on or off. Com­pressor operation is indicated by means of the LED. If the LED flashes, the compressor will be activated in max. 3 mins.
Button „▼ ▲“ Temperature setting
The desired nominal temperature can be set with the „▼ ▲“ buttons in steps of 1°C between 16 and 30°C.
lating fins can be adjusted to fixed or oscillating by pressing the "AUTO SWING" button.
LED „DRAIN WATER“
If the pump is unable to transport the collected condensate then this is signalised via an acoustic alarm in combination with the flashing "DRAIN WATER" LED. The device will be operational again after the container is emptied by means of the con­densate drain.
Infrared receiver
The device receives the signals from the infrared remote control via the sensor.
„FAN“ button(only on the infrared remote con-
trol)
The ventilator speed can be adjusted by means of pressing the "FAN" button.
9
IR
2
1
10
12
14
FAN
TEMP.
ON/OFF
FUZZY
C
TIMER
MODE
17
FUZZY
REMKO RKL
Dehumidifying mode DE-HUM. ( )
Position the indoor unit and the outdoor unit in the room that is to be dehumidified.
1. Ensure that the indoor unit cannot extract warm air from the outdoor unit.
2. Do not hang the outdoor unit onto the indoor unit.
3. Please observe: The condensate formed during dehumidification may not be pumped to the outdoor unit as otherwise it will be dis­sipated back into the air in the room or may run out of the outdoor unit.
4. Take the condensate drain hose on the back of the indoor unit out of its bracket and remove the plug.
5. Allow the condensate to drain downwards into a drain or container.
Fig. 4: Infrared remote control
IR Infrared transmitter
Cooling mode ( )
1. Switch the unit on by means of the "I / 0"
button.
2. Set the temperature selection switch to the desired nominal temperature.
3. Select the desired fan mode to AUTO, HI, MED or LO by means of the "MODE" button.
Circulated air mode ( )
1. Switch the unit on by means of the "I / 0"
button.
2. Select FAN mode by means of the "MODE" button. (Remote control )
The outdoor unit can remain in the room in circu­lated air mode. However, do not hang the outdoor unit onto the indoor unit.
Indication of the fan speed:
= high speed
= average speed
= low speed
= automatic speed
NOTICE!
Ensure that the external container does not overflow. This could result in water damage.
6. Switch the unit on by means of the "I / 0" button.
7. Set the temperature selection switch to the lowest nominal temperature.
8. Set the "MODE" button to the lowest fan speed "LO".
10
20 cm
20 cm
5
Installation instructions
The device is supplied in a fully operational condi­tion and is equipped as standard with a 3.0 m long connection pipe linking the indoor and outdoor devices, meaning that it is ready for use. The scope of delivery includes various accessories for mounting the outdoor unit.
Indoor unit
The indoor unit is positioned at the desired location with the air discharge side pointing into the room. When positioning, ensure there is a minimum gap of 20 cm around the device.
Connector pipes
The connector pipes can be laid through a tilted window or through a gap in the door. The con­nector pipe can be separated from the indoor unit, meaning that there is the additional option of fitting it to a wall opening (Ø min. 60 mm). Please note the following information when laying the con­nector pipes:
n The connector pipes may not be jammed in or
n There may not be any tension of other
n The pipe insulation and the protective jacket

