2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions............................................................................................................................. 11
3Design and function............................................................................................................................ 12
Carefully read the operating manual before commissioning the units or their components for the
first time. It provides useful tips and notes such as
hazard warnings to prevent injury and material
damage. Failure to follow the directions in this
manual can endanger persons, the environment
and the equipment itself or its components and will
void any claims for liability.
Store this manual and the information required for
the operation of this system (e.g. refrigerant datasheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If
applicable, observe the local safety conditions.
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger, which if not avoided may be fatal or
cause serious injury.
WARNING!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury.
Warning of inflammable substances!
1.2 Identification of notes
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or material and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient
and fault-free operation.
1.3 Personnel qualifications
DANGER!
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
Personnel responsible for commissioning, operation, maintenance, inspection and installation must
be able to demonstrate that they hold a qualification which proves their ability to undertake the
work.
1.4 Dangers of failure to observe
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
5
Page 6
REMKO BL series
In particular, failure to observe the safety notes
may pose the following risks:
n The failure of important unit functions.
n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.
1.5 Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
1.6 Safety instructions
for the operator
The operational safety of the units and components is only assured providing they are used as
intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified personnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in
operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury.
n The units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Otherwise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commissioning may lead to water leaks, electric
shocks or fire. Commissioning must take place
as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components
independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same
room.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear.
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and
fully functional at least once yearly. Visual
inspections and cleaning may be performed by
the operator when the units are disconnected
from the mains.
1.7 Safety notes for installation,
maintenance and inspection
n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety
conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling circuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use
of non-standardised components may result in
water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply, leaks may
result in the room filling with a flammable mixture!
The minimum room size of 4 m2 required for
installation and storage pertains to the basic fill
quantity of the unit. This varies according to the
installation type and total fill quantity of the
system. The calculation must take place in
accordance with valid DIN standards. Make
sure that the installation site is suitable for safe
unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are
operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant.
Never solder or grind unit components!
n Note that refrigerant may be odourless.
n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry
room. If the humidity is too high, this can cause
short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate
drainage of condensate can lead to water
damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber
of industry and commerce, which confirms their
ability to work with refrigerant.
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when performing installation, repair, maintenance or
cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a
detachable, reusable connection is not permissible.
1.8 Unauthorised modification
and changes
1.10 Warranty
For warranty claims to be considered, it is essential
that the ordering party or its representative complete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
1.11 Transport and packaging
The devices are supplied in a sturdy shipping container. Please check the equipment immediately
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety. The
use of other parts may invalidate liability for
resulting consequences.
1.9 Intended use
Depending on the model, the units and the additional fittings with which they are equipped are only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed space.
Any different or additional use is a non-intended
use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use.
The user bears the sole risk in such cases.
Intended use also includes working in accordance
with the operating and installation instructions and
complying with the maintenance requirements.
The threshold values specified in the technical
data must not be exceeded.
7
Page 8
REMKO BL series
1.12 Environmental protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved
collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not disposed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner, e.g. using certified firms and recycling specialists or at collection points.
8
Page 9
2 Technical data
2.1 Unit data
SeriesBL 264 DCBL 354 DC
Operating mode
Nominal cooling output
1)
Energy efficiency ratio SEER
1)
kW2.7 (0.6-3.8)3.5 (0.8-4.1)
Inverter wall-mounted room air conditioning unit
combination for cooling and heating
6.206.19
El. power consumption, coolingkW0.8 (0.1-1.6)1.18 (0.1-1.6)
El. current consumption, coolingA3.8 (0.7-7.8)5.6 (0.7-7.8)
Power consumption, annual, QCE
Energy efficiency ratio, cooling
Nominal heat capacity
2)
Energy efficiency ratio SCOP
3)
1)
kWh148198
A++
kW3.0 (0.8-4.2)3.8 (1.0-4.2)
4)
4.0
El. power consumption, heatingkW0.85 (0.3-1.6)1.10 (0.3-1.6)
El. current consumption, heatingA4.1 (1.5-8.0)4.9 (1.5-8.0)
Power consumption, annual, QHE
Energy efficiency ratio, heating
3)
1)
kWh938
A+
Max. power consumptionkW1900
Max. current consumptionA9.5
EDP no.16292681629360
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO BL series
Data specific to indoor unitBL 264 DC ITBL 354 DC IT
Application area (room volume), approx.
Adjustment range, room temperature°C+17 to +30
m
3
80110
Air flow volume per stage
Sound pressure level per stage
m3/h
5)
dB (A)29/35/4228/31/41
400/500/600
Sound pressure level, silent modedB (A)18920
Sound power level max.dB(A)5453
Enclosure classIPIPX0
Condensate drainage connectionmm16
Dimensions: H/W/Dmm292/792/201
Weightkg8.5
EDP no.16292701629362
5)
At distance of 1m in the open air; specified values are maximum values
Data specific to outdoor unitBL 264 DC ATBL 354 DC AT
Power supply
V/Ph/
Hz
230/1~/50
Operating range, cooling°C+5 to +48
Operating range, heating
7)
°C+5 to +32
Air flow rate, max.
m3/h
600
Enclosure classIPIP24
Sound power level max.dB (A)6162
Sound pressure level
Refrigerant
6)
5)
dB (A)5354
R32
Refrigerant, basic quantitykg0.56
CO2 equivalentt0.378
Operating pressure, max.kPa4300/25004150/1150
Refrigerant piping, max. lengthm3, 5, 8
Refrigerant piping, max. height differencem5
Dimensions: H/W/Dmm530/705/279
Weightkg22.5
EDP no.16292691629361
5)
At distance of 1m in the open air; specified values are maximum values
6)
Contains greenhouse gas according to Kyoto protocol, GWP 2088
7)
This can be extended to -20 °C with the appropriate accessory kit
10
Page 11
2.2 Unit dimensions
D
E
B
A
C
B
A
C
Outdoor units
Fig. 1: Outdoor unit dimensions BL 264-354 DC AT
Measurements (mm)ABCDE
BL 264-354 DC AT798535280480282
Indoor units
Fig. 2: Indoor unit dimensions BL 264-354 DC IT
Measurements (mm)ABC
BL 264-354 DC IT792290202
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
11
Page 12
21
4
3
2
1
4
3
5
7
8
9
6
1
7
8
9
B
A
4
3
5
6
2
3
5
REMKO BL series
3 Design and function
Unit description
The BL 264-354 DC room air conditioners have a
REMKO BL...AT outdoor unit as well as a BL...IT
indoor unit.
