REMKO Multi-talent Plus User Manual

REMKO
WITH HEAT FLOW VOLUMEMETER
HEAT PUMP MANAGER MULTI-TALENT PLUS
Manual for experienced specialists
Edition GB – W05
Contents
Safety notes
Environmental protection and recycling
Warranty
Transport and packaging
Intended use
Function
Heating curves
Commissioning
Menu structure / menu navigation
System selection / hydraulic diagram
Merlin I/O circuit board contact layout
Troubleshooting and customer service
Sensor values / characteristic curve
4
4
4
4
4
5
6
7
8-45
46-55
56
57-59
60
Technical data
60
Made by REMKO
before commissioning / using this device!
These instructions are an integral part of the system and must always
be kept near or on the device. This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO Heat Pump Manager
Safety notes
Read the operating instructions carefully before commissioning the equipment. They provide useful tips and information as well as warnings to prevent endangering persons and property . Failure to follow the directions in this man­ual can result in endangerment to persons, the environment and the equipment itself and will void any claims for liability.
Keep this manual close to the
equipment.
Modification of equipment and
components supplied by REM­KO is not permitted and can cause malfunctions.
Operating equipment
or components with obvious defects or damage is not permit­ted.
Repairs may only be carried out
by authorised personnel, while cleaning may be carried out by the operating company.
The equipment or components
are not to be exposed to any mechanical stresses, extreme levels of humidity or direct sunlight.
Environmental protection and recycling
Disposal of packaging
All products are packed for trans­port in environmentally compat­ible materials. To avoid waste and sustain raw materials, dispose of packaging only at appropriate col­lection points.
Disposal of equipment and
components
The equipment and com-
ponents have been manu­factured from recyclable materials only. Help protect the environment by ensuring that the equipment or components (for example bat­teries) are not disposed of with household waste but in an envi­ronmentally acceptable manner in accordance with applicable regulations, e.g. using authorised disposal and recycling specialists or municipal collection points.
Warranty
A prerequisite for any warranty claims is that the enclosed "war­ranty registration card" was com­pletely filled out and returned to REMKO GmbH & Co. KG by the buyer or his agent immediately fol­lowing purchase or commissioning. The warranty conditions are listed in the "General terms and condi­tions". Special agreements can furthermore only be agreed be­tween the contract partners. Please contact your contract partner directly about this.
Transport and packaging
The equipment is shipped in sturdy transport packaging. Please inspect the equipment immediately upon delivery. Note any damage or miss­ing parts on the delivery note and inform the forwarding agent and your contract partner. Warranty claims at a later date will not be accepted.
Intended use
Depending on the model, the equipment and the additional fittings with which it is equipped is only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed room. Different or additional use shall not be classed as intended use. The manufacturer/supplier assumes no liability for damages arising from an unintended use of the equipment. The user bears the sole risk in such cases. Using the equipment as intended also includes working in accord­ance with the operating manual and installation instructions and complying with the maintenance requirements.
4
Function
It is the function of the Multi­talent heat pump manager to operate and effectively manage the entire warm water pump system including any additionally installed heating appliances. The multitude of functions provided by the heat pump manager must be configured in accordance with the existing heating system. This manual provides both installation instructions and a overview of what actually lies behind the heat pump manager's configuration pa­rameters. The following functions are displayed in the heat pump manager:
• Heat pump operation
• Weather managed regulation
of a direct heating circuit and a mixing circuit (e.g.: floor heating)
• Hot-water heating
• Cooling
• Solar function
• Demand oriented circulation
pump switching
• Automatic summer/ winter time change
• Individually configurable reduction times and holiday operation for heating circuits and hot-water
• Cascade modulating heating appliance
• Cascade switching heating ap­pliance
• Bivalence regulator
tion depth in % as a function of the difference between the current flow temperature and the target temperature. The modulation depth reflects the system's target output in %, for example the heat output made necessary by the cur­rent outdoor temperature.
T
< T
SUPPLY ACTUAL
SUPPLY TARGET
100
98
80
Modulation depth [%]
WP modulating ON
WP 100% +2. WE, if Ta < bivalence point
120
100
80
60
40
Modulation depth [%]
20
0
0 1 2 3 4 5 6 7 8 9 10
0-10 V - signal output
The modulation depth is converted to a 0-10 V signal and made avail­able to the heat pump's outdoor unit for further processing.
T
> T
T
SUPPLY ACTUAL
> T
SUPPLY TARGET
T
SUPPLY ACTUAL
WP modulating ON
2. WE OFF
< T
SUPPLY ACTUAL
SUPPLY TARGET
WP OFF
SUPPLY TARGET
+ 2K
Control principles
Using an outdoor temperature sensor and the selected heating curve, the heat pump manager continuously establishes the target flow temperature and compares this temperature with the current system flow temperature (T col­lection sensor F8). The heat pump manager calculates the modula-
120
100
80
60
40
Modulation depth [%]
20
Level
0
0 1,88 3,13 4,38 5,63 6,88 8,13 9,38 10
Level
0
Level
1
2
Level
3
0-10 V - signal
Level
Level
4
Level
5
6
Level
8
7
7
6
5
4
3
2
1
0
5
REMKO Heat Pump Manager
Heating curves
The heating curve is used for the purpose of assigning the building and appropriate target supply tem­perature in accordance with the outdoor temperature. The heating curves 0.2 to 0.8 have their base point at 20°C and are intended for surface heating. The heating
curves 1 to 3 have their base point at 27°C are therefore appropriate for radiator heating (steel radia­tors). The heating curve is easiest to set at outdoor temperatures below 5 °C. Changing the heating curve setting must be carried out in small steps and in larger time
intervals (at least 5 to 6 hours), because the system must first ad­just to the new values after every change in the heating curve.
Target supply temperature in °C
Outdoor temperature in °C
6
Commissioning
The Multitalent heat pump man­ager serves to operate and control the entire plant. The heat pump manager itself is operated by the control unit. The control console is connected to the basic device and is located behind the flap on the indoor module.
C
B
! CAUTION
After a power failure etc., the previously programmed configuration can be accepted immediately by pressing the F-button next to
End.
This also happens automatically after a delay of 10 minutes.
System 1 is pre-installed at the factory. After a reset of the heat-pump manager, the parameters for System 1 are loaded.
Carry out a thorough visual inspection before the actual commissioning process.
Switch the supply voltage back on.
The following screen appears on the Multitalent display.
the parameters that go with it (see the hydraulic schematic in the heat-pump manager handbook).
The system has to be matched to the customer's personal val­ues (e.g. inlet temperature).
The brief instructions supplied give an overview of how to set the most important values.
■ After configuration, the system is to be run-in and the meas­ured values are to be recorded in the commissioning report.
NOTE
The commissioning and pro­gramming of the heat-pump manager may only be carried out by a mechanic authorised by REMKO.
A
The remote control used to regu­late the heat pump manager is operated with the following keys.
The rotary knob (A) can be used to:
- move between the displayed menu items ­change setting values
Home
Pressing the Home but­ton (B) always returns you to the standard display.
Each of the four function keys (C) stands for one of the four rows on the dis­play. Press one of these function keys to select a menu item or setting value.
End
Installation
OK
■ Determine which system diagram is to be used (see the hydraulic diagram in the heat­pump manager manual).
If the System 1 schematic is applicable, you need only press the F-button next to End . Should a different system schematic be selected, press the F-button next to OK to begin installation.
The configuration in the installation level for the selected hydraulics has to be completely programmed with
NOTE
Please review the heat-pump manager manual for impor­tant details about successful commissioning.
NOTE
During commissioning, only a typical heat-manager default setting can be carried out. Individual settings must be op­timised for construction materi­als and the practices of various users. Especially during the first heating period.
7
REMKO Heat Pump Manager
Functions heat flow meters
The Multitalent heat pump manager PLUS is equipped with the following displays relevant for the heat flow meters:
Display level
The displays relevant to the heat flow meters are called up with the following steps on the heat pump manager.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C T-collector 36.2 °C
Heating
Home
Level 1
Main menu
End01
Terminal Controller
Specialist level
The heat pump menu is found in the specialist level. The param­eters for the heat flow meters are configured here.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C T-collector 36.2 °C Heating
Home
Level 1
Main menu
End01
Terminal Controller
Including in display of favourites
As many as 10 display values can be copied to level 0. The system operator can quickly access these "favourites" for control purposes without involving himself with the heat pump manager. The possible heat flow meter displays included in the favourite menu are shown in the following section.
Level 0
Fr 23 Apr 10 16:05
T-external 19.0 °C T-collector 36.2 °C Heating
Level 2
Controller
End01
Display
User Time programme
Level 3
Display
End01
Plant
Hot water Heating circuit 1
Level 4
Plant
End07
Flow volume 28 l/min Current output 8070 W Output day 30.2 kWh
Level 4 (continued)
Plant
End07
Output day 30.2 kWh Output total 99 kWh Error 00
Level 2
Controller
End04
Time-Date Service
Specialist
Level 3
Specialist
End02
Heating appliance Cascade
Heat pump
Level 4 (continued)
Heat pump
End05
E1 function 02 E2 function 03 E15 function 09
Level 4
Heat pump
End12
Impulse rate 1 Impulse unit l/Imp Min FlowVol 12.0 l/min
Level 0
Fr 23 Apr 10 16:05
Current output 8070 W T-collector 36.2 °C Heating
Level 0
Fr 23 Apr 10 16:05
Output day 30.2 kWh T-collector 36.2 °C Heating
Level 0
Fr 23 Apr 10 16:05
Output total 99 kWh T-collector 36.2 °C Heating
8
Menu structure / menu navigation
Level 1 Level 2 Level 3Level 0
Mo
T-external T-collector Automatic 1
08:3030 Mar 09
15.3 °C
36.2 °C
Home
Main menu
End01
Terminal
Controller
Controller
Display
User Time programme
End01
Display
Plant Hot water Heating circuit 1 Heating circuit 2 Solar / MF
End01
Current operating mode (Mode)
- Automatic 1
- Automatic 2
- Heating
- Cooling
- Standby
- Reduction
Controller
Display
User
Time programme
Controller
Display User
Time programme
Controller
Time-Date
Service Specialist
End01
End01
End04
User
End01
Plant Hot water
Heating circuit 1 Heating circuit 2
Time programme
End01
Heating circuit 1 prog 1 Heating circuit 1 prog 2 Heating circuit 2 prog 1 Heating circuit 2 prog 2 Hot water Circulation program WE 1 enable WE 2 enable WE 3 enable WE 4 enable S-Kick enable PU night enable
Time-Date
End01
Time Date Holiday start Holiday end Summer time setting start Summer time setting end
Controller
Time-Date
Service
Specialist
Controller
Time-Date Service
Specialist
Service
End04
End04
Relay test Sensor test Software number Manual cascade operation Burner running-time Burner starts STB test Customer service Reset user Reset specialist Reset time programme Communication BM 1 Communication BM 2 Communication KM
Specialist
Conguration
Heating appliance Cascade Heat pump Cooling mode 0-10V I/O Screed Hot water Heating circuit 1 Heating circuit 2 Solar / MF
End01
End01
9
REMKO Heat Pump Manager
Level 4
DISPLAY
Plant
01
T-external T-collector T-WE WE status T-return total T-tank 3 Modgrad
Volumetric ow
Output current Output day Output total Error
USER
Plant
Operating mode Language LCD contrast LCD brightness °C/°F
End
End01
Hot water
End01
T-WW T-WW U WW demand WW pump WW enable Circulation pump
Hot water
End01
1 x hot water T-WW 1 target T-WW 2 target T-WW 3 target BoB value Circ with WW prog
Anti-legionella
Heating circuit 1
End01
T-room T-supply Heating circuit enable Heating circuit pump B-warm up-time
Heating circuit 1
End01
Operating mode T-room target 1 T-room target 2 T-room target 3 T-reduction T-absent T-room cooling T-external cooling Heating threshold day Heating threshold night heating curve T-supply const T T-supply const N Room impact Heating curve adaptation
Warm up opt Max warm up-time Reduction opt
PC enable
Heating circuit 2
End01
T-room T-supply Heating circuit enable Heating circuit pump B-warm up-time
Heating circuit 2
End01
Operating mode T-room target 1 T-room target 2 T-room target 3 T-reduction
T-absent T-room cooling T-external cooling Heating threshold day Heating threshold night heating curve
T-supply const T T-supply const N Room impact Heating curve adaptation
Warm up opt Max warm up-time Reduction opt
PC enable
Solar / MF
End01
MF 1 MF 2 T-MF 3 MF 3 MF 4 T-solar 1 T-WW T-WW U Solar pump 1 Load Sp WW
SPECIALIST
Conguration
Terminal address Regulator address BUS code 1 BUS code 2 eBUS supply System selection Regulator type WE 1 type WE BUS WE 2 type WE 2 tank WE 3 type WE 4 type Buffer type Cooling mode F 15 function E 1 function E 2 function Sensor
10
End01
Heating appliance
End01
Max T-collector Min T-collector Min T-WE 2 Hysteresis Hysteresis period Sequence change Clock inhibition Hyst burner 2 Gradient Max reduction Dyn shut-off WE cooling function T-WE cold start
Cascade
End01
WE found Output/level BUS scan min mod cascade WW-WE System deviation Output target Remaining idle time Max T-WE WE Dyn up WE Dyn down Reset time Modgrad on Modgrad off Min modgrad Modgrad WW WE sequence 1 WE sequence 2 Sequence mode Sequence change Clock inhibition
Heat pump
End01
Max T-return Min T-return WP Max TA WE Min TA WP E1 function E2 function F15 function Return offset Min T-WW Min T-PU WE Max WE idle time Impulse rate Impulse unit Min FlowVol
Cooling mode
T-RL cooling Cooling off at WW
Cooling with WP
End01
Level 4 - continued
SPECIALIST - continued
0-10V I/O
End01
SPG curve Curve 11 U 1 Curve 11 U 2 Curve 11 T 1 Curve 11 T 2 Curve 11 U A
Solar / MF
End01
MF 1 function MF 2 function MF 3 function MF 4 function MF 4 Hyst MF 4 Hyst Off Max T-supply Min T-solar on Min T-solar off T-solar protection Re-cooling difference Max T-SP WW Max T-SP PU Max T-SP 3 Solar kick duration Solar kick interval Solar kick gradient
Screed
End01
Screed Screed programme
Hot water
End01
Charge pump lock PPL T-WE WW Hysteresis WW WW lag TH inlet Thermal function Charging
Heating circuit 1
HC function Operation HCP Max T-supply Min T-supply T-supply cooling T-frost protection
T-external delay
End01
Heating circuit 2
End01
HC function Operation HCP Mixer Open Mixer CLOSED Max T-supply Min T-supply T-supply cooling T-frost protection T-external delay Curve displacement Demand requirement
11
REMKO Heat Pump Manager
Level 4 - DISPLAY - Description of parameters and settings
DISPLAY
Plant
01
T-external T-collector T-WE WE status T-return total T-tank 3 Modgrad
Volumetric ow
Output current Output day Output total Error
End
Hot water
T-WW T-WW U WW demand WW pump WW enable Circulation pump
End01
Heating circuit 1
End01
T-room T-supply Heating circuit enable Heating circuit pump B-warm up-time
Heating circuit 2
End01
T-room T-supply Heating circuit enable Heating circuit pump B-warm up-time
Solar / MF
End01
MF 1 MF 2 T-MF 3 MF 3 MF 4 T-solar 1 T-WW T-WW U Solar pump 1 Load Sp WW
Display of system values
Values cannot be changed in the display section. There is a display only if the respective sensor is connected or the value exists in the system. If the setting does not exist, it is either hidden or dashes (----) are shown in the display. Factory settings can vary depending on the system.
