DuraChill® Portable Chiller Specifications
•Choice of Turbine or Positive Displacement pump
•Intuitive touch screen display with a choice of 5 operating languages
•Home screen simultaneously displays set temperature, actual temperature, fluid pressure, fluid level, air filter status and timer
•Self-changing air filter system eliminates preventative maintenance by automatically changing the filter media at user-definable intervals.
•Continuous fluid level monitoring protects pump and prevents freezing
•Patented Whispercool® noise reduction system reduces operating noise levels to the almost imperceptible levels while maintaining optimal cooling performance
•Reduced global warming potential through a highly optimized refrigeration system design that greatly reduces the amount of refrigerant gas needed in the chiller and allows for migration to natural refrigerants that have little or no global warming potential
•Components are recyclable and meet or exceed global environmental standards
•UV Light Biological Growth Inhibitor System eliminates the need for algaecides
•Patent-pending self-diagnostic system compares the chiller's functionality to its operating state the day it was built to minimize operating downtime and unnecessary service calls
•Front-fill reservoir access
•Externally accessible adjustable pressure regulator valve
|
|
CA02 |
|
CA03 |
|
CA05 |
|
CA10 |
|
|
|
|
|
|
|
|
|
Cooling Capacity @ 20°C |
60Hz |
0.85 kW |
|
1.4 kW |
|
1.74 kW |
|
2.9 kW |
50HZ |
0.7 kW |
|
1.28 kW |
|
1.84 kW |
|
2.65 kW |
|
|
|
|
|
|||||
Cooling Capacity @ 10°C |
60Hz |
0.6 kW |
|
0.99 kW |
|
1.29 kW |
|
1.93 kW |
50HZ |
0.5 kW |
|
0.94 kW |
|
1.29 kW |
|
1.9 kW |
|
|
|
|
|
|||||
Cooling Capacity @ 0°C |
60Hz |
0.4 kW |
|
0.53 kW |
|
0.77 kW |
|
1.0 kW |
50HZ |
0.3 kW |
|
0.49 kW |
|
0.77 kW |
|
1.0 kW |
|
|
|
|
|
|||||
Fluid Temperature Range |
|
|
|
-10 to 70°C / 14 to 158°F |
|
|||
|
|
|
|
|
|
|
|
|
Temperature Stability |
|
|
|
|
|
±0.1°C |
|
|
|
|
|
|
|
|
|
|
|
Displayable Temperature Units |
|
|
|
|
|
°C or °F |
|
|
|
|
|
|
|
|
|
|
|
Displayable Pressure Units |
|
|
|
|
|
PSI or kPa |
|
|
|
|
|
|
|
|
|
||
Pump Inlet and Outlet |
|
|
|
|
½ inch female NPT |
|
||
|
|
|
||||||
Connectivity |
|
RS-232, USB Serial Port Emulation, USB TMC, Dry Contact On/Off/Status |
||||||
|
|
|
|
|
|
|||
Selectable Operating Languages |
|
|
|
English, Spanish, French, German, Mandarin |
|
|||
|
|
|
|
|
|
|
|
|
Self-Changing Air Filter |
|
|
|
|
|
Yes |
|
|
|
|
|
|
|
|
|
|
|
UV Biological Growth Inhibitor |
|
|
|
|
|
Yes |
|
|
|
|
|
|
|
|
|||
Optional Remote Temperature Probe |
|
|
|
Remote monitoring / Remote control |
|
|||
|
|
|
|
|
|
|
|
|
Ambient Air Temperature Tracking |
|
|
|
|
|
Yes |
|
|
|
|
|
|
|
|
|||
Pump Pressure Range |
60Hz |
|
|
20 to 90 psi / 138 to 689 kPa |
|
|||
(Turbine pump) |
50HZ |
|
|
20 to 75 psi / 138 to 621 kPa |
|
|||
Pump Pressure Range |
60Hz |
|
45 to 100 psi / 310 to 689 kPa |
|
20 to 100 psi / 138 to 689 kPa |
|||
(Positive Displacement pump) |
50HZ |
|
20 to 83 psi / 138 to 572 kPa |
|
20 to 83 psi / 138 to 572 kPa |
|||
Maximum Pump Flow Rate |
60Hz |
|
|
3.5 gpm / 13.2 lpm |
|
|
|
3.5 gpm / 13.2 lpm |
(Turbine pump) |
50HZ |
|
|
2.2 gpm / 8.3 lpm |
|
|
|
2.9 gpm / 11 lpm |
Maximum Pump Flow Rate |
60Hz |
|
|
2.6 gpm / 9.8 lpm |
|
|
|
3.5 gpm / 13.2 lpm |
(Positive Displacement Pump) |
50HZ |
|
|
2.0 gpm / 7.6 lpm |
|
|
|
2.9 gpm / 11 lpm |
Power Requirements |
60Hz |
120V, 60Hz, 13.7A |
|
120V, 60Hz, 16.3A |
|
120V, 60Hz, 17.4A |
|
230V, 60Hz, 13.5A |
(With Turbine pump) |
50Hz |
240V, 50Hz 8.9A |
|
240V, 50Hz 9.0A |
|
240V, 50Hz 9.2A |
|
240V, 50Hz 13.5A |
Power Requirements |
60Hz |
120V, 60Hz, 13.6A |
|
120V, 60Hz, 16.2A |
|
120V, 60Hz, 17.3A |
|
230V, 60Hz, 13.4A |
(With Positive Displacement pump) |
50Hz |
240V, 50Hz 8.2A |
|
240V, 50Hz 8.3A |
|
240V, 50Hz 8.5A |
|
240V, 50Hz 12.0A |
Part Number |
60Hz |
CA02A1T1-41AA1N |
|
CA03A1T1-41AA1N |
|
CA05A1T1-41AA1N |
|
CA10A3T1-41AA1N |
(With Turbine pump) |
50Hz |
CA02A2T1-41AA1N |
|
CA03A2T1-41AA1N |
|
CA05A2T1-41AA1N |
|
CA10A2T1-41AA1N |
Part Number |
60Hz |
CA02A1P1-41AA1N |
|
CA03A1P1-41AA1N |
|
CA05A1P1-41AA1N |
|
CA10A3P2-41AA1N |
(With Positive Displacement pump) |
50Hz |
CA02A2P1-41AA1N |
|
CA03A2P1-41AA1N |
|
CA05A2P1-41AA1N |
|
CA10A2P2-41AA1N |
Shipping Weight |
|
169 lbs / 76.7 kg |
|
169 lbs / 76.7 kg |
|
172 lbs / 78.1 kg |
|
177lbs / 80.3 kg |
|
|
|
|
|
|
|
|
|
Shipping Dimensions |
|
|
|
33 x 22 x 33 in / 84 x 56 x 84 cm |
|
Note: Specifications are subject to change
PolyScience • 6600 W. Touhy Ave. • Niles, IL 60714 • www.PolyScience.com
Toll-Free +1.800.229.7569 • Phone +1.847.647.0611 • sales@PolyScience.com
090419