These instructions are an integral part of the system and must always
be kept near or on the device.
This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO Heat Pump Manager
Safety notes
Read the operating instructions
carefully before commissioning the
equipment. They provide useful
tips and information as well as
warnings to prevent endangering
persons and property . Failure to
follow the directions in this manual can result in endangerment to
persons, the environment and the
equipment itself and will void any
claims for liability.
■ Keep this manual close to the
equipment.
■ Modification of equipment and
components supplied by REMKO is not permitted and can
cause malfunctions.
■ Operating equipment
or components with obvious
defects or damage is not permitted.
■ Repairs may only be carried out
by authorised personnel, while
cleaning may be carried out by
the operating company.
■ The equipment or components
are not to be exposed to any
mechanical stresses, extreme
levels of humidity or direct
sunlight.
Environmental
protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally compatible materials. To avoid waste and
sustain raw materials, dispose of
packaging only at appropriate collection points.
Disposal of equipment and
components
The equipment and com-
ponents have been manufactured from recyclable materials
only.
Help protect the environment by
ensuring that the equipment or
components (for example batteries) are not disposed of with
household waste but in an environmentally acceptable manner
in accordance with applicable
regulations, e.g. using authorised
disposal and recycling specialists or
municipal collection points.
Warranty
A prerequisite for any warranty
claims is that the enclosed "warranty registration card" was completely filled out and returned to
REMKO GmbH & Co. KG by the
buyer or his agent immediately following purchase or commissioning.
The warranty conditions are listed
in the "General terms and conditions". Special agreements can
furthermore only be agreed between the contract partners. Please
contact your contract partner
directly about this.
Transport and
packaging
The equipment is shipped in sturdy
transport packaging. Please inspect
the equipment immediately upon
delivery. Note any damage or missing parts on the delivery note and
inform the forwarding agent and
your contract partner. Warranty
claims at a later date will not be
accepted.
Intended use
Depending on the model, the
equipment and the additional
fittings with which it is equipped
is only intended to be used as an
air-conditioner for the purpose of
cooling or heating the air in an
enclosed room.
Different or additional use shall not
be classed as intended use. The
manufacturer/supplier assumes no
liability for damages arising from an
unintended use of the equipment.
The user bears the sole risk in such
cases.
Using the equipment as intended
also includes working in accordance with the operating manual
and installation instructions and
complying with the maintenance
requirements.
4
Function
It is the function of the Multitalent heat pump manager to
operate and effectively manage
the entire warm water pump
system including any additionally
installed heating appliances. The
multitude of functions provided
by the heat pump manager must
be configured in accordance with
the existing heating system. This
manual provides both installation
instructions and a overview of
what actually lies behind the heat
pump manager's configuration parameters. The following functions
are displayed in the heat pump
manager:
• Heat pump operation
• Weather managed regulation
of a direct heating circuit and
a mixing circuit (e.g.: floor
heating)
• Hot-water heating
• Cooling
• Solar function
• Demand oriented circulation
pump switching
• Automatic summer/
winter time change
• Individually configurable
reduction times and holiday
operation for heating circuits
and hot-water
• Cascade modulating heating
appliance
• Cascade switching heating appliance
• Bivalence regulator
tion depth in % as a function of
the difference between the current
flow temperature and the target
temperature. The modulation
depth reflects the system's target
output in %, for example the heat
output made necessary by the current outdoor temperature.
T
< T
SUPPLY ACTUAL
SUPPLY TARGET
100
98
80
Modulation depth [%]
WP modulating ON
WP 100% +2. WE, if
Ta < bivalence point
120
100
80
60
40
Modulation depth [%]
20
0
012345678910
0-10 V - signal output
The modulation depth is converted
to a 0-10 V signal and made available to the heat pump's outdoor
unit for further processing.
T
> T
T
SUPPLY ACTUAL
> T
SUPPLY TARGET
T
SUPPLY ACTUAL
WP modulating ON
2. WE OFF
< T
SUPPLY ACTUAL
SUPPLY TARGET
WP OFF
SUPPLY TARGET
+ 2K
Control
principles
Using an outdoor temperature
sensor and the selected heating
curve, the heat pump manager
continuously establishes the target
flow temperature and compares
this temperature with the current
system flow temperature (T collection sensor F8). The heat pump
manager calculates the modula-
120
100
80
60
40
Modulation depth [%]
20
Level
0
0 1,88 3,13 4,38 5,636,888,13 9,38 10
Level
0
Level
1
2
Level
3
0-10 V - signal
Level
Level
4
Level
5
6
Level
8
7
7
6
5
4
3
2
1
0
5
REMKO Heat Pump Manager
Heating curves
The heating curve is used for the
purpose of assigning the building
and appropriate target supply temperature in accordance with the
outdoor temperature. The heating
curves 0.2 to 0.8 have their base
point at 20°C and are intended
for surface heating. The heating
curves 1 to 3 have their base point
at 27°C are therefore appropriate
for radiator heating (steel radiators). The heating curve is easiest
to set at outdoor temperatures
below 5 °C. Changing the heating
curve setting must be carried out
in small steps and in larger time
intervals (at least 5 to 6 hours),
because the system must first adjust to the new values after every
change in the heating curve.
Target supply temperature in °C
Outdoor temperature in °C
6
Commissioning
The Multitalent heat pump manager serves to operate and control
the entire plant.
The heat pump manager itself is
operated by the control unit. The
control console is connected to the
basic device and is located behind
the flap on the indoor module.
C
B
! CAUTION
After a power failure etc.,
the previously programmed
configuration can be accepted
immediately by pressing the
F-button next to
End.
This also
happens automatically after
a delay of 10 minutes.
■
System 1 is pre-installed at
the factory. After a reset of
the heat-pump manager, the
parameters for System 1 are
loaded.
■
Carry out a thorough visual
inspection before the actual
commissioning process.
■
Switch the supply voltage back
on.
■
The following screen appears
on the Multitalent display.
the parameters that go with it
(see the hydraulic schematic
in the heat-pump manager
handbook).
■
The system has to be matched
to the customer's personal values (e.g. inlet temperature).
■
The brief instructions supplied
give an overview of how to set
the most important values.
■ After configuration, the system
is to be run-in and the measured values are to be recorded
in the commissioning report.
NOTE
The commissioning and programming of the heat-pump
manager may only be carried
out by a mechanic authorised
by REMKO.
A
The remote control used to regulate the heat pump manager is
operated with the following keys.
The rotary knob (A) can
be used to:
- move between the
displayed menu items change setting values
Home
Pressing the Home button (B) always returns
you to the standard
display.
Each of the four function
keys (C) stands for one of
the four rows on the display. Press one of these
function keys to select
a menu item or setting
value.
End
Installation
OK
■ Determine which system
diagram is to be used (see the
hydraulic diagram in the heatpump manager manual).
■
If the System 1 schematic is
applicable, you need only press
the F-button next to End .
Should a different system
schematic be selected, press the
F-button next to OK to begin
installation.
■
The configuration in the
installation level for the
selected hydraulics has to be
completely programmed with
NOTE
Please review the heat-pump
manager manual for important details about successful
commissioning.
NOTE
During commissioning, only
a typical heat-manager default
setting can be carried out.
Individual settings must be optimised for construction materials and the practices of various
users. Especially during the first
heating period.
7
REMKO Heat Pump Manager
Functions heat flow meters
The Multitalent heat pump manager PLUS is equipped with the following displays relevant for the heat flow
meters:
Display level
The displays relevant to the heat
flow meters are called up with the
following steps on the heat pump
manager.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C
T-collector 36.2 °C
Heating
Home
Level 1
Main menu
End01
Terminal
Controller
Specialist level
The heat pump menu is found in
the specialist level. The parameters for the heat flow meters are
configured here.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C
T-collector 36.2 °C
Heating
Home
Level 1
Main menu
End01
Terminal
Controller
Including in display of favourites
As many as 10 display values can
be copied to level 0. The system
operator can quickly access these
"favourites" for control purposes
without involving himself with the
heat pump manager.
The possible heat flow meter
displays included in the favourite
menu are shown in the following
section.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C
T-collector 36.2 °C
Heating
Level 2
Controller
End01
Display
User
Time programme
Level 3
Display
End01
Plant
Hot water
Heating circuit 1
Level 4
Plant
End07
Flow volume 28 l/min
Current output 8070 W
Output day 30.2 kWh
Level 4 (continued)
Plant
End07
Output day 30.2 kWh
Output total 99 kWh
Error 00
Level 2
Controller
End04
Time-Date
Service
Specialist
Level 3
Specialist
End02
Heating appliance
Cascade
Heat pump
Level 4 (continued)
Heat pump
End05
E1 function 02
E2 function 03
E15 function 09
Level 4
Heat pump
End12
Impulse rate 1
Impulse unit l/Imp
Min FlowVol 12.0 l/min
Level 0
Fr 23 Apr 10 16:05
Current output 8070 W
T-collector 36.2 °C
Heating
Level 0
Fr 23 Apr 10 16:05
Output day 30.2 kWh
T-collector 36.2 °C
Heating
Level 0
Fr 23 Apr 10 16:05
Output total 99 kWh
T-collector 36.2 °C
Heating
8
Menu structure / menu navigation
Level 1Level 2Level 3Level 0
Mo
T-external
T-collector
Automatic 1
08:3030 Mar 09
15.3 °C
36.2 °C
Home
Main menu
End01
Terminal
Controller
Controller
Display
User
Time programme
End01
Display
Plant
Hot water
Heating circuit 1
Heating circuit 2
Solar / MF
End01
Current operating mode
(Mode)
- Automatic 1
- Automatic 2
- Heating
- Cooling
- Standby
- Reduction
Controller
Display
User
Time programme
Controller
Display
User
Time programme
Controller
Time-Date
Service
Specialist
End01
End01
End04
User
End01
Plant
Hot water
Heating circuit 1
Heating circuit 2
Time programme
End01
Heating circuit 1 prog 1
Heating circuit 1 prog 2
Heating circuit 2 prog 1
Heating circuit 2 prog 2
Hot water
Circulation program
WE 1 enable
WE 2 enable
WE 3 enable
WE 4 enable
S-Kick enable
PU night enable
Time-Date
End01
Time
Date
Holiday start
Holiday end
Summer time setting start
Summer time setting end
Controller
Time-Date
Service
Specialist
Controller
Time-Date
Service
Specialist
Service
End04
End04
Relay test
Sensor test
Software number
Manual cascade operation
Burner running-time
Burner starts
STB test
Customer service
Reset user
Reset specialist
Reset time programme
Communication BM 1
Communication BM 2
Communication KM
Specialist
Conguration
Heating appliance
Cascade
Heat pump
Cooling mode
0-10V I/O
Screed
Hot water
Heating circuit 1
Heating circuit 2
Solar / MF
End01
End01
9
REMKO Heat Pump Manager
Level 4
DISPLAY
Plant
01
T-external
T-collector
T-WE
WE status
T-return total
T-tank 3
Modgrad
Volumetric ow
Output current
Output day
Output total
Error
USER
Plant
Operating mode
Language
LCD contrast
LCD brightness
°C/°F
Terminal address
Regulator address
BUS code 1
BUS code 2
eBUS supply
System selection
Regulator type
WE 1 type
WE BUS
WE 2 type
WE 2 tank
WE 3 type
WE 4 type
Buffer type
Cooling mode
F 15 function
E 1 function
E 2 function
Sensor
10
End01
Heating appliance
End01
Max T-collector
Min T-collector
Min T-WE 2
Hysteresis
Hysteresis period
Sequence change
Clock inhibition
Hyst burner 2
Gradient
Max reduction
Dyn shut-off
WE cooling function
T-WE cold start
Cascade
End01
WE found
Output/level
BUS scan
min mod cascade
WW-WE
System deviation
Output target
Remaining idle time
Max T-WE
WE Dyn up
WE Dyn down
Reset time
Modgrad on
Modgrad off
Min modgrad
Modgrad WW
WE sequence 1
WE sequence 2
Sequence mode
Sequence change
Clock inhibition
Heat pump
End01
Max T-return
Min T-return WP
Max TA WE
Min TA WP
E1 function
E2 function
F15 function
Return offset
Min T-WW
Min T-PU WE
Max WE idle time
Impulse rate
Impulse unit
Min FlowVol
Cooling mode
T-RL cooling
Cooling off at WW
Cooling with WP
End01
Level 4 - continued
SPECIALIST - continued
0-10V I/O
End01
SPG curve
Curve 11 U 1
Curve 11 U 2
Curve 11 T 1
Curve 11 T 2
Curve 11 U A
Solar / MF
End01
MF 1 function
MF 2 function
MF 3 function
MF 4 function
MF 4 Hyst
MF 4 Hyst Off
Max T-supply
Min T-solar on
Min T-solar off
T-solar protection
Re-cooling difference
Max T-SP WW
Max T-SP PU
Max T-SP 3
Solar kick duration
Solar kick interval
Solar kick gradient
Screed
End01
Screed
Screed programme
Hot water
End01
Charge pump lock
PPL
T-WE WW
Hysteresis WW
WW lag
TH inlet
Thermal function
Charging
Heating circuit 1
HC function
Operation HCP
Max T-supply
Min T-supply
T-supply cooling
T-frost protection
T-external delay
End01
Heating circuit 2
End01
HC function
Operation HCP
Mixer Open
Mixer CLOSED
Max T-supply
Min T-supply
T-supply cooling
T-frost protection
T-external delay
Curve displacement
Demand requirement
11
REMKO Heat Pump Manager
Level 4 - DISPLAY - Description of parameters and settings
DISPLAY
Plant
01
T-external
T-collector
T-WE
WE status
T-return total
T-tank 3
Modgrad
Values cannot be changed in the display section.
