Remko BL 264 DC, BL 354 DC User guide

Page 1
Operating and installation instructions
REMKO BL series
Inverter wall - room air conditioner in split design with quick­release coupling system
BL 264 DC, BL 354 DC
0316-2022-07 Edition 1, en_GB
Read the instructions prior to performing any task!
Page 2
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Translation of the original
Page 3

Table of contents

1 Safety and usage instructions............................................................................................................. 5
1.1 General safety notes....................................................................................................................... 5
1.2 Identification of notes...................................................................................................................... 5
1.3 Personnel qualifications.................................................................................................................. 5
1.4 Dangers of failure to observe the safety notes................................................................................ 5
1.5 Safety-conscious working............................................................................................................... 6
1.6 Safety instructions for the operator................................................................................................. 6
1.7 Safety notes for installation, maintenance and inspection ............................................................. 6
1.8 Unauthorised modification and changes......................................................................................... 7
1.9 Intended use................................................................................................................................... 7
1.10 Warranty........................................................................................................................................ 7
1.11 Transport and packaging............................................................................................................... 7
1.12 Environmental protection and recycling........................................................................................ 8
2 Technical data........................................................................................................................................ 9
2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions............................................................................................................................. 11
3 Design and function............................................................................................................................ 12
4 Operation............................................................................................................................................. 13
4.1 General notes................................................................................................................................ 13
4.2 Display on indoor unit.................................................................................................................... 14
4.3 Keys on the remote control........................................................................................................... 14
5 Installation instructions for qualified personnel.............................................................................. 17
5.1 Important notes prior to installation............................................................................................... 17
5.2 Wall openings................................................................................................................................ 17
5.3 Installation materials..................................................................................................................... 17
5.4 Selection of installation location ................................................................................................... 18
5.5 Minimum clearances..................................................................................................................... 19
5.6 Connection variants for the indoor unit......................................................................................... 20
5.7 Wall bracket for the indoor unit..................................................................................................... 21
6 Installation........................................................................................................................................... 21
6.1 Installation of the indoor unit......................................................................................................... 21
6.2 Connection of refrigerant piping.................................................................................................... 22
6.3 Connection of quick-release couplings......................................................................................... 22
6.4 Leak testing................................................................................................................................... 24
7 Condensate drainage connection and safe drainage...................................................................... 24
8 Electrical wiring................................................................................................................................... 26
8.1 General Information...................................................................................................................... 26
8.2 Connecting the indoor unit............................................................................................................ 26
8.3 Outdoor unit connection................................................................................................................ 27
8.4 Electrical wiring diagram............................................................................................................... 27
8.5 Electrical drawings........................................................................................................................ 29
9 Before commissioning....................................................................................................................... 31
10 Commissioning................................................................................................................................... 31
11 Troubleshooting and customer service............................................................................................ 33
11.1 Troubleshooting and customer service........................................................................................ 33
11.2 Indoor unit fault analysis.............................................................................................................. 36
3
Page 4
REMKO BL series
12 Care and maintenance........................................................................................................................ 43
13 Shutdown............................................................................................................................................. 45
14 Spare parts list and exploded view................................................................................................... 46
15 Index..................................................................................................................................................... 47
4
Page 5
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units or their components for the first time. It provides useful tips and notes such as hazard warnings to prevent injury and material damage. Failure to follow the directions in this manual can endanger persons, the environment and the equipment itself or its components and will void any claims for liability.
Store this manual and the information required for the operation of this system (e.g. refrigerant data­sheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.
WARNING!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.
Warning of inflammable substances!

1.2 Identification of notes

This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.

1.3 Personnel qualifications

DANGER!
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.

1.4 Dangers of failure to observe the safety notes

Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
5
Page 6
REMKO BL series
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.

1.6 Safety instructions for the operator

The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury.
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Other­wise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commis­sioning may lead to water leaks, electric shocks or fire. Commissioning must take place as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same room.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear.
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.

1.7 Safety notes for installation, maintenance and inspection

n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling cir­cuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use of non-standardised components may result in water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply, leaks may result in the room filling with a flammable mix­ture!
The minimum room size of 4 m2 required for installation and storage pertains to the basic fill quantity of the unit. This varies according to the installation type and total fill quantity of the system. The calculation must take place in accordance with valid DIN standards. Make sure that the installation site is suitable for safe unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant. Never solder or grind unit components!
n Note that refrigerant may be odourless. n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry room. If the humidity is too high, this can cause short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate drainage of condensate can lead to water damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber of industry and commerce, which confirms their ability to work with refrigerant.
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a detachable, reusable connection is not permis­sible.

1.8 Unauthorised modification and changes

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.

1.11 Transport and packaging

The devices are supplied in a sturdy shipping con­tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety. The use of other parts may invalidate liability for resulting consequences.

1.9 Intended use

Depending on the model, the units and the addi­tional fittings with which they are equipped are only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed space.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
7
Page 8
REMKO BL series

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recy­cling specialists or at collection points.
8
Page 9

