Edition GB - Q04Read the instructions prior to performing any task!
Content
Safety notes
Unit description
Specifications for fan-assisted heaters
Installation instructions
Safety device
Exhaust gas ducting
Before commissioning
Commissioning
Shutdown
Care and maintenance
Troubleshooting
Intended use
4
5
6
7
8
9
10
11
12
13
15
16
Customer service and guarantee
Environmental protection and recycling
Electrical wiring diagram
Exploded view of the unit
Spare parts list
Commissioning of forced-air oil burners
Maintenance log
Technical data
Carefully read this original Operating Manual prior to
commissioning/using the units.
16
16
17
18
19
20
22
23
This manual is an integral part of the unit and must always be kept
in the vicinity of the installation location or on the unit itself.
Subject to modifications. No liability accepted for errors or misprints!
3
REMKO CLK SERIES
Safety notes
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of
the accident prevention and insurance associations when using the units.
The units have been subjected
to extensive material, functional
and quality inspections prior to
delivery. However, dangers can
arise from the units if they are used
improperly or not as intended by
untrained personnel!
Please observe the following notes:
■
The units may only be operated
by persons that have been
adequately instructed in their
operation
■
The units must be installed and
operated in such a way that
personnel are not endangered
by exhaust gases and radiant
heat, and no fires may occur
■
The units must only be
operated in areas where the
units can be supplied with an
adequate amount of air for
combustion
■
This unit can be used by
children above the age of
8, as well as by people with
impaired physical, sensory or
mental capabilities or a lack
of experience and knowledge
if they are supervised or have
received instruction in the safe
operation of the unit, and if
they understand the associated
potential hazards. Children
must never play with the unit.
Cleaning and user maintenance
must not be carried out by
unsupervised children
Appropriate prohibition signs
must be displayed at the
entrances!
■
Portable fuel containers must
only be set up and used in
observance of the technical
rules for combustible liquids
"TRbF 20"
■
Only set the units down
on a steady, level and noncombustible base
■
The units must not be installed
or operated in potentially
flammable or explosive
environments
■
The units must not be installed
or operated in atmospheres
containing oil, sulphur or salt
■
A safety zone of 1.5 m must be
maintained around the units,
including to non-combustible
items
■
The protective grille of the
intake must always be kept free
of dirt and loose objects
■
Never insert foreign objects into
the unit
■
The units may not be exposed
to direct jets of water.
such as a high-pressure cleaner
etc.
■
All electrical cables for the
units must be protected against
damage (e.g. by animals etc.)
■
Unattended unit operation
is only permitted with
a thermostatic control
NOTE
Only type-approved forced-air
oil burners in WLE design per
DIN EN 298 and DIN EN 267
(oil)/DIN EN 676 (gas) should
be used.
!
CAUTION
If there is a gas leak,
immediately close the shut-off
valve to the gas supply system,
switch off the gas heater,
unplug the power plug, open
windows/doors for ventilation
and seek the cause of the gas
leak in order to neutralise this.
Do not use the unit again
before the gas leak has been
eliminated!
■
Without exhaust gas system,
the units may only be operated
in well ventilated spaces.
Personnel must not remain in
the installation area
4
■
Safety devices must not be
bypassed or disabled
■
The power plug must be pulled
out of the mains socket before
maintenance and repair work
Unit description
The units are portable, directly
fired fan-assisted heaters (WLE)
with heat exchanger and exhaust
gas connections exclusively for
commercial applications.
The units can be directly fired with
EL heating oil, diesel fuel or liquid
gas.
The units can be operated with or
without exhaust gas pipe.
They are designed to be portable
and for fully automatic operation.
The units are to be exclusively
operated with separate typeapproved forced-air burners.
The units are equipped with
a noise-optimised and lowmaintenance, high performance
axial fan, a room thermostat
receptacle and a power cable with
protective contact plug.
In the case of units supplied ex
works with blower oil burners, the
units are equipped as standard
with a drum fitting and electrical
oil preheating.
■
Up to CLK 70: Nozzle preheater
in the burner
(REMKO Multiflex also
available as optional accessory)
■
From CLK 120: REMKO
Multiflex oil preheating
Locations at which units are
used
As mobile, directly fired fanassisted heaters, the units deliver
instant heat.
They are designed exclusively for
commercial use.
