Quadra-Fire QVI35S, QVI30S User Manual

Model(s): QVI30S
QVI35S
R
Owner’s Manual
Installation and Operation
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury, or death.
• Do not store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- Do not try to light any appliance
- Do not touch any electrical switch. Do not
use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli­er’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency , or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard, Title
24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
• Read, understand and follow these instructions for safe installation and operation.
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts:
• installation must be performed by a licensed plumber or gas fi tter;
• a CO detector shall be installed in the room where the appliance is installed.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional.
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
1
Read this manual before installing or operating this appliance.
Not
for
use
with
solid
fuel.
Ne
doit
pas
entre
utilise
avec
un
combustible
solide).
This
appliance
must
be
installed
in
accordance
with
local
codes,
if
any;
if
not,
follow
ANSI
Z223.1
in
the
USA
or
CAN/CGA
B149
installation
codes.
(Installer
l’appareil
selon
les
codes
ou
reglements
locaux
ou,
en
l’absence
de
tels
reglements,
selon
les
codes
d’installation
CAN/CGA-B149.)
Type
of
Gas
(Sorte
De
Gaz):
NA
TURAL
GAS
MADE
IN
USA
Minimum
Permissible
Gas
Supply
for
Purposes
of
Input
Adjustment.
Approved
Minimum
(De
Gaz)
Acceptable
0.0
in
w.c.
(Po.
Col.
d’eau)
Maximum
Pressure
(Pression)
0.0
in
w.c.
(Po.
Col.
d’eau)
Maximum
Manifold
Pressure
(Pression)
0.0
in
w.c.
(Po.
Col.
d’eau)
Minimum
Manifold
Pressure
(Pression)
0.0
in
w.c.
(Po.
Col.
d’eau)
Model:
(Modele):
Serial
(Serie):
ANSI
Z21XX-XXXX · ·
CSA
2.XX-MXX · ·
UL307B
XXXXXXXX
IN
CANADA
ALTITUDE:
0-0000
FT.
0000-0000FT.
MAX.
INPUT
BTUH:
00,000
00,000
MIN.
INPUT
BTUH:
00,000
00,000
ORIFICE
SIZE:
#XXXXX
#XXXXX
XXXXXXXX
Total
Electrical
Requirements:
000Vac,
00Hz.,
less
than
00
Amperes
Please retain this owner’s manual for future reference.
Congratulations
Congratulations on selecting a Quadra-Fire gas appliance —an elegant and clean alternative to wood burning appliances. The Quadra-Fire gas appliance you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new appliance, you’ll want to read and carefully follow all of the instructions contained in this Owner’s Manual. Pay special attention to all Cautions and Warnings.
Homeowner Reference Information
This Owner’s Manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this Owner’s Manual, unless noted otherwise, applies to all models and gas control systems.
Y our new Quadra-Fire gas appliance will give you years of durable use and trouble-free enjoyment. Welcome to the Quadra-Fire family of appliance products!
We recommend that you record the following pertinent information about your appliance.
Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on appliance: ____________________ Dealership purchased from: _______________________________ Dealer Phone: __________________________ Notes: _______________________________________________________________________________________ _____________________________________________________________________________________________
Listing Label Information/Location
This product may be covered by one or more of the following patents: (Nos produits sont couverts par un ou plusieurs des brevets suivants): (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, D320652, D445174, D462436; (Canada)1297749, 2195264, 2225408; or other U.S. and foreign patents pending (ou autres brevets americains et etrangers en attente).
Type of Gas
Not ((Ne
Type
Gas and Electric Information
2
ALTITUDE: MAX. MIN. ORIFICE
Minimum
Approved
Maximum
Maximum
Minimum
Total
for
use
doit
pas
of
Gas
TURAL
Electrical
INPUT
INPUT
SIZE:
The model information regarding your specifi c appliance can be found on the rating plate usually located in the control area of the appliance.
R
Quadra-Fire, a brand of Hearth & Home Technologies Inc. 1445 North Highway 395, Colville, WA 99114
with
solid
fuel.
entre
utilise
avec
un
combustible
This
appliance
(Sorte
De
Gaz)
GAS
Permissible
Minimum
Pressure
Manifold
Manifold
Requirements:
BTUH:
BTUH:
Gas
(De
(Pression)
Pressure
Pressure
0-0000 00,000 00,000 #XXXXX
in
locaux
the
USA
or
ou,
en
Supply
Gaz)
Acceptable
(Pression)
(Pression)
000Vac,
IN
FT.