In cooling mode, the outdoor unit serves to output
the heat extracted by the indoor unit from the room
being cooled. In heating mode, the heat taken up
by the outdoor unit can be discharged by the
indoor unit into the room to be heated. In both
operating modes, the output produced by the compressor precisely matches requirements, and
thereby regulates the nominal temperature with
minimal temperature deviations. This "inverter
technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor unit
can be installed in an outdoor area or, providing
that certain requirements are met, an indoor area.
The indoor unit is designed to be mounted high up
on the wall, in indoor areas. It is operated by an
infrared remote control.
The outdoor unit consists of a cooling cycle with
compressor, fin condenser, condenser fan,
reversing valve and throttle element. The outdoor
unit is controlled by the regulation of the indoor
unit.
The indoor unit consists of a fin evaporator, evaporator fan, controller and condensate tray.
Floor brackets, wall brackets, refrigerant piping and
condensate pumps are available as accessories.
3: Condensate drainage line
4: Condenser fan
5: Power supply cable
6: Shut-off valve
7: Suction pipe
8: Injection pipe
9: Control line
Refrigerant piping is used to connect the indoor
unit to the outdoor unit.
12
Page 13
4 Operation
max. 6 m
4.1 General notes
The indoor unit is easily operated using the
standard infrared remote control. The indoor unit
beeps to acknowledge the correct transmission of
data. If it is not possible to program the indoor unit
with the remote control, then it can also be manually operated.
Manual mode
The indoor unit can also be switched on manually
if the infrared remote control is lost/defective.
Manual operation is intended for emergency operation and is not suitable for basic unit operation.
Please replace the remote control. The key for
manual activation is located below the housing
cover on the right side.
The following settings apply for manual operation:
Pressing once: Automatic mode,
Pressing twice: Cooling mode,
Pressing three times: Unit OFF
Fig. 6: Maximum distance
Infrared remote control
The infrared remote control sends the programmed
settings a distance of up to 6 m to the receiver of
the indoor unit. Data will only be received correctly
if the remote control is pointed at the receiver and
no objects are obstructing the transmission path.
Two AAA batteries must be inserted into the
remote control in preparation. To do so, remove
the flap from the battery compartment and insert
the batteries the correct way around (see markings). Removing the batteries causes all stored
data to be lost. The remote control will then access
the default settings, which you are free to customise at any time.
Alarms are indicated by a code (see chapter
Troubleshooting and customer service).
NOTICE!
Immediately replace flat batteries with a new
set, otherwise there is a risk of leakage. It is
recommended that the batteries are removed if
the equipment is shut down for longer periods.
Help save on energy consumption in stand-by
mode! If the device, system or component is not
in use, we recommend disconnecting the power
supply. Components with a safety function is
excluded from our recommendation!
13
Page 14
1
1
10
7
6
9
8
5
2
3
4
1
2
3
4
5
6
7
REMKO BL series
4.2 Display on indoor unit
The display illuminates according to the settings.
Fig. 7: Display on indoor unit
1: Display
4.3 Keys on the remote control
"ON/OFF" key (ON/OFF)
This key switches the room air conditioner on and
off.
"MODE" key (operating mode)
This key is used to set the desired operating mode.
The automatic, cooling, dehumidification, heating
and recirculation modes are available.
"TIMER" key (switch-on/switch-off delay)
Pressing this key activates the switch-on/switch-off
delay. The delay time can be set in 0.5 second
increments (30 minutes).
"+" and "–” key (up arrow / down arrow)
Using these keys, the setpoint can be decreased
or increased in 1 °C increments. The keys are also
used to set various functions.
"SPEED” key (fan speed)
Press this key to set the desired fan speed. The
low, medium, high, turbo and automatic functions
are available. A high fan speed enables higher performance, quicker circulation of the room air and
larger casting distances, but at the cost of noise
development and air speed (draught phenomena).
Fig. 8: Keys on the remote control
In “Recirculation” mode, the “automatic” stage
cannot be used.
In the dehumidification mode, the fan speed
cannot be set manually.
“COOL” key (cooling pre-setting)
“HEAT” key (heating pre-setting)
This activates the self-clean function on the unit.
14
Page 15
8
9
10
“MENU / OK” key (additional functions / con-
firm)
After pressing this key, an additional function can
be activated using the “+” (up arrow), “-” (down
arrow) “L/R SWING” (left arrow) and “U/D SWING”
(right arrow) keys. The selected function flashes in
the display and can be activated or deactivated by
pressing the “OK” key. The following functions are
available:
HEALT
Using this key, the REMKO BioClean function (ionisation) can be activated which contributes to
improving the room air quality.
ECO (energy saving mode)
After activation of energy saving mode, the controller lowers the compressor frequency to a minimum in order to save energy. Energy saving mode
is automatically deactivated after 8 hours and is
only available in cooling mode.
SLEEP
Pressing this key will automatically increase or
decrease the target temperature by 1 °C within an
hour in cooling mode and heating mode respectively. Press this key to maintain the most convenient temperature and save energy.