The units may be used among
other things for the following:
■
Spot heating of outdoor
workplaces
■
Drying newly completed
buildings
■
Spot heating workplaces
in open, non-flammable
manufacturing facilities and
halls
■
Temporarily heating enclosed
and open spaces
■
De-icing machines, vehicles and
non-combustible warehoused
goods
■
Maintaining the temperature of
frost-sensitive goods
■
Heating, ventilating or frost
protection of lightweight
structures
■
Heating, ventilating or frost
protection of tents
■
Heating or frost protection in
garden/agricultural outbuildings
Operating sequence
After switching off the units via
the operating switch or the room
thermostats the supply air fan runs
to cool the combustion chamber
with the heat exchanger for a
certain time and then switches
off. This process may be repeated
several times.
Monitoring of the unit
The safety devices of the devices
and the burner control unit
(component of the blower burner)
are used to perform all functions of
the units fully automatically and to
monitor their safety.
In the event of malfunctions or
if the flame is extinguished, the
automatic burner switches the
units off.
The indicator lights on the control
panel and the burner lamp on the
burner control unit light up.
Before restarting the device,
the automatic burner must be
manually released. To do this, press
the external reset button on the
control panel or the reset button
on the automatic burner unit.
The temperature controller (TR)
controls fan operation.
The units conform to the
fundamental health and safety
requirements of the appropriate
EU stipulations, and are simple to
operate.
CAUTION
The units may never be
disconnected from the mains
prior to the completion of
the follow-up cooling phase
(except in emergencies).
If the units are set to heating
mode, then the forced-air burner
starts automatically.
After the burner has run for a short
time the temperature controller
"TR" switches the supply air fan
on automatically. Warm air is
blown out.
When operating with a room
thermostat, this process is repeated
automatically depending on the
heating requirement.
The temperature monitor "TW"
monitors the internal temperature
of the unit.
The temperature monitor (TW)
limits or regulates the device
temperature during heating
operation.
The safety temperature limiter
(STB) interrupts the heating
function in case of extreme
overheating or a failure or
malfunction of the TW.
The STB can only be manually
reset after the units have cooled
down.
5
REMKO CLK SERIES
Specifications for fanassisted heaters
When using the units the
respective applicable guidelines
must always be observed.
■
Combustion plant order
(FeuVo) for the individual
federal states
■
Workplace directives ASR 5
■
Workplace regulations
§§ 5 and 14
■
Ordinance for implementation
of Federal Emissions Control
Regulations (BImSchG) and the
subsequently issued legislation
(ENEG)
Combustion air supply
Installation instructions
The safety regulations of the
accident prevention and insurance
associations, the respective
regional building regulations
and the combustion appliances
regulations apply to the operation
of the units.
NOTE
Overpressure and
underpressure in the
installation area should be
avoided as this will inevitably
lead to combustion-related
faults.
■
Make sure that there is an
adequate fresh air supply
appropriate to the respective
forced-air burner capacity
(see name plate)
■
The units must not be used
below ground level, e.g. in
basements, without suitable gas
monitoring equipment
■
The fuel supply must be
installed in accordance with
DIN 4755 for oil-fired fanassisted heaters, DVGW Code
of Practice G 600 for gas-fired
warm air heaters and TRF for
liquid gas
■
The gas connection/unit
operation must take place
exclusively on the basis of the
accident prevention regulation
DGUV 79, “Use of liquid gas”,
as well as the respective local
construction and fire prevention
regulations.
There is good natural ventilation
and aeration for example if:
1. the room volume in m³ is at
least 30 times the nominal heating
capacity in kW of all of the units
operating in the space and if the
natural change of air is provided
by windows and doors, or
2. constantly open ventilation
openings are present for incoming
and exhaust air in the vicinity of
the ceiling and floor, whose size
in m² is at least 0.003 times the
nominal heating capacity in kW
of all of the units operating in the
space.
Outdoor installation
■
Operation of the units must
not present a hazard or
unreasonable discomfort
■
The unit operator must
ensure that it is impossible
for unauthorised persons to
manipulate either the unit or
the power supply
■
Precipitation such as rain or
snow can be sucked in through
the supply air fan.
For this reason suitable weather
protection should be provided
NOTE
The burner setting must be
checked after every change of
location and adapted to the
new environmental conditions
and atmospheric conditions if
necessary.
6
Installation in enclosed, well
ventilated areas without
exhaust gas connection
■
Reliable extraction of the
combustion gases must be
guaranteed in all cases in
order to exclude impermissible
contamination of the room air
with hazardous substances
Fresh air is fed from belowExhaust gases are routed
upwards
Room heating
■
The units may only be operated
for room heating with a room
thermostat (accessory)
■
The fresh air supply required
for trouble-free combustion
must be ensured. It is practical
to have the fresh air supply
provided by windows and
doors or through appropriately
dimensioned openings in the
outside wall
Safety distances
■
In order to guarantee safe
operation and maintenance of
the units, 1.5 m safety distance
should be maintained around
the unit
■
Flooring and ceilings must be
fire retardant
■
Intake and outlet diameters
must not be narrowed or
blocked with foreign objects
Electrical wiring
■
The units are operated with
230 V/50 Hz alternating
current
■
The electrical connection is
made using a built-in mains
cable with earthed safety plug
NOTE
The electrical connection for
the units must be made at
a separate feed point with
a residual current device in
accordance with VDE 0100,
Section 55.