2 Technical data

2.1 Unit data

Series BL 264 DC BL 354 DC
Operating mode
Nominal cooling output
1)
Energy efficiency ratio SEER
1)
kW 2.7 (0.6-3.8) 3.5 (0.8-4.1)
Inverter wall-mounted room air conditioning unit
combination for cooling and heating
6.20 6.19
El. power consumption, cooling kW 0.8 (0.1-1.6) 1.18 (0.1-1.6)
El. current consumption, cooling A 3.8 (0.7-7.8) 5.6 (0.7-7.8)
Power consumption, annual, QCE
Energy efficiency ratio, cooling
Nominal heat capacity
2)
Energy efficiency ratio SCOP
3)
1)
kWh 148 198
A++
kW 3.0 (0.8-4.2) 3.8 (1.0-4.2)
4)
4.0
El. power consumption, heating kW 0.85 (0.3-1.6) 1.10 (0.3-1.6)
El. current consumption, heating A 4.1 (1.5-8.0) 4.9 (1.5-8.0)
Power consumption, annual, QHE
Energy efficiency ratio, heating
3)
1)
kWh 938
A+
Max. power consumption kW 1900
Max. current consumption A 9.5
EDP no. 1629268 1629360
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO BL series
Data specific to indoor unit BL 264 DC IT BL 354 DC IT
Application area (room volume), approx.
Adjustment range, room temperature °C +17 to +30
m
3
80 110
Air flow volume per stage
Sound pressure level per stage
m3/h
5)
dB (A) 29/35/42 28/31/41
400/500/600
Sound pressure level, silent mode dB (A) 189 20
Sound power level max. dB(A) 54 53
Enclosure class IP IPX0
Condensate drainage connection mm 16
Dimensions: H/W/D mm 292/792/201
Weight kg 8.5
EDP no. 1629270 1629362
5)
At distance of 1m in the open air; specified values are maximum values
Data specific to outdoor unit BL 264 DC AT BL 354 DC AT
Power supply
V/Ph/
Hz
230/1~/50
Operating range, cooling °C +5 to +48
Operating range, heating
7)
°C +5 to +32
Air flow rate, max.
m3/h
600
Enclosure class IP IP24
Sound power level max. dB (A) 61 62
Sound pressure level
Refrigerant
6)
5)
dB (A) 53 54
R32
Refrigerant, basic quantity kg 0.56
CO2 equivalent t 0.378
Operating pressure, max. kPa 4300/2500 4150/1150
Refrigerant piping, max. length m 3, 5, 8
Refrigerant piping, max. height difference m 5
Dimensions: H/W/D mm 530/705/279
Weight kg 22.5
EDP no. 1629269 1629361
5)
At distance of 1m in the open air; specified values are maximum values
6)
Contains greenhouse gas according to Kyoto protocol, GWP 2088
7)
This can be extended to -20 °C with the appropriate accessory kit
10
Page 11

2.2 Unit dimensions

D
E
B
A
C
B
A
C
Outdoor units
Fig. 1: Outdoor unit dimensions BL 264-354 DC AT
Measurements (mm) A B C D E
BL 264-354 DC AT 798 535 280 480 282
Indoor units
Fig. 2: Indoor unit dimensions BL 264-354 DC IT
Measurements (mm) A B C
BL 264-354 DC IT 792 290 202
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
11
Page 12
21
4
3
2
1
4
3
5
7
8
9
6
1
7
8
9
B
A
4
3
5
6
2
3
5
REMKO BL series

3 Design and function

Unit description
The BL 264-354 DC room air conditioners have a REMKO BL...AT outdoor unit as well as a BL...IT indoor unit.
In cooling mode, the outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating mode, the heat taken up by the outdoor unit can be discharged by the indoor unit into the room to be heated. In both operating modes, the output produced by the com­pressor precisely matches requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter technology" results in energy savings over conven­tional split systems and also reduces noise emis­sions to a particularly low level. The outdoor unit can be installed in an outdoor area or, providing that certain requirements are met, an indoor area. The indoor unit is designed to be mounted high up on the wall, in indoor areas. It is operated by an infrared remote control.
The outdoor unit consists of a cooling cycle with compressor, fin condenser, condenser fan, reversing valve and throttle element. The outdoor unit is controlled by the regulation of the indoor unit.
The indoor unit consists of a fin evaporator, evapo­rator fan, controller and condensate tray.
Floor brackets, wall brackets, refrigerant piping and condensate pumps are available as accessories.
Fig. 4: Cooling cycle diagram for outdoor unit
1: Condenser 2: Condenser fan 3: Reversing valve 4: Compressor 5: Filter dryer 6: Capillary tube throttle element 7: Pressure gauge connection 8: Suction pipe connection valve 9: Liquid line connection valve
Fig. 5: System layout
A: Outdoor area B: Indoor area 1: Indoor unit 2: Outdoor unit
Fig. 3: Cooling cycle diagram for indoor unit
1: Evaporator 2: Evaporator fan 3: Suction pipe connection 4: Liquid pipe connection
3: Condensate drainage line 4: Condenser fan 5: Power supply cable 6: Shut-off valve 7: Suction pipe 8: Injection pipe 9: Control line
Refrigerant piping is used to connect the indoor unit to the outdoor unit.
12
Page 13

4 Operation

max. 6 m

4.1 General notes

The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit with the remote control, then it can also be man­ually operated.
Manual mode
The indoor unit can also be switched on manually if the infrared remote control is lost/defective. Manual operation is intended for emergency oper­ation and is not suitable for basic unit operation. Please replace the remote control. The key for manual activation is located below the housing cover on the right side.
The following settings apply for manual operation:
Pressing once: Automatic mode,
Pressing twice: Cooling mode,
Pressing three times: Unit OFF
Fig. 6: Maximum distance
Infrared remote control
The infrared remote control sends the programmed settings a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects are obstructing the transmission path.
Two AAA batteries must be inserted into the remote control in preparation. To do so, remove the flap from the battery compartment and insert the batteries the correct way around (see mark­ings). Removing the batteries causes all stored data to be lost. The remote control will then access the default settings, which you are free to cus­tomise at any time.
Alarms are indicated by a code (see chapter Troubleshooting and customer service).
NOTICE!
Immediately replace flat batteries with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.
Help save on energy consumption in stand-by mode! If the device, system or component is not in use, we recommend disconnecting the power supply. Components with a safety function is excluded from our recommendation!
13
Page 14
1
1
10
7
6
9
8
5
2
3
4
1
2
3
4
5
6
7
REMKO BL series

4.2 Display on indoor unit

The display illuminates according to the settings.
Fig. 7: Display on indoor unit
1: Display