This function is only available in "Cooling",
"Heating" and "Auto" modes. The unit goes back
into its original state after 10 hours.
SILENCE (quiet operation)
Activates/deactivates the silent mode.
In silent unit mode, the compressor runs at a lower
frequency, and the indoor unit fan rotates at a
slower speed. This provides particularly quiet unit
operation.
ELE.H
DISPLAY (display switch-off)
Activating this function switches the display indicators on the indoor unit.
LIGHT
This function is not available.
ELE.H
This function is not available.
I-FEEL
This key can be used to activate/deactivate the IFEEL function. In this mode, the room temperature
is measured on the remote control. This sends a
signal to the indoor unit every 3 minutes. If the
remote control does not send a signal to the indoor
unit for 7 minutes, this mode is automatically deactivated.
Anti-F
This function is not available.
iCLEAN (self-cleaning)
Due to the formation of condensate on the heat
exchanger and the residual moisture that remains,
bacteria can multiply quickly. In regular normal
operation, the heat exchanger is dried by the air
volume flow.
This drying process can also be started manually
with the “Clean” function (for example, if the unit is
not in regular use). In cooling or dehumidification
mode, the self-cleaning function can be activated.
The unit switches off automatically after cleaning
(30 minutes). "CL" appears in the display indicator.
Selection of the self-cleaning function is only possible in standby mode.
"L/R SWING" key
This function is not available.
"U/D SWING" key
The oscillation of the horizontal fins can be set
using this key. This function can be switched on
and off by pressing the key.
15
Page 16
10
9
5
1
2
3
4
6
7
8
1
2
3
4
5
6
7
8
9
10
REMKO BL series
Indicators on the LCD
Fig. 9: Indicators on the LCD
RUN
This symbol appears when the "ON/OFF" key is
pressed and the system is activated. Pressing this
key again causes the indicator to go out.
Key lockIs displayed if key lock is activated.
I-FEEL
Is displayed when the temperature probe on the
infrared remote control is activated.
Operating mode indicator
Shows the current operating modes, including
automatic (AUTO), cooling (COOL), dehumidification (DRY), heating (HEAT), fan (FAN) and back to
automatic (AUTO) mode.
Temperature indicators
Shows the set temperature setpoint. If fan (FAN)
mode is set, no temperature is displayed.
Additional function indicators
Shows the activated additional functions (see keys
on the remote control).
Swing fins
Shows the position of the horizontal and vertical
swing fins.
Timer function
Displays when switch-on delay ON is active and
when switch-off delay OFF is active. Furthermore,
a set time is displayed in 0.5 second increments.
Fan speed
Shows the set fan mode and the current fan stage
(see keys on the remote control).
Data transfer
Flashes when data is sent from the infrared remote
control to the indoor unit.
16
Page 17
5 Installation instructions for qualified personnel
215
34
5.1 Important notes prior to installation
n Transport the unit in its original packaging as
close as possible to the installation location.
You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible transport damage. Report any damage immediately
to your contractual partner and the shipping
company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connections.
n The refrigerant piping (liquid and suction pipe),
valves and connections must be insulated to
make them vapour diffusion proof. If necessary
also insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet
(see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal
radiation. Installation in the vicinity of thermal
radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltration of moisture and never kink or compress
the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and
ensures that the compressor oil can flow back
without obstruction.
n Perform all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals, otherwise there is a
risk of fire.
n Only use the fasteners contained in the scope
of delivery with the units.
n Use four supports and the associated hooks to
attach the ceiling cassette (only applies to
ceiling cassettes).
n Use the insulated condensate hose in the
scope of delivery as a junction piece to the
continuing condensate drain. Secure the condensate drain with the supplied clamps.
5.2 Wall openings
n A wall opening of at least 65 mm diameter and
10mm incline from the inside to the outside
must be created.
n To prevent damage to the lines, the interior of
the wall opening should be padded or, for
example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall
opening, taking account of fire protection regulations (provided by the customer). Do not use
cement or lime containing substances!
Fig. 10: Wall opening
1: Liquid line
2: Control line
3: Condensate drainage line
4: Suction pipe
5: PVC pipe
5.3 Installation materials
The indoor unit is attached to the wall by a wall
bracket and 4 screws (to be provided by the customer).
The outdoor unit is attached by 4 screws and a
wall bracket to the wall or fixed by a floor bracket to
the ground.
17
Page 18
1
20 cm
1
REMKO BL series
5.4 Selection of installation
location
Indoor unit
The indoor unit is designed for horizontal wall
installation above doors. However, it can also be
used in the upper wall area (min. 1.75m above the
floor).
Outdoor unit
The outdoor unit is designed for horizontal installation on a base in outdoor areas. The installation
site must be level, flat and firm. The unit should
also be secured to prevent it from tipping over. The
outdoor unit can be set up outside as well as inside
a building. For external installation, please observe
the following notes to protect the unit from the
influence of the weather.
Rain
For floor or roof set-up, the unit should be installed
with at least 10cm ground clearance. A floor
bracket is available as an optional accessory.
Wind
If the unit is being installed in windy areas, ensure
that the warm outlet air is discharged in the prevailing wind direction. If this is not the possible, it
may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak
does not adversely affect the air intake to the unit.
An additional stabilization is recommended. This
can, for example, be realized with ropes or other
structures.
Fig. 11: Windbreak
1: Wind
Sun
The condenser on the outdoor unit emits heat.
Exposure to sunlight further increases the temperature of the fins and reduces the heat released by
the finned heat exchanger. The outdoor unit should
be installed on to the north side of the building
whenever possible. If necessary, take measures to
provide sufficient shade (responsibility of customer). One possible solution is to build a small
roofed area over the unit. These measures should
not affect the flow of warm outlet air.