■
Extensions to the cable
may only be carried out by
authorised electricians, subject
to the length of the cable,
connected load of the unit and
taking into consideration how
the unit is used at its location
!
CAUTION
The units must only be
installed in well ventilated
spaces and not in living areas
or similar recreational areas.
NOTE
For optimum operation the
units should not be operated
above an ambient temperature
of 25 °C.
!
CAUTION
For use in public buildings,
national regulations must be
observed.
7
REMKO CLK SERIES
Safety equipment
Safety temperature limiter
(STB)
The heating function is
permanently interrupted by the
safety temperature limiter (STB) in
the event of the units overheating
or malfunctioning.
A manual reset of the STB can only
be implemented after the units
have cooled down.
!
CAUTION
If the safety temperature
limiter has been triggered, the
cause of the malfunction must
be identified and rectified
before a reset is performed.
The STB is reset by actuating the
reset key 2.
1. Unscrew the protective cap 1.
Regulating devices
The temperature sensor of the
controller is self-monitoring.
The probes are cold-resistant
down to -20 °C.
At temperatures below -20 °C
the controller current flow will be
interrupted, if the temperature
rises above -20 °C the current flow
will be released again.
In the event of the probe or the
capillary tube being damaged, as
well as if an overtemperature of
ca. 220 °C is reached, the filling
medium will be emptied and
the safety device is permanently
triggered.
Resetting is no longer possible.
The controller is no longer fully
functional and must be replaced.
Only
"REMKO original
replacement parts"
when replacing safety devices.
must be used
❄
The units have the following
control or safety equipment:
Temperature controller (TR)
The temperature controller controls
the switching on and off of the
recirculating fan. The switch point
is set via the "Scale 21 - 60°"
controller in the switching cabinet.
Setpoint value approx. 35 - 40 °C.
Temperature monitor (TW)
The temperature monitor limits
the unit or outlet temperature
in heating mode via the burner.
The switch point is set via the
"Scale 34 - 110°" controller in the
switching cabinet.
Setpoint value approx. 80 - 85 °C.
Safety temperature limiter (STB)
2
1
2. Carefully press in the reset key
2 with a suitable tool.
3. Screw the protective cap 1 back
on again.
NOTE
In order to prevent a renewed
exceedance of the triggering
temperature the operating
conditions of the unit should
be checked before resetting
the STB.
!
CAUTION
■
Ensure that the device is fitted
properly
■
The capillary tubes must not be
kinked or bent in the immediate
vicinity of the soldering points
■
The capillary tubes must not
be damaged or kinked during
installation
■
The probes must only be fitted
at the fastening points provided
by the factory
■
The probes must always be free
of dust and dirt in order to be
sure of their correct functioning
The unit is permanently switched
off by the safety temperature
limiter (STB) in the event of the
unit overheating or a temperature
monitor malfunction.
Manual resetting is required.
Automatic burner
The unit is permanently switched
off by the automatic burner
through the optical flame
monitoring in the event of
irregularities in the combustion,
the flame extinguishing, fuel
deficiencies etc.
Manual resetting is required.
Safety devices may be neither
bypassed nor disabled.
8
Exhaust gas ducting
It is also possible to operate the
units outdoors or in open spaces
without exhaust ducting.
However, we recommend fitting
a 1m exhaust gas duct with a rain
hood on top (example 2), in order
to exclude the ingress of rainwater
and dirt.
If the units are used for room
heating then the combustion
gases must be routed away, to the
outside if necessary.
■
The exhaust gas ducting must
be designed so that the thermal
lift of the exhaust gases is
guaranteed at all times
■
The exhaust gas ducting must
be designed so that no counterpressure can be generated
■
Fault-free operation is
guaranteed if the exhaust gas
ducting is fitted in a rising
arrangement and with a vertical
end pipe
■
The exhaust gas routing should
end at least above the height of
the eaves but ideally above the
height of the ridge, in order to
prevent any counter-pressure
being caused by poor weather
conditions (e.g. wind)
■
The minimum distance of 0.6 m
to combustible parts must be
met
■
Exhaust gas ducting parts and
fastening materials are available
as accessories
■
All parts of the exhaust gas
ducting must be reliably
fastened Its diameter must
not be smaller than the outlet
nozzle of the unit
!