There is a display only if the respective sensor is connected or the value exists in the system. If the setting does
not exist, it is either hidden or dashes (----) are shown in the display.
Factory settings can vary depending on the system.
Plant
DesignationDescription
T-externalCurrent outdoor temperature [sensor 09] (smoothed value).
Current collector temperature [sensor 8] and (collector) target temperature Display following pressing of
T-collector
the respective function key.
The target corresponds with the highest temperature demanded in the load circuits (incl. water heating).
T-WECurrent temperature of all connected heating appliances [sensor 08].
WE statusHeating appliance's status (on / off).
Current return temperature for the start of the cooling machines (see specialist cooling mode
T-return total
T-RL cooling) and for the shut-off of the heat pumps (see specialist heat pump
Max T-return WP, return offset) [sensor 17].
T-tank 3Current temperature of the tank 3/buffer tank bottom [sensor 01]. No assignment by REMKO
ModgradCurrent target modulation depths for all active WE and required modulation depth.
Volumetric flowDisplay of the current flow volume (flow) in l/min
Output currentDisplay of the current heating/cooling output in W
Output day
Output total
Error
Display of the amount of heat delivered in kWh during the previous day. The value updates itself automatically at 0:00 (midnight)
Display of the amount of heat delivered since commissioning (cumulative). The meter reading is updated
every day at 0:00 (midnight) by the amount of the day's output.
Error number (00 = no errors).
12
Level 4 - DISPLAY - Description of parameters and settings - continued
Hot water
DesignationDescription
T-WW
T-WW UCurrent temperature of the buffer tank bottom [sensor 12] (e.g. systems with a solid fuel boiler)
WW demandStatus of heat demand hot water (on/off).
WW pumpStatus of the hot water charge pump (on/off / 3-way switch valve.
WW enableEnable water heating (on/off).
Current hot water temperature and hot water target temperature (see user hot water
T-WW target). [sensor 06]
Circulation pump
Circulation pump status (on/off).
Heating circuit 1/2
DesignationDescription
T-supply
Heating circuit enable Heating circuit in heating mode (on/off).
Heating circuit pump Heating circuit pump status (on/off).
B-warm up-time
Current supply temperature [sensors 05/08] and supply target temperature following pressing of the
respective function key.
Last required warm up-time with active warm up optimisation.
Solar / MF
DesignationDescription
MF 1Status of the relay MF 1 (on/off) outlet A8 - 2nd heating appliance.
MF 2Status of the relay MF 2 (on/off) outlet A9 - charge pump indoor unit.
T-MF 3Current temperature of the MF 3 sensor [sensor 13] - solid fuel boiler.
MF 3Status of the relay MF 3 (on/off) outlet A10 - 3-way switch valve cooling / MP cooling
MF 4Status of the relay MF 4 (on/off) outlet A12 - solar.
T-solar 1Current collector temperature 1 [sensor 14].
T-WWCurrent hot water temperature and hot water target temperature [sensor 6].
T-WW UCurrent temperature of the buffer tank bottom [sensor 12] (e.g. systems with a solid fuel boiler).
Solar pump 1Status of the collector pump 1 (on/off).
Load Sp WW
Status of the tank charge pump 1 (on/off) not used by REMKO.
13
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings
USER
Plant
End01
Operating mode
Language
LCD contrast
LCD brightness
°C/°F
Hot water
1 x hot water
T-WW 1 target
T-WW 2 target
T-WW 3 target
BoB value
Circ with WW prog
Anti-legionella
End01
Heating circuit 1
End01
Operating mode
T-room target 1
T-room target 2
T-room target 3
T-reduction
T-absent
T-room cooling
T-external cooling
Heating threshold day
Heating threshold night
heating curve
T-supply const T
T-supply const N
Room impact
Heating curve adaptation
Warm up opt
Max warm up-time
Reduction opt
PC enable
Summary of settings that can be set by the system operator.
Plant
DesignationValue rangeFactory settingDescription
Setting the operating mode / the operating mode for the
system.
Heating circuit 2
End01
Operating mode
T-room target 1
T-room target 2
T-room target 3
T-reduction
T-absent
T-room cooling
T-external cooling
Heating threshold day
Heating threshold night
heating curve
T-supply const T
T-supply const N
Room impact
Heating curve adaptation
Warm up opt
Max warm up-time
Reduction opt
PC enable
•Standby (heating OFF, water heating OFF,
only frost protection).
•Cooling (heating OFF, only water heating, activation of
the cooling machines, regulation of the heating circuits to
T-supply cooling).
•Automatic 1+2 (heating in accordance with the
heating programme 1/2, WW in accordance with WWprogramme).
Operating mode /
Operating mode
Standby
Cooling
Automatic 1+2
Summer
Heating
Standby
Reduction
Service
•Summer (heating OFF, WW in accordance with WW-
programme).
•Heating (regulation to T-room target).
•Reduction (regulation to T-reduction).
•Service (regulation to max T-WE, automatic reset after
15 min. in the previous operating mode).
LanguageD/GB/F/NL/E/IEnglishSetting the language for the controller.
LCD contrast00-0604Setting the display intensity.
LCD brightness00-3030Setting the display lighting brightness.
°C/°F
Celsius
Fahrenheit
CelsiusSetting the temperature unit.
14
Level 4 - USER - Description of parameters and settings - continued
Hot water
DesignationValue rangeFactory settingDescription
The tank is only enabled for a one time loading
(= ON) (e.g. for showering outside of hot water times).
1xhot waterOn/OffOff
T-WW 1 target10°C-70°C50°C
T-WW 2 target10°C-70°C50°C
T-WW 3 target10°C-70°C50°C
Loading begins if the T-WW 1 target temperature has been
undercut in the amount of the switching hysteresis (see specialist hot water hysteresis WW).
Setting the desired hot water temperatures for the hot water
programme's 1st, 2nd and 3rd enabling times (see time
programme hot water).
Power saving function for solar or solid fuel boiler (operation
without burner).
BoB value0.0K-70.0K0.0K
Circ with WW progOn/OffOff
Anti-legionellaOn/OffOff
The burner is activated if the current hot water temperature
in the amount of the set value here + switching hysteresis
(see specialist hot water hysteresis WW) has fallen
below the set hot water target temperature.
Activating the circulation pump.
The circulation pump runs when hot water is enabled
(= ON), the circulation programme (see time programme
circulation programme) has no impact.
Activating the anti-legionella function.
With every 20th heating or at least once a week (on
Saturdays at 01:00) the tank is warmed to 65°C (= ON).
It is possible to set a separate anti-legionella function e.g.
by means of the 3rd hot water enabling time (see time
programme hot water).
Be submitted to activation of anti-legionella program must
usually electric heating thermostat to 65 °C.
Heating circuit 1/2
Adjustable values can vary depending on the function selected for the heating circuit.
DesignationValue rangeFactory settingDescription
Setting the operating mode for the respective heating circuit.
Operating mode
----
Standby
Automatic 1+2
Summer
Heating
Reduction
----
! CAUTION
If an operating mode is set here outside of "----", this
operating mode will always apply for the respective heating
circuit regardless of the operating mode setting in the main
menu. (see page 7). This setting possibility is intended for
the use of a remote control.
T-room target 15.0°C-40.0°C20.0°C
T-room target 25.0°C-40.0°C20.0°C
T-room target 35.0°C-40.0°C20.0°C
T-reduction
5.0°C-40.0°C15.0°C
Setting the desired room temperature for the
1st, 2nd and 3rd enable time of the active heating
programme for the selected heating circuit.
Setting the desired room temperature during night reduction
(time between heating periods, see time programme
heating circuit 1/2 prog 1/2).
15
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
DesignationValue rangeFactory settingDescription
T-absent5.0°C-40.0°C15.0°C
T-room cooling
T-external cooling0.0℃-40.0°C20.0°C
----/20.0°C-40.0°C25.0°C
Setting the desired room temperature during holiday reduction
(time away) (see Time-Date holiday start / end).
Setting the desired room temperature in cooling mode for
the selected heating circuit.
The cooling operation is activated if the temperature set
here is exceeded and ends if this temperature is undercut
by 2K. Only in connection with a remote control. With the
value "----", the cooling operation is independent of the
room temperature.
Furthermore, the cooling operation must be enabled by
T-external cooling.
The cooling operation is enabled and activated if the
outdoor temperature exceeds the value set here and ends if
this temperature is undercut by 1K.
Heating threshold
day
Heating threshold
night
----/-5.0°C-4 0.0°C
----/-5.0℃-40.0°C10.0°C
19.0°C
The operating mode heating threshold for the the heating
circuit pump must be activated (see specialist heating
circuit 1/2 operation HCP).
Setting the heating threshold.
If the outdoor temperature measured and determined by
the controller exceeds the heating threshold set here, the
heating will lock, the pumps shut off and the mixers close.
The heating will be enabled again if the outdoor
temperature undercuts the set heating threshold by 1K.
•Heating threshold day (operates during heating periods).
•Heating threshold night (operates during reduction periods).
At "----", the heating threshold is deactivated and the
circulation pump will be switched in accordance with the
standard function.
The curve's slope indicates by how many degrees the supply
temperature will change if the outdoor temperature rises or
falls by 1°C.
If during cold outdoor temperatures the room temperature
is too low (too high), the heating curve must be raised
(lowered).
heating curve
16
0,00-3,000,60
If during high outdoor temperatures the room temperature
is too low, the room temperature must be corrected by
means of the room target temperature (parallel adjustment
of the heating curve).
At "0.00", room regulation is active.
Changing the heating curve must be carried out in small
steps and in larger time intervals (at least 5 to 6 hours),
because the system must first adjust to the new values after
every change in the heating curve.
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
DesignationValue rangeFactory settingDescription
The T-supply const function must be activated (see specialist
T-supply const T10°C-110°C35.0°C
T-supply const N
Room impact
10°C-110°C10.0°C
Off
00-20
Off
heating circuit 1/2 HC function).
Setting the desired supply temperature with which the selected
heating circuit is operated during the heating period.
The T-supply const function must be activated (see specialist
heating circuit 1/2 HC function).
Setting the desired supply temperature with which the
selected heating circuit is operated during the reduction
period.
Only in the absence of an analogue room device (FBR).
The WE temperature is increased in the amount of the value
set here if the desired room temperature (T-room target) is
undercut by 1K (room sensor impact).
Automatic regulation of the heating curve
(Heating curve adaptation).
The current room temperature is measured at the beginning
of the reduction period. This temperature is applied in
the following 4 hours as the target value for the room
regulation. The heating curve is calculated from the values
captured in this time period by the regulator for the supply
and outdoor temperatures.
The setting remains on until the adaptation has been
completed successfully and was not interrupted (e.g. by
a demand for hot water from an external heating circuit).
The controller's water heating and the warm up
optimisation are blocked during the adaptation.
Automatic bringing forward of the heating period start
(warm up optimisation).
Dependent on the weather (T-external) or the current
room temperature (T-room, only in the absence of an
analogue room device (FBR), heating is started up early
enough so that at the beginning of the set heating period,
the temperature in the living area (see time programme
heating circuit 1/2 prog 1/2) just reaches the set room
target temperature (T-room target).
