Successful application of this module requires a reasonable working knowledge of the Rockwell
Automation ControlLogix hardware, the MVI56-CAS Module and the application in which the
combination is to be used. For this reason, it is important that those responsible for implementation
satisfy themselves that the combination will meet the needs of the application without exposing
personnel or equipment to unsafe or inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to ensure that the
information provided is accurate and a true reflection of the product's installation requirements. In
order to ensure a complete understanding of the operation of the product, the user should read all
applicable Rockwell Automation documentation on the operation of the Rockwell Automation
hardware.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential
damages resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from
ProSoft Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a
commitment on the part of ProSoft Technology Improvements and/or changes in this manual or the
product may be made at any time. These changes will be made periodically to correct technical
inaccuracies or typographical errors.
Warnings
UL Warnings
A Warning - Explosion Hazard - Substitution of components may impair
B Warning - Explosion Hazard - When in Hazardous Locations, turn off
C Suitable for use in Class I, division 2 Groups A, B, C and D Hazardous
ATEX Warnings and Conditions of Safe Usage:
Power, Input, and Output (I/O) wiring must be in accordance with the authority
having jurisdiction
A Warning - Explosion Hazard - When in hazardous locations, turn off power
B Warning - Explosion Hazard - Do not disconnect equipment unless power
C These products are intended to be mounted in an IP54 enclosure. The
D DO NOT OPEN WHEN ENERGIZED.
suitability for Class I, Division 2.
power before replacing or rewiring modules.
Warning - Explosion Hazard - Do not disconnect equipment unless power
has been switched off or the area is known to be nonhazardous.
Locations or Non-Hazardous Locations.
before replacing or wiring modules.
has been switched off or the area is known to be non-hazardous.
devices shall provide external means to prevent the rated voltage being
exceeded by transient disturbances of more than 40%. This device must
be used only with ATEX certified backplanes.
Electrical Ratings
Backplane Current Load: 800 mA @ 5 V DC; 3mA @ 24V DC
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Shock: 30g Operational; 50g non-operational; Vibration: 5 g from 10 to 150
Hz
Relative Humidity 5% to 95% (non-condensing)
All phase conductor sizes must be at least 1.3 mm(squared) and all earth
ground conductors must be at least 4mm(squared).
Markings:
II 3 G 0C <=Ta<= 60C EEx nA IIC T4 DEMKO 07ATEX0710717X
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have
suggestions, comments, compliments or complaints about the product, documentation or support,
please write or call us.
MVI56-CAS User Manual
December 26, 2007
PSFT.CAS.MVI56.UM.07.12.26
ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk® and RadioLinx ® are Registered Trademarks
of ProSoft Technology, Inc.
Contents MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Contents
PLEASE READ THIS NOTICE.............................................................................................................................. 2
Your Feedback Please ...................................................................................................................................... 3
GUIDE TO THE MVI56-CAS USER MANUAL...................................................................................................... 7
1 START HERE ............................................................................................................................................... 9
1.1 System Requirements.............................................................................................................................. 9
2.1.1 Power Up ......................................................................................................................................24
2.1.2 Changing Parameters During Operation .......................................................................................24
2.1.3 Module Data Object (CASModuleDef)...........................................................................................24
2.1.4 User Data Objects.........................................................................................................................27
4.1.4 Using the Configuration/Debug Port..............................................................................................33
4.1.5 Main Menu ....................................................................................................................................34
4.1.6 Data Analyzer................................................................................................................................37
4.1.7 Data Analyzer Tips........................................................................................................................39
4.1.8 Database View Menu ....................................................................................................................42
4.2 LED Status Indicators.............................................................................................................................44
4.2.1 Clearing a Fault Condition.............................................................................................................45
5.5 MVI56-CAS Status Data Definition.........................................................................................................63
5.6 MVI56-CAS Configuration Data Definition..............................................................................................65
5.6.1 Port 1 ............................................................................................................................................65
5.6.2 Port 2 ............................................................................................................................................67
6.5.9 Additional Restrictions Relating To Software And Other Intellectual Property ..............................82
6.5.10 Allocation of risks ..........................................................................................................................83
6.5.11 Controlling Law and Severability...................................................................................................83
This Section introduces the customer to the
module. Included are: package contents,
system requirements, hardware installation,
and basic configuration.
This section describes how to verify
communications with the network. Diagnostic
and Troubleshooting procedures.
These sections contain general references
associated with this product, Specifications,
and the Functional Overview.
This section contains Support, Service and
Warranty information.
Index of chapters.
ProSoft Technology, Inc. Page 7 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
Page 8 of 86 ProSoft Technology, Inc.
December 26, 2007
Start Here MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
1 Start Here
In This Chapter
¾ System Requirements.............................................................. 9
¾ Install the Module in the Rack ................................................ 12
¾ Connect your PC to the Processor......................................... 13
¾ Download the Sample Program to the Processor ..................14
¾ Connect your PC to the Module ............................................. 17
Installing the MVI56-CAS module requires a reasonable working knowledge of
the Rockwell Automation hardware, the MVI56-CAS Module and the application
in which they will be used.
Caution: It is important that those responsible for implementation can complete
the application without exposing personnel, or equipment, to unsafe or inappropriate
working conditions. Safety, quality and experience are key factors in a successful
installation.
1.1 System Requirements
The MVI56-CAS module requires the following minimum hardware and software
components:
Rockwell Automation ControlLogix™ processor, with compatible power
supply and one free slot in the rack, for the MVI56-CAS module. The module
requires 800mA of available power.
Rockwell Automation RSLogix 5000 programming software version 2.51 or
higher.
Rockwell Automation RSLinx communication software
Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
Supported operating systems:
o Microsoft Windows XP Professional with Service Pack 1 or 2
o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
o Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
ProSoft Technology, Inc. Page 9 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 × 768 recommended)
CD-ROM drive
HyperTerminal or other terminal emulator program.
Note: You can install the module in a local or remote rack. For remote rack installation,
the module requires EtherNet/IP or ControlNet communication with the processor.
1.2 Package Contents
The following components are included with your MVI56-CAS module, and are all
required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following
items are present.
Qty. Part Name Part Number Part Description
1
1 Cable
3 Cable
2 Adapter 1454-9F
1
MVI56-CAS
Module
ProSoft
Solutions
CD
MVI56-CAS Teledyne CA Slave Module
RS232 Null
Modem
Cable #14, RJ45 to
DB9 Male Adapter
For RS232 Connection to the CFG Port
For DB9 Connection to Module's Port
Two Adapters, DB9 Female to Screw Terminal.
For RS422 or RS485 Connections to Port 1 and 2
of the Module
Contains sample programs, utilities and
documentation for the MVI56-CAS module.
If any of these components are missing, please contact ProSoft Technology
Support for replacement parts.
Page 10 of 86 ProSoft Technology, Inc.
December 26, 2007
Start Here MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
1.3 Setting Jumpers
If you use an interface other than RS-232 (default), you must change the jumper
configuration to match the interface. There are three jumpers located at the
bottom of the module.
The following illustration shows the MVI56-CAS jumper configuration:
1 Set the PRT 2 (for application port 1) and PRT 3 (for application port 2)
jumpers for RS232, RS422 or RS485 to match the wiring needed for your
application. The default jumper setting for both application ports is RS-232.
2 The Setup Jumper acts as "write protection" for the module's flash memory.
In "write protected" mode, the Setup pins are not connected, and the
module's firmware cannot be overwritten. Do not jumper the Setup pins
together unless you are directed to do so by ProSoft Technical Support.
ProSoft Technology, Inc. Page 11 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
1.4 Install the Module in the Rack
If you have not already installed and configured your ControlLogix processor and
power supply, please do so before installing the MVI56-CAS module. Refer to
your Rockwell Automation product documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other
electronic devices. Failure to follow safety procedures could result in damage to
hardware or data, or even serious injury or death to personnel. Refer to the
documentation for each device you plan to connect to verify that suitable safety
procedures are in place before installing or servicing the device.
After you have checked the placement of the jumpers, insert MVI56-CAS into the
ControlLogix chassis. Use the same technique recommended by Rockwell
Automation to remove and install ControlLogix modules.
Warning: When you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Verify that power is removed or the area is non-hazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical resistance that
can affect module operation.
1 Turn power OFF.
2 Align the module with the top and bottom guides, and slide it into the rack
until the module is firmly against the backplane connector.
Page 12 of 86 ProSoft Technology, Inc.
December 26, 2007
Start Here MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
3 With a firm but steady push, snap the module into place.
4 Check that the holding clips on the top and bottom of the module are securely
in the locking holes of the rack.
5 Make a note of the slot location. You will need to identify the slot in which the
module is installed in order for the sample program to work correctly. Slot
numbers are identified on the green circuit board (backplane) of the
ControlLogix rack.
6 Turn power ON.
Note: If you insert the module improperly, the system may stop working, or may
behave unpredictably.
Note: If you are installing MVI56-CAS with other modules connected to the PCI bus,
the peripheral modules will not have holding clips. Make sure all of the modules are
aligned with their respective slots before you snap them into place.
1.5 Connect your PC to the Processor
7 Connect the right-angle connector end of the cable to your controller at the
communications port.
ProSoft Technology, Inc. Page 13 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
8 Connect the straight connector end of the cable to the serial port on your
computer.
1.6 Download the Sample Program to the Processor
¾ To download the sample program from RSLogix 5000 to the
ControlLogix processor:
Note: The key switch on the front of the ControlLogix module must be in the REM
position.
1 If you are not already online to the processor, open the Communications
menu, and then choose Download. RSLogix will establish communication
with the processor.
2 When communication is established, RSLogix will open a confirmation dialog
box. Click the Download button to transfer the sample program to the
processor.
3 RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
Page 14 of 86 ProSoft Technology, Inc.
December 26, 2007
Start Here MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
4 When the download is complete, RSLogix will open another confirmation
dialog box. Click OK to switch the processor from Program mode to Run
mode.
Note: If you receive an error message during these steps, refer to your RSLogix
documentation to interpret and correct the error.
1.6.1 Configuring RSLinx
¾ If RSLogix is unable to establish communication with the processor,
follow these steps:
1 Open RSLinx.
2 Open the Communications menu, and choose Configure Drivers.
This action opens the Configure Drivers dialog box.
ProSoft Technology, Inc. Page 15 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
Note: If the list of configured drivers is blank, you must first choose and configure a
driver from the Available Driver Types list. The recommended driver type to choose for
serial communication with the processor is "RS-232 DF1 Devices".
3 Click to select the driver, and then click Configure. This action opens the
4 Click the Auto-Configure button. RSLinx will attempt to configure your serial
port to work with the selected driver.
5 When you see the message "Auto Configuration Successful", click the OK
button to dismiss the dialog box.
Note: If the auto-configuration procedure fails, verify that the cables are connected
correctly between the processor and the serial port on your computer, and then try
again. If you are still unable to auto-configure the port, refer to your RSLinx
documentation for further troubleshooting steps.
Page 16 of 86 ProSoft Technology, Inc.
December 26, 2007
Start Here MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
1.7 Connect your PC to the Module
With the module securely mounted, connect your PC to the
Configuration/Debug port using an RJ45-DB-9 Serial Adapter Cable and a Null
Modem Cable.
1 Attach both cables as shown.
2 Insert the RJ45 cable connector into the Configuration/Debug port of the
module.
3 Attach the other end to the serial port on your PC or laptop.
ProSoft Technology, Inc. Page 17 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Start Here
Teledyne CA Slave Module
Page 18 of 86 ProSoft Technology, Inc.
December 26, 2007
Installing and Configuring the Module MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
This chapter describes how to install and configure the module to work with your
application. The configuration process consists of the following steps.
1 Use RSLogix 5000 to identify the module to the processor and add the
module to a project.
Note: The RSLogix 5000 software must be in "offline" mode to add the module to a
project.
2 Modify the example ladder logic to meet the needs of your application, and
copy the ladder logic to the processor. Example ladder logic files are provided
on the CD-ROM.
Note: If you are installing this module in an existing application, you can copy the
necessary elements from the example ladder logic into your application.
The rest of this chapter describes these steps in more detail.