CAUTION
There must be no counter
pressure arising from incorrect
installation of the exhaust
gas ducting under any
circumstances.
Notes for implementing the 1st.
BImSchV
Units that are not expected to
be operated for longer than
3 months in the same location
are not subject to any approvals
or monitoring as per the
1st. BImSchV.
Example 1
Operation with
extended exhaust
gas ducting
Condensate trap
required
Max. 1 metre
Example 2
Operation without
extended exhaust
gas ducting
Max. 1 metre
Over 1 metre
Example 3
Impermissible
layout
In order to avoid the combustion
chamber being damaged due
to condensation of moisture
(condensate) in example 3,
make sure that the exhaust gas
ducting is correctly installed with
a condensate trap as shown in
example 1.
NOTE
After installing an exhaust
gas system the settings on the
burner should be adapted to
suit the new conditions.
9
REMKO CLK SERIES
Before commissioning
The units should be checked for
visible defects on the operating
and safety devices as well as
proper installation and correct
electrical connections before
commissioning.
It is essential that the following
points be observed:
■
Set up the units in a stable
position
■
Ensure there is sufficient supply
of combustion air
■
Check that the inlet and outlet
are free
■
Prevent overpressure or
underpressure in the installation
area
■
Ensure that there is sufficient
fuel supply and that it complies
with the respective local
regulations
■
Only use clean EL heating oil or
Diesel fuel
Do not use Bio-Diesel!
■
The replacement of gas
cylinders must take place in an
environment without ignition
sources
Fuel supply
All common gas cylinder sizes
are permitted for the gas supply.
However, a gas cylinder with
at least 11kg filling weight
is recommended. For longer
operation and nominal heat outputs
above 50kW, it is recommended
that the gas be drawn from several
gas cylinders in parallel. (Multicylinder accessories set)
!
CAUTION
The operability of flexible
fuel lines must be verified
according to local conditions.
They must always be protected
against damage such as from
forklifts, animals, etc.
■
The connection hose must not
be subject to torsional forces!
■
The fan-assisted heater must not
be pointed in the direction of
the fuel supply!
Paraffin formation with low
outside temperatures
Even at low outside temperatures
it is necessary to ensure that there
is an adequate supply of heating
oil that is capable of flowing.
■
Paraffin formation can start
from temperatures below 5 °C
■
To avoid this appropriate
preventative measures must be
implemented
e.g. Winter-proof EL heating
oil or winter Diesel, heated oil
tank, insulated oil lines etc.
■
Note that fault-free operation
of the Multiflex oil pre-heating
can only be guaranteed if the
unit has been supplied with
electrical power for a long
period of time before starting
■
It is not possible to rectify
paraffin separation that has
already occurred with the
heating. If paraffin has already
formed it is necessary to clean
out the complete fuel system
NOTE
After fulfilling the respective
local regulations as well as
a professional installation of
the unit, the exhaust values
for the forced-air burner must
be checked and adjusted
if necessary by authorised
specialists.
Air distribution
The units are equipped with a
high performance axial fan. This
fan is designed to specifically and
effectively transport the heated air.
The distribution of the air is
preferably implemented via
ducting or special warm air or
membrane hoses.
The possible lengths depend on
the air-side resistances of the air
ducts used.
■
Use hot air hoses approved by
us (accessories) exclusively
■
Observe the air flow direction
of the hoses with this!
The inner overlapping on the
seams of the hot air hoses must
point in the direction of the air
flow
■
Make sure that the hose or
ducting is securely fastened to
the unit outlet nozzle and any
connection pieces that may be
being used
■
Only suitable air distributors
or air distributors approved by
ourselves should be used for
the air distribution
NOTE
The burner setting must be
checked after every change of
location and adapted to the
new environmental conditions
and atmospheric conditions if
necessary.
NOTE
The hot air hoses must only
be used in fully extended form
and without any constrictions.
10
Commissioning
■
There should be no kinks or
bends in the hose lines in order
to prevent hot-spots forming.
Membrane hoses must not be
twisted
■
Enclosed spaces being heated
via hoses must not present any
overpressure
■
The forced-air burner can be
switched off briefly during
operation by the temperature
monitor (TW) in the event of
increased intake temperatures
or resistance at the unit's outlet.
After the temperature drops
again the burner restarts
automatically!
NOTE
Cycled operation of the
forced-air burner with run
times under 5 min. must in any
event be avoided.
■
If the cycle intervals are too
short the length and layout of
the hot air ducting should be
checked
!
CAUTION
If a build-up of heat should
occur then the heating
operation will be interrupted
by the STB permanently!