Snow
The unit should be wall-mounted in areas of heavy
snowfall. Installation should be at least 20cm
above the expected level of snow to prevent snow
from entering the outdoor unit. An optional wall
bracket is available as an accessory.
Fig. 12: Minimum clearance to snow
1: Snow
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts,
adjoining rooms or halls (Fig. 13).
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being
installed in the room and which can compensate any additional pressure loss in ventilation
ducts (Fig. 13).
n Comply with any regulations and conditions
affecting the statics of the building. If necessary, fit acoustic installation.
18
Page 19
2
1
K
3
W
3
Fig. 13: Installation inside buildings
2
1
e
c
a
b
f
AB
2
1
a
b
c
d
e
K: Cold fresh air / W: Warm air
1: Outdoor unit / 2: Additional fan
3: Air shaft
5.5 Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air
distribution.
Fig. 14: Minimum clearances of the indoor unit and outdoor unit
A: Indoor unit
B: Outdoor unit
Indoor unitsOutdoor units
Measure-
ments (mm)
BL 264-354 DC ITBL 264-354 DC AT
1: Air inlet
2: Air outlet
a120300
b15002000
c120600
d-300
e120600
f200-
19
Page 20
C
B
C
A
B
A
REMKO BL series
5.6 Connection variants for the indoor unit
The following connection variants can be used for the refrigerant, condensate and control lines.
Fig. 15: Connection variant (view from the rear)
A: Infeed of the refrigerant piping at the wall, left
B: Outlet through the wall, right
C: Outlet on the wall, right
20
Page 21
5.7 Wall bracket for the indoor unit
AB
D
G
C
E
F
Fig. 16: Mounting points for the wall bracket BL 264-354 DC IT (rear view, all dimensions in mm)
Unit type / dimensions
BL 264-354 DC IT3714215045216526266
(All dimensions in mm)
The diameter of the pipe break-through is 65 mm for all unit types.
The wall bracket for the units must be attached with suitable screws and anchors.
ABCDEFG
6 Installation
6.1 Installation of the indoor unit
The indoor unit is attached by means of a wall
bracket, taking into consideration the air outlet side
located in the lower part.
1.Mark the mounting points on the structurally
permissible building sections according to the
dimensions of the wall bracket.
2.If necessary, remove the break out opening
of the housing.
3.Connect the refrigerant piping, electrical
cables and condensate drainage line to the
indoor unit as described below.
4.Hang the indoor unit onto the wall bracket by
tilting it back slightly and by pressing the
bottom part of the unit against the bracket.
Fig. 17: Horizontal positioning
5.Check again that the unit is level. (Fig. 17)
The wall bracket for the units must be attached
with suitable screws and anchors.
21
Page 22
REMKO BL series
6.2 Connection of
refrigerant piping
The refrigerant pipes should be connected by the
customer on the right-hand side of the outdoor
component.
1.Use the wall or floor brackets to fit the out-
door unit against structural parts approved to
support the static load (refer to the installation instructions for the brackets).
2.Ensure that structure-borne sound is not
transferred to parts of the building. Use vibration dampers to reduce the effects of structure-borne sound!
NOTICE!
Installation should only be performed by authorised specialists.
CAUTION!
6.3 Connection of
quick-release couplings
The refrigerant pipes should be connected by the
customer on the right-hand side of the outdoor
component. The pre-filled refrigerant piping are
connected to the outdoor unit by means of the
quick-connector system. Once installed, the connections should be insulated to make them vapour
diffusion proof. The following instructions describe
the installation of the refrigerant piping for the
indoor unit on the outdoor unit.
Please note that the following figures are only
schematic representations. The actual appearance of the units may vary from those shown.
1.Remove the pre-installed plastic cover from
the outdoor unit(Fig. 19).
Both units are pre-filled with refrigerant at the
factory. Suitable protective clothing must be
worn during installation.
NOTICE!
Use only tools which are approved for use in an
HVAC environment.
The refrigerant piping on the indoor unit are
extended at the factory so that the quick-release
couplings can be located outside the building if
they are fed through the masonry.
Fig. 19: Remove the plastic cover
2.Remove the green/black protective caps from
the quick-connectors on the outdoor component, as well as the flexible refrigerant pipes
on the indoor unit (Fig. 20 and Fig. 21).
Fig. 18: Placing of the quick-release couplings
Fig. 20: Remove protective caps
22
Page 23
Fig. 21: Remove protective caps
2
1
3.Before connecting the refrigerant pipes,
ensure that the quick-release couplings are
situated in front of one another (Fig. 22).
Fig. 24: Tightening the fitting
1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner
7.Open the stop cocks with an Allen key before
switch the system on!
Fig. 22: Position of the quick-release couplings
4.First connect and hand-tighten the refrigerant
piping to ensure it is correctly seated.
5.Then install the suction pipe with the largest
diameter.
Fig. 23: Installation on the indoor unit
Pipe dimension
in inches
1/4"15-20
3/8"33-40
CAUTION!
Only open the stop cocks following complete
installation of the quick-release couplings and
before switching the system on!
Tightening torque in Nm
6.Then tighten the fittings with 2 appropriately-
sized open-ended spanners. Use one
spanner to counter the force when tightening
the fitting (Fig. 24).
23
Page 24
3
2
4
9
55
11
100
6
8
7
1010
1212
1
REMKO BL series
6.4 Leak testing
Once all the connections have been made, the
pressure gauge station is attached to the Schrader
valve as follows (if fitted):
red = small valve = high pressure
blue = large valve = suction pressure
Leak testing involves spraying a leak detection
spray onto the connections. If bubbles are visible,
the connections have not been made properly.
Then tighten the screw connection.
NOTICE!
The escape of refrigerant contributes to climatic
change. In the event of escape, refrigerant with
a low greenhouse potential has a lesser impact
on global warming than those with a high
greenhouse potential. This device contains
refrigerant with a greenhouse potential of 2088.