The first step in installing and configuring the module is to define the module to
the system. Right-click the mouse button on the I/O Configuration option in the
Controller Organization window to display a pop-up menu. Select the New
Module… option from the I/O Configuration menu:
ProSoft Technology, Inc. Page 19 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Installing and Configuring the Module
Teledyne CA Slave Module
This action opens the following dialog box:
Select the 1756-Module (Generic 1756 Module) from the list and click OK. The
following dialog box is displayed:
Page 20 of 86 ProSoft Technology, Inc.
December 26, 2007
Installing and Configuring the Module MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
Fill in the dialog boxes as shown adjusting the Name, Description and Slot
options for your application. You must select the Comm Format as Data - INT in
the dialog box. Failure to set the Assembly Instance and Size values correctly
will result in a module that will not communicate over the backplane of the
ControlLogix rack. Click Next to display the next dialog box.
Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle scheduled
events. This value should not be set to less than 1 millisecond. Values between 1
and 10 milliseconds should work with most applications.
After completing the module setup, the Controller Organization window will
display the module's presence. The data required for the module will be defined
to the application, and objects will be allocated in the Controller Tags data area.
An example of the Controller Organization window is shown below:
ProSoft Technology, Inc. Page 21 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Installing and Configuring the Module
Teledyne CA Slave Module
The next step in the module's setup is to define the User Defined Data Types to
be used with the module. Copy these data types from the example ladder logic if
you are not using the example. They will be defined if you are starting from the
example ladder logic. The Controller Organization window should display the
User Defined Data Types shown below:
The next step in module setup is to define the data to be used to interface with
the module and the ladder logic. Open the Controller Tags Edit Tags dialog box
and enter the values shown in the following example. The MVI56-CAS module is
defined in the example as CAS1. You can set the tag name to any valid tag
name you desire. If you are using the example ladder logic, this step has already
been performed.
At this point, take the time to fill in the configuration values in the CAS1 data
table and adjust array sizes. Refer to the Module Data Object section of this
document for information on configuring the module.
Page 22 of 86 ProSoft Technology, Inc.
December 26, 2007
Installing and Configuring the Module MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
The last step in the module setup is to add the ladder logic. If you are using the
example ladder logic, adjust the ladder to fit your application. If you are not using
the ladder example, copy the ladder logic shown in the Controller Organization
window below to your application.
The module is now set up and ready to be used with your application. Insert the
module in the rack and attach the TCA serial communication cables. Download
the new application to the controller and place the processor in run mode. If all
the configuration parameters are set correctly and the module is attached to a
TCA network, the module's Application LED (APP LED) should remain off and
the backplane activity LED (BP ACT) should blink very rapidly. Refer to the
Diagnostics andTroubleshooting section of this manual if you encounter
errors. Attach a computer or terminal to Debug/Configuration port on the module
and look at the status of the module using the Configuration/Debug Menu in the
module.
2.1 Module Configuration
In order for the MVI56-CAS module to function, a minimum amount of
configuration data must be transferred to the module. The following table
provides an overview of the different types of configuration data that the module
will require, depending on the operating modes to be supported.
Module
Register
Address
5000 to 5009 Data Transfer General Module
5010 to 5039
and 5040 to
5069
Refer to the Installing and Configuring the Module section for a description of the
configuration of the module. The MVI56-CAS module must be configured at least
once when the card is first powered, and any time thereafter when the
parameters must be changed.
ProSoft Technology, Inc. Page 23 of 86
December 26, 2007
Functional Modes
Affected
Master and Slave Port Configuration These sections define the characteristics of each of
Name Description
This section of the configuration data contains the
Configuration
module configuration data that defines the data
transfer between the module and the ControlLogix
processor.
the TCA serial communication ports on the module.
These parameters must be set correctly for proper
module operation.
MVI56-CAS ♦ ControlLogix Platform Installing and Configuring the Module
Teledyne CA Slave Module
2.1.1 Power Up
On power up, the module enters into a logical loop waiting to receive
configuration data from the processor. Upon receipt, the module will begin
execution of the command list if it is present.
2.1.2 Changing Parameters During Operation
A copy of the module's configuration data is mapped in the module's database as
displayed in the table above. These values are initialized when the module first
receives its configuration from the ControlLogix processor. Any node on the
network can change this data. The module will not use this data until it is
commanded. Ladder logic can be written to issue a Write Configuration
command block (9997) to the module. A remote device can set a value of 9997
at address 6800 in the module to download the configuration to the processor.
Alternatively, the configuration/debug port on the module can be used to issue
the command directly to the module. All three of these methods will force the
module to download the configuration to the ControlLogix processor. Ladder logic
must exist in the processor to accept the blocks sent by the module. If everything
is configured correctly, the module can receive its configuration from a remote
device.
2.1.3 Module Data Object (CASModuleDef)
All data related to the MVI56-CAS is stored in a user defined data type. An
instance of the data type is required before the module can be used. This is done
by declaring a variable of the data type in the Controller Tags Edit Tags dialog
box. The structure of the object is displayed in the following figure.
Page 24 of 86 ProSoft Technology, Inc.
December 26, 2007
Installing and Configuring the Module MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
This object contains objects that define the configuration, user data, status and
command control data related to the module. Each of these object types is
discussed in the following topics of the document.
Configuration Objects
Configuration of the module is performed by filling in the values in the module
object defined in the Controller Tags Edit Tags dialog. Each parameter required
by the module has a defined location in the object. The tables and discussions
below describe the parameters set in the dialog box. You can view these tables
by opening the data type under the User Defined Data Type option in the
Controller Organization window.
Data Transfer Parameters (CASModule)
This object defines the parameters for data movement between the module and
the processor. Values entered determine the ladder logic and data size required
in the application. The ReadData and WriteData arrays must be sized to or larger
than the count values entered. The ladder logic must process the number of
blocks of data to be transferred. The number of blocks is computed as follows:
BlockCnt = INT(RegCnt/200) + if(MOD(RegCnt,200), 1,0)
If the register count is evenly divisible by 200, the number of blocks is easy to
compute and the ladder is much simpler to write. If the number is not evenly
divisible by 200, special handling of the last block of data must developed, as it
must transfer less than 200 words. It is recommended that the count values always be set to values evenly divisible by 200.
ProSoft Technology, Inc. Page 25 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Installing and Configuring the Module
Teledyne CA Slave Module
The BPFail parameter determines if the module should continue communicating
on the TCA network when the backplane transfer operation fails. A value of zero
indicates that the module should continue communicating when the backplane is
not operational. If the value is greater than zero, the backplane will be retried the
entered number of times before a failure will be reported and communication will
cease on the ports. When backplane communication is restored, the module will
start communicating on the network. For example, if you enter a value of 10 for
the parameter, the module will stop all TCA communications if 10 successive
backplane errors are recognized. When a successful transfer is recognized, the
module will resume communications on the network.
TCA Port Parameters (CASPort)
This object defines the parameters for the operation of each of the TCA ports on
the module. Refer to the Reference chapter for the definition of each parameter.
Page 26 of 86 ProSoft Technology, Inc.
December 26, 2007
Installing and Configuring the Module MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
Status Object (CASInStat)
This object views the status of the module. The CASInStat object shown below
is updated each time a read block is received by the processor. Use this data to
monitor the state of the module at a "real-time rate".
Refer to the Reference chapter for a complete listing of the data stored in this
object.
2.1.4 User Data Objects
These objects hold data to be transferred between the processor and the MVI56CAS module. The user data is the read and write data transferred between the
processor and the module as "pages" of data up to 200 words long.
The read data (ReadData) is an array set to match the value entered in the
ReadRegCnt parameter of the CASModule object. For ease of use, this array
should be dimensioned as an even increment of 200 words. This data is paged
up to 200 words at a time from the module to the processor. The ReadData task
is responsible for placing the data received into the proper position in the read
data array. Use this data for status and control in the ladder logic of the
processor.
ProSoft Technology, Inc. Page 27 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Installing and Configuring the Module
Teledyne CA Slave Module
The write data (WriteData) is an array set to match the value entered in the
WriteRegCnt parameter of the CASModule object. For ease of use, this array
should be dimensioned as even increments of 200 words. This data is paged up
to 200 words at a time from the processor to the module. The WriteData task is
responsible for placing the write data into the output image for transfer to the
module. This data is passed from the processor to the module for status and
control information for use in other nodes on the network
2.1.5 TCA Message Data
The module's program relies on the pass-through mode. Write messages sent to
a slave port are passed directly through to the processor. It is the responsibility of
the ladder logic to process the message received using this feature. Three data
objects are required for this mode: a variable to hold the length of the message, a
variable to hold the address, and a buffer to hold the message. This information
is passed from the module to the processor using block identification codes of
9991, 9992, or 9994. Word two of this block contains the length of the message,
word three contains the address and the message starts at word 5.
Page 28 of 86 ProSoft Technology, Inc.
December 26, 2007
Ladder Logic MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
3 Ladder Logic
Ladder logic is required for application of the MVI56-CAS module. Tasks that
must be handled by the ladder logic are module data transfer, special block
handling and status data receipt. Additionally, a power-up handler may be
needed to handle the initialization of the module's data and to clear any
processor fault conditions.
The sample ladder logic, on the ProSoft Solutions CD-ROM, is extensively
commented, to provide information on the purpose and function of each rung. For
most applications, the sample ladder will work without modification.
ProSoft Technology, Inc. Page 29 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Ladder Logic
Teledyne CA Slave Module
Page 30 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
4 Diagnostics and Troubleshooting
In This Chapter
¾ Reading Status Data From the Module.................................. 31
¾ LED Status Indicators ............................................................ 44
The module provides information on diagnostics and troubleshooting in the
following forms:
Status data values are transferred from the module to the processor.
Data contained in the module can be viewed through the
Configuration/Debug port attached to a terminal emulator.
LED status indicators on the front of the module provide information on the
module's status.
4.1 Reading Status Data From the Module
The MVI56-CAS module returns a 35-word Status Data block that can be used to
determine the module's operating status. This data is located in the module's
database at registers 6000 to 6034 and at the location specified in the
configuration. This data is transferred to the ControlLogix processor continuously
with each read block. For a complete listing of the status data object, refer to the
Module Set Up section.
4.1.1 The Configuration/Debug Menu
The Configuration and Debug menu for this module is arranged as a tree
structure, with the Main Menu at the top of the tree, and one or more sub-menus
for each menu command. The first menu you see when you connect to the
module is the Main menu.
Because this is a text-based menu system, you enter commands by typing the
command letter from your computer keyboard in the terminal application (for
example, HyperTerminal). The module does not respond to mouse movements
or clicks. The command executes as soon as you press the command letter —
you do not need to press [Enter]. When you type a command letter, a new
screen will be displayed in your terminal application.
Navigation
All of the sub-menus for this module contain commands to redisplay the menu or
return to the previous menu. You can always return from a sub-menu to the next
higher menu by pressing [M] on your keyboard.
ProSoft Technology, Inc. Page 31 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
The organization of the menu structure is represented in simplified form in the
following illustration:
The remainder of this section shows you the menus available for this module,
and briefly discusses the commands available to you.
Keystrokes
The keyboard commands on these menus are almost always non-case sensitive.
You can enter most commands in lower case or capital letters.
The menus use a few special characters ([?], [-], [+], [@]) that must be entered
exactly as shown. Some of these characters will require you to use the [Shift],
[Ctrl] or [Alt] keys to enter them correctly. For example, on US English
keyboards, enter the [?] command as [Shift][/].
Also, take care to distinguish capital letter [I] from lower case letter [l] (L) and
number [1]; likewise for capital letter [O] and number [0]. Although these
characters look nearly the same on the screen, they perform different actions on
the module.
4.1.2 Required Hardware
You can connect directly from your computer's serial port to the serial port on the
module to view configuration information and perform maintenance.
ProSoft Technology recommends the following minimum hardware to connect
your computer to the module:
80486 based processor (Pentium preferred)
1 megabyte of memory
At least one serial communications port available
A null modem serial cable.
Page 32 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
4.1.3 Required Software
In order to send and receive data over the serial port (COM port) on your
computer to the module, you must use a communication program (terminal
emulator).
A simple communication program called HyperTerminal is pre-installed with
recent versions of Microsoft Windows operating systems. If you are connecting
from a machine running DOS, you must obtain and install a compatible
communication program. The following table lists communication programs that
have been tested by ProSoft Technology.
