In chapter 2.1 of this Guide:General aspects,section 2.1:Main ballast
functions,the main functions of ballasts hav e been described.The term
‘ballasts’ is generally reserved for current limiting devices,including
resistors,choke coils and (autoleak) transformers.Other pieces of
auxiliary equipment are compensating capacitors,filter coils and
starters or ignitors.Some systems use an additional series capacitor
for stabilisation.
With the components summed up,all control functions which are
necessary to operate standard fluorescent lamps can be carried out.
Special arrangements,including sequence start,constant wattage or
dimming circuits will not be described in this Guide,as such circuits
are more and more being replaced by the modern high-frequency
(HF)systems.
Stabilisation
In section 3.2:Stabilisation,the need for current stabilisation in
fluorescent lamps has been described,resulting in the following two
formulae:
I
= (V
lamp
and:P
whereI
From these formulae it can be concluded that the power of the lamp
(and therefore the light output) is influenced by:
- the lamp voltage V
the operating temperature (see section 5.3.12:Ambient and operating
temperatures) and on the lamp current,according to the negative
lamp characteristic (see section 3.2:Stabilisation).
- the lamp current I
section 5.3.13:Effects of mains voltage fluctuations),the lamp voltage
and the linearity of the ballast impedance.
In order to av oid undesirable variations in light output as a consequence
of mains voltage fluctuations,the lamp voltage must be not more
than approx.half the value of the mains voltage (100 to 130 V) and the
impedance should be as linear as possible.
lamp
V
V
Z
P
α
lamp
mains
lamp
ballast
lamp
lamp
= V
- V
mains
lamp.Ilamp.αlamp
= the current through the lamp
= the mains voltage
= the voltage across the lamp
= the impedance of the ballast
= the power of the lamp
= a constant called lamp factor
lamp
lamp
) / Z
lamp
,which in turn is highly dependent on
,which is dependent on the mains voltage (see
ballast
13
Ignition and re-ignition
In chapter 3:Lamps,section 3.3:Ignition,the need for ignition of a
fluorescent lamp has been described.
107
5
1.3 Ignition and re-ignition
In the case of electromagnetic control gear,a combination of preheating
and a high ignition peak is obtained by using a normal choke ballast
and a preheat starter or an electronic ignitor.
Energy is supplied to the discharge in the form of electrons.The lamp
current,just like the mains voltage,is sinusoidal,with a frequency of
50 or 60 Hz.If the energy flow is zero (at lamp current reversal) the
lamp stops burning and in theory would have to be re-ignited.
This could be done by supplying additional energy to the electrodes
via a higher lamp voltage,the way it is done when initially starting the
lamp.But from the moment the lamp has reached its stationary
condition,the lamp voltage is constant.
And yet,in practice the lamp does not extinguish at current reversal.
Why not?
The phase shift introduced by the inductive element of the ballast
ensures that the mains voltage is not zero at that moment.Because of
the inductive properties of choke coil ballasts a phase shift ϕ occurs
between the mains voltage and the lamp current (see Fig.102).So,at
the moment of current rev ersal the lamp voltage would be equal to the
mains voltage,since the voltage over the ballast is nil.The difference
(gap) between the mains voltage and the average lamp voltage as a
consequence of the phase shift ensures proper re-ignition of the lamp
at the moment the current passes the point of reversal (zero-point A
in figure).
Fig. 102. Phase shift between supply voltage
and lamp current (and lamp voltage) in a
discharge lamp with an inductive ballast. In
the case shown, the supply voltage is
sufficiently high for re-igniting the lamp after
every cur rent reversal.
14
V, A
gap
V
m
I
l
V
l
ϕ
A
t
Types of ballasts
1 Resistor ballasts
Current limitation by means of resistor ballasts is a very uneconomic
form of current limitation,because in the resistor electrical energy is
dissipated in the form of heat.Nevertheless,until the advent of
electronic circuitry,use of a series resistor was the only wa y of stabilising
fluorescent lamps operated on DC,for example the ‘TL’R lamp (see
Fig.103).For stable operation on a resistor ballast,it is necessary that
the supply voltage be at least twice the lamp voltage under operating
conditions.This means that 50 per cent of the power will be
dissipated by the ballast.A considerable improvement in efficiency
can,however,be achieved by using a resistor with a very pronounced
positive temperature characteristic (an ordinary or specially
constructed incandescent lamp serves well for this purpose).
A temperature-dependent resistor compensates for variations in the
lamp current resulting from variations in the mains voltage,which means
108
5
1.4 Types of ballasts
that the no-load voltage need be no more than 25 to 30 per cent
higher than the lamp voltage.This is also the proportion of the power
dissipated by the ballast compared to the total circuit power.
‘TL’ R
+
Fig. 103. Schematic diagram of a
fluorescent lamp operated on a resistor
ballast in a DC circuit.