4.3 Keys on the remote control

"ON/OFF" key (ON/OFF)
This key switches the room air conditioner on and off.
"MODE" key (operating mode)
This key is used to set the desired operating mode. The automatic, cooling, dehumidification, heating and recirculation modes are available.
"TIMER" key (switch-on/switch-off delay)
Pressing this key activates the switch-on/switch-off delay. The delay time can be set in 0.5 second increments (30 minutes).
"+" and "–” key (up arrow / down arrow)
Using these keys, the setpoint can be decreased or increased in 1 °C increments. The keys are also used to set various functions.
"SPEED” key (fan speed)
Press this key to set the desired fan speed. The low, medium, high, turbo and automatic functions are available. A high fan speed enables higher per­formance, quicker circulation of the room air and larger casting distances, but at the cost of noise development and air speed (draught phenomena).
Fig. 8: Keys on the remote control
In “Recirculation” mode, the “automatic” stage cannot be used.
In the dehumidification mode, the fan speed cannot be set manually.
“COOL” key (cooling pre-setting)
“HEAT” key (heating pre-setting)
This activates the self-clean function on the unit.
14
Page 15
8
9
10
“MENU / OK” key (additional functions / con-
firm)
After pressing this key, an additional function can be activated using the “+” (up arrow), “-” (down arrow) “L/R SWING” (left arrow) and “U/D SWING” (right arrow) keys. The selected function flashes in the display and can be activated or deactivated by pressing the “OK” key. The following functions are available:
HEALT
Using this key, the REMKO BioClean function (ioni­sation) can be activated which contributes to improving the room air quality.
ECO (energy saving mode)
After activation of energy saving mode, the con­troller lowers the compressor frequency to a min­imum in order to save energy. Energy saving mode is automatically deactivated after 8 hours and is only available in cooling mode.
SLEEP
Pressing this key will automatically increase or decrease the target temperature by 1 °C within an hour in cooling mode and heating mode respec­tively. Press this key to maintain the most conven­ient temperature and save energy.
This function is only available in "Cooling", "Heating" and "Auto" modes. The unit goes back into its original state after 10 hours.
SILENCE (quiet operation)
Activates/deactivates the silent mode.
In silent unit mode, the compressor runs at a lower frequency, and the indoor unit fan rotates at a slower speed. This provides particularly quiet unit operation.
ELE.H
DISPLAY (display switch-off)
Activating this function switches the display indica­tors on the indoor unit.
LIGHT
This function is not available.
ELE.H
This function is not available.
I-FEEL
This key can be used to activate/deactivate the I­FEEL function. In this mode, the room temperature is measured on the remote control. This sends a signal to the indoor unit every 3 minutes. If the remote control does not send a signal to the indoor unit for 7 minutes, this mode is automatically deac­tivated.
Anti-F
This function is not available.
iCLEAN (self-cleaning)
Due to the formation of condensate on the heat exchanger and the residual moisture that remains, bacteria can multiply quickly. In regular normal operation, the heat exchanger is dried by the air volume flow.
This drying process can also be started manually with the “Clean” function (for example, if the unit is not in regular use). In cooling or dehumidification mode, the self-cleaning function can be activated.
The unit switches off automatically after cleaning (30 minutes). "CL" appears in the display indicator. Selection of the self-cleaning function is only pos­sible in standby mode.
"L/R SWING" key
This function is not available.
"U/D SWING" key
The oscillation of the horizontal fins can be set using this key. This function can be switched on and off by pressing the key.
15
Page 16
10
9
5
1
2
3
4
6
7
8
1
2
3
4
5
6
7
8
9
10
REMKO BL series
Indicators on the LCD
Fig. 9: Indicators on the LCD
RUN
This symbol appears when the "ON/OFF" key is pressed and the system is activated. Pressing this key again causes the indicator to go out.
Key lockIs displayed if key lock is activated.
I-FEEL
Is displayed when the temperature probe on the infrared remote control is activated.
Operating mode indicator
Shows the current operating modes, including automatic (AUTO), cooling (COOL), dehumidifica­tion (DRY), heating (HEAT), fan (FAN) and back to automatic (AUTO) mode.
Temperature indicators
Shows the set temperature setpoint. If fan (FAN) mode is set, no temperature is displayed.
Additional function indicators
Shows the activated additional functions (see keys on the remote control).
Swing fins
Shows the position of the horizontal and vertical swing fins.
Timer function
Displays when switch-on delay ON is active and when switch-off delay OFF is active. Furthermore, a set time is displayed in 0.5 second increments.
Fan speed
Shows the set fan mode and the current fan stage (see keys on the remote control).
Data transfer
Flashes when data is sent from the infrared remote control to the indoor unit.
16
Page 17

5 Installation instructions for qualified personnel

21 5
3 4
5.1 Important notes prior to instal­lation
n Transport the unit in its original packaging as
close as possible to the installation location. You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible trans­port damage. Report any damage immediately to your contractual partner and the shipping company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connec­tions.
n The refrigerant piping (liquid and suction pipe),
valves and connections must be insulated to make them vapour diffusion proof. If necessary also insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet (see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltra­tion of moisture and never kink or compress the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and ensures that the compressor oil can flow back without obstruction.
n Perform all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals, otherwise there is a risk of fire.
n Only use the fasteners contained in the scope
of delivery with the units.
n Use four supports and the associated hooks to
attach the ceiling cassette (only applies to ceiling cassettes).
n Use the insulated condensate hose in the
scope of delivery as a junction piece to the continuing condensate drain. Secure the con­densate drain with the supplied clamps.

5.2 Wall openings

n A wall opening of at least 65 mm diameter and
10mm incline from the inside to the outside must be created.
n To prevent damage to the lines, the interior of
the wall opening should be padded or, for example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall opening, taking account of fire protection regu­lations (provided by the customer). Do not use cement or lime containing substances!
Fig. 10: Wall opening
1: Liquid line 2: Control line 3: Condensate drainage line 4: Suction pipe 5: PVC pipe

5.3 Installation materials

The indoor unit is attached to the wall by a wall bracket and 4 screws (to be provided by the cus­tomer).
The outdoor unit is attached by 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.
17
Page 18
1
20 cm
1
REMKO BL series