Plant
Designation Description
T-external Current outdoor temperature [sensor 09] (smoothed value).
Current collector temperature [sensor 8] and (collector) target temperature Display following pressing of
T-collector
the respective function key. The target corresponds with the highest temperature demanded in the load circuits (incl. water heating).
T-WE Current temperature of all connected heating appliances [sensor 08].
WE status Heating appliance's status (on / off).
Current return temperature for the start of the cooling machines (see specialist cooling mode
T-return total
T-RL cooling) and for the shut-off of the heat pumps (see specialist heat pump Max T-return WP, return offset) [sensor 17].
T-tank 3 Current temperature of the tank 3/buffer tank bottom [sensor 01]. No assignment by REMKO
Modgrad Current target modulation depths for all active WE and required modulation depth.
Volumetric flow Display of the current flow volume (flow) in l/min
Output current Display of the current heating/cooling output in W
Output day
Output total
Error
Display of the amount of heat delivered in kWh during the previous day. The value updates itself auto­matically at 0:00 (midnight)
Display of the amount of heat delivered since commissioning (cumulative). The meter reading is updated every day at 0:00 (midnight) by the amount of the day's output.
Error number (00 = no errors).
12
Level 4 - DISPLAY - Description of parameters and settings - continued
Hot water
Designation Description
T-WW
T-WW U Current temperature of the buffer tank bottom [sensor 12] (e.g. systems with a solid fuel boiler)
WW demand Status of heat demand hot water (on/off).
WW pump Status of the hot water charge pump (on/off / 3-way switch valve.
WW enable Enable water heating (on/off).
Current hot water temperature and hot water target temperature (see user hot water T-WW target). [sensor 06]
Circulation pump
Circulation pump status (on/off).
Heating circuit 1/2
Designation Description
T-supply
Heating circuit enable Heating circuit in heating mode (on/off).
Heating circuit pump Heating circuit pump status (on/off).
B-warm up-time
Current supply temperature [sensors 05/08] and supply target temperature following pressing of the respective function key.
Last required warm up-time with active warm up optimisation.
Solar / MF
Designation Description
MF 1 Status of the relay MF 1 (on/off) outlet A8 - 2nd heating appliance.
MF 2 Status of the relay MF 2 (on/off) outlet A9 - charge pump indoor unit.
T-MF 3 Current temperature of the MF 3 sensor [sensor 13] - solid fuel boiler.
MF 3 Status of the relay MF 3 (on/off) outlet A10 - 3-way switch valve cooling / MP cooling
MF 4 Status of the relay MF 4 (on/off) outlet A12 - solar.
T-solar 1 Current collector temperature 1 [sensor 14].
T-WW Current hot water temperature and hot water target temperature [sensor 6].
T-WW U Current temperature of the buffer tank bottom [sensor 12] (e.g. systems with a solid fuel boiler).
Solar pump 1 Status of the collector pump 1 (on/off).
Load Sp WW
Status of the tank charge pump 1 (on/off) not used by REMKO.
13
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings
USER
Plant
End01
Operating mode Language LCD contrast LCD brightness °C/°F
Hot water
1 x hot water T-WW 1 target T-WW 2 target T-WW 3 target BoB value
Circ with WW prog
Anti-legionella
End01
Heating circuit 1
End01
Operating mode T-room target 1 T-room target 2 T-room target 3 T-reduction T-absent T-room cooling T-external cooling Heating threshold day Heating threshold night heating curve T-supply const T T-supply const N Room impact Heating curve adaptation
Warm up opt Max warm up-time Reduction opt
PC enable
Summary of settings that can be set by the system operator.
Plant
Designation Value range Factory setting Description
Setting the operating mode / the operating mode for the system.
Heating circuit 2
End01
Operating mode T-room target 1 T-room target 2 T-room target 3 T-reduction T-absent T-room cooling T-external cooling Heating threshold day Heating threshold night heating curve T-supply const T T-supply const N Room impact Heating curve adaptation
Warm up opt Max warm up-time Reduction opt
PC enable
•Standby (heating OFF, water heating OFF, only frost protection).
•Cooling (heating OFF, only water heating, activation of the cooling machines, regulation of the heating circuits to T-supply cooling).
•Automatic 1+2 (heating in accordance with the heating programme 1/2, WW in accordance with WW­programme).
Operating mode / Operating mode
Standby
Cooling
Automatic 1+2
Summer
Heating
Standby
Reduction
Service
•Summer (heating OFF, WW in accordance with WW- programme).
•Heating (regulation to T-room target).
•Reduction (regulation to T-reduction).
•Service (regulation to max T-WE, automatic reset after
15 min. in the previous operating mode).
Language D/GB/F/NL/E/I English Setting the language for the controller.
LCD contrast 00-06 04 Setting the display intensity.
LCD brightness 00-30 30 Setting the display lighting brightness.
°C/°F
Celsius
Fahrenheit
Celsius Setting the temperature unit.
14
Level 4 - USER - Description of parameters and settings - continued
Hot water
Designation Value range Factory setting Description
The tank is only enabled for a one time loading (= ON) (e.g. for showering outside of hot water times).
1xhot water On/Off Off
T-WW 1 target 10°C-70°C 50°C
T-WW 2 target 10°C-70°C 50°C
T-WW 3 target 10°C-70°C 50°C
Loading begins if the T-WW 1 target temperature has been undercut in the amount of the switching hysteresis (see spe­cialist hot water hysteresis WW).
Setting the desired hot water temperatures for the hot water programme's 1st, 2nd and 3rd enabling times (see time programme hot water).
Power saving function for solar or solid fuel boiler (operation without burner).
BoB value 0.0K-70.0K 0.0K
Circ with WW prog On/Off Off
Anti-legionella On/Off Off
The burner is activated if the current hot water temperature in the amount of the set value here + switching hysteresis (see specialist hot water hysteresis WW) has fallen below the set hot water target temperature.
Activating the circulation pump.
The circulation pump runs when hot water is enabled (= ON), the circulation programme (see time programme
circulation programme) has no impact.
Activating the anti-legionella function.
With every 20th heating or at least once a week (on Saturdays at 01:00) the tank is warmed to 65°C (= ON).
It is possible to set a separate anti-legionella function e.g. by means of the 3rd hot water enabling time (see time programme hot water). Be submitted to activation of anti-legionella program must usually electric heating thermostat to 65 °C.
Heating circuit 1/2
Adjustable values can vary depending on the function selected for the heating circuit.
Designation Value range Factory setting Description
Setting the operating mode for the respective heating circuit.
Operating mode
----
Standby
Automatic 1+2
Summer Heating
Reduction
----
! CAUTION
If an operating mode is set here outside of "----", this operating mode will always apply for the respective heating circuit regardless of the operating mode setting in the main menu. (see page 7). This setting possibility is intended for the use of a remote control.
T-room target 1 5.0°C-40.0°C 20.0°C
T-room target 2 5.0°C-40.0°C 20.0°C
T-room target 3 5.0°C-40.0°C 20.0°C
T-reduction
5.0°C-40.0°C 15.0°C
Setting the desired room temperature for the 1st, 2nd and 3rd enable time of the active heating programme for the selected heating circuit.
Setting the desired room temperature during night reduction (time between heating periods, see time programme heating circuit 1/2 prog 1/2).
15
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
Designation Value range Factory setting Description
T-absent 5.0°C-40.0°C 15.0°C
T-room cooling
T-external cooling 0.0℃-40.0°C 20.0°C
----/20.0°C-40.0°C 25.0°C
Setting the desired room temperature during holiday reduction (time away) (see Time-Date holiday start / end).
Setting the desired room temperature in cooling mode for the selected heating circuit.
The cooling operation is activated if the temperature set here is exceeded and ends if this temperature is undercut by 2K. Only in connection with a remote control. With the value "----", the cooling operation is independent of the room temperature.
Furthermore, the cooling operation must be enabled by T-external cooling.
The cooling operation is enabled and activated if the outdoor temperature exceeds the value set here and ends if this temperature is undercut by 1K.
Heating threshold day
Heating threshold night
----/-5.0°C-4 0.0°C
----/-5.0℃-40.0°C 10.0°C
19.0°C
The operating mode heating threshold for the the heating circuit pump must be activated (see specialist heating circuit 1/2 operation HCP).
Setting the heating threshold.
If the outdoor temperature measured and determined by the controller exceeds the heating threshold set here, the heating will lock, the pumps shut off and the mixers close.
The heating will be enabled again if the outdoor temperature undercuts the set heating threshold by 1K.
•Heating threshold day (operates during heating periods).
•Heating threshold night (operates during reduction periods).
At "----", the heating threshold is deactivated and the circulation pump will be switched in accordance with the standard function.
The curve's slope indicates by how many degrees the supply temperature will change if the outdoor temperature rises or falls by 1°C.
If during cold outdoor temperatures the room temperature is too low (too high), the heating curve must be raised (lowered).
heating curve
16
0,00-3,00 0,60
If during high outdoor temperatures the room temperature is too low, the room temperature must be corrected by means of the room target temperature (parallel adjustment of the heating curve).
At "0.00", room regulation is active.
Changing the heating curve must be carried out in small steps and in larger time intervals (at least 5 to 6 hours), because the system must first adjust to the new values after every change in the heating curve.
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
Designation Value range Factory setting Description
The T-supply const function must be activated (see specialist
T-supply const T 10°C-110°C 35.0°C
T-supply const N
Room impact
10°C-110°C 10.0°C
Off
00-20
Off
heating circuit 1/2 HC function).
Setting the desired supply temperature with which the selected heating circuit is operated during the heating period.
The T-supply const function must be activated (see specialist
heating circuit 1/2 HC function).
Setting the desired supply temperature with which the selected heating circuit is operated during the reduction period.
Only in the absence of an analogue room device (FBR).
The WE temperature is increased in the amount of the value set here if the desired room temperature (T-room target) is undercut by 1K (room sensor impact).
Automatic regulation of the heating curve (Heating curve adaptation).