DOS ProComm, as well as several other terminal emulation programs
Windows 3.1 Terminal
Windows 95/98 HyperTerminal
Windows NT/2000/XP HyperTerminal
4.1.4 Using the Configuration/Debug Port
To connect to the module's Configuration/Debug port:
1 Connect your computer to the module's port using a null modem cable.
2 Start the communication program on your computer and configure the
communication parameters with the following settings:
3 Open the connection. When you are connected, press the [?] key on your
keyboard. If the system is set up properly, you will see a menu with the
module name followed by a list of letters and the commands associated with
them.
If there is no response from the module, follow these steps:
1 Verify that the null modem cable is connected properly between your
computer's serial port and the module. A regular serial cable will not work.
2 Verify that RSLinx is not controlling the COM port. Refer to Disabling the
RSLinx Driver for the Com Port on the PC (page 57).
3 Verify that your communication software is using the correct settings for baud
rate, parity and handshaking.
4 On computers with more than one serial port, verify that your communication
program is connected to the same port that is connected to the module.
If you are still not able to establish a connection, you can contact ProSoft
Technology Technical Support for further assistance.
ProSoft Technology, Inc. Page 33 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
4.1.5 Main Menu
When you first connect to the module from your computer, your terminal screen
will be blank. To activate the main menu, press the [?] key on your computer's
keyboard. If the module is connected properly, the following menu will appear on
your terminal screen:
Caution: Some of the commands available to you from this menu are designed for
advanced debugging and system testing only, and can cause the module to stop
communicating with the processor or with other devices, resulting in potential data loss
or other failures. Only use these commands if you are specifically directed to do so by
ProSoft Technology Technical Support staff. Some of these command keys are not
listed on the menu, but are active nevertheless. Please be careful when pressing keys
so that you do not accidentally execute an unwanted command.
Opening the Data Analyzer Menu
Press [A] to open the Data Analyzer Menu. Use this command to view all bytes
of data transferred on each port. Both the transmitted and received data bytes
are displayed. Refer to Data Analyzer for more information about this menu.
Important: When in analyzer mode, program execution will slow down. Only use this
tool during a troubleshooting session. Before disconnecting from the Config/Debug
port, please press [S] to stop the data analyzer, and then press [M] to return to the
main menu. This action will allow the module to resume its normal high speed
operating mode.
Viewing Block Transfer Statistics
Press [B] from the Main Menu to view the Block Transfer Statistics screen.
Use this command to display the configuration and statistics of the backplane
data transfer operations between the module and the processor. The information
on this screen can help determine if there are communication problems between
the processor and the module.
Page 34 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
Tip: To determine the number of blocks transferred each second, mark the numbers
displayed at a specific time. Then some seconds later activate the command again.
Subtract the previous numbers from the current numbers and divide by the quantity of
seconds passed between the two readings.
Viewing Module Configuration
Press [C] to view the Module Configuration screen.
Use this command to display the current configuration and statistics for the
module.
Opening the Database Menu
Press [D] to open the Database View menu. Use this menu command to view the
current contents of the module's database.
Viewing Version Information
Press [V] to view Version information for the module.
Use this command to view the current version of the software for the module, as
well as other important values. You may be asked to provide this information
when calling for technical support on the product.
Values at the bottom of the display are important in determining module
operation. The Program Scan Counter value is incremented each time a
module's program cycle is complete.
Tip: Repeat this command at one-second intervals to determine the frequency of
program execution.
Warm Booting the Module
Caution: Some of the commands available to you from this menu are designed for
advanced debugging and system testing only, and can cause the module to stop
communicating with the processor or with other devices, resulting in potential data loss
or other failures. Only use these commands if you are specifically directed to do so by
ProSoft Technology Technical Support staff. Some of these command keys are not
listed on the menu, but are active nevertheless. Please be careful when pressing keys
so that you do not accidentally execute an unwanted command.
Press [W] from the Main Menu to warm boot (restart) the module. This command
will cause the program to exit and reload, refreshing configuration parameters
that must be set on program initialization. Only use this command if you must
force the module to re-boot.
ProSoft Technology, Inc. Page 35 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
Transferring Module Configuration to the Processor
Press [Y] to transfer the module's configuration data to the processor. Ladder
logic is required in the processor to receive and implement the updated
configuration. You will be prompted to confirm the transfer.
If the operation is not successful, an error code will be returned.
Code Description
0 Transfer successful
-1 Error transferring module configuration data (block -9000)
-2 Error transferring device definition data (blocks -9100 to -9103)
-3 Error transferring master command list data (blocks -6000 to -6007)
After successful data transfer, the module will perform a warm-boot operation to
read in the new data.
Viewing Port Communication Status
Press [1] or [2] from the Main Menu to view the port communication status for
Ports 1 and 2.
Use this command to view communication status and statistics for the selected
port. This information can be informative when troubleshooting communication
problems.
Viewing Port Configuration
Press [6] or [7] from the Main Menu to view configuration information for ports 1
and 2.
Use this command to display detailed configuration information for the selected
port.
Exiting the Program
Caution: Some of the commands available to you from this menu are designed for
advanced debugging and system testing only, and can cause the module to stop
communicating with the processor or with other devices, resulting in potential data loss
or other failures. Only use these commands if you are specifically directed to do so by
ProSoft Technology Technical Support staff. Some of these command keys are not
listed on the menu, but are active nevertheless. Please be careful when pressing keys
so that you do not accidentally execute an unwanted command.
Press [Esc] to restart the module and force all drivers to be loaded. The module
will use the configuration stored in the module's Flash ROM to configure the
module.
Page 36 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
4.1.6 Data Analyzer
The data analyzer mode allows you to view all bytes of data transferred on each
port. Both the transmitted and received data bytes are displayed. Use of this
feature is limited without a thorough understanding of the protocol.
Note: The Port selection commands on the Data Analyzer menu differs very slightly in
different modules, but the functionality is basically the same. Use the illustration above
as a general guide only. Refer to the actual data analyzer menu on your module for the
specific port commands to use.
Important: When in analyzer mode, program execution will slow down. Only use this
tool during a troubleshooting session. Before disconnecting from the Config/Debug
port, please press [S] to stop the data analyzer, and then press [M] to return to the
main menu. This action will allow the module to resume its normal high speed
operating mode.
Analyzing Data for the first application port
Press [1] to display I/O data for the first application port in the Data Analyzer.
The following illustration shows an example of the Data Analyzer output.
Analyzing Data for the second application port
Press [2] to display I/O data for the second application port in the Data Analyzer.
Displaying Timing Marks in the Data Analyzer
You can display timing marks for a variety of intervals in the data analyzer
screen. These timing marks can help you determine communication-timing
characteristics.
Press [0] to turn off timing marks in the Data Analyzer screen.
ProSoft Technology, Inc. Page 37 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
Viewing Data in Hexadecimal Format
Press [H] to display the data on the current page in hexadecimal format.
Viewing Data in ASCII (Text) Format
Press [A] to display the data on the current page in ASCII format. This is useful
for regions of the database that contain ASCII data.
Starting the Data Analyzer
Press [B] to start the data analyzer. After the key is pressed, all data transmitted
and received on the currently selected port will be displayed. An example display
is shown below:
The Data Analyzer displays the following special characters:
Character Definition
[ ] Data enclosed in these characters represent data received on the port.
< > Data enclosed in these characters represent data transmitted on the port.
<R+> These characters are inserted when the RTS line is driven high on the port.
<R-> These characters are inserted when the RTS line is dropped low on the port.
<CS> These characters are displayed when the CTS line is recognized high.
_TT_
These characters are displayed when the timing mark interval has been reached.
This parameter is user defined.
Stopping the Data Analyzer
Press [S] to stop the data analyzer. Use this option to freeze the display so the
data can be analyzed. To restart the analyzer, press [B].
Page 38 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
Important: When in analyzer mode, program execution will slow down. Only use this
tool during a troubleshooting session. Before disconnecting from the Config/Debug
port, please press [S] to stop the data analyzer, and then press [M] to return to the
main menu. This action will allow the module to resume its normal high speed
operating mode.
Returning to the Main Menu
Press [M] to return to the Main Menu.
4.1.7 Data Analyzer Tips
From the main menu, press [A] for the "Data Analyzer". You should see the
following text appear on the screen:
After the "Data Analyzer" mode has been selected, press [?] to view the Data
Analyzer menu. You will see the following menu:
From this menu, you can select the "Port", the "format", and the "ticks" that you
can display the data in.
For most applications, HEX is the best format to view the data, and this does
include ASCII based messages (because some characters will not display on
HyperTerminal and by capturing the data in HEX, we can figure out what the
corresponding ASCII characters are supposed to be).
The Tick value is a timing mark. The module will print a _TT for every xx
milliseconds of no data on the line. Usually 10milliseconds is the best value to
start with.
ProSoft Technology, Inc. Page 39 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
After you have selected the Port, Format, and Tick, we are now ready to start a
capture of this data. The easiest way to do so is to go up to the top of you
HyperTerminal window, and do a Transfer / Capture Text as shown below:
After selecting the above option, the following window will appear:
Next name the file, and select a directory to store the file in. In this example, we
are creating a file ProSoft.txt and storing this file on our root C: drive. After you
have done this, press the
button.
Now you have everything that shows up on the HyperTerminal screen being
logged to a file called ProSoft.txt. This is the file that you will then be able to
email to ProSoft Technical Support to assist with issues on the communications
network.
To begin the display of the communications data, you will then want to press 'B'
to tell the module to start printing the communications traffic out on the debug
port of the module. After you have pressed 'B', you should see something like the
following:
Page 40 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
The <R+> means that the module is transitioning the communications line to a
transmit state.
All characters shown in <> brackets are characters being sent out by the module.
The <R-> shows when the module is done transmitting data, and is now ready to
receive information back.
And finally, all characters shown in the [ ] brackets is information being received
from another device by the module.
After taking a minute or two of traffic capture, you will now want to stop the "Data
Analyzer". To do so, press the 'S' key, and you will then see the scrolling of the
data stop.
When you have captured the data you want to save, open the Transfer menu and
choose Capture Text. On the secondary menu, choose Stop.
You have now captured, and saved the file to your PC. This file can now be used
in analyzing the communications traffic on the line, and assist in determining
communication errors.
ProSoft Technology, Inc. Page 41 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
4.1.8 Database View Menu
Press [D] from the Main Menu to open the Database View menu. Use this menu
command to view the current contents of the module's database. Press [?] to
view a list of commands available on this menu.
M = Main Menu
D = Database Menu
? = Display MenuRedisplays (refreshes) this menu
0 – 3 = Pages 0 to 3000
S = Show AgainRedisplays last select ed page of data
–= Back 5 Pages
P = Previous Page
+ = Skip 5 Pages
N = Next Page
D = Decimal Display
H = Hexadecimal Display
F = Float Display
A = ASCII Display
M = Main MenuGoes up one level to main menu
Selects page 0, 1000, 2000 or 3000
Goes back five pages of data
Goes back one page of data
Goes forward five pages of data
Goes forward one page of data
Displays data in decimal format
Displays data in hex format
Displays data in floating point format
Displays data in text format
Viewing Register Pages
To view sets of register pages, use the keys described below:
Command Description
[0]
[1]
[2]
Display registers 0 to 99
Display registers 1000 to 1099
Display registers 2000 to 2099
And so on. The total number of register pages available to view depends on your
module's configuration.
Displaying the Current Page of Registers Again
This screen displays the current page of 100 registers in the database.
Page 42 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
Moving Back Through 5 Pages of Registers
Press [-] from the Database View menu to skip back to the previous 500
registers of data.
Viewing the Previous 100 Registers of Data
Press [P] from the Database View menu to display the previous 100 registers of
data.
Skipping 500 Registers of Data
Hold down [Shift] and press [=] to skip forward to the next 500 registers of data.
Viewing the Next 100 Registers of Data
Press [N] from the Database View menu to select and display the next 100
registers of data.
Viewing Data in Decimal Format
Press [D] to display the data on the current page in decimal format.
Viewing Data in Hexadecimal Format
Press [H] to display the data on the current page in hexadecimal format.
Viewing Data in Floating Point Format
Press [F] from the Database View menu. Use this command to display the data
on the current page in floating point format. The program assumes that the
values are aligned on even register boundaries. If floating-point values are not
aligned as such, they are not displayed properly.