5.4 Selection of installation location

Indoor unit
The indoor unit is designed for horizontal wall installation above doors. However, it can also be used in the upper wall area (min. 1.75m above the floor).
Outdoor unit
The outdoor unit is designed for horizontal installa­tion on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over. The outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from the influence of the weather.
Rain
For floor or roof set-up, the unit should be installed with at least 10cm ground clearance. A floor bracket is available as an optional accessory.
Wind
If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the pre­vailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be pro­vided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit. An additional stabilization is recommended. This can, for example, be realized with ropes or other structures.
Fig. 11: Windbreak
1: Wind
Sun
The condenser on the outdoor unit emits heat. Exposure to sunlight further increases the temper­ature of the fins and reduces the heat released by the finned heat exchanger. The outdoor unit should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of cus­tomer). One possible solution is to build a small roofed area over the unit. These measures should not affect the flow of warm outlet air.
Snow
The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20cm above the expected level of snow to prevent snow from entering the outdoor unit. An optional wall bracket is available as an accessory.
Fig. 12: Minimum clearance to snow
1: Snow
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts, adjoining rooms or halls (Fig. 13).
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being installed in the room and which can compen­sate any additional pressure loss in ventilation ducts (Fig. 13).
n Comply with any regulations and conditions
affecting the statics of the building. If neces­sary, fit acoustic installation.
18
Page 19
2
1
K
3
W
3
Fig. 13: Installation inside buildings
2
1
e
c
a
b
f
A B
2
1
a
b
c
d
e
K: Cold fresh air / W: Warm air 1: Outdoor unit / 2: Additional fan
3: Air shaft

5.5 Minimum clearances

Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.
Fig. 14: Minimum clearances of the indoor unit and outdoor unit
A: Indoor unit B: Outdoor unit
Indoor units Outdoor units
Measure-
ments (mm)
BL 264-354 DC IT BL 264-354 DC AT
1: Air inlet 2: Air outlet
a 120 300
b 1500 2000
c 120 600
d - 300
e 120 600
f 200 -
19
Page 20
C
B
C
A
B
A
REMKO BL series

5.6 Connection variants for the indoor unit

The following connection variants can be used for the refrigerant, condensate and control lines.
Fig. 15: Connection variant (view from the rear)
A: Infeed of the refrigerant piping at the wall, left B: Outlet through the wall, right
C: Outlet on the wall, right
20
Page 21

5.7 Wall bracket for the indoor unit

A B
D
G
C
E
F
Fig. 16: Mounting points for the wall bracket BL 264-354 DC IT (rear view, all dimensions in mm)
Unit type / dimen­sions
BL 264-354 DC IT 371 421 50 45 216 526 266
(All dimensions in mm)
The diameter of the pipe break-through is 65 mm for all unit types.
The wall bracket for the units must be attached with suitable screws and anchors.
A B C D E F G

6 Installation

6.1 Installation of the indoor unit

The indoor unit is attached by means of a wall bracket, taking into consideration the air outlet side located in the lower part.
1. Mark the mounting points on the structurally
permissible building sections according to the dimensions of the wall bracket.
2. If necessary, remove the break out opening
of the housing.
3. Connect the refrigerant piping, electrical
cables and condensate drainage line to the indoor unit as described below.
4. Hang the indoor unit onto the wall bracket by
tilting it back slightly and by pressing the bottom part of the unit against the bracket.
Fig. 17: Horizontal positioning
5. Check again that the unit is level. (Fig. 17)
The wall bracket for the units must be attached with suitable screws and anchors.
21
Page 22
REMKO BL series

6.2 Connection of refrigerant piping

The refrigerant pipes should be connected by the customer on the right-hand side of the outdoor component.
1. Use the wall or floor brackets to fit the out-
door unit against structural parts approved to support the static load (refer to the installa­tion instructions for the brackets).
2. Ensure that structure-borne sound is not
transferred to parts of the building. Use vibra­tion dampers to reduce the effects of struc­ture-borne sound!
NOTICE!
Installation should only be performed by author­ised specialists.
CAUTION!

6.3 Connection of quick-release couplings

The refrigerant pipes should be connected by the customer on the right-hand side of the outdoor component. The pre-filled refrigerant piping are connected to the outdoor unit by means of the quick-connector system. Once installed, the con­nections should be insulated to make them vapour diffusion proof. The following instructions describe the installation of the refrigerant piping for the indoor unit on the outdoor unit.
Please note that the following figures are only schematic representations. The actual appear­ance of the units may vary from those shown.
1. Remove the pre-installed plastic cover from
the outdoor unit(Fig. 19).
Both units are pre-filled with refrigerant at the factory. Suitable protective clothing must be worn during installation.
NOTICE!
Use only tools which are approved for use in an HVAC environment.
The refrigerant piping on the indoor unit are extended at the factory so that the quick-release couplings can be located outside the building if they are fed through the masonry.
Fig. 19: Remove the plastic cover
2. Remove the green/black protective caps from
the quick-connectors on the outdoor compo­nent, as well as the flexible refrigerant pipes on the indoor unit (Fig. 20 and Fig. 21).
Fig. 18: Placing of the quick-release couplings
Fig. 20: Remove protective caps
22
Page 23
Fig. 21: Remove protective caps
2
1
3. Before connecting the refrigerant pipes, ensure that the quick-release couplings are situated in front of one another (Fig. 22).
Fig. 24: Tightening the fitting
1: Tighten with the first open-ended spanner 2: Counter with the second open-ended spanner
7. Open the stop cocks with an Allen key before switch the system on!
Fig. 22: Position of the quick-release couplings
4. First connect and hand-tighten the refrigerant piping to ensure it is correctly seated.
5. Then install the suction pipe with the largest diameter.
Fig. 23: Installation on the indoor unit
Pipe dimension
in inches
1/4" 15-20
3/8" 33-40
CAUTION!
Only open the stop cocks following complete installation of the quick-release couplings and
before switching the system on!
Tightening torque in Nm
6. Then tighten the fittings with 2 appropriately-
sized open-ended spanners. Use one spanner to counter the force when tightening the fitting (Fig. 24).
23
Page 24
3
2
4
9
5 5
11
100
6
8
7
10 10
12 12
1
REMKO BL series