-
2 Capacitor ballasts
A capacitor used as a ballast causes only very little losses,but cannot
be used by itself,as this would give rise to very high peaks in the lamp
current wave form at each half cycle.Only at very high frequencies
can a capacitor serve satisfactorily as a ballast.
3 Inductive ballasts or chokes
Choke coils are frequently used as current limiting devices in
gas-discharge lamp circuits (see Fig.104).They cause somewhat higher
losses than a capacitor, but produce far less distortion in the lamp
current at 50 Hz.Moreover,in combination with a switch starter,they
can be made to produce the high voltage pulse needed to ignite the
lamp.
In practice,a choke ballast consists of a large number of windings of
copper wire on a laminated iron core.It operates on the self-inductance
principle.The impedance of such a ballast must be chosen in
accordance with the mains supply voltage and frequency, the lamp type
and the voltage of the lamp,to ensure that the lamp current is at the
correct value.In other words:each type of lamp requires for each supply
voltage its own choke as a ballast with a specific impedance setting.
Heat losses,occurring through the ohmic resistance of the windings
and hysteresis in the core,much depend upon the mechanical
construction of the ballast and the diameter of the copper wire.
The right ballast for a given lamp and supply voltage should be chosen
by consulting documentation and/or ballast markings.
The Philips standard range of ballasts is for supply voltages of
220/230/240 V and for frequencies of 50/60 Hz.
Fig. 104. Schematic diagram of a
fluorescent lamp operated on a choke
ballast in an AC starter circuit.
+
Vm
0
-
109
I
b
B
+-+-
V
l
La
S
I
l
5
1.4 Types of ballasts
The most important value for stabilisation is the ballast impedance.It
is expressed as voltage/current ratio in ohm (Ω) and defined for a
certain mains voltage,mains frequency and calibration current (normally
the nominal lamp current).
Chokes can be used for virtually all discharge lamps,provided that
one condition is fulfilled:the mains voltage should be about twice the
arc voltage of the lamp.If the mains voltage is too low,another type
of circuit should be used,like the autoleak or constant-wattage cir cuits.
The advantages of a choke coil are:
- the wattage losses are low in comparison to those of a resistor,
- it is a simple circuit:the ballast is connected in series with the lamp.
Disadvantages of a choke coil are:
- the current in a lamp with choke circuit exhibits a phase shift with
respect to the applied voltage,the current lagging behind the voltage
(see also section 5.3.4:Power factor correction).
- a high starting current:in inductive circuits the starting current is
about 1.5 times the rated current.
- sensitivity to mains voltage fluctuations:variations in the mains
voltage cause variations in the current through the lamp.
15
Ballast specification and marking
There are two ways of selecting the right ballast for a certain lamp
and/or to compare various ballasts:
1) the ballast marking,
2) the manufacturer’s documentation.
As all ballasts have to comply with the norm IEC 920/921 some data
has to be marked on the ballast and other data can be mentioned in
the documentation.
On the ballast can be found:
- marks of origin,such as the manufacturer’s name or trade mark,
model or reference n umber,country of origin,production date code,
- rated supply voltage and frequency, nominal ballast current(s),
- type(s) of lamp with rated wattage,
- type(s) of ignitor with wiring diagram and peak voltage if this
exceeds 1500 V,
- t
and ∆t (see section 5.1.6),
w
- max.cross-section of mains or lamp cable;e.g.4means 4 mm2,
- symbols of the officially recognised certification institutes,such as
VDE,SEMKO,SEV, KEMA, if applicable; CE marking for safety,
- in case of an independent ballast:the symbol ; an independent
ballast is a ballast which is intended to be mounted separately outside
a luminaire and without any additional enclosure,
- a symbol like top if there are mounting restrictions,
- F-marking if the ballast fulfils the IEC F-requirements;that means
it is suitable to be mounted directly on normally flammable surfaces,
- TS, P-marking or if the ballast is thermally protected
(* = thermo-switch temperature in degrees Celsius),
- indication of terminals:L for single phase,N for neutral,for
protective earth (PE),for functional earth,
110
5
1.5 Ballast specification and marking
- rated voltage,capacitance and tolerance of separate series capacitor.
In the documentation can be found:
- weight,
- overall and mounting dimensions,
- power factor (λ,P.F.or cos ϕ),
- compensating capacitor value and voltage for λ = 0.85 or 0.9,
- mains current nominal and during running-up,both with and
without power factor correction,
- watt losses (normally in cold condition),
- description of version,e.g.open impregnated,‘plastic’ encapsulated,
potted or compound filled.
This information suffices to find the right ballast for a certain
application.Additional information can be obtained on request or can
be found in special application notes.Philips ballasts are designed for
use with IEC standardised fluorescent lamps.