Start-up requirements:
•Outdoortemperature<8°C
•Operatingmodeisautomatic1/2
•Durationofthereductionphaseatleast6hours
Heating curve ad­aptation
Warm up opt
On/Off Off
Off
T-room
T-external
Off
The current room temperature is measured at the beginning of the reduction period. This temperature is applied in the following 4 hours as the target value for the room regulation. The heating curve is calculated from the values captured in this time period by the regulator for the supply and outdoor temperatures.
The setting remains on until the adaptation has been completed successfully and was not interrupted (e.g. by a demand for hot water from an external heating circuit).
The controller's water heating and the warm up optimisation are blocked during the adaptation.
Automatic bringing forward of the heating period start (warm up optimisation).
Dependent on the weather (T-external) or the current room temperature (T-room, only in the absence of an analogue room device (FBR), heating is started up early enough so that at the beginning of the set heating period, the temperature in the living area (see time programme
heating circuit 1/2 prog 1/2) just reaches the set room
target temperature (T-room target).
The warm up optimisation is only carried out if the reduction time for the heating circuit is at least 6 hours.
17
REMKO Heat Pump Manager
Level 4 - USER - Description of parameters and settings - continued
Heating circuit 1/2-continued
Designation Value range Factory setting Description
Max warm up-time 00:00-03:00 02:00
Reduction opt
00:00-03:00 00:00
Setting the time by which the heating start should as a maximum be brought forward (maximum bringing forward).
Automatic optimisation of the stopping of the burner at the end of the set heating period.
During the time period set here before the end of the heating period (only for the last heating period) (see time programme heating circuit 1/2 prog 1/2) the burner is no longer started if it is not already in operation (prevents short-term warming up of the WE at the end of the heating period).
PC enable
0000-9999 0000 Code number to allow access to the heating circuit data via PC.
18
Level 4 - TIME PROGRAMME - Description of parameters and settings
All time programmes can be set here.
Factory setting
Designation
Heating circuit 1 prog 1
Day Time
Mo.-Fr.
Mo.-Su.
Sa.+Su.
06:00-22:00 06:00-22:00 07:00-23:00
Operating mode / description
Automatic 1
Heating circuit 1 prog 2
Heating circuit 2 prog 1
Heating circuit 2 prog 2
Hot water
Circulation pro­gram
WE 1-4 enable
S-Kick enable
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Fr.
Mo.-Su.
Sa.+Su.
Mo.-Su. 07:00-22:00
06:00-08:00, 16:00-22:00 06:00-08:00, 16:00-22:00
07:00-23:00
06:00-22:00 06:00-22:00 07:00-23:00
06:00-08:00, 16:00-22:00 06:00-08:00, 16:00-22:00
07:00-23:00
05:00-21:00 05:00-21:00 06:00-22:00
05:00-21:00 05:00-21:00 06:00-22:00
00:00-24:00 00:00-24:00 00:00-24:00
Automatic 2
Automatic 1
Automatic 2
Automatic 1+2
Automatic 1+2
The heating appliances can only be put into operation in the enabled times set here. (A demand for heat from a user or tank must also exist for a heating appliance to operate).
Enable time for the solar kick functions (see specialist solar MF).
PU night charging Mo.-Su. 00:00-05:00
Conventional heat pumps are blocked during the enable time set here. In this time period, the buffer tank is only warmed by the heat pump to the set temperature (see specialist
heat pump Min T-PU WE).
PU night charging should not be enabled in the heating and hot water time periods.
19
REMKO Heat Pump Manager
Level 4 - TIME-DATE - Description of parameters and settings
Various values are summarised here for the user to provide quick access.
Designation Factory setting Description
The controller's time display (The time can only be set using Terminal Time).
Time
Date The controller's date display (The date can only be set using Terminal Date).
Holiday start Off Setting the first holiday (no more heating beginning from this day).
Holiday end Off Setting the last holiday (there will be no more heating until this day).
Summer time setting start
Summer time setting end
If a controller was set as Time Master for the heating system (time standard for all controllers), entering the time in the system's other controllers is blocked. (As a maximum, only one Time Master can be set at the BUS).
The automatic switch from summer time to winter time is made possible with the input of the date.
The earliest date on which switchover takes place is to be set. The controller carries out the time switch on the Sunday following the set date at 02:00 or 03:00 in the morning.
20
Level 4 - SERVICE - Description of parameters and settings
Various values are summarised here in order toe enable quick access for customer service. The input of the code number is necessary for some functions. The relay test and sensor test are automatically reset after 1 minute!
Sensor test no. Sensor no.
01 Buffer tank temperature bottom
02 Buffer tank temperature middle (or room temperature Heating circuit 1)
03 Buffer tank temperature top
04 not used
05 F5 X3.16 Supply temperature heating circuit 2 (mixer circuit)
06 F6 X3.15 Hot water temperature top (process water tank)
07 not used
08 F8 X3.14 Collector temperature (collective supply temperature sensor)
09 F9 X3.13 Outdoor temperature
10 not used
11 F11 X3.12
12 F12 X3.11 Hot water temperature bottom (reference sensor for solar regulation)
REMKO Sensor designa­tion
Terminal layout in the indoor unit
Description
For CMF 80/90/140/150 and CMT 100/150:
Supply temperature heating circuit 1 (direct heating circuit) or
for CMF/CMT 120 and CMF/CMT 160:
Supply temperature heat pump
13 F13 X3.10 not yet used (solid material WE temperature (PT1000))
14 F14 X3.9
15 F15 X3.8 Flow meter
16 not used
17 F17 X3.7 Return temperature sensor
Collector temperature solar system (special control characteristic (PT 1000))
21
REMKO Heat Pump Manager
Level 4 - SERVICE - Description of parameters and settings - continued
Relay test
Select the desired relay using the rotary knob at the service level (01-11) The selected relay is switched on for 1 minute and all other relays are switched off.
Please note that the input of the code number is required for this function. The relay test breaks off automatically after 5 minutes if no further operation takes place.
Relays Output Description
00 Normal operation => relays switch in accordance with the regulating function
01 A1 Circulation pump heating circuit 1 (direct heating circuit) on
02 A2 Circulation pump heating circuit 2 (mixer circuit) on
03 A3 Switch valve/charge pump process water
04 A4 Mixer heating circuit 2 open
05 A5 Mixer heating circuit 2 closed
06 A6 Enable heat pump on (charge pump run parallel)
For CMF/CMT 120/160: Enable cooling
07 A7
08 A8 Enable 2nd heating appliance (multi-function 1-output)
09 A9 Charge pump inside unit (multi-function 2-output)
10 A10
12 A12
For CMF 80/140: 2. Heating appliance on For CMF 90/150 and CMT100/150 circulation pump cooling on
For CMF 80/90: Condenser pump For CMF/CMT 120/160, CMF 90/150, CMT 100/150: Switch valve cooling (multi-function 3-output)
Circulation pump or solar pump or charge pump UP-solid fuel boiler (Multi-function 4-output)
Additional entries
Designation Description
Software number Display of the software number with index.
Only for cascades; the operating mode Service must be activated.
Manual cascade operation
Burner running-time Display of the heating appliance running time for all levels.
Burner starts Display of the heating appliance starts for all levels.
Setting the heating appliance's output (For a switching, multi-level WE, the second level can be switched on with a performance target of > 50%). Inputs are automatically reset when the Service function is ended.
STB test Safety temperature limiter test with display of the temperature for the WE. (Start with the F-key)
Input of the date for the annual maintenance reminder (at Year = "00" no reminder) or input of the
Customer service
Reset user
Reset time programme
Communication BM 1 Remote control HC 1 at the BUS.
Communication BM 2 Remote control HC 2 at the BUS.
Communication KM
22
running time for the system after which a maintenance reminder should generate (for running time < "50" no reminder).
Respective areas can be reset to the factory setting using the reset function (factory setting = "01").Reset specialist
Communication with expansion module (for additional heating circuits).
Level 4 - SPECIALIST - Description of parameters and settings
SPECIALIST
Conguration
Terminal address BUS code 1 BUS code 2 eBUS supply System selection Regulator type WE 1 type WE BUS WE 2 type WE 2 tank WE 3 type WE 4 type Buffer type Cooling mode F 15 function E 1 function E 2 function Sensor
End01
End01
Max T-collector Min T-collector Min T-WE 2 Hysteresis Hysteresis period Sequence change Clock inhibition Hyst burner 2 Gradient Max reduction Dyn shut-off WE cooling function T-WE cold start
Heating appliance
Cascade
End01
WE found Output/level BUS scan min mod cascade WW-WE System deviation Output target Remaining idle time Max T-WE WE Dyn up WE Dyn down Reset time Modgrad on Modgrad off
Heat pump
End01
Max T-return Min T-return WP Max TA WE Min TA WP E1 function E2 function F15 function Return offset Min T-WW Min T-PU WE Max WE idle time Impulse rate Impulse unit Min FlowVol
Cooling mode
T-RL cooling Cooling off at WW
Cooling with WP
End01
Min modgrad Modgrad WW WE sequence 1 WE sequence 2 Sequence mode Sequence change Clock inhibition
SPECIALIST - continued
0-10V I/O
End01
SPG curve Curve 11 U 1 Curve 11 U 2 Curve 11 T 1 Curve 11 T 2 Curve 11 U A
Solar / MF
End01
MF 1 function MF 2 function MF 3 function MF 4 function MF 4 Hyst MF 4 Hyst Off Max T-supply Min T-solar on Min T-solar off T-solar protection Re-cooling difference Max T-SP WW Max T-SP PU Max T-SP 3 Solar kick duration Solar kick interval Solar kick gradient
Screed
End01
Screed Screed programme
Hot water
End01
Charge pump lock PPL T-WE WW Hysteresis WW WW lag TH inlet Thermal function Charging
Heating circuit 1
HC function Operation HCP Max T-supply Min T-supply T-supply cooling T-frost protection
T-external delay
End01
Heating circuit 2
End01
HC function Operation HCP Mixer Open Mixer CLOSED Max T-supply Min T-supply T-supply cooling T-frost protection T-external delay Curve displacement Demand requirement
23
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Changing of the set specialist values is not possible until the code number has been input because setting the values incorrectly can lead to malfunctions and damage to the system.
Configuration
Designation Value range Factory setting Description
The BM-T is a terminal (input device). If there are
Terminal address On/Off On
BUS code 1
BUS code 2
00-15 01
00-15 02
more than one terminal at the BUS, each must be given a different terminal address.
Heating circuits are numbered in sequence begin­ning with "01" (heating circuit number); the same number may not be assigned more than once.
Heating circuits are numbered in sequence begin­ning with "01" (heating circuit number); the same number may not be assigned more than once.
24
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
Designation Value range Factory setting Description
eBUS supply On/Off Off
Activating the eBUS supply in accordance with the con­nected devices.
With this setting, additional values at the configuration level can be brought forward (selecting the basic functions). The display value here is always "00".
•01 = Basic hydraulics for the functions “Heating and hot water”, single energy-source mode, 1 supplemental electric heating, bivalence point -5°C
•02 = only heating version, single energy-source mode, 2 levels for supplemental electric heating, bivalence point -5°C.
•03 = only heating version, bivalent mode, boiler + option for 1 supplemental electric heating, bivalence point -3°C.
•04 = only heating version, bivalent mode, solid fuel boiler + option for supplemental electric Supplemental heating, bivalence point -3°C.
•05 = only heating version, single energy-source mode, 1 supplemental electric heating, solar system, bivalence point -5°C.
System selection
Regulator type 00-06 06
----/01-12 01
•06 = only heating/cooling version, single energy-source mode, 1 supplemental electric heating, bivalence point -5°C.
•07 = only heating/cooling version, single energy-source mode, 1 supplemental electric heating, solar system, bivalence point -5°C.
•08 = only heating version, single energy-source mode, 2 levels for supplemental electric heating, solar system, bivalence point -5°C.
•09 = only heating version, bivalent mode + option for 1 supplemental electric heating, solar system, bivalence point -3°C.
•10 = only heating/cooling version, bivalent mode, bivalence point -3°C
•11 = heating/cooling version, bivalent mode, solar system, bivalence point -3°C
•12 = heating/cooling version, bivalent mode with solid fuel + option for 1 supplemental electric heating, bivalence point -3°C
There is no change for "----".
Setting the regulation type for the system.
•00 = No heating appliance (mixer expansion).
•01 = Single stage WE (switching).
•02 = Single stage (modulating).
•03 = Two stage WE (switching).
•04 = Two individual WE (switching).
•05 = Multi-level switching (cascade over BUS).
•06 = Multi-level modulating (cascade over BUS).
WE 1 type (Output A6 enable or demand heat pump)
00-09 07
•00 = Relay has no function.
•01 = Switch on WE.
•07 = Switch on heat pump.
•08 = Switch on cooling 1.
•09 = Switch on cooling 2.
25
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
Designation Value range Factory setting Description
•00 = Relay (switching WE).
•01 = CAN-BUS (cascade switching).
•02 = eBUS (WE without temperature controller, default
modulation depth, cascade modulating).
