Remko ATY 266 DC, ATY 356 DC User guide

Page 1
Operating and installation instructions
REMKO ATY series
Designer wall units for cooling and heating
ATY 266 DC, ATY 356 DC
0232-2019-09 Edition 1, en_GB
Read the instructions prior to performing any task!
Page 2
Refrigerant
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Translation of the original
Page 3

Table of contents

1 Safety and usage instructions............................................................................................................. 5
1.1 General safety notes....................................................................................................................... 5
1.2 Identification of notes...................................................................................................................... 5
1.3 Personnel qualifications.................................................................................................................. 5
1.4 Dangers of failure to observe the safety notes................................................................................ 5
1.5 Safety-conscious working............................................................................................................... 6
1.6 Safety instructions for the operator................................................................................................. 6
1.7 Safety notes for installation, maintenance and inspection ............................................................. 6
1.8 Unauthorised modification and changes......................................................................................... 7
1.9 Intended use................................................................................................................................... 7
1.10 Warranty........................................................................................................................................ 7
1.11 Transport and packaging............................................................................................................... 7
1.12 Environmental protection and recycling........................................................................................ 8
2 Technical data........................................................................................................................................ 9
2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions............................................................................................................................. 12
3 Design and function............................................................................................................................ 13
3.1 Unit description............................................................................................................................. 13
4 Operation............................................................................................................................................. 14
4.1 General notes................................................................................................................................ 14
4.2 Display on indoor unit.................................................................................................................... 14
4.3 Keys on the remote control........................................................................................................... 15
5 Installation instructions for qualified personnel.............................................................................. 22
5.1 Important notes prior to installation............................................................................................... 22
5.2 Wall openings................................................................................................................................ 22
5.3 Installation materials..................................................................................................................... 22
5.4 Selection of installation location ................................................................................................... 23
5.5 Connection variants for the indoor unit......................................................................................... 24
5.6 Minimum clearances..................................................................................................................... 25
5.7 Connection of the indoor unit when the refrigerant piping is installed under the plaster............... 26
5.8 Wall bracket.................................................................................................................................. 27
5.9 Oil return measures....................................................................................................................... 27
6 Installation........................................................................................................................................... 27
6.1 Installation of the indoor unit......................................................................................................... 27
6.2 Connection of refrigerant piping.................................................................................................... 28
6.3 Additional notes on connecting the refrigerant piping................................................................... 31
6.4 Leak testing................................................................................................................................... 31
6.5 Adding refrigerant.......................................................................................................................... 32
7 Condensate drainage connection and safe drainage...................................................................... 32
8
Electrical wiring................................................................................................................................... 34
8.1 General notes................................................................................................................................ 34
8.2 Connecting the indoor unit............................................................................................................ 34
8.3 Outdoor unit connection................................................................................................................ 35
8.4 Electrical wiring diagram............................................................................................................... 35
8.5 Electrical drawings........................................................................................................................ 37
9 Before commissioning....................................................................................................................... 39
3
Page 4
REMKO ATY series
10 Commissioning................................................................................................................................... 39
1
1 Troubleshooting and customer service............................................................................................ 41
11.1 Troubleshooting and customer service........................................................................................ 41
11.2 Indoor unit fault analysis.............................................................................................................. 43
11.3 Resistances of the temperature probes...................................................................................... 54
12 Care and maintenance........................................................................................................................ 57
13 Shut-down............................................................................................................................................ 59
14 Exploded view and spare parts lists................................................................................................. 60
14.1 Exploded view - Indoor unit......................................................................................................... 60
14.2 Spare parts list - Indoor unit........................................................................................................ 61
14.3 Exploded view - Outdoor unit...................................................................................................... 62
14.4 Spare parts list - Outdoor unit..................................................................................................... 63
15 Index..................................................................................................................................................... 64
4
Page 5
1 Safety and
usage instructions

1.1 General safety notes

Carefully read the operating manual before com­missioning the units or their components for the first time. It provides useful tips and notes such as hazard warnings to prevent injury and material damage. Failure to follow manual can endanger persons, the environment and the equipment itself or its components and will void any claims for liability.
Store this manual and the information required for the operation of this system (e.g. refrigerant data­sheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.
the directions in this
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger cause serious injury.
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury
, which if not avoided may be fatal or
WARNING!
.
Warning of inflammable substances!

Identification of notes

1.2
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.
DANGER!
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.

1.3 Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Dangers of failure to observe
1.4 the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
5
Page 6
REMKO ATY series
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.

1.5 Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
Safety instructions
1.6 for the operator
The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Other­wise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commis­sioning may lead to water leaks, electric shocks or fire. Commissioning must take place as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same room.
.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
.

1.7 Safety notes for installation, maintenance and inspection

n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling cir­cuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use of non-standardised components may result in water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply result in the room filling with a flammable mix­ture!
The minimum room size of 4 m2 required for installation and storage pertains to the basic fill quantity of the unit. This varies according to the installation type and total fill quantity of the system. The calculation must take place in accordance with valid DIN standards. Make sure that the installation site is suitable for safe unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant. Never solder or grind unit components!
n Note that refrigerant may be odourless. n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry room. If the humidity is too high, this can cause short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate drainage of condensate can lead to water damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber of industry and commerce, which confirms their ability to work with refrigerant.
, leaks may
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units may only be secured or mounted on stable structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a detachable, reusable connection is not permis­sible.
, maintenance or

1.8 Unauthorised modification and changes

1.10 Warranty

For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
1.1

1 Transport and packaging

The devices are supplied in a sturdy shipping con­tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety use of other parts may invalidate liability for resulting consequences.
. The

1.9 Intended use

Depending on the model, the units and the addi­tional fittings with which they are equipped are only intended to be used as an air-conditioner for the purpose of cooling or heating the air in an enclosed space.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
7
Page 8
REMKO ATY series

1.12 Environmental protection and recycling

Disposal of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac­ture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not dis­posed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recy­cling specialists or at collection points.
8
Page 9

2 Technical data

2.1 Unit data

Series ATY 266 DC ATY 356 DC
Operating mode
Nominal cooling output
Energy efficiency ratio SEER
1)
1)
Electrical rated power consumption, cooling
Electrical rated current consumption, cooling
Power consumption, annual, QCE
Energy efficiency ratio, cooling
Nominal heat capacity
2)
Energy efficiency ratio SCOP
3)
1)
4)
Electrical rated power consumption, heating
Electrical rated current consumption, heating
Power consumption, annual, QHE
Energy efficiency ratio, heating
3)
2)
kW
1)
kW
1)
kWh 132 178
kW
2)
kW
2)
kWh 785 922
Inverter wall-mounted room air conditioner com-
bination for cooling and heating
2.64 (1.23-3.29) 3.51 (1.26-4.44)
6.7 6.1
0.71 1.21
A
3.10 5.25
A++
2.93 (0.85-3.72) 3.81 (1.1-4.36)
4.0
0.77 1.34
A
3.4 4.9
A+
Max. power consumption kW 2.20
Max. current consumption A 10.0
EDP no. 1624460 1624465
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO ATY series
Data specific to indoor unit ATY 266 DC IT ATY 356 DC IT
Application area (room volume), approx.
Adjustment range, room temperature °C +17 to +30
m
3
80 110
Air flow volume per stage
Sound pressure level per stage
Sound pressure level, Silent/Turbo mode
Sound power level max. dB(A) 50
Enclosure class IP X0
Condensate drainage connection mm 16
Dimensions: H/W/D mm 312/897/182
Weight kg 9.5 9.9
EDP no. 1624462 1624467
5)
At distance of 1 m in the open air; specified values are maximum values
5)
5)
m3/h
dB (A) 26/31/37 27/30/37
dB (A) 21/39 22/38
305/421/530 305/421/530
10
Page 11
Data specific to outdoor unit ATY 266 DC AT ATY 356 DC AT
Power supply V/Ph/Hz 230/1~/50
Operating range, cooling
Operating range, heating
7)
8)
°C +5 to +30
°C +5 to +50
Air flow rate, max.
m3/h
1900 2000
Enclosure class IP X4
Sound power level max. dB (A) 63
Sound pressure level
Refrigerant
6)
5)
dB (A) 54
R32
Refrigerant, basic quantity kg 0.80
CO2 equivalent t 0.54
Refrigerant, additional quantity >5 m g/m 20
Refrigerant piping, max. length m 25
Refrigerant piping, max. height m 10
Inches
Refrigerant connection, injection pipe
1/4 (6.35)
(mm)
Inches
Refrigerant connection, suction pipe
3/8 (9.52)
(mm)
Dimensions: H/W/D mm 555/770/300
Weight kg 27.0
EDP no. 1624461 1624466
5)
At distance of 1 m in the open air; specified values are maximum values
6)
Contains greenhouse gas according to Kyoto protocol, GWP 675
7)
Expandable to -15 °C with WRK-1
8)
Expandable to -20 °C with WRH-1
11
Page 12
B
C
D
A
E
A
B
C
D
REMKO ATY series