16
Maximum coil temperature twand ∆T
A ballast,like most electrical components,generates heat due to its
ohmic resistance and magnetic losses.Each component has a
maximum temperature which may not be exceeded.For ballasts it is
the temperature of the choke coil during operation that is important.
The maximum permissible coil temperature t
ballast.Coil insulating material,in combination with lacquer,
encapsulation material etc.,is so chosen that below that temperature
the life specified for the ballast is achieved.A t
nowadays with a coil insulating class F (150 ºC) or class H (180 ºC).
Under standard conditions,an average ballast life of ten years may be
expected in the case of continuous operation at a coil temperature of
t
ºC.As a rule of thumb,a 10 ºC temperature rise above the twvalue
w
will halve its expected life (see Fig.105). If,for instance,the operating
temperature is 20 ºC above the t
value,one may expect a ballast life
w
of 2.5 years of continuous operation.If no t
ballast,a maximum of 105 ºC is assumed for the coil temperature.
As the ballast normally does not function continuously, the actual life
of the ballast can be very long.It also takes some hours before the
thermal equilibrium is reached in the ballast,which again increases the
practical ballast lifetime.
To verify the t
marking,accelerated lifetime tests are done at ballast
w
temperatures above 200 ºC for 30 or 60 days.
is marked on the
w
value of 130 ºC is usual
w
value is marked on the
w
Fig. 105.The nominal life of choke coils
in relation to the permitted rated
maximum operating temperature of a
ballast winding t
, dependent on
w
insulation material:
a) class A: t
b) class E: t
c) class F or H: t
105 ºC,
w
120 ºC,
w
130 ºC.
w
temp. (°C)
250
200
150
100
111
(c)
(b)
(a)
0,1
1,0
10
t (years)
5
1.6 Maximum coil temperature twand ∆T
Another value marked on the ballast is the coil temperature rise ∆t.
This is the difference between the absolute coil temperature and the
ambient temperature in standard conditions and is measured by a
method specified in IEC Publ.920 (EN 60920).Common values for ∆t
are from 50 to 70 degrees in steps of 5 degrees.
The coil temperature rise is measured by measuring the ohmic
resistance of the cold and warm copper coil and using the formula:
= ambient temperature at measuring R2in Celsius
= initial ambient temperature at measuring R1in Celsius
= calculated warm coil temperature in Celsius
- t2in Kelvin
c
The value 234.5 applies to copper wire;in case of aluminium
wire,the value 229 should be used.
So a ballast marked with t
130 and ∆t 70,will have the specified 10
w
years average life in continuous operation at standard conditions at an
ambient temperature of 130 - 70 = 60 ºC.When the ambient
temperature around the ballast is higher,a shorter ballast life has to
be accepted or sufficient air circulation or cooling has to be applied.
The so-called ambient temperature mentioned in this chapter is not
the room or outside temperature,but the temperature of the microenvironment of the ballast.Built into a luminaire or ballast box the air
temperature around the ballast is higher than the outside ambient
temperature.This higher temperature has to be added to the coil
temperature rise ∆t to find the absolute coil temperature:t
= t2+ ∆t.
c
Additionally, a third temperature figure can be mentioned on the ballast:
the ballast temperature rise in abnormal conditions,again measured
according to specifications like EN 60920.In short: it is the winding
temperature rise at 110 per cent mains voltage when the glow-switch
starter,belonging to the system,is short-circuited.
The marking of the three temperature markings should be :
Example:∆t 70 / 140 / t
17
Watt losses
∆t ** / *** / t
*** with * = figure
w
130.
w
Ballast losses normally are published as ‘cold’ values, meaning that the
ballast is not energised or only very shortly before and the ballast
winding is at ambient temperature (25 ºC).In practice the ballast will
reach more or less the marked ∆t value and then the copper resistance
is approx.25 per cent higher than in the ‘cold’ situation.Therefore the
‘warm’ losses in practice will be 10 - 30 per cent higher than the
published values.
112
5
1.7 Watt losses
As in some applications the power consumption is of prime importance,
there are low-loss ballasts for the major lamp types ‘TL’D 18,36 and
58 W ( BTA**L31LW).The 18 and 36 W LW ballasts are bigger than the
standard types,resulting in lower ballast temperatures and 25 to
30 per cent less ballast watt losses.Due to practical restrictions the
BTA 58L31LW type could not be made bigger.The 15 per cent lower
ballast losses are the result of a better iron lamination quality,while
the ballast temperatures are only slightly lower than those of the
standard types.
STARTERS
52
Main starter function
21
Fluorescent lamps do not ignite at mains voltage.To ignite the lamps, a
starter is applied to preheat the lamp electrodes and to give a peak
voltage high enough to initiate the discharge.