Viewing Data in ASCII (Text) Format
Press [A] to display the data on the current page in ASCII format. This is useful
for regions of the database that contain ASCII data.
Returning to the Main Menu
Press [M] to return to the Main Menu.
ProSoft Technology, Inc. Page 43 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
4.2 LED Status Indicators
The LEDs indicate the module's operating status as follows:
ProSoft
Module
CFG Green
P1 Green
P2 Green
BP ACT Amber
OK Red/
During module configuration, the OK LED will be red and the APP and BP ACT
LEDs will be on. If the LEDs are latched in this mode for a long period of time,
look at the configuration error words in the configuration request block. The
structure of the block is as shown below.
Offset Description Length
0 Reserved 1
1 9000 1
2 Module Configuration Errors 1
3 Port 1 Configuration Errors 1
4 Port 2 Configuration Errors 1
5 to 248 Spare 244
249 -2 or -3 1
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call Prosoft Technology support to
arrange for repairs.
Color Status Indication
On
Off
On
Off No data is being transferred on the port.
On
Off No data is being transferred on the port.
On The MVI56-CAS is working normally. APP Amber
Off
On
Off
Off
Green
Green The module is operating normally.
Red
Off The battery voltage is OK and functioning. BAT Red
On
Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.
No data is being transferred on the Configuration/Debug
port.
Data is being transferred between the module and the TCA
network on its TCA Port 1.
Data is being transferred between the module and the TCA
network on its TCA Port 2.
The MVI56-CAS module program has recognized a
communication error on one of its TCA ports.
The LED is on when the module is performing a write
operation on the backplane.
The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the
LED should blink rapidly on and off.
The card is not receiving any power and is not securely
plugged into the rack.
The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and reinsert the card to restart the module's program.
The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
Page 44 of 86 ProSoft Technology, Inc.
December 26, 2007
Diagnostics and Troubleshooting MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
4.2.1 Clearing a Fault Condition
Typically, if the OK LED on the front of the module turns red for more than ten
seconds, a hardware problem has been detected in the module, or the program
has exited.
To clear the condition, follow these steps:
1 Turn off power to the rack
2 Remove the card from the rack
3 Verify that all jumpers are set correctly
4 If the module requires a Compact Flash card, verify that the card is installed
correctly
5 Re-insert the card in the rack and turn the power back on
6 Verify the configuration data being transferred to the module from the
ControlLogix processor.
If the module's OK LED does not turn green, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Support.
4.2.2 Troubleshooting
Use the following troubleshooting steps if you encounter problems when the
module is powered up. If these steps do not resolve your problem, please contact
ProSoft Technology Technical Support.
Processor Errors
Problem Description Steps to take
Processor Fault
Processor I/O LED
flashes
Verify that the module is plugged into the slot that has been configured
for the module.
Verify that the slot in the rack configuration has been set up correctly in
the ladder logic.
This indicates a problem with backplane communications. Verify that all
modules in the rack are configured in the ladder logic.
Module Errors
Problem Description Steps to take
BP ACT LED remains
off or blinks slowly
OK LED remains red
This indicates that backplane transfer operations are failing. Connect to
the module's Configuration/Debug port to check this.
To establish backplane communications, verify the following items:
The processor is in Run mode.
The backplane driver is loaded in the module.
The module is configured for read and write block data transfer.
The ladder logic handles all read and write block situations.
The module is configured in the processor.
The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program
has halted, turn off power to the rack, remove the card from the rack
and re-insert the card in the rack, and then restore power to the rack.
ProSoft Technology, Inc. Page 45 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Diagnostics and Troubleshooting
Teledyne CA Slave Module
Page 46 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
The MVI56 Teledyne CA Slave Module allows ControlLogix I/O compatible
processors to interface easily with TCA protocol compatible devices.
5.1.1 Features and Benefits
The MVI56-CAS module acts as an input/output module between the TCA
network and the ControlLogix backplane. The data transfer from the ControlLogix
processor is asynchronous from the actions on the TCA network. A 5000-word
register space in the module exchanges data between the processor and the
TCA network.
5.1.2 General Specifications
Single Slot - 1756 backplane compatible
Local or remote rack
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module
Ladder Logic is used for data transfer between module and processor.
Configuration data obtained through user-defined ladder. Sample ladder file
included
ProSoft Technology, Inc. Page 47 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
5.1.3 Hardware Specifications
Specification Description
Backplane Current Load 800 mA @ 5 V DC; 3mA @ 24V DC
Operating Temperature 0 to 60°C (32 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Shock 30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity 5% to 95% (non-condensing)
LED Indicators Module Status
Backplane Transfer Status
Application Status
Serial Activity
Debug/Configuration port (CFG)
CFG Port (CFG) RJ45 (DB-9M with supplied cable)
RS-232 only
Application ports (PRT1 & PRT2)
Full hardware handshaking control, providing radio, modem and multi-drop support
Software configurable
communication parameters
App Ports (P1,P2) (Serial modules) RJ45 (DB-9M with supplied cable)
Shipped with Unit RJ45 to DB-9M cables for each port
Baud rate: 110 to 115,200 baud, depending on protocol
RS-232 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
RS-232 handshaking configurable
500V Optical isolation from backplane
6-foot RS-232 configuration cable
5.1.4 Functional Specifications
Function codes
o 1: Read output data
o 2: Read analog data
o 3: Read meter data
o 10: Read frozen analog values
o 11: Read frozen meter data
o 16: Read all data
o 20: Read tank data from RTU
o 30: Control momentary select
o 31: Control momentary operate
o 32: Control continuous select
o 33: Control continuous operate
Page 48 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
o 34: Setpoint select
o 35: Setpoint operate
o 43: Freeze meters
o 44: Freeze analogs
o 45: Freeze meters/analogs
o 46/6: Special freeze
o 50: Exception data request
Supports broadcast commands from master
Register addressing
o Status: Up to 250 words
o Analog: Up to 250 words
o Meter: Up to 125 values (2 words per value)
o Tank: Up to 250 words
Supports write commands from host
Operates in both direct or indirect modes
Setpoint select and operate
o Control point continuous and momentary
5.2 Functional Overview
This section provides an overview of how the MVI56-CAS module transfers data
using the CAS protocol. You should understand the important concepts in this
chapter before you begin installing and configuring the module.
5.2.1 General Concepts
The following topics describe several concepts that are important for
understanding the operation of the MVI56-CAS module.
On power up the module begins performing the following logical functions:
1 Initialize hardware components
2 Initialize ControlLogix backplane driver
3 Test and Clear all RAM
4 Initialize the serial communication ports
5 Wait for Module Configuration from ControlLogix processor
6 Initialize Module Register space
7 Enable Slave Driver on selected ports
After the module has received the Module Configuration Block from the
processor, the module will begin communicating with other nodes on the
network, depending on the configuration.
ProSoft Technology, Inc. Page 49 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Main Logic Loop
Upon completing the power up configuration process, the module enters an
infinite loop that performs the functions shown in the following diagram.
From Power Up Logic
Call I/O Handler
Call CFG/DEBUG Port
Driver
Call Network
Slave Drivers
Transfers data between the module and processor
Rx and Tx buffer routines are interrupt driven. Call to
serial port routines check to see if there is any data
in the buffer, and depending on the value, will either
service the buffer or wait for more characters.
Call I/O Handler
(user, status, etc.)
Call Serial P o rt D riv e r
Call Network Slave Drivers
Respond to messages received.
ControlLogix Processor Not in Run
Whenever the module detects that the processor has gone out of the Run mode
(that is, Fault or PGM), the TCA ports can be shut down as prescribed in the user
configuration. When the processor is returned to a running state, the module will
resume communications on the network.
Backplane Data Transfer
The MVI56-CAS module communicates directly over the ControlLogix backplane.
Data is paged between the module and the ControlLogix processor across the
backplane using the module's input and output images. The update frequency of
the images is determined by the scheduled scan rate defined by the user for the
module and the communication load on the module. Typical updates are in the
range of 2 to 10 milliseconds.
This bi-directional transference of data is accomplished by the module filling in
data in the module's input image to send to the processor. Data in the input
image is placed in the Controller Tags in the processor by the ladder logic. The
input image for the module is set to 250 words. This large data area permits fast
throughput of data between the module and the processor.
The processor inserts data to the module's output image to transfer to the
module. The module's program extracts the data and places it in the module's
internal database. The output image for the module is set to 248 words. This
large data area permits fast throughput of data from the processor to the module.
Page 50 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
The following illustration shows the data transfer method used to move data
between the ControlLogix processor, the MVI56-CAS module and the TCA
network.
As shown in the diagram above, all data transferred between the module and the
processor over the backplane is through the input and output images. Ladder
logic must be written in the ControlLogix processor to interface the input and
output image data with data defined in the Controller Tags. All data used by the
module is stored in its internal database. This database is defined as a data table
with addresses from 0 to 6999. The following illustration shows the layout of the
database:
Module’s Internal Database Structure
5000 registers for user data
2000 words of configuration
and status data
Register
Data
Status
and
Config
0
4999
5000
6999
ProSoft Technology, Inc. Page 51 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Data contained in this database is paged through the input and output images by
coordination of the ControlLogix ladder logic and the MVI56-CAS module's
program. Up to 248 words of data can be transferred from the module to the
processor at a time. Up to 247 words of data can be transferred from the
processor to the module. Each image has a defined structure depending on the
data content and the function of the data transfer as defined below.
5.2.2 Normal Data Transfer
Normal data transfer includes the paging of the user data found in the module's
internal database in registers 0 to 4999 and the status data. These data are
transferred through read (input image) and write (output image) blocks. Refer to
the Module Set Up section for a description of the data objects used with the
blocks and the ladder logic required. The structure and function of each block is
discussed below.
Read Block
These blocks of data transfer information from the module to the ControlLogix
processor. The structure of the input image used to transfer this data is shown in
the following table:
Offset Description Length
0 Reserved 1
1 Write Block ID 1
2 to 201 Read Data 200
202 Program Scan Counter 1
203 to 204 Product Code 2
205 to 206 Product Version 2
207 to 208 Operating System 2
209 to 210 Run Number 2
211 to 217 Port 1 Error Status 7
218 to 224 Port 2 Error Status 7
225 to 230 Data Transfer Status 6
231 Port 1 Current Error/Index 1
232 Port 1 Last Error/Index 1
233 Port 2 Current Error/Index 1
234 Port 2 Last Error/Index 1
235 Port 1 Status Scan 1
236 Port 2 Status Scan 1
237 to 248 Spare 12
249 Read Block ID 1
Page 52 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
The Read Block ID is an index value used to determine the location of where the
data will be placed in the ControlLogix processor controller tag array of module
read data. Each transfer can move up to 200 words (block offsets 2 to 201) of
data. In addition to moving user data, the block also contains status data for the
module. This last set of data is transferred with each new block of data and is
used for high-speed data movement.
The Write Block ID associated with the block requests data from the ControlLogix
processor. Under normal, program operation, the module sequentially sends
read blocks and requests write blocks. For example, if three read and two write
blocks are used with the application, the sequence will be as follows:
R1W1R2W2R3W1R1W2R2W1R3W2R1W1
This sequence will continue until interrupted by other write block numbers sent by
the controller or by a command request from a node on the TCA network or
operator control through the module's Configuration/Debug port.
Write Block
These blocks of data transfer information from the ControlLogix processor to the
module. The structure of the output image used to transfer this data is shown in
the following table:
Offset Description Length
0 Write Block ID 1
1 to 200 Write Data 200
201 to 206 Time Data 6
207 to 247 Spare 41
The Write Block ID is an index value used to determine the location in the
module's database where the data will be placed. Each transfer can move up to
200 words (block offsets 1 to 200) of data.
5.2.3 Configuration Data Transfer
When the module performs a restart operation, it will request configuration
information from the ControlLogix processor. This data is transferred to the
module in specially formatted write blocks (output image). The module will poll for
each block by setting the required write block number in a read block (input
image). Refer to the Module Set Up section for a description of the data objects
used with the blocks and the ladder logic required. The format of the blocks for
configuration is given in the following topics.
ProSoft Technology, Inc. Page 53 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Module Configuration Data
This block sends general configuration information from the processor to the
module. The data is transferred in a block with an identification code of 9000.