Installation

kinked.
mechanical stress exerted on the connector pipes.
may not be damaged.
Installation on the ground
Fig. 5: Minimum clearance to wall
It is not necessary to use any mounting accesso­ries when installing the outdoor unit on a patio or balcony. The outdoor unit should be positioned vertically and protected from direct sunlight. A min­imum gap of 20 cm should be maintained from the air discharge side to the wall. It must be ensured that the air can be discharged freely (min. 50 cm gap to any obstacles). The connecting pipe is fed through a gap in the window ( (Fig. 7).
Fig. 5) or door
Outdoor unit
The outdoor unit expels the heat from the room into the outside air. In order to do so, the outdoor unit can be positioned on the ground or mounted on an external wall.
Fig. 6: Absence of minimum gap
11
353 mm
220 mm
1
REMKO RKL
Fig. 8: Required air circulation
Fig. 7: Example assembly outdoor unit
Mounting on an external wall with wall bracket
n Fasten to the wall using the supplied wall
bracket.
n Hook the outdoor unit into the wall bracket and
secure it with the supplied M4 bolts ( Fig. 9).
The wall brackets can be fastened with the sup­plied fastening elements (dowel 6mm and screws).
Should this not be suitable for the characteristics of the wall then the fastening elements should be selected on site to ensure suitable holding force. When mounting, ensure that the cable is not stressed and that the insulation is not damaged in the process. Maintain the minimum gaps. The air outlets of the indoor and outdoor units may not be blocked.
Fig. 8 and
Fig. 9: Gaps assembly bracket
1 Safety bolt M4
Mounting height
The outdoor unit (lower edge) may only be mounted max. 1.8 m above the installation level of the indoor unit (Fig. 10). If the outdoor unit is mounted below the installation level of the indoor unit, then the height difference may not exceed 1.5 m.
12
20 cm
max. 1,8 m
2
1
4
3
Fig. 10: Max. assembly height
External wall mounting with fastening straps
Fastening straps are an additional option for mounting the outdoor unit to an external wall or parapet wall.
n Hook the wall bracket onto the outdoor unit and
secure it with the screws (M4).
n Hook one end of the fastening strap with the
spring catch into the fastening eyelet of the outdoor unit.
n Hook the other end of the fastening strap into
the eyelet bolt which is to be attached to the on-site external wall or parapet wall ( Ensure sufficient stability.
NOTICE!
Depending on the weather can out of the con­densate drain at the back of the outer part con­densation run and cause noise. This is a normal process. Select the installation site for the outdoor unit in such a way as the draining water cannot cause any form of damage or hook up the connection to a drain.
Fig. 11).
Fig. 11: Assembly with fastening straps
1 Spring catch 2 Fastening eyelet 3 Safety bolt M4 4 Eyebolt
13
REMKO RKL
6
The connecting line is connected to the indoor unit with quick-release couplings. This provides the facility to disconnect the connecting line from the indoor unit for assembly purposes without losing refrigerant.

Connecting line

DANGER!
The unit must be disconnected from the mains supply during the entire process! It may only be switched back on when all of the connections have been made and checked. The fastenings and all of the covers must be attached before­hand.
DANGER!
Suitable protective gear must be worn when connecting or disconnecting the connection pipe.
Instructions for disconnecting the connecting line:
n Disconnect the units only immediately before
assembly and only leave the units discon­nected for as long as is absolutely necessary.
n Before the pipes are reconnected, it is to be
ensured that there is no dirt, moisture or other foreign bodies in the quick release couplings which could impair their function.
n Always mount the cable strap as soon as the
pipelines are connected.
n The pipelines may only be disconnected and
connected by authorised specialist engineers.
NOTICE!
The escape of refrigerant contributes to cli­matic change. In the event of escape, refrig­erant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This device contains refrigerant with a greenhouse poten­tial of 1975. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 1975 times greater than 1 kg CO2, based on 100 years. Do not conduct any work on the refrigerant circuit or dismantle the device - always enlist the help of qualified experts.
14
In doing so, the following procedure must be
2
1
2
2
1
3
4
5
adhered to:
1. Switch the unit off.
2. Pull the power plug out of the socket.
3. Remove the 2 screws from the cover on the
rear side of the unit (Fig. 12).
Fig. 12: Rear view, indoor unit
1: Cover 2: Screws
4. Remove the cover from the unit.
5. Unscrew the cable strap from the connecting
line (Fig. 13).
6. Push in the side clips on the plugged connec­tion and pull the plug out of the socket (Fig. 13).
7. Remove the upper section from the bracket by means of unscrewing the two screws (Fig. 13).
8. Pull off the condensate drainage hose (Fig. 13).
Fig. 13: Dismantling the connecting line
1: Connecting line 2: Cable strap 3: Plug connection 4: Condensate hose 5: Cable strap
9. Unscrew the left-hand union nut with the size 24 open-ended spanner provided. In doing so, use the second size 21 open-ended spanner to hold the lower coupling section still (Fig. 14).
NOTICE!
Never twist the the fixed lower section.
NOTICE!
It is possible that residual fluid can leak out of the the condensate hose.
10. Screw continuously until the connection is disconnected.
11. Unscrew the right-hand union nut with the size 24 open-ended spanner provided. In doing so, use the second size 21 open­ended spanner to hold the upper coupling section still (Fig. 15).
15
A
B
C
D
A
B
C
1
1
REMKO RKL
NOTICE!
Never twist the the fixed upper section.
12. Screw continuously until the connection is disconnected.
NOTICE!
Do not stop screwing in the event that refrigerant escapes and a slight hissing sound is heard.
13. Screw the protective caps provided onto the 4 coupling halves (
14. Ensure that there is a wall opening available of Ø 60 mm in the event that the connecting line is to be fed through a wall.
15. After the placement or mounting of the indoor unit and outdoor unit is complete, the con­necting line can be hooked up to the indoor unit in the opposite order.
16. After making the connections, check the quick-release couplings for leaks.
Fig. 16).
Fig. 15: Unscrew the right-hand union nut
A: Hold to prevent turning B: Tighten C: Loosen
Fig. 16: Screw on protective caps
1: Protective caps
Fig. 14: Unscrew the left-hand union nut
A: Hold to prevent turning B: Tighten C: Loosen D: Remove cable strap
16
7
Electrical connection diagram