2.2 Unit dimensions

Outdoor units
Fig. 1: Outdoor unit ATY 266-356 DC AT dimensions
Measurements (mm) A B C D E
ATY 266-356 DC AT 770 487 298 555 300
Indoor units
Fig. 2: Indoor unit dimensions ATY 266-356 DC IT
Measurements (mm) A B C D
ATY 266-356 DC IT 897 312 158 182
12
Page 13

3 Design and function

21
4
3
2
1
4
3
5
7
8
9
6
1
7
8
9
B
A
4
3
5
6
2
3

3.1 Unit description

The ATY 266-356 DC room air conditioners have a REMKO ATY...AT outdoor unit as well as an ATY...IT indoor unit.
In cooling mode, the outdoor unit serves to output the heat extracted by the indoor unit from the room being cooled. In heating mode, the heat taken up by the outdoor unit can be discharged by the indoor unit into the room to be heated. In both operating modes, the output produced by the com­pressor precisely matches requirements, and thereby regulates the nominal temperature with minimal temperature deviations. This "inverter technology" results in energy savings over conven­tional split systems and also reduces noise emis­sions to a particularly low level. The outdoor unit can be installed in an outdoor area or, providing that certain requirements are met, an indoor area. The indoor unit is designed to be mounted high up on the wall, in indoor areas. It is operated by an infrared remote control.
The outdoor unit consists of a cooling cycle with compressor, fin condenser, condenser fan, reversing valve and throttle element. The outdoor unit is controlled by the regulation of the indoor unit.
The indoor unit consists of a fin evaporator, evapo­rator fan, controller and condensate tray.
Floor brackets, wall brackets, refrigerant piping and condensate pumps are available as accessories.
Fig. 4: Cooling cycle diagram for outdoor unit
1: Condenser 2: Condenser fan 3: Reversing valve 4: Compressor 5: Filter dryer 6: Capillary tube throttle element 7: Pressure gauge connection 8: Suction pipe connection valve 9: Injection pipe connection valve
Fig. 5: System layout
A: Outdoor area B: Indoor area 1: Indoor unit 2: Outdoor unit
Fig. 3: Cooling cycle diagram for indoor unit
1: Evaporator 2: Evaporator fan 3: Suction pipe connection 4: Injection pipe connection
3: Condensate drainage line 4: Condenser fan 5: Mains cable 6: Shut-off valve 7: Suction pipe 8: Injection pipe 9: Control line
Refrigerant piping is used to connect the indoor unit to the outdoor unit.
13
Page 14
max. 6 m
1
REMKO ATY series

4 Operation

4.1 General notes

The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit with the remote control, then it can also be man­ually operated.
Alarms are indicated by a code (see chapter T
roubleshooting and customer service).
NOTICE!
Manual mode
The indoor unit can also be switched on manually if the infrared remote control is lost/defective. Manual operation is intended for emergency oper­ation and is not suitable for basic unit operation. Please replace the remote control. The key for manual activation is located below the housing cover on the right side.
The following settings apply for manual operation:
Pressing once: Automatic mode,
Pressing twice: Cooling mode,
Pressing three times: Unit OFF
Infrared remote control
The infrared remote control sends the programmed settings a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects are obstructing the transmission path.
wo AAA batteries must be inserted into the
T remote control in preparation. To do so, remove the flap from the battery compartment and insert the batteries the correct way around (see mark­ings). Removing the batteries causes all stored data to be lost. The remote control will then access the default settings, which you are free to cus­tomise at any time.
Immediately replace flat batteries with a new set, otherwise there is a risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.
Help save on energy consumption in stand-by mode! If the device, system or component is not in use, we recommend disconnecting the power supply
. Components with a safety function is
excluded from our recommendation!

4.2 Display on indoor unit

Display
Fig. 6: Maximum distance
Fig. 7: Display
1: Display of coded error messages, room and
target temperature
14
Page 15
6
8
11
147
9
10
12
13
2
1
4
3
5
1
2
3
4
5
6
7
8