The warm up optimisation is only carried out if the reduction
time for the heating circuit is at least 6 hours.
17
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
DesignationValue rangeFactory settingDescription
Max warm up-time00:00-03:0002:00
Reduction opt
00:00-03:0000:00
Setting the time by which the heating start should as
a maximum be brought forward (maximum bringing forward).
Automatic optimisation of the stopping of the burner at the
end of the set heating period.
During the time period set here before the end of the
heating period (only for the last heating period) (see time
programme heating circuit 1/2 prog 1/2) the burner is
no longer started if it is not already in operation (prevents
short-term warming up of the WE at the end of the heating
period).
PC enable
0000-99990000Code number to allow access to the heating circuit data via PC.
18
Level 4 - TIME PROGRAMME - Description of parameters and settings
All time programmes can be set here.
Factory setting
Designation
Heating circuit 1
prog 1
DayTime
Mo.-Fr.
Mo.-Su.
Sa.+Su.
06:00-22:00
06:00-22:00
07:00-23:00
Operating mode / description
Automatic 1
Heating circuit 1
prog 2
Heating circuit 2
prog 1
Heating circuit 2
prog 2
Hot water
Circulation program
WE 1-4 enable
S-Kick enable
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Su.07:00-22:00
06:00-08:00, 16:00-22:00
06:00-08:00, 16:00-22:00
07:00-23:00
06:00-22:00
06:00-22:00
07:00-23:00
06:00-08:00, 16:00-22:00
06:00-08:00, 16:00-22:00
07:00-23:00
05:00-21:00
05:00-21:00
06:00-22:00
05:00-21:00
05:00-21:00
06:00-22:00
00:00-24:00
00:00-24:00
00:00-24:00
Automatic 2
Automatic 1
Automatic 2
Automatic 1+2
Automatic 1+2
The heating appliances can only be put into
operation in the enabled times set here.
(A demand for heat from a user or tank must
also exist for a heating appliance to operate).
Enable time for the solar kick functions
(see specialist solar MF).
PU night chargingMo.-Su.00:00-05:00
Conventional heat pumps are blocked during
the enable time set here. In this time period,
the buffer tank is only warmed by the heat
pump to the set temperature (see specialist
heat pump Min T-PU WE).
PU night charging should not be enabled in
the heating and hot water time periods.
19
REMKO Heat Pump Manager
Level 4 - TIME-DATE - Description of parameters and settings
Various values are summarised here for the user to provide quick access.
DesignationFactory settingDescription
The controller's time display (The time can only be set using Terminal Time).
Time
DateThe controller's date display (The date can only be set using Terminal Date).
Holiday startOffSetting the first holiday (no more heating beginning from this day).
Holiday endOffSetting the last holiday (there will be no more heating until this day).
Summer time setting
start
Summer time setting
end
If a controller was set as Time Master for the heating system (time standard for
all controllers), entering the time in the system's other controllers is blocked.
(As a maximum, only one Time Master can be set at the BUS).
The automatic switch from summer time to winter time is made possible with
the input of the date.
The earliest date on which switchover takes place is to be set.
The controller carries out the time switch on the Sunday following the set date
at 02:00 or 03:00 in the morning.
20
Level 4 - SERVICE - Description of parameters and settings
Various values are summarised here in order toe enable quick access for customer service.
The input of the code number is necessary for some functions.
The relay test and sensor test are automatically reset after 1 minute!
Sensor test no.
Sensor no.
01Buffer tank temperature bottom
02Buffer tank temperature middle (or room temperature Heating circuit 1)
03Buffer tank temperature top
04not used
05F5X3.16Supply temperature heating circuit 2 (mixer circuit)
06F6X3.15Hot water temperature top (process water tank)
07not used
08F8X3.14Collector temperature (collective supply temperature sensor)
09F9X3.13Outdoor temperature
10not used
11F11X3.12
12F12X3.11Hot water temperature bottom (reference sensor for solar regulation)
REMKO
Sensor
designation
Terminal
layout in the
indoor unit
Description
For CMF 80/90/140/150 and CMT 100/150:
Supply temperature heating circuit 1 (direct heating circuit) or
for CMF/CMT 120 and CMF/CMT 160:
Supply temperature heat pump
13F13X3.10not yet used (solid material WE temperature (PT1000))
14F14X3.9
15F15X3.8Flow meter
16not used
17F17X3.7Return temperature sensor
Collector temperature solar system (special control characteristic
(PT 1000))
21
REMKO Heat Pump Manager
Level 4 - SERVICE - Description of parameters and settings - continued
Relay test
Select the desired relay using the rotary knob at the service level (01-11)
The selected relay is switched on for 1 minute and all other relays are switched off.
Please note that the input of the code number is required for this function.
The relay test breaks off automatically after 5 minutes if no further operation takes place.
Relays OutputDescription
00Normal operation => relays switch in accordance with the regulating function
01A1Circulation pump heating circuit 1 (direct heating circuit) on
02A2Circulation pump heating circuit 2 (mixer circuit) on
03A3Switch valve/charge pump process water
04A4Mixer heating circuit 2 open
05A5Mixer heating circuit 2 closed
06A6Enable heat pump on (charge pump run parallel)
09A9Charge pump inside unit (multi-function 2-output)
10A10
12A12
For CMF 80/140: 2. Heating appliance on
For CMF 90/150 and CMT100/150 circulation pump cooling on
For CMF 80/90: Condenser pump
For CMF/CMT 120/160, CMF 90/150, CMT 100/150: Switch valve cooling (multi-function 3-output)
Circulation pump or solar pump or charge pump UP-solid fuel boiler
(Multi-function 4-output)
Additional entries
DesignationDescription
Software numberDisplay of the software number with index.
Only for cascades; the operating mode Service must be activated.
Manual cascade operation
Burner running-timeDisplay of the heating appliance running time for all levels.
Burner startsDisplay of the heating appliance starts for all levels.
Setting the heating appliance's output (For a switching, multi-level WE, the second level can be
switched on with a performance target of > 50%).
Inputs are automatically reset when the Service function is ended.
STB testSafety temperature limiter test with display of the temperature for the WE. (Start with the F-key)
Input of the date for the annual maintenance reminder (at Year = "00" no reminder) or input of the
Customer service
Reset user
Reset time programme
Communication BM 1Remote control HC 1 at the BUS.
Communication BM 2Remote control HC 2 at the BUS.
Communication KM
22
running time for the system after which a maintenance reminder should generate
(for running time < "50" no reminder).
Respective areas can be reset to the factory setting using the reset function (factory setting = "01").Reset specialist
Communication with expansion module (for additional heating circuits).
Level 4 - SPECIALIST - Description of parameters and settings
SPECIALIST
Conguration
Terminal address
BUS code 1
BUS code 2
eBUS supply
System selection
Regulator type
WE 1 type
WE BUS
WE 2 type
WE 2 tank
WE 3 type
WE 4 type
Buffer type
Cooling mode
F 15 function
E 1 function
E 2 function
Sensor
End01
End01
Max T-collector
Min T-collector
Min T-WE 2
Hysteresis
Hysteresis period
Sequence change
Clock inhibition
Hyst burner 2
Gradient
Max reduction
Dyn shut-off
WE cooling function
T-WE cold start
Heating appliance
Cascade
End01
WE found
Output/level
BUS scan
min mod cascade
WW-WE
System deviation
Output target
Remaining idle time
Max T-WE
WE Dyn up
WE Dyn down
Reset time
Modgrad on
Modgrad off
Heat pump
End01
Max T-return
Min T-return WP
Max TA WE
Min TA WP
E1 function
E2 function
F15 function
Return offset
Min T-WW
Min T-PU WE
Max WE idle time
Impulse rate
Impulse unit
Min FlowVol
Cooling mode
T-RL cooling
Cooling off at WW
Cooling with WP
End01
Min modgrad
Modgrad WW
WE sequence 1
WE sequence 2
Sequence mode
Sequence change
Clock inhibition
SPECIALIST - continued
0-10V I/O
End01
SPG curve
Curve 11 U 1
Curve 11 U 2
Curve 11 T 1
Curve 11 T 2
Curve 11 U A
Solar / MF
End01
MF 1 function
MF 2 function
MF 3 function
MF 4 function
MF 4 Hyst
MF 4 Hyst Off
Max T-supply
Min T-solar on
Min T-solar off
T-solar protection
Re-cooling difference
Max T-SP WW
Max T-SP PU
Max T-SP 3
Solar kick duration
Solar kick interval
Solar kick gradient
Screed
End01
Screed
Screed programme
Hot water
End01
Charge pump lock
PPL
T-WE WW
Hysteresis WW
WW lag
TH inlet
Thermal function
Charging
Heating circuit 1
HC function
Operation HCP
Max T-supply
Min T-supply
T-supply cooling
T-frost protection
T-external delay
End01
Heating circuit 2
End01
HC function
Operation HCP
Mixer Open
Mixer CLOSED
Max T-supply
Min T-supply
T-supply cooling
T-frost protection
T-external delay
Curve displacement
Demand requirement
23
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Changing of the set specialist values is not possible until the code number has been input because setting the
values incorrectly can lead to malfunctions and damage to the system.
Configuration
DesignationValue rangeFactory settingDescription
The BM-T is a terminal (input device). If there are
Terminal addressOn/OffOn
BUS code 1
BUS code 2
00-1501
00-1502
more than one terminal at the BUS, each must be
given a different terminal address.
Heating circuits are numbered in sequence beginning with "01" (heating circuit number); the same
number may not be assigned more than once.
Heating circuits are numbered in sequence beginning with "01" (heating circuit number); the same
number may not be assigned more than once.
24
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
DesignationValue rangeFactory settingDescription
eBUS supplyOn/OffOff
Activating the eBUS supply in accordance with the connected devices.
With this setting, additional values at the configuration level
can be brought forward (selecting the basic functions).
The display value here is always "00".
•01 = Basic hydraulics for the functions “Heating and hot
water”, single energy-source mode, 1 supplemental electric
heating, bivalence point -5°C
•02 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, bivalence point -5°C.
•03 = only heating version, bivalent mode, boiler + option
for 1 supplemental electric heating, bivalence point -3°C.
•04 = only heating version, bivalent mode, solid fuel boiler
+ option for supplemental electric
Supplemental heating, bivalence point -3°C.
•05 = only heating version, single energy-source mode,
1 supplemental electric heating, solar system, bivalence point -5°C.
System selection
Regulator type00-0606
----/01-1201
•06 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, bivalence point -5°C.
•07 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, solar system,
bivalence point -5°C.
•08 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, solar system,
bivalence point -5°C.
•09 = only heating version, bivalent mode + option for 1
supplemental electric heating, solar system, bivalence point -3°C.
•10 = only heating/cooling version, bivalent mode,
bivalence point -3°C
•11 = heating/cooling version, bivalent mode, solar system,
bivalence point -3°C
•12 = heating/cooling version, bivalent mode with solid fuel +
option for 1 supplemental electric heating, bivalence point -3°C
There is no change for "----".
Setting the regulation type for the system.
•00 = No heating appliance (mixer expansion).
•01 = Single stage WE (switching).
•02 = Single stage (modulating).
•03 = Two stage WE (switching).
•04 = Two individual WE (switching).
•05 = Multi-level switching (cascade over BUS).
•06 = Multi-level modulating (cascade over BUS).
WE 1 type
(Output A6
enable or demand
heat pump)
00-0907
•00 = Relay has no function.
•01 = Switch on WE.
•07 = Switch on heat pump.
•08 = Switch on cooling 1.
•09 = Switch on cooling 2.
25
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
DesignationValue rangeFactory settingDescription
•00 = Relay (switching WE).
•01 = CAN-BUS (cascade switching).
•02 = eBUS (WE without temperature controller, default
modulation depth, cascade modulating).
•03 = eBUS (WE with temperature controller, default target
WE BUS00-0505
temperature T-WE target).
•04 = 0-10V (default target temperature T-WE target,
burner relays are controlled in parallel).
Only for regulation type 01, 02, 03, 07.
Sensor 08 must be connected.
•05 = 0-10V (default modulation depth).
Only for regulation type 02 or 06.
WE 2 type
(Output A7
enable cooling)
WE 2 tank
00-2208
00-0300
Not active for WE 1 with two stage burner.