That means the escape of 1 kg of this refrigerant has an effect on global warming that is
2088 times greater than 1 kg CO2, based on
100 years. Do not conduct any work on the
refrigerant circuit or dismantle the device always enlist the help of qualified experts.
7 Condensate drainage
connection and safe
drainage
Fig. 25: Condensate drainage, seepage of condensate and strip foundation (cross-section)
1:Outdoor unit
2:Leg
3:Condensate collection tray
4:Floor bracket
5:Reinforced strip foundation
H x W x D = 300 x 200 x 800 mm
6:Gravel layer for seepage
7:Condensate drainage heating
8:Drainage channel
9:Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60°C)
10: Frost line
11: Drainage pipe
12: Soil
24
Page 25
EB
B
A
D
C
11
1
5
5
8
1
9
3
Fig. 26: Dimensions for the strip foundation (bird's
min. 2%
eye view)
For the designations of 1,3,5,8,9 and 11, please
refer to the legend for Fig. 25
Dimensioning of the strip foundation
Dimen-
Value in mm
sion
A800
B200
C480
D282
E280
Fig. 27: Condensate drainage connection - Indoor
unit
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the following list of requirements from regional regulations and laws.
NOTICE!
Local regulations or environmental laws, for
example the German Water Resource Law
(WHG), can require suitable precautions to protect against uncontrolled draining in case of
leakage to provide for safe disposal of escaping
refrigerator oil or hazardous media.
Condensate drainage connection
If the temperature falls below the dew point, condensation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
NOTICE!
If condensate is removed via a duct in accordance with DIN EN 1717, ensure that any microbiological contamination present on the wastewater side (bacteria, fungi, viruses) cannot
enter the unit connected to it.
underside of the unit to drain any condensate.
n The condensate drainage line should have an
incline of min. 2% and is the responsibility of
the customer. If necessary, fit vapour-diffusionproof insulation.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost.
The lower part of the housing and condensate
tray is also to be kept frost free in order to
ensure permanent draining of the condensate.
If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
25
Page 26
2
1
4
3
1
REMKO BL series
8 Electrical wiring
8.1 General Information
A protected power supply cable is to be connected
to the outdoor unit and a five-core control line to
the indoor unit respectively.
DANGER!
All electrical installation work is to be performed
by specialist companies. Disconnect the power
supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regulations to dimension and to lay.
NOTICE!
The electrical connection of the units must be
carried out in accordance with VDE regulations.
We recommend using an FI circuit breaker that
is sensitive to all currents, as increased leakage
currents can occur.
The control line to the outdoor unit contains a data
cable which is used to establish communication
between the indoor unit and the outdoor unit. This
is used for controlling the cooling and heating
capacity and for forwarding alarm codes to the
indoor unit. If the length is insufficient, you can
extend the control lines on the indoor unit.
Make the connection as follows:
1.Open the panel of the unit.
2.Remove the covers on the right-hand side
(Fig. 28).
3.Feed the control line through the opening on
the rear of the unit in the connection area.
4.Connect the control line to the terminals
(Fig. 28).
5.Re-assemble the unit.
We recommend using shielded wires for the
control lines.
Check all plugged and clamped terminals to
verify that they are seated correctly and make
permanent contact. Tighten as required.
8.2 Connecting the indoor unit
n We recommend that a mains/repair switch be
installed near the outdoor unit.
n The terminal blocks for making the connections
are located at the rear of the unit. When the
unit is installed, measurements can be made
from the front by removing the cover.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may
be necessary to install an additional relay with
a higher contact rating after the switch-off contact on the pump to switch off the compressor.
Fig. 28: Connecting the indoor unit
1: Cover
2: Strain relief
3: Terminal block for control line
4: Control line from outdoor unit
26
Page 27
LO N S PE
A
N S PE
B
1
230 V/1~/50 Hz
LL LO
2
8.3 Outdoor unit connection
Proceed as follows to connect the line:
1.Remove the side-panel cover.
2.Choose the cable cross-section in accord-
ance with the relevant specifications.
3.Connect the lines as shown on the electrical
connection diagram.
8.4 Electrical wiring diagram
Connection BL 264-354 DC
4.Fix the line in the strain relief and re-
assemble the unit.
Fig. 29: Outdoor unit connection
Fig. 30: Electrical wiring diagram
A: Outdoor unit / B: Indoor unit1: Power supply cable / 2: Communication line
27
Page 28
NS PE
LONS PE
L
N
WH
BK
230 V/1~/50 Hz
1
3
2
A
B
LLLO
REMKO BL series
Connection of optional condensate pump KP 6/KP 8
Fig. 31: Electrical wiring diagram
A:Outdoor unit
B:Indoor unit
C:KP6/KP8 condensate pump
1:Power supply cable
2:Condensate pump supply
3:Condensate pump fault contact
BK: black
WH: white
28
Page 29
8.5 Electrical drawings
BN
YE/GN
RD
BK
BU
A
B
2
1
4
3
5
6
7
8
9
Indoor units BL 264-354 DC IT
Fig. 32: Electrical drawings
A: Indoor unit control board
B: Indoor unit connection block
1: Fan motor
2: Wi-Fi connection
3: Display circuit board
4: Horizontal swing motor
5: Not available
6: Ion generator
7: Transformer
8: Probe, evaporator
9: Room temperature probe
29
Page 30
A
B
2
1
4
3
5
CD
6
7
BN
BU
BK
RD
BU
BK
M
M
M
YE/GN
YE/GN
YE/GN
REMKO BL series
Outdoor units BL 264-354 DC AT
Fig. 33: Electrical drawings
A: Control board, outdoor unit
B: Outdoor unit connection block
C: Control line to indoor unit
D: Power supply cable
1: Not available
2: Fan motor
Perform the following checks prior to putting the
unit into operation for the first time and after any
work on the cooling cycle. Record the results in the
commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy
water.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct
polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.