4.3 Keys on the remote control

"SLEEP" key
Activates/deactivates the "SLEEP" function.
Pressing this key will automatically increase or decrease the target temperature by 1 °C within an hour in cooling mode and heating mode respec-
. Press this key to maintain the most conven-
tively ient temperature and save energy. This function is only available in "Cooling", "Heating" and "Auto" modes. If the unit is working in "SLEEP" mode, this activity is interrupted by pressing the "MODE", "FAN", "Speed" or "ON/OFF" keys.
"FRESH" key
Press this key to activate/deactivate the ion gener­ator (air freshener).
"TURBO" key
Activation of the turbo function makes it possible to reach the setpoint in cooling or heating mode as fast as possible.
Fig. 8: Keys on the remote control
"ON/OFF" key
Press this key to switch the air conditioning unit on
f.
and of
Operating mode selection
This key is used to set the desired operating mode. The automatic, cooling, dehumidification, heating and recirculation modes are available.
The automatic mode is only available to a limited degree with multi-split applications (see note
Ä
on page 18)
Fan speed
Use this key to select the desired fan speed. The automatic, low
, medium and high functions are available. Note: In the dehumidification mode, the fan speed cannot be set manually.
"SELF CLEAN" key (not available)
This activates the self-clean function on the unit.
“ARROW UP” and “ARROW DOWN” keys
“ARROW UP” key
Press the key in order to increase the setpoint in 1 °C steps to a maximum 30°C.
“ARROW DOWN” key
Press the key in order to reduce the setpoint in 1°C steps to a minimum 17°C.
15
Page 16
9
10
11
12
13
14
REMKO ATY series
“SILENCE/FP” key
Activates/deactivates the silent mode. Pressing the key for longer than 2 seconds activates the unit's frost protection function.
In silent unit mode, the compressor runs at a lower frequency
, and the indoor unit fan rotates at a slower speed. This obtains particularly silent unit operation.
The frost protection function can only be activated in heating mode. The unit operates with a fixed setpoint of 8°C. The indoor unit displays "FP". Pressing the ON/OFF, SLEEP, FP, Mode, FAN or up or down arrow key, the frost protection function is deactivated.
Note please!
Both functions are not available when con­necting to the MVT unit series!
"TIMER ON" key
Press this key to activate the unit start delay time. Each press of this key increases the delay time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. T
o deactivate the delay
time, set the time to 0.0.
"FOLLOW ME" key
This key can be used to activate/deactivate the FOLLOW ME function. In this mode, the room tem­perature is measured on the remote control. This sends a signal to the indoor unit every 3 minutes. If the remote control does not send a signal to the indoor unit for 7 minutes, this mode is automati­cally deactivated.
"LED" key
This activates the display on the indoor unit.
This is only possible if the display has been auto­matically switched of
f by the integrated light indi-
cator.
"TIMER OFF" key
This key can be used to program the delayed switch-of
f time. Each press of this key increases the switch-off time by 30 minutes. When the set time on the display exceeds 10.0, each press of the button increases the set time by 60 minutes. To deactivate the switch-off time, set the time to 0.0.
3-D swing mode
Press this key to start or stop the swing mode. With the 2-point key, you can adjust the horizontal fin on the left side and the vertical fin on the right side. Press this key once to change the angle by 6 degrees. Pressing the key for 2 seconds stops the swing function. When the swing function is stopped, LC appears on the display for three sec­onds.
16
Page 17
Indicators on the LCD
2
1
4
3
6
9
8
10
5
7
11
13 12
1
3
2
Fig. 9: Indicators on the LCD
1: Mode indicator - shows the current operating
modes, including Auto ( ), Cooling ( ), Dehumidification ( ), Heating ( ), Fan ( ) and back to Auto ( ) mode.
2: Signal transmission symbol. This symbol
appears when signals are being transmitted from the remote control to the indoor unit.
3: ON/OFF symbol. This symbol appears when
the "ON/OFF" key is pressed. Pressing this key again causes the indicator to go out.
4: TIMER ON symbol. This symbol appears
when TIMER ON is switched on. 5: ECO function (not available) 6: TIMER OFF symbol. This symbol appears
when TIMER OFF is switched on. 7: Battery charge status (weak) 8: Sleep symbol. This symbol appears when the
"Sleep" function is activated. Pressing this key
again causes the indicator to go out. 9: Temperature/Timer symbol. Shows the tem-
perature setting (-17°C~30°C). If "F
AN" mode is selected, the temperature setting is not dis­played. In Timer mode, the ON and OFF set­tings appear for the TIMER.
10: FOLLOW ME symbol. This symbol appears
when the "Follow me" function is activated.
11: Display of ion generator active (optional) 12: Fan speed symbol. This is where the selected
fan speeds are displayed: AUTO (no indicator) and the three fan speed settings:
(slow),
(medium) and (fast). The fan speed is set to "Automatic" when either "Auto" or "Dehumidification" mode is activated.
13: Silent mode active (optional)
The illustration of the LCD with all of the sym­bols present is only intended to provide a clearer overview
. During operation, only those symbols relevant to the respective functions appear on the display.
Key functions
A symbol is shown on the display to indicate that the settings are being transferred.
“Auto” mode (please observe notes!)
Make sure that the indoor unit is connected to the power supply
, and is switched on.
The operating mode indicator on the display of the indoor unit begins to flash.
1. Press the "MODE" key to select "Auto" mode.
2. Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30°C, in increments of 1°C.
3. Press the "ON/OFF" key to switch on the air conditioning unit.
Fig. 10: "Auto" mode
17
Page 18
1
4
2
3
1
3
2
REMKO ATY series
Important Note
In "Automatic" mode, the cooling unit automati­cally chooses between cooling, recirculation and heating operation.
In multi-split systems that can either cool or heat, a mode conflict therefore occurs when using “Automatic” mode (error P5). In order to prevent this error operating mode for all indoor units.
"Cooling", "Heating" and "Recirculation" mode
Make sure that the indoor unit is connected to the power supply
1. Press the "MODE" key to select from oper­ating modes "Cooling", "Heating" or "Recircu­lation".
2. Press the "Arrow up/down" key to set the desired temperature. The temperature can be set between 17 and 30°C, in increments of 1°C.
3. Press the "F fan speeds (Auto, slow, medium and fast).
4. Press the "ON/OFF" key to switch on the air conditioning unit.
, use “Cooling” or “Heating”
, and is switched on.
AN" key to select from the four
"Dehumidification" mode
Make sure that the indoor unit is connected to the power supply
The operating mode indicator on the display of the indoor unit begins to flash.
1. Press the "MODE" key to select "Dehumidifi­cation" mode.
2. The temperature setting on the remote con­trol has no ef
3. Press the "ON/OFF" key to switch on the air conditioning unit.
, and is switched on.
fect on unit operation.
Fig. 11: "Cooling", "Heating" and "Recirculation" mode
Fig. 12: "Dehumidification" mode
In the “Dehumidification” mode, manual selec­tion of the fan speed is not possible! Please note that temperature pre-selection is not pos­sible and the dehumidified room can cool dra­matically!
18
Page 19
2
1
"Timer" mode
Press the "TIMER ON" key to set the "switch-on time" and the "TIMER OFF" key to set the "switch­of
f" time for the unit.
Setting the “switch-on time”
1. Press the "TIMER ON" key
. The remote con­trol shows "TIMER ON", the last "switch-on time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-on time" and to start "TIMER ON" mode.
2. Press the "TIMER ON" key again to set the desired "switch-on time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.
3. Once these settings have been made, there is a one second delay before the remote con­trol transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display
, and the set temperature appears again on the display.
Setting the “switch-off time”
1. Press the "TIMER OFF" key
. The remote control shows "TIMER OFF", the last "switch­off time" setting and the symbol "H" appear on the display. The unit is now ready to reset the "switch-off time" and to stop "TIMER OFF" mode.
2. Press the "TIMER OFF" key again to set the desired "switch-of
f time". Each time the key is pressed, the time is increased by half an hour between 0 and 10 hours, and by an hour between 10 and 24 hours.
3. Once these settings have been made, there is a one second delay before the remote con­trol transmits the signal to the indoor unit. Then, after approx. two seconds, the "H" symbol disappears from the LCD display
, and the set temperature appears again on the display.
When T
imer mode is selected, the remote control automatically transfers the timer signal to the indoor unit for the specified period of time. Therefore, you should hold the remote control in a location where it can transfer the signal to the indoor unit without interference.
The effective operation for the time settings
by the remote control for the timer function is restricted to the following settings:
0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0,
5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23 and 24.
Fig. 13: "Timer" mode
19
Page 20
Start
Off
2 hours laterSet time
Stop
On
4 hours laterSet time
On
Set time
Stop
Start
2 hours later after setting
10 hours later after setting
REMKO ATY series
Example TIMER function settings
"TIMER ON" (Auto on mode)
Example:
Y
ou want the air conditioning unit to switch on 2
hours from the time it was programmed.
1. Press the "TIMER ON" key
. The last oper­ating time setting for the timer, and the "H" symbols, appear on the display.
2. Press the "TIMER ON" key until the desired start time is shown in the "TIMER ON" area on the remote control.
3. W
ait for 3 seconds and the temperature appears again in this area of the digital dis­play. The "TIMER ON" indicator stays lit, and this function is activated.
Combined TIMER (setting "TIMER ON" and "TIMER OFF" at the same time)
"TIMER OFF ð "TIMER ON"
(On ð Stop ð Start)
Example:
Y
ou want the air conditioning unit to switch off in two hours from the time it was programmed, and switch back on ten hours later.
1. Press the "TIMER OFF" key.
2. Press the "TIMER OFF" key again until the
desired stop time is shown in the "TIMER OFF" area on the remote control.
3. Press the "TIMER ON" key.
4. Press the "TIMER ON" key again until "10H"
is shown in the "TIMER ON" area on the remote control.
5. Wait for 3 seconds and the temperature
appears again in this area of the digital dis­play. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is acti­vated.
Fig. 14: "TIMER ON" example
"TIMER OFF" (Auto off mode)
Example:
ou want the air conditioning unit to switch off 4
Y hours from the time it was programmed.
1. Press the "TIMER OFF" key
. The last oper­ating time setting for the timer, and the "H" symbols, appear on the display.
2. Press the "TIMER OFF" key until "10H" is shown in the "TIMER OFF" area on the remote control.
3. W
ait for 3 seconds and the temperature appears again in this area of the digital dis­play. The "TIMER OFF" indicator stays lit, and this function is activated.
Fig. 16: "TIMER OFF" / "TIMER ON" example
Fig. 15: "TIMER OFF" example
20
Page 21
Off
Set time
Stop
Start
2 hours later after setting
5 hours later after setting
1
Setpoint
After 7 hours unit OFF
1 hr
1 hr
"TIMER ON ð
"TIMER OFF"
(Off ð Start ð Stop)
Example:
You want the air conditioning unit to switch on in two hours from the time it was programmed, and switch back off five hours later.
1. Press the "TIMER ON" key.
2. Press the "TIMER ON" key again until "2.0H"
is shown in the "TIMER ON" area on the remote control.
3. Press the "TIMER OFF" key.
4. Press the "TIMER OFF" key again until
"5.0H" is shown in the "TIMER OFF" area on the remote control.
5. Wait for 3 seconds and the temperature appears again in this area of the digital dis­play. The "TIMER ON" and "TIMER OFF" indicators stay lit, and this function is acti­vated.
SLEEP function
The sleep function saves energy while you sleep. This function is activated by pressing the key on the remote control. Press the key before going to sleep. In cooling mode, the unit automatically increases the set room temperature by 1 °C after 1 hour
. After one more hour, the room temperature is increased by an additional 1 °C. In heating mode, the room temperature is decreased within the first two hours of operation by 2°C. After 7 hours of unit operation, the unit switches off automatically in cooling and heating mode.
This function is not available in the modes recircu­lation and dehumidification!
Fig. 17: "TIMER ON" / "TIMER OFF" example
Fig. 18: "Sleep" function
Fig. 19: Sleep mode
21
Page 22
21 5
3 4
REMKO ATY series

5 Installation instructions for qualified personnel

5.1 Important notes prior to instal­lation
ransport the unit in its original packaging as
n T
close as possible to the installation location. You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible trans­port damage. Report any damage immediately to your contractual partner and the shipping company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connec­tions.
n The refrigerant piping (liquid and suction pipe),
valves and connections must be insulated to make them vapour diffusion proof. If necessary also insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet (see section "Minimum clearances")
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltra­tion of moisture and never kink or compress the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and ensures that the compressor oil can flow back without obstruction.
n Make special preparations regarding the oil
return if the outdoor unit is located above the indoor unit (see section "Oil return measures").
n Add refrigerant if the basic length of the refrig-
erant piping exceeds 5 metres. For the quantity of additional refrigerant, refer to chapter "Adding refrigerant".
n Perform all electrical wiring in accordance with
applicable DIN and VDE standards.
n Ensure the electrical cables are properly con-
nected to the terminals, otherwise there is a risk of fire.
n Only use the fasteners contained in the scope
of delivery with the units.
n Use four supports and the associated hooks to
attach the ceiling cassette (only applies to ceiling cassettes).
n Use the insulated condensate hose in the
scope of delivery as a junction piece to the continuing condensate drain. Secure the con­densate drain with the supplied clamps.