•00 = no second WE.
•01 = Single stage WE (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
•20 = Solid fuel boiler (supplemental not controllable WE).
•21 = Collector pump
•22 = Pump for WE 1 (e.g. supplemental WE for cascades).
Only active if WE 2 type as solid fuel boiler was selected.
Start-up release:
ON: T-WE 2 > Min T-WE 2.
OFF: T-WE 2 < [Min T-WE 2-5K].
•00 = Heating in countercurrent with collector (no tank)
[sensor 08].
ON: T-WE 2 > [T-collector+Hyst burner 2+5K].
OFF: T-WE 2 < [T-collector+Hyst burner 2].
•01 = Heating in countercurrent with buffer tank [sensors
01, 03].
ON: T-WE 2 > [T-buffer O+Hyst burner 2+5K].
OFF: T-WE 2 < [T-buffer+Hyst burner 2].
26
•02 = Heating in countercurrent with WW tank [sensor 06].
ON: T-WE 2 > [T-WW+Hyst burner 2+5K].
OFF: T-WE 2 > [T-WW+Hyst burner 2].
•03 = Heating in countercurrent with tank 3 (swimming
pool) [sensor 15].
ON: T-WE 2 > [T-tank 3+Hyst burner 2+5K].
OFF: T-WE 2 < [T-tank 3+Hyst burner 2].
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
DesignationValue rangeFactory settingDescription
Switching characteristics:
The pump switches on if the temperature of the solid fuel
boiler T-WE 2 exceeds the temperature of the reference sensor [sensor 12] in the amount of the hysteresis [Hyst burner
2+5K]. It shuts off if the temperature T-WE 2 falls below this
WE 2 tank
(continued)
00-0300
switch on temperature by 5K,
Start-up release:
It shuts off if the temperature for the solid fuel boiler T-WE 2 falls
below the temperature limit Min T-WE 2 (see specialist heat-
ing appliance) by 5K.The pump is enabled again if the tempera-
ture T-WE 2 rises above the set temperature limit Min T-WE 2.
•00 = No third heating appliance (multi-function MF 1).
WE 3 type
(Output A8
enable 2nd heating
appliance)
WE 4 type
(Output A9
Charging pump
indoor unit)
Buffer type
00-0901
00-0900
0 0 - 0 20 0
•01 = Single stage heating appliance (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
•00 = No fourth heating appliance (multi-function MF 2).
•01 = Single stage WE (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
Setting the tank type for the heating buffer.
•00 = no buffer tank for heating operation.
•01 = Buffer tank for heating operation [sensors 02, 03].
The activation of the WE 1 takes place with reference to
sensor buffer top [sensor 03].
The charge pump lock impacts the sensor
Buffer top.
WW-charge pump ON: Buffer top > T-WW+5K hysteresis.
WW-charge pump ON: Buffer top < T-WW.
•02 = Combination tank for heating and hot water operation.
The activation of the WE 1 takes place with reference to
sensor buffer middle [sensor 02].
WW-charge pump ON: T-collector > T-WW+5K hysteresis.
WW-charge pump ON: T-collector < T-WW.
27
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
DesignationValue rangeFactory settingDescription
Cooling modeOn/OffOnEnabling the operating mode cooling and the required settings.
Setting the sensor function for sensor 15.
•00 = Room sensor for heating circuit 2.
If in this position an additional sensor is recognised at the
impulse input (IMP = sensor 17), an FBR at sensors 15 and
17 will be analysed. If sensor 17 is occupied by another
function, an RFB will be analysed at sensor 15.
•01 = 0-10V input for default of an external collector target
temperature.
•02 = Light sensor (no function).
•03 = 0-10V input for default of an external modulation depth.
•04 = Second sensor for MF - function.
•05 = Tank 3 (e.g. swimming pool).
F15 function
00-0909
•06 = Sequence/priority switching (e.g. for sequence heat
pumps - conventional heating appliances).
Open contact: WE sequence 1 is active.
Short circuit against ground: WE sequence 2 is active.
•07 = Locking the heat pumps (e.g. energy supply provider
contact).
Open contact: Heat pumps are enabled.
Short circuit against ground: Heat pumps are locked and the message "energy supply provide shut-off" appears in the display.
•08 = Collective fault heat pumps.
Open contact: Heat pumps are enabled.
Short circuit against ground: Fault in all heat pumps (fault
message, locking of the heat pumps and the corresponding
WE-pumps following termination of the pump run-on).
E1 function
Signal processing
(Energy supply
provider disable/
enable)
E2 function
Signal processing
Collective fault outdoor unit and
flow monitor
28
00-0302
00-0303
•09 = Configuration of the F15-input for a flow volume
sensor (impulse sensor). Important in order to activate the
heating meter function.
•00 = No function.
•01 = Sequence/priority switching (e.g. for sequence heat
pumps – conventional heating appliances).
230V at E1/E2: WE sequence 1 is active.
No phase at E1/E2: WE sequence 2 is active.
•02 = Locking the heat pumps (e.g. energy supply provider
contact).
230V at E1/E2: Heat pumps are enabled.
No phase at E1/E2: Heat pumps are locked and the message
"WP lock" appears in the display.
•03 = Collective fault heat pumps.
230V at E1/E2: Heat pumps are enabled.
No phase at E1/E2: Fault in all heat pumps (fault message,
locking of the heat pumps and the corresponding WEpumps following termination of the pump run-on).
"Fault heat pump" appears in the display.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
DesignationValue rangeFactory settingDescription
Sensor
1k/5k sensors5k sensorsSetting the existing resistance for the connected sensor.
Heating appliance
DesignationValue rangeFactory settingDescription
Max T-collector30.0°C-110.0°C70.0°C
Setting the maximum collector temperature [sensor 8] (collective supply temperature).
Min T-collector
Min T-WE 20.0°C-80.0°C0.0°C
Hysteresis2.0K-20.0K2.0K
Hysteresis period00 Min.-30 Min.00 Min.Setting the hysteresis period.
Sequence change00 h-800 h00 h
0.0°C-80.0°C0.0°C
Setting the minimum collector temperature [sensor 8] (collective supply temperature).
Setting the desired minimum temperature for the WE 2.
Reduces condensate formation in the WE if demand for heat
is low. Shut-off of the WE takes place in all cases at the earliest when the minimum temperature+hysteresis set here is
reached.
Function optimisation of the WE operation at variously
heavy demands on the heating appliance.
The effective switching hysteresis is reduced linearly from
the set hysteresis to the minimum hysteresis in the hysteresis
period following switching on of the burner (= 2.0K).
At low heat transfers the higher hysteresis setting is effective
(short runtimes and frequent synchronising of the burner are
prevented).
For longer burner operation (high heating loads) the hysteresis is automatically reduced to 5K (Preheating the heating
appliance to unnecessarily high temperatures is avoided).
Setting the desired operating hours for the first WE in
the active sequence, but the active sequence with which
the WE-sequence should switch (time until the sequence
change).
When operating with at least 2 WE, there is the possibility
to switch the WE sequence in accordance with the operating
hours set here.
Clock inhibition
00 Min.-120 Min.00 Min.
There is no switch at "00 h".
Setting the minimum wait time following switching on of the
WE or for a switching WE, also for switching off of a stage
until switching on of the next stage
(Idle time for the next stage).
At "00 min" the clock inhibition is 10 sec.
29
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating appliances - continued
DesignationValue rangeFactory settingDescription
Only for two stage burners or solid material integration.
Hyst burner 22.0K-20.0K2.0K
Gradient
Max reduction1.0K-20.0K1.0K
On/OffOff
Setting the hysteresis for the charge pump (solid material
integration) or the 2nd burner
Activating the gradient process (only for WE 1)
When heat transfer is low, the heating appliance will be shut
off early (e.g. burnout in a pellet boiler).
At "OFF", the shut-off is carried out by the target value and
the hysteresis.
Setting the value for the determination of the earliest shutoff point (only for WE 1).
The earliest shut-off point is the difference between the
maximum heating appliance temperature Max T-WE
(see specialist cascade) and the value set here.
Load dependent, early shut-off of the WE by the the temperature increase gradients [K/min].
Dyn shut-off
WE cooling functionOn/OffOffActivating the emergency cooling for the WE.
T-WE cold start
0.5K/min.-10K/
min.
30.0°C-120.0°C95.0°C
2.0K/min.
If the WE reaches or exceeds the gradient set here, the WE
will be switched off at the earliest dynamic shut-off point
(difference between Max T-WE and Max reduction).
At a low temperature increase, the shut-off point will be increased linearly up to Max T-WE.
Setting the maximum temperature for the heating appliance
(Cooling start temperature).
If emergency cooling for the heating appliance has been activated (WE cooling function = ON), the heating circuits will
then be taken with
Max T-supply (see specialist heating circuit 1/2) into
operation (if emergency cooling is permitted in the heating
circuit), as soon as the temperature set here has been exceeded by one of the heating appliances.
Emergency cooling is ended if the start temperature T-WE
cold start is undercut by 5K.
30
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade
DesignationValue rangeFactory settingDescription
Display of the heating appliance automatically logged by the
WE found1-3---/x-x--- 1-3/x-x
Output/level
BUS scanOn/OffOff
WE 1-WE 8
WE internal
WE 1 level 1 = 50
WE 2 level 1 = 01
WE 3 level 1 = 01
BUS with BUS identifier (WE-number).
The displayed "x" indicates that the heating appliance has
answered the BUS.
Display of the WE-number and level.
For "---" the level for the WE does not exist.
Following a restart or new configuration, the controller
searches in the BUS systems for heating appliances. In this
period (approx. 1 min.) the output cannot yet be entered
manually.
If a heating appliance answers indicating the output, this
output will automatically be entered in the list.
If a WE answers without indicating the output, the output is
entered in the list with 15KW.
(this value can then be corrected manually).
Search for heating appliances in the BUS.
If the displayed configuration is correct, it can be saved with
"OK". All current values are then overwritten.
Min. Mod Cascade00-100 %00 %
WW-WE00-0800
System deviation
Output target0-100 %
Remaining idle timeRemainder (min.)
Max T-WE
50.0°C-110.0°C72.0°C
If the cascade controller calculates a total modulation depth
greater than nil and smaller than Min. Mod Cascade, total
modulation depth will set to the value set here (minimum
modulation depth).
At the same time, clock inhibition will be set to 10 sec.
Water heating by means of collector (00).
The Number of WEs in the cascade which for water heating
are hydraulically decoupled from the cascade (01-08).
Display of the current collector system deviation (difference
between target temperature and current temperature
[sensor 08]).
Display of the currently required total system output
(corresponds with the calculated target value in the
controller).
Display of the currently remaining idle time (not until "0"
can the next WE be put into operation).
Setting the maximum heating appliance temperature.
The WEs shut off/modulate themselves down independently
if they have not reached the temperature set here (protects
the cascade's individual WEs against overheating and
prevents the STB from triggering).
The WEs switch on again if the set temperature is undercut
by 5K.
The temperature set here should be higher than the
maximum collector temperature Max T-collector
(see specialist heating appliances).
31
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade - continued
DesignationValue rangeFactory settingDescription
Setting the value for the connection of all WE-levels
(WE-connection dynamic [K]).
If the cumulative system deviation in Kelvin reaches the
WE Dyn up20-500350
WE Dyn down20-50020
value set here, this effects the connection of all
WE-levels (the smaller the value, the faster the connection).
Values that are too small can lead to overheating or to a
short-term connection of a WE.
Setting the value for the shut-off of all WEs
(WE-shut-off dynamic).
If the cumulative system deviation in Kelvin reaches the
value set here, this effects the shut-off of all WEs (the
smaller the value, the faster the shut-off).
Values that are too large can lead to overheating and
triggering of the STB.
Reset time05-50030
Modgrad on0 %-100 %100 %
Modgrad off0 %-100 %80 %
Min modgrad0 %-100 %00 %
Modgrad WW
40 %-100 %100 %
Setting of the reset time for the I-controller.
Small values lead to fast controller response and can lead to
vibrations.
Adjusting this value can lead to overshooting the controller.
Setting the modulation depth at which the next WE in the
sequence should be connected.
The connection can take place at the end of the remaining
idle time.
Setting the modulation depth at which the last WE in the
current sequence should be shut off.
Setting the modulation depth at which the next WE should
be connected.
The connection of the next WE only takes place if the resulting modulation depth for the individual WE following connection exceeds the value set here.
