Boiler Type :Quinta Pro 45
Issue Date : July 2014
TECHNICAL SPECIFICATION SHEET
This is a quick reference specification sheet, full details can be found in the Quinta Pro Installation/Service guide via www.remeha.co.uk/documents
General Details
Fully condensing wall mounted boiler supplied c/w electronic temperature and safety controls.
One piece cast aluminium heat exchanger. Powder coated, enamel steel casing forming sealed air box. Ultra low NOx, fully modulating (18-100%), pre-mix burner, gas/air ratio control for maximum efficiency and minimum emissions. NOx classification to EN 483 and EN15420 (EN 297 A3) Intelligent "abc®" boiler control system c/w numerical display providing operating and service parameters. Manufactured to ISO 9001. CE approved (Pin 0063CL3333) and supplied pre-assembled.
|
MODEL : Quinta Pro 45 |
|
|
|
|
|
|
|
|
|
No of SECTIONS : One piece casting |
|
|
|
|
|
|
|
||
|
Rated Output kW (80/60°c) |
: |
|
40 |
|
|
|
|
Gas Council No. : |
|
41-288-16 |
|
|
|||||||
|
Rated Output kW (50/30°c) |
: |
|
43 |
|
|
|
|
SBEM Seasonal Efficiency % : GCV(¹) |
|
95.75 |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
Weight (dry) kgs : |
|
|
53 |
|
|
|
|
Min/Max Gas pressure mbar : |
|
17-30 NG |
|
||||||||
|
|
|
|
|
|
|
|
|
||||||||||||
|
Overall Dim WxHxD mm : |
|
|
500x750x500 |
|
Min/Max Gas pressure mbar : |
|
37-50 LPG |
|
|||||||||||
|
|
|
|
|
|
|||||||||||||||
|
Radiated Losses watt % : |
|
|
0.245@ 30° |
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
BURNER TYPE Pre mix |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Std Fuel Available : |
|
|
Natural Gas |
|
Optional Fuel : |
|
Propane |
|
|||||||||||
|
Fuel Consumption M3/h : |
|
|
4.4 NG max |
|
LPG adjustment(²) |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
Fuel Consumption M3/h : |
|
|
1.7 LPG max |
|
Gas Connection size BSP : |
|
¾” (M) |
|
|||||||||||
|
|
|
|
|
|
|||||||||||||||
|
Flame Protection : |
|
|
Ionisation |
|
Noise levels dB(A) at 1 metre : |
|
45 |
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Ignition : |
|
|
Electronic |
|
NOx (Dry 0% O ) Mg/kW : |
|
37 |
|
|
|
|
|
|
||||||
|
HYDRAULICS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Water Content ltrs : |
|
|
|
|
|
|
5.5 |
|
|
Connection Size “ BSP : |
|
1¼” (M) |
|
||||||
|
Resistance @ 11 C t mbar : |
|
|
297.5 |
|
|
Std Operating Temp C : |
|
20 - 90(³) |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
||||||||||||
|
Resistance @ 20 C t mbar : |
|
|
90 |
|
|
Max Operating Temp C : |
|
90 (³) |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
Nom Flow Rate @ 11 C t l/s : |
|
|
0.87 |
|
|
High Limit Set Point C : |
|
110(³) |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
Nom Flow Rate @ 20 C t l/s : |
|
|
0.48 |
|
|
Max operating pressure bar : |
|
4 |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
Min Flow Rate m3/hr : |
|
|
|
|
|
|
0.4 |
|
|
Min operating pressure bar : |
|
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
Condensate Connection : |
|
|
|
|
|
|
¾” OD |
|
Min operating pressure bar : |
|
0.3 o/v |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|||||||||||
|
FLUE/AIR INLET |
|
|
Concentric connection |
|
Supplied as standard * # |
|
|
|
|
|
|
|
|
||||||
|
Flue diameter mm I/D : |
|
|
80 |
|
|
|
|
Mass flue gas flow rate kgs/hr : |
|
14 - 69 |
|
|
|
|
|||||
|
Air inlet diameter mm I/D : |
|
|
125 |
|
|
|
Flue Gas Temperature °C : |
|
30 - 67 |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
Maximum counter pressure PA : |
|
150 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
ELECTRICAL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power Supply : |
|
|
230v – 1ph – 50hz |
|
Fuse Rating amps : |
|
6.3 |
|
|
|
|
|
|
||||||
|
Start Current amps : |
|
|
1.8 |
|
|
|
|
Controls Voltage : |
|
24 (max 4va) |
|
||||||||
|
|
|
|
|
|
|
|
|
||||||||||||
|
Power Consumption W : |
|
|
18 - 68 |
|
|
Insulation Class IP : |
|
X4D |
|
||||||||||
|
|
|
|
|
|
|
||||||||||||||
|
Modulating input V dc : |
|
|
0 -10 |
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
CONTROL OPERATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard : |
|
|
On/Off, 0-10v dc, Open Therm |
|
Manual o/ride |
|
|
|
|
|
|
|
|||||||
|
|
|
|
High limit protection |
|
Modulating (18 - 100%) |
|
|
|
|
|
|
|
|||||||
|
|
|
|
Low water protection |
|
Hot water priority facility (3 way valve or pump) |
|
|
|
|
||||||||||
|
|
|
|
Volt free common alarm and |
|
Two Safety interlocks |
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
boiler run indication |
|
Hours run indication |
|
|
|
|
|
|
|
|||||||
|
Optional : |
|
|
|
Optimising/Compensators, |
|
For single and multiple boiler controls |
|
|
|
|
|
|
|
||||||
|
For further options |
|
|
|
Cascade Kits |
|
Multiple boiler pipework kits |
|
|
|
|
|
|
|
||||||
|
Contact our sales team |
|
|
Low loss headers |
|
Single and multiple boiler |
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
Outside sensor |
|
For simple weather compensation |
|
|
|
|
|
|
|
||||||
|
|
|
|
Hot water priority kits |
|
Pump or valve kits |
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
Relay Kits |
|
230v switching relay |
|
|
|
|
|
|
|
(¹) In aaccordance with the Non Domestic Building Services Compliance Guide 2013 Edition – For use in England
(²) See installation and service manual
(³) Open vented option maximum operating temperature 80°c high limit 95°c
*For conventional or room sealed operation
#Flue adaptor available for CLV systems
Ours is a policy of continuous development, we therefore reserve the right to alter specifications without prior notification. Remeha Commercial accept no liability for any loss or damage rising from any errors or omissions that may be inadvertently contained in this specification sheet.