5.2 Wall openings

n A wall opening of at least 70mm diameter and
10mm incline from the inside to the outside must be created.
o prevent damage to the lines, the interior of
n T
the wall opening should be padded or, for example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall opening, taking account of fire protection regu­lations (responsibility of customer). Do not use cement or lime containing substances!
Fig. 20: Wall opening
1: Liquid line 2: Control line 3: Condensate drainage line 4: Suction pipe 5: PVC pipe

5.3 Installation materials

The indoor unit is attached to the wall using 4 screws (provided by the customer)
The outdoor unit is attached by 4 screws and a wall bracket to the wall or fixed by a floor bracket to the ground.
22
Page 23
1
20 cm
1
5.4 Selection of installation
location
Indoor unit
The indoor unit is designed for horizontal wall installation above doors. However used in the upper wall area (min. 1.75m above the floor).
Outdoor unit
The outdoor unit is designed for horizontal installa­tion on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over. The outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from the influence of the weather.
Rain
For floor or roof set-up, the unit should be installed with at least 10cm ground clearance. A floor bracket is available as an optional accessory.
, it can also be
Wind
If the unit is being installed in windy areas, ensure that the warm outlet air is discharged in the pre­vailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be pro­vided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit. An additional stabilization is recommended. This can, for example, be realized with ropes or other structures.
Fig. 21: Windbreak
1: Wind
Sun
The condenser on the outdoor unit emits heat. Exposure to sunlight further increases the temper­ature of the fins and reduces the heat released by the finned heat exchanger. The outdoor unit should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of cus­tomer). One possible solution is to build a small roofed area over the unit. These measures should not affect the flow of warm outlet air.
Snow
The unit should be wall-mounted in areas of heavy snowfall. Installation should be at least 20cm above the expected level of snow to prevent snow from entering the outdoor unit. An optional wall bracket is available as an accessory
Fig. 22: Minimum clearance to snow
1: Snow
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts, adjoining rooms or halls (
Fig. 23).
.
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being installed in the room and which can compen­sate any additional pressure loss in ventilation ducts (Fig. 23).
n Comply with any regulations and conditions
fecting the statics of the building. If neces-
af sary, fit acoustic installation.
23
Page 24
2
1
K
3
W
3
D
C
D
B
A
C
A
B
REMKO ATY series
Fig. 23: Installation inside buildings
K: Cold fresh air / W: Warm air 1: Outdoor unit / 2: Additional fan
3: Air shaft

5.5 Connection variants for the indoor unit

The following connection variants can be used for the refrigerant, condensate and control lines.
Fig. 24: Connection variant (view from the rear)
A: Infeed of the refrigerant piping at the wall, left B: Infeed of the refriger. piping through the wall, left C: Outlet through the wall, right
D: Outlet at the wall, right (the refrigerant piping
must be bent through 180 degrees for this)
24
Page 25

5.6 Minimum clearances

2
1
2
1
A
B
C
D
E
E
C
A
B
F
IT AT
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.
Fig. 25: Minimum clearances of the indoor unit and outdoor unit
AT: Outdoor unit / IT: Indoor unit 1: Air inlet / 2: Air outlet
Measure-
ments (mm)
Indoor units Outdoor units
ATY 266-356 DC IT ATY 266-356 DC AT
A 120 300
B - 2000
C 120 600
D - 300
E 150 600
F 1600 -
25
Page 26
REMKO ATY series

5.7 Connection of the indoor unit when the refrigerant piping is installed under the plaster

If the customer routes the refrigerant piping to the unit underneath the plaster, observe the following note. The principal connection options can be found in the "Connection variants for the indoor unit" and "W bracket" chapters.
If the refrigerant piping is routed underneath the plaster, ensure that the customer-fitted refrigerant piping does not protrude from the wall at a 90° angle. As a result of the required bending radius, the unit would then be very difficult to connect or would possibly be impossible to fasten to the wall mount.
For this reason, route the customer-fitted refrigerant piping with as flat an angle as possible (<30°) out of the wall, from the left and into the unit. This enables direct connection of the refrigerant piping (see Fig. 26).
NOTICE!
The flare connection should be implemented in the unit in the case of under-plaster installations. A detachable connection below the level of the plaster is not generally permitted!
all
Fig. 26: Under the plaster installation (View from above)
26
Page 27

5.8 Wall bracket

A B
C
D
G
F
E
H
1
2
B
A
Fig. 27: Wall bracket for indoor units ATY 266-356 DC IT (rear view)
Measurements (mm) A B C D E F G H
ATY 266-356 DC IT 450 445 50 50 75 263 639 254

5.9 Oil return measures

If the outdoor unit is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually every 7.0 metres of height difference.
, an oil pump bend is installed for

6 Installation

6.1

Installation of the indoor unit

The indoor unit is attached directly to the wall using screws
1. Mark the mounting points on the structurally permissible building sections according to the dimensions of the wall bracket.
2. The unit trim is opened using the two pres­sure points located on the sides.
Fig. 28: Oil return measures
A: Outdoor unit B: Indoor unit 1: 1 x oil pump bend in suction pipe to outdoor
unit every 7.0 metres of height dif radius: 50 mm
2: Max. 10 m
27
ference,
Fig. 29: Open display cover
Page 28
REMKO ATY series

6.2 Connection of refrigerant piping

The refrigerant piping connection is established by the customer on the back side of the units.
It may be necessary to fit a reducer or flared adapter to the indoor unit. These fittings are included with the indoor unit as an accessory kit. Once installed, the connections should be insu­lated to make them vapour dif
NOTICE!
fusion proof.
Fig. 30: Open display cover
3. Once you have pressed this, you can lift the panel. The unit is equipped with a latching mechanism, which helps to hold the panel.
ou are now also able to remove the com-
Y plete panel.
4. Once the panel has been opened, you can perform the electrical wiring. The terminal block is located beneath a plastic cover on the right side.
Installation should only be performed by author­ised specialists.
NOTICE!
The unit is factory filled with dry nitrogen for leak testing purposes. The pressurised nitrogen is released when the union nuts are undone.
NOTICE!
Use only tools which are approved for use in an HVAC environment. (z. B.: bending pliers, pipe/ tubing cutters, de-burrers and flaring tools). Do not cut refrigerant pipes with a saw.
NOTICE!
All work must be carried out in a way that pre­vents dirt, particles, water etc. from entering, refrigerant lines!
Fig. 31: Terminal block for the electrical wiring
5. Remove the part of the housing at the respective predetermined breaking point, at which the lines should be fed in.
6. Connect the refrigerant piping, electrical cables and condensate drainage line to the indoor unit.
7. Check that the unit is level.
8. Re-assemble the unit.
28
Page 29
The following instructions describe the installation
2
1
of the cooling cycle and the assembly of the indoor unit and the outdoor unit.
1. The required pipe diameters are given in the table "T
2. Install the indoor unit and connect the refrig­erant piping as described in the operating manual for the indoor unit.
3. Use the wall or floor brackets to fit the out­door unit against structural parts approved to support the static load (refer to the installa­tion instructions for the brackets).
4. Ensure that structure-borne sound is not transferred to parts of the building. Use vibra­tion dampers to reduce the ef ture-borne sound!
5. Lay the refrigerant piping from the indoor unit to the outdoor unit. Ensure that the fasten­ings are adequate and if necessary appropriate oil return measures!
6. Remove the factory-fitted protective caps and union nuts on the connections. These should be used later in the installation process.
7. Before flanging the refrigerant piping, ensure that the union nut is fitted on the pipe.
8. Prepare the laid refrigerant piping as shown below (
9. V (Fig. 34).
10. First connect and hand-tighten the refrigerant piping to ensure it is correctly seated.
11. Then tighten the fittings with 2 appropriately­sized open-ended spanners. Use one spanner to counter the force when tightening the fitting (Fig. 35).
12. Use insulation hoses which are designed for this temperature range and are dif proof.
13. Observe the permitted bending radius for the refrigerant piping during installation. Never bend a pipe twice in the same place. Brittle­ness and cracking can result.
14. Apply appropriate heat insulation to the installed refrigerant piping, including con­nector
15. T for all subsequent refrigerant piping.
echnical data".
fects of struc-
, take
Fig. 32 and Fig. 33).
erify that the shape of the flange is correct
fusion
.
ake the same action at the shut-off valves
Label the refrigerant piping (injection and suc­tion pipes) as well as the associated electrical control lines of each interior unit with a letter Only connect the lines to their associated con­nections.
NOTICE!
Always pay attention to the af electrical lines and refrigerant piping! The con­nections of the individual circuits must not be mixed up. Mixing up the assignment of control lines and refrigerant piping can have fatal con­sequences (compressor damage)!
Commissioning of the individual circuits must be carried out successively.
Fig. 32: Deburring the refrigerant piping
1: Refrigerant piping 2: Deburrer
filiation of the
.
29
Page 30
1
2
1
REMKO ATY series
Fig. 33: Flanging the refrigerant piping
1: Flanging tool
Fig. 34: Correct flange shape
Fig. 35: Tightening the fitting
1: Tighten with the first open-ended spanner 2: Counter with the second open-ended spanner
Pipe dimension in inches
1/4" 15-20
3/8" 33-40
1/2" 50-60
Tightening torque in Nm
30
Page 31
6.3 Additional notes on connecting
the refrigerant piping
n When combining the outdoor unit with some
indoor units, the procedure for connecting the refrigerant piping may dif vided reducer or expansion fittings to the indoor unit.
n If the basic length of the connecting line
exceeds 5m, add refrigerant when commis­sioning the system for the first time (see chapter "Adding refrigerant").
fer. Install the pro-

