PROFLO PFTP1500, PFTP2500, PFTPR500 Installation Manual

0 (0)
PROFLO PFTP1500, PFTP2500, PFTPR500 Installation Manual

PFTPR500 PFTP1500 PFTP2500

Trap Primer Valve

Installation Instructions

Installation Instructions

A1-1/8” open end wrench should be used to install the PFTP Series of trap seal primers to the line by using the flats on the top of the trap seal primer. Water lines must be flushed before installing the PFTP Series of trap seal primers. The trap seal primers should be cycled at least six times to ensure optimum performance. Ensure that all flux and other debris is removed. Use only teflon tape around threads. Do not use pipe dope. Do not solder fittings directly onto the inlet or outlet of the primer. Failure to follow these instructions will negatively affect performance of the product. The primers have a unique design which allows the primer to be taken apart and cleaned before re-assembly. Do this in the event of excess water discharge. Do not install the trap seal primers closer than forty feet apart when using the same potable water supply line. The device should be located within 20 feet of the valve or faucet for optimal discharge. Trap seal primers should be mounted one foot above the finished floor for every twenty feet of floor drain trap make-up water line. For easy assess to the trap seal primer, install a union connection above it. Install a line shut off valve upstream of the trap seal primer in order to shut off the water supply when performing maintenance on the trap seal primer.

Inspection Instructions

After installing and pre-cycling the trap seal primer a minimum of five (5) times, use any of the four holes to view water discharge from the orifice. Alight can be placed opposite the observed view hole to improve clarity in this inspection.

Maintenance Instructions

In order to replace the filter screen, remove the trap seal primer by using an open end wrench on the top

set of flats. Grasp the top of the filter screen with fingers, squeeze and remove filter. Insert the new filter screen by squeezing and pushing it firmly down into the top of the trap seal primer. Re-install the trap seal primer using the top set of flats. In regions that experience heavy residual deposits such as calcium in the water supply, the PFTP Series of trap seal primers can be field refurbished by removing the bottom end of the primer and replacing the cartridge.

Warranty and Codes

This PROFLO product carries a 1-year limited warranty.

The wetted surface contacted by consumable water contains less than one quarter of one percent (0.25%) of lead by weight.

Line Shut Off Valve

Filter Screen

Avoid direct installation to prevent foreign material from entering directly into the primer.

Union Connection

Trap Primer Valve

Air Gap Fitting

Four View Holes

Trap Primer Valve should be mounted

 

 

12 inches (305 mm) above the finished

Water Trap

Sewer Gas

floor for every 20 feet or primer line.

 

 

 

 

CALIFORNIA PROPOSITION 65 WARNING

 

 

 

 

WARNING: This product can expose you to

 

 

 

 

chemicals including Pb, Formaldehyde, Carbon Black,

 

 

 

 

 

 

 

 

TNT, Acrylonitrile, Butadiene which are known to the

 

 

 

 

 

 

 

 

State of California to cause cancer, and birth defects or

 

Assembled in U.S.A.

 

other reproductive harm. For more information go to

 

 

 

 

www. P65Warnings.ca.gov.