REMKO CLK Series, CLK 70, CLK 120, CLK 30, CLK 150 Operating And Installation Instructions

...
Operating and installation instructions
REMKO CLK series
Automatic oil/gas heaters
CLK 30, CLK 50, CLK 70, CLK 120, CLK 150
Edition GB - Q04 Read the instructions prior to performing any task!
Content
Safety notes
Unit description
Specifications for fan-assisted heaters
Installation instructions
Safety device
Exhaust gas ducting
Before commissioning
Commissioning
Shutdown
Care and maintenance
Troubleshooting
Intended use
4
5
6
7
8
9
10
11
12
13
15
16
Customer service and guarantee
Environmental protection and recycling
Electrical wiring diagram
Exploded view of the unit
Spare parts list
Commissioning of forced-air oil burners
Maintenance log
Technical data
Carefully read this original Operating Manual prior to commissioning/using the units.
16
16
17
18
19
20
22
23
This manual is an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications. No liability accepted for errors or misprints!
3
REMKO CLK SERIES
Safety notes
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations when using the units.
The units have been subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can arise from the units if they are used improperly or not as intended by untrained personnel! Please observe the following notes:
The units may only be operated
by persons that have been adequately instructed in their operation
The units must be installed and
operated in such a way that personnel are not endangered by exhaust gases and radiant heat, and no fires may occur
The units must only be
operated in areas where the units can be supplied with an adequate amount of air for combustion
This unit can be used by
children above the age of 8, as well as by people with impaired physical, sensory or mental capabilities or a lack of experience and knowledge if they are supervised or have received instruction in the safe operation of the unit, and if they understand the associated potential hazards. Children must never play with the unit. Cleaning and user maintenance must not be carried out by unsupervised children
Appropriate prohibition signs must be displayed at the entrances!
Portable fuel containers must
only be set up and used in observance of the technical rules for combustible liquids "TRbF 20"
Only set the units down
on a steady, level and non­combustible base
The units must not be installed
or operated in potentially flammable or explosive environments
The units must not be installed
or operated in atmospheres containing oil, sulphur or salt
A safety zone of 1.5 m must be
maintained around the units, including to non-combustible items
The protective grille of the
intake must always be kept free of dirt and loose objects
Never insert foreign objects into
the unit
to direct jets of water. such as a high-pressure cleaner
etc.
All electrical cables for the
units must be protected against damage (e.g. by animals etc.)
Unattended unit operation
is only permitted with a thermostatic control
NOTE
Only type-approved forced-air oil burners in WLE design per DIN EN 298 and DIN EN 267 (oil)/DIN EN 676 (gas) should be used.
!
CAUTION
If there is a gas leak, immediately close the shut-off valve to the gas supply system, switch off the gas heater, unplug the power plug, open windows/doors for ventilation and seek the cause of the gas leak in order to neutralise this. Do not use the unit again before the gas leak has been eliminated!
Without exhaust gas system,
the units may only be operated in well ventilated spaces. Personnel must not remain in the installation area
4
Safety devices must not be
bypassed or disabled
The power plug must be pulled
out of the mains socket before maintenance and repair work
Unit description
The units are portable, directly fired fan-assisted heaters (WLE) with heat exchanger and exhaust gas connections exclusively for commercial applications.
The units can be directly fired with EL heating oil, diesel fuel or liquid gas.
The units can be operated with or without exhaust gas pipe. They are designed to be portable and for fully automatic operation.
The units are to be exclusively operated with separate type­approved forced-air burners.
The units are equipped with a noise-optimised and low­maintenance, high performance axial fan, a room thermostat receptacle and a power cable with protective contact plug.
In the case of units supplied ex works with blower oil burners, the units are equipped as standard with a drum fitting and electrical oil preheating.
Up to CLK 70: Nozzle preheater
in the burner (REMKO Multiflex also available as optional accessory)
From CLK 120: REMKO
Multiflex oil preheating
Locations at which units are used
As mobile, directly fired fan­assisted heaters, the units deliver instant heat. They are designed exclusively for commercial use.
The units may be used among other things for the following:
Spot heating of outdoor
workplaces
Drying newly completed
buildings
Spot heating workplaces
in open, non-flammable manufacturing facilities and halls
Temporarily heating enclosed
and open spaces
De-icing machines, vehicles and
non-combustible warehoused goods
Maintaining the temperature of
frost-sensitive goods
Heating, ventilating or frost
protection of lightweight structures
Heating, ventilating or frost
protection of tents
Heating or frost protection in
garden/agricultural outbuildings
Operating sequence
After switching off the units via the operating switch or the room thermostats the supply air fan runs to cool the combustion chamber with the heat exchanger for a certain time and then switches off. This process may be repeated several times.
Monitoring of the unit
The safety devices of the devices and the burner control unit (component of the blower burner) are used to perform all functions of the units fully automatically and to monitor their safety.
In the event of malfunctions or if the flame is extinguished, the automatic burner switches the units off.
The indicator lights on the control panel and the burner lamp on the burner control unit light up. Before restarting the device, the automatic burner must be manually released. To do this, press the external reset button on the control panel or the reset button on the automatic burner unit.
The temperature controller (TR) controls fan operation.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations, and are simple to operate.