6.4 Leak testing

Once all the connections have been made, the pressure gauge station is attached to the Schrader valve as follows (if fitted):
red = small valve = high pressure
blue = large valve = suction pressure
Once the connection has been made successfully the leak test is carried out with dry nitrogen.
Leak testing involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been made properly. In that case, tighten the connection or, if necessary, create a new flange.
After completing a successful leak test, the excess pressure in the refrigerant piping is removed and a vacuum pump with an absolute final partial pres­sure of min. 10 mbar is used to remove all of the air and empty the pipes. Any moisture present in the pipes will also be removed.
NOTICE!
,
A vacuum of at least 20 mbar must be pro­duced!
The time required to generate the vacuum is dependent on the final pressure pipe volume of the indoor units and the length of the refrigerant piping. However minutes. Once any foreign gases and humidity have been completely extracted from the system, the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the "Commissioning" sec­tion.
, the process will take at least 60
31
Page 32
3
2
4
9
5 5
11
100
6
8
7
10 10
12 12
1
REMKO ATY series

6.5 Adding refrigerant

The units contain a basic quantity of refrigerant. In addition, an additional amount of refrigerant must be added for refrigerant piping lengths exceeding 5 metres per circuit. Refer to the following chart:
Up to and
incl. 5m
ATY 266-356
DC
CAUTION!
ear protective clothing when handling refrig-
W erant.
DANGER!
Only refrigerant in a liquid state may be used to fill the cooling cycle!
0 g/m 20 g/m
From 5m to max. length
7 Condensate drainage
connection and safe drainage
NOTICE!
Check the overheating to determine the refrig­erant fill quantity
NOTICE!
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This unit contains refrigerant potential of 675. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 675 times greater than 1 kg CO2, based on 100 years. Do not conduct any
work on the refrigerant circuit or dismantle the unit - always enlist the help of qualified experts.
.
Fig. 36: Condensate drainage, seepage of conden­sate and strip foundation (cross-section)
1: Outdoor unit 2: Leg 3: Condensate collection tray 4: Floor bracket
with a greenhouse
5: Reinforced strip foundation
H x W x T = 300 x 200 x 800 mm 6: Gravel layer for seepage 7: Condensate drainage heating 8: Drainage channel 9: Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 60 °C) 10: Frost line 11: Drainage pipe 12: Soil
32
Page 33
EB
B
A
D
C
11
1
5
5
8
1
9
3
Fig. 37: Dimensions for the strip foundation
min. 2%
(plan view)
For the designations of 1, 3, 5, 8, 9 and 11, please refer to the legend for the Fig. 36
dimensioning of the strip foundation (in mm)
n When operating the unit at outside tempera-
tures below 0 °C, ensure the condensate drainage line is laid to protect it against frost. The lower part of the housing and condensate tray is also to be kept frost free in order to ensure permanent draining of the condensate. If necessary
, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the line is durably leak tight.
Dim ensi on
A 800
B 200
C 487
ATY 266-356 DC AT
Fig. 38: Condensate drainage connection - Indoor unit
The condensate hose is designed to be connected on the right and the left side (view from front). Remove the stopper from the corresponding con­nection.
D 300
E 287
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the fol­lowing list of requirements from regional regula-
Condensate drainage connection
Due to the dew point shortfall on the evaporator condensation is created on the indoor unit in
,
tions and laws.
NOTICE!
cooling mode and on the outdoor unit in heating mode.
Below the evaporator is a collection tray, which must be connected to a drain.
n The condensate drainage line should have an
incline of min. 2% (
Fig. 38). This is the respon-
Local regulations or environmental laws, for example the German W
ater Resource Law (WHG), can require suitable precautions to pro­tect against uncontrolled draining in case of leakage to provide for safe disposal of escaping refrigerator oil or hazardous media.
sibility of the customer. If necessary, fit vapour­diffusion-proof insulation.
n Route the unit's condensate drainage line
NOTICE!
freely into the drain line. If the condensate runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
If condensate is removed via a duct in accord­ance with DIN EN 1717, ensure that any micro­biological contamination present on the waste­water side (bacteria, fungi, viruses) cannot enter the unit connected to it.
33
Page 34
1
REMKO ATY series

8 Electrical wiring

8.1 General notes

DANGER!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regula­tions to dimension and to lay
NOTICE!
The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regula­tions and should be laid out by an electrician.
.

8.2 Connecting the indoor unit

n If a condensate pump, available as an acces-
, is used in conjunction with the unit, it may
sory be necessary to install an additional relay with a higher contact rating after the switch-off con­tact on the pump to switch off the compressor (see Fig. 42).
n The control lines used should comprise
shielded wire, if laid in areas exposed to strong magnetic fields.
n Details concerning the electrical protection of
the system are provided in the technical data.
Establish the indoor unit connection as follows:
1. Remove the front of the unit, as described in chapter “Unit installation”.
2. Choose the cable cross-section in accord­ance with the relevant specifications.
3. Connect the unit to the control line from the
Ä
outdoor unit (see wiring diagram’ on page 35).
4. Re-assemble the unit.
Chapter 8.4 ‘Electrical
e recommend using shielded wires for the
W control lines.
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent contact. T
ighten as required.
Fig. 39: Indoor unit connection
1: Control line
34
Page 35
BA
230V/1~/50 Hz
L N PE W 1(L) 2(N) S 2(N) S PE PE
2
1
W 1(L)

8.3 Outdoor unit connection

e recommend that a mains/repair switch be
n W
installed near the outdoor unit.
n The power supply is established on the outdoor
unit. The indoor unit is supplied via the control line from the outdoor unit.
Proceed as follows to connect the line:
1. Remove the side-panel cover.
2. Choose the cable cross-section in accord-
ance with the relevant specifications.
3. Connect the lines as shown on the electrical connection diagram.

8.4 Electrical wiring diagram

Connection ATY 266-356 DC
4. Fix the line in the strain relief and re-
assemble the unit.
Fig. 40: Outdoor unit connection
Fig. 41: Electrical wiring diagram
A: Outdoor unit B: Indoor unit
35
1: Mains cable 2: Control line
Page 36
L N PE
L N PE
L
N
WH
BK
PE
A
B
C
1
2
3
W 1(L) 2(N) S
PE
W 1(L) 2(N) S
REMKO ATY series
Connection of optional condensate pump KP-6/KP-8
Fig. 42: Electrical wiring diagram
A: Outdoor unit B: Indoor unit C: KP-6/KP-8 condensate pump 1: Mains cable
2: Condensate pump power supply 3: Condensate pump fault contact BK: black WH: white
36
Page 37

8.5 Electrical drawings

1
2
3
5
A
C
6
4
W
1(L)
2(N)
S
Yellow/ Gelb
Rot/ Red
Weiß/ White
CN 12
M
Cn15
L-OUT
L-IN
N-IN
Cn31
Blau/ Blue
CN 24
CN 33
CN 22
CN 19
CN 27
CN 18
B
Indoor units ATY 266-356 DC IT
Fig. 43: Electrical drawings
A: Control board B: Display circuit board C: Control line from outdoor unit 1: DC fan motor 2: Engine trim + LED board
3: Fin motor, vertical 4: Fin motor, horizontal 5: Temperature probe, evaporator T2 6: Ion generator
37
Page 38
1 2
3
5
A
B
7
6
C
8
4
W
1(L)
2(N)
S
L
N
CN 1A
CN 60
CN 17 CN 15
CN 31
CN 7
CN 21
CN 50
Blau/Blue
Rot/Red
Schwarz/Black
U
V
W
M
M
Rot/
Red
Blau/
Blue
Yellow or Black/
Gelb oder Schwarz
Braun/
Brown
Yellow and Green/
Gelb und Grün
REMKO ATY series
Outdoor units ATY 266-356 DC AT
Fig. 44: Electrical drawings
A: Control board B: Mains cable C: Lines to indoor unit 1: Reversing valve 2: Crankcase heating 3: Condensate tray heating
4: Condenser/DC fan 5: Temperature probe for condenser air inlet T4 6: Temperature probe for heat gas line
compressor T5 7: Temperature probe for condenser outlet T3 8: Compressor
38
Page 39

9 Before commissioning

After leak testing has been successfully com­pleted, connect the vacuum pump via the pressure gauge station to the valve connections on the out­door unit (see chapter "Leak testing") and create a vacuum.
Perform the following checks prior to putting the unit into operation for the first time and after any work on the cooling cycle. Record the results in the commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy water
.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.