•03 = eBUS (WE with temperature controller, default target
WE BUS 00-05 05
temperature T-WE target).
•04 = 0-10V (default target temperature T-WE target, burner relays are controlled in parallel). Only for regulation type 01, 02, 03, 07. Sensor 08 must be connected.
•05 = 0-10V (default modulation depth). Only for regulation type 02 or 06.
WE 2 type (Output A7 enable cooling)
WE 2 tank
00-22 08
00-03 00
Not active for WE 1 with two stage burner.
•00 = no second WE.
•01 = Single stage WE (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
•20 = Solid fuel boiler (supplemental not controllable WE).
•21 = Collector pump
•22 = Pump for WE 1 (e.g. supplemental WE for cascades).
Only active if WE 2 type as solid fuel boiler was selected.
Start-up release: ON: T-WE 2 > Min T-WE 2. OFF: T-WE 2 < [Min T-WE 2-5K].
•00 = Heating in countercurrent with collector (no tank) [sensor 08]. ON: T-WE 2 > [T-collector+Hyst burner 2+5K]. OFF: T-WE 2 < [T-collector+Hyst burner 2].
•01 = Heating in countercurrent with buffer tank [sensors 01, 03]. ON: T-WE 2 > [T-buffer O+Hyst burner 2+5K]. OFF: T-WE 2 < [T-buffer+Hyst burner 2].
26
•02 = Heating in countercurrent with WW tank [sensor 06]. ON: T-WE 2 > [T-WW+Hyst burner 2+5K]. OFF: T-WE 2 > [T-WW+Hyst burner 2].
•03 = Heating in countercurrent with tank 3 (swimming pool) [sensor 15]. ON: T-WE 2 > [T-tank 3+Hyst burner 2+5K]. OFF: T-WE 2 < [T-tank 3+Hyst burner 2].
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
Designation Value range Factory setting Description
Switching characteristics:
The pump switches on if the temperature of the solid fuel boiler T-WE 2 exceeds the temperature of the reference sen­sor [sensor 12] in the amount of the hysteresis [Hyst burner 2+5K]. It shuts off if the temperature T-WE 2 falls below this
WE 2 tank (continued)
00-03 00
switch on temperature by 5K,
Start-up release:
It shuts off if the temperature for the solid fuel boiler T-WE 2 falls below the temperature limit Min T-WE 2 (see specialist heat-
ing appliance) by 5K. The pump is enabled again if the tempera- ture T-WE 2 rises above the set temperature limit Min T-WE 2.
•00 = No third heating appliance (multi-function MF 1).
WE 3 type (Output A8 enable 2nd heating appliance)
WE 4 type (Output A9 Charging pump indoor unit)
Buffer type
00-09 01
00-09 00
0 0 - 0 2 0 0
•01 = Single stage heating appliance (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
•00 = No fourth heating appliance (multi-function MF 2).
•01 = Single stage WE (switching).
•07 = Heat pump.
•08 = Cooling 1.
•09 = Cooling 2.
Setting the tank type for the heating buffer.
•00 = no buffer tank for heating operation.
•01 = Buffer tank for heating operation [sensors 02, 03].
The activation of the WE 1 takes place with reference to sensor buffer top [sensor 03]. The charge pump lock impacts the sensor Buffer top. WW-charge pump ON: Buffer top > T-WW+5K hysteresis. WW-charge pump ON: Buffer top < T-WW.
•02 = Combination tank for heating and hot water operation. The activation of the WE 1 takes place with reference to sensor buffer middle [sensor 02]. WW-charge pump ON: T-collector > T-WW+5K hysteresis. WW-charge pump ON: T-collector < T-WW.
27
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
Designation Value range Factory setting Description
Cooling mode On/Off On Enabling the operating mode cooling and the required settings.
Setting the sensor function for sensor 15.
•00 = Room sensor for heating circuit 2. If in this position an additional sensor is recognised at the impulse input (IMP = sensor 17), an FBR at sensors 15 and 17 will be analysed. If sensor 17 is occupied by another function, an RFB will be analysed at sensor 15.
•01 = 0-10V input for default of an external collector target temperature.
•02 = Light sensor (no function).
•03 = 0-10V input for default of an external modulation depth.
•04 = Second sensor for MF - function.
•05 = Tank 3 (e.g. swimming pool).
F15 function
00-09 09
•06 = Sequence/priority switching (e.g. for sequence heat pumps - conventional heating appliances). Open contact: WE sequence 1 is active. Short circuit against ground: WE sequence 2 is active.
•07 = Locking the heat pumps (e.g. energy supply provider contact). Open contact: Heat pumps are enabled. Short circuit against ground: Heat pumps are locked and the mes­sage "energy supply provide shut-off" appears in the display.
•08 = Collective fault heat pumps. Open contact: Heat pumps are enabled. Short circuit against ground: Fault in all heat pumps (fault message, locking of the heat pumps and the corresponding WE-pumps following termination of the pump run-on).
E1 function Signal processing (Energy supply provider disable/ enable)
E2 function Signal processing Collective fault out­door unit and flow monitor
28
00-03 02
00-03 03
•09 = Configuration of the F15-input for a flow volume sensor (impulse sensor). Important in order to activate the heating meter function.
•00 = No function.
•01 = Sequence/priority switching (e.g. for sequence heat
pumps – conventional heating appliances). 230V at E1/E2: WE sequence 1 is active. No phase at E1/E2: WE sequence 2 is active.
•02 = Locking the heat pumps (e.g. energy supply provider contact). 230V at E1/E2: Heat pumps are enabled. No phase at E1/E2: Heat pumps are locked and the message "WP lock" appears in the display.
•03 = Collective fault heat pumps. 230V at E1/E2: Heat pumps are enabled. No phase at E1/E2: Fault in all heat pumps (fault message, locking of the heat pumps and the corresponding WE­pumps following termination of the pump run-on). "Fault heat pump" appears in the display.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Configuration - continued
Designation Value range Factory setting Description
Sensor
1k/5k sensors 5k sensors Setting the existing resistance for the connected sensor.
Heating appliance
Designation Value range Factory setting Description
Max T-collector 30.0°C-110.0°C 70.0°C
Setting the maximum collector temperature [sensor 8] (col­lective supply temperature).
Min T-collector
Min T-WE 2 0.0°C-80.0°C 0.0°C
Hysteresis 2.0K-20.0K 2.0K
Hysteresis period 00 Min.-30 Min. 00 Min. Setting the hysteresis period.
Sequence change 00 h-800 h 00 h
0.0°C-80.0°C 0.0°C
Setting the minimum collector temperature [sensor 8] (col­lective supply temperature).
Setting the desired minimum temperature for the WE 2.
Reduces condensate formation in the WE if demand for heat is low. Shut-off of the WE takes place in all cases at the earli­est when the minimum temperature+hysteresis set here is reached.
Function optimisation of the WE operation at variously heavy demands on the heating appliance.
The effective switching hysteresis is reduced linearly from the set hysteresis to the minimum hysteresis in the hysteresis period following switching on of the burner (= 2.0K).
At low heat transfers the higher hysteresis setting is effective (short runtimes and frequent synchronising of the burner are prevented).
For longer burner operation (high heating loads) the hyster­esis is automatically reduced to 5K (Preheating the heating appliance to unnecessarily high temperatures is avoided).
Setting the desired operating hours for the first WE in the active sequence, but the active sequence with which the WE-sequence should switch (time until the sequence change).
When operating with at least 2 WE, there is the possibility to switch the WE sequence in accordance with the operating hours set here.
Clock inhibition
00 Min.-120 Min. 00 Min.
There is no switch at "00 h".
Setting the minimum wait time following switching on of the WE or for a switching WE, also for switching off of a stage until switching on of the next stage
(Idle time for the next stage).
At "00 min" the clock inhibition is 10 sec.
29
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating appliances - continued
Designation Value range Factory setting Description
Only for two stage burners or solid material integration.
Hyst burner 2 2.0K-20.0K 2.0K
Gradient
Max reduction 1.0K-20.0K 1.0K
On/Off Off
Setting the hysteresis for the charge pump (solid material integration) or the 2nd burner
Activating the gradient process (only for WE 1)
When heat transfer is low, the heating appliance will be shut off early (e.g. burnout in a pellet boiler).
At "OFF", the shut-off is carried out by the target value and the hysteresis.
Setting the value for the determination of the earliest shut­off point (only for WE 1).
The earliest shut-off point is the difference between the maximum heating appliance temperature Max T-WE (see specialist cascade) and the value set here.
Load dependent, early shut-off of the WE by the the tem­perature increase gradients [K/min].
Dyn shut-off
WE cooling function On/Off Off Activating the emergency cooling for the WE.
T-WE cold start
0.5K/min.-10K/ min.
30.0°C-120.0°C 95.0°C
2.0K/min.
If the WE reaches or exceeds the gradient set here, the WE will be switched off at the earliest dynamic shut-off point (difference between Max T-WE and Max reduction).
At a low temperature increase, the shut-off point will be in­creased linearly up to Max T-WE.
Setting the maximum temperature for the heating appliance (Cooling start temperature).
If emergency cooling for the heating appliance has been ac­tivated (WE cooling function = ON), the heating circuits will then be taken with Max T-supply (see specialist heating circuit 1/2) into operation (if emergency cooling is permitted in the heating circuit), as soon as the temperature set here has been ex­ceeded by one of the heating appliances.
Emergency cooling is ended if the start temperature T-WE cold start is undercut by 5K.
30
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade
Designation Value range Factory setting Description
Display of the heating appliance automatically logged by the
WE found 1-3---/x-x--- 1-3/x-x
Output/level
BUS scan On/Off Off
WE 1-WE 8 WE internal
WE 1 level 1 = 50 WE 2 level 1 = 01 WE 3 level 1 = 01
BUS with BUS identifier (WE-number).
The displayed "x" indicates that the heating appliance has answered the BUS.
Display of the WE-number and level.
For "---" the level for the WE does not exist.
Following a restart or new configuration, the controller searches in the BUS systems for heating appliances. In this period (approx. 1 min.) the output cannot yet be entered manually. If a heating appliance answers indicating the output, this output will automatically be entered in the list. If a WE answers without indicating the output, the output is entered in the list with 15KW. (this value can then be corrected manually).
Search for heating appliances in the BUS.
If the displayed configuration is correct, it can be saved with "OK". All current values are then overwritten.
Min. Mod Cascade 00-100 % 00 %
WW-WE 00-08 00
System deviation
Output target 0-100 %
Remaining idle time Remainder (min.)
Max T-WE
50.0°C-110.0°C 72.0°C
If the cascade controller calculates a total modulation depth greater than nil and smaller than Min. Mod Cascade, total modulation depth will set to the value set here (minimum modulation depth). At the same time, clock inhibition will be set to 10 sec.
Water heating by means of collector (00).
The Number of WEs in the cascade which for water heating are hydraulically decoupled from the cascade (01-08).
Display of the current collector system deviation (difference between target temperature and current temperature [sensor 08]).
Display of the currently required total system output (corresponds with the calculated target value in the controller).
Display of the currently remaining idle time (not until "0" can the next WE be put into operation).
Setting the maximum heating appliance temperature.
The WEs shut off/modulate themselves down independently if they have not reached the temperature set here (protects the cascade's individual WEs against overheating and prevents the STB from triggering).
The WEs switch on again if the set temperature is undercut by 5K.
The temperature set here should be higher than the maximum collector temperature Max T-collector
(see specialist heating appliances).
31
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade - continued
Designation Value range Factory setting Description
Setting the value for the connection of all WE-levels (WE-connection dynamic [K]).
If the cumulative system deviation in Kelvin reaches the
WE Dyn up 20-500 350
WE Dyn down 20-500 20
value set here, this effects the connection of all WE-levels (the smaller the value, the faster the connection).
Values that are too small can lead to overheating or to a short-term connection of a WE.
Setting the value for the shut-off of all WEs (WE-shut-off dynamic).
If the cumulative system deviation in Kelvin reaches the value set here, this effects the shut-off of all WEs (the smaller the value, the faster the shut-off).
Values that are too large can lead to overheating and triggering of the STB.
Reset time 05-500 30
Modgrad on 0 %-100 % 100 %
Modgrad off 0 %-100 % 80 %
Min modgrad 0 %-100 % 00 %
Modgrad WW
40 %-100 % 100 %
Setting of the reset time for the I-controller.
Small values lead to fast controller response and can lead to vibrations.
Adjusting this value can lead to overshooting the controller.
Setting the modulation depth at which the next WE in the sequence should be connected.
The connection can take place at the end of the remaining idle time.
Setting the modulation depth at which the last WE in the current sequence should be shut off.
Setting the modulation depth at which the next WE should be connected.
The connection of the next WE only takes place if the result­ing modulation depth for the individual WE following con­nection exceeds the value set here.