CAUTION
The units may never be disconnected from the mains prior to the completion of the follow-up cooling phase (except in emergencies).
If the units are set to heating mode, then the forced-air burner starts automatically.
After the burner has run for a short time the temperature controller "TR" switches the supply air fan on automatically. Warm air is blown out.
When operating with a room thermostat, this process is repeated automatically depending on the heating requirement.
The temperature monitor "TW" monitors the internal temperature of the unit.
The temperature monitor (TW) limits or regulates the device temperature during heating operation.
The safety temperature limiter (STB) interrupts the heating function in case of extreme overheating or a failure or malfunction of the TW. The STB can only be manually reset after the units have cooled down.
5
REMKO CLK SERIES
Specifications for fan­assisted heaters
When using the units the respective applicable guidelines must always be observed.
Combustion plant order
(FeuVo) for the individual federal states
Workplace directives ASR 5
Workplace regulations
§§ 5 and 14
Ordinance for implementation
of Federal Emissions Control Regulations (BImSchG) and the subsequently issued legislation (ENEG)
Combustion air supply
Installation instructions
The safety regulations of the accident prevention and insurance associations, the respective regional building regulations and the combustion appliances regulations apply to the operation of the units.
NOTE
Overpressure and underpressure in the installation area should be avoided as this will inevitably lead to combustion-related faults.
Make sure that there is an
adequate fresh air supply appropriate to the respective forced-air burner capacity (see name plate)
The units must not be used
below ground level, e.g. in basements, without suitable gas monitoring equipment
The fuel supply must be
installed in accordance with DIN 4755 for oil-fired fan­assisted heaters, DVGW Code of Practice G 600 for gas-fired warm air heaters and TRF for liquid gas
The gas connection/unit
operation must take place exclusively on the basis of the accident prevention regulation DGUV 79, “Use of liquid gas”, as well as the respective local construction and fire prevention regulations.
There is good natural ventilation and aeration for example if:
1. the room volume in m³ is at least 30 times the nominal heating capacity in kW of all of the units operating in the space and if the natural change of air is provided by windows and doors, or
2. constantly open ventilation openings are present for incoming and exhaust air in the vicinity of the ceiling and floor, whose size in m² is at least 0.003 times the nominal heating capacity in kW of all of the units operating in the space.
Outdoor installation
Operation of the units must
not present a hazard or unreasonable discomfort
The unit operator must
ensure that it is impossible for unauthorised persons to manipulate either the unit or the power supply
Precipitation such as rain or
snow can be sucked in through the supply air fan. For this reason suitable weather protection should be provided
NOTE
The burner setting must be checked after every change of location and adapted to the new environmental conditions and atmospheric conditions if necessary.
6
Installation in enclosed, well ventilated areas without exhaust gas connection
Reliable extraction of the
combustion gases must be guaranteed in all cases in order to exclude impermissible contamination of the room air with hazardous substances
Fresh air is fed from below Exhaust gases are routed
upwards
Room heating
The units may only be operated
for room heating with a room thermostat (accessory)
The fresh air supply required
for trouble-free combustion must be ensured. It is practical to have the fresh air supply provided by windows and doors or through appropriately dimensioned openings in the outside wall
Safety distances
In order to guarantee safe
operation and maintenance of the units, 1.5 m safety distance should be maintained around the unit
Flooring and ceilings must be
fire retardant
Intake and outlet diameters
must not be narrowed or blocked with foreign objects
Electrical wiring
The units are operated with
230 V/50 Hz alternating current
The electrical connection is
made using a built-in mains cable with earthed safety plug
NOTE
The electrical connection for the units must be made at a separate feed point with a residual current device in accordance with VDE 0100, Section 55.
Extensions to the cable
may only be carried out by authorised electricians, subject to the length of the cable, connected load of the unit and taking into consideration how the unit is used at its location
!
CAUTION
The units must only be
installed in well ventilated
spaces and not in living areas
or similar recreational areas.
NOTE
For optimum operation the units should not be operated above an ambient temperature of 25 °C.
!
CAUTION
For use in public buildings,
national regulations must be
observed.
7
REMKO CLK SERIES
Safety equipment
Safety temperature limiter (STB)
The heating function is permanently interrupted by the safety temperature limiter (STB) in the event of the units overheating or malfunctioning.
A manual reset of the STB can only be implemented after the units have cooled down.
!
CAUTION
If the safety temperature limiter has been triggered, the cause of the malfunction must be identified and rectified before a reset is performed.
The STB is reset by actuating the reset key 2.
1. Unscrew the protective cap 1.
Regulating devices
The temperature sensor of the controller is self-monitoring. The probes are cold-resistant down to -20 °C. At temperatures below -20 °C the controller current flow will be interrupted, if the temperature rises above -20 °C the current flow will be released again. In the event of the probe or the capillary tube being damaged, as well as if an overtemperature of ca. 220 °C is reached, the filling medium will be emptied and the safety device is permanently triggered. Resetting is no longer possible. The controller is no longer fully functional and must be replaced.
Only
"REMKO original
replacement parts"
when replacing safety devices.
must be used
The units have the following control or safety equipment:
Temperature controller (TR)
The temperature controller controls the switching on and off of the recirculating fan. The switch point is set via the "Scale 21 - 60°" controller in the switching cabinet. Setpoint value approx. 35 - 40 °C.