10 Commissioning

NOTICE!
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued. Observe the operating manuals for the indoor unit and outdoor unit when commissioning the entire system.
Once all the components have been connected and tested, the system can be put into operation. A functional check should be performed to verify its correct function and identify any unusual operating behaviour prior to handing it over to the operator
NOTICE!
Check that the shut-of are tight after carrying out any work on the cooling cycle. Use appropriate sealant products as necessary.
f valves and valve caps
.
Functional checks and test run
Check the following points:
n Leak-tightness of the refrigerant piping. n Compressor and fan running smoothly. n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not over­heating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured tempera­ture.
n Record the measured temperatures in the
commissioning report.
39
Page 40
REMKO ATY series
Function test of cooling operating mode
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-of unit until the pressure gauge indicates a pressure of approx. 2 bar.
3. Check all connections for leaks with leak detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-of valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection. It is imperative that the vacuum creation and drying steps are repeated.
5. Switch on the main circuit breaker or fuse.
6. Use the remote control to switch on the unit
and select the cooling mode, maximum fan speed and lowest target temperature.
7. Measure and record all the required values in the commissioning report and check the safety functions.
8. Check the unit control system using the func­tions described in the chapter "Operation". T
imer, temperature setting, fan speeds and switching to recirculation or dehumidifying mode.
9. Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray recommended for pouring the water into the condensate tray.
10. Switch the indoor unit to cooling mode.
f valves on the outdoor
f
. A bottle with a spout is
Due to the turn on delay start up a few minutes later.
11. Check all regulating, control and safety devices for function and correct adjustment during the test run.
12. Check the control of the indoor unit with the functions described in the operating instruc­tions (timer mode settings).
13. Measure the overheating, outside, internal, outlet and evaporator temperatures and record the test data in the commissioning log.
14. Remove the pressure gauge and install the caps
Final tasks
n Re-install all disassembled parts. n Familiarise the operator with the system.
, temperature adjustments and all
, the compressor will
40
Page 41

11 Troubleshooting and customer service

11.1 Troubleshooting and customer service

The unit and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!
Operational malfunctions
Malfunction Possible causes Checks Remedial measures
, if alarms should occur, please check the functions as detailed
The unit does not start or switches itself of
f
Power failure, under­voltage, defective mains fuse / main switch in OFF position
Damaged power supply Does all other elec.
Wait time after switching on is too short
Temperature outside operating range
Electrical surges caused by thunderstorms
Malfunction of the external condensate pump
Transmission distance too far / receiver af by interference
fected
Does all other electrical equipment function cor­rectly?
equipment function cor­rectly?
Have approx. 5 minutes elapsed since the restart?
Are the fans in the indoor unit and outdoor unit working correctly?
Have there been light­ning strikes in the area recently?
Has the pump shut down due to a malfunction?
Does the indoor unit beep when pressing a key?
Check the voltage and if necessary come back on
Repair by specialist firm
Schedule longer wait times
Observe temperature ranges of indoor unit and outdoor unit
Switch off the mains breaker and switch it back on. Have it inspected by a specialist
Check and if necessary clean the pump
Reduce the distance to less than 6 m or change position
, wait for it to
Defective remote control Is the unit running in
manual mode?
Receiver or transmitter unit exposed to exces-
The unit does not respond to the remote control
The unit works at reduced or no cooling capacity
41
sive solar radiation
Electromagnetic fields are interfering with trans­mission
Key in remote control jammed / two buttons pressed at same time
Batteries in remote con­trol are flat
Filter is dirty / air inlet / outlet opening is blocked by debris
Does it function correctly in the shade?
Does it function after removing potential sources of interference?
Does the “Transmitting” symbol appear on the display?
Have new batteries been inserted? Is the display incomplete?
Have the filters been cleaned?
Replace the remote con­trol
Place the receiver and/or transmitter unit in the shade
Signal is not transmitted when interference sources are operational
Release the key / only press one key
Insert new batteries
Clean the filters
Page 42
REMKO ATY series
Malfunction Possible causes Checks Remedial measures
Condensate discharge on unit
Windows and doors open. Heating / cooling load has increased
Cooling mode is not set Does the cooling symbol
Fins on outdoor unit blocked by foreign objects
Leaking cooling cycle Are there signs of frost
Drainage pipe on collec­tion container clogged / damaged
Faulty external conden­sate pump or float
Condensate has not drained away and has collected in the conden­sate drainage line
Have structural / usage modifications been made?
appear on the display?
Does the fan of the out­door unit work? Are the exchanger fins unob­structed?
on the exchanger fins of the indoor unit?
Can the condensate drain of obstruction?
Is the collection tray full of water and the pump not running?
Is there an incline on the condensate drainage line? Check there is no blockage in the pipe.
f without any
Close windows and doors / install additional units
Correct the settings for the unit
Check the fan or winter fan speed control, reduce the air resistance
Repair by specialist
Clean the drainage pipe and collection container
Call out a specialist to replace the pump
Route the condensate drainage line with an incline and clean.
Condensate does not drain of
NOTE
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then you can switch off the breaker will be required!
f
. Switch it back on again at least 12 hours before the next time that the unit
Are the condensate drainage lines unblocked and is there a steady incline? Are the conden­sate pump and liquid level switch functioning correctly?
Route the condensate drainage line with an incline and clean it. If the liquid level switch or the condensate pump is defective, have them replaced
42
Page 43
Fault display on the indoor unit
YES
Display Error description
E0 EEPROM error, indoor unit
E1 Communication error between indoor unit and outdoor unit
E3 Fan speed control indoor unit disabled
E4 Room temperature probe T1 defective
E5 Temperature probe, evaporator T2 defective
F0 Overflow protection
F1 Temperature probe air inlet outdoor unit T4 defective
F2 Temperature probe, evaporator outlet T3 defective
F3 Temperature probe, heat gas line T5 defective
F4 EEPROM error, outdoor unit
F5 Condenser fan speed control probe not working
P0 Compressor actuation error
P1 Over-voltage or under-voltage error
P2 Compressor overheating protection (heat gas temperature too high)
P4 Inverter control disabled
P5 Mode Conflict (indoor units set in different operating modes)
P6 Probe low pressure outdoor unit is aktivated
EC No cooling capacity after 30 minutes
dF Defrosting
For fault elimination refer to troubleshooting on the following pages.
1