Electrical connection

Fig. 17: Electrical connection diagram
PCB1 Control board PCB2 Main board SM Swing motor FM1 Vaporiser fan FM2 Condenser fan WM Condensate pump CM Compressor OLP Compressor excessive temperature protec-
tion CX1 Condenser, vaporiser fan CX2 Condenser, condenser fan CX3 Condenser compressor RT Sensor circulating air temperature
CT Sensor frost protection MS1 Microswitch alarm (container full) MS2 Microswitch condensate pump Colour code: BK Black BR Brown BU Blue GR Gray OR Orange R Red W White Y Yellow
17
REMKO RKL
8
The unit has been manufactured using state-of-the-art production methods and tested several times to ensure its correct function. If malfunctions should occur, please check the unit as detailed in the list below. If all functional checks have been carried out and the device still fails to operate properly, then please notify your nearest specialist dealer.
Functional trouble
Fault description Cause Remedy
The unit does not start Mains failure Check voltage and if necessary wait
The unit is running with Reduced ventilation output

Troubleshooting and customer service

Mains fuse or controller fuse faulty
Mains plug not inserted in socket
Condensate container full, display "DRAIN WATER" flashes
Timer mode active Wait for timer period to expire or press
Used air or outlet openings soiled or blocked by foreign bodies
until power is back on
Arrange to have exchanged
Insert mains plug
Empty container via condensate drain hose
"I / 0" button again
Clean the openings Remove foreign bodies
Filter soiled Clean the filter in accordance with the
instructions
Outdoor unit soiled Clean the fins on the inside of the out-
door unit
Cooling load of the room excessive
Condensate leaks out of the unit Device standing at an angle Position vertically, ensure stable posi-
Plugs missing from conden­sate drain hose
Error codes
Error codes Fault description / note
01 I/O PCBA error communication
02 Air intake sensor defective
03 Evaporator sensor defective
32 Liquid line sensor defective
Reduce the thermal load
tioning
Seal the hose so that it is watertight again
33 Hot gas sensor compressor defective
35 Compressor speed is not correct
36 Compressor over temperature
37 Liquid line heat exchanger is too high
18
Error codes Fault description / note
1
38 Low power AC
39 High power AC(A)
40 AC(PCON) overcurrent active
41 IPM board error communication
42 IPM board general error
43 IPM board DC overcurrent
44 PFC overcurrent
45 Over-/undervoltage
46 IPM board current error
47 PFC over temperature
9
Regular care and observation of some basic points will ensure trouble-free operation and a long service life of the unit.
The device should be checked and thoroughly cleaned after each prolonged use, but in any case at least once per year.
The entire plant may only be maintained or repaired by specialist authorised firms.

Care and maintenance

DANGER!
Prior to performing any work, ensure the equip­ment is disconnected from the voltage supply and secured to prevent accidental switch-on!
n Clean the equipment using a damp cloth. Do
not use a jet of water.
n Do not use any caustic, abrasive or solvent-
based cleaning products.
n Only use suitable cleaning agents, even in the
event of severe soiling.
n Empty the condensate container and check if
the diameter of the condensate lines have tapered as a result of soiling prior to and after each operating season. If this is the case, they must be cleaned.
NOTICE!
Check the level of dirt on the on the exchanger fins.
n Clean the air filter on the indoor unit at regular
intervals, and more frequently if necessary.
n It is recommended that you take out a mainte-
nance contract with an appropriate specialist firm.
This enables you to ensure the operational reli­ability of the plant at all times!
Fig. 18: Remove filter
1 Filter
19
NOTICE!
Never operate the indoor unit without the orig­inal filter. The heat exchanger fins on the indoor unit with soil up if operated without a filter and the device will suffer performance loss.
REMKO RKL
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.
Cleaning the filter on the indoor unit
Please proceed as follows in order to clean the unit:
1. Remove the mains plug.
2. Pull the filter out of the unit (Fig. 18).
3. Clean the filter of dust. Use a vacuum
cleaner in the event of slight soiling.
4. In the event of more severe soiling, carefully clean in lukewarm water.
5. Subsequently allow the filter to dry in the air.
6. Insert the filter back into the device.
10
Never switch off the equipment by pulling out the mains plug.
Temporary shut-down
If it is planned to shut down the equipment for longer periods e.g. during the winter, proceed as follows:
1. Allow the equipment run for 2-3 hours in cir-
2. Shut down the equipment by pressing the "I /
3. Empty the internal condensate container via
4. Make sure that there is no condensate in the
5. Clean the filter and the plastic surfaces.
6. Hang the outdoor unit onto the indoor unit.
7. Cover the equipment with a synthetic tar-