6.4 Leak testing

Once all the connections have been made, the pressure gauge station is attached to the Schrader valve as follows (if fitted):
red = small valve = high pressure
blue = large valve = suction pressure
Leak testing involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been made properly. Then tighten the screw connection.
NOTICE!
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This device contains refrigerant with a greenhouse potential of 2088. That means the escape of 1 kg of this refrig­erant has an effect on global warming that is 2088 times greater than 1 kg CO2, based on 100 years. Do not conduct any work on the refrigerant circuit or dismantle the device ­always enlist the help of qualified experts.
7 Condensate drainage
connection and safe drainage
Fig. 25: Condensate drainage, seepage of conden­sate and strip foundation (cross-section)
1: Outdoor unit 2: Leg 3: Condensate collection tray 4: Floor bracket 5: Reinforced strip foundation
H x W x D = 300 x 200 x 800 mm 6: Gravel layer for seepage 7: Condensate drainage heating 8: Drainage channel 9: Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60°C) 10: Frost line 11: Drainage pipe 12: Soil
24
Page 25
EB
B
A
D
C
11
1
5
5
8
1
9
3
Fig. 26: Dimensions for the strip foundation (bird's
min. 2%
eye view)
For the designations of 1,3,5,8,9 and 11, please refer to the legend for Fig. 25
Dimensioning of the strip foundation
Dimen-
Value in mm
sion
A 800
B 200
C 480
D 282
E 280
Fig. 27: Condensate drainage connection - Indoor unit
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the fol­lowing list of requirements from regional regula­tions and laws.
NOTICE!
Local regulations or environmental laws, for example the German Water Resource Law (WHG), can require suitable precautions to pro­tect against uncontrolled draining in case of leakage to provide for safe disposal of escaping refrigerator oil or hazardous media.
Condensate drainage connection
If the temperature falls below the dew point, con­densation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
NOTICE!
If condensate is removed via a duct in accord­ance with DIN EN 1717, ensure that any micro­biological contamination present on the waste­water side (bacteria, fungi, viruses) cannot enter the unit connected to it.
underside of the unit to drain any condensate.
n The condensate drainage line should have an
incline of min. 2% and is the responsibility of the customer. If necessary, fit vapour-diffusion­proof insulation.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate drainage line is laid to protect it against frost. The lower part of the housing and condensate tray is also to be kept frost free in order to ensure permanent draining of the condensate. If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the line is durably leak tight.
25
Page 26
2
1
4
3
1
REMKO BL series

8 Electrical wiring

8.1 General Information

A protected power supply cable is to be connected to the outdoor unit and a five-core control line to the indoor unit respectively.
DANGER!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regula­tions to dimension and to lay.
NOTICE!
The electrical connection of the units must be carried out in accordance with VDE regulations. We recommend using an FI circuit breaker that is sensitive to all currents, as increased leakage currents can occur.
The control line to the outdoor unit contains a data cable which is used to establish communication between the indoor unit and the outdoor unit. This is used for controlling the cooling and heating capacity and for forwarding alarm codes to the indoor unit. If the length is insufficient, you can extend the control lines on the indoor unit.
Make the connection as follows:
1. Open the panel of the unit.
2. Remove the covers on the right-hand side
(Fig. 28).
3. Feed the control line through the opening on
the rear of the unit in the connection area.
4. Connect the control line to the terminals
(Fig. 28).
5. Re-assemble the unit.
We recommend using shielded wires for the control lines.
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. Tighten as required.

8.2 Connecting the indoor unit

n We recommend that a mains/repair switch be
installed near the outdoor unit.
n The terminal blocks for making the connections
are located at the rear of the unit. When the unit is installed, measurements can be made from the front by removing the cover.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may be necessary to install an additional relay with a higher contact rating after the switch-off con­tact on the pump to switch off the compressor.
Fig. 28: Connecting the indoor unit
1: Cover 2: Strain relief 3: Terminal block for control line 4: Control line from outdoor unit
26
Page 27
LO N S PE
A
N S PE
B
1
230 V/1~/50 Hz
L L LO
2

8.3 Outdoor unit connection

Proceed as follows to connect the line:
1. Remove the side-panel cover.
2. Choose the cable cross-section in accord-
ance with the relevant specifications.
3. Connect the lines as shown on the electrical connection diagram.

8.4 Electrical wiring diagram

Connection BL 264-354 DC
4. Fix the line in the strain relief and re-
assemble the unit.
Fig. 29: Outdoor unit connection
Fig. 30: Electrical wiring diagram
A: Outdoor unit / B: Indoor unit 1: Power supply cable / 2: Communication line
27
Page 28
N S PE
LO N S PE
L
N
WH
BK
230 V/1~/50 Hz
1
3
2
A
B
LLLO
REMKO BL series
Connection of optional condensate pump KP 6/KP 8
Fig. 31: Electrical wiring diagram
A: Outdoor unit B: Indoor unit C: KP6/KP8 condensate pump 1: Power supply cable
2: Condensate pump supply 3: Condensate pump fault contact BK: black WH: white
28
Page 29

8.5 Electrical drawings

BN
YE/GN
RD
BK
BU
A
B
2
1
4
3
5
6
7
8
9
Indoor units BL 264-354 DC IT
Fig. 32: Electrical drawings
A: Indoor unit control board B: Indoor unit connection block 1: Fan motor 2: Wi-Fi connection 3: Display circuit board 4: Horizontal swing motor
5: Not available 6: Ion generator 7: Transformer 8: Probe, evaporator 9: Room temperature probe
29
Page 30
A
B
2
1
4
3
5
C D
6
7
BN
BU
BK
RD
BU
BK
M
M
M
YE/GN
YE/GN
YE/GN
REMKO BL series
Outdoor units BL 264-354 DC AT
Fig. 33: Electrical drawings
A: Control board, outdoor unit B: Outdoor unit connection block C: Control line to indoor unit D: Power supply cable 1: Not available 2: Fan motor
3: 4-way changeover valve 4: Heating element 5: Sensors 6: Electronic expansion valve 7: Compressor
30
Page 31

9 Before commissioning

Perform the following checks prior to putting the unit into operation for the first time and after any work on the cooling cycle. Record the results in the commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy water.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.