A person, who has been
adequately trained in the handling
of the units, must be tasked with
operation and monitoring of the
units.
Connecting the units to the
electrical power supply
1. Move the operating
switch to the "0" (off)
position.
2. Connect the power
plug to a properly
installed and
appropriately
safeguarded mains
socket.
230 V/50 Hz
!
CAUTION
All cable extensions must only
be used in fully un-reeled or
reeled off condition.
3. Open all of the oil supply shut-
off devices.
With the initial commissioning,
air in the oil lines can lead to a
fault shut-down of the burner.
The units are operating in
permanent operating mode.
1. Connect the strapping plug
supplied 2 with the thermostat
receptacle 1 on the unit.
1
2
NOTE
Air feeds on the intake side
must always be implemented
by means of non-distorting
hoses/ducts (no unstable
hoses).
NOTE
Cold start
With the CLK 30 to CLK
70 units fitted ex works
with a blower oil burner,
a temperature-dependent
delayed device start takes
place due to the preheating of
the nozzle block.
2. Move the operating
switch to the "I"
(Heating) position.
!
CAUTION
Never interrupt the mains
connection (except in emergencies)
prior to the completion of the
follow-up cooling phase.
s
s
s
11
REMKO CLK SERIES
s
s
s
Shutdown
Heating with room thermostat
(Accessories)
The units operate fully
automatically and according to the
room temperature.
1. Pull out the strapping plug 2.
2. Connect the plug 3 of the
room thermostat 4 with the
thermostat socket 1 on the unit.
1
3
3. Place the room thermostat 4 at
a suitable location in the room.
The thermostat sensor must not
be located directly in the warm
air flow and must not be placed
directly on a cold floor.
4. Set the desired temperature on
the room thermostat 4.
Ventilation
In this switch position, the supply
air fan runs permanently.
The units can be used for air
recirculation or ventilation
purposes.
1. Move the operating
switch to the "II"
(Ventilate) position.
Thermostatic regulation and
heating operation are not possible
in this operating mode.
NOTE
Indicator light "Operation"
The indicator light signals the
"Heating" operating mode.
There is no display in the
"Ventilate" operating mode
or with the room thermostat
switched off and when the STB
has been triggered.
1. Move the operating
switch to the "0" (off)
position.
2. Shut off fuel
supply.
3. With longer
periods of inactivity, disconnect
the units from the
mains power supply.
The supply air fan runs on to cool
the combustion chamber and the
heat exchanger and only switches
off after the cooling down phase is
complete.
The fan can switch on and run
several times before the final
shutdown.
4
5. Move the operating
switch to the "I"
(Heating) position.
The unit starts automatically after
a brief burner pre-ventilation if
heat is required and then runs fully
automatically.
!
CAUTION
Never interrupt the power
supply prior to the completion
of the follow-up cooling
phase.
There is no guarantee
entitlement in case of
damage to the units due to
overheating.
NOTE
In the case of longer periods
of inactivity or if the units are
in storage, ensure that the
fuel tank is always filled with
heating oil or diesel.
12
Care and maintenance
Regular care and observation of
some basic requirements, once
yearly or after extended times at
a standstill, will ensure trouble-free
operation and a long service life of
the units.
!
CAUTION
Before undertaking any work
on the units, the power plug
must be removed from the
mains socket.
NOTE
Adjustment and maintenance
work may only be carried out
by authorised and qualified
technicians.
■
Keep the units free of dust and
other deposits
■
Only clean the units with a dry
or moistened cloth
■
Never subject to direct jets of
water
e.g. pressure washers etc.
■
Never use abrasive or solvent-
based cleaners
■
Use only suitable cleaners, even
for heavy contamination
■
Use only clean EL heating oil or
diesel fuel
Beware of paraffin formation!
■
Check the fuel filter(s) for
contamination at regular
intervals. Replace contaminated
filter if necessary
■
Check the units for mechanical
damage and have defective
parts properly replaced
■
Check the fan blades and
combustion chamber with heat
exchanger for contamination at
regular intervals and clean these
if necessary
■
Check the on-site oil tank
regularly for contamination,
condensate water, foreign
bodies and clean if necessary
■
Check that the safety devices
are operating correctly at
regular intervals
■
Keep the probes for the safety
devices free of dust and dirt
■
Have the exhaust gas values for
the forced-air burners checked
by authorised specialists at
regular intervals.
For safety reasons we
recommend the conclusion of a
maintenance contract
■
Observe maintenance and care
intervals
■
In the event of defects that
endanger the operational safety
of the units, operation of the
units must be discontinued
immediately and the supervisor
informed!
Cleaning tasks
The units, including the heat
exchanger, combustion chamber
and forced-air burner must be
cleared of dust and dirt after
every heating period, or possibly
earlier depending on the operating
conditions.