10 Commissioning
NOTICE!
Commissioning should only be performed by
specially trained personnel and documented
after the certificate has been issued. Observe
the operating manuals for the indoor unit and
outdoor unit when commissioning the entire
system.
Once all the components have been connected
and tested, the system can be put into operation. A
functional check should be performed to verify its
correct function and identify any unusual operating
behaviour prior to handing it over to the operator.
NOTICE!
Check that the shut-off valves and valve caps
are tight after carrying out any work on the
cooling cycle. Use appropriate sealant products
as necessary.
Functional checks and test run
Check the following points:
n Leak-tightness of the refrigerant piping.
n Compressor and fan running smoothly.
n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not overheating. To measure the temperature, hold the
thermometer to the suction pipe and subtract
the boiling point temperature reading on the
pressure gauge from the measured temperature.
n Record the measured temperatures in the
commissioning report.
31
Page 32
REMKO BL series
Function test of the cooling and heating modes
1.Remove the protective caps from the valves.
2.Start the commissioning procedure by briefly
opening the shut-off valves on the outdoor
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3.Check all connections for leaks with leak
detection spray and suitable leak detectors.
4.If no leaks are found, fully open the shut-off
valves by turning them anti-clockwise using a
spanner. If leaks are found, remedy the faulty
connection. It is imperative that the vacuum
creation and drying steps are repeated.
5.Activate the main circuit breaker or fuse (to
be provided by the customer).
6.Use the remote control to switch on the unit
and select the cooling mode, maximum fan
speed and lowest target temperature.
7.Check the overheating, outside, inside, outlet
and vaporisation temperatures and record
the measured values in the commissioning
report. Check the correct function and settings of all regulation, control and safety
devices.
8.Check the unit control system using the functions described in the chapter "Operation".
Timer, temperature setting, fan speeds and
switching to ventilation or dehumidification
mode.
9.Check the correct function of the condensate
drainage line by pouring distilled water into
the condensate tray. A bottle with a spout is
recommended for pouring the water into the
condensate tray.
10.Switch the indoor unit to heating mode.
11.During the test run, check the functionality of
all of the previously described safety devices.
12.Record the measured values into the commissioning report and familiarise the operator
with the system.
13.Remove the pressure gauge. Check that
seals have been fitted in the sealing caps.
14.Re-install all disassembled parts.
32
Page 33
11 Troubleshooting and customer service
11.1 Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several
times to verify that they function correctly. However, if malfunctions do occur, please check the functions as
detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not
working correctly after all function checks have been performed!
Operational malfunctions
MalfunctionPossible causesChecksRemedial measures
The unit does not start or
switches itself off
Power failure, undervoltage, defective mains
fuse/main switch in OFF
position
Damaged power supply
cable
Wait time after switching
on is too short
Temperature outside
operating range
Electrical surges caused
by thunderstorms
Malfunction of the
external condensate
pump
Transmission distance
too far/receiver affected
by interference
Does all other electrical
equipment function correctly?
Does all other elec.
equipment function correctly?
Have approx. 5 minutes
elapsed since the
restart?
Are the fans in the indoor
unit and outdoor unit
working correctly?
Have there been lightning strikes in the area
recently?
Has the pump shut down
due to a malfunction?
Does the indoor unit
beep when pressing a
key?
Check the voltage and if
necessary, wait for it to
come back on
Repair by specialist firm
Schedule longer wait
times
Observe temperature
ranges of indoor unit and
outdoor unit
Switch off the mains
breaker and switch it
back on. Have it
inspected by a specialist
Check and if necessary
clean the pump
Reduce the distance to
less than 6 m or change
position
Remote control is faultyIs the unit running in
manual mode?
Receiver or transmitter
unit exposed to exces-
The unit does not
respond to the remote
control
The unit works at
reduced or no cooling
capacity
33
sive solar radiation
Electromagnetic fields
are interfering with transmission
Key on remote control
stuck/dual key operation
Batteries in remote control are flat
Filter is dirty/air inlet/
outlet opening is blocked
by debris
Does it function correctly
in the shade?
Does it function after
removing potential
sources of interference?
Does the "Transmitting"
symbol appear on the
display?
Have new batteries been
inserted? Is the display
incomplete?
Have the filters been
cleaned?
Replace the remote control
Place the receiver and/or
transmitter unit in the
shade
Signal is not transmitted
when interference
sources are operational
Release the key/only
press one key
Insert new batteries
Clean the filters
Page 34
REMKO BL series
MalfunctionPossible causesChecksRemedial measures
Condensate discharge
on unit
Windows and doors
open. Heating/cooling
load has increased
Cooling mode is not setDoes the cooling symbol
Fins on outdoor unit
blocked by foreign
objects
Leaking cooling cycleAre there signs of frost
Drainage pipe on collection container clogged/
damaged
Faulty external condensate pump or float
Condensate has not
drained away and has
collected in the condensate drainage line
Have structural/usage
modifications been
made?
appear on the display?
Does the fan of the outdoor unit work? Are the
exchanger fins unobstructed?
on the exchanger fins of
the indoor unit?
Can the condensate
drain off without any
obstruction?
Is the collection tray full
of water and the pump
not running?
Is there an incline on the
condensate drainage line
and is it clear?
Close windows and
doors/install additional
units
Correct the settings for
the unit
Check the fan or winter
fan speed control,
reduce the air resistance
Repair by specialist
Clean the drainage pipe
and collection container
Call out a specialist to
replace the pump
Route the condensate
drainage line with an
incline and clean it
Condensate does not
drain off
NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a
malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and
also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then
you can switch off the breaker. Switch it back on again at least 12 hours before the next time that the unit
will be required!