0000-0000FT. 00,000 00,000 #XXXXX
must
CAN/CGA
l’absence
for
CANADA
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
be
installed B149
de
ANSI
Z21XX-XXXX
Purposes
00Hz.,
solide).
in
installation
tels
reglements,
0.0
in
0.0
in
0.0
in
0.0
in
less
accordance
codes.
of
Input
w.c.
w.c.
w.c.
w.c.
than
Model:
(Modele):
Serial
(Serie):
with
local
codes,
(Installer
l’appareil
selon
les
codes
CSA
2.XX-MXX
Adjustment.
(Po.
Col.
(Po.
Col.
(Po.
Col.
(Po.
Col.
00
Amperes
if
d’installation
d’eau)
d’eau)
d’eau)
d’eau)
XXXXXXXX
XXXXXXXX
any;
selon
UL307B
if
not,
les
MADE
follow
codes
ANSI
Z223.1
ou
reglements
CAN/CGA-B149.)
IN
USA
Model Number
Serial Number
Table of Contents
1 Listing and Code Approvals
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 4
D. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 4
E. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 4
F. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 5
B. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . 5
C. Inspect Appliance and Components . . . . . . . . . . . . . . . . . . 5
3 Fireplace Size Requirements
A. Minimum Fireplace Opening . . . . . . . . . . . . . . . . . . . . . . . 6
B. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Termination Locations
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . . 8
5 Vent Information and Diagrams
A. Vent Table Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
B. Horizontal Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
C. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 Installation Preparation
A. Flue Damper. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
B. Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
C. Gas Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
D. Hearth or Hearth Extension . . . . . . . . . . . . . . . . . . . . . . . 10
E. Fireplace Conversion Notice . . . . . . . . . . . . . . . . . . . . . . 10
F. Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Installing Vent Pipe and Appliance
A. Venting Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
B. Connecting Vent Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
C. Placing, Securing and Leveling the Appliance . . . . . . . . . 12
D. Installing Adaptor and Termination Cap . . . . . . . . . . . . . . 13
8 Gas Information
A. Fuel Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
B. Gas Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Electrical Information
A. Wiring the Appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
B. Junction Box Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 17
10 Finishing
A. Mantel Projections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
11 Appliance Setup
A. Remove Shipping Materials . . . . . . . . . . . . . . . . . . . . . . . 20
B. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
C. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
D. Ember Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
E. Refractory Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
F. Positioning the Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
G. Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
H. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
12 Operating Instructions
A. Before Lighting Appliance. . . . . . . . . . . . . . . . . . . . . . . . . 28
B. Lighting Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
C. Check Pilot Flame Appearance . . . . . . . . . . . . . . . . . . . . 30
D. After Appliance is Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
E. Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . 31
13 Troubleshooting
A. Standing Pilot Ignition System . . . . . . . . . . . . . . . . . . . . . 32
14 Maintaining and Servicing Appliance
A. Maintenance Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
15 Reference Materials
A. Appliance Dimension Diagram . . . . . . . . . . . . . . . . . . . . . 36
B. Vent Kits Components . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
C. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
D. Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . 43
E. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Î
Î Î
Î
Î = Contains updated information.
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
3
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODELS: QVI30S, QVI35S LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Vented Gas Appliance Heaters STANDARD: ANSI Z21.88-2000 • CSA2.33-M00 • UL307B
This product is listed to ANSI standards for “Vented Gas Appliance Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOT INTENDED FOR USE AS A PRIMAR Y HEA T SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
Note: To assure top performance, safety and effi ciency, inserts must be installed with an approved fl ue liner as per CAN/CGA B-149 or National Fuel Gas Code ANSI Z223 and these instructions.
Note: This installation must conform with local codes. In the absence of local c odes you must comply w ith the National Fuel Gas Code, ANSI Z223.1 -latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
C. High Altitude Installations
U.L. Listed gas appliances are tested and approved with­out requiring changes for elevations from 0 to 2000 feet in the U.S.A. and Canada.