Temperature monitor (TW)
The temperature monitor limits the unit or outlet temperature in heating mode via the burner. The switch point is set via the "Scale 34 - 110°" controller in the switching cabinet. Setpoint value approx. 80 - 85 °C.
Safety temperature limiter (STB)
2
1
2. Carefully press in the reset key 2 with a suitable tool.
3. Screw the protective cap 1 back on again.
NOTE
In order to prevent a renewed exceedance of the triggering temperature the operating conditions of the unit should be checked before resetting the STB.
!
CAUTION
Ensure that the device is fitted
properly
The capillary tubes must not be
kinked or bent in the immediate vicinity of the soldering points
The capillary tubes must not
be damaged or kinked during installation
The probes must only be fitted
at the fastening points provided by the factory
The probes must always be free
of dust and dirt in order to be sure of their correct functioning
The unit is permanently switched off by the safety temperature limiter (STB) in the event of the unit overheating or a temperature monitor malfunction. Manual resetting is required.
Automatic burner
The unit is permanently switched off by the automatic burner through the optical flame monitoring in the event of irregularities in the combustion, the flame extinguishing, fuel deficiencies etc. Manual resetting is required.
Safety devices may be neither bypassed nor disabled.
8
Exhaust gas ducting
It is also possible to operate the units outdoors or in open spaces without exhaust ducting. However, we recommend fitting a 1m exhaust gas duct with a rain hood on top (example 2), in order to exclude the ingress of rainwater and dirt. If the units are used for room heating then the combustion gases must be routed away, to the outside if necessary.
The exhaust gas ducting must
be designed so that the thermal lift of the exhaust gases is guaranteed at all times
The exhaust gas ducting must
be designed so that no counter­pressure can be generated
Fault-free operation is
guaranteed if the exhaust gas ducting is fitted in a rising arrangement and with a vertical end pipe
The exhaust gas routing should
end at least above the height of the eaves but ideally above the height of the ridge, in order to prevent any counter-pressure being caused by poor weather conditions (e.g. wind)
The minimum distance of 0.6 m
to combustible parts must be met
Exhaust gas ducting parts and
fastening materials are available as accessories
All parts of the exhaust gas
ducting must be reliably fastened Its diameter must not be smaller than the outlet nozzle of the unit
!
CAUTION
There must be no counter pressure arising from incorrect installation of the exhaust gas ducting under any circumstances.
Notes for implementing the 1st. BImSchV
Units that are not expected to be operated for longer than 3 months in the same location are not subject to any approvals or monitoring as per the 1st. BImSchV.
Example 1
Operation with extended exhaust gas ducting
Condensate trap required
Max. 1 metre
Example 2
Operation without extended exhaust gas ducting
Max. 1 metre
Over 1 metre
Example 3
Impermissible layout
In order to avoid the combustion chamber being damaged due to condensation of moisture (condensate) in example 3, make sure that the exhaust gas ducting is correctly installed with a condensate trap as shown in example 1.
NOTE
After installing an exhaust gas system the settings on the burner should be adapted to suit the new conditions.
9
REMKO CLK SERIES
Before commissioning
The units should be checked for visible defects on the operating and safety devices as well as proper installation and correct electrical connections before commissioning.
It is essential that the following points be observed:
Set up the units in a stable
position
Ensure there is sufficient supply
of combustion air
Check that the inlet and outlet
are free
Prevent overpressure or
underpressure in the installation area
Ensure that there is sufficient
fuel supply and that it complies with the respective local regulations
Only use clean EL heating oil or
Diesel fuel
Do not use Bio-Diesel!
The replacement of gas
cylinders must take place in an environment without ignition sources
Fuel supply
All common gas cylinder sizes are permitted for the gas supply. However, a gas cylinder with at least 11kg filling weight is recommended. For longer operation and nominal heat outputs above 50kW, it is recommended that the gas be drawn from several gas cylinders in parallel. (Multi­cylinder accessories set)
!
CAUTION
The operability of flexible fuel lines must be verified according to local conditions. They must always be protected against damage such as from forklifts, animals, etc.
The connection hose must not
be subject to torsional forces!
The fan-assisted heater must not be pointed in the direction of the fuel supply!
Paraffin formation with low outside temperatures
Even at low outside temperatures it is necessary to ensure that there is an adequate supply of heating oil that is capable of flowing.
Paraffin formation can start
from temperatures below 5 °C
To avoid this appropriate
preventative measures must be implemented e.g. Winter-proof EL heating
oil or winter Diesel, heated oil tank, insulated oil lines etc.
Note that fault-free operation
of the Multiflex oil pre-heating can only be guaranteed if the unit has been supplied with electrical power for a long period of time before starting
It is not possible to rectify
paraffin separation that has already occurred with the heating. If paraffin has already formed it is necessary to clean out the complete fuel system
NOTE
After fulfilling the respective local regulations as well as a professional installation of the unit, the exhaust values for the forced-air burner must be checked and adjusted if necessary by authorised specialists.
Air distribution
The units are equipped with a high performance axial fan. This fan is designed to specifically and effectively transport the heated air.