For operation with the maximum number of burners,
Modgrad On must be set to "00%" and Min. Modgrad
must be set to the minimum modulation depth for the WElevels.
Setting the target modulation depth for the heating appliances in hot water mode.
WE sequence 11-2-3-4-5-6-7-8
WE sequence 2
32
1-2-3-4-5-6-7-8
1-3-2-4-5-6-7-8
3-1-2-4-5-6-7-8
Setting the sequence in which the heating appliances go into
operation at sequence 1.
Setting the sequence in which the heating appliances go
into operation at sequence 2 (for two stage WEs, the second
stage is always switched after the first stage).
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade - continued
DesignationValue rangeFactory settingDescription
•OnlyWE sequence 1.
•OnlyWE sequence 2.
•Chronological (switch between sequence 1 and 2 in accord-
ance with operating hours of the first WE in the active sequence).
•1/2 switch (switch for heating appliances with different
nominal output: With the connection of the 2nd WE, the
first WE is taken out of operation until the next connection).
•Rotating (the first WE in the sequence is put in the last
position in the current sequence at the end of the sequence
switch period).
•Sorting (new WE sequence by means of automatic sorting
by operating hours for a sequence change).
For the operation of heat pumps, various protection functions (e.g. return temperature monitoring) and functions
for effective operation (monovalence/bivalence mode) are necessary and can be set or activated here (only for
the selection WE 1 type = 07 (heat pump) (see specialist configuration)).
DesignationValue rangeFactory settingDescription
Setting the system's maximum return temperature [sensor 17].
All of the heat pumps in the system will be shut off once the
Max T-return WP30.0°C-110.0°C60.0°C
Min T-return WP0.0°C-20.0°C0.0°C
Max TA WE-20.0°C-40.0°C
-5.0°C
or -3.0°C
temperature set here has been reached.
The heat pumps will be switched on again if the return temperature has fallen below the value set here by 5K.
Setting the system's minimum return temperature [sensor 17].
All of the heat pumps in the system will be shut off if the
temperature set here is undercut.
The heat pumps will be switched on again if the return temperature has risen above the value set here by 3K.
Setting the bivalence point.
The 2nd heating appliance will be enabled if the outdoor
temperature is colder than this setting.
Min TA WP
-30.0°C-10.0°C-20.0°C
Setting the minimum bivalence point.
If the outdoor temperature falls below the value set here, all
heat pumps will be locked and the system will operate only
with conventional heating appliances.
33
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heat pump - continued
DesignationValue rangeFactory settingDescription
E 1 function00-03 02
Description see specialist configuration.E 2 function00-03 03
F 15 function00-08 07
Setting the return offset temperature.
Return offset-5.0K-15.0K0.0K
Min T-WW WE0.0°C-90.0°C45.0°C
Min T-PU WE0°C-90°C0. 0 °C
The heat pumps are not switched off after enabling before
the value in sensor 17 [collector target temperature–return
offset] has been reached.
Setting the minimum hot water temperature only for heat
pump operation.
Only the heat pump works to reach the temperature set
here in the WW-tank.
Setting the minimum buffer temperature for heating
appliances, not relevant for REMKO.
Until the temperature set here has been reached in the
buffer tank [sensor 02], only the heat pump will be operated
during the trickle charging.
Setting the maximum idle time for heating appliances (clock
protection).
Max WE idle timeOff/10-210 minOff
Impulse rate11Configuration of the flow volume sensor for the heating meter
Impulse unitl/Impl/ImpConfiguration of the flow volume sensor for the heating meter
MinFlowVol
... l/min12.0 l/min.
When conventional WEs are locked, these are enabled again
at the end of the time period set here until the target value
in the collector or tank has been reached.
When the flow volume set here is undercut, the heat pump
shuts off with a 2 minute delay and a heat pump fault is
triggered.
Cooling mode
The chillers are regulated by the return temperature T-return (switching hysteresis 2K).
DesignationValue rangeFactory settingDescription
Setting the maximum return temperature in cooling mode.
For a cooling request, the heat pump is switched on if the
T-RL cooling10.0°C-25.0°C15.0°C
temperature in the return as set here [sensor 17] is exceeded
(operating mode "Cooling" must be active).
The heat pump switches off if the temperature in sensor 17
falls below the temperature set here by 2K.
Cooling Off for WWOn/OffOn
Cooling with WP
34
00(Off)/01(On)01
The cooling operation is interrupted with activation of the
water heating.
The heat pump shuts off if the signal "WP-lock" or "WPfault" are present at the inputs F15, E1 or E2 (=01/ON).
Level 4 - SPECIALIST - Description of parameters and settings - continued
0-10V I/O
The outdoor unit is controlled with a 0-10V signal (conversion of the target output or modulation depth).
The factory settings for the following parameters may only be carried out in coordination with REMKO's product
management!
DesignationValue rangeFactory settingDescription
Selection for the voltage curves for the configuration of the
SPG curve00-1111
voltage in and output (default voltage curve or the freely
adjustable curve 11).
Curve 11-U1
Curve 11-U20.0 V-10.0 V10.0 V
Curve 11-T1
Curve 11-T20,0-120,0100,0
Curve 11-UA
0.0 V-10.0 V2.0 V
0,0-120,010,0
0.0V-10.0 V0.0 V
An individual curve can be defined with the parameters U1,
U2, T1, T2 und UA.
•U = voltage.
•T = temperature.
•UA = heating appliance Off.
Beginning at this voltage, the WE is shut off. UA must lie
outside of the valid voltage values.
•U1 and T1 = point 1 on the voltage curve.
•U2 and T2 = point 2 on the voltage curve.
The line between the two limit points defines the voltage
curve.
Screed
DesignationValue rangeFactory settingDescription
Activating the screed programme (only for mixing circuits).
When started the programme shuts down the set supply
temperatures. The integrated mixer circuits regulate in accordance with the set supply temperature. The heat pump
makes
this temperature available independent of the set operating mode. In the standard display, this is identified with the
ScreedOn/OffOff
entry "Screed" and the display of the currently valid supply
temperature.
The screed programme starts at 00:00 with the set supply
temperature from "Day 1" (the start day is not counted)
and switches to each subsequent day at 00:00.
The current day is identified in the screed programme with
an "x".
Following interruption/ending of the function, the controller
continues to heat in the currently set operating mode.
Day 1-3: 25°C
Day 4-7: 55°C
Screed programme
Day 1-28
10°C-60°C/----
Day 8: 25°C
Day 9: 40°C
Day 10-19: 55°C
Day 20: 40°C
Day 21: 25°C
Day 22-28: ----
Setting the desired temperatures for the respective days.
The input "----" ends the programme (even during the
operation for the following day).
! CAUTION
The screed program may be conducted only in conjunction with the two heat sources. The bivalence is highly enforce, if necessary.
35
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Hot water
DesignationValue rangeFactory settingDescription
Activating the 3-way switch valve for process hot water or
alternatively a charge pump for process hot water.
The 3-way switch valve only switches if the temperature
Charge pump lockOn/OffOff
PartialPriority WW
PPL
On/Off
PPL all
PPL all
[sensor 08] exceeds the tank temperature [sensor 06] by 5K
(= ON).
Back to position heating if the temperature of the F-8 sensor
falls below the tank temperature. This prevents cooling of
the tank at the beginning of the water heating.
•WW (partial priority WW).
Heating circuits are locked for water heating. The mixers
close and the heating circuit pumps switch off.
The mixer circuits are enabled again if the WE reaches the
hot water target temperature (see user hot water
T-WW target)+WE target increase (T-WE WE).
The mixer circuits lock again if the WE temperature [sensor
08] falls below the enable temperature by the amount of the
switching hysteresis (hysteresis WW).
•ON (pump parallel operation).
Only the direct heating circuits are locked for water heating.
The mixer circuits continue to be heated
(the water heating is extended with this function).
•Off (hot water priority mode).
Heating circuits are locked for water heating. The mixers
close and the heating circuit pumps switch off.
•PPL all (pump parallel operation also for the direct heating
circuit).
All heating circuits continue to be heated during water heating.
If the temperature exceeds the maximum supply tempera-
ture (see specialist heating circuit 1/2 Max T-supply)
by 8K, the heating circuit pump for this circuit will shut off
(overheating protection).
The heating circuit pump switches on again if the temperature falls below the temperature (Max T-supply+5K).
T-WE WW
36
0.0K-50.0K10.0K
Setting the additive temperature for the heating appliance
during water heating (target increase in WW mode).
The target temperature for heating appliances during
water heating is arrived at by adding the hot water target
temperature (see user hot water T-WW target) to
the temperature set here.
The WE must be operated at an increased temperature
during water heating so that the hot water temperature in
the tank can be reached over the heat exchanger.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Hot water - continued
DesignationValue rangeFactory settingDescription
Setting the hot water hysteresis.
Water heating starts if the temperature in the hot water tank
(sensor F-6) falls below the target temperature (see user
Hysteresis WW3. 0 K - 3 0. 0 K5. 0 K
WW lag0 0 - 3 0 0 1
hot water T-WW target) by the temperature set here.
Water heating ends if the tank reaches the set target
temperature
(in the anti-legionella mode the target temperature is set to
65°C, see user hot water anti-legionella).
Setting the pump lag period.
The pump lag period (5 min.) is extended by the value set
here.
The indoor unit's charge pump continues to run for
another 5 minutes after the heat pump has been shut off
(independent of the period set here).
The lag period is interrupted if there is a demand for heat in
a heating circuit.
An activated charge pump lock can likewise lead to an
interruption of the lag function.
TH inletOn / OffOff
Thermal functionOn / OffOff
Charging
On / OffOff
Activating the water heating by means of thermostat or sensor.
•On (water heating by means of thermostat)
In the event of a short circuit, water heating is started at the
tank sensor's connection terminals. It ends if the short circuit
has been corrected.
•Off (water heating by means of tank sensor).
Activating the aligned target temperature.
The target temperature during water heating is arrived at by
adding the current tank temperature [sensor 6] to T-WE WW.
Activating the charging function
(only possible with sensor 12 = T-WW U).
Water heating with activation of this function (charging =
ON) is not ended until the sensor F 12 (not F 6) has reached
the WW target temperature.
37
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2
The parameters for this level change in accordance with the function selected for the heating circuit.
Depending on the heating circuit, the values that can be adjusted here can vary.
DesignationValue rangeFactory settingDescription
Setting the function for the respective heating circuit.
•Standard (weather managed target temperature regulation
using heating curves).
•T-supply const (control in accordance with fixed supply
temperatures).
During heating periods (see time programme heating
circuit 1/2 prog 1/2) the heating circuit is operated with the
set fixed supply temperature T-supply const T, during reduction periods correspondingly with the set fixed supply tem-
perature T-supply const N (see user heating circuit 1/2
T-supply const T/N).
•Swimming pool (swimming pool regulation, only for heat-
ing circuit 2).
•WW (hot water circuit).
The supply sensor for heating circuit 2 is located in the hot
water tank [sensor 05].
The target value for the hot water temperature can be en-
tered under user hot water T-WW target 1/2/3.
The heating programme for the heating circuit functions as
an enabling programme for the tank.
During the reduction period, the tank's target temperature is
set to 10°C.
The WE controller's hot water priority function can be used
(see specialist hot water PPL).
•Return (return riser above mixer, only for heating circuit 2)
- not relevant for REMKO.
The supply sensor for the heating circuit is used as the return
sensor for the WE [sensor 11/05].
The mixer regulates 24h based on the heating circuit's set
value, Min T-supply.
Installation note:
Mixer Open: The WE's supply is fed into the return (return
riser) (circulation must be ensured by the WE).
Mixer Closed: Return for the heating circuits is piped.
HC function
Standard
T-supply const
Swimming pool
(HC2)
WW(HC2)
Return(HC2)
Standard
38
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2-continued
DesignationValue rangeFactory settingDescription
Setting the operating mode for the pumps.
The circulation pumps are shut off if there is no heating
requirement. Mixers are closed at the same time (the heating
circuit is shut off).
•Standard (standard circulation pump switching).
Room managed regulation (OFF: Room temperature > set
room target value + 1K).
Weather managed regulation in heating mode (OFF:
Outdoor temperature > set room target value).
Weather managed regulation in reduction mode (room impact = 0; OFF: The switching off takes place during the transition to reduction mode. The pump operates after switching
on with ON: Room temperature < room target value; room
impact = OFF; OFF: Supply target temperature < 20°C.)