When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rat­ing by changing the existing burner orifi ce to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A., or 10% for elevations between 2000 and 4500 feet in Canada. If the heating value of the gas has been reduced, these rules do not apply. To identify the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.
WARNING
Do NOT use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
D. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750º C, shall be considered
non-combustible materials.
B. BTU Specifi cations
Models
(U.S. or Canada)
US
QVI30S (NG)
QVI35S (NG)
QVI30S (LP)
QVI35S (LP)
4
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
E. Combustible Materials Specifi cation
Maximum
Input
BTU/h
32,000 22,000 #35
28,800 19,800 #36
35,500 23,500 #32
31,950 21,150 #33
31,000 18,000 #52
27,900 16,200 #53
31,000 19,000 #51
27,900 17,100 #52
Minimum
Input
BTU/h
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
Orifi ce
Size
(DMS)
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ig- nite and burn, whether fl ame proofed or not, or whether plastered or unplastered shall be considered combustible materials.
F. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
2
2
Getting Started
A. Design and Installation Considerations
Quadra-Fire direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
CAUTION
Check building codes prior to installation.
• Installation MUST comply with local, regional, state and national codes and regulations.
• Consult insurance carrier, local building, fi re offi cials or authorities having jurisdiction about restrictions, installation inspection, and permits.
Quadra-Fire gas inserts are designed for recessed installa­tions into solid fuel masonry or factory built non-combustible replaces that have been installed in accordance with the National, Provincial, State and local building codes.
Prior to installing the gas insert:
• Have the chimney and adjacent structure inspected and cleaned by qualifi ed professionals. Hearth & Home Technologies recommends that NFI or CSIA certifi ed professionals, or technicians under the direction of certi­ ed professionals, conduct a minimum of a NFPA 211 Level 2 inspection of the chimney.
• Replace component parts of the chimney and fi replace as specifi ed by the professionals.
• Ensure all joints are properly engaged and the chimney is properly secured.
When planning an appliance installation, it’s necessary to determine the following information before installing:
• Minimum fi replace size. See Section 3.A.
• Gas supply piping.
• Electrical wiring.
• Finishing details.
• Existing mantel, mantel legs and wall projection loca­tions. See Section 3.C.
• Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Pliers Hi temp caulking material Hammer Flat blade screwdriver Voltmeter Framing square Gloves Variable speed drill 1/4 Hex drive Safety glasses Manometer Phillips screwdriver Tape measure Non-corrosive leak check solution 1/2 - 3/4 inch length, #6 or #8 Self-drilling screws
C. Inspect Appliance and Components
WARNING
Inspect appliance and components for damage. Damaged parts may impair safe operation.
• Do NOT install damaged components.
• Do NOT install incomplete components.
• Do NOT install substitute components. Report damaged parts to dealer.
• Carefully remove the appliance and components from the packaging.
• The vent system components, surrounds and fronts are shipped in separate packages.
• The fi ber logs may be packaged separately and must be fi eld installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
• Read all of the instructions before starting the insta­llation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING
Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING
Keep appliance dry.
• Mold or rust may cause odors.
• Water may damage controls.
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
5
3
3
Fireplace Size Requirements
A. Minimum Fireplace Opening
Minimum fi replace opening requirements are shown in Figure 5.1.
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat­ed out of traffi c and away from furniture and draperies.
• The fi rebrick (refractory), glass doors, screen rails, screen mesh and log grates can be removed from a factory built fi rebox in order to gain minimum gas insert opening requirements.
• Any smoke shelves, shields and baffl es may be removed from the factory built fi rebox if attached with mechanical fasteners.
• The metal fl oor of the solid fuel fi rebox may be removed to facilitate the installation of the insert. The appliance may not be placed directly on the base of the outer wrap, a 1/4 inch airspace must be provided between the insert and the fl oor of the outer wrap. Use the levelling legs to raise the insert a minimum of 1/4 inch. The original fi replace may never be returned to solid fuel in this condition. The sidewalls and top structure of the fi rebox may not be altered with the exception of removable baffl es and dampers.
• Cutting of any sheet metal parts of the fi replace in which the gas fi replace insert is to be installed is prohibited, except the fl oor as tested for and as noted above.
NOTE: For actual appliance dimensions refer to Section 15.