The structure of the block is displayed in the following table:
Offset Description Length
0 9000 1
1 to 5 Backplane Setup 5
6 to 19 Port 1 Configuration 14
20 to 33 Port 2 Configuration 14
34 to 247 Spare 214
The read block used to request the configuration has the following structure:
Offset Description Length
0 Reserved 1
1 9000 1
2 Module Configuration Errors 1
3 Port 1 Configuration Errors 1
4 Port 2 Configuration Errors 1
5 to 248 Spare 244
249 -2 or -3 1
If there are any errors in the configuration, the bit associated with the error will be
set in one of the three configuration error words. The error must be corrected
before the module starts operating.
5.2.4 Write Configuration
This block is sent from the ControlLogix processor to the module to force the
module to write its current configuration back to the processor. This function is
used when the module's configuration has been altered remotely using database
write operations. The write block contains a value of -9000 in the first word. The
module will respond with blocks containing the module configuration data. Ladder
logic must handle the receipt of these blocks. The blocks transferred from the
module are as follows:
Block -9000, General Configuration Data:
Offset Description Length
0 Reserved 1
1 -9000 1
2 to 6 Backplane Setup 5
7 to 20 Port 1 Configuration 14
21 to 34 Port 2 Configuration 14
35 to 248 Spare 214
249 -9000 1
Page 54 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Warm Boot
This block is sent from the ControlLogix processor to the module (output image)
when the module is required to perform a warm-boot (software reset) operation.
This block is commonly sent to the module any time configuration data
modifications are made in the controller tags data area. This will force the module
to read the new configuration information and to restart. The structure of the
control block is shown below:
Offset Description Length
0 9998 1
1 to 247 Spare 247
Cold Boot
This block is sent from the ControlLogix processor to the module (output image)
when the module is required to perform the cold boot (hardware reset) operation.
This block is sent to the module when a hardware problem is detected by the
ladder logic that requires a hardware reset. The structure of the control block is
shown in the following table:
Offset Description Length
0 9999 1
1 to 247 Spare 247
5.2.5 Pass-Through Control Blocks
The module will pass blocks with identification codes of 9991, 9992 and 9994 to
the processor for each received write command. Ladder logic must handle the
receipt of all TCA write functions to the processor and to respond as expected to
commands issued by the remote TCA device. The structure of the pass-through
control block is shown in the following table:
Offset Description Length
0 0 1
1 9991, 9992, or 9994 1
2 Number of bytes in message 1
3 Write Address 1 1
4 Write Address 2 1
5 to 248 Message Received 244
249 9991, 9992, or 9994 1
The ladder logic will be responsible for parsing and copying the received
message and performing the proper control operation as expected by the master
device. The processor must then respond to the pass-through control block with
a write block with the following format.
Offset Description Length
0 9991, 9992, or 9994 1
1 to 247 Spare 247
ProSoft Technology, Inc. Page 55 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
This will inform the module that the command has been processed and can be
cleared from the pass-through queue.
5.2.6 Data Flow Between MVI56-CAS Module and ControlLogix
Processor
The following topics describe the flow of data between the two pieces of
hardware (ControlLogix processor and MVI56-CAS module) and other nodes on
the TCA network under the module's different operating modes. Each port on the
module is configured to emulate a TCA slave device. The operation of each port
is dependent on this configuration. The sections below discuss the operation of
each mode.
Slave Driver
The Slave Driver Mode allows the MVI56-CAS module to respond to data read
and write commands issued by a master on the TCA network. The following flow
chart and associated table describe the flow of data into and out of the module.
Processor Memory
Controller Tags
ControlLogix
from Module
Configuration
Register
Data
storage
Status
Data
Database
Addresses
0
Register
Data
4999
Status
Configuration
Read Functions
Status
Configuration
Write Functions
CAS ModuleBackplane Interface
Slave
Mode
Driver
Step Description
1
2
3
4
5
The TCA slave port driver receives the configuration information from the ControlLogix
processor. This information configures the serial port and define the slave node
characteristics. Additionally, the configuration information contains data that can be
used to offset data in the database to addresses requested in messages received from
master units.
A Host device issues a read or write command to the module's node address. The port
driver qualifies the message before accepting it into the module.
After the module accepts the command, the data is immediately transferred to the
processor or from the internal database in the module. If the command is a read
command, the data is read out of the database and a response message is built. If the
command is a write command, the data is written directly to the processor and a
response message is built.
After the data processing has been completed in Step 2, the response is issued to the
originating master node.
Counters are available in the Status Block that permit the ladder logic program to
determine the level of activity of the Slave Driver.
Page 56 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
5.3 Cable Connections
The application ports on the MVI56-CAS module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.
Note: When using RS-232 with radio modem applications, some radios or modems
require hardware handshaking (control and monitoring of modem signal lines). Enable
this in the configuration of the module by setting the UseCTS parameter to 1.
5.3.1 RS-232 Configuration/Debug Port
This port is physically an RJ45 connection. An RJ45 to DB-9 adapter cable is
included with the module. This port permits a PC based terminal emulation
program to view configuration and status data in the module and to control the
module. The cable for communications on this port is shown in the following
diagram:
Disabling the RSLinx Driver for the Com Port on the PC
The communication port driver in RSLinx can occasionally prevent other
applications from using the PC's COM port. If you are not able to connect to the
module's configuration/debug port using ProSoft Configuration Builder (PCB),
HyperTerminal or another terminal emulator, follow these steps to disable the
RSLinx Driver.
1 Open RSLinx and go to Communications>RSWho
ProSoft Technology, Inc. Page 57 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
2 Make sure that you are not actively browsing using the driver that you wish to
stop. The following shows an actively browsed network:
3 Notice how the DF1 driver is opened, and the driver is looking for a processor
on node 1. If the network is being browsed, then you will not be able to stop
this driver. To stop the driver your RSWho screen should look like this:
Branches are displayed or hidden by clicking on the
4 When you have verified that the driver is not being browsed, go to
Communications>Configure Drivers
You may see something like this:
or the icons.
Page 58 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
If you see the status as running, you will not be able to use this com port for
anything other than communication to the processor. To stop the driver press
the "Stop" on the side of the window:
5 After you have stopped the driver you will see the following:
6 Upon seeing this, you may now use that com port to connect to the debug
port of the module.
Note: You may need to shut down and restart your PC before it will allow you to stop
the driver (usually only on Windows NT machines). If you have followed all of the
above steps, and it will not stop the driver, then make sure you do not have RSLogix
open. If RSLogix is not open, and you still cannot stop the driver, then reboot your PC.
5.3.2 RS-232
When the RS-232 interface is selected, the use of hardware handshaking
(control and monitoring of modem signal lines) is user definable. If no hardware
handshaking will be used, the cable to connect to the port is as shown below:
ProSoft Technology, Inc. Page 59 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
RS-232: Modem Connection
This type of connection is required between the module and a modem or other
communication device.
The "Use CTS Line" parameter for the port configuration should be set to 'Y' for
most modem applications.
This type of connection is used when the device connected to the module
requires hardware handshaking (control and monitoring of modem signal lines).
Page 60 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field
device communication port.
Note: If the port is configured with the "Use CTS Line" set to 'Y', then a jumper is
required between the RTS and the CTS line on the module connection.
5.3.3 RS-422
ProSoft Technology, Inc. Page 61 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
5.3.4 RS-485
The RS-485 interface requires a single two or three wire cable. The Common
connection is optional and dependent on the RS-485 network. The cable required
for this interface is shown below:
RS-485 and RS-422 Tip
If communication in the RS-422/RS-485 mode does not work at first, despite all
attempts, try switching termination polarities. Some manufacturers interpret +/and A/B polarities differently.
5.3.5 DB9 to RJ45 Adaptor (Cable 14)
Page 62 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
5.4 MVI56-CAS Database Definition
This section contains a listing of the internal database of the MVI56-CAS module.
This information can be used to interface other devices to the data contained in
the module.
Register Range TCA Low TCA High Content Size
0 to 4999 40001 45000 User Data 5000
5000 to 5009 45001 45010 Backplane Configuration 10
5010 to 5039 45011 45040 Port 1 Setup 30
5040 to 5069 45041 45070 Port 2 Setup 30
6000 to 6034 47601 47633 Misc. Status Data 335
The User Data area holds data received from the processor (write blocks).
Additionally, this data area is used as a data source for the processor (read
blocks).
Detailed definition of the miscellaneous status data area can be found in the
Reference chapter.
Definition of the configuration data areas can be found in the data definition
section of this document and in the Reference chapter.
Refer to the Reference chapter for a discussion of the command control section
of the database.
5.5 MVI56-CAS Status Data Definition
This section contains a description of the members present in the CASInStat
object. This data is transferred from the module to the processor as part of each
read block.
Offset Content Description
202 Program Scan Count
203 to 204 Product Code These two registers contain the product code of "CAS"
205 to 206 Product Version
207 to 208 Operating System
209 to 210 Run Number
211
212
213
214 Port 1 Requests
Port 1 Command List
Requests
Port 1 Command List
Response
Port 1 Command List
Errors
This value is incremented each time a complete
program cycle occurs in the module.
These two registers contain the product version for the
currently running software.
These two registers contain the month and year values
for the program operating system.
These two registers contain the run number value for
the currently running software.
This field contains the number of requests made from
this port to slave devices on the network.
This field contains the number of slave response
messages received on the port.
This field contains the number of command errors
processed on the port. These errors could be due to a
bad response or command.
This field contains the total number of messages sent
out of the port.
ProSoft Technology, Inc. Page 63 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Offset Content Description
215 Port 1 Responses
216 Port 1 Errors Sent
217 Port 1 Errors Received
218
219
220
221 Port 2 Requests
222 Port 2 Responses
223 Port 2 Errors Sent
224 Port 2 Errors Received
225 Read Block Count
226 Write Block Count
227 Parse Block Count
228
229
230 Error Block Count
231 Port 1 Current Error
232 Port 1 Last Error
233 Port 2 Current Error
234 Port 2 Last Error
Port 2 Command List
Requests
Port 2 Command List
Response
Port 2 Command List
Errors
Command Event Block
Count
Command Block
Count
This field contains the total number of messages
received on the port.
This field contains the total number of error messages
sent out of the port.
This field contains the total number of message errors
received on the port.
This field contains the number of requests made from
this port to slave devices on the network.
This field contains the number of slave response
messages received on the port.
This field contains the number of command errors
processed on the port. These errors could be due to a
bad response or command.
This field contains the total number of messages sent
out the port.
This field contains the total number of messages
received on the port.
This field contains the total number of message errors
sent out the port.
This field contains the total number of message errors
received on the port.
This field contains the total number of read blocks
transferred from the module to the processor.
This field contains the total number of write blocks
transferred from the processor to the module.
This field contains the total number of blocks
successfully parsed that were received from the
processor.
This field contains the total number of command event
blocks received from the processor.
This field contains the total number of command blocks
received from the processor.
This field contains the total number of block errors
recognized by the module.
For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the currently executing command.
For a slave port, this field contains the value of the last
error code returned. For a master port, this field
contains the index of the command with an error.
For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the currently executing command.
For a slave port, this field contains the value of the last
error code returned. For a master port, this field
contains the index of the command with an error.
Page 64 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Offset Content Description
235 Port 1 Status Scan
236 Port 2 Status Scan
Contains the port's scan status in the upper byte and
the port's current error status in the lower byte. The
scan status is encoded in the upper byte as follows:
Bit 13 - Status Data Scan
Bit 14 - Analog Data Scan
Bit 15 - Read All Data Scan
Contains the port's scan status in the upper byte and
the port's current error status in the lower byte. The
scan status is encoded in the upper byte as follows:
Bit 13 - Status Data Scan
Bit 14 - Analog Data Scan
Bit 15 - Read All Data Scan
5.6 MVI56-CAS Configuration Data Definition
This section contains listings of the MVI56-CAS module's database that are
related to the module's configuration. This data is available to any node on the
network and is read from the ControlLogix processor when the module first
initializes.
5.6.1 Port 1
Group Register Content Description
Backplane
Setup
5001
5002
5003
5004
5005 Spare Spare
5006 Spare Spare
5007 Spare Spare
5008 Spare Spare
5009 Spare Spare
5010 Enabled This parameter enables the port. Valid values are 0 and 1.
5000
Status
Length
Analog
Length
Meter
Length
Tank
Length
Backplane
Fail
This parameter specifies the number of status words in
the module (0 to 250).