For operation with the maximum number of burners, Modgrad On must be set to "00%" and Min. Modgrad must be set to the minimum modulation depth for the WE­levels.
Setting the target modulation depth for the heating appli­ances in hot water mode.
WE sequence 1 1-2-3-4-5-6-7-8
WE sequence 2
32
1-2-3-4-5-6-7-8
1-3-2-4-5-6-7-8
3-1-2-4-5-6-7-8
Setting the sequence in which the heating appliances go into operation at sequence 1.
Setting the sequence in which the heating appliances go into operation at sequence 2 (for two stage WEs, the second stage is always switched after the first stage).
Level 4 - SPECIALIST - Description of parameters and settings - continued
Cascade - continued
Designation Value range Factory setting Description
•OnlyWE sequence 1.
•OnlyWE sequence 2.
•Chronological (switch between sequence 1 and 2 in accord-
WE sequence 1+2
Chronological
Sequence mode
Sequence change 00 h-800 h 00 h See description specialist heating appliances.
1/2 switch
Rotating
Sorting
WE sequence 1
ance with operating hours of the first WE in the active sequence).
•1/2 switch (switch for heating appliances with different nominal output: With the connection of the 2nd WE, the first WE is taken out of operation until the next connection).
•Rotating (the first WE in the sequence is put in the last position in the current sequence at the end of the sequence switch period).
•Sorting (new WE sequence by means of automatic sorting by operating hours for a sequence change).
Clock inhibition
00 Min.-120 Min. 00 Min. See description specialist heating appliances.
Heat pump
For the operation of heat pumps, various protection functions (e.g. return temperature monitoring) and functions for effective operation (monovalence/bivalence mode) are necessary and can be set or activated here (only for the selection WE 1 type = 07 (heat pump) (see specialist configuration)).
Designation Value range Factory setting Description
Setting the system's maximum return temperature [sensor 17].
All of the heat pumps in the system will be shut off once the
Max T-return WP 30.0°C-110.0°C 60.0°C
Min T-return WP 0.0°C-20.0°C 0.0°C
Max TA WE -20.0°C-40.0°C
-5.0°C
or -3.0°C
temperature set here has been reached.
The heat pumps will be switched on again if the return tem­perature has fallen below the value set here by 5K.
Setting the system's minimum return temperature [sensor 17].
All of the heat pumps in the system will be shut off if the temperature set here is undercut.
The heat pumps will be switched on again if the return tem­perature has risen above the value set here by 3K.
Setting the bivalence point.
The 2nd heating appliance will be enabled if the outdoor temperature is colder than this setting.
Min TA WP
-30.0°C-10.0°C -20.0°C
Setting the minimum bivalence point.
If the outdoor temperature falls below the value set here, all heat pumps will be locked and the system will operate only with conventional heating appliances.
33
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heat pump - continued
Designation Value range Factory setting Description
E 1 function 00-03 02
Description see specialist configuration.E 2 function 00-03 03
F 15 function 00-08 07
Setting the return offset temperature.
Return offset -5.0K-15.0K 0.0K
Min T-WW WE 0.0°C-90.0°C 45.0°C
Min T-PU WE 0°C-90°C 0. 0 °C
The heat pumps are not switched off after enabling before the value in sensor 17 [collector target temperature–return offset] has been reached.
Setting the minimum hot water temperature only for heat pump operation.
Only the heat pump works to reach the temperature set here in the WW-tank.
Setting the minimum buffer temperature for heating appliances, not relevant for REMKO.
Until the temperature set here has been reached in the buffer tank [sensor 02], only the heat pump will be operated during the trickle charging.
Setting the maximum idle time for heating appliances (clock protection).
Max WE idle time Off/10-210 min Off
Impulse rate 1 1 Configuration of the flow volume sensor for the heating meter
Impulse unit l/Imp l/Imp Configuration of the flow volume sensor for the heating meter
MinFlowVol
... l/min 12.0 l/min.
When conventional WEs are locked, these are enabled again at the end of the time period set here until the target value in the collector or tank has been reached.
When the flow volume set here is undercut, the heat pump shuts off with a 2 minute delay and a heat pump fault is triggered.
Cooling mode
The chillers are regulated by the return temperature T-return (switching hysteresis 2K).
Designation Value range Factory setting Description
Setting the maximum return temperature in cooling mode.
For a cooling request, the heat pump is switched on if the
T-RL cooling 10.0°C-25.0°C 15.0°C
temperature in the return as set here [sensor 17] is exceeded (operating mode "Cooling" must be active).
The heat pump switches off if the temperature in sensor 17 falls below the temperature set here by 2K.
Cooling Off for WW On/Off On
Cooling with WP
34
00(Off)/01(On) 01
The cooling operation is interrupted with activation of the water heating.
The heat pump shuts off if the signal "WP-lock" or "WP­fault" are present at the inputs F15, E1 or E2 (=01/ON).
Level 4 - SPECIALIST - Description of parameters and settings - continued
0-10V I/O
The outdoor unit is controlled with a 0-10V signal (conversion of the target output or modulation depth). The factory settings for the following parameters may only be carried out in coordination with REMKO's product management!
Designation Value range Factory setting Description
Selection for the voltage curves for the configuration of the
SPG curve 00-11 11
voltage in and output (default voltage curve or the freely adjustable curve 11).
Curve 11-U1
Curve 11-U2 0.0 V-10.0 V 10.0 V
Curve 11-T1
Curve 11-T2 0,0-120,0 100,0
Curve 11-UA
0.0 V-10.0 V 2.0 V
0,0-120,0 10,0
0.0V-10.0 V 0.0 V
An individual curve can be defined with the parameters U1, U2, T1, T2 und UA.
•U = voltage.
•T = temperature.
•UA = heating appliance Off.
Beginning at this voltage, the WE is shut off. UA must lie outside of the valid voltage values.
•U1 and T1 = point 1 on the voltage curve.
•U2 and T2 = point 2 on the voltage curve.
The line between the two limit points defines the voltage curve.
Screed
Designation Value range Factory setting Description
Activating the screed programme (only for mixing circuits).
When started the programme shuts down the set supply temperatures. The integrated mixer circuits regulate in ac­cordance with the set supply temperature. The heat pump makes this temperature available independent of the set operat­ing mode. In the standard display, this is identified with the
Screed On/Off Off
entry "Screed" and the display of the currently valid supply temperature.
The screed programme starts at 00:00 with the set supply temperature from "Day 1" (the start day is not counted) and switches to each subsequent day at 00:00. The current day is identified in the screed programme with an "x".
Following interruption/ending of the function, the controller continues to heat in the currently set operating mode.
Day 1-3: 25°C Day 4-7: 55°C
Screed programme
Day 1-28
10°C-60°C/----
Day 8: 25°C Day 9: 40°C Day 10-19: 55°C Day 20: 40°C Day 21: 25°C Day 22-28: ----
Setting the desired temperatures for the respective days.
The input "----" ends the programme (even during the operation for the following day).
! CAUTION
The screed program may be conducted only in conjunction with the two heat sources. The bivalence is highly enforce, if necessary.
35
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Hot water
Designation Value range Factory setting Description
Activating the 3-way switch valve for process hot water or alternatively a charge pump for process hot water.
The 3-way switch valve only switches if the temperature
Charge pump lock On/Off Off
PartialPriority WW
PPL
On/Off
PPL all
PPL all
[sensor 08] exceeds the tank temperature [sensor 06] by 5K (= ON).
Back to position heating if the temperature of the F-8 sensor falls below the tank temperature. This prevents cooling of the tank at the beginning of the water heating.
•WW (partial priority WW). Heating circuits are locked for water heating. The mixers close and the heating circuit pumps switch off. The mixer circuits are enabled again if the WE reaches the
hot water target temperature (see user hot water T-WW target)+WE target increase (T-WE WE). The mixer circuits lock again if the WE temperature [sensor 08] falls below the enable temperature by the amount of the switching hysteresis (hysteresis WW).
•ON (pump parallel operation). Only the direct heating circuits are locked for water heating. The mixer circuits continue to be heated (the water heating is extended with this function).
•Off (hot water priority mode). Heating circuits are locked for water heating. The mixers close and the heating circuit pumps switch off.
•PPL all (pump parallel operation also for the direct heating circuit). All heating circuits continue to be heated during water heat­ing. If the temperature exceeds the maximum supply tempera-
ture (see specialist heating circuit 1/2 Max T-supply) by 8K, the heating circuit pump for this circuit will shut off (overheating protection). The heating circuit pump switches on again if the tempera­ture falls below the temperature (Max T-supply+5K).
T-WE WW
36
0.0K-50.0K 10.0K
Setting the additive temperature for the heating appliance during water heating (target increase in WW mode).
The target temperature for heating appliances during water heating is arrived at by adding the hot water target
temperature (see user hot water T-WW target) to the temperature set here.
The WE must be operated at an increased temperature during water heating so that the hot water temperature in the tank can be reached over the heat exchanger.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Hot water - continued
Designation Value range Factory setting Description
Setting the hot water hysteresis.
Water heating starts if the temperature in the hot water tank (sensor F-6) falls below the target temperature (see user
Hysteresis WW 3. 0 K - 3 0. 0 K 5. 0 K
WW lag 0 0 - 3 0 0 1
hot water T-WW target) by the temperature set here.
Water heating ends if the tank reaches the set target temperature (in the anti-legionella mode the target temperature is set to
65°C, see user hot water anti-legionella).
Setting the pump lag period.
The pump lag period (5 min.) is extended by the value set here.
The indoor unit's charge pump continues to run for another 5 minutes after the heat pump has been shut off (independent of the period set here). The lag period is interrupted if there is a demand for heat in a heating circuit. An activated charge pump lock can likewise lead to an interruption of the lag function.
TH inlet On / Off Off
Thermal function On / Off Off
Charging
On / Off Off
Activating the water heating by means of thermostat or sensor.
•On (water heating by means of thermostat) In the event of a short circuit, water heating is started at the tank sensor's connection terminals. It ends if the short circuit has been corrected.
•Off (water heating by means of tank sensor).
Activating the aligned target temperature.
The target temperature during water heating is arrived at by adding the current tank temperature [sensor 6] to T-WE WW.
Activating the charging function (only possible with sensor 12 = T-WW U).
Water heating with activation of this function (charging = ON) is not ended until the sensor F 12 (not F 6) has reached the WW target temperature.
37
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2
The parameters for this level change in accordance with the function selected for the heating circuit. Depending on the heating circuit, the values that can be adjusted here can vary.
Designation Value range Factory setting Description
Setting the function for the respective heating circuit.
•Standard (weather managed target temperature regulation using heating curves).
•T-supply const (control in accordance with fixed supply temperatures).
During heating periods (see time programme heating circuit 1/2 prog 1/2) the heating circuit is operated with the set fixed supply temperature T-supply const T, during reduc­tion periods correspondingly with the set fixed supply tem-
perature T-supply const N (see user heating circuit 1/2
T-supply const T/N).
•Swimming pool (swimming pool regulation, only for heat- ing circuit 2).
•WW (hot water circuit). The supply sensor for heating circuit 2 is located in the hot water tank [sensor 05]. The target value for the hot water temperature can be en-
tered under user hot water T-WW target 1/2/3. The heating programme for the heating circuit functions as an enabling programme for the tank. During the reduction period, the tank's target temperature is set to 10°C. The WE controller's hot water priority function can be used
(see specialist hot water PPL).
•Return (return riser above mixer, only for heating circuit 2)
- not relevant for REMKO. The supply sensor for the heating circuit is used as the return sensor for the WE [sensor 11/05]. The mixer regulates 24h based on the heating circuit's set value, Min T-supply.
Installation note:
Mixer Open: The WE's supply is fed into the return (return riser) (circulation must be ensured by the WE). Mixer Closed: Return for the heating circuits is piped.
HC function
Standard
T-supply const
Swimming pool
(HC2)
WW(HC2)
Return(HC2)
Standard
38
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2-continued
Designation Value range Factory setting Description
Setting the operating mode for the pumps.
The circulation pumps are shut off if there is no heating requirement. Mixers are closed at the same time (the heating circuit is shut off).
•Standard (standard circulation pump switching). Room managed regulation (OFF: Room temperature > set room target value + 1K). Weather managed regulation in heating mode (OFF: Outdoor temperature > set room target value). Weather managed regulation in reduction mode (room im­pact = 0; OFF: The switching off takes place during the tran­sition to reduction mode. The pump operates after switching on with ON: Room temperature < room target value; room impact = OFF; OFF: Supply target temperature < 20°C.)
•Heating limits (Pump switching based on heating limits). Heating period (OFF: Outdoor temperature < set heating limit day). Reduction period (OFF: Outdoor temperature < set heating limit night).
•only time prog (Pump switching based on heating pro- gramme). Heating period (ON, heating circuit is free). Reduction period (OFF, heating circuit is locked).
•Continuous operation. The pump runs continuously for 24h. The heating circuit is continuously free.