1.2 Indoor unit fault analysis

Error code: E0 / F4
Reason: The control board of the outdoor unit or indoor unit cannot read the unit memory
(EEPROM)
Cause:
n Installation error n Control boards of outdoor unit or indoor unit defective
Switch off voltage, switch on again 2 minutes
later
. Is the error still present?
Replace the circuit boards of the outdoor unit
and indoor unit in turn, in order to locate the
defective EEPROM
43
Page 44
YES
NO
YES YES
YES
NO
NO
YES
NO
REMKO ATY series
Error code: E1
Reason: The indoor unit does not receive a signal from the outdoor unit within 110 seconds.
Cause:
Switch off voltage, switch on again 2 minutes
later
Measure the voltage between the “S” and “N”
terminals of the outdoor unit. Is the measured
Check electrical connections in the outdoor
n Electrical connection not configured correctly n Control boards outdoor unit or indoor unit defective
. Is the error still present?
value positive?
unit. Are they OK?
Is the transformer OK?
Check electrical connections in the indoor unit.
Are they OK?
Replace the control boards of the indoor unit. Is
the fault remedied?
Replace the control boards of the outdoor unit
Replace the transformer
Replace the control boards of the outdoor unit.
Is the fault remedied?
Replace the control boards of the indoor unit
44
Page 45
Error code: E3 / F5
NO
YES
NO
YES
NO
YES
NO
YES
NO
Reason: If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off
and the display shows error code E3 or E5
Cause:
Switch off voltage, switch on again 2
minutes later
De-energise the unit and attempt to
turn the fan wheel by hand. Does it
Check the electrical connections.
Are these correctly implemented?
Measure the voltage at the corre-
sponding connector plug on the con-
trol board (see section
dure’ on page 46). Does the
measured voltage lie within the toler-
n Electrical connection faulty n Evaporator fan wheel defective n Evaporator fan motor defective n Control board faulty
. Is the error still
present?
rotate freely?
Ä
‘Proce-
ance range?
The unit operates normally.
Check the motor and the fan
wheel bearing, and replace the
defective parts.
Correctly establish the electrical
connection
Replace the control board.
Replace the fan motor. Is the fault
remedied?
45
Page 46
1 3 4 5 6
REMKO ATY series
Procedure
DC fan motor of the indoor unit (control chip is installed in the motor):
Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the connector plug. Check the measured values against those listed in the table below problem with the control board and it must be replaced.
. If these differ, there is a
Fig. 45: Motor measurements
Terminal Colour Voltage
1 Red 280 V~380 V
2 --- ---
3 Black 0 V
4 White 17-17.5 V
5 Yellow 0~5.6 V
6 Blue 17-17.5 V
DC fan motor of the outdoor unit (control chip is installed in the motor):
Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance deviates significantly, assume that the motor is defective and must be replaced.
46
Page 47
Error code: EC
YES
YES
NO YES
YES
NO
Reason: The evaporator probe T2 measures the actual value with the compressor start and takes
this as the reference value T has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrig-
erant is low error code "EC".
. The measurement is performed a total of 3 times before the display shows the
. If, 5 minutes after the compressor start, the value T
Start
Start
Cause:
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
Check whether the indoor unit blows out cold
Check the cooling circuit for leaks. Leaks
Check the cooling circuit for any blockages. Are
the shut-of
n Refrigerant low or cooling circuit blocked n Evaporator probe T2 defective n Indoor unit control board defective
.
air
found?
f valves on the outdoor unit open?
Check the position and function of the evapo-
rator probe T2. Is it correctly seated and with
the correct resistance?
Exchange the control boards of the indoor unit.
Remedy leaks and put the unit back into opera-
tion.
47
Page 48
NO
YES
NO
YES
REMKO ATY series
Error code: E4 / E5 / F1 / F2 / F3
Reason: If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display
shows the error code of the corresponding probe.
Cause:
Check the connecting cable between the con­trol board and the temperature probe. Is it OK
Check the probe for correct resistance,
depending on the temperature (see resistance
Replace the corresponding control board.
n Electrical connection faulty n T
emperature probe defective
n Control board defective
and correctly connected?
table)
Establish a proper connection.
Replace the probe.
Fig. 46: Check the probes
48
Page 49
Error code: F0
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
Reason: Safety shutdown due to overly high current consumption of individual unit components
Cause:
Check the supply voltage. Is this correct?
Check the cooling circuit for any blockages. Is
Check the winding resistances of the com-
Check the electrical connections. Are these cor-
n Faulty power supply n Cooling circuit blocked n Faulty control board n Electrical connections faulty n Compressor defective
the cooling circuit OK?
pressor
. Are they OK?
rectly implemented?
Switch the unit off and ensure correct supply
voltage.
Remove the blockage (shut-off valve open?)
Replace the compressor.
Replace or correct the electrical connections.
Does the transformer operate fault-free?
Replace the outdoor unit.
Replace the transformer or control boards of
the outdoor unit.
49
Page 50
YES
NO
NO
YES
NO
YES
NO
YES
REMKO ATY series
Error code: P0
Reason: If the power supply to the compressor controller is faulty, the display shows the error code
“P0” and the unit switches of
f
Cause:
Check the connecting cables between the con-
trol board and compressor? Are they faulty?
Check the inverter controller (see section
Ä
‘Check the inverter controller’ on page 50).
Check the condenser fan motor. Is it working
Check the winding resistances of the com-
n Electrical connection faulty n Faulty control board n Condenser fan motor defective or blocked n Compressor defective
Fault eliminated?
correctly?
pressor
. Are they OK?
Establish a correct connection between the
control board and compressor
Replace the control board.
See troubleshooting fault F5
Replace the compressor.
.
Exchange the control boards of the outdoor
unit.
Check the inverter controller
Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the com­pressor from the control board.
Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:
Voltmeter Normal resistance
(+) Red (-) Black
U
V
N
W
(+) Red
¥
(multiple MW)
50
Page 51
Error code: P1
NO
YES
NO
YES
NO
YES
NO
YES
Reason: Overvoltage or undervoltage protection has tripped
Cause:
Check the power supply. Is the supply voltage
Check the electrical connections. Are they OK?
Switch the power on and put the unit into
standby mode. Measure the voltage on the
board, at contacts "P" and "N". This should be
approx. 310 V
the unit. The voltage between "P" and "N"
should now be between 220-400V. Is the cor-
Check the transformer. Is a defect present?
n Faulty supply voltage n Refrigerant low or cooling circuit blocked n Faulty control board
correct?
, 340 V or 380 V DC. Now start
rect voltage applied?
Switch the unit off and have the power supply
checked/corrected.
Replace the electrical connections.
Replace the control board.
Replace the control board.
Replace the transformer.
51
Page 52
YES
NO
YES
NO
YES
NO
YES
YES
NO
YES
REMKO ATY series
Error code: P2 (with units with a thermal contact)
Reason: If the test voltage of the thermal contact does not lie at 5 V, then the display shows the
error message “P2”
Cause:
Check the air flow
volumes of the
indoor unit and out-
door unit. Are they
blocked or dirty?
Switch off the power
supply to the unit
and switch it on
again after 10 mins.
Does the unit start
up?
Check the tempera-
ture of the com-
pressor
heated up?
n Faulty supply voltage n Refrigerant low or cooling circuit blocked n Faulty control board
. Has it
Clean the filter or heat exchanger and ensure a sufficient air flow volume.
Check the thermal contact. Is it correctly connected?
Measure the resistance of the thermal contact.
Is it 0?
Connect it correctly.
Check the cooling
circuit. Is it OK?
Replace the thermal
contact.
Replace the control board of the outdoor unit.
52
Page 53
Error code: P4
YES
NO
NO
YES
NO
YES
NO
YES
1
Reason: Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communi-
cation problem between board and compressor
, the compressor speed is not OK)
Cause:
Check the electrical connection between the
control board and compressor
Check the inverter controller. Is this functional?
Check the condenser fan motor. Is it OK?
Check the winding resistances of the com-
n Faulty electrical connections n Inverter regulation on board defective n Condenser fan motor defective n Compressor defective n Control board defective
. Are these cor-
rectly implemented?
pressor
. Are they OK?
Establish a proper connection.
Replace the control board.
Follow the instructions for troubleshooting fault
F5
Replace the compressor
Replace the control boards of the outdoor unit.
Check individual components
Check the temperature probes
Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.
1: Multimeter
Error code: dF
Reason: The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase,
the indoor unit automatically switches back to the last operating mode.
53
Page 54
REMKO ATY series
11.3 Resistances of the
temperature probes
Probe T1, T2, T3 and T4
Temp.
(°C)
-20 115.27 12 18.72
-19 108.15 13 17.80
-18 101.52 14 16.93
-17 96.34 15 16.12
-16 89.59 16 15.34
-15 84.22 17 14.62
-14 79.31 18 13.92
-13 74.54 19 13.26
-12 70.17 20 12.64
-11 66.09 21 12.06
-10 62.28 22 11.50
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
44 4.39 79 1.21
45 4.21 80 1.17
46 4.05 81 1.14
47 3.89 82 1.10
48 3.73 83 1.06
49 3.59 84 1.03
50 3.45 85 1.00
51 3.32 86 0.97
52 3.19 87 0.94
53 3.07 88 0.91
54 2.96 89 0.88
55 2.84 90 0.85
56 2.74 91 0.83
57 2.64 92 0.80
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
-9 58.71 23 10.97
-8 56.37 24 10.47
-7 52.24 25 10.00
-6 49.32 26 9.55
-5 46.57 27 9.12
-4 44.00 28 8.72
-3 41.59 29 8.34
-2 39.82 30 7.97
-1 37.20 31 7.62
0 35.20 32 7.29
1 33.33 33 6.98
2 31.56 34 6.68
3 29.91 35 6.40
4 28.35 36 6.13
5 26.88 37 5.87
6 25.50 38 5.63
58 2.54 93 0.78
59 2.45 94 0.75
60 2.36 95 0.73
61 2.27 96 0.71
62 2.19 97 0.69
63 2.11 98 0.67
64 2.04 99 0.65
65 1.97 100 0.63
66 1.90 101 0.61
67 1.83 102 0.59
68 1.77 103 0.58
69 1.71 104 0.56
70 1.65 105 0.54
71 1.59 106 0.53
72 1.54 107 0.51
73 1.48 108 0.50
7 24.19 39 5.40
8 22.57 40 5.18
9 21.81 41 4.96
10 20.72 42 4.76
11 19.69 43 4.57
74 1.43 109 0.48
75 1.39 110 0.47
76 1.34 111 0.46
77 1.29 112 0.45
78 1.25 113 0.43
54
Page 55
Temp.
(°C)
114 0.42 127 0.30
115 0.41 128 0.29
116 0.40 129 0.28
117 0.39 130 0.28
118 0.38 131 0.27
119 0.37 132 0.26
120 0.36 133 0.26
121 0.35 134 0.25
122 0.34 135 0.25
123 0.33 136 0.24
124 0.32 137 0.23
125 0.32 138 0.23
126 0.31 139 0.22
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
16 82.54 51 18.96
17 78.79 52 18.26
18 75.24 53 17.58
19 71.86 54 16.94
20 68.66 55 16.32
21 65.62 56 15.73
22 62.73 57 15.16
23 59.98 58 14.62
24 57.37 59 14.09
25 54.89 60 13.59
26 52.53 61 13.11
27 50.28 62 12.65
28 48.14 63 12.21
29 46.11 64 11.79
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Probe T5
Temp.
(°C)
-20 542.7 -2 200.7
-19 511.9 -1 190.5
-18 483.0 0 180.9
-17 455.9 1 171.9
-16 430.5 2 163.3
-15 406.7 3 155.2
-14 384.3 4 147.6
-13 363.3 5 140.4
-12 343.6 6 133.5
-11 325.1 7 127.1
-10 307.7 8 121.0
-9 291.3 9 115.2
-8 275.9 10 109.8
-7 261.4 11 104.6
-6 247.8 12 99.69
-5 234.9 13 95.05
-4 222.8 14 90.66
-3 211.4 15 86.49
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
30 44.17 65 11.38
31 42.33 66 10.99
32 40.57 67 10.61
33 38.89 68 10.25
34 37.30 69 9.90
35 35.78 70 9.57
36 34.32 71 9.25
37 32.94 72 8.94
38 31.62 73 8.64
39 30.36 74 8.36
40 29.15 75 8.08
41 28.00 76 7.82
42 26.90 77 7.57
43 25.86 78 7.32
44 24.85 79 7.09
45 23.89 80 6.86
46 22.89 81 6.64
47 22.10 82 6.43
48 21.26 83 6.23
49 20.46 84 6.03
50 19.69 85 5.84
55
Page 56
REMKO ATY series
Temp.
(°C)
86 5.66 109 2.86
87 5.49 110 2.78
88 5.32 111 2.70
89 5.16 112 2.63
90 5.00 113 2.56
91 4.85 114 2.49
92 4.70 115 2.42
93 4.56 116 2.36
94 4.43 117 2.29
95 4.29 118 2.23
96 4.17 119 2.17
97 4.05 120 2.12
98 3.93 121 2.06
99 3.81 122 2.01
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
100 3.70 123 1.96
101 3.60 124 1.91
102 3.49 125 1.86
103 3.39 126 1.81
104 3.30 127 1.76
105 3.20 128 1.72
106 3.11 129 1.67
107 3.03 130 1.63
108 2.94
56
Page 57