So in fact there is only one basic function for a starter:to deliver the
ignition voltage to start the discharge in a fluorescent lamp in a proper
way.After ignition the starter has to stop producing ignition peaks.This
can be obtained by sensing the lamp voltage or lamp current and/or
by a timer function.
Starter types
22
There are two types of fluorescent lamp starters:
1 Glow-switch starters
The glow-switch starter consists of one or two bimetallic electrodes
enclosed in a glass container filled with noble gas.The starter is
connected parallel across the lamp in such a way that the preheat
current can run through the lamp electr odes when the starter is closed
(Fig.106).At the moment of switching on the mains voltage, the total
mains voltage is across the open glow-switch starter.This results in a
glow discharge starting between the bimetallic electrodes of the
starter.The glow discharge causes a temperature increase in these
bimetallic electrodes,resulting in the closure of the electrodes of the
starter.During this closure the lamp electrodes are preheated by the
short-circuit current of the ballast.After closure the temperature of
the starter electrodes decreases and the starter re-opens.At the
moment of re-opening,the current through the ballast is interrupted,
causing a peak voltage over the lamp electrodes high enough for lamp
ignition.This peak voltage depends on the inductance of the choke,
the level of the short- circuit current and the speed of the opening of
the glow-switch electrodes.In formula:
Peak voltage:V
The minimum specified peak voltage depends on the type and is between
800 and 900 V.
If the lamp electrodes are not yet hot enough or the peak voltage is
not high enough,the glow-switch starter will resume the whole
peak
= L dI/dt
113
5
Fig. 106. Working principle of a glow-
discharge starter circuit.
2.2 Starter types
starting process again until the lamp ignites.If the lamp will not ignite
(end of life) the starter will continue producing peaks (flickering) until
the mains voltage is switched off or until the electrodes of the glowswitch starter stick together.In the latter case the short-circuit
current is continuously running through the lamp electrodes,which
can be seen at the glowing lamp ends.
1. The heat from the dischar ge in the
starter bulb causes the bimetallic
electrodes to bend together.
2.When the bimetallic electrodes make
contact, a current starts to flow through
the circuit, sufficient for preheating the
electrodes of the fluorescent lamp.
3. The bimetallic electrodes cool down
and open again, causing a voltage peak,
which ignites the fluorescent lamp.
0
0
0
Once the lamp is properly ignited,the lamp voltage is too low for a
glow discharge between the starter electrodes.So these electrodes
stay ‘cool’ and in open position.
A capacitor across the starter electrodes prevents radio-interference
of the lamp.
There are five types of glo w-s witch starters,specified for a certain mains
voltage and/or lamp wattage ( S2-10-11-12-16).There are also r esettable
glow-switch starters:SiS2,Si S3 and SiS10.These starters switch off
after a certaintime in case the lamps do not ignite and have to be
reset manually by a push button.Switching the mains supply does not
reactivate a switched-off resettable starter.
114
5
2.2 Starter types
2 Electronic starters
In principle the electronic starter or ignitor is working in the same
manner as the glow-switch starter. But now the switching does not
come from bi-metallic electrodes,but from a triac.
The electronic circuit in the starter gives a well-defined preheat time
(1.7 sec) for the lamp electrodes and,after the preheat, a well-defined
peak voltage,which ensures optimum lamp ignition.The heart of the
electronic starter is a customized integrated circuit,containing the
intelligence of the product.It makes the starter switch off after seven
unsuccessful ignition attempts,so it is called ‘flicker free’.
The electronic starter also contains an over-heating detection by
means of a PTC resistor, to switch off in case the starter becomes
too hot (e.g.with a short-circuited ballast).This second stop function
resets after approx.4 minutes.
The electronic starter extends the lamp lifetime up to 25 per cent on
account of the well-defined preheat time.The exact digital timing makes
the electronic starter independent of mains voltage fluctuations.
In the Philips programme there are two types of electronic starters:
one in the canister of the glow-switch starters (two-pin types S2-E and
S10-E Perform version),and one in a plastic housing (four-pin type ES08).
SYSTEMS
23
Lifetime
The lifetime of fluorescent lamp starters is expressed in the number
of switches.
At present the glow-switch starters have a lifetime of 10 000 switches
or more,while the electronic starters have a lif etime of 100 000 switches
or more.
53
31
Components
A customer primarily needs a solution to his lighting requirements.
Basically,he needs two things to obtain an installation which completely
fulfils his specifications:a design and components.To make sure that
the installation works properly under all circumstances,the right
components must be chosen and selected in combination with each
other.
In principle the following components are required in a lighting
installation:
- lamps,
- lampholders,
- luminaires,
- gear (ballasts,starters),
- compensating capacitors,
- cabling,
- fusing and switching devices,
- filter coils (if necessary),
- dimming equipment (if possible and required).