Wearing parts, such as exhaust
gas suppressors, seals, oil filter
inserts and oil nozzles for example,
should be checked and replaced if
necessary.
Cleaning the heat exchanger
1. Set the operating switch to the
"0" position and remove the
power plug from the mains
socket.
2. Take off the exhaust hood 1
after removing the 4 fastening
screws. Hot air hoses present
need not necessarily be
removed.
3. Remove the inspection cover 2
and withdraw the exhaust gas
suppressors 4.
4.
Clean the flues 5.
A special cleaning brush is
available as an accessory with
EDP no. 1103110.
432
5
5. Clean the exhaust gas
suppressors or replace damaged
exhaust gas suppressors.
6. Check the seal 3 for the
inspection cover and replace
any damaged seals.
7. Following maintenance work,
refit all parts carefully in reverse
order.
Please also observe the
instructions on the next page.
1
s
s
s
13
REMKO CLK SERIES
s
s
s
Inspection cover
■
Always check that the seal
is correctly seated in the
inspection cover.
■
When fitting the inspection
cover ensure that the fastening
nuts are tightened evenly.
Unevenly tightened fixing nuts
can result in leaks.
Cleaning the combustion chamber
1. Set the operating switch to the
"0" position and remove the
power plug from the mains
socket.
2. Remove the burner
cladding 1 after
opening the two
quick-release couplings
2.
3. Unscrew the fuel filter 3
including the fuel lines and take
the plug 4 off the burner 5.
5. Set down the burner and the
fuel filter carefully beside the
unit.
6. Remove the burner flange 6.
7. Take care not to damage
the flange seals, as far as is
possible.
Damaged flange seals can
result in incorrect air induction.
8. Clean the combustion chamber
through the burner opening
with a vacuum cleaner.
A special boiler cleaning set for
the REMKO industrial vacuum
cleaner is available as an
accessory.
Installation of the burner flange
and the burner
1. Check the flange seal and
replace if necessary.
2. Fix the burner flange to the unit
housing with the four fastening
screws.
Note the "UP" sign!
5. Slide the flame tube of the
burner into the burner flange.
Note dimension X in the
sketch!
6. Clamp the flame tube firmly
into place with the clamping
screw 7 whilst lifting the burner
slightly (3° tilt).
7. Lastly, tighten the bottom 2
fastening screws firmly.
8. Remount the fuel filter insert
and lines and check for leaks.
9. Re-fit burner cladding and
fasten with the quick couplings.
Additional notes for maintenance
of the unit
■
All work must be carried out
exclusively by authorised
specialists with the appropriate
equipment.
A log should be created and
kept safely by the operator
NOTE
5
3
6
4
2
1
4. Loosen the 2 lower fastening
screws on the burner flange 6.
4. Loosen the clamping screw
7 on the burner flange 6 and
take out the burner by pulling
towards the front.
3. Tighten the top 2 fastening
screws firmly.
4. Gently tighten the lower 2
fastening screws with only light
force so that the burner flange
can still be pulled together.
Burner up to size 33: X = 20 mm
Burner from size 44: X = 30 mm
X
6
The restrictions on exhaust
gas losses per §10 of the
ordinance on small furnace
systems (1st. BImSchV) must
be observed.
■
It is essential that the forced-air
burner is serviced and adjusted
by authorised specialists
!
CAUTION
An electrical safety check must
7
be carried out in accordance
with VDE 0701 after any work
on the units.
14
Troubleshooting
!
CAUTION
Before undertaking any work
on the units, the power plug
must be removed from the
mains socket.
The unit does not start
1. Check power supply.
2. Move the operating switch to
the "I" (Heating) position.
3. Check whether the
"Operation" indicator light on
the control panel is illuminated.
It must light up in the
"Heating" mode.
NOTE
The indicator light only indicates
the "Heating" mode. There is
no display in the "Ventilate"
operating mode or with the room
thermostat switched off and
when the STB has been triggered.
4. Check the strapping connector
or the room thermostat plug,
if fitted, is seated properly and
making good contact.
5. Check the setting of the room
thermostat.
The temperature set must be
higher than the current room
temperature.
6. Check whether the safety
temperature limiter (STB) has
tripped.
To do so, remove the protective
cap next to the control panel.
7. Before an STB reset ensure that
the causes have been analysed
and rectified.
The following causes are
possible:
- The units were not able to cool
down because the electrical
connection was interrupted.
- Too high an outlet temperature
due to incorrectly implemented
air ducting when operating with
hoses.
- Air inlets or outlets are not free
or are inadequate.