Shut-down

NOTICE!
culation mode. This extracts any residual humidity from the unit.
0" button on the operating panel. Only then should you pull out the mains plug and wind up the cable.
the condensate drain hose on the rear side of the indoor unit.
outdoor unit before storing the indoor and outdoor unit indoors. To drain the conden­sate, remove the plug from the outdoor unit.
paulin to protect it against dust.
8. Store the equipment in a cool and dry loca­tion away from direct sunlight.
Permanent shut-down
The entire system should only be dismantled by a specialist firm familiar with all environmental aspects involved. REMKO GmbH & Co. KG or your sales partner will be be pleased to provide details of refrigerant specialists in your area.
20
11
11.1

Exploded view and spare parts lists

Exploded view indoor unit

Fig. 19: Exploded view indoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
21
REMKO RKL
11.2
Please contact REMKO GmbH & Co. KG directly to order spare parts. All of the spare parts numbers for your unit can be found in the download area at www.remko.de.
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation RKL 491 DC
1 Front panel
2 Recessed grip
3 Cover, top
4 Exhaust grille
5 Fins
6 Shift lever for fins
7 Back wall
8 Air filter

Spare parts list - Indoor unit

IMPORTANT!
RKL 491 DC
9 Cover for connecting line
10 Unit base
11 Base plate, cpl.
12 Conveyor rollers
13 Side cover, right / left
14 Condensate container
15 Partition wall
16 Sound absorption plate
17 Bracket for microswitch
18 Microswitch, (container full)
19 Microswitch, (pump on / off)
20 Float, (container full)
21 Float, (pump on / off)
22 Swing motor for fins
23 Coupling for swing motor
24 Condensation pump cpl.
On request by providing the serial number
25 Electrical terminal block
26 Capacitor, evaporator fan
27 Capacitor, condenser fan
28 Frame, rear right
29 Fan, cpl.
22
No. Designation RKL 491 DC
30 Evaporator fan
31 Compressor, cpl.
32 Evaporator
33 Coupling, set (1x m / 1x w)
34 Connecting line, cpl.
35 Fastening block, cpl.
36 Condensate drain hose
37 Keypad board
38 Keypad foil
39 Control board
40 IPM protection board
41 Mains cable with plug
42 Motherboard
43 Capacitor board
44 Covering for fan
On request by providing the serial number
RKL 491 DC
45 Ambient air probe
46 Anti-freeze protection probe
When ordering spare parts, please quote the serial no., unit number and type (see name plate)!
23
REMKO RKL
11.3
Fig. 20: Exploded view outdoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

Exploded view outdoor unit

11.4
No. Designation RKL 491 DC
50 Back wall
51 Front panel
52 Unit base
53 Covering for fan
54 Condenser fan
55 Fastening for condenser fan
56 Condenser fan, motor
57 Condenser
58 Seal

Spare parts list - Outdoor unit

Spare parts not illustrated
Remote control
Capacitor, compressor
Fastening set for outdoor unit, cpl.
On request by providing the serial number
On request by providing the serial number
RKL 491 DC
Wall bracket
When ordering spare parts, please quote the serial no., unit number and type (see name plate)!
24
12
A
Assembly
C
Care and maintenance ...................................... 19
D
Disposal of equipment......................................... 6
E
Environmental protection..................................... 6
Exploded view drawing
F
Filter cleaning..................................................... 20
I
Installation

Index

Connecting line............................................. 14
Indoor unit..................................................... 21
Outdoor unit.................................................. 24
Connector pipes ........................................... 11
External wall mounting with fastening
straps ........................................................... 13
Indoor unit..................................................... 11
Installation on the ground
Mounting height ........................................... 12
Mounting on an external wall with wall
bracket ......................................................... 12
Outdoor unit.................................................. 11
............................. 11
M
Maintenance...................................................... 19
O
Operation
Circulated air mode....................................... 10
Control panel................................................... 9
Cooling mode ............................................... 10
Dehumidifying mode .................................... 10
S
Safety
Dangers of failure to observe the safety
notes............................................................... 4
General........................................................... 4
Identification of notes...................................... 4
Notes for inspection........................................ 5
Notes for installation....................................... 5
Notes for maintenance.................................... 5
Personnel qualifications.................................. 4
Safety-conscious working............................... 4
Safety notes for the operator.......................... 5
Unauthorised modification ............................. 5
Unauthorised replacement part manufacture.. 5
W
Warranty.............................................................. 5
25
REMKO RKL
26
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 6 06-0 Telefax +49 52 32 606-2 60 E-mail info@remko.de Website www.remko.de
Loading...