115
5
3.1 Components
Information about lamps can be found in the lamp documentation,
where also the type of lampholder or lamp cap is mentioned.Be sure
to use the appropriate lampholder, as there are many different types.
Lamp types with different wattage are in principle not interchangeable
in a certain circuit,even though they may have the same lamp cap and
do fit in the same lampholder.
In some lamp types the glow-switch starter is incorporated in the
lamp base (2-pin version PL).In the SL family the total electric circuit
is incorporated with the lamp in the outer shell (see Fig.107).
Fig. 107.The circuit of an SL lamp
consists of the following components:
1. Discharge tube,
2. Starter,
3. Capacitor,
4. Ballast,
5. Ther mal protector.
32
4
2
3
1
L
mains
supply
N
5
In the luminaire documentation,information can be found on which
lamp types can be used.When installing other than specified types,
electrical,thermal or lighting problems will arise.In the luminaire
documentation it can also be found if the gear is incorporated in the
luminaire and what the cable entries and connections are.
In the gear documentation,information can be found about the
electrical terminals and the electrical diagrams.Also the value and the
voltage range of capacitors is mentioned here.
The remaining system-related components and subjects mentioned
above will be described in the following sections.
Capacitors
Two types of capacitors are possible in fluorescent lamp circuits.One
type is the parallel compensating capacitor for power factor
improvement,connected across the mains.The second type is the series
capacitor which also determines the lamp current.
Series capacitors are used in capacitive or duo circuits.
In installations with fluorescent lamps of more than 25 W, capacitors
are necessary for power factor correction,as the power factor of an
inductively stabilised circuit is only approx.0.5. Power factor
compensating capacitors are connected across the mains supply voltage
(parallel compensation) between phase and neutral (220/240 V).
In the relevant ballast documentation figures can be found for the
capacitor value in microfarad (µF) for a certain combination of lamp
and supply voltage to achieve a power factor of ≥ 0.9.
Every user can in fact create his own solution for obtaining the necessary
capacitance.
116
5
3.2 Capacitors
To do things well,some aspects have to be considered:
- First of all,capacitors for discharge lamp circuits have to fulfil the
requirements as specified in IEC publications 1048 and 1049.The use
of PCB (chlorinated biphenyl) is forbidden.
- It is recommended that capacitors which have some approval marks,
such as VDE,KEMA,DEMKO or ENEC be used.
- Normally every lamp circuit is compensated by its own capacitance.
Only in some special cases group or central compensation for more
lamp circuits can be a better solution.
- In case of failure of the parallel capacitor (open or short-circuited)
the lamp behaviour is not affected.Regular control of the mains
currents and/or power factor (λ or cos ϕ) is advisable.
- In case of failure of the series capacitor the lamp behaviour is
immediately affected.This type of capacitor must create an open cir cuit
in case of failure,so that the lamp will be extinguished.
- The lifetime of capacitors depends on the capacitor voltage and
capacitor case temperature.Therefore capacitors with the correct
voltage marking (parallel 250 V with a maximum capacitance
tolerance of +/- 10% or series 450 V with a maximum capacitance
tolerance of +/- 4 %) and within the specified temperature range
(normally - 25 ºC to + 85 or 100 ºC) should be used.
Used within the specifications,capacitors with the VDE marking will
have a lifetime equal to that of ballasts:30 000 hours or 10 years.
- If a specified parallel capacitance value occasionally is not available,
the next higher value can be used,provided that the value is not more
than 20 per cent above specification.
Two general types of capacitors are currently in use:the wet and the
dry type.
Wet capacitors available today contain a non-PCB oil and are equipped
with internal interrupters to prevent can rupture and resultant oil
leakage in the event of failure.So a clearance of at least 15 mm above
the terminals has to be provided to allow f or expansion of the capacitor.
In case of failure,these capacitors will result in an appar ent open circuit,
which means the mains current drawn by the circuit approximately
doubles in case of a parallel capacitor.This can cause a fuse to blow,a
circuit breaker to open,but will have no further detrimental effect.
Used as a series capacitor, the open circuit of the failing capacitor will
extinguish the lamp.
Dry,metallised-film capacitors are relativel y ne w to the lighting industry
and are not yet available in all ratings for all applications.However,
they are rapidly gaining popularity because of their compact size and
extreme ease of installation and are,therefore,widely used nowadays.
During its lifetime this type of capacitor gradually loses its ca pacitance,
resulting in a gradually increasing mains current when used as a
parallel capacitor. In the end the capacitor acts like an open circuit.
For the series capacitor a capacitance loss of only 5% during its
lifetime can be accepted,so the dry capacitor is not recommended
for series applications.
Dry capacitors are more sensitive to voltage peaks than w et ca pacitors.