•Heating limits (Pump switching based on heating limits).
Heating period (OFF: Outdoor temperature < set heating
limit day).
Reduction period (OFF: Outdoor temperature < set heating
limit night).
•only time prog (Pump switching based on heating pro-
gramme).
Heating period (ON, heating circuit is free).
Reduction period (OFF, heating circuit is locked).
•Continuous operation.
The pump runs continuously for 24h. The heating circuit is
continuously free.
Operation HCP
Standard
Heating limits
only time prog
Continuous
operation
Standard
Mixer Open5,0-25,07,0
Mixer Closed5,0-25,07,0
Max T-supply
10.0°C-110.0°C55.0°C
Setting the speed with which the mixer opens in the event
of a control deviation (mixer dynamic opening).
The control deviation is entered in Kelvin where the mixer
opens without interruption.
Small values lead to fast operation of the mixer and can lead
to vibrations.
Setting the speed with which the mixer closes in the event of
a control deviation (mixer dynamic closing).
The control deviation is entered in Kelvin where the mixer
closes without interruption.
Small values lead to fast operation of the mixer and can lead
to vibrations.
Setting the maximum supply temperature for the selected
heating circuit.
The calculated supply target temperature for the heating
circuit is limited by the set maximum supply temperature
(overheating protection).
The heating circuit pump for the direct heating circuit is only
switched off if the [sensor 08] exceeds the temperature set
here by 8K.
The heating circuit pump switches on again if the
temperature [sensor 08] falls below the temperature
(Max T-supply+5K).
39
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2-continued
DesignationValue rangeFactory settingDescription
Setting the minimum supply temperature for the selected
Min T-supply10.0°C-110.0°C18.0°C
T-supply cooling
T-frost protection
Off/Closed
10°C-25°C
Off
-15.0°C-5.0°C5.0°C
Off
heating circuit.
Setting the supply temperature in cooling mode.
In the operating mode cooling, the temperature set here
might possibly be tuned by means of a mixer.
•Off = This heating circuit does not cool
(Mixer Closed, pump Off).
•Closed = mixer as bypass valve (mixer Closed, pump On).
Setting the frost protection temperature.
If the outdoor temperature falls below the temperature set
here, the system switches into frost protection mode (pumps
switch on)
At "Off", the frost protection function is activated.
T-external delay
Curve displacement0.0K-50.0 K0.0K
Demand requirement
00:00-24:0001:00
On / OffOff
Setting the outdoor temperature delay
The type of outdoor temperature delay selected must take
the building design into account.
Because a change in outdoor temperature impacts the room
temperature later for a building with a heavy design (thick
walls), a long delay must be selected.
For a light design (in which the walls do not store heat) the
delay should be set to 0 hours.
Setting the heating curve distance.
The calculated target temperature for the heating circuit is
increased by the value set here.
The heating curve distance equalises sensor tolerances and
heat losses up to the mixer.
The heating circuit can be used with superior functions
(e.g. emergency cooling of a heating appliance to protect
against overheating; heat dissipation in service mode) as
a heat sink/consumer (= ON).
For the duration of the function, the heating circuit is heated
with the maximum set supply temperature Max T-supply.
40
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar / MF
DesignationValue rangeFactory settingDescription
Function selection for the MF - relay (programmable multi-
MF 1 function
(Output A8
enable 2nd heating
appliance)
MF 2 function
(Output A9
Charging pump
indoor unit)
MF 3 function
(Output A10
Switch valve cooling)
MF 4 function
(Output A12
solar pump
or charge pump
solid fuel boiler or
circulation pump)
00-3737
00-3618
00-3634
00-3600
function outputs).
A sensor 1-4 (sensors 11-14) can be assigned to the MFrelay 1-4.
If an additional sensor is necessary for a specific function,
this is to be connected as sensor 15.
•00 = not MF - function.
•01 = collector pump.
ON: In the event of a heat demand from a user.
OFF: In the event of no heat demand from a user.
•02 = circulation (time).
Switching the relay in accordance with the time programme
for the circulation pump.
•03 = supply pump.
ON: In the event of a heat demand from an internal user.
OFF: In the event of no heat demand from an internal user.
A pump lag takes place.
•05 = pump WE 1.
The relay can be used to control the charge pump for heating appliance 1 (relay switches to lag = 5 min.).
•06 = pump WE 2.
The relay can be used to control the charge pump for heating
appliance 2 (relay switches with burner relay; lag = 5 min.).
•07 = switch valve tank 2 (buffer).
The valve switches the solar output of the hot water tank
to the storage tank if a collector can no longer feed into the
hot water tank.
•08 = switch valve tank 3 (swimming pool).
The valve switches the solar output of the storage tank to
the tank 3 (sensor 15) if a collector can no longer feed into
the storage tank (the F15 function must be positioned at 5).
•09 = switch valve tank 3 (swimming pool, only for systems
without solar trickle charging).
The valve switches the solar output of the hot water tank to
tank 3 (sensor 15) if a collector can no longer feed into the
hot water tank
(the F15 function must be positioned at 5).
•10 = pump WE 3.
The relay can be used to control the charge pump for heating appliance 3 (relay switches to lag = 5 min.).
•11 = pump WE 4.
The relay can be used to control the charge pump for heating appliance 4 (relay switches to lag = 5 min.).
41
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Descriptions of additional values (12 to 35) for the
MF 4 function can be found in the following tables
(output A12 solar pump or charge pump solid fuel
boiler or circulation pump)
Description
•12 = Remote controlled output heating circuit 1.
The relay can be switched via the BUS from the heating
circuit's control unit (function see instructions for the remote control).
•13 = Remote controlled output heating circuit 2.
The relay can be switched via the BUS from the heating
circuit's control unit (function see instructions for the remote control).
•14 = pump WE 1.
The relay can be used to control the charge pump for
heating appliance 1 (relay switches to lag = 5 min.).
with buffer in the system (buffer > 00 and sensor PU top
[sensor 03]):
The pump switches on if the temperature of the heating
appliance T-WE1 exceeds the temperature of the buffer
top [sensor 03] by 5K.
The pump switches off if T-WE1 < T-buffer O.
•18 = charge pump indoor unit.
In response to a demand from a heating appliance WE 1
to WE 4 (that is a heat pump and any 2nd heating appliance), the charge pump indoor unit switches on (parallel
mode with 5 min lag). This setting is important in the
bivalent-alternative mode if the boiler does not have its
own circulation pump.
•20 = temperature controlled circulation pump.
T-circ = return temperature in the circulation line.
The circulation pump switches on if the return temperature falls below the set limit temperature T-MF 1 target
(T-circ < T-MF 1 target).
The circulation pump switches off again if the return
temperature rises above the set limit temperature by the
amount of the hysteresis (T-circ > [T-MF 1 target + MF 1
hyst]).
The set circulation programme (see time programme) and
the setting circ with WW prog
(see user hot water) has priority
(switching on takes place only in the enable period).
•21 = circulation pump over impulse.
ON: In the event of a short circuit at the assigned sensor
input.
OFF: After 5 minutes.
The circulation pump switches on for 5 min. in the event
of a short circuit at the sensor input MF. Activation takes
place once on the side.
The set circulation programme (see time programme) and
the setting circ with WW prog
(see user hot water) has priority
(switching on takes place only in the enable period).
! CAUTION
The programming or control for the multi-function outputs must be carried out in accordance
with the parameters for the selected system!
(Basis programming beginning on page 47)
Description
•22 = solid fuel boiler integration (e.g. in connection with
a 2-step WE).
T-MF 1-4 = temperature in the solid fuel boiler.
T-Puffer U = temperature in the storage tank in the area
around the infeed [sensor 01].
Start-up relief:
The circulation pump switches on if the temperature in
the solid fuel boiler rises above the temperature in the
storage tank in the area around the infeed T-buffer U by
the amount of the hysteresis MF 1 hyst + 5K (T-MF 1 >
[T-buffer U + MF 1 hyst + 5K]).
It shuts off if the temperature falls below the activation
temperature by 5K
(T-MF1 < [T-buffer U + MF 1 hyst]).
It also shuts off if the temperature in the sold fuel boiler
falls below the set limit temperature T-MF 1 target by 5K
(T-MF 1 < [T-MF 1 target-5K]).
The pump is enabled again if the temperature in the solid fuel
boiler rises above T - MF1 target (T-MF1 > T-MF1 target).
Locking WE1:
ON: T-MF 1 > T-WE target + 5K
and solid fuel boiler pump = ON.
OFF: T-MF 1 <= T-WE target
and solid fuel boiler pump = OFF.
•23 = solar pump (pump operates if the collector can feed
into one of the solar storage tanks).
Collector 1 pump only to MF4.
Collector 2 pump only to MF3.
This can be used for MF1 and MF2 to charge the tank in
a heat exchanger.
T-solar = temperature of the solar collector.
T-U = temperature of the active tank in the area around
the infeed.
The circulation pump switches on if the temperature of the
solar collector rises above the temperature of the active
tank in the area around the infeed (see switch valve) by
the amount of the activation hysteresis MF hyst (T-solar >
[T-U + MF hyst]).
It shuts off if the temperature of the solar collector falls
below the temperature [T-U + MF hyst Off] (T-solar <
[T-U + MF hyst Off]).
Before shutting off, it is checked whether the secondary
tank (see switch valve) can be charged.
42
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Description
•24 = return riser WE 1.
T-return 1 = return temperature from the system
(= T-MF 1-4).
The return riser pump switches on if the return temperature
falls below the set limit temperature T-MF 1 target.
(T-return 1 < T-MF 1 target).
It switches off again if the return temperature rises above
the set limit temperature by the amount of the hysteresis
MF 1 hyst
(T-return 1 > [T-MF 1 target + MF 1 hyst]).
•25 = return riser WE 2.
T-return 2 = return temperature from the system
(= T-MF 1-4).
The return riser pump switches on if the return temperature
falls below the set limit temperature T-MF 1 target.
(T-return 2 < T-MF 1 target).
It switches off again if the return temperature rises above
the set limit temperature by the amount of the hysteresis
MF 1 hyst
(T-return 2 > [T-MF 1 target + MF 1 hyst]).
•26 = return riser WE via the storage tank.
The return risers valve over storage tank opens if the temperature storage tank bottom (T-buffer U) rises above the
return temperature of the system [sensor 01 or 01-04] by
the the amount of the hysteresis MF 1 hyst + 5K (T-buffer
U > T-MF 1 + MF 1 hyst + 5K).
It switches off again if the temperature storage tank bottom
falls below the return temperature (T-buffer U < T-MF 1 +
MF 1 hyst).
•27 = tank charge pump 1 (pump operates if the hot water
tank can be solar charged).
The temperature of the charging medium for the tank is
always measured at the MF 4-sensor (T-MF 4). Exception:
For function 23 on MF 4, the sensor assigned to the
MF-relay tank charge pump 1 for the calculation of the
temperature of the medium for the charging of the tank
(T-solar) is used.
T-solar (T-MF 4) = temperature of the solar collector.
T-solar (T-MF 1-3) = temperature of the heat exchanger.
T-WW U [sensor 12] = temperature of the hot water tank in
the area around the infeed.
ON: T-solar > [T-WW U + MF hyst].
OFF: T-solar < [T-WW U + MF hyst Off].
The circulation pump switches on if the temperature of the
solar collector rises above the temperature of the tank in
the area around the infeed T - WW U by the amount of the
hysteresis MF Hyst (T-solar > [T-WW U + MF hyst]).
It shuts off if the temperature of the solar collector falls
below the temperature T-WW U + MF hyst Off (T-solar <
[T-WW U + MF hyst Off]).
Description
•28 = tank charge pump 2 (pump operates if the storage
tank can be solar charged and the hot water tank cannot be
solar charged).
The F15 function must be at the position 5.
The temperature of the charging medium for the tank is
always measured at the MF 4-sensor (T-MF 4).
Exception: For function 23 on MF 4, the sensor assigned to
the MF-relay tank charge pump 2 for the calculation of the
temperature of the medium for the charging of the tank
(T-solar) is used.
T-solar (T-MF 4) = temperature of the solar collector.
T-buffer U [sensor 01] = temperature in the storage tank in
the area around the infeed.
The circulation pump switches on if the temperature of the
solar collector rises above the temperature of the tank in
the area around the infeed T-buffer U by the amount of the
hysteresis (T-solar > [T-buffer U + MF hyst]).