B
C
Location QVI35S QVI30S
A Front Width 33-1/4 845 29-1/4 743 B Rear Width 24-1/4 616 20-1/4 515 C Depth 13-5/8 346 13-5/8 346
* Height 22-3/4 578 20-1/4 515
* NOTE: If exhaust collar on insert and fi replace damper do not line up, add 4
inches (102mm) to minimum fi replace height for bends in vent pipe.
Figure 3.1 Fireplace Opening
TOP VIEW
A
Minimum Appliance Size
Inches Millimeters Inches Millimeters
6
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
B. Clearances
Fire Risk. Odor Risk.
• Clearance to combustible material under the insert is 1/4 inch (0.6 cm).
• Use leveling legs to raise insert minimum 1/4 inch above combustible material or outer wrap of factory built fi rebox.
Fire Risk.
• Locate and install appliance to all clearance specifi cations in manual.
WARNING
WARNING
EXHAUST
VENT PIPE
INLET AIR
VENT PIPE
12 in. MAX.
MANTEL
12 in. MIN.
MEASUREMENTS FROM
TOP EDGE OF UNIT
Figure 3.2 Clearances to Mantels or other Combustibles above Appliance
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
7
4
4
Termination Locations
A. Vent Termination Minimum Clearances
Figure 4.1 specifi es minimum vent heights for various pitched roofs.
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
VERTICAL
WALL
IS X/ 12
* 3 foot minimum in snow regions
Figure 4.1 Minimum height from roof to lowest discharge opening
WARNING
Fire Risk. Asphyxiation Risk.
• Terminations MUST meet minimum clearances.
• Exhaust gases are hot.
• Nearby vents may draw fumes into house.
8
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
5
5
Vent Information and Diagrams
A. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
V
MIN
V
MIN
Minimum Vertical Run Length 14 ft.
Maximum Vertical Run Length 50 ft.
B. Horizontal Venting
Horizontal venting is NOT allowed.
C. Measuring Standards
Vertical measurements listed in the vent diagram (Figure
5.1) were made using the following standard:
• Vertical terminations are measured to top of chimney.
WARNING
Fire Hazard. Explosion Risk. Asphyxiation Risk. Do NOT connect this gas appliance to a
chimney fl ue serving a separate solid fuel or gas burning appliance.
• May impair safe operation of this appliance or other appliances connected to the fl ue.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
CAUTION
ALL vent specifi cations MUST be followed.
• This product is tested and listed to these specifi cations.
• Appliance performance will suffer if specifi cations are not followed.
TERMINATION CAP
ADAPTOR
EXHAUST VENT PIPE
INSULATION SEAL
Figure 5.1
INLET VENT AIR PIPE
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
9
6
6
Installation Preparation
Prepare the existing solid fuel masonry or factory built non-combustible fi rebox for installation.
A. Flue Damper
Fully lock the solid fuel fi replace’s fl ue damper in the open position, OR completely remove it.
B. Chimney
• Ensure chimney is constructed of non-combustible materials.
• Ensure chimney is clean and in good working order.
• Ensure that all chimney cleanouts fi t properly to prevent air leakage into chimney.
C. Gas Line
Note: If the factor y built replace has no gas acces s hole
provided, an acces s hole of 1 inch (25 mm) diameter o r less may be drilled through the lower sides or bottom of the rebox in a proper workmanship - like manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed.
• Install gas line into fi rebox cavity.
• Check local codes and gas line sizing requirements following NFPA54. See Section 8.
E. Fireplace Conversion Notice
Permanently attach the label with the following warning to the inside lower back of the fi replace fi rebox into which the insert is being installed. Silicone may be required to properly secure the label.
WARNING
Fire Risk. This fi replace has been converted for use with
a gas fi replace insert only and cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fi replace re- approved by the authority having jurisdiction.
Prior to installing the gas insert:
• Have the chimney and adjacent structure inspected and cleaned by qualifi ed professionals. Hearth & Home Technologies recommends that NFI or CSIA certifi ed professionals, or technicians under the direction of certi­ ed professionals, conduct a minimum of a NFPA 211 Level 2 inspection of the chimney.
• Replace component parts of the chimney and fi replace as specifi ed by the professionals.
• Ensure all joints are properly engaged and the chimney is properly secured.