In critical applications (mains supply containing peaks,frequent
switching,high level of humidity or condensation) the wet capacitor is
advisable.
117
5
33
3.2 Capacitors
Capacitors for lighting applications must have a discharge resistor
connected across the terminals to ensure that the capacitor voltage is
less than 50 V within 1 minute after switching off the mains power. In
special cases the voltage level must be 35 V within 1 second,see
IEC 598-8.2.7.
Filter coils
In some countries,including Belgium,the Netherlands and France, the
electric distribution network is used for transmitting messages under
responsibility of the local energy supply authority.
Signals are sent over the electricity supply network for a number of
purposes:to switch road lighting,to call up fire brigades and the
police,to switch night-tariff kWh-meters,and so on.It is important,
therefore,that this signalling system is not disturbed, which may occur
when parallel power factor correction capacitors for lamp circuits are
employed.Capacitors present a low reactance to the 200-1600 Hz
signals employed for signalling,with the result that these are in danger
of being short-circuited in a capacitive circuit.To avoid this,a coil must
be connected in series with the capacitor connected parallel to the
mains.This filter coil, as it is termed, presents a reactance that
increases with rising signal frequency.The coil reactance is therefore
chosen such as to balance out the reactance of the capacitor at 200 Hz
(the resonance frequency, see Fig. 108).
For currents with a frequency of 50 Hz the circuit is predominantly
capacitive,which is necessary for power factor correction.Above 200 Hz
the circuit becomes predominantly inductive,which is necessary for
the blocking of audio-frequency signals.At 200 Hz the impedance is
only formed by the ohmic resistance,mainly of the filter coil.
As can be seen from the graph,the filter coil is effective for audio signals
of 300 Hz and higher, because then the impedance of the coil/capacitor
combination is higher than the impedance of the sole capacitor. Filter
coils should not be used when the audio signals are 300 HZ or lower.
Fig. 108. Impedance of a filter coil, a
capacitor and a coil/capacitor
combination as a function of frequency.
impedance (Z)
3
10
8
6
4
2
2
10
8
6
4
2
1
10
1
10
118
impedance of filtercoil
capacitiveinductive
2
4
2
6
8
10
Z = ωL
2
4
impedance of coil
and capacitor
Z =
ωL -1
___
ωC
|
impedance of capacitor
Z = 1
___
ωC
3
6
8
2
10
|
6
4
frequency(Hz)
4
8
10
5
3.3 Filter coils
There are other advantages to be gained from employing filter coils.
The parallel capacitor can cause troublesome switching phenomena
to occur, which can give rise to very large current surges.Although
these surges are of only very short duration (a few milliseconds),they
are nevertheless sufficient to cause switching relays to stick or circuit
breakers to switch off.The filter coil serves to prevent this problem
by damping the very short,high amplitude pulses in the current.
The type of filter coil needed depends on the capacitance of the
capacitor employed.So,in fact every capacitor needs its own filter coil.
But in some cases it is possible to group the capacitors and match
them with the corresponding filter coil.For example: two capacitors
of 4 µF parallel can be connected in series with one filter coil for 8 µF
(see Fig.109).
Also central filter coil systems exist where a filter system in the supply
system is blocking the applied signalling frequencies.
Although the voltage across the filter coils is rather low (approx.14 to
20 V),the filter coils have to be regarded as ballasts,as they are directly
connected to the mains.They also cause some additional watt losses.
The amount of third and fifth harmonics in the mains current will rise
in cases where the mains supply voltage is disturbed with third or fifth
harmonics,when applying a filter coil.The total impedance for the
combination of capacitor and filter coil is lower than the impedance
of the sole capacitor for these frequencies (see section 5.3.9:Harmonic
distortion and Fig.108).
Fig. 109. Different ways of grouping
capacitors to match them with the
corresponding filter coil.
34
L
2 x 4 µF
capacitors
2 x 4 µF
coils
N
=
L
4 x 4 µF
capacitors
1 x 8 µF
filter coil
N
Power factor correction
Circuits with gas-discharge lamps are stabilised with inductive ballasts
and compensated for a good power factor with a parallel compensating
capacitor (mono-compensation,Fig.110).
Without the capacitor the inductive ballast causes a phase shift of the
current,which is lagging behind the applied voltage.
B
L
C
La
Fig. 110. Power factor correction with a
parallel compensating capacitor.
N
119
5
Fig. 111. Lamp current (Il), lamp voltage (Vl)
and mains voltage (V
m
3.4 Power factor correction
V
m
I
V
l
ϕ
).
This can be seen in Fig.111,which is showing the lamp current Il,the
lamp voltage V
the mains voltage V
(both in phase with each other) and the sinus form of
l
.
m
The power factor of the circuit can be calculated by dividing the total
wattage by the product of mains voltage and current.In formula:
Fig. 112. Example of a vector diagram
showing lamp voltage and lamp current in
phase.