The distribution of the air is preferably implemented via ducting or special warm air or membrane hoses.
The possible lengths depend on the air-side resistances of the air ducts used.
Use hot air hoses approved by
us (accessories) exclusively
Observe the air flow direction
of the hoses with this! The inner overlapping on the seams of the hot air hoses must point in the direction of the air flow
Make sure that the hose or
ducting is securely fastened to the unit outlet nozzle and any connection pieces that may be being used
Only suitable air distributors
or air distributors approved by ourselves should be used for the air distribution
NOTE
The burner setting must be checked after every change of location and adapted to the new environmental conditions and atmospheric conditions if necessary.
NOTE
The hot air hoses must only be used in fully extended form and without any constrictions.
10
Commissioning
There should be no kinks or
bends in the hose lines in order to prevent hot-spots forming. Membrane hoses must not be twisted
Enclosed spaces being heated
via hoses must not present any overpressure
The forced-air burner can be
switched off briefly during operation by the temperature monitor (TW) in the event of increased intake temperatures or resistance at the unit's outlet.
After the temperature drops again the burner restarts automatically!
NOTE
Cycled operation of the forced-air burner with run times under 5 min. must in any event be avoided.
If the cycle intervals are too
short the length and layout of the hot air ducting should be checked
!
CAUTION
If a build-up of heat should occur then the heating operation will be interrupted by the STB permanently!
A person, who has been adequately trained in the handling of the units, must be tasked with operation and monitoring of the units.
Connecting the units to the electrical power supply
1. Move the operating switch to the "0" (off) position.
2. Connect the power plug to a properly installed and appropriately safeguarded mains socket.
230 V/50 Hz
!
CAUTION
All cable extensions must only be used in fully un-reeled or reeled off condition.
3. Open all of the oil supply shut-
off devices. With the initial commissioning, air in the oil lines can lead to a fault shut-down of the burner.
Control panel
8765
2
1
9
1 = Thermostat receptacle 2 = Strapping plug 5 = Operating switch 6 = Indicator light "GREEN"
"Operation"
7 = Indicator light "RED" "Burner
fault" 8 = Reset button "Burner" 9 = Mains cable with plug
Heating without room thermostat
The units are operating in permanent operating mode.
1. Connect the strapping plug
supplied 2 with the thermostat receptacle 1 on the unit.
1
2
NOTE
Air feeds on the intake side must always be implemented by means of non-distorting hoses/ducts (no unstable hoses).
NOTE
Cold start With the CLK 30 to CLK 70 units fitted ex works with a blower oil burner, a temperature-dependent delayed device start takes place due to the preheating of the nozzle block.
2. Move the operating switch to the "I" (Heating) position.
!
CAUTION
Never interrupt the mains connection (except in emergencies) prior to the completion of the follow-up cooling phase.
s
s
s
11
REMKO CLK SERIES
s
s
s
Shutdown
Heating with room thermostat
(Accessories)
The units operate fully automatically and according to the room temperature.
1. Pull out the strapping plug 2.
2. Connect the plug 3 of the room thermostat 4 with the thermostat socket 1 on the unit.
1
3
3. Place the room thermostat 4 at a suitable location in the room. The thermostat sensor must not be located directly in the warm air flow and must not be placed directly on a cold floor.
4. Set the desired temperature on the room thermostat 4.
Ventilation
In this switch position, the supply air fan runs permanently. The units can be used for air recirculation or ventilation purposes.
1. Move the operating switch to the "II" (Ventilate) position.
Thermostatic regulation and heating operation are not possible in this operating mode.
NOTE
Indicator light "Operation"
The indicator light signals the "Heating" operating mode. There is no display in the "Ventilate" operating mode or with the room thermostat switched off and when the STB has been triggered.
1. Move the operating switch to the "0" (off) position.
2. Shut off fuel supply.
3. With longer periods of inactivity, disconnect the units from the mains power supply.
The supply air fan runs on to cool the combustion chamber and the heat exchanger and only switches off after the cooling down phase is complete. The fan can switch on and run several times before the final shutdown.
4
5. Move the operating switch to the "I" (Heating) position.
The unit starts automatically after a brief burner pre-ventilation if heat is required and then runs fully automatically.
!
CAUTION
Never interrupt the power supply prior to the completion of the follow-up cooling phase. There is no guarantee entitlement in case of damage to the units due to overheating.
NOTE
In the case of longer periods of inactivity or if the units are in storage, ensure that the fuel tank is always filled with heating oil or diesel.
12
Care and maintenance
Regular care and observation of some basic requirements, once yearly or after extended times at a standstill, will ensure trouble-free operation and a long service life of the units.
!
CAUTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
Keep the units free of dust and
other deposits
Only clean the units with a dry
or moistened cloth
Never subject to direct jets of
water
e.g. pressure washers etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
Use only clean EL heating oil or
diesel fuel
Beware of paraffin formation!