It shuts off if the temperature falls below the temperature
T-buffer U + MF hyst Off
(T-solar < [T-buffer U + MF hyst Off]).
•29 = tank charge pump 3 (pump operates if tank 3 can be
solar charged and the storage tank cannot be solar charged).
The F15 function must be at the position 5.
The temperature of the charging medium for the tank is
always measured at the MF 4-sensor (T-MF 4).
Exception: For function 23 on MF 4, the sensor assigned to
the MF-relay tank charge pump 3 for the calculation of the
temperature of the medium for the charging of the tank
(T-solar) is used.
T-solar (T-MF 4) = temperature of the solar collector.
T-tank 3 [sensor 159 = temperature of tank 3 in the area
around the infeed.
The circulation pump switches on if the temperature of the
solar collector rises above the temperature of the tank in
the area around the infeed T-tank 3 by the amount of the
hysteresis MF hyst (T-solar > [T-tank 3 + MF hyst]).
It shuts off if the temperature falls below the temperature
T-tank 3 + MF hyst Off
(T-solar < [T-tank 3 + MF hyst Off]).
•30 = Reloading pump WW-tank 2.
The F15 function must be at the position 4.
The relay switches if the temperature of the hot water tank
rises above the temperature sensor 15 by the amount of the
hysteresis MF hyst.
It shuts off if the temperature of the tank falls below the
temperature [sensor 15 + MF hyst Off].
43
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Description
•31 = Reloading pump storage tank 2.
The F15 function must be at the position 4.
The relay switches if the temperature of the storage tank
rises above the temperature sensor 15 by the amount of the
hysteresis MF hyst.
It shuts off if the temperature falls below the temperature
[F15 + MF hyst Off].
•32 = direct heating circuit.
Heating circuit with fixed supply temperature (T-MF target).
In the event of a short circuit at the assigned MF-sensor
(over room thermostat/time switch) the heating circuit
pump switches ON and the supply target temperature for
the WE is defined.
The pump experiences a lag period after the sensor short
circuit has been corrected.
•34 = bypass valve cooling mode.
The relay switches in the cooling mode
(Separating the conventional WE from the cooling circuit
and water heating is possible during the cooling operation).
The MF-sensor captures the supply temperature for the
WW-regulation.
•35 = bypass valve cooling mode invers.
The relay is switched in the opposite direction to function 34.
•37 = sensor F11 is set as the supply reference sensor (WP-
supply sensor) for the heating meter.
Solar/MF - continued
DesignationValue rangeFactory settingDescription
MF 4 Hyst2.0K-10.0K5.0KSetting the MF 4 hysteresis.
MF 4 Hyst Off2.0K-10.0K2.0KSetting the MF 4 hysteresis for the shut-off process.
Setting the maximum collector temperature.
Max T-supply80.0°C-180.0°C110.0°C
Min T-solar on-20.0°C-95.0°C50.0°C
Min T-solar off-15.0°C-95.0°C45.0°C
T-solar protection80.0°C-180.0°C110.0°C
The collector pumps lock if the corresponding collector
temperature rises above the temperature set here (system
protection).
The pumps are enabled again if the collector temperature
falls below the temperature
[Max T-solar-10K].
Setting the minimum collector temperature.
The collector pump is enabled if the corresponding collector
temperature rises above the temperature set here.
Setting the minimum locking temperature for the collector
pump.
The collector pump locks if the corresponding collector
temperature falls below the temperature set here.
This function prevents the pump from operating without
relevant heat output.
Setting the collector protection temperature.
The collector protection function protects the collector
against overheating. If the collector temperature exceeds the
temperature set here and the tank temperature is less than
92°C, the tank will be charged in excess of its maximum
temperature up to 95°C to cool the collector.
44
The function is interrupted if the collector exceeds its
maximum temperature.
The function is enabled again if the collector temperature
falls below the maximum temperature-3K.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - continued
DesignationValue rangeFactory settingDescription
Setting the return cooling difference.
If the collector protection function has charged the tank
to temperatures higher than the set maximum tank
temperatures during the day, with activation of this
function the tank can be cooled automatically during the
Re-cooling difference
Max T-Sp WW
Max T-Sp PU
Max T-Sp 310.0°C-130.0°C30.0°C
0.0K-30.0K20.0K
10.0°C-130.0°C85.0°C
10.0°C-130.0°C85.0°C
night, between 01:00 and 06:00, to the set maximum tank
temperature (Max T-Sp WW/PU/3) by activation of the
charge pumps (charging is not possible in this period).
Return cooling can only take place if the temperature of
the tank rises above the collector temperature at least by
the amount of the return cooling difference set here + 3K
hysteresis.
Setting the safety temperature limits.
If a tank has a top mounted sensor, the maximum
temperature set here will be monitored by this sensor.
If this sensor is not mounted, the maximum tank
temperature will be monitored by the bottom mounted
sensor (In this case the layer arrangement in the tank must
be taken into account).
The charge pumps lock if the heating tank temperature rises
above the safety limit set here (system protection).
The pumps are enabled again if the heating tank
temperature falls below the temperature
[Max T-Sp WW/PU/3-5K).
Solar kick duration00-59 sec30 sec.Setting the running time of the collector pump for pump kick.
Setting the solar kick interval.
Solar kick interval
Solar kick gradient
10-60 min.30 min.
01-05 min01 min
The pump for the time solar kick duration switches on if the
collector pump has not run for the duration set here.
Setting the solar kick gradients.
In the period set here, the collector temperature progression
following a pump kick is checked.
If there has been an increase of 0.5K, the pump will be
started for another minute.
45
REMKO Heat Pump Manager
System selection
12 basic hydraulic configurations
are provided in the heat pump
manager which can be pulled up
with the system selection and applied in the controller.
Pulled up with the system selection
and applied in the controller.
The system selection was decided in
accordance with the following criteria:
1. by type of heat pump
- only heating series:
CMF 80, CMF 140
- Heating/cooling series:
CMF 90/150/120/160,
CMT 100/150/120/160
CMF 120/160
System
selection
1
Functions
Basic hydraulics for the functions “Heating and hot water”, single energy-source mode, 1 supplemental electric heating, bivalence point -5°C
2. by operating mode
- single energy source
operation (supplemental
heating is a supplemental
electric heater)
- bivalent mode (supplemental
heating is a boiler)
3. by special case
- integration of solar systems
- integration of solid fuel boilers
The following pages show a selection of these basic hydraulic configurations with the corresponding
basic programming list.
In any case, during commissioning,
assign one of the basic hydraulic
configurations via the menu item
system selection to the “On-sitesystem”. Take special care that
the system you select is as near as
possible to system installed onsite. The location of the sensors is
especially important. Please orient
yourself on the system diagram for
the selected system.
2
3
4
5
6
7
8
9
10
11
12
not for heat pumps with heating meters
not for heat pumps with heating meters
not for heat pumps with heating meters
not for heat pumps with heating meters
Heating/cooling version, single energy-source mode, 1 supplemental electric heating,
Bivalence point -5°C
Heating/cooling version, single energy-source mode, 1 supplemental electric heating, solar system,
bivalence point -5°C
not for heat pumps with heating meters
not for heat pumps with heating meters
Heating/cooling version, bivalent mode, bivalence point -3°C
Heating/cooling version, bivalent mode, solar system, bivalence point -3°C
Heating/cooling version, bivalent mode with solid fuel + option for 1 supplemental electric heating,
bivalence point -3°C
NOTE
Heating circuit 2 and hot water are recognised by the connected sensor. The relevant menus are hidden if
no sensor is connected.
The systems 2, 3, 4, 5, 8 and 9 were programmed for the equipment type CMF 80/140 and cannot therefore be selected for heat pumps with heating meters!
46
Basic hydraulics "System selection 1"
is loaded with reset specialist
Functions: Heating and hot water,
monoenergetic operating mode
Indoor unit
CMF
Heating circuit 1
Heating circuit 2
2)
F9
Outdoor unit
A6
A8
V
V
A9
F11
F17
II
0
I
B
AB
A3
A
F8
Heating/cooling
water
Storage tank
A1
KPS 300
Process hot water
tankEWS 300
F6
A12
F5
A2
1)
1)
A4/A5
M
Taps
CW input
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
DesignationValue rangeProgramming
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1201
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2200
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOff
Functions: Heating or cooling and hot water
monoenergetic operating mode
“System selection 6”
A1
Tmax
Heating circuit 1
1)
A12
l/h
Outdoor unit
Indoor unit
CMF
F9
A6
A8
V
V
A9
F11
F17
II
0
I
B
AB
A3
A
F8
Heating/cooling
water
Storage tank
KPS 300
F6
Process water
Storage tank
HPS 500
Heating circuit 2
F5
A2
1)
A4/A5
M
Taps
2)3)
Cooling circuit
A10
CW inlet
Fresh water station
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
3) Cooling is activated over heating circuit 2 (mixer circuit). If cooled with a separate cooling circuit,
menu item "T-supply cooling" must be set to "Closed".
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1206
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
WE 1 level 1 = 50
Output/level00 – 9950 kW
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 60 2
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K( ---- )
MF 4 Hyst Off2 K - 1 0 K( ---- )
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
48
Hydraulic diagram for heat pump assembly WP 12
Functions: Heating or cooling and hot water
monoenergetic operating mode
“System selection 6”
F9
Outdoor unit
F17
II
0
I
A
A6
B
Surface heating /
1)
Surface cooling
F5
A2
M
Heating circuit 1
A1
V
V
F8
F11
Process hot water
water tank
2)
1)
A4/A5
EWS 300
AB
F6
Taps
A12
Indoor unit
CMT 120/160
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
The cooling must be activated via heating circuit 2 by setting T-supply cooling to the desired cooling target supply temperature.
DesignationValue rangeFactory setting
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1206
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
Output/level00 – 9950 kW
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 60 2
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K( ---- )
MF 4 Hyst Off2 K - 1 0 K( ---- )
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
WE 1 level 1 = 50
WE 3 level 1 = 1
49
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 11
Functions: Heating or cooling, solar and hot water
monoenergetic operating mode
“System selection 7”
F14
Outdoor unit
A
Indoor unit
CMF 120/160
F9
A8
V
V
A9
F11
F17
II
0
I
A3
AB
B
Multi-function
Storage tank
MPS 1000
A
A3
AB
B
F6
F8
F12
Tmax
Fresh water station
Heating circuit
F5
Taps
3)
l/h
A2
CW inlet
2)
1)
A4/A5
M
Cooling circuit
B
A6
AB
A12
A10
A
Coolant
Storage tank
KPS 300
r
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
4) The cooling must be activated via heating circuit 1 by setting T-supply cooling to the desired cooling target supply temperature.
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1207
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
Output/level00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 62 3
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K5.0K
MF 4 Hyst Off2 K - 1 0 K2.0 K
F15 function0 0 - 0 909
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
4)
A10
50
Hydraulic diagram for heat pump assembly WP 12
Functions: Heating or surface cooling and process hot water
single energy source operating mode, solar thermal process water support
"System selection 7"
F9
Collector surface:
max. 3-4 m
Outdoor unit
2!
F14
V
V
F17
F8
F11
II
0
I
A
AB
A6
B
Process hot
water tank
EWS 300
F6
Heating circuit 1
A1
1)
Taps
A12
Surface heating /
Surface cooling
F5
A2
1)
A4/A5
M
2)
Indoor unit
CMT 120/160
A12
F12
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
The cooling must be activated via heating circuit 2 by setting T-supply cooling to the desired cooling target supply temperature.
3) If a circulation pump is installed, it must be controlled separately.
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
DesignationValue rangeProgramming
WE 1 level 1 = 50
Output/level00 – 9950 kW
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1207
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 62 3
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K5.0 K
MF 4 Hyst Off2 K - 1 0 K2.0 K
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
WE 3 level 1 = 1
51
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 9
Functions: Heating or cooling and hot water,
bivalent operating mode with boiler
“System selection 10”
Indoor unit
CMF 120/160
F9
A9
Outdoor unit
A6
Oil fired boiler
V
V
F11
F17
II
0
I
Gas/
A8
A8
Heating circuit 1
M
AB
A
B
A3
F8
Heating/cooling
water
Storage tank
KPS 300
F6
Process water
Storage tank
PS 500
A1
1)
Tmax
A12
l/h
Heating circuit 2
F5
A2
1)
A4/A5
M
Taps
2)3)
Cooling circuit
A10
CW inlet
Fresh water station
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
3) Cooling is activated over heating circuit 2 (mixer circuit). If cooled with a separate cooling circuit,
menu item "T-supply cooling" must be set to "Closed".