P.F. = (W
+ Wb)/(Vm.Im) (1)
l
Without the parallel compensating capacitor the power factor of a
gas-discharge circuit is approx.0.5.
For the fundamentals of the voltages and current a so-called vector
diagram can be made (see Fig.112).Lamp voltage and lamp current
are in phase and the voltage across the ballast is leading 90 electrical
degrees to the current.The vectorial sum of lamp voltage and ballast
voltage gives the mains voltage.Now we see that cos ϕ = V
l/Vm
,which
is less accurate than (1).
In any case the energy supply authority has to deliver an apparent
power of V
to the system on which the distribution network must
m.Il
be based (cabling,transformers).
The energy meter only records the in-phase component V
m.Il
cos ϕ,
so the supply authority does not get paid for the so-called ‘blind’ part:
I
sin ϕ .Vm(Fig.113).
l
1.1 V
V
b
V
0.9 V
V
b
m
m
m
Il cos ϕ
V
m
Fig. 113. Uncompensated circuit with lamp
current and mains voltage out of phase.
ϕ
V
I
l
l
ϕ
V
I
I
l
sin j
l
l
For this reason,the supply authority demands compensation of the
phase shift.
Where in general the ‘unadjusted’ power factor is about 0.50,it has to
be compensated to a minimum of 0.85 or even 0.90.This is achieved
by adding a capacitor across the mains.In contrast to an inductive
120
5
3.4 Power factor correction
ballast,the capacitor current is leading 90 electrical degrees to the
capacitor voltage (which is the mains voltage).So the capacitor
current has the opposite direction of I
sin ϕ (see Fig.114).
l
Fig. 114. Compensated circuit.
I
cap
V
b
Il cos ϕ
ϕ
I
I
sin ϕ
l
l
V
m
V
l
Maximum compensation is achieved when the current through the
capacitor I
= Ilsin ϕ ;then the power factor is 1.This is purely
c
theoretical,as the vector diagram is only valid for the fundamentals of
the currents.Due to distortion in the lamp current (see section 5.3.9:
Harmonic distortion),the maximum practical power factor is
between 0.95 and 0.98.This explains the difference between power
factor and cos ϕ.
The power factor is the result of the quotient of the actual wattage
and the product of mains voltage and mains current,including the
harmonics,and can be calculated as follows:
Power factor (P.F.) = total wattage/mains voltage .mains current
The angle ϕ is the phase shift angle between mains voltage and mains
current and can be found and calculated by means of the vector
diagram.This is only valid for the fundamentals and does not take into
account the harmonics.
The same analogy is valid for the lamp:there is practically no phase
shift between lamp voltage and lamp current:both are zero at the
same time.So the phase angle α is zero and cos α = 1.
The product of lamp voltage and lamp current does not equal the
lamp wattage;the difference is called lamp factor:
Lamp factor = lamp wattage / lamp voltage .lamp current
and has a value between 0.8 and 0.9.For the same lamp type the lamp
factor is higher for higher wattages,identical to the lamp efficacy.
Typical capacitor values for this parallel compensation (also sometimes
called mono-compensation) for a 50 Hz mains are 4.5 µF for a 36 or
40 W fluorescent lamp and 6.5 µF for a 58 or 65 W lamp.
A second method for compensation is the so-called duo-circuit.This is
employed for pairs of lamps,as for example in two-lamp luminaires.Here
the capacitor is placed in series with one of the ballasts (see Fig.115).
121
5
3.4 Power factor correction
Fig. 115. Duo-circuit with the capacitor
placed in series with one of the ballasts.
L2
L1
‘TL’
1
0
C
‘TL’
SS
2
The series capacitor has an impedance which is twice the normal
ballast impedance,resulting in a power factor of approx.0.5 capacitive
for one branch.Together with the power factor of 0.5 inductive for the
other branch,the total power factor of the two branches is appro x.0.95.
With a normal 230 V supply,the voltage across the capacitor is about
400 V.To fulfil all relevant requirements,the tolerance on the capacitor
capacitance value has to be within +/- 4 %.The nominal value of the
capacitance is depending on the mains supply voltage,the applied
ballast impedance and the lamp wattage.Typical values are 3.4 µF for a
36 W and 5.3 µF for a 58 W lamp.
Compared with the mono-compensation the advantages of this way
of compensation are:
- only one capacitor is required for two lamps,instead of two,
- the capacitive branch is less sensitive to supply voltage deviations,as
it has a constant current characteristic,
- in case of actadis signals (see section 5.3.3:Filter coils) these signals
are not influenced,so no filter coil is needed.
Disadvantages of duo-compensation are:
- series capacitors are more expensive than parallel capacitors,
- the lamp power and so the light output from the capacitive branch
is slightly higher than that from the inductive branch.