10 Commissioning

NOTICE!
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued. Observe the operating manuals for the indoor unit and outdoor unit when commissioning the entire system.
Once all the components have been connected and tested, the system can be put into operation. A functional check should be performed to verify its correct function and identify any unusual operating behaviour prior to handing it over to the operator.
NOTICE!
Check that the shut-off valves and valve caps are tight after carrying out any work on the cooling cycle. Use appropriate sealant products as necessary.
Functional checks and test run
Check the following points:
n Leak-tightness of the refrigerant piping. n Compressor and fan running smoothly. n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not over­heating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured tempera­ture.
n Record the measured temperatures in the
commissioning report.
31
Page 32
REMKO BL series
Function test of the cooling and heating modes
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-off valves on the outdoor unit until the pressure gauge indicates a pressure of approx. 2 bar.
3. Check all connections for leaks with leak detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-off valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection. It is imperative that the vacuum creation and drying steps are repeated.
5. Activate the main circuit breaker or fuse (to be provided by the customer).
6. Use the remote control to switch on the unit and select the cooling mode, maximum fan speed and lowest target temperature.
7. Check the overheating, outside, inside, outlet and vaporisation temperatures and record the measured values in the commissioning report. Check the correct function and set­tings of all regulation, control and safety devices.
8. Check the unit control system using the func­tions described in the chapter "Operation". Timer, temperature setting, fan speeds and switching to ventilation or dehumidification mode.
9. Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray. A bottle with a spout is recommended for pouring the water into the condensate tray.
10. Switch the indoor unit to heating mode.
11. During the test run, check the functionality of
all of the previously described safety devices.
12. Record the measured values into the com­missioning report and familiarise the operator with the system.
13. Remove the pressure gauge. Check that seals have been fitted in the sealing caps.
14. Re-install all disassembled parts.
32
Page 33

11 Troubleshooting and customer service

11.1 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly. However, if malfunctions do occur, please check the functions as detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Trouble­shooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Possible causes Checks Remedial measures
The unit does not start or switches itself off
Power failure, under­voltage, defective mains fuse/main switch in OFF position
Damaged power supply cable
Wait time after switching on is too short
Temperature outside operating range
Electrical surges caused by thunderstorms
Malfunction of the external condensate pump
Transmission distance too far/receiver affected by interference
Does all other electrical equipment function cor­rectly?
Does all other elec. equipment function cor­rectly?
Have approx. 5 minutes elapsed since the restart?
Are the fans in the indoor unit and outdoor unit working correctly?
Have there been light­ning strikes in the area recently?
Has the pump shut down due to a malfunction?
Does the indoor unit beep when pressing a key?
Check the voltage and if necessary, wait for it to come back on
Repair by specialist firm
Schedule longer wait times
Observe temperature ranges of indoor unit and outdoor unit
Switch off the mains breaker and switch it back on. Have it inspected by a specialist
Check and if necessary clean the pump
Reduce the distance to less than 6 m or change position
Remote control is faulty Is the unit running in
manual mode?
Receiver or transmitter unit exposed to exces-
The unit does not respond to the remote control
The unit works at reduced or no cooling capacity
33
sive solar radiation
Electromagnetic fields are interfering with trans­mission
Key on remote control stuck/dual key operation
Batteries in remote con­trol are flat
Filter is dirty/air inlet/ outlet opening is blocked by debris
Does it function correctly in the shade?
Does it function after removing potential sources of interference?
Does the "Transmitting" symbol appear on the display?
Have new batteries been inserted? Is the display incomplete?
Have the filters been cleaned?
Replace the remote con­trol
Place the receiver and/or transmitter unit in the shade
Signal is not transmitted when interference sources are operational
Release the key/only press one key
Insert new batteries
Clean the filters
Page 34
REMKO BL series
Malfunction Possible causes Checks Remedial measures
Condensate discharge on unit
Windows and doors open. Heating/cooling load has increased
Cooling mode is not set Does the cooling symbol
Fins on outdoor unit blocked by foreign objects
Leaking cooling cycle Are there signs of frost
Drainage pipe on collec­tion container clogged/ damaged
Faulty external conden­sate pump or float
Condensate has not drained away and has collected in the conden­sate drainage line
Have structural/usage modifications been made?
appear on the display?
Does the fan of the out­door unit work? Are the exchanger fins unob­structed?
on the exchanger fins of the indoor unit?
Can the condensate drain off without any obstruction?
Is the collection tray full of water and the pump not running?
Is there an incline on the condensate drainage line and is it clear?
Close windows and doors/install additional units
Correct the settings for the unit
Check the fan or winter fan speed control, reduce the air resistance
Repair by specialist
Clean the drainage pipe and collection container
Call out a specialist to replace the pump
Route the condensate drainage line with an incline and clean it
Condensate does not drain off
NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then you can switch off the breaker. Switch it back on again at least 12 hours before the next time that the unit will be required!
Are the condensate drainage lines clear and is there an incline? Are the condensate pump and liquid level switch functioning correctly?
Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced
34
Page 35
Fault display on the indoor unit
Display Error description
E0 Indoor unit overcurrent protection
E1 Ambient air probe fault
E2 Outdoor unit heat exchanger probe fault
E3 Indoor unit heat exchanger probe fault
E4 Fan speed control indoor unit disabled
E5 (5E) Communication error between indoor unit and outdoor unit
Eb EEPROM error, indoor unit
F0 Fan speed control outdoor unit disabled
F1 Power module protective function triggered
F2 Power factor correction filter fault (PFC), outdoor unit
F3 Overcurrent protection on the compressor
F4 Compressor outlet probe fault
F5 Compressor overheating protection switch triggered
F6 Outdoor unit air inlet probe fault
F7 Under and overvoltage protection triggered
F9 EEPROM error, outdoor unit
FA Circuit reversal probe defective
P2 High pressure fault
P3 Refrigerant level low
P4 Outdoor unit heat exchanger probe overtemperature
P5 Compressor outlet temperature probe overtemperature
P6 Indoor unit heat exchanger temperature probe overtemperature
P7 Indoor unit heat exchanger anti-freeze protection
P8 Outdoor unit overcurrent protection
For fault elimination refer to troubleshooting on the following pages.
35
Page 36
REMKO BL series