Operation HCP
Standard
Heating limits
only time prog
Continuous
operation
Standard
Mixer Open 5,0-25,0 7,0
Mixer Closed 5,0-25,0 7,0
Max T-supply
10.0°C-110.0°C 55.0°C
Setting the speed with which the mixer opens in the event of a control deviation (mixer dynamic opening).
The control deviation is entered in Kelvin where the mixer opens without interruption.
Small values lead to fast operation of the mixer and can lead to vibrations.
Setting the speed with which the mixer closes in the event of a control deviation (mixer dynamic closing).
The control deviation is entered in Kelvin where the mixer closes without interruption.
Small values lead to fast operation of the mixer and can lead to vibrations.
Setting the maximum supply temperature for the selected heating circuit.
The calculated supply target temperature for the heating circuit is limited by the set maximum supply temperature (overheating protection).
The heating circuit pump for the direct heating circuit is only switched off if the [sensor 08] exceeds the temperature set here by 8K.
The heating circuit pump switches on again if the temperature [sensor 08] falls below the temperature (Max T-supply+5K).
39
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Heating circuit 1/2-continued
Designation Value range Factory setting Description
Setting the minimum supply temperature for the selected
Min T-supply 10.0°C-110.0°C 18.0°C
T-supply cooling
T-frost protection
Off/Closed 10°C-25°C
Off
-15.0°C-5.0°C 5.0°C
Off
heating circuit.
Setting the supply temperature in cooling mode.
In the operating mode cooling, the temperature set here might possibly be tuned by means of a mixer.
•Off = This heating circuit does not cool (Mixer Closed, pump Off).
•Closed = mixer as bypass valve (mixer Closed, pump On).
Setting the frost protection temperature.
If the outdoor temperature falls below the temperature set here, the system switches into frost protection mode (pumps switch on)
At "Off", the frost protection function is activated.
T-external delay
Curve displacement 0.0K-50.0 K 0.0K
Demand require­ment
00:00-24:00 01:00
On / Off Off
Setting the outdoor temperature delay
The type of outdoor temperature delay selected must take the building design into account. Because a change in outdoor temperature impacts the room temperature later for a building with a heavy design (thick walls), a long delay must be selected. For a light design (in which the walls do not store heat) the delay should be set to 0 hours.
Setting the heating curve distance.
The calculated target temperature for the heating circuit is increased by the value set here.
The heating curve distance equalises sensor tolerances and heat losses up to the mixer.
The heating circuit can be used with superior functions (e.g. emergency cooling of a heating appliance to protect against overheating; heat dissipation in service mode) as a heat sink/consumer (= ON). For the duration of the function, the heating circuit is heated with the maximum set supply temperature Max T-supply.
40
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar / MF
Designation Value range Factory setting Description
Function selection for the MF - relay (programmable multi-
MF 1 function (Output A8 enable 2nd heating appliance)
MF 2 function (Output A9 Charging pump indoor unit)
MF 3 function (Output A10 Switch valve cool­ing)
MF 4 function (Output A12 solar pump or charge pump solid fuel boiler or circulation pump)
00-37 37
00-36 18
00-36 34
00-36 00
function outputs).
A sensor 1-4 (sensors 11-14) can be assigned to the MF­relay 1-4. If an additional sensor is necessary for a specific function, this is to be connected as sensor 15.
•00 = not MF - function.
•01 = collector pump.
ON: In the event of a heat demand from a user. OFF: In the event of no heat demand from a user.
•02 = circulation (time). Switching the relay in accordance with the time programme for the circulation pump.
•03 = supply pump. ON: In the event of a heat demand from an internal user. OFF: In the event of no heat demand from an internal user. A pump lag takes place.
•05 = pump WE 1. The relay can be used to control the charge pump for heat­ing appliance 1 (relay switches to lag = 5 min.).
•06 = pump WE 2. The relay can be used to control the charge pump for heating appliance 2 (relay switches with burner relay; lag = 5 min.).
•07 = switch valve tank 2 (buffer). The valve switches the solar output of the hot water tank to the storage tank if a collector can no longer feed into the hot water tank.
•08 = switch valve tank 3 (swimming pool). The valve switches the solar output of the storage tank to the tank 3 (sensor 15) if a collector can no longer feed into the storage tank (the F15 function must be positioned at 5).
•09 = switch valve tank 3 (swimming pool, only for systems without solar trickle charging). The valve switches the solar output of the hot water tank to tank 3 (sensor 15) if a collector can no longer feed into the hot water tank (the F15 function must be positioned at 5).
•10 = pump WE 3. The relay can be used to control the charge pump for heat­ing appliance 3 (relay switches to lag = 5 min.).
•11 = pump WE 4. The relay can be used to control the charge pump for heat­ing appliance 4 (relay switches to lag = 5 min.).
41
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Descriptions of additional values (12 to 35) for the MF 4 function can be found in the following tables (output A12 solar pump or charge pump solid fuel boiler or circulation pump)
Description
•12 = Remote controlled output heating circuit 1. The relay can be switched via the BUS from the heating circuit's control unit (function see instructions for the re­mote control).
•13 = Remote controlled output heating circuit 2. The relay can be switched via the BUS from the heating circuit's control unit (function see instructions for the re­mote control).
•14 = pump WE 1. The relay can be used to control the charge pump for heating appliance 1 (relay switches to lag = 5 min.). with buffer in the system (buffer > 00 and sensor PU top [sensor 03]): The pump switches on if the temperature of the heating appliance T-WE1 exceeds the temperature of the buffer top [sensor 03] by 5K. The pump switches off if T-WE1 < T-buffer O.
•18 = charge pump indoor unit. In response to a demand from a heating appliance WE 1 to WE 4 (that is a heat pump and any 2nd heating appli­ance), the charge pump indoor unit switches on (parallel mode with 5 min lag). This setting is important in the bivalent-alternative mode if the boiler does not have its own circulation pump.
•20 = temperature controlled circulation pump. T-circ = return temperature in the circulation line. The circulation pump switches on if the return tempera­ture falls below the set limit temperature T-MF 1 target (T-circ < T-MF 1 target). The circulation pump switches off again if the return temperature rises above the set limit temperature by the amount of the hysteresis (T-circ > [T-MF 1 target + MF 1 hyst]). The set circulation programme (see time programme) and the setting circ with WW prog (see user hot water) has priority (switching on takes place only in the enable period).
•21 = circulation pump over impulse. ON: In the event of a short circuit at the assigned sensor input. OFF: After 5 minutes. The circulation pump switches on for 5 min. in the event of a short circuit at the sensor input MF. Activation takes place once on the side. The set circulation programme (see time programme) and the setting circ with WW prog (see user hot water) has priority (switching on takes place only in the enable period).
! CAUTION
The programming or control for the multi-func­tion outputs must be carried out in accordance with the parameters for the selected system! (Basis programming beginning on page 47)
Description
•22 = solid fuel boiler integration (e.g. in connection with a 2-step WE). T-MF 1-4 = temperature in the solid fuel boiler. T-Puffer U = temperature in the storage tank in the area around the infeed [sensor 01].
Start-up relief: The circulation pump switches on if the temperature in the solid fuel boiler rises above the temperature in the storage tank in the area around the infeed T-buffer U by the amount of the hysteresis MF 1 hyst + 5K (T-MF 1 > [T-buffer U + MF 1 hyst + 5K]). It shuts off if the temperature falls below the activation temperature by 5K (T-MF1 < [T-buffer U + MF 1 hyst]).
It also shuts off if the temperature in the sold fuel boiler falls below the set limit temperature T-MF 1 target by 5K (T-MF 1 < [T-MF 1 target-5K]). The pump is enabled again if the temperature in the solid fuel boiler rises above T - MF1 target (T-MF1 > T-MF1 target).
Locking WE1: ON: T-MF 1 > T-WE target + 5K and solid fuel boiler pump = ON. OFF: T-MF 1 <= T-WE target and solid fuel boiler pump = OFF.
•23 = solar pump (pump operates if the collector can feed into one of the solar storage tanks). Collector 1 pump only to MF4. Collector 2 pump only to MF3. This can be used for MF1 and MF2 to charge the tank in a heat exchanger. T-solar = temperature of the solar collector. T-U = temperature of the active tank in the area around the infeed.
The circulation pump switches on if the temperature of the solar collector rises above the temperature of the active tank in the area around the infeed (see switch valve) by the amount of the activation hysteresis MF hyst (T-solar > [T-U + MF hyst]). It shuts off if the temperature of the solar collector falls below the temperature [T-U + MF hyst Off] (T-solar < [T-U + MF hyst Off]).
Before shutting off, it is checked whether the secondary tank (see switch valve) can be charged.
42
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Description
•24 = return riser WE 1. T-return 1 = return temperature from the system (= T-MF 1-4). The return riser pump switches on if the return temperature falls below the set limit temperature T-MF 1 target. (T-return 1 < T-MF 1 target). It switches off again if the return temperature rises above the set limit temperature by the amount of the hysteresis MF 1 hyst (T-return 1 > [T-MF 1 target + MF 1 hyst]).
•25 = return riser WE 2. T-return 2 = return temperature from the system (= T-MF 1-4). The return riser pump switches on if the return temperature falls below the set limit temperature T-MF 1 target. (T-return 2 < T-MF 1 target). It switches off again if the return temperature rises above the set limit temperature by the amount of the hysteresis MF 1 hyst (T-return 2 > [T-MF 1 target + MF 1 hyst]).
•26 = return riser WE via the storage tank. The return risers valve over storage tank opens if the tem­perature storage tank bottom (T-buffer U) rises above the return temperature of the system [sensor 01 or 01-04] by the the amount of the hysteresis MF 1 hyst + 5K (T-buffer U > T-MF 1 + MF 1 hyst + 5K). It switches off again if the temperature storage tank bottom falls below the return temperature (T-buffer U < T-MF 1 + MF 1 hyst).
•27 = tank charge pump 1 (pump operates if the hot water tank can be solar charged). The temperature of the charging medium for the tank is always measured at the MF 4-sensor (T-MF 4). Exception: For function 23 on MF 4, the sensor assigned to the MF-relay tank charge pump 1 for the calculation of the temperature of the medium for the charging of the tank (T-solar) is used. T-solar (T-MF 4) = temperature of the solar collector. T-solar (T-MF 1-3) = temperature of the heat exchanger. T-WW U [sensor 12] = temperature of the hot water tank in the area around the infeed. ON: T-solar > [T-WW U + MF hyst]. OFF: T-solar < [T-WW U + MF hyst Off].
The circulation pump switches on if the temperature of the solar collector rises above the temperature of the tank in the area around the infeed T - WW U by the amount of the hysteresis MF Hyst (T-solar > [T-WW U + MF hyst]). It shuts off if the temperature of the solar collector falls below the temperature T-WW U + MF hyst Off (T-solar < [T-WW U + MF hyst Off]).
Description
•28 = tank charge pump 2 (pump operates if the storage tank can be solar charged and the hot water tank cannot be solar charged). The F15 function must be at the position 5. The temperature of the charging medium for the tank is always measured at the MF 4-sensor (T-MF 4). Exception: For function 23 on MF 4, the sensor assigned to the MF-relay tank charge pump 2 for the calculation of the temperature of the medium for the charging of the tank (T-solar) is used. T-solar (T-MF 4) = temperature of the solar collector. T-buffer U [sensor 01] = temperature in the storage tank in the area around the infeed.
The circulation pump switches on if the temperature of the solar collector rises above the temperature of the tank in the area around the infeed T-buffer U by the amount of the hysteresis (T-solar > [T-buffer U + MF hyst]). It shuts off if the temperature falls below the temperature T-buffer U + MF hyst Off (T-solar < [T-buffer U + MF hyst Off]).
•29 = tank charge pump 3 (pump operates if tank 3 can be solar charged and the storage tank cannot be solar charged). The F15 function must be at the position 5. The temperature of the charging medium for the tank is always measured at the MF 4-sensor (T-MF 4). Exception: For function 23 on MF 4, the sensor assigned to the MF-relay tank charge pump 3 for the calculation of the temperature of the medium for the charging of the tank (T-solar) is used. T-solar (T-MF 4) = temperature of the solar collector. T-tank 3 [sensor 159 = temperature of tank 3 in the area around the infeed.
The circulation pump switches on if the temperature of the solar collector rises above the temperature of the tank in the area around the infeed T-tank 3 by the amount of the hysteresis MF hyst (T-solar > [T-tank 3 + MF hyst]). It shuts off if the temperature falls below the temperature T-tank 3 + MF hyst Off (T-solar < [T-tank 3 + MF hyst Off]).
•30 = Reloading pump WW-tank 2. The F15 function must be at the position 4. The relay switches if the temperature of the hot water tank rises above the temperature sensor 15 by the amount of the hysteresis MF hyst. It shuts off if the temperature of the tank falls below the temperature [sensor 15 + MF hyst Off].