12 Care and maintenance

Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
DANGER!
Prior to performing any work, ensure the equip­ment is disconnected from the voltage supply and secured to prevent accidental switch-on!
Care
n Ensure the unit is protected against dirt, mould
and other deposits.
n Only clean the unit using a damp cloth. Do not
use any caustic, abrasive or solvent-based cleaning products. Do not use a jet of water.
n Before an extended shut down period starts,
clean the fins on the outdoor unit and cover the outdoor unit with plastic to avoid infiltration of dirt into the unit.
Type of task
Checks/maintenance/inspection
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an appropriate specialist firm.
This enables you to ensure the operational reli­ability of the plant at all times!
NOTICE!
Statutory regulations require an annual leak test for the cooling cycle dependant on the refrig­erant quantity. Inspection and documentation of the work performed is to be carried out by spe­cialist technicians.
Commis-
sioning
Monthly Half-
yearly
Yearly
General
Check voltage and current
Check function of compressor/fans
Dirt on condenser/evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
see note
Cleaning the housing
1. Disconnect the power supply to the unit.
2. Clean the grill and cover with a soft, damp
cloth.
3. Switch the power supply back on.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval if the air is especially
.
dirty
l
l
l
l l
l
l
l
l
l
Cleaning the filter
1. Disconnect the power supply to the unit.
2. Open the front side of the unit by folding the
unit trim upwards and allowing it to engage (Fig. 47).
3. Raise the filter and pull it out pulling down­wards.
4. Clean the filter with a commercially available vacuum cleaner so it is facing upwards (Fig. 48).
. To do so, turn the dirty side
l
l
l
l
l
l
l
1)
l
57
Page 58
REMKO ATY series
5. Dirt can also be removed by carefully
cleaning with lukewarm water and mild cleaning agents. T so it is facing down (Fig. 49).
6. If water is used, let the filter dry out properly in the air before fitting it back into the unit.
7. Carefully insert the filter locates correctly.
8. Close the front side as described above in reverse order
9. Switch the power supply back on.
10. Switch the unit back on.
o do so, turn the dirty side
. Ensure that it
.
Cleaning the condensate pump (accessories)
The indoor unit may contain an optional integrated or separate condensate pump, which pumps out any accumulated condensate into higher posi­tioned drains.
Observe the care and maintenance instructions in the separate operating manual.
Fig. 47: Open the unit trim upwards
Fig. 48: Cleaning with a vacuum cleaner
Fig. 49: Cleaning with lukewarm water
58
Page 59

13 Shut-down

Temporary shut-down
1. Allow the indoor unit to run for 2 to 3 hours in
air circulation mode or in cooling mode at the maximum temperature setting in order to remove any residual moisture from the unit.
2. Shut down the system using the remote con­trol.
3. Switch of
4. Check the unit for visible signs of damage
and clean it as described in the chapter "Care and maintenance"
Permanent shut-down
Ensure that equipment and components are dis­posed of in accordance with the applicable regula­tions, e.g. through authorised disposal and recy­cling specialists or at collection points.
REMKO GmbH & Co. KGor your contractual partner will be pleased to provide a list of certified firms near you.
f the voltage supply to the unit.
59
Page 60
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
24
23
REMKO ATY series

14 Exploded view and spare parts lists

14.1 Exploded view - Indoor unit

Fig. 50: Exploded view of the ondoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
60
Page 61

14.2 Spare parts list - Indoor unit

IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
1 Unit trim
2 Air filter, set
3 Fine dust filter
4 Unit trim, bracket
5 Servo motor, LED light indicator
6 Servo motor, LED light indicator
7 Housing front
8 Evaporator
9 Fan motor
10 Fan wheel
11 Rubber mount fan rotor
12 IR remote control
TANT!
13 Air outlet flap, horizontal
14 Air outlet flap, vertical
15 Condensate hose
16 Housing rear wall incl. condensate tray
17 Wall bracket
18 Control board
19 Temperature probe for evaporator T2
20 Room temperature probe T1
21 Display board
22 Swing motor, horizontal/vertical
23 LED lighting, right
24 LED lighting, left
61
Page 62
1
2
3
4
5
6
7
8
9
10
11
12
13
14
17
18
16
21
19
15
20
22
REMKO ATY series

14.3 Exploded view - Outdoor unit

Fig. 51: Exploded view of the outdoor unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
62
Page 63

14.4 Spare parts list - Outdoor unit

IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial number (see type plate)
No. Designation
1 Front panel, left
2 Protection grid, front plate
3 Fan blade
4 Fan motor
5 Fan motor bracket
6 Corner panel
7 Housing cover
8 Base plate
9 Partitioning panel
10 Air probe condenser
11 Condenser
12 Condenser pipe placement probe
TANT!
13 Inductor
14 Control board
15 Shut-off valve, injection pipe
16 Side section, housing, right
17 Plastic covering, terminal block
18 Plastic covering, pipe connections
19 Shut-off valve, suction pipe
20 4-way valve
21 Compressor pipe placement probe
22 Compressor
23 Crankcase heating
24 Condensate tray heating
63
Page 64
REMKO ATY series

15 Index

A
Alarms
Checks .............................41
Possible causes ...................... 41
Remedial measures ................... 41
Assembly
Strip foundation ...................... 32
C
Care and maintenance ................... 57
Cleaning
Air filter for indoor unit ................. 57
Condensate pump ....................58
Housing ............................ 57
Condensate drainage connection and safe
drainage .............................. 32
Condensate pump, electrical wiring diagram ... 36
Customer service ....................... 41
D
Disposal of equipment .....................8
E
Electrical drawings ................... 37
Electrical wiring ......................... 34
Electrical wiring diagram .................. 35
Electrical wiring diagram, condensate pump ... 36
Environmental protection ...................8
Exploded view of the unit .............. 60, 62
, 38
F
Fault display on the indoor unit ............. 43
Function test of the cooling and heating modes 40
Functional checks ....................... 39
I
Infrared remote control ................... 14
Installation location, selection .............. 23
Installation materials ..................... 22
Intended use ............................ 7
K
Keys on the remote control ................ 15
M
Maintenance ........................... 57
Manual mode .......................... 14
Minimum clearances ..................... 25
O
Oil return measures ......................27
Ordering spare parts .................. 61, 63
P
Propellant in accordance with Kyoto Protocol .. 1
1
R
Remote control
Keys ...............................15
Resistances
Temperature probes ................... 54
S
Safe drainage in the event of leakages ....... 33
Safety
Dangers of failure to observe the safety
notes ............................... 5
General ............................. 5
Identification of notes ................... 5
Instructions for the operator .............. 6
Note for inspection work .................6
Note for installation work ................ 6
Note for maintenance work .............. 6
Personnel qualifications ................. 5
Safety-conscious working ................6
Unauthorised modification ...............7
Unauthorised replacement part manufacture . 7
Selection of installation location ............ 23
Shut-down
Permanent .......................... 59
Temporary .......................... 59
Spare parts list ...................... 61, 63
T
Temperature probes
Resistances ......................... 54
Test run ............................... 39
Troubleshooting and customer service ....... 41
U
Unit installation ......................... 27
W
Wall opening ........................... 22
Warranty ............................... 7
64
Page 65
65
Page 66
REMKO ATY series
66
Page 67
Page 68
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Hotline within Germany
+49 (0) 5232 606-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...