11.2 Indoor unit fault analysis

Fault E0: Indoor unit overcurrent protection
Check whether the power supply is present
and correct. Is this normal?
YES
Check all electrical connections. Are they
OK?
YES
Exchange the control boards of the indoor
unit.
Fault E1: Ambient air probe fault
Check the connection of the respective probe to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 15 kW at 25 °C.
YES
Replace the respective control board.
NO
NO Correct the electrical connections.
NO Establish a proper connection.
NO Replace the probe.
Switch the supply and try again as soon as
this is normal again.
Fault E2, E3: Outdoor unit / indoor unit heat exchanger probe fault
Check the connection of the respective probe to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 20 kW at 25 °C
YES
Replace the respective control board.
NO Establish a proper connection.
NO Replace the probe.
36
Page 37
Fault E4: Indoor unit fan speed disabled
Check the connection of the fan motor to the
circuit board. Is this correctly implemented?
YES
Measure the voltage between the yellow and
black cable when starting the air-conditioning
system. Does the voltage continuously
increase?
YES
Replace the fan motor.
Fault E5 (5E): Communication error between indoor unit and outdoor unit
Check the connecting line between the indoor
unit and outdoor unit. Is it properly con-
nected?
YES
Exchange the control boards of the indoor
unit. Is the fault still present?
YES
Exchange the control boards of the outdoor
unit.
NO Establish a proper connection.
NO Replace the indoor unit control board.
NO Establish a proper connection.
NO Error rectified.
Faults Eb and F9: EEPROM error
Switch the unit off for 5 seconds. Is the fault
still shown on the display?
YES
Is the EEPROM chip properly seated on the
circuit board?
YES
Replace the indoor unit or outdoor unit circuit
board.
NO Error rectified.
NO Insert the chip properly.
37
Page 38
REMKO BL series
Fault F0: Fan speed control outdoor unit disabled
Is the fan motor blocked by a foreign body YES Remove foreign body.
NO
Check all electrical connections. Are these
correctly implemented?
YES
Replace the outdoor unit circuit board. Is the
fault still present?
YES
Replace the fan motor.
Fault F1: Power module protective function triggered
Check all electrical connections to the com-
pressor. Are these correctly implemented?
YES
Are the refrigerant pressures in a normal
range?
YES
Replace the outdoor unit circuit board. Is the
fault still present?
NO Replace the connections.
NO Error rectified.
NO Replace the connections.
NO
NO Error rectified.
Check the heat exchanger for contamination.
Check the cooling circuit.
YES
Replace the compressor.
Fault F2: Power factor correction filter fault (PFC), outdoor unit
Check all electrical connections on the control
board. Are these correctly implemented?
YES
Replace the outdoor unit circuit board.
NO Replace the connections.
38
Page 39
Fault F3: Overcurrent protection on the compressor
Check all electrical connections. Are these
correctly implemented?
YES
Check the compressor windings. Are they
OK?
YES
Exchange the control boards of the outdoor
unit
Fault F4: Compressor outlet probe fault
Check the connection of the respective probe to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 50 kW at 25 °C.
YES
Replace the respective control board.
NO Replace the connections.
NO Replace the compressor.
NO Establish a proper connection.
NO Replace the probe.
Fault F5: Compressor overtemperature has tripped
Check the indoor unit and outdoor unit heat
exchangers for cleanliness. Is the air
exchange guaranteed?
YES
Switch the unit off for 10 minutes. Check
whether the unit starts up again normally.
YES
Check the fill level of the refrigerant. Is this
correct?
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
NO Clean the respective heat exchanger.
NO
NO
Check all electrical connections and the heat
gas probe.
Check the unit for leaks and fill with new
refrigerant.
39
Page 40
REMKO BL series
Fault F6: Outdoor unit air inlet probe fault
Check the connection of the respective probe to the circuit board. Are these correctly imple-
mented?
YES
NO Establish a proper connection.
Check the resistance of the probe. Is the
measured value plausible? 15 kW at 25 °C.
YES
Replace the respective control board.
Fault F7: The outdoor unit overvoltage or undervoltage protection has tripped
Check whether the power supply is present
and correct. Is this normal?
YES
Check all electrical connections. Are they
OK?
YES
Exchange the control boards of the outdoor
unit.
NO Replace the probe.
NO
NO Correct the electrical connections.
Switch the supply and try again as soon as
this is normal again.
Fault FA: Circuit reversal probe fault
Check the connection of the respective probe to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 20 kW at 25 °C.
YES
Replace the respective control board.
NO Establish a proper connection.
NO Replace the probe.
40
Page 41
Fault P2: High pressure fault
Check the heat exchanger of the outdoor unit
and indoor unit. Are the heat exchangers
clean?
YES
Are the corner shut-off valves open? NO Open corner shut-off valves
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
Fault P3: Refrigerant level low
Are the corner shut-off valves open? NO Clean the heat exchangers.
NO Clean the heat exchangers.
YES
Check the joints of the refrigerant circuit for
leaks. Are oily areas present?
NO
Perform an overpressure leak test. Is the
cooling circuit tight?
YES
Extract the refrigerant and check the refrig-
erant fill quantity. Refill the refrigerant to the
appropriate fill quantity.
Fault P4: Outdoor unit heat exchanger probe overtemperature
Check the heater exchanger of the outdoor
unit. Is the heat exchanger clean?
YES
Is the fan motor working correctly? NO Check fan motor.
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
YES
NO
NO Clean the heat exchangers.
Rectify the leak. Adjust the refrigerant quan-
tity.
41
Page 42
REMKO BL series
Fault P5: Compressor outlet probe overtemperature
Check the heater exchanger of the outdoor
unit. Is the heat exchanger clean?
YES
Is there a lack of refrigerant? YES
NO
Check the current consumption and winding
resistances of the compressor and replace it if
necessary.
Fault P6: Indoor unit heat exchanger probe overtemperature
Check the heat exchanger and air filter on the
indoor unit. Are the heat exchanger and filter
clean?
NO
Check the function of the fan motor.
NO Clean the heat exchangers.
YES Clean heat exchanger and filter.
Rectify the leak. Adjust the refrigerant quan-
tity.
Fault P7: Indoor unit heat exchanger probe anti-freeze protection
Is the room temperature below 4 °C? YES Increase room temperature
NO
Check the heat exchanger and air filter on the
indoor unit. Are the heat exchanger and filter
clean?
NO
Check the function of the fan motor.
Fault P8: Outdoor unit overcurrent protection
Check all electrical connections. Are these
correctly implemented?
YES
Check the compressor windings. Are they
OK?
YES
Exchange the control boards of the outdoor
unit.
YES Clean heat exchanger and filter.
NO Replace the connections.
NO Replace the compressor.
42
Page 43