D. Hearth or Hearth Extension
WARNING
Fire Risk. A hearth or hearth extension (if present) must
comply with either of the following:
• The solid fuel burning fi replace manufacturer’s specifi cation.
• Local building codes required by authority having jurisdiction.
• NFPA 211
F. Remote Control
The receiver for the remotes must be installed BETWEEN the base pan of the insert and the fi rebox of the wood- burning fi replace (see photo below).
EXISTING SIDE
REFRACTORY
REMOTE
RECEIVER
UNIT
EXISTING BOTTOM OF
FIREPLACE
10
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
7
7
Installing Vent Pipe and Appliance
A. Venting Components
CAUTION
Sharp Edges
• Wear protective gloves and safety glasses during installation.
The vertical vent termination system installed on this model includes:
• One length of 3-inch fl exible vent pipe for combustion air (included with vent kit). Pipe will be either a 4-foot or 30-foot section depending on which kit is being used in the application.
• Flexible vent pipe for exhaust air (included with vent kit).
• One pipe-to-cap adaptor (included with vent kit).
• One vertical termination cap (included with vent kit).
B. Connecting Vent Pipe
Reference instructions in the termination kit.
• Install the 3-inch fl exible vent pipe(s) down through the chimney.
• Use three screws to secure the exhaust fl exible vent pipe to the 3 foot section stainless steel fl exible vent pipe using the factory-installed 3-inch collar in the stainless steel section of pipe (see Figure 7.1).
• Use 3 screws to attach either a 4 foot or 30 foot section of inlet air vent to the inlet collar on the collar slide plate (see Figure 7.1). NOTE: The collar slide plate may be removed from appliance to aid installation.
• Seal opening between fl ex vent and chimney just above insert. Non-combustible, unfaced fi berglass insulation may be used for this purpose.
EXHAUST
AIR
VENT PIPE
TERMINATION
CAP
INLET AIR STARTING COLLAR
LOCKING TAB
STARTING COLLAR BRACKET
EXHAUST STARTING COLLAR
INLET AIR VENT PIPE
INLET AIR STARTING COLLAR
Figure 7.1
STARTING COLLAR BRACKET
EXHAUST STARTING COLLAR
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
11
CUT AND BEND
FLASHING AS NEEDED
TO FIT CHIMNEY
SEALANT
ADHESIVE
WARNING
Fire Risk. Only an approved Hearth & Home Technologies
surround may be used to cover integral grills on solid fuel burning fi replaces.
• No other components such as shrouds, sheet­metal plates, etc., may be used to seal off vents.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this appliance may result in property damage or personal injury.
Figure 7.2
• T rim chimney top plate to minimize excess overhang or bend over fl ue tile (see Figure 7.2).
• Place 3/8 inch bead of 300º F silicone on fl ue tile top.
C. Placing, Securing and Leveling the
Appliance
• Install insert (without surround attached) into existing replace while pulling collar slide plate forward.
• Install gas line into hole provided on insert side.
• If applicable install remote control wires into insert side (see Section 6, F.).
• Secure collar slide plate to appliance by placing locking handle into position with locking tabs (see Figure 7.1) and secure with #8 screw.
• Level the appliance from side to side and front to back. If necessary , use the leveling legs included with the manual bag to set each corner of the base.
• Position any excess fl exible vent pipe back up into chimney without sagging. Twist and push flex vent together to shorten.
• Non-combustible, unfaced fi berglass insulation may be installed between the back of the decorative surround and the face of the existing fi replace surround to which the insert is being installed. This insulation is not required, but can assist in the prevention of infi ltration of cold air and odors from the chimney.
• Attach surround. Follow instructions accompanying surround.
• Push insert so that surround becomes tight against face of fi replace.
WARNING
Explosion Risk. Combustion Fume Risk.
• Connect vent sections per installation instructions.
• Connect exhaust vent pipe ONL Y to exhaust starting collar and termination cap center collar.
• Connect inlet air vent ONLY to inlet air collar on appliance and either the termination cap inlet air collar OR terminate within chimney.
• Do NOT allow vent to sag below connection point to appliance.
12
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
D. Installing Adaptor and Termination Cap
For installation of termination cap see minimum vent heights for various pitched roofs (see Figure 7.2) .
To install adaptor see Figure 7.3.