This parameter specifies the number of analog words in
the module (0 to 250).
This parameter specifies the number of meter words in the
module (0 to 250).
This parameter specifies the number of tank words in the
module (0 to 250).
This parameter specifies the number of successive
transfer errors that must occur before the communication
ports are shut down. If the parameter is set to zero, the
communication ports will continue to operate under all
conditions. If the value is set to larger than zero (1 to
65535), communications will cease if the specified number
of failures occur.
ProSoft Technology, Inc. Page 65 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Group Register Content Description
5011 Baud Rate
5012 Parity
5013 Data Bits
5014 Stop Bits
5015 RTS On
5016 RTS Off
5017
Minimum
Response
Time
5018
Use CTS
Line
5019 Slave ID
5020
Use Guard
Band
5021
Guard
Band Time
5022
Direct
Control
5023
Swap
Config
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200. Valid entries for this field include 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 28800, 38400,
57600, and 115.
This is the parity code to be used for the port. None, Odd,
Even.
This parameter sets the number of data bits for each word
used by the protocol. Valid entries are 5 or 8.
This parameter sets the number of stop bits to be used
with each data value set. Valid entries are 1 and 2.
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data is transmitted. Valid
values are 0 to 65535.
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low. Valid values are 0 to 65535.
This parameter specifies the minimum number of
milliseconds to delay before responding to a request
message. This pre-send delay is applied before the RTS
on time. This may be required when communicating with
slow devices.
This parameter specifies if the CTS modem control line is
to be used. If the parameter is set to 0, the CTS line will
not be monitored. If the parameter is set to 1, the CTS line
will be monitored and must be high before the module will
send data. This parameter is normally only required when
half-duplex modems are used for communication (2-wire).
This parameter defines the virtual slave address for the
internal database. Any request received by the port with
this address will be processed by the module. Be certain
each device has a unique address on a network. Valid
range for this parameter is 1 to 255 (247 on some
networks).
Not implemented.
Not Implemented.
This parameter enables direct control. If enabled, a Select
command is not required before a Control command.
Valid entries are 0 and 1.
This parameter sets the data swapping. The swapping is
set as a bit field. Bit 0 corresponds to status data, Bit 1 to
analog data, and Bit 2 to meter data.
Page 66 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
5.6.2 Port 2
Group Register Content Description
5040 Enabled This parameter enables the port. Valid entries are 0 and 1.
5041 Baud Rate
5042 Parity
5043 Data Bits
5044 Stop Bits
5045 RTS On
5046 RTS Off
5047
Minimum
Response
Time
5048
Use CTS
Line
5049 Slave ID
5050
Use Guard
Band
5051
Guard
Band Time
5052
Direct
Control
5053
Swap
Config
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200. Valid entries for this field include 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 28800, 38400,
57600, and 115.
This is the parity code to be used for the port. None, Odd,
Even.
This parameter sets the number of data bits for each word
used by the protocol. Valid entries are 5 or 8.
This parameter sets the number of stop bits to be used
with each data value set. Valid entries are 1 and 2.
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data is transmitted. Valid
values are 0 to 65535.
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low. Valid values are 0 to 65535.
This parameter specifies the minimum number of
milliseconds to delay before responding to a request
message. This pre-send delay is applied before the RTS
on time. This may be required when communicating with
slow devices.
This parameter specifies if the CTS modem control line is
to be used. If the parameter is set to 0, the CTS line will
not be monitored. If the parameter is set to 1, the CTS line
will be monitored and must be high before the module will
send data. This parameter is normally only required when
half-duplex modems are used for communication (2-wire).
This parameter defines the virtual slave address for the
internal database. Any request received by the port with
this address will be processed by the module. Be certain
each device has a unique address on a network. Valid
range for this parameter is 1 to 255 (247 on some
networks).
Not implemented.
Not implemented.
This parameter enables direct control. If enabled, a Select
command is not required before a Control command.
Valid entries are 0 and 1.
This parameter sets data swapping. The swapping is set
as a bit field. Bit 0 corresponds to status data, Bit 1 to
analog data, and Bit 2 to meter data.
ProSoft Technology, Inc. Page 67 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
5.6.3 Status
Group Register Content Description
Misc.
Status
6001, 6002
6003, 6004
6005, 6006
6007, 6008
6009
6010
6011
6012
6013
6014
6015
6016
6017
6018
6019
6020
6021
6000
Program
Scan Count
Product
Code
Product
Version
Operating
System
Run
Number
Port 1
Command
List
Requests
Port 1
Command
List
Response
Port 1
Command
List Errors
Port 1
Requests
Port 1
Responses
Port 1
Errors Sent
Port 1
Errors
Received
Port 2
Command
List
Requests
Port 2
Command
List
Response
Port 2
Command
List Errors
Port 2
Requests
Port 2
Responses
Port 2
Errors Sent
This value is incremented each time a complete
program cycle occurs in the module.
These two registers contain the product code of
"CAS"
These two registers contain the product version for
the currently running software.
These two registers contain the month and year
values for the program operating system.
These two registers contain the run number value for
the currently running software.
This field contains the number of requests made from
this port to slave devices on the network.
This field contains the number of slave response
messages received on the port.
This field contains the number of command errors
processed on the port. These errors could be due to a
bad response or command.
This field contains the total number of messages sent
out of the port.
This field contains the total number of messages
received on the port.
This field contains the total number of error messages
sent out of the port.
This field contains the total number of message errors
received on the port.
This field contains the number of requests made from
this port to slave devices on the network.
This field contains the number of slave response
messages received on the port.
This field contains the number of command errors
processed on the port. These errors could be due to a
bad response or command.
This field contains the total number of messages sent
out the port.
This field contains the total number of messages
received on the port.
This field contains the total number of message errors
sent out the port.
Page 68 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Group Register Content Description
6022
Port 2
Errors
Received
6023
Read Block
Count
6024
Write Block
Count
6025
Parse Block
Count
6026
Command
Event Block
Count
6027
Command
Block Count
6028
Error Block
Count
6029
Port 1
Current
Error/Index
6030
Port 1 Last
Error
6031
Port 2
Current
Error
6032
Port 2 Last
Error
6033
Port 1
Status Scan
6034
Port 2
Status Scan
6703 Spare Spare
- - 6799 Spare Spare
This field contains the total number of message errors
received on the port.
This field contains the total number of read blocks
transferred from the module to the processor.
This field contains the total number of write blocks
transferred from the processor to the module.
This field contains the total number of blocks
successfully parsed that were received from the
processor.
This field contains the total number of command event
blocks received from the processor.
This field contains the total number of command
blocks received from the processor.
This field contains the total number of block errors
recognized by the module.
For a slave port, this field contains the value of the
current error code returned. For a master port, this
field contains the index of the currently executing
command.
For a slave port, this field contains the value of the
last error code returned. For a master port, this field
contains the index of the command with an error.
For a slave port, this field contains the value of the
current error code returned. For a master port, this
field contains the index of the currently executing
command.
For a slave port, this field contains the value of the
last error code returned. For a master port, this field
contains the index of the command with an error.
This register contains the port's Scan Status in the
upper byte and the port's current Error Status in the
lower byte. The Scan Status is encoded in the upper
byte as follows:
Bit 13 - Status Data scan
Bit 14 - Analog Data scan
Bit 15 - Read All Data scan
This register contains the port's Scan Status in the
upper byte and the port's current Error Status in the
lower byte. The Scan Status is encoded in the upper
byte as follows:
Bit 13 - Status Data scan
Bit 14 - Analog Data scan
Bit 15 - Read All Data scan
ProSoft Technology, Inc. Page 69 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
5.7 MVI56-CAS Command Control
Command Control data is received from other nodes on the network that can
control the MVI56-CAS module. Specific values are written to regions of this
block to control the module. Currently, the module is programmed to handle the
receipt of the following requests: write configuration to processor, warm boot and
cold boot.
The remote node controls the module by writing one of the following values to
register 6800:
Value Description
9997 Write configuration in database to the processor and warm boot the module.
9998 Warm boot the module.
9999 Cold boot the module.
The control register is cleared (a value of 0) after the operation is executed with
the exception of the 9997 command. If the module fails to successfully transfer
the configuration to the processor, an error code will be returned in the control
register as follows:
Value Description
0 No error, transfer successful
-1 Error transferring general configuration information.
Ladder logic must handle the 9997 command. No ladder logic is required when
using the warm or cold boot commands.
5.8 Protocol Commands
The ProSoft Technology CAS module communication driver supports several
data read and write commands. When configuring an application, it may be
important to understand how the commands function in order to determine how
to structure the application data.
5.8.1 Data Read Functions
As stated in earlier sections, the data sent to the master is taken directly out of
the module's memory at the time a response is sent.
Function Function Name Description
1 Read Status Data
2 Read Analog Data
The module supports access to a total of up to 250 words of
status data from the ladder processor. In TCAP vernacular,
the "Start Card Address" identifies the starting word, and the
"Number of Cards" identifies the number of words.
The module supports access to a total of up to 250 words of
analog data from the ladder processor. In TCAP vernacular,
the "Start Card No." and the "Start Point No." (upper and lower
four bits respectively) are treated as one byte to develop a
starting word address, while the "Number of Analogs"
determines the number of words to be returned to the master.
Page 70 of 86 ProSoft Technology, Inc.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Function Function Name Description
3 Read Meter Data
10
11
16 Read All Data
Read Frozen Analog
Data
Read Frozen Meter
Data
The module supports access to a total of up to 250 words of
Meter data (125 meter readings) from the ladder processor. In
TCAP vernacular, the "Starting Meter Number" determines the
first word to be accessed, while the "Number of meters to be
returned" value determines the number of words to be
returned to the master.
This function provides the master access to the contents of up
to a 250 word buffer maintained in the module. This buffer
contains the analog values stored as a result of the last
"Freeze Analogs" command (44/45) received from the Master.
It is addressed in the same fashion as Function 2.
This function provides the Master access to the contents of up
to a 250 word buffer maintained in the module. This buffer
contains the meter values stored as a result of the last "Freeze
Meters" command (43/45) received from the Master. It is
addressed in the same fashion as Function 3.
This general-purpose command is supported in the ProSoft
module. The following Data Select Types are available from
the module:
Status Inputs (Data Select 1, bit 7)
Analog Inputs (Data Select 1, bit 6)
Meter Accumulator Inputs (Data Select 1, bit 5)
Current Tank Data (Data Select 1, bit 2)
Maximum Analogs Register (Data Select 1, bit 1)
Local Freeze Analog Data (Data Select 1, bit 0)
Local Freeze Meter Data (Data Select 2, bit 7)
Local Freeze Tank Data (Data Select 2, bit 6)
Hourly Freeze Analog Data (Data Select 2, bit 5)
Hourly Freeze Meter Data (Data Select 2, bit 4)
Hourly Freeze Tank Data (Data Select 2, bit 3)
Periodic Analog Data (Data Select 2, bit 2)
Periodic Meter Data (Data Select 2, bit 1)
Periodic Tank Data (Data Select 2, bit 0)
The command allows up to 63 analog values to be requested
and up to 7 meters. If no data quantity is requested (length
fields are zero), all of the available data, as defined in the
Configuration Parameters, will be returned. When the Status
Inputs are requested, the full status table is returned.
5.8.2 Control Commands From Master
When Control commands are received from a Master, their action is immediately
communicated to the PLC/SLC for action. No modification is made directly to the
ProSoft Module's memory as a result of a Control command. In order for and
Control action to be reflected in the module's memory, it must be transferred
within the Status Data block.
ProSoft Technology, Inc. Page 71 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Function Function Name Description
30/31
Momentary Control
Select/Operate
32/33
Continuous Control
Select/Operate
34/35 Setpoint Select/Operate
These control commands are recognized by the
module. If the Operate command is received out of
sequence (must be received in next communication
sequence after Select command), the command is
disregarded. If the module is configured for Direct
Control, then the Master need only send the Operate
command for action to occur. In TCAP vernacular, the
"Card Number" and the "Point Number" are combined
to identify the bit number. The action value is always
set to 1, so the action will always be to set a bit true
momentarily.