Check the fuel filter(s) for
contamination at regular intervals. Replace contaminated filter if necessary
Check the units for mechanical
damage and have defective parts properly replaced
Check the fan blades and
combustion chamber with heat exchanger for contamination at regular intervals and clean these if necessary
Check the on-site oil tank
regularly for contamination, condensate water, foreign bodies and clean if necessary
Check that the safety devices
are operating correctly at regular intervals
Keep the probes for the safety
devices free of dust and dirt
Have the exhaust gas values for
the forced-air burners checked by authorised specialists at regular intervals. For safety reasons we recommend the conclusion of a maintenance contract
Observe maintenance and care
intervals
In the event of defects that
endanger the operational safety of the units, operation of the units must be discontinued immediately and the supervisor informed!
Cleaning tasks
The units, including the heat exchanger, combustion chamber and forced-air burner must be cleared of dust and dirt after every heating period, or possibly earlier depending on the operating conditions. Wearing parts, such as exhaust gas suppressors, seals, oil filter inserts and oil nozzles for example, should be checked and replaced if necessary.
Cleaning the heat exchanger
1. Set the operating switch to the "0" position and remove the power plug from the mains socket.
2. Take off the exhaust hood 1 after removing the 4 fastening screws. Hot air hoses present need not necessarily be removed.
3. Remove the inspection cover 2 and withdraw the exhaust gas suppressors 4.
4.
Clean the flues 5. A special cleaning brush is available as an accessory with EDP no. 1103110.
4 3 2
5
5. Clean the exhaust gas suppressors or replace damaged exhaust gas suppressors.
6. Check the seal 3 for the inspection cover and replace any damaged seals.
7. Following maintenance work, refit all parts carefully in reverse order.
Please also observe the instructions on the next page.
1
s
s
s
13
REMKO CLK SERIES
s
s
s
Inspection cover
Always check that the seal
is correctly seated in the inspection cover.
When fitting the inspection
cover ensure that the fastening nuts are tightened evenly. Unevenly tightened fixing nuts can result in leaks.
Cleaning the combustion chamber
1. Set the operating switch to the "0" position and remove the power plug from the mains socket.
2. Remove the burner cladding 1 after opening the two quick-release couplings
2.
3. Unscrew the fuel filter 3 including the fuel lines and take the plug 4 off the burner 5.
5. Set down the burner and the fuel filter carefully beside the unit.
6. Remove the burner flange 6.
7. Take care not to damage the flange seals, as far as is possible.
Damaged flange seals can result in incorrect air induction.
8. Clean the combustion chamber through the burner opening with a vacuum cleaner. A special boiler cleaning set for the REMKO industrial vacuum cleaner is available as an accessory.
Installation of the burner flange and the burner
1. Check the flange seal and replace if necessary.
2. Fix the burner flange to the unit housing with the four fastening screws. Note the "UP" sign!
5. Slide the flame tube of the burner into the burner flange.
Note dimension X in the sketch!
6. Clamp the flame tube firmly into place with the clamping screw 7 whilst lifting the burner slightly (3° tilt).
7. Lastly, tighten the bottom 2 fastening screws firmly.
8. Remount the fuel filter insert and lines and check for leaks.
9. Re-fit burner cladding and fasten with the quick couplings.
Additional notes for maintenance of the unit
All work must be carried out
exclusively by authorised specialists with the appropriate equipment. A log should be created and kept safely by the operator
NOTE
5
3
6
4
2
1
4. Loosen the 2 lower fastening screws on the burner flange 6.
4. Loosen the clamping screw 7 on the burner flange 6 and take out the burner by pulling towards the front.
3. Tighten the top 2 fastening screws firmly.
4. Gently tighten the lower 2 fastening screws with only light force so that the burner flange can still be pulled together.
Burner up to size 33: X = 20 mm Burner from size 44: X = 30 mm
X
6
The restrictions on exhaust gas losses per §10 of the ordinance on small furnace systems (1st. BImSchV) must be observed.
It is essential that the forced-air
burner is serviced and adjusted by authorised specialists
!
CAUTION
An electrical safety check must
7
be carried out in accordance with VDE 0701 after any work on the units.
14
Troubleshooting
!
CAUTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
The unit does not start
1. Check power supply.
2. Move the operating switch to the "I" (Heating) position.
3. Check whether the "Operation" indicator light on the control panel is illuminated. It must light up in the "Heating" mode.
NOTE
The indicator light only indicates the "Heating" mode. There is no display in the "Ventilate" operating mode or with the room thermostat switched off and when the STB has been triggered.
4. Check the strapping connector or the room thermostat plug, if fitted, is seated properly and making good contact.
5. Check the setting of the room thermostat. The temperature set must be higher than the current room temperature.
6. Check whether the safety temperature limiter (STB) has tripped. To do so, remove the protective cap next to the control panel.
7. Before an STB reset ensure that the causes have been analysed and rectified. The following causes are possible:
- The units were not able to cool down because the electrical connection was interrupted.
- Too high an outlet temperature due to incorrectly implemented air ducting when operating with hoses.
- Air inlets or outlets are not free or are inadequate.
8. Check whether the "Burner
fault" indicator light on the control panel is illuminated. If this is the case, then reset the automatic burner.
9. Move the operating switch to
the "II" (Ventilate) position. If the supply air fan now starts up the fault may well be in the burner area.
Forced-air burner and power supply
1. Check the oil filter(s) for
contamination. Replace contaminated oil filter(s).
2. Check whether the shut-off
cock on the oil filter is open.
