Boiler Type :Quinta Pro 45

Issue Date : July 2014

TECHNICAL SPECIFICATION SHEET

This is a quick reference specification sheet, full details can be found in the Quinta Pro Installation/Service guide via www.remeha.co.uk/documents

General Details

Fully condensing wall mounted boiler supplied c/w electronic temperature and safety controls.

One piece cast aluminium heat exchanger. Powder coated, enamel steel casing forming sealed air box. Ultra low NOx, fully modulating (18-100%), pre-mix burner, gas/air ratio control for maximum efficiency and minimum emissions. NOx classification to EN 483 and EN15420 (EN 297 A3) Intelligent "abc®" boiler control system c/w numerical display providing operating and service parameters. Manufactured to ISO 9001. CE approved (Pin 0063CL3333) and supplied pre-assembled.

 

MODEL : Quinta Pro 45

 

 

 

 

 

 

 

 

 

No of SECTIONS : One piece casting

 

 

 

 

 

 

 

 

Rated Output kW (80/60°c)

:

 

40

 

 

 

 

Gas Council No. :

 

41-288-16

 

 

 

Rated Output kW (50/30°c)

:

 

43

 

 

 

 

SBEM Seasonal Efficiency % : GCV(¹)

 

95.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (dry) kgs :

 

 

53

 

 

 

 

Min/Max Gas pressure mbar :

 

17-30 NG

 

 

 

 

 

 

 

 

 

 

 

Overall Dim WxHxD mm :

 

 

500x750x500

 

Min/Max Gas pressure mbar :

 

37-50 LPG

 

 

 

 

 

 

 

 

Radiated Losses watt % :

 

 

0.245@ 30°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BURNER TYPE Pre mix

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std Fuel Available :

 

 

Natural Gas

 

Optional Fuel :

 

Propane

 

 

Fuel Consumption M3/h :

 

 

4.4 NG max

 

LPG adjustment(²)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuel Consumption M3/h :

 

 

1.7 LPG max

 

Gas Connection size BSP :

 

¾(M)

 

 

 

 

 

 

 

 

Flame Protection :

 

 

Ionisation

 

Noise levels dB(A) at 1 metre :

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ignition :

 

 

Electronic

 

NOx (Dry 0% O ) Mg/kW :

 

37

 

 

 

 

 

 

 

HYDRAULICS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Content ltrs :

 

 

 

 

 

 

5.5

 

 

Connection Size “ BSP :

 

1¼” (M)

 

 

Resistance @ 11 C t mbar :

 

 

297.5

 

 

Std Operating Temp C :

 

20 - 90(³)

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance @ 20 C t mbar :

 

 

90

 

 

Max Operating Temp C :

 

90 (³)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nom Flow Rate @ 11 C t l/s :

 

 

0.87

 

 

High Limit Set Point C :

 

110(³)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nom Flow Rate @ 20 C t l/s :

 

 

0.48

 

 

Max operating pressure bar :

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Flow Rate m3/hr :

 

 

 

 

 

 

0.4

 

 

Min operating pressure bar :

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensate Connection :

 

 

 

 

 

 

¾” OD

 

Min operating pressure bar :

 

0.3 o/v

 

 

 

 

 

 

 

 

 

 

 

 

FLUE/AIR INLET

 

 

Concentric connection

 

Supplied as standard * #

 

 

 

 

 

 

 

 

 

Flue diameter mm I/D :

 

 

80

 

 

 

 

Mass flue gas flow rate kgs/hr :

 

14 - 69

 

 

 

 

 

Air inlet diameter mm I/D :

 

 

125

 

 

 

Flue Gas Temperature °C :

 

30 - 67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum counter pressure PA :

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply :

 

 

230v – 1ph – 50hz

 

Fuse Rating amps :

 

6.3

 

 

 

 

 

 

 

Start Current amps :

 

 

1.8

 

 

 

 

Controls Voltage :

 

24 (max 4va)

 

 

 

 

 

 

 

 

 

 

 

Power Consumption W :

 

 

18 - 68

 

 

Insulation Class IP :

 

X4D

 

 

 

 

 

 

 

 

 

Modulating input V dc :

 

 

0 -10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard :

 

 

On/Off, 0-10v dc, Open Therm

 

Manual o/ride

 

 

 

 

 

 

 

 

 

 

 

High limit protection

 

Modulating (18 - 100%)

 

 

 

 

 

 

 

 

 

 

 

Low water protection

 

Hot water priority facility (3 way valve or pump)

 

 

 

 

 

 

 

 

Volt free common alarm and

 

Two Safety interlocks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

boiler run indication

 

Hours run indication

 

 

 

 

 

 

 

 

Optional :

 

 

 

Optimising/Compensators,

 

For single and multiple boiler controls

 

 

 

 

 

 

 

 

For further options

 

 

 

Cascade Kits

 

Multiple boiler pipework kits

 

 

 

 

 

 

 

 

Contact our sales team

 

 

Low loss headers

 

Single and multiple boiler

 

 

 

 

 

 

 

 

 

 

 

 

Outside sensor

 

For simple weather compensation

 

 

 

 

 

 

 

 

 

 

 

Hot water priority kits

 

Pump or valve kits

 

 

 

 

 

 

 

 

 

 

 

 

Relay Kits

 

230v switching relay

 

 

 

 

 

 

 

(¹) In aaccordance with the Non Domestic Building Services Compliance Guide 2013 Edition – For use in England

(²) See installation and service manual

(³) Open vented option maximum operating temperature 80°c high limit 95°c

*For conventional or room sealed operation

#Flue adaptor available for CLV systems

Ours is a policy of continuous development, we therefore reserve the right to alter specifications without prior notification. Remeha Commercial accept no liability for any loss or damage rising from any errors or omissions that may be inadvertently contained in this specification sheet.

Loading...