8. Check whether the "Burner
fault" indicator light on the
control panel is illuminated. If
this is the case, then reset the
automatic burner.
9. Move the operating switch to
the "II" (Ventilate) position.
If the supply air fan now starts
up the fault may well be in the
burner area.
Forced-air burner and power
supply
1. Check the oil filter(s) for
contamination. Replace
contaminated oil filter(s).
2. Check whether the shut-off
cock on the oil filter is open.
3. Check the fuel tank for
sufficient fuel level.
4. Check the heating oil for
paraffin separation.
Possible even from 5 °C!
5. Check the oil hoses for damage.
6. Check the safety devices'
capillary tubes and probes for
damage or contamination.
7. Use appropriate means to check
that the temperature monitor
(TW) is functioning properly.
8. Check the forced-air burner for
possible damage to the nozzles,
baffle plate, filter etc.
!
CAUTION
If the burner should carry out
a fault shut-down once again
after the start phase, then
another reset should be carried
out after a waiting period of 5
minutes has passed.
Further reset procedures must
be prohibited as there is a
danger of deflagration.
The supply air fan does not
start
1. Check the fan can move freely.
2. Check the electrical cables on
the supply air fan for damage.
3. Check the operating condenser
of the fan.
It is located in the unit's
switching cabinet.
4. Use appropriate means to check
that the temperature controller
(TR) is functioning properly.
!
CAUTION
Repair work on the electrical
installation and on the burner
must be performed exclusively
by authorised specialists for
safety reasons.
!
CAUTION
An electrical safety check must
be carried out in accordance
with VDE 0701 after any work
on the units.
15
REMKO CLK SERIES
Intended
use
The units are designed exclusively
for heating and ventilation
purposes in industrial or
commercial use (not for living
space heating in private use) on
the basis of their structural design
and equipment.
The units must only be operated
by appropriately instructed
personnel.
With non-observance of the
manufacturer's specifications, the
respective local legal requirements
or after arbitrary alterations to the
units, the manufacturer shall not
be liable for resulting damages.
Customer service and
guarantee
As a prerequisite for any guarantee
claims to be considered, it is
essential that the ordering
party or their representative
complete and return the
"Certificate of guarantee" to
REMKO GmbH & Co. KG at the
time when the units are purchased
and commissioned.
The units are tested several times
to verify their correct function.
However, if malfunctions should
arise that cannot be remedied by
the operator with the assistance of
the troubleshooting section, please
contact your specialist dealer or
contractual partner.
Environmental
protection and
recycling
Disposal of packaging
When disposing of packaging
material, please consider our
environment.
Our units are carefully packed
and delivered in stable transport
packaging and, if applicable, on
a wooden pallet.
The packaging materials are
environmentally-friendly and can
be recycled.
By recycling packaging materials,
you make a valuable contribution
to the reduction of waste and
conservation of raw materials.
Therefore, only dispose of
packaging material at appropriate
collection points.
NOTE
Operation other than the types
listed in this operating manual
is prohibited.
Failing to observe this renders
any manufacturer liability or
guarantee claims void.
!
CAUTION
NOTE
Adjustment and maintenance
work may only be carried out
by authorised and qualified
technicians.
Disposal of the old unit
The manufacturing process for
the units is subject to continuous
quality control.
Only high-grade materials are
processed, the majority of which
are recyclable.
You also contribute to
environmental protection by
ensuring that your old equipment
is only disposed of in an
environment friendly manner.
Therefore, only bring the old
unit to an authorised recycling
business or to an appropriate
collection point
.
Copyright
The redistribution, even in part,
or the use of this documentation
for purposes other than intended
is strictly prohibited without the
written authorisation of
REMKO GmbH & Co. KG
is prohibited.
16
Electrical wiring diagram
white
white
brown
orange
black
blue
Legend:
C
= Start-up capacitor
H1 = Operating lamp (green)
H2 = External burner fault lamp (red)
KL = Terminal block
M = Fan motor
RT = Thermostat socket
S1 = Operating switch
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Multiflex oil pre-heating
Optional: For CLK 30/50 and 70.
Series: With CLK 120/150 with oil burner
fitted ex works.
S2 = Reset button (burner)
STB = Safety temperature limiter
TR = Temperature controller
TW = Temperature monitoring device
WS = Burner plug, 7-pin
(only fitted with factory burner delivery)
ÖV = Multiflex oil pre-heating
17
REMKO CLK SERIES
Exploded view of the unit
60
8
57
56
61
17
65
63
64
15
18
11
45
58502
1
46
4
3
STB probe
TW probe
TR probe
57
5
49
48
63
9
676869
72
66
70 71
27
REMKO Multiflex oil
preheating
Standard with CLK 120/150
with oil burner fitted ex works.