3. Check the fuel tank for
sufficient fuel level.
4. Check the heating oil for
paraffin separation.
Possible even from 5 °C!
5. Check the oil hoses for damage.
6. Check the safety devices'
capillary tubes and probes for damage or contamination.
7. Use appropriate means to check
that the temperature monitor (TW) is functioning properly.
8. Check the forced-air burner for
possible damage to the nozzles, baffle plate, filter etc.
!
CAUTION
If the burner should carry out a fault shut-down once again after the start phase, then another reset should be carried out after a waiting period of 5 minutes has passed.
Further reset procedures must be prohibited as there is a danger of deflagration.
The supply air fan does not start
1. Check the fan can move freely.
2. Check the electrical cables on the supply air fan for damage.
3. Check the operating condenser of the fan. It is located in the unit's switching cabinet.
4. Use appropriate means to check that the temperature controller (TR) is functioning properly.
!
CAUTION
Repair work on the electrical installation and on the burner must be performed exclusively by authorised specialists for safety reasons.
!
CAUTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
15
REMKO CLK SERIES
Intended use
The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (not for living space heating in private use) on the basis of their structural design and equipment.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
Customer service and guarantee
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or their representative complete and return the "Certificate of guarantee" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units are tested several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Environmental protection and recycling
Disposal of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in stable transport packaging and, if applicable, on a wooden pallet. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
NOTE
Operation other than the types listed in this operating manual is prohibited. Failing to observe this renders any manufacturer liability or guarantee claims void.
!
CAUTION
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
Disposal of the old unit
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point
.
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended is strictly prohibited without the written authorisation of
REMKO GmbH & Co. KG
is prohibited.
16
Electrical wiring diagram
white
white
brown
orange
black
blue
Legend: C
= Start-up capacitor
H1 = Operating lamp (green) H2 = External burner fault lamp (red) KL = Terminal block M = Fan motor RT = Thermostat socket S1 = Operating switch
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Multiflex oil pre-heating
Optional: For CLK 30/50 and 70. Series: With CLK 120/150 with oil burner
fitted ex works.
S2 = Reset button (burner) STB = Safety temperature limiter TR = Temperature controller TW = Temperature monitoring device WS = Burner plug, 7-pin
(only fitted with factory burner delivery)
ÖV = Multiflex oil pre-heating
17
REMKO CLK SERIES
Exploded view of the unit
60
8
57
56
61
17
65
63
64
15
18
11
45
58 502
1
46
4
3
STB probe TW probe TR probe
57
5
49
48
63
9
676869
72
66
70 71
27
REMKO Multiflex oil preheating
Standard with CLK 120/150 with oil burner fitted ex works. Available as option for all types.
10
38
28 29
30
6
37
36
35
39
19
20
REMKO oil filter,
standard up to CLK 70 with oil burner fitted ex works. Available as option for all types.
22
25
47
55
7
26
32
33
31
Fig. CLK 70
18
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Designation CLK 30 CLK 50 CLK 70 CLK 120 CLK 150
EDP no. EDP no. EDP no. EDP no. EDP no. 1 Cover panel 1104703 1104703 1104740 1104770 1104770 2 Insulation, top 1104704 1104704 1104741 1104771 1104771 3 Insulation, right 1104705 1104705 1104742 1104772 1104772 4 Side panel, top right 1104706 1104706 1104743 1104773 1104773 5 Side panel, bottom right 6 Floor pan 1104708 1104708 1104745 1104775 1104775 7 Insulation, bottom 1104709 1104709 1104746 1104776 1104776 8 Side panel, top left 1104710 1104710 1104747 1104777 1104777 9 Side panel, bottom left 1104711 1104711 1104748 1104778 1104778
10 Insulation, left 1104712 1104712 1104749 1104779 1104779 11 Back panel, compl. 1104713 1104737 1104750 1104780 1104805 15 Insulation 1104714 1104714 1104751 1104781 1104781 17 Switching cabinet, compl. 1104716 1104753 1104783 1104807 1104808 18 Seal for switching cabinet 1104717 1104717 1104754 1104754 1104754 19 Front wall 1104718 1104718 1104755 1104785 1104785 20 Front wall insulation 1104719 1104719 1104756 1104786 1104786 22 2-line oil filter 1002526 1002526 1002526 1002526 1002526 25 Guide bracket 1104720 26 Holding bracket, oil filter 1104721 1104721 1104721 1104721 1104721 27 Multiflex oil pre-heating, compl. 1071410 1071410 1071410 1071410 1071410 28 O-ring 1108464 1108464 1108464 1108464 1108464 29 Filter insert 1108462 1108462 1108462 1108462 1108462 30 Oil filter cup 1108463 1108463 1108463 1108463 1108463 31 Hose pass-through 1104722 1104722 1104722 1104722 1104722 32 Outlet nozzle 1104723 1104723 1104758 1104788 1104788 33 Burner housing 1104724 1104724 1104759 1104789 1104789 35 Support foot 1104725 1104725 1104725 1104790 1104790 36 Axle 1104726 1104726 1104760 1104791 1104791 37 Wheel 1101621 1101621 1101621 1108369 1108369 38 Hubcap 1101623 1101623 1101623 1101623 1101623 39 Locking ring 1101622 1101622 1101622 1101622 1101622 45 Combustion chamber, compl. 