Are the condensate
drainage lines clear and
is there an incline? Are
the condensate pump
and liquid level switch
functioning correctly?
Route the condensate
drainage line with an
incline and clean it. If the
liquid level switch or the
condensate pump is
defective, have them
replaced
34
Page 35
Fault display on the indoor unit
DisplayError description
E0Indoor unit overcurrent protection
E1Ambient air probe fault
E2Outdoor unit heat exchanger probe fault
E3Indoor unit heat exchanger probe fault
E4Fan speed control indoor unit disabled
E5 (5E)Communication error between indoor unit and outdoor unit
EbEEPROM error, indoor unit
F0Fan speed control outdoor unit disabled
F1Power module protective function triggered
F2Power factor correction filter fault (PFC), outdoor unit
P4Outdoor unit heat exchanger probe overtemperature
P5Compressor outlet temperature probe overtemperature
P6Indoor unit heat exchanger temperature probe overtemperature
P7Indoor unit heat exchanger anti-freeze protection
P8Outdoor unit overcurrent protection
For fault elimination refer to troubleshooting on the following pages.
35
Page 36
REMKO BL series
11.2 Indoor unit fault analysis
Fault E0: Indoor unit overcurrent protection
Check whether the power supply is present
and correct. Is this normal?
YES
Check all electrical connections. Are they
OK?
YES
Exchange the control boards of the indoor
unit.
Fault E1: Ambient air probe fault
Check the connection of the respective probe
to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 15 kW at 25 °C.
YES
Replace the respective control board.
NO
NOCorrect the electrical connections.
NOEstablish a proper connection.
NOReplace the probe.
Switch the supply and try again as soon as
this is normal again.
Fault E2, E3: Outdoor unit / indoor unit heat exchanger probe fault
Check the connection of the respective probe
to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 20 kW at 25 °C
YES
Replace the respective control board.
NOEstablish a proper connection.
NOReplace the probe.
36
Page 37
Fault E4: Indoor unit fan speed disabled
Check the connection of the fan motor to the
circuit board. Is this correctly implemented?
YES
Measure the voltage between the yellow and
black cable when starting the air-conditioning
system. Does the voltage continuously
increase?
YES
Replace the fan motor.
Fault E5 (5E): Communication error between indoor unit and outdoor unit
Check the connecting line between the indoor
unit and outdoor unit. Is it properly con-
nected?
YES
Exchange the control boards of the indoor
unit. Is the fault still present?
YES
Exchange the control boards of the outdoor
unit.
NOEstablish a proper connection.
NOReplace the indoor unit control board.
NOEstablish a proper connection.
NOError rectified.
Faults Eb and F9: EEPROM error
Switch the unit off for 5 seconds. Is the fault
still shown on the display?
YES
Is the EEPROM chip properly seated on the
circuit board?
YES
Replace the indoor unit or outdoor unit circuit
board.
NOError rectified.
NOInsert the chip properly.
37
Page 38
REMKO BL series
Fault F0: Fan speed control outdoor unit disabled
Is the fan motor blocked by a foreign bodyYESRemove foreign body.
NO
Check all electrical connections. Are these
correctly implemented?
YES
Replace the outdoor unit circuit board. Is the
fault still present?
YES
Replace the fan motor.
Fault F1: Power module protective function triggered
Check all electrical connections to the com-
pressor. Are these correctly implemented?
YES
Are the refrigerant pressures in a normal
range?
YES
Replace the outdoor unit circuit board. Is the
fault still present?
NOReplace the connections.
NOError rectified.
NOReplace the connections.
NO
NOError rectified.
Check the heat exchanger for contamination.
Check the cooling circuit.
YES
Replace the compressor.
Fault F2: Power factor correction filter fault (PFC), outdoor unit
Check all electrical connections on the control
board. Are these correctly implemented?
YES
Replace the outdoor unit circuit board.
NOReplace the connections.
38
Page 39
Fault F3: Overcurrent protection on the compressor
Check all electrical connections. Are these
correctly implemented?
YES
Check the compressor windings. Are they
OK?
YES
Exchange the control boards of the outdoor
unit
Fault F4: Compressor outlet probe fault
Check the connection of the respective probe
to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 50 kW at 25 °C.
YES
Replace the respective control board.
NOReplace the connections.
NOReplace the compressor.
NOEstablish a proper connection.
NOReplace the probe.
Fault F5: Compressor overtemperature has tripped
Check the indoor unit and outdoor unit heat
exchangers for cleanliness. Is the air
exchange guaranteed?
YES
Switch the unit off for 10 minutes. Check
whether the unit starts up again normally.
YES
Check the fill level of the refrigerant. Is this
correct?
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
NOClean the respective heat exchanger.
NO
NO
Check all electrical connections and the heat
gas probe.
Check the unit for leaks and fill with new
refrigerant.
39
Page 40
REMKO BL series
Fault F6: Outdoor unit air inlet probe fault
Check the connection of the respective probe
to the circuit board. Are these correctly imple-
mented?
YES
NOEstablish a proper connection.
Check the resistance of the probe. Is the
measured value plausible? 15 kW at 25 °C.
YES
Replace the respective control board.
Fault F7: The outdoor unit overvoltage or undervoltage protection has tripped
Check whether the power supply is present
and correct. Is this normal?
YES
Check all electrical connections. Are they
OK?
YES
Exchange the control boards of the outdoor
unit.
NOReplace the probe.
NO
NOCorrect the electrical connections.
Switch the supply and try again as soon as
this is normal again.
Fault FA: Circuit reversal probe fault
Check the connection of the respective probe
to the circuit board. Are these correctly imple-
mented?
YES
Check the resistance of the probe. Is the
measured value plausible? 20 kW at 25 °C.