These control commands are recognized by the
module. If the Operate command is received out of
sequence (must be received in next communication
sequence after Select command), the command is
disregarded. If the module is configured for Direct
control, then the master need only send the Operate
command for action to occur. In TCAP vernacular, the
"Card Number" and the "Point Number" are combined
to identify the bit number.
These control commands are recognized by the
module. If the Operate command is received out of
sequence (must be received in next communication
sequence after Select command), the command is
disregarded. If the module is configured for Direct
Control, then the Master need only send the Operate
command for action to occur. In TCAP vernacular, the
"Card Number" (upper 7 bits) is combined with the
"Point Number" (low 1 bit) to obtain an effective
addressing range of 256 registers. The value written
to the ladder logic is limited to a 12 bit value by the
protocol specification.
5.8.3 Freeze Data Commands
These general purpose commands initiate the movement of data within buffers in
the ProSoft Technology module. These buffers are maintained for access by
related read commands, discussed previously.
The module one-shots the freeze commands from the Master, enable the
movement of the buffers only if the Master has previously issued a read to the
previously frozen buffer.
Function Function Name Description
43 Freeze Meters
44 Freeze Analogs
45
Freeze Meters and
Analogs
46/6 Special Freeze
Page 72 of 86 ProSoft Technology, Inc.
Moves the Meter Data buffer to the Freeze Meter
buffer.
Moves the Analog Data buffer to the Freeze Analog
buffer.
Moves the Meter Data buffer and the Analog Data
buffer to their respective Freeze buffers.
Moves current data to hourly, local, and periodic
registers.
December 26, 2007
Reference MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
5.8.4 Exception Data Commands
The polled exception functionality is implemented in the module. The module
copies data that changes enough to meet exception requirements into an
exception table. The data must change more than the default dead-bands in
order to record an exception. The default dead-bands are:
Analog Dead-Band: 1000
Meter Dead-Band: 100
Tank Dead-Band: 0
Status Dead-Band: 0
Function Function Name Description
50 Exception Data Request
Two modes are supported; Current Exceptions and All
Exception Data. The mode is selected by the update
bit in the master message.
ProSoft Technology, Inc. Page 73 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Reference
Teledyne CA Slave Module
Page 74 of 86 ProSoft Technology, Inc.
December 26, 2007
Support, Service & Warranty MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
6 Support, Service & Warranty
In This Chapter
¾ How to Contact Us: Sales and Support.................................. 76
¾ Return Material Authorization (RMA) Policies and Conditions 77
¾ Procedures for Return of Units Under Warranty..................... 77
¾ Procedures for Return of Units Out of Warranty..................... 78
Be sure and read the full Warranty that can be found on our web site at
www.prosoft-technology.com
content in this summary is subject to change without notice. The content is
current at date of publication.
for details and other terms and conditions. The
ProSoft Technology, Inc. strives to provide meaningful support to its customers.
Should any questions or problems arise, please feel free to contact us at:
Internet
Web Site: http://www.prosoft-technology.com/support
E-mail address: support@prosoft-technology.com
Those of us at ProSoft Technology, Inc. want to provide the best and quickest
support possible, so before calling please have the following information
available. You may wish to fax this information to us prior to calling.
1 Product Version Number
2 System architecture
3 Network details
In the case of hardware, we will also need the following information:
1 Module configuration and contents of file
2 Module Operation
3 Configuration/Debug status information
4 LED patterns
5 Information about the processor and user data files as viewed through the
development software and LED patterns on the processor
6 Details about the networked devices interfaced, if any
For technical support calls within the United States, an after-hours answering
system allows pager access to one of our qualified technical and/or application
support engineers at any time to answer your questions.
ProSoft Technology, Inc. Page 75 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Support, Service & Warranty
Teledyne CA Slave Module
6.1 How to Contact Us: Sales and Support
All ProSoft Technology Products are backed with full technical support. Contact
our worldwide Technical Support team and Customer Service representatives
directly by phone or email:
USA / Latin America (excluding Brasil) (Office in California)
+603.7724.2080
+603.7724.2090 (Fax)
C210, Damansara Intan,
1 Jalan SS20/27, 47400 Petaling Jaya
Selangor, Malaysia
+603.7724.2080, asiapc@prosoft-technology.com
Languages spoken include: Chinese, Japanese, English
China Pacific (office in China)
+86.21.64518356 x 8011
+86.21.64756957 (Fax)
4/F, No. 16 Hongcao Road
Shanghai, China 200233
China
+86.21.64518356 x 8011, zhang@prosoft-technology.com
Languages spoken include: Chinese, English
Europe / Middle East / Africa (office in Toulouse, France)
+33 (0) 5.34.36.87.20
+33 (0) 5.61.78.40.52 (Fax)
Zone d'activité de Font Grasse
17, rue des Briquetiers
F-31700 Blagnac
France
+33 (0) 5.34.36.87.20. support. EMEA@prosoft-technology.com
Languages spoken include: French, English
Brasil (office in Sao Paulo)
+55-11-5084-5178
+55-11-5083-3776 (Fax)
Rua Vergueiro, 2949 - sala 182 - Edifício Vergueiro Work Center
Vila Mariana - São Paulo
Cep: 04101-300 - Brasil
+55-11-5084-5178, eduardo@prosoft-technology.com
Languages spoken include: Portuguese, English
Page 76 of 86 ProSoft Technology, Inc.
December 26, 2007
Support, Service & Warranty MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
6.2 Return Material Authorization (RMA) Policies and Conditions
The following RMA Policies and Conditions apply to any returned product. These
RMA Policies are subject to change by ProSoft without notice. For warranty
information, see Section C below entitled "Limited Warranty". In the event of any
inconsistency between the RMA Policies and the Warranty, the Warranty shall
govern.
6.2.1 All Product Returns
1 In order to return a Product for repair, exchange or otherwise, the Customer
must obtain a Returned Material Authorization (RMA) number from ProSoft
and comply with ProSoft shipping instructions.
2 In the event that the Customer experiences a problem with the Product for
any reason, Customer should contact ProSoft Technical Support at one of the
telephone numbers listed above in Section A. A Technical Support Engineer
will request several tests in an attempt to isolate the problem. If after these
tests are completed, the Product is found to be the source of the problem,
ProSoft will issue an RMA.
3 All returned Products must be shipped freight prepaid, in the original shipping
container or equivalent, to the location specified by ProSoft, and be
accompanied by proof of purchase. The RMA number is to be prominently
marked on the outside of the shipping box. Customer agrees to insure the
Product or assume the risk of loss or damage in transit. Products shipped to
ProSoft without an RMA number will be returned to the Customer, freight
collect. Contact ProSoft Technical Support for further information.
4 Out of warranty returns are not allowed on RadioLinx accessories such as
antennas, cables, and brackets.
The following policy applies for Non-Warranty Credit Returns:
A 10% Restocking Fee if Factory Seal is not broken
B 20% Restocking Fee if Factory Seal is broken
ProSoft retains the right, in its absolute and sole discretion, to reject any nonwarranty returns for credit if the return is not requested within three (3) months
after shipment of the Product to Customer, if the Customer fails to comply with
ProSoft's shipping instructions, or if the Customer fails to return the Product to
ProSoft within six (6) months after Product was originally shipped.
6.3 Procedures for Return of Units Under Warranty
1 A Technical Support Engineer must pre-approve all product returns.
2 Module is repaired or replaced after a Return Material Authorization Number
is entered and a replacement order is generated.
3 Credit for the warranted item is issued within 10 business days after receipt of
product and evaluation of the defect has been performed by ProSoft. The
credit will only be issued provided the product is returned with a valid Return
Material Authorization Number and in accordance with ProSoft's shipping
instructions.
ProSoft Technology, Inc. Page 77 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Support, Service & Warranty
Teledyne CA Slave Module
a) If no defect is found, a credit is issued.
b) If a defect is found and is determined to be customer generated or if the
defect is otherwise not covered by ProSoft's Warranty, or if the module is
not repairable, a credit is not issued and payment of the replacement
module is due.
6.4 Procedures for Return of Units Out of Warranty
1 Customer sends unit in for evaluation.
2 If no defect is found, Customer will be charged the equivalent of US $100
plus shipping, duties and taxes that may apply. A new Purchase Order will be
required for this evaluation fee.
If the unit is repaired the charge to the Customer will be 30%* of the list price
plus any shipping, duties and taxes that may apply. A new Purchase Order
will be required for a product repair.
3 For an immediate exchange, a new module may be purchased and sent to
Customer while repair work is being performed. Credit for purchase of the
new module will be issued when the new module is returned in accordance
with ProSoft's shipping instructions and subject to ProSoft's policy on nonwarranty returns. This is in addition to charges for repair of the old module
and any associated charges to Customer.
4 If, upon contacting ProSoft Customer Service, the Customer is informed that
unit is believed to be unrepairable, the Customer may choose to send unit in
for evaluation to determine if the repair can be made. Customer will pay
shipping, duties and taxes that may apply. If unit cannot be repaired, the
Customer may purchase a new unit.
6.4.1 Un-repairable Units
3150-All
3750
3600-All
3700
3170-All
3250
1560 can be repaired, if defect is the power supply
1550 can be repaired, if defect is the power supply
3350
3300
1500-All
* 30% of list price is an estimated repair cost only. The actual cost of
repairs will be determined when the module is received by ProSoft and
evaluated for needed repairs.
Page 78 of 86 ProSoft Technology, Inc.
December 26, 2007
Support, Service & Warranty MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
6.4.2 Purchasing Warranty Extension
As detailed below in ProSoft's Warranty, the standard Warranty Period is one
year (or in the case of RadioLinx modules, three years) from the date of delivery.
The Warranty Period may be extended for an additional charge, as follows:
Additional 1 year = 10% of list price
Additional 2 years = 20% of list price
Additional 3 years = 30% of list price
6.5 LIMITED WARRANTY
This Limited Warranty ("Warranty") governs all sales of hardware, software and
other products (collectively, "Product") manufactured and/or offered for sale by
ProSoft, and all related services provided by ProSoft, including maintenance,
repair, warranty exchange, and service programs (collectively, "Services"). By
purchasing or using the Product or Services, the individual or entity purchasing or
using the Product or Services ("Customer") agrees to all of the terms and
provisions (collectively, the "Terms") of this Limited Warranty. All sales of
software or other intellectual property are, in addition, subject to any license
agreement accompanying such software or other intellectual property.
6.5.1 What Is Covered By This Warranty
A Warranty On New Products: ProSoft warrants, to the original purchaser
only, that the Product that is the subject of the sale will (1) conform to and
perform in accordance with published specifications prepared, approved,
and issued by ProSoft, and (2) will be free from defects in material or
workmanship; provided these warranties only cover Product that is sold as
new. This Warranty expires one year (or in the case of RadioLinx
modules, three years) from the date of shipment (the "Warranty Period").
If the Customer discovers within the Warranty Period a failure of the
Product to conform to specifications, or a defect in material or
workmanship of the Product, the Customer must promptly notify ProSoft
by fax, email or telephone. In no event may that notification be received by
ProSoft later than 15 months (or in the case of RadioLinx modules, 39
months) from the date of delivery. Within a reasonable time after
notification, ProSoft will correct any failure of the Product to conform to
specifications or any defect in material or workmanship of the Product,
with either new or used replacement parts. Such repair, including both
parts and labor, will be performed at ProSoft's expense. All warranty
service will be performed at service centers designated by ProSoft. If
ProSoft is unable to repair the Product to conform to this Warranty after a
reasonable number of attempts, ProSoft will provide, at its option, one of
the following: a replacement product, a full refund of the purchase price or
a credit in the amount of the purchase price. All replaced product and
parts become the property of ProSoft. These remedies are the Customer's
only remedies for breach of warranty.
B Warranty On Services: Material and labor used by ProSoft to repair a
verified malfunction or defect are warranted on the terms specified above
ProSoft Technology, Inc. Page 79 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Support, Service & Warranty
Teledyne CA Slave Module
for new Product, provided said warranty will be for the period remaining on
the original new equipment warranty or, if the original warranty is no
longer in effect, for a period of 90 days from the date of repair.
C The Warranty Period for RadioLinx accessories (such as antennas,
cables, brackets, etc.) are the same as for RadioLinx modules, that is,
three years from the date of shipment.