43
REMKO Heat Pump Manager
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - M 4 function - continued
Description
•31 = Reloading pump storage tank 2. The F15 function must be at the position 4. The relay switches if the temperature of the storage tank rises above the temperature sensor 15 by the amount of the hysteresis MF hyst. It shuts off if the temperature falls below the temperature [F15 + MF hyst Off].
•32 = direct heating circuit. Heating circuit with fixed supply temperature (T-MF target). In the event of a short circuit at the assigned MF-sensor (over room thermostat/time switch) the heating circuit pump switches ON and the supply target temperature for the WE is defined. The pump experiences a lag period after the sensor short circuit has been corrected.
Description
•33 = thermostat function. ON: T-MF > T-MF target. OFF: T-MF < [T-MF target-MF hyst].
•34 = bypass valve cooling mode. The relay switches in the cooling mode (Separating the conventional WE from the cooling circuit and water heating is possible during the cooling operation). The MF-sensor captures the supply temperature for the WW-regulation.
•35 = bypass valve cooling mode invers. The relay is switched in the opposite direction to function 34.
•37 = sensor F11 is set as the supply reference sensor (WP- supply sensor) for the heating meter.
Solar/MF - continued
Designation Value range Factory setting Description
MF 4 Hyst 2.0K-10.0K 5.0K Setting the MF 4 hysteresis.
MF 4 Hyst Off 2.0K-10.0K 2.0K Setting the MF 4 hysteresis for the shut-off process.
Setting the maximum collector temperature.
Max T-supply 80.0°C-180.0°C 110.0°C
Min T-solar on -20.0°C-95.0°C 50.0°C
Min T-solar off -15.0°C-95.0°C 45.0°C
T-solar protection 80.0°C-180.0°C 110.0°C
The collector pumps lock if the corresponding collector temperature rises above the temperature set here (system protection).
The pumps are enabled again if the collector temperature falls below the temperature [Max T-solar-10K].
Setting the minimum collector temperature.
The collector pump is enabled if the corresponding collector temperature rises above the temperature set here.
Setting the minimum locking temperature for the collector pump.
The collector pump locks if the corresponding collector temperature falls below the temperature set here. This function prevents the pump from operating without relevant heat output.
Setting the collector protection temperature.
The collector protection function protects the collector against overheating. If the collector temperature exceeds the temperature set here and the tank temperature is less than 92°C, the tank will be charged in excess of its maximum temperature up to 95°C to cool the collector.
44
The function is interrupted if the collector exceeds its maximum temperature.
The function is enabled again if the collector temperature falls below the maximum temperature-3K.
Level 4 - SPECIALIST - Description of parameters and settings - continued
Solar/MF - continued
Designation Value range Factory setting Description
Setting the return cooling difference.
If the collector protection function has charged the tank to temperatures higher than the set maximum tank temperatures during the day, with activation of this
function the tank can be cooled automatically during the Re-cooling differ­ence
Max T-Sp WW
Max T-Sp PU
Max T-Sp 3 10.0°C-130.0°C 30.0°C
0.0K-30.0K 20.0K
10.0°C-130.0°C 85.0°C
10.0°C-130.0°C 85.0°C
night, between 01:00 and 06:00, to the set maximum tank
temperature (Max T-Sp WW/PU/3) by activation of the
charge pumps (charging is not possible in this period).
Return cooling can only take place if the temperature of
the tank rises above the collector temperature at least by
the amount of the return cooling difference set here + 3K
hysteresis.
Setting the safety temperature limits.
If a tank has a top mounted sensor, the maximum
temperature set here will be monitored by this sensor.
If this sensor is not mounted, the maximum tank
temperature will be monitored by the bottom mounted
sensor (In this case the layer arrangement in the tank must
be taken into account).
The charge pumps lock if the heating tank temperature rises
above the safety limit set here (system protection).
The pumps are enabled again if the heating tank
temperature falls below the temperature
[Max T-Sp WW/PU/3-5K).
Solar kick duration 00-59 sec 30 sec. Setting the running time of the collector pump for pump kick.
Setting the solar kick interval.
Solar kick interval
Solar kick gradient
10-60 min. 30 min.
01-05 min 01 min
The pump for the time solar kick duration switches on if the
collector pump has not run for the duration set here.
Setting the solar kick gradients.
In the period set here, the collector temperature progression
following a pump kick is checked.
If there has been an increase of 0.5K, the pump will be
started for another minute.
45
REMKO Heat Pump Manager
System selection
12 basic hydraulic configurations are provided in the heat pump manager which can be pulled up with the system selection and ap­plied in the controller. Pulled up with the system selection and applied in the controller.
The system selection was decided in accordance with the following criteria:
1. by type of heat pump
- only heating series: CMF 80, CMF 140
- Heating/cooling series: CMF 90/150/120/160,
CMT 100/150/120/160
CMF 120/160
System selection
1
Functions
Basic hydraulics for the functions “Heating and hot water”, single energy-source mode, 1 supple­mental electric heating, bivalence point -5°C
2. by operating mode
- single energy source operation (supplemental heating is a supplemental electric heater)
- bivalent mode (supplemental
heating is a boiler)
3. by special case
- integration of solar systems
- integration of solid fuel boilers
The following pages show a selec­tion of these basic hydraulic con­figurations with the corresponding basic programming list.
In any case, during commissioning, assign one of the basic hydraulic configurations via the menu item system selection to the “On-site­system”. Take special care that the system you select is as near as possible to system installed on­site. The location of the sensors is especially important. Please orient yourself on the system diagram for the selected system.
2
3
4
5
6
7
8
9
10
11
12
not for heat pumps with heating meters
not for heat pumps with heating meters
not for heat pumps with heating meters
not for heat pumps with heating meters
Heating/cooling version, single energy-source mode, 1 supplemental electric heating, Bivalence point -5°C
Heating/cooling version, single energy-source mode, 1 supplemental electric heating, solar system, bivalence point -5°C
not for heat pumps with heating meters
not for heat pumps with heating meters
Heating/cooling version, bivalent mode, bivalence point -3°C
Heating/cooling version, bivalent mode, solar system, bivalence point -3°C
Heating/cooling version, bivalent mode with solid fuel + option for 1 supplemental electric heating, bivalence point -3°C
NOTE
Heating circuit 2 and hot water are recognised by the connected sensor. The relevant menus are hidden if no sensor is connected.
The systems 2, 3, 4, 5, 8 and 9 were programmed for the equipment type CMF 80/140 and cannot there­fore be selected for heat pumps with heating meters!
46
Basic hydraulics "System selection 1" is loaded with reset specialist
Functions: Heating and hot water, monoenergetic operating mode
Indoor unit CMF
Heating circuit 1
Heating circuit 2
2)
F9
Outdoor unit
A6
A8
V
V
A9
F11
F17
II 0 I
B
AB
A3
A
F8
Heating/cooling
water
Storage tank
A1
KPS 300
Process hot water tank EWS 300
F6
A12
F5
A2
1)
1)
A4/A5
M
Taps
CW input
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
Designation Value range Programming
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German)
Terminal address On / Off On
Time 0-24 Set time
Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 01
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 00 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On Off
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Output/level 00–9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
continue with key next to "End" MF 1 function 00-37 37 T - MF 1 target -20°C-90°C (----) MF 1 Hyst 2K-10K (----) MF 1 Hyst Off 2K-10K (----) MF 2 function 00-36 18 T - MF 2 target -20°C-90°C (----) MF 2 Hyst 2K-10K (----) MF 2 Hyst Off 2K-10K (----) MF 3 function 00-36 10 T - MF 3 target -20°C-90°C (----) MF 3 Hyst 2K-10K (----) MF 3 Hyst Off 2K-10K (----) MF 4 function 00-36 02 T - MF 4 target -20°C-90°C (----) MF 4 Hyst 2K-10K (----) MF 4 Hyst Off 2K-10K (----) F15 function 00-09 09 E1 function 00-03 02 E2 function 00-03 03 Sensor 1k/5k sensors 5k sensors
47
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 9
Functions: Heating or cooling and hot water monoenergetic operating mode
“System selection 6”
A1
Tmax
Heating circuit 1
1)
A12
l/h
Outdoor unit
Indoor unit CMF
F9
A6
A8
V
V
A9
F11
F17
II 0 I
B
AB
A3
A
F8
Heating/cooling
water
Storage tank
KPS 300
F6
Process water Storage tank
HPS 500
Heating circuit 2
F5
A2
1)
A4/A5
M
Taps
2) 3)
Cooling circuit
A10
CW inlet
Fresh water station
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
3) Cooling is activated over heating circuit 2 (mixer circuit). If cooled with a separate cooling circuit, menu item "T-supply cooling" must be set to "Closed".
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 06
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
WE 1 level 1 = 50
Output/level 00 – 9950 kW
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 0 2 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K ( ---- ) MF 4 Hyst Off 2 K - 1 0 K ( ---- ) F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
48
Hydraulic diagram for heat pump assembly WP 12
Functions: Heating or cooling and hot water monoenergetic operating mode
“System selection 6”
F9
Outdoor unit
F17
II 0 I
A
A6
B
Surface heating /
1)
Surface cooling
F5
A2
M
Heating circuit 1
A1
V
V
F8
F11
Process hot water
water tank
2)
1)
A4/A5
EWS 300
AB
F6
Taps
A12
Indoor unit CMT 120/160
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case! The cooling must be activated via heating circuit 2 by setting T-supply cooling to the desired cooling target supply temperature.
Designation Value range Factory setting
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German)
Terminal address On / Off On
Time 0-24 Set time
Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 06
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Output/level 00 – 9950 kW
continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 0 2 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K ( ---- ) MF 4 Hyst Off 2 K - 1 0 K ( ---- ) F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
WE 1 level 1 = 50
WE 3 level 1 = 1
49
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 11
Functions: Heating or cooling, solar and hot water monoenergetic operating mode
“System selection 7”
F14
Outdoor unit
A
Indoor unit CMF 120/160
F9
A8
V
V
A9
F11
F17
II 0 I
A3
AB
B
Multi-function
Storage tank
MPS 1000
A
A3
AB
B
F6
F8
F12
Tmax
Fresh water station
Heating circuit
F5
Taps
3)
l/h
A2
CW inlet
2)
1)
A4/A5
M
Cooling circuit
B
A6
AB
A12
A10
A
Coolant
Storage tank
KPS 300
r
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
4) The cooling must be activated via heating circuit 1 by setting T-supply cooling to the desired cooling target supply temperature.
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 07
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 2 3 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K 5.0K MF 4 Hyst Off 2 K - 1 0 K 2.0 K F15 function 0 0 - 0 9 09 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
4)
A10
50
Hydraulic diagram for heat pump assembly WP 12
Functions: Heating or surface cooling and process hot water single energy source operating mode, solar thermal process water support "System selection 7"
F9
Collector sur­face: max. 3-4 m
Outdoor unit
2!
F14
V
V
F17
F8
F11
II 0 I
A
AB
A6
B
Process hot
water tank
EWS 300
F6
Heating circuit 1
A1
1)
Taps
A12
Surface heating / Surface cooling
F5
A2
1)
A4/A5
M
2)
Indoor unit CMT 120/160
A12
F12
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case! The cooling must be activated via heating circuit 2 by setting T-supply cooling to the desired cooling target supply temperature.
3) If a circulation pump is installed, it must be controlled separately.
Designation Value range Programming
BUS code BM Off, 00-15 Off
Designation Value range Programming
WE 1 level 1 = 50
Output/level 00 – 9950 kW
Language D/GB/F/NL/E/I D (German)
Terminal address On / Off On
Time 0-24 Set time
Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 07
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard, T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 2 3 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K 5.0 K MF 4 Hyst Off 2 K - 1 0 K 2.0 K F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
WE 3 level 1 = 1
51
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 9
Functions: Heating or cooling and hot water, bivalent operating mode with boiler
“System selection 10”
Indoor unit CMF 120/160
F9
A9
Outdoor unit
A6
Oil fired boiler
V
V
F11
F17
II 0 I
Gas/
A8
A8
Heating circuit 1
M
AB
A
B
A3
F8
Heating/cooling
water
Storage tank
KPS 300
F6
Process water
Storage tank
PS 500
A1
1)
Tmax
A12
l/h
Heating circuit 2
F5
A2
1)
A4/A5
M
Taps
2) 3)
Cooling circuit
A10
CW inlet
Fresh water station
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) If the surface heating is the only heat distribution system, it automatically becomes heating circuit 1. A mixer is not necessary in this case!
3) Cooling is activated over heating circuit 2 (mixer circuit). If cooled with a separate cooling circuit, menu item "T-supply cooling" must be set to "Closed".
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 10
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 0 0 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 02 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K ( ---- ) MF 4 Hyst Off 2 K - 1 0 K ( ---- ) F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
52
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating, hot water and solar bi-fuel operating mode with gas wall mounted heater
“System selection 11”
Indoor unit CMF 120/160
F9
F14
V
V
A9
Outdoor unit
A6
F11
F17
II 0 I
Gas wall mounted
A12
heater.