12 Care and maintenance

Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
DANGER!
Prior to performing any work, ensure the equip­ment is disconnected from the voltage supply and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
n Clean the fins on the unit prior to long shut-
down periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an appropriate specialist firm.
This enables you to ensure the operational reli­ability of the plant at all times!
NOTICE!
Statutory regulations require an annual leak test for the cooling cycle dependant on the refrig­erant quantity. Inspection and documentation of the work performed is to be carried out by spe­cialist technicians.
Type of task
Checks/maintenance/inspection
General
Check voltage and current
Check function of compressor/fans
Dirt on condenser/evaporator
Check refrigerant fill quantity
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
See note
Commis-
sioning
l
l
l
l l
l
l
l
l
l
Monthly
Every 6 months
l
l
Yearly
l
l
l
l
l
1)
l
43
Page 44
REMKO BL series
Cleaning the housing
1. Disconnect the power supply to the unit.
2. Open and fold the air inlet grill on the front
side upwards.
3. Clean the grill and cover with a soft, damp cloth.
4. Switch the power supply back on.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially dirty.
Cleaning the filter
1. Disconnect the power supply to the unit.
2. Open the front side of the unit by folding the
grill upwards and allowing it to engage (Fig. 34).
3. Raise the filter and pull it out in a downwards direction (Fig. 34).
4. Clean the filter with a commercially available vacuum cleaner (Fig. 35). To do so, turn the dirty side so it is facing upwards.
5. Dirt can also be removed by carefully cleaning with lukewarm water and mild cleaning agents (Fig. 36). The dirty side should be face down.
6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
7. Carefully insert the filter. Ensure that it locates correctly.
8. Close the front side as described above in reverse order.
9. Switch the power supply back on.
10. Switch the unit back on.
Fig. 34: Folding the grill upwards
Fig. 35: Cleaning with a vacuum cleaner
Cleaning the condensate pump (accessories)
The indoor unit may contain an optional integrated or separate condensate pump, which pumps out any accumulated condensate into higher posi­tioned drains.
Observe the care and maintenance instructions in the separate operating manual.
Fig. 36: Cleaning with lukewarm water
44
Page 45

13 Shutdown

Temporary shutdown
1. Let the indoor unit run for 2 to 3 hours in
recirculation mode, or in cooling mode at maximum temperature, to extract any residual humidity from the unit.
2. Shut down the system using the remote con­trol.
3. Switch off the electrical power supply to the unit.
4. Cover the unit as far as possible with plastic foil in order to protect it from the influences of weather.
Permanent shutdown
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
45
Page 46
REMKO BL series

14 Spare parts list and exploded view

The continuous further development of REMKO products sometimes involve adjustments to spare parts within a unit series which are linked to each production batch.
To ensure the correct delivery of spare parts, unit series number information is therefore required (see name plate).
The following QR code takes you to the input field on our website.
Alternatively, the following address can also be entered directly into your web browser:
www.remko.de\ersatzteil-suche\
In both cases, you are taken to the following search screen in which the serial number can then be entered.
46
Page 47

15 Index

C
Care and maintenance ................... 43
Cleaning
Air filter for indoor unit ................. 44
Condensate pump ....................44
Housing ............................ 44
Condensate drainage connection and safe
drainage .............................. 24
Condensate pump, electrical wiring diagram ... 28
Customer service ....................... 33
D
Disposal of equipment .....................8
E
Electrical drawings ................... 29, 30
Electrical wiring ......................... 26
Electrical wiring diagram .................. 27
Electrical wiring diagram, condensate pump ... 28
Environmental protection ...................8
Exploded view ..........................46
F
Fault display on the indoor unit ............. 35
Function test of the cooling and heating modes 32
Functional checks ....................... 31
I
Infrared remote control ................... 13
Installation
Strip foundation ...................... 24
Installation location, selection .............. 18
Installation materials ..................... 17
Intended use ............................ 7
K
Keys on the remote control ................ 14
M
Maintenance ........................... 43
Malfunctions
Checks .............................33
Possible causes ...................... 33
Remedial measures ................... 33
Manual mode .......................... 13
Minimum clearances ..................... 19
P
Propellant in accordance with Kyoto Protocol .. 10
Q
Quick-release couplings .................. 22
R
Remote control
Keys ...............................14
S
Safe drainage in the event of leakages ....... 25
Safety
Dangers of failure to observe the safety
notes ............................... 5
General ............................. 5
Identification of notes ................... 5
Instructions for the operator .............. 6
Note for inspection work .................6
Note for installation work ................ 6
Note for maintenance work .............. 6
Personnel qualifications ................. 5
Safety-conscious working ................6
Unauthorised modification ...............7
Unauthorised replacement part manufacture . 7
Selection of installation location ............ 18
Shutdown
Permanent .......................... 45
Temporary .......................... 45
Spare parts list and exploded view .......... 46
Spare parts lists ........................ 46
T
Test run ............................... 31
Troubleshooting and customer service ....... 33
U
Unit installation ......................... 21
V
View of the unit ......................... 46
W
Wall bracket ........................... 21
Wall opening ........................... 17
Warranty ............................... 7
47
Page 48
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Hotline within Germany
+49 (0) 5232 6 06-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...