1104727 1104738 1104761 1104792 1104806 46 Sealing cap ———— ———— 1104728 1104784 1104784 47 Exhaust gas suppressor (set) 1104729 1104762 1104793 1104809 1104810 48 Inspection cover 1104730 1104730 1104763 1104794 1104794 49 Seal for inspection cover 1104731 1104731 1104764 1104795 1104795 50 Collar, exhaust gas nozzle 1104732 1104732 55 Transportation bracket, front 1104733 1104733 1104765 1104797 1104797 56 Transportation bracket, rear 1104734 1104734 1104766 1104798 1104798 57 Transportation bracket, middle 1104735 1104735 1104767 1104799 1104799 58 Crane eye 1102554 1102554 1102554 1102554 1102554 60 Fan, compl. 1108158 1108199 1108178 1104815 1104815 61 Condenser (fan) 1102516 1102716 1102817 1104802 1104802 63 Safety temperature limiter (STB) 1101197 1101197 1101197 1101197 1101197 64 Temperature controller (TR) 1103166 1103166 1103166 1103166 1103166 65 Temperature monitor (TW) 1103146 1103146 1103146 1103146 1103146 66 Operating switch 1101188 1101188 1101188 1101188 1101188 67 Indicator light, green (Operation) 1105514 1105514 1105514 1105514 1105514 68 Indicator light, red (Burner fault) 1105363 1105363 1105363 1105363 1105363 69 Reset button (Burner) 1103408 1103408 1103408 1103408 1103408 70 Thermostat socket 1101018 1101018 1101018 1101018 1101018 71 Strapping plug 1101019 1101019 1101019 1101019 1101019 72 Mains cable with plug 1104701 1104701 1104701 1104701 1104701
xx Burner connector, 7-pin 1102537 1102537 1102537 1102537 1102537 xx Drum fitting, compl. 1002544 1002544 1002544 1002544 1002544 xx Cleaning brush, compl. 1103110 1103110 1103110
xx = not illustrated
1104707 1104707
1104720 1104757 1104787 1104787
1104744 1104774 1104774
1104732 1104796 1104796
1103110 1103110
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
19
REMKO CLK SERIES
Commissioning of forced-air oil burners
Preparatory tasks
!
CAUTION
The commissioning of the forced-air oil burner may only be carried out by trained specialists.
After loosening the 4 fastening bolts the mounting baseplate M is pulled off the housing G.
NOTE
Because the air flap, up to size 44, is sprung this should be closed beforehand with the help of the adjustment screw [3] (turn adjusting screw approx. as far as scale value 1).
The most important functional parts for the installation/ maintenance are now immediately accessible, as per the respective requirements. From size SL 44, 6 fastening screws must be removed (note marking arrows).
Fig.: 1
MG
Adjusting the ignition electrode and baffle plate
Size/dimensions A B C D
SLV 11 to SLV 33 5 5 7 3
SL 44 and SL 55 7 8 5 3
Required nozzle sizes
The selection of the required oil nozzle is dependent on the pump pressure and the unit capacity. Only a nozzle that is approved for the respective combustion chamber geometry with corresponding spray angle and cone characteristics may be used. Refer to the technical data for the required oil nozzle size.
All sizes are approximate values and are in mm. The optimum setting must be adapted to the unit­specific and structural conditions.
Air inlet nozzle
The required blower pressure can be adjusted with the adjustable air inlet nozzle A in accordance with the combustion chamber resistance and chimney draft, without having to change the output diameter.
1. Loosen the Allen screw B.
2. Turn the air inlet nozzle A to the desired position (note arrows!).
"min" = Smaller blower pressure "max" = Larger blower pressure
For maintenance work or for installing/replacing the oil nozzle, the mounting baseplate M can be positioned on the burner housing G in 2 ways (see figs. 1 and 2).
The baseplate can be positioned in the desired/possible position on the special mounting points in accordance with the unit-specific options.
20
Fig.: 2
G
M
A
B
Mounting baseplate
After having replaced the nozzle and carried out any adjustments required to the air inlet nozzle A, the mounting baseplate M is re­fitted in reverse order.
Adjusting the secondary air (Nozzle fitting adjustment)
2
Air flap
Setting the pump pressure
The pump pressure should be adjusted, and checked if necessary,
3
during burner commissioning and during all maintenance work.
1
Carry out the presetting of the secondary air as follows:
Set the nozzle fitting 2 to the desired value with the adjusting screw 1.
SLV 11 to SLV 33
Turning to left (–) = smaller scale value larger pressure behind the baffle plate
lower power range
Turning to the right (+)
= larger scale value smaller pressure behind the baffle plate
upper power range
4
The quantity of combustion air required is adjusted by means of the adjusting screw 3. The air flap is set according to the unit capacity and the further burner settings.
Adjustment of the air flap
Adjust the air flap as follows:
1. Loosen the knurled nut 4.
2. Set the adjusting screw 3 accordingly.
Turn to the right = Less air
Turn to the left = More air
4. After having set the adjusting screw 3 lock it again with the knurled knob 4.
NOTE
Never let the pump run for extended periods without any fuel. Never leave the units for extended periods with a pump that has run dry.