YES
Replace the respective control board.
NOEstablish a proper connection.
NOReplace the probe.
40
Page 41
Fault P2: High pressure fault
Check the heat exchanger of the outdoor unit
and indoor unit. Are the heat exchangers
clean?
YES
Are the corner shut-off valves open?NOOpen corner shut-off valves
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
Fault P3: Refrigerant level low
Are the corner shut-off valves open?NOClean the heat exchangers.
NOClean the heat exchangers.
YES
Check the joints of the refrigerant circuit for
leaks. Are oily areas present?
NO
Perform an overpressure leak test. Is the
cooling circuit tight?
YES
Extract the refrigerant and check the refrig-
erant fill quantity. Refill the refrigerant to the
appropriate fill quantity.
Fault P4: Outdoor unit heat exchanger probe overtemperature
Check the heater exchanger of the outdoor
unit. Is the heat exchanger clean?
YES
Is the fan motor working correctly?NOCheck fan motor.
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
YES
NO
NOClean the heat exchangers.
Rectify the leak. Adjust the refrigerant quan-
tity.
41
Page 42
REMKO BL series
Fault P5: Compressor outlet probe overtemperature
Check the heater exchanger of the outdoor
unit. Is the heat exchanger clean?
YES
Is there a lack of refrigerant?YES
NO
Check the current consumption and winding
resistances of the compressor and replace it if
necessary.
Fault P6: Indoor unit heat exchanger probe overtemperature
Check the heat exchanger and air filter on the
indoor unit. Are the heat exchanger and filter
clean?
NO
Check the function of the fan motor.
NOClean the heat exchangers.
YESClean heat exchanger and filter.
Rectify the leak. Adjust the refrigerant quan-
tity.
Fault P7: Indoor unit heat exchanger probe anti-freeze protection
Is the room temperature below 4 °C?YESIncrease room temperature
NO
Check the heat exchanger and air filter on the
indoor unit. Are the heat exchanger and filter
clean?
NO
Check the function of the fan motor.
Fault P8: Outdoor unit overcurrent protection
Check all electrical connections. Are these
correctly implemented?
YES
Check the compressor windings. Are they
OK?
YES
Exchange the control boards of the outdoor
unit.
YESClean heat exchanger and filter.
NOReplace the connections.
NOReplace the compressor.
42
Page 43
12 Care and maintenance
Regular care and observation of some basic points
will ensure trouble-free operation and a long
service life.
DANGER!
Prior to performing any work, ensure the equipment is disconnected from the voltage supply
and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based
cleaning products. Do not use a jet of water.
n Clean the fins on the unit prior to long shut-
down periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an
appropriate specialist firm.
This enables you to ensure the operational reliability of the plant at all times!
NOTICE!
Statutory regulations require an annual leak test
for the cooling cycle dependant on the refrigerant quantity. Inspection and documentation of
the work performed is to be carried out by specialist technicians.
Type of task
Checks/maintenance/inspection
General
Check voltage and current
Check function of compressor/fans
Dirt on condenser/evaporator
Check refrigerant fill quantity
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
See note
Commis-
sioning
l
l
l
ll
l
l
l
l
l
Monthly
Every 6
months
l
l
Yearly
l
l
l
l
l
1)
l
43
Page 44
REMKO BL series
Cleaning the housing
1.Disconnect the power supply to the unit.
2.Open and fold the air inlet grill on the front
side upwards.
3.Clean the grill and cover with a soft, damp
cloth.
4.Switch the power supply back on.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2
weeks. Reduce this interval if the air is especially
dirty.
Cleaning the filter
1.Disconnect the power supply to the unit.
2.Open the front side of the unit by folding the
grill upwards and allowing it to engage
(Fig. 34).
3.Raise the filter and pull it out in a downwards
direction (Fig. 34).
4.Clean the filter with a commercially available
vacuum cleaner (Fig. 35). To do so, turn the
dirty side so it is facing upwards.
5.Dirt can also be removed by carefully
cleaning with lukewarm water and mild
cleaning agents (Fig. 36). The dirty side
should be face down.
6.If water is used, let the filter dry out properly
in the air before fitting it back into the unit.
7.Carefully insert the filter. Ensure that it
locates correctly.
8.Close the front side as described above in
reverse order.
9.Switch the power supply back on.
10.Switch the unit back on.
Fig. 34: Folding the grill upwards
Fig. 35: Cleaning with a vacuum cleaner
Cleaning the condensate pump (accessories)
The indoor unit may contain an optional integrated
or separate condensate pump, which pumps out
any accumulated condensate into higher positioned drains.
Observe the care and maintenance instructions in
the separate operating manual.
Fig. 36: Cleaning with lukewarm water
44
Page 45
13 Shutdown
Temporary shutdown
1.Let the indoor unit run for 2 to 3 hours in
recirculation mode, or in cooling mode at
maximum temperature, to extract any
residual humidity from the unit.
2.Shut down the system using the remote control.
3.Switch off the electrical power supply to the
unit.
4.Cover the unit as far as possible with plastic
foil in order to protect it from the influences of
weather.
Permanent shutdown
Ensure that units and components are disposed of
in accordance with local regulations, e.g. through
authorised disposal and recycling specialists or at
collection points.
REMKO GmbH & Co. KG or your contractual
partner will be pleased to provide a list of certified
firms in your area.
45
Page 46
REMKO BL series
14 Spare parts list and exploded view
The continuous further development of REMKO products sometimes involve adjustments to spare parts
within a unit series which are linked to each production batch.
To ensure the correct delivery of spare parts, unit series number information is therefore required (see name
plate).
The following QR code takes you to the input field on our website.
Alternatively, the following address can also be entered directly into your web browser:
www.remko.de\ersatzteil-suche\
In both cases, you are taken to the following search screen in which the serial number can then be entered.