HORIZONTAL
OVERHANG
CAUTION
Sharp Edges
• Wear protective gloves and safety glasses during installation.
Damper Flashing Kit (Optional)
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12....................1.0*
Over 6/12 to 7/12 ........1.25*
Over 7/12 to 8/12 ..........1.5*
Over 8/12 to 9/12 ..........2.0*
Over 9/12 to 10/12 ........2.5*
Over 10/12 to 11/12 .....3.25
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
IS X/ 12
VERTICAL
WALL
Roof Pitch H (Min.) Ft.
Over 11/12 to 12/12 .......4.0
Over 12/12 to 14/12 .......5.0
Over 14/12 to 16/12 .......6.0
Over 16/12 to 18/12 .......7.0
Over 18/12 to 20/12 .......7.5
Over 20/12 to 21/12 .......8.0
* 3 foot minimum in snow regions
Figure 7.2 Minimum Height from Roof to Lowest Discharge Opening
For use with LINK-DV4-30B Liner Kit. Note: Damper may have to be removed to use this kit.
• Run fl ex liners through 3” holes in damper fl ashing.
• Attach damper fl ashing to fi rebox roof with self tapping screws included in kit.
CLASS A PIPE
Figure 7.3
To help eliminate cold air drafts, it may be necessary to place non­combustible insulation around the fl ues as they go though the damper.
Masonry
EXHAUST
VENT PIPE
Figure 7.4
AIR
LINK-DV30B
Installation
TERMINATION
CAP
ÍORÎ
INLET AIR
VENT PIPE
LINK-DV4-30B
Installation
WARNING: DO NOT BLOCK THIS PIPE END!
Note: Untwist the pipe while extending it, to achieve full 30’ length.
Note: The LINK-DV4-30B
system REQUIRES this insulation.
Factory Built
Wood Burning
OPTIONAL LINK-ZC-ADPB
FOR USE WITH CLASS A
WOODBURNING PIPE
Remove 18 inch x 18 inch fl ashing on cap by removing 3 screws. Connect both the LINK-ZC-ADPB to Class A Pipe and the termination cap to the LINK-ZC-ADPB with the self tapping screws provided.
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
13
8
8
Gas Information
A. Fuel Conversions
Before making gas connections ensure that appliance be­ing installed is compatible with the available gas type.
Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a qualifi ed technician using Hearth & Home Technologies specifi ed and approved parts.
B. Gas Pressures
Proper input pressures are required for optimum appli­ance performance. Gas line sizing requirements need to be made following NFPA54.
WARNING
Fire Risk. Explosion Hazard. High pressure will damage valve.
• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.
• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
C. Gas Connection
Note: Have the gas supply line installed in accordanc e
with local building codes, if any. If not, follow ANSI
223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter).
NOTE: A listed (and Commonwealth of Massachusetts ap­proved) 1/2 inch (13 mm) T-handle manual shut-of f valve and exible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.
• If substituting for these components, please consult local codes for compliance.
Refer to Reference Section 15 for location of gas line access in appliance.
NOTE: Gas line may be run from either side of the appliance provided the hole in the outer wrap does NOT exceed 2-1/2 inches in diameter and does not penetrate the fi rebox.
WARNING
WARNING
Verify inlet pressures.
• High pressure may cause overfi re condition.
• Low pressure may cause explosion.
• Verify minimum pressures when other household gas appliances are operating.
Install regulator upstream of valve if line pressure is greater than 1/2 psig.
Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.
Pressure Natural Gas Propane
Minimum inlet pressure
Maximum inlet gas pressure
Manifold pressure
5.0 inches w.c.
14.0 inches w.c.
3.5 inches w.c.
11.0 inches w.c.
14.0 inches w.c.
10.0 inches w.c.
Gas Leak Risk
• Support control when attaching pipe to prevent bending gas line.
NOTE: The gap bet ween supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to pre ven t cold air infi ltration.
• Ensure that gas line does not come in contact with outer wrap of appliance. Follow local codes.
• Incoming gas line should be piped into the valve compartment and connected to the 1/2 inch connection on the manual shutoff valve.
• Check all fi ttings and connections of appliance which may have loosened during shipping.
14
Quadra-Fire • QVI30S, QVI35S • 340-901 Rev. i • 6/09
Loading...