AB
A8
A
A3
AB
B
Multi-function
Storage tank
MPS 1000
A
A3
B
F6
Tmax
F8
Fresh water station
F12
3)
Taps
l/h
CW inlet
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
Heating circuit
F5
A2
1)
A4/A5
M
2)
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 11
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 2 3 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K 5.0K MF 4 Hyst Off 2 K - 1 0 K 2.0 K F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
53
REMKO Heat Pump Manager
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating, hot water and solar bivalent operating mode with boiler
“System selection 11”
Indoor unit CMF 120/160
F9
F14
Outdoor unit
Oil fired boiler
A8
V
V
A9
F11
F17
II 0 I
Gas/
A8
M
A
A3
AB
B
Multi-function
Storage tank
F6
Tmax
MPS 1000
A
A3
AB
B
F8
F12
Fresh water station
Heating circuit
F5
A2
3)
Taps
l/h
2)
1)
A4/A5
M
CW inlet
A6
A12
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solar plant, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 11
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 37 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 2 3 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K 5.0K MF 4 Hyst Off 2 K - 1 0 K 2.0 K F15 function 0 0 - 0 9 09 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
54
Hydraulic diagram for heat pump assembly WP 10
Functions: Heating and hot water single energy source operating mode and solid fuel boiler
“System selection 12”
F14
Indoor unit CMF 120/160
Outdoor unit
F9
TH2
A6
A8
V
V
A9
F11
F17
II 0 I
A12
Solid fuel
boiler
AB
AB
Heating circuit
F5
A2
1)
A
A3
B
Multi-function
Storage tank
MPS 1000
A
A3
B
F6
Tmax
Taps
3)
l/h
F8
F1
Fresh water station
CW inlet
A4/A5
M
Notes:
1) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
2) We recommend, because of possible high temperatures - caused by the solid fuel boiler, to always connect the heating circuit via a 3-way mixer.
3) If a circulation pump is installed, it must be controlled separately.
Designation Value range Programming
BUS code BM Off, 00-15 Off
Language D/GB/F/NL/E/I D (German) Terminal address On / Off On Time 0-24 Set time Date Year, month, day Set date BUS code 1 00-15 01 BUS code 2 00-15 02
System selection ---/01-12 12
Regulator type 00-06 06 WE 1 type 00-09 07 WE BUS 00-05 05 Gradient On / Off Off WE 2 type 00-22 08 WE 2 tank 00-03 00 WE 3 type 00-09 01 WE 4 type 00-09 00 Buffer type 00-02 00 Cooling mode Off/On On
Standard,T-feed
HC1 function
const, swimming
pool, WW,
Standard
return
HC2 function see HC1 Standard
Designation Value range Programming
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1 continue with key next to "End" MF 1 function 0 0 - 3 7 0 0 T - MF 1 target - 2 0 °C - 9 0 °C ( ---- ) MF 1 Hyst 2 K - 1 0 K ( ---- ) MF 1 Hyst Off 2 K - 1 0 K ( ---- ) MF 2 function 0 0 - 3 6 18 T - MF 2 target - 2 0 °C - 9 0 °C ( ---- ) MF 2 Hyst 2 K - 1 0 K ( ---- ) MF 2 Hyst Off 2 K - 1 0 K ( ---- ) MF 3 function 0 0 - 3 6 3 4 T - MF 3 target - 2 0 °C - 9 0 °C ( ---- ) MF 3 Hyst 2 K - 1 0 K ( ---- ) MF 3 Hyst Off 2 K - 1 0 K ( ---- ) MF 4 function 0 0 - 3 6 2 2 T - MF 4 target - 2 0 °C - 9 0 °C ( ---- ) MF 4 Hyst 2 K - 1 0 K 50 MF 4 Hyst Off 2 K - 1 0 K 10 F15 function 0 0 - 0 9 0 9 E 1 function 0 0 - 0 3 0 2 E 2 function 0 0 - 0 3 0 3 Sensor 1k/5k sensors 5k sensors
55
REMKO Heat Pump Manager
Contact layout Merlin I/O circuit board (solder side view)
Remko specific contact layout for the circuit board inputs
Terminal Sensor no. Description Note
1 F9 External sensor
2 F8
3 F6 Hot water sensor
4 F5 Supply sensor HC 2 (mixer circuit)
5 F3 not assigned
6 F2 not assigned
7 F1 not assigned
8 F11 Supply sensor WP or HC 1 HC 1 is a direct heating circuit
9 F12 Sensor storage tank bottom Reference sensor solar or solid-fuel boiler
10 F13 Sensor solid fuel boiler Pt 1000
11 F14 Sensor solar collector Pt 1000
12 F15 Flow volume sensor Impulse input
13 F17 Return sensor (cooling control sensor)
14 eBUS + Signal output 0-10 V Modulation depth (target output in %)
15 eBus - Signal output 0-10 V Modulation depth (target output in %)
16 CAN-Bus H
17 CAN-Bus L
18 CAN-Bus -
19 CAN-Bus +
Collector sensor (collective supply) Heating control sensor
Heating control sensor. Must be located in accordance with the system diagram!
is found as set in the factory in the indoor unit. Depending on the selected (hydraulic) system, the sensor may have to be mounted at a different position
NOTE
Please also note the connection diagrams or the electrical circuit diagrams for the installed heat pump. These are found in the respective installation manual.
56
Troubleshooting and customer service
Fault numbers appear in the controller display if your heating system malfunctions.
There are three types of reports:
1. Info: Information and descriptions "Display" heat generation.
2. W 051 Warning: Maintenance required "Maintenance"
3. Info 055 Information: Heat pump lock "WP lock"
The meanings of the displayed error codes can be taken from the table on the next page. The system should be restarted after the fault has been corrected => RESET.
RESET : Brief shut-off or the equip­ment (mains switch). Controller starts again, configures itself again and continues to work with the already set values (fault mes­sages for defective sensors may no longer appear => corresponding functions may be deactivated).
General troubleshooting information
If the system does not operate cor­rectly, first check the cabling in the controller and controller components.
Sensor
At the level "General/ Service/ Sensor test", all sensors can be checked. All of the connected sensors have to appear here with plausible measured values.
Actuators (mixers, pumps => only with code number)
At the level "General/ Service/ Sensor test", all actuators can be checked. All relays can be switched individually at this level. This enables the correct connection of these components (e.g. direction of rotation of the mixers) to be easily checked.
BUS - connection
In controllers with connection to mixers => display of the com­munication icon in the standard display (depending on the design " " or "v") or under "Service/com­munication MM 1“ WE control­ler => display of the outdoor and WE temperature (see "Displays/ system") or in the boiler control if connected to the controller => dis­play of the room temperature and hiding of the current room target temperature "----" (see "Displays/ heating circuit") in the mixer ex­pansion controller if connected to the boiler controller => display of the outdoor and WE temperature (see "Displays/system") controller => display of the room tempera­ture and the hiding of the current room target temperature "----" (see Displays/heating circuit")
RESET of settings: Overwriting settings with standard values can be carried out separate­ly at the "Service level" for the "user" and "specialist" param­eters and the "time programme" respectively.
57
REMKO Heat Pump Manager
The equipment and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!
Malfunctions
Fault Possible cause Checks Remedial measures
Communications fault
Pumps do not switch off
Pumps fail to switch on
Bus and sensor wiring were laid together
Switched poles Check poles
To little voltage at the BUS plug
Operating mode Settings misaligned
Operating mode Time and heating programme pump switching Outdoor temperature and room target temperature Heating limits or Room control misaligned
Check connection cables
Check voltage
Check operating mode and settings
Operating mode Time and heating programme pump switching Outdoor temperature and room target temperature Heating limits or Check room control
Bus wiring and sensor wiring must be separated spatially from mains wiring.
Check poles
There must be at least 8V DC between the BUS plug's "+" and "-" terminals [terminals 18+19]. If too little voltage is measured, an external supply must be installed.
Type of pump switching at the specialist level heating circuit
Check operating mode => standard. Check time and heating pro­gramme => heating period Check pump switching => type of pump switching Standard => outdoor tempera­ture > room target tempera­ture? Heating limits => outdoor temperature > valid heating limit? Room controller => room temperature > target tempera­ture + 1K Additional tests via the controller's relay test function.
58
Fault indicated by code
Only the fault with the highest priority is displayed.
- The message "Fault" appears in the standard display and the fault number in the favourites line. The fault can be rotated out of view and rotated back into view in the display => see favourites.
- The current fault can always be found at the end of the display level "Display".
Display Fault description
Heat pump fault The flow monitor has tripped. A flow problem has occurred. Possible causes are air in the
E 54
E 69 Failure or short in supply sensor HC2 (mixing circuit). Sensor F5
E 70 Break or short in supply sensor HC1 (direct heating circuit). Multi-purpose sensor 1 Sensor F11
E 71 Failure or short in lower buffer sensor Sensor F12
E 72 Failure or short in upper buffer sensor No assignment by REMKO
E 75 Failure or short, external sensor Sensor F9
E 76 Failure or short, domestic water sensor Sensor F6
E 78 Failure or short, collector sensor Sensor F8
E 80 Failure or short, room sensor heating circuit 1. No assignment by REMKO
system, a clogged dirt trap or a defect of the charging pump in the indoor module. If the red indicator lamp illuminates, there is a problem in the outdoor module which can only be remedied through customer service.
E 81 EEPROM error. The invalid value has been replaced by the default value. Check parameter values!
E 83 Failure or short, room sensor heating circuit 2. No assignment by REMKO
E 84 Fault humidity, sensor No assignment by REMKO
E 90 Address 0 and 1 on bus. Bus codes 0 and 1 may not be used simultaneously.
E 91 Bus code assigned. The set bus code is already being used by another device.
E 135 Failure or short, lower WW buffer sensor, multifunction sensor 2. No assignment by REMKO
E 136 Break of short sensor heating appliance 2, collector sensor 2, multifunction sensor 3. Not used by REMKO
E 137 Break or short collector sensor 1, multifunction sensor 4. Not used by REMKO
E 140 Break or short return line sensor control sensor cooling-mode. Sensor F17
E 200 - E 207 Communication heating appliance 1 to WE 7
E 220 - E 253 Communication BM 0 to BM 15
E 240 Communication Manager
E 241 Communication (individual) heating appliances
E 242 Communication mixer
E 243 Communication Solar
Info 51 Information: Maintenance necessary. Customer service is also displayed.
Heat pump fault Flow monitor responded or an outdoor-module defect, but only if the red indicator light
Info 55
Info 55 Information: Heat pump cut off
also illuminates. If the red indicator light does not illuminate: check the circulation pump or the flow. There is a possibility of air in the pump or heating circuit
59
REMKO Heat Pump Manager
Sensor values / characteristic curve
Temperature 5 kOhm sensor (NTC) Pt1000 (solar/solid fuel)
-60℃ 698961 Ohm -
-50℃ 333908 Ohm -
-40℃ 167835Ohm -
-30℃ 88340 Ohm -
-20℃ 48487 Ohm 922 Ohm
-10℃ 27648 Ohm 961 Ohm
-0℃ 16325 Ohm 1000 Ohm
10℃ 9952 Ohm 1039 Ohm
20℃ 6247 Ohm 1078 Ohm
25℃ 5000 Ohm
30℃ 4028 Ohm 1118 Ohm
40℃ 2662 Ohm 1155Ohm
50℃ 1801 Ohm 1194 Ohm
60℃ 1244 Ohm 1232Ohm
70℃ 876 Ohm 1270Ohm
80℃ 628 Ohm 1309 Ohm
90℃ 458 Ohm 1347 Ohm
100℃ 339 Ohm 1385 Ohm
110℃ 255 Ohm 1422 Ohm
120℃ 194 Ohm 1460 Ohm
Technical data
Supply voltage V (DC) 12 - 20
Power consumption mA 25
Protection category in accordance with EN 60529 IP 40
Protection class in accordance with EN 60730 Part III
The clocks power reserve Hr. > 10
permitted ambient temperature in the workplace °C 0 - +50
permitted ambient temperature in storage °C - 20 - +60
permitted humidity, non-condensing r.H.% 95
Humidistat
Tolerance of the temperature sensor shunt NTC 5 k +/-1% at 25°C or +/- 0.2K at 25°
Tolerance of the temperature sensor Pt 1000? +/-0.2% at 0°C
60
+/-5% relative humidity at 25°C and 60% air humidity room sensor
Notes
Notes
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
Consulting
Thanks to intensive training, our consultants are always com­pletely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reli­able supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
REMKO GmbH & Co. KG Air conditioning and heating technology
Customer Service
Our equipment operates pre­cisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
Im Seelenkamp 12 D-32791 Lage Postbox 1827 D-32777 Lage Telephone +49 52 32 6 06-0 Fax +49 5232 606-260 Email info@remko.de Website www.remko.de
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...