6.5.2 What Is Not Covered By This Warranty
A ProSoft makes no representation or warranty, expressed or implied, that
the operation of software purchased from ProSoft will be uninterrupted or
error free or that the functions contained in the software will meet or
satisfy the purchaser's intended use or requirements; the Customer
assumes complete responsibility for decisions made or actions taken
based on information obtained using ProSoft software.
B With the exception of RadioLinx accessories referenced in paragraph 1(c)
this Warranty does not cover any product, components, or parts not
manufactured by ProSoft.
C This Warranty also does not cover the failure of the Product to perform
specified functions, or any other non-conformance, defects, losses or
damages caused by or attributable to any of the following: (i) shipping; (ii)
improper installation or other failure of Customer to adhere to ProSoft's
specifications or instructions; (iii) unauthorized repair or maintenance; (iv)
attachments, equipment, options, parts, software, or user-created
programming (including, but not limited to, programs developed with any
IEC 61131-3 programming languages, or "C") not furnished by ProSoft; (v)
use of the Product for purposes other than those for which it was
designed; (vi) any other abuse, misapplication, neglect or misuse by the
Customer; (vii) accident, improper testing or causes external to the
Product such as, but not limited to, exposure to extremes of temperature
or humidity, power failure or power surges outside of the limits indicated
on the product specifications; or (viii) disasters such as fire, flood,
earthquake, wind or lightning.
D The information in this Agreement is subject to change without notice.
ProSoft shall not be liable for technical or editorial errors or omissions
made herein; nor for incidental or consequential damages resulting from
the furnishing, performance or use of this material. The user guides
included with your original product purchased by you from ProSoft,
contains information protected by copyright. No part of the guide may be
duplicated or reproduced in any form without prior written consent from
ProSoft.
Page 80 of 86 ProSoft Technology, Inc.
December 26, 2007
Support, Service & Warranty MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
6.5.3 DISCLAIMER REGARDING HIGH RISK ACTIVITIES
PRODUCT MANUFACTURED OR SUPPLIED BY PROSOFT IS NOT FAULT
TOLERANT AND IS NOT DESIGNED, MANUFACTURED OR INTENDED FOR
USE IN HAZARDOUS ENVIRONMENTS REQUIRING FAIL-SAFE
PERFORMANCE (INCLUDING, WITHOUT LIMITATION, THE OPERATION OF
NUCLEAR FACILITIES, AIRCRAFT NAVIGATION OF COMMUNICATION
SYSTEMS, AIR TRAFFIC CONTROL, DIRECT LIFE SUPPORT MACHINES
OR WEAPONS SYSTEMS), IN WHICH THE FAILURE OF THE PRODUCT
COULD LEAD DIRECTLY OR INDIRECTLY TO DEATH, PERSONAL INJURY,
OR SEVERE PHYSICAL OR ENVIRONMENTAL DAMAGE (COLLECTIVELY,
"HIGH RISK ACTIVITIES"). PROSOFT SPECIFICALLY DISCLAIMS ANY
EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR HIGH RISK
ACTIVITIES.
6.5.4 DISCLAIMER OF ALL OTHER WARRANTIES
THE WARRANTIES SET FORTH IN PARAGRAPH 1 ABOVE ARE IN LIEU OF
ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT
LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
6.5.5 LIMITATION OF REMEDIES**
IN NO EVENT WILL PROSOFT (OR ITS DEALER) BE LIABLE FOR ANY
SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES BASED ON
BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT
TORT, OR ANY OTHER LEGAL THEORY. DAMAGES THAT PROSOFT AND
ITS DEALER WILL NOT BE RESPONSIBLE FOR INCLUDE, BUT ARE NOT
LIMITED TO: LOSS OF PROFITS; LOSS OF SAVINGS OR REVENUE; LOSS
OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT; LOSS OF
DATA; COST OF CAPITAL; COST OF ANY SUBSTITUTE EQUIPMENT,
FACILITIES, OR SERVICES; DOWNTIME; THE CLAIMS OF THIRD PARTIES,
INCLUDING CUSTOMERS OF THE PURCHASER; AND INJURY TO
PROPERTY.
** Some areas do not allow time limitations on an implied warranty, or allow the exclusion or
limitation of incidental or consequential damages. In such areas the above limitations may not
apply. This Warranty gives you specific legal rights, and you may also have other rights which vary
from place to place.
6.5.6 Time Limit for Bringing Suit
Any action for breach of warranty must be commenced within 15 months (or in
the case of RadioLinx modules, 39 months) following shipment of the Product.
ProSoft Technology, Inc. Page 81 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Support, Service & Warranty
Teledyne CA Slave Module
6.5.7 No Other Warranties
Unless modified in writing and signed by both parties, this Warranty is
understood to be the complete and exclusive agreement between the parties,
suspending all oral or written prior agreements and all other communications
between the parties relating to the subject matter of this Warranty, including
statements made by salesperson. No employee of ProSoft or any other party is
authorized to make any warranty in addition to those made in this Warranty. The
Customer is warned, therefore, to check this Warranty carefully to see that it
correctly reflects those terms that are important to the Customer.
6.5.8 Intellectual Property
A Any documentation included with Product purchased from ProSoft is
protected by copyright and may not be photocopied or reproduced in any
form without prior written consent from ProSoft.
B ProSoft's technical specifications and documentation that are included
with the Product are subject to editing and modification without notice.
C Transfer of title shall not operate to convey to Customer any right to make,
or have made, any Product supplied by ProSoft.
D Customer is granted no right or license to use any software or other
intellectual property in any manner or for any purpose not expressly
permitted by any license agreement accompanying such software or other
intellectual property.
E Customer agrees that it shall not, and shall not authorize others to, copy
software provided by ProSoft (except as expressly permitted in any
license agreement accompanying such software); transfer software to a
third party separately from the Product; modify, alter, translate, decode,
decompile, disassemble, reverse-engineer or otherwise attempt to derive
the source code of the software or create derivative works based on the
software; export the software or underlying technology in contravention of
applicable US and international export laws and regulations; or use the
software other than as authorized in connection with use of Product.
6.5.9 Additional Restrictions Relating To Software And Other
Intellectual Property
In addition to complying with the Terms of this Warranty, Customers purchasing
software or other intellectual property shall comply with any license agreement
accompanying such software or other intellectual property. Failure to do so may
void this Warranty with respect to such software and/or other intellectual
property.
Page 82 of 86 ProSoft Technology, Inc.
December 26, 2007
Support, Service & Warranty MVI56-CAS ♦ ControlLogix Platform
Teledyne CA Slave Module
6.5.10 Allocation of risks
This Warranty allocates the risk of product failure between ProSoft and the
Customer. This allocation is recognized by both parties and is reflected in the
price of the goods. The Customer acknowledges that it has read this Warranty,
understands it, and is bound by its Terms.
6.5.11 Controlling Law and Severability
This Warranty shall be governed by and construed in accordance with the laws of
the United States and the domestic laws of the State of California, without
reference to its conflicts of law provisions. If for any reason a court of competent
jurisdiction finds any provisions of this Warranty, or a portion thereof, to be
unenforceable, that provision shall be enforced to the maximum extent
permissible and the remainder of this Warranty shall remain in full force and
effect. Any cause of action with respect to the Product or Services must be
instituted in a court of competent jurisdiction in the State of California.
ProSoft Technology, Inc. Page 83 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Support, Service & Warranty
Teledyne CA Slave Module
Page 84 of 86 ProSoft Technology, Inc.
December 26, 2007
Index MVI56-CAS ♦ ControlLogix Platform Teledyne CA Slave Module
Download the Sample Program to the
Processor • 14
Index
Additional Restrictions Relating To Software
All Product Returns • 77
Allocation of risks • 83
Analyzing Data for the first application port •
Analyzing Data for the second application
Backplane Data Transfer • 50
Cable Connections • 57
Changing Parameters During Operation • 24
Clearing a Fault Condition • 45
Cold Boot • 55
Configuration Data Transfer • 53
Configuration Objects • 25
Configuring RSLinx • 15
Connect your PC to the Module • 17
Connect your PC to the Processor • 13
Control Commands From Master • 71
Controlling Law and Severability • 83
ControlLogix Processor Not in Run • 50
A
And Other Intellectual Property • 82
37
port • 37
B
C
E
Exception Data Commands • 73
Exiting the Program • 36
F
Features and Benefits • 47
Freeze Data Commands • 72
Functional Overview • 7, 49
Functional Specifications • 48
G
General Concepts • 49
General Specifications • 47
Guide to the MVI56-CAS User Manual • 7
H
Hardware Specifications • 48
How to Contact Us
Sales and Support • 76
I
Install the Module in the Rack • 12
Installing and Configuring the Module • 19
Intellectual Property • 82
K
Keystrokes • 32
D
Data Analyzer • 37
Data Analyzer Tips • 39
Data Flow Between MVI56-CAS Module and
ControlLogix Processor • 56
Data Read Functions • 70
Data Transfer Parameters (CASModule) • 25
Database View Menu • 42
DB9 to RJ45 Adaptor (Cable 14) • 62
Diagnostics and Troubleshooting • 7, 31
Disabling the RSLinx Driver for the Com Port
on the PC • 33, 57
DISCLAIMER OF ALL OTHER
WARRANTIES • 81
DISCLAIMER REGARDING HIGH RISK
ACTIVITIES • 81
Displaying the Current Page of Registers
Again • 42
Displaying Timing Marks in the Data
Analyzer • 37
Ladder Logic • 29
LED Status Indicators • 44
LIMITATION OF REMEDIES** • 81
LIMITED WARRANTY • 79
Main Logic Loop • 50
Main Menu • 34
Module Configuration • 23
Module Configuration Data • 54
Module Data Object (CASModuleDef) • 24
Moving Back Through 5 Pages of Registers •
43
MVI56-CAS Command Control • 70
MVI56-CAS Configuration Data Definition •
65
MVI56-CAS Database Definition • 63
MVI56-CAS Status Data Definition • 63
L
M
ProSoft Technology, Inc. Page 85 of 86
December 26, 2007
MVI56-CAS ♦ ControlLogix Platform Index
Teledyne CA Slave Module
N
Navigation • 31
No Other Warranties • 82
Normal Data Transfer • 52
Status Object (CASInStat) • 27
Stopping the Data Analyzer • 38
Support, Service & Warranty • 7, 75
System Requirements • 9
T
O
Opening the Data Analyzer Menu • 34
Opening the Database Menu • 35
P
Package Contents • 10
Pass-Through Control Blocks • 55
Please Read This Notice • 2
Port 1 • 65
Port 2 • 67
Power Up • 24
Procedures for Return of Units Out of
and Conditions • 77
Returning to the Main Menu • 39, 43
RS-232 • 59
Modem Connection • 60
Null Modem Connection (Hardware
Handshaking) • 60
Null Modem Connection (No Hardware
Handshaking) • 61
RS-232 Configuration/Debug Port • 57
RS-422 • 61
RS-485 • 62
RS-485 and RS-422 Tip • 62
S
TCA Message Data • 28
TCA Port Parameters (CASPort) • 26
The Configuration/Debug Menu • 31
Time Limit for Bringing Suit • 81
Transferring Module Configuration to the
Processor • 36
Troubleshooting • 45
U
Un-repairable Units • 78
User Data Objects • 27
Using the Configuration/Debug Port • 33
V
Viewing Block Transfer Statistics • 34
Viewing Data in ASCII (Text) Format • 38, 43
Viewing Data in Decimal Format • 43
Viewing Data in Floating Point Format • 43
Viewing Data in Hexadecimal Format • 38,
43
Viewing Module Configuration • 35
Viewing Port Communication Status • 36
Viewing Port Configuration • 36
Viewing Register Pages • 42
Viewing the Next 100 Registers of Data • 43
Viewing the Previous 100 Registers of Data •
43
Viewing Version Information • 35
W
Warm Boot • 55
Warm Booting the Module • 35
Warnings • 2
What Is Covered By This Warranty • 79
What Is Not Covered By This Warranty • 80
Write Block • 53
Write Configuration • 54
Y
Your Feedback Please • 3
Setting Jumpers • 11
Skipping 500 Registers of Data • 43
Slave Driver • 56
Start Here • 7, 9
Starting the Data Analyzer • 38
Status • 68
Page 86 of 86 ProSoft Technology, Inc.
December 26, 2007
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.