Adjust the pump pressure as follows:
1. Remove the stopper on the measurement nozzle "P".
2. Fit a suitable oil pressure manometer here.
3. Open all oil shut-off devices.
4. Switch on the burner.
5. Set the required oil pressure in accordance with the nozzle size and the unit capacity.
6. Switch off the burner after completing the adjustments.
7. Remove the oil pressure manometer again. Re-fit stopper incl. seal.
From SL 44 to SL 88
Turning to the left (+) = larger scale value smaller pressure behind the baffle plate
upper power range.
Turning to the right (–)
= smaller scale value larger pressure behind the baffle plate lower power range.
Additional notes
If the flame should give off
sooty smoke or break away with a fully opened air flap, reduce the pressure behind the baffle plate with the help of the secondary air setting
It may also be necessary to
open the air inlet nozzle further
!
CAUTION
If the burner should carry out a fault shut-down once again after the start phase, then another reset should be carried out after a waiting period of 5 minutes has passed.
Further reset procedures must be prohibited as there is a danger of deflagration.
All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.
21
REMKO CLK SERIES
Maintenance log
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Combustion chamber cleaned
Heat exchanger cleaned
Exhaust gas suppressors replaced
Inspection cover seal replaced
Fuel filter insert replaced
Safety equipment checked
Safety devices checked
Unit checked for damage
Electrical safety check
Burner maintenance *)
Test run
Comments: .....................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
*) Have the forced-air burner maintained and adjusted only by authorised specialists and in accordance with the legal
provisions (1st. BImSchV.). A corresponding measurement log should be generated.
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
22
Technical data
Unit type CLK 30 CLK 50 CLK 70 CLK 120 CLK 150
Nominal heat load max
. kW 29 46 68 114 150
Nominal heat capacity P
Minimum heat capacity P
nom
min
Room heating emissions
Nominal flow rate
Temperature increase Δ
(Max. total) pressure Pa 90 145 165 220 260
1)
t
Fuel Heating oil EL acc. to
Fuel Liquid gas cat. I
Max. fuel consumption (heating oil) l/h 2.85 4.5 6.6 11.2 14.8
Max. fuel consumption (liquid gas) kg/h 2.3 3.6 5.3 8.9 11.7
Danfoss oil nozzle
Pump pressure, approx.
2)
2)
kW 26.5 42 62 105 138
kW N.A. N.A. N.A. N.A. N.A.
mg/kWh
121 122 N.A. N.A. N.A.
m3/h 1,760 3,050 4,920 8,050 9,710
K 45 52 46 50 51
DIN 51603 or diesel fuel
3B/P
USG
0.6/60°S 1.00/60°S 1.35/60°S 2.25/80°S 2.75/80°S
bar 11.0 11.0 12.0 12.0 14.0
Liquid gas connection pressure mbar 50 50 50 50 50
Auxiliary power consumption
at nominal heating capacity el
at minimum heating capacity el
in Stand-By mode el
Pilot flame power requirement P
Thermal efficiency at nominal heating capacity
Thermal efficiency at minimum heating capacity
Type of room temperature control
Exhaust gas flow,
approx. kg/h 48 75 115 180 235
pilot
η
th,nom
η
th,min
max
min
kW 0.370 0.420 0.860 1.800 1.900
kW 0.000 0.000 0.000 0.000 0.000
kW 0.000 0.000 0.000 0.000 0.000
SB
kW N.A. N.A. N.A. N.A. N.A.
% 92.8 92.2 92.9 91.3 91.4
% N.A. N.A. N.A. N.A. N.A.
Room temperature control with mechanical
thermostat
Combustion chamber resistance (start up / operation)
Pa 145/40 150/45 180/80 400/90 480/120
Required flue draft Pa 0 0 0 0 0
Power supply V/Hz 230/1~/50
Max. nominal current
Operating condenser
Max. power consumption
Electrical protection (provided by the customer)
Sound pressure level L
1) At Δt 45K/1.2 kg/m3)
2) The specified nozzle sizes and pump pressures are based on test bench results. The oil flow rate was derived from this.
Based on the product-specific nozzle and pressure tolerances as well as the oil temperature, the specifications should only be
considered guidelines.
3) Workplace-related emission value 1m LpA as per DIN ISO 11203 (without burner mode)
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
(complete unit) A 1.8 2.0 4.0 8.2 8.8
(fan) μF 3 5 14 30 30
(oil preheating) W 30 30
A 10 10 10 16 16
1m 3) dB (A) 54 61 61 72 72
pA
23
REMKO CLK SERIES
Unit type CLK 30 CLK 50 CLK 70 CLK 120 CLK 150
Air outlet Ø mm 300 300 400 500 500
Flue gas connection ø mm 150 150 150 200 200
Dimensions: Length mm 1,450 1,450 1,610 2,100 2,100
Width mm 660 660 730 920 920
Height mm 1,000 1,000 1,120 1,350 1,350
Weight without blower oil burner kg 112 118 158 275 291
Weight with forced-air oil burner kg 126 132 172 296 312
24
Notes
25
REMKO CLK SERIES
26
27
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
Hotline within Germany
+49 (0) 5232 606-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...