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1210
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
Output/level00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 70 0
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 602
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K( ---- )
MF 4 Hyst Off2 K - 1 0 K( ---- )
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
52
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating, hot water and solar
bi-fuel operating mode with gas wall mounted heater
“System selection 11”
Indoor unit
CMF 120/160
F9
F14
V
V
A9
Outdoor unit
A6
F11
F17
II
0
I
Gas wall mounted
A12
heater.
AB
A8
A
A3
AB
B
Multi-function
Storage tank
MPS 1000
A
A3
B
F6
Tmax
F8
Fresh water station
F12
3)
Taps
l/h
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
Heating circuit
F5
A2
1)
A4/A5
M
2)
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1211
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
Output/level00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 62 3
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K5.0K
MF 4 Hyst Off2 K - 1 0 K2.0 K
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
53
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating, hot water and solar
bivalent operating mode with boiler
“System selection 11”
Indoor unit
CMF 120/160
F9
F14
Outdoor unit
Oil fired boiler
A8
V
V
A9
F11
F17
II
0
I
Gas/
A8
M
A
A3
AB
B
Multi-function
Storage tank
F6
Tmax
MPS 1000
A
A3
AB
B
F8
F12
Fresh water station
Heating circuit
F5
A2
3)
Taps
l/h
2)
1)
A4/A5
M
CW inlet
A6
A12
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1211
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
Output/level00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 737
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 62 3
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K5.0K
MF 4 Hyst Off2 K - 1 0 K2.0 K
F15 function0 0 - 0 909
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
54
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating and hot water
single energy source operating mode and solid fuel boiler
“System selection 12”
F14
Indoor unit
CMF 120/160
Outdoor unit
F9
TH2
A6
A8
V
V
A9
F11
F17
II
0
I
A12
Solid fuel
boiler
AB
AB
Heating circuit
F5
A2
1)
A
A3
B
Multi-function
Storage tank
MPS 1000
A
A3
B
F6
Tmax
Taps
3)
l/h
F8
F1
Fresh water station
CW inlet
A4/A5
M
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solid fuel boiler, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
DesignationValue rangeProgramming
BUS code BMOff, 00-15Off
LanguageD/GB/F/NL/E/ID (German)
Terminal addressOn / OffOn
Time0-24 Set time
DateYear, month, daySet date
BUS code 100-1501
BUS code 200-1502
System selection---/01-1212
Regulator type00-0606
WE 1 type00-0907
WE BUS00-0505
GradientOn / OffOff
WE 2 type00-2208
WE 2 tank00-0300
WE 3 type00-0901
WE 4 type00-0900
Buffer type00-0200
Cooling modeOff/OnOn
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 functionsee HC1Standard
DesignationValue rangeProgramming
Output/level00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function0 0 - 3 70 0
T - MF 1 target - 2 0 °C - 9 0 °C( ---- )
MF 1 Hyst2 K - 1 0 K( ---- )
MF 1 Hyst Off2 K - 1 0 K( ---- )
MF 2 function0 0 - 3 618
T - MF 2 target - 2 0 °C - 9 0 °C( ---- )
MF 2 Hyst2 K - 1 0 K( ---- )
MF 2 Hyst Off2 K - 1 0 K( ---- )
MF 3 function0 0 - 3 63 4
T - MF 3 target - 2 0 °C - 9 0 °C( ---- )
MF 3 Hyst2 K - 1 0 K( ---- )
MF 3 Hyst Off2 K - 1 0 K( ---- )
MF 4 function0 0 - 3 62 2
T - MF 4 target - 2 0 °C - 9 0 °C( ---- )
MF 4 Hyst2 K - 1 0 K50
MF 4 Hyst Off2 K - 1 0 K10
F15 function0 0 - 0 90 9
E 1 function0 0 - 0 30 2
E 2 function0 0 - 0 30 3
Sensor1k/5k sensors5k sensors
55
REMKO Heat Pump Manager
Contact layout Merlin I/O circuit board (solder side view)
Remko specific contact layout for the circuit board inputs
TerminalSensor no.DescriptionNote
1F9External sensor
2F8
3F6Hot water sensor
4F5Supply sensor HC 2 (mixer circuit)
5F3not assigned
6F2not assigned
7F1not assigned
8F11Supply sensor WP or HC 1HC 1 is a direct heating circuit
9F12Sensor storage tank bottomReference sensor solar or solid-fuel boiler
10F13Sensor solid fuel boilerPt 1000
11F14Sensor solar collectorPt 1000
12F15Flow volume sensorImpulse input
13F17Return sensor (cooling control sensor)
14eBUS +Signal output 0-10 VModulation depth (target output in %)
15eBus -Signal output 0-10 VModulation depth (target output in %)
16CAN-Bus H
17CAN-Bus L
18CAN-Bus -
19CAN-Bus +
Collector sensor (collective supply)
Heating control sensor
Heating control sensor. Must be located in accordance with the
system diagram!
is found as set in the factory in the indoor unit. Depending on the
selected (hydraulic) system, the sensor may have to be mounted
at a different position
NOTE
Please also note the connection diagrams or the electrical circuit diagrams for the installed heat pump.
These are found in the respective installation manual.
56
Troubleshooting and customer service
Fault numbers appear in the
controller display if your heating
system malfunctions.
There are three types of reports:
1. Info:
Information and descriptions
"Display" heat generation.
2. W 051
Warning: Maintenance required
"Maintenance"
3. Info 055
Information: Heat pump
lock "WP lock"
The meanings of the displayed
error codes can be taken from the
table on the next page.
The system should be restarted
after the fault has been corrected
=> RESET.
RESET : Brief shut-off or the equipment (mains switch). Controller
starts again, configures itself again
and continues to work with the
already set values (fault messages for defective sensors may no
longer appear => corresponding
functions may be deactivated).
General troubleshooting information
If the system does not operate correctly, first check the cabling in the
controller and controller components.
Sensor
At the level "General/ Service/
Sensor test", all sensors can be
checked. All of the connected
sensors have to appear here with
plausible measured values.
Actuators (mixers, pumps => only
with code number)
At the level "General/ Service/
Sensor test", all actuators can be
checked. All relays can be switched
individually at this level. This
enables the correct connection of
these components (e.g. direction
of rotation of the mixers) to be
easily checked.
BUS - connection
In controllers with connection to
mixers => display of the communication icon in the standard
display (depending on the design "
" or "v") or under "Service/communication MM 1“ WE controller => display of the outdoor and
WE temperature (see "Displays/
system") or in the boiler control if
connected to the controller => display of the room temperature and
hiding of the current room target
temperature "----" (see "Displays/
heating circuit") in the mixer expansion controller if connected to
the boiler controller => display of
the outdoor and WE temperature
(see "Displays/system") controller
=> display of the room temperature and the hiding of the current
room target temperature "----"
(see Displays/heating circuit")
RESET of settings:
Overwriting settings with standard
values can be carried out separately at the "Service level" for the
"user" and "specialist" parameters and the "time programme"
respectively.
57
REMKO Heat Pump Manager
The equipment and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the
list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have
been performed!
Malfunctions
FaultPossible causeChecksRemedial measures
Communications fault
Pumps do not switch off
Pumps fail to switch on
Bus and sensor wiring were
laid together
Switched polesCheck poles
To little voltage at the
BUS plug
Operating mode
Settings misaligned
Operating mode
Time and heating programme
pump switching
Outdoor temperature and
room target temperature
Heating limits or
Room control misaligned
Check connection cables
Check voltage
Check operating mode and
settings
Operating mode
Time and heating programme
pump switching
Outdoor temperature and
room target temperature
Heating limits or
Check room control
Bus wiring and sensor wiring
must be separated spatially
from mains wiring.
Check poles
There must be at least 8V DC
between the BUS plug's "+"
and "-" terminals [terminals
18+19]. If too little voltage is
measured, an external supply
must be installed.
Type of pump switching at the
specialist level heating circuit
Check operating mode =>
standard.
Check time and heating programme => heating period
Check pump switching =>
type of pump switching
Standard => outdoor temperature > room target temperature?
Heating limits => outdoor
temperature > valid heating
limit?
Room controller => room
temperature > target temperature + 1K
Additional tests via the
controller's relay test function.
58
Fault indicated by code
Only the fault with the highest priority is displayed.
- The message "Fault" appears in the standard display and the fault number in the favourites line.
The fault can be rotated out of view and rotated back into view in the display => see favourites.
- The current fault can always be found at the end of the display level "Display".
DisplayFault description
Heat pump fault The flow monitor has tripped. A flow problem has occurred. Possible causes are air in the
E 54
E 69Failure or short in supply sensor HC2 (mixing circuit). Sensor F5
E 70Break or short in supply sensor HC1 (direct heating circuit). Multi-purpose sensor 1 Sensor F11
E 71Failure or short in lower buffer sensor Sensor F12
E 72Failure or short in upper buffer sensor No assignment by REMKO
E 75Failure or short, external sensor Sensor F9
E 76Failure or short, domestic water sensor Sensor F6
E 78Failure or short, collector sensor Sensor F8
E 80Failure or short, room sensor heating circuit 1. No assignment by REMKO
system, a clogged dirt trap or a defect of the charging pump in the indoor module. If the red indicator lamp
illuminates, there is a problem in the outdoor module which can only be remedied through customer service.
E 81EEPROM error. The invalid value has been replaced by the default value. Check parameter values!
E 83Failure or short, room sensor heating circuit 2. No assignment by REMKO
E 84Fault humidity, sensor No assignment by REMKO
E 90Address 0 and 1 on bus. Bus codes 0 and 1 may not be used simultaneously.
E 91Bus code assigned. The set bus code is already being used by another device.
E 135Failure or short, lower WW buffer sensor, multifunction sensor 2. No assignment by REMKO
E 136 Break of short sensor heating appliance 2, collector sensor 2, multifunction sensor 3. Not used by REMKO
E 137Break or short collector sensor 1, multifunction sensor 4. Not used by REMKO
E 140Break or short return line sensor control sensor cooling-mode. Sensor F17
E 200 - E 207Communication heating appliance 1 to WE 7
E 220 - E 253Communication BM 0 to BM 15
E 240Communication Manager
E 241Communication (individual) heating appliances
E 242Communication mixer
E 243Communication Solar
Info 51 Information: Maintenance necessary. Customer service is also displayed.
Heat pump fault Flow monitor responded or an outdoor-module defect, but only if the red indicator light
Info 55
Info 55 Information: Heat pump cut off
also illuminates. If the red indicator light does not illuminate: check the circulation pump or the flow.
There is a possibility of air in the pump or heating circuit
Protection category in accordance with EN 60529IP40
Protection classin accordance with EN 60730 Part III
The clocks power reserveHr.> 10
permitted ambient temperature in the workplace°C0 - +50
permitted ambient temperature in storage°C- 20 - +60
permitted humidity, non-condensingr.H.%95
Humidistat
Tolerance of the temperature sensor shunt NTC 5 k+/-1% at 25°C or +/- 0.2K at 25°
Tolerance of the temperature sensor Pt 1000?+/-0.2% at 0°C
60
+/-5% relative humidity at 25°C and 60%
air humidity room sensor
Notes
Notes
REMKO INTERNATIONAL
… and also right in your neighbourhood!
Make use of our experience and advice
Consulting
Thanks to intensive training, our
consultants are always completely up-to-date in terms of
technical knowledge. This has
given us the reputation of being
more than just an excellent, reliable supplier:
REMKO, a partner helping you
find solutions to your problems.
Distribution
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highlyqualified sales specialists.
REMKO field staff are more than
just sales representatives: above
all, they must act as advisers to
our customers in air conditioning
and heating technology.
REMKO GmbH & Co. KG
Air conditioning and heating technology
Customer Service
Our equipment operates precisely and reliably. However, in
the event of a fault, REMKO
customer service is quickly at
the scene. Our comprehensive
network of experienced dealers
always guarantees quick and
reliable service.
Im Seelenkamp 12 D-32791 Lage
Postbox 1827 D-32777 Lage
Telephone +49 52 32 6 06-0
Fax +49 5232 606-260
Email info@remko.de
Website www.remko.de
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.