Available as option for all types.
10
38
28
29
30
6
37
36
35
39
19
20
REMKO oil filter,
standard up to CLK 70 with oil
burner fitted ex works.
Available as option for all types.
22
25
47
55
7
26
32
33
31
Fig. CLK 70
18
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
When ordering spare parts, please state the EDP no., unit number and type(see name plate)!
19
REMKO CLK SERIES
Commissioning of forced-air oil burners
Preparatory tasks
!
CAUTION
The commissioning of the
forced-air oil burner may
only be carried out by trained
specialists.
After loosening the 4 fastening
bolts the mounting baseplate M is
pulled off the housing G.
NOTE
Because the air flap, up to
size 44, is sprung this should
be closed beforehand with
the help of the adjustment
screw [3] (turn adjusting screw
approx. as far as scale value 1).
The most important functional
parts for the installation/
maintenance are now immediately
accessible, as per the respective
requirements.
From size SL 44, 6 fastening screws
must be removed (note marking
arrows).
Fig.: 1
MG
Adjusting the ignition electrode and baffle plate
Size/dimensionsABC D
SLV 11 to SLV 335573
SL 44 and SL 557853
Required nozzle sizes
The selection of the required oil
nozzle is dependent on the pump
pressure and the unit capacity.
Only a nozzle that is approved
for the respective combustion
chamber geometry with
corresponding spray angle and
cone characteristics may be used.
Refer to the technical data for the
required oil nozzle size.
All sizes are approximate values and
are in mm. The optimum setting
must be adapted to the unitspecific and structural conditions.
Air inlet nozzle
The required blower pressure can
be adjusted with the adjustable air
inlet nozzle A in accordance with
the combustion chamber resistance
and chimney draft, without having
to change the output diameter.
1. Loosen the Allen screw B.
2. Turn the air inlet nozzle A to the
desired position (note arrows!).
For maintenance work or for
installing/replacing the oil nozzle,
the mounting baseplate M can be
positioned on the burner housing
G in 2 ways (see figs. 1 and 2).
The baseplate can be positioned
in the desired/possible position
on the special mounting points in
accordance with the unit-specific
options.
20
Fig.: 2
G
M
A
B
Mounting baseplate
After having replaced the nozzle
and carried out any adjustments
required to the air inlet nozzle A,
the mounting baseplate M is refitted in reverse order.
Adjusting the secondary air
(Nozzle fitting adjustment)
2
Air flap
Setting the pump pressure
The pump pressure should be
adjusted, and checked if necessary,
3
during burner commissioning and
during all maintenance work.
1
Carry out the presetting of the
secondary air as follows:
Set the nozzle fitting 2 to the
desired value with the adjusting
screw 1.
SLV 11 to SLV 33
Turning to left (–)
= smaller scale value
larger pressure behind the
baffle plate
lower power range
Turning to the right (+)
= larger scale value
smaller pressure behind
the baffle plate
upper power range
4
The quantity of combustion air
required is adjusted by means of
the adjusting screw 3.
The air flap is set according to
the unit capacity and the further
burner settings.
Adjustment of the air flap
Adjust the air flap as follows:
1. Loosen the knurled nut 4.
2. Set the adjusting screw 3
accordingly.
Turn to the right = Less air
Turn to the left = More air
4. After having set the adjusting
screw 3 lock it again with the
knurled knob 4.
NOTE
Never let the pump run for
extended periods without any
fuel. Never leave the units for
extended periods with a pump
that has run dry.
Adjust the pump pressure as
follows:
1. Remove the stopper on the
measurement nozzle "P".
2. Fit a suitable oil pressure
manometer here.
3. Open all oil shut-off devices.
4. Switch on the burner.
5. Set the required oil pressure in
accordance with the nozzle size
and the unit capacity.
6. Switch off the burner after
completing the adjustments.
Turning to the left (+)
= larger scale value
smaller pressure behind
the baffle plate
upper power range.
Turning to the right (–)
= smaller scale value
larger pressure behind the
baffle plate
lower power range.
Additional notes
■
If the flame should give off
sooty smoke or break away
with a fully opened air flap,
reduce the pressure behind the
baffle plate with the help of the
secondary air setting
■
It may also be necessary to
open the air inlet nozzle further
!
CAUTION
If the burner should carry out
a fault shut-down once again
after the start phase, then
another reset should be carried
out after a waiting period of 5
minutes has passed.
Further reset procedures must
be prohibited as there is a
danger of deflagration.
All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.
21
REMKO CLK SERIES
Maintenance log
Unit type: ..................................Unit number: ...................................