In some countries,practically all multi-lamp luminaires have built-in
duo-circuits for each pair of lamps (also called a ‘dual-lamp’ or ‘lead-lag’
circuit).Mono-compensation, on the other hand,is generally left to
the installer, although there are also single-lamp luminaires available
with the compensation built in.
The capacitive circuit has a so-called ‘constant current characteristic’.
This can be explained by the non-linearity of the inductive ballast.
Suppose that the impedance of the ballast is 400 Ω,which varies,say
10 per cent when the ballast voltage changes 10 per cent (see Fig.116).
With the inductive ballast the resulting (lamp) current at 90 per cent
mains voltage will be lower:
A:as result of the lower mains voltage,
B:as result of the higher impedance.
With the capacitive ballast combination,the resulting impedance of
inductive ballast and capacitor is reacting in just the opposite way:at
lower mains voltage the total impedance is also lower.This results in
a nearly constant current.
122
5
3.4 Power factor correction
Mains voltage90 %100 %110 %
CircuitInd.Cap.Ind.Cap.Ind.Cap.
Z ballast (Ω)440440400400360360
Z capacitor (Ω)800800800
Z result (Ω)440360400400360440
Therefore the behaviour of the inductive and capacitive branch of a
duo-circuit is different at mains v oltage de viations and deviations of the
ambient temperature.This can be seen rather well in a duo-luminaire.
V
(V)
ballast
Fig. 116. Voltage/current characteristic
of an inductive ballast (example).
35
180
160
140
120
100
3
80
60
40
20
100
200
180
300
180
180
1
2
400
500
180
600
180
180
Z1 = 165 = 360 Ω
____
0,458
= 150 = 400 Ω
Z
____
1
0,375
Z1 = 135 = 440 Ω
____
0,307
700
800
180
180
900
180
I
180
1000
ballast
(mA)
Series connection of lamps
Under certain conditions it is possible to operate two lamps in series
on a common ballast (see Fig.117).A prerequisite for such operation
is that the sum of the operating voltages of the lamps is not higher
than approximately 60 per cent of the supply voltage.This means that
two lamps,each with an arc voltage of no more than 65 volt,can be
connected in series via a common ballast to the 220/240 V mains.This
restricts the maximum lamp length to 600 mm (2 ft),or the lamp
power to 18/20 W (26 or 38 mm diameter lamps only).
The series circuit can be compensated in the normal way by using a
parallel or series capacitor.
Fig. 117.Tandem circuit with two lamps
in series on a common ballast.
0
123
‘TL’1
‘TL’2
S
S
5
3.5 Series connection of lamps
Parallel connection of two lamps on a common ballast is impossible
because of the negative characteristic of the fluorescent lamp.All the
current would flow through the lamp with the lower arc voltage.
Moreover,once the first lamp is ignited the lamp voltage is too low for
the ignitor of the second lamp to ignite this lamp.
36
Neutral interruption and resonance
Normally each lamp circuit has its own compensating capacitor.In this
way every luminaire can be switched separately without influencing the
power factor.For the same reason lamp circuits based on phase-neutral
(230 V),are compensated with capacitors connected between each of
the phases and neutral.
In the phase-neutral network failure of one phase has no other effect
than to switch off the circuits on that phase.But if the neutral is not
connected,resonance will occur. For example,the current from phase
L1 via ballast and lamp 3 (see Fig.118) can pass via capacitor C1 to
phase L3.So lamp 3 is energised by 400 V and stabilised by a ballast
with a capacitor in series.This will surely destroy components.
A good neutral is essential.
Moreover,when the neutral is interrupted and the loads on the phases
are not completely balanced ( i.e.the same wattage),then the voltage
across the smallest load will increase and much more power will be
consumed by that load.This will surely damage lamps and/or ballasts
(see Fig.119).
Suppose there are five loads of 1000 Ω,one connected between L1
and neutral and four connected between L2 and neutral.The current
from L1 will be 230/1000 = 0.23 A and the power in the load will be
230 .0.23 = 53 W.
The current from L2 will be four times higher (0.92 A) and the power
too:212 W .
If the neutral is interrupted,the phase-phase voltage of 400 V will result
in a current which can be calculated from the resistances:1000 Ω in
series with 4 times 1000 Ω parallel.
Fig. 118. Compensation in a
phase/neutral network.
L
L
L
124
1
2
3
C3
C2
C1
N
B
B
B
1
2
3
LaLa
La
5
Fig. 119.The consequences of
interrupted neutral in a phase/neutral
network.
3.6 Neutral interruption and resonance
I
L
1
400V
L
2
I
total
1000
250
V
1
V
2
R
L
1
230V
N
R2R3R4R
230V
L
2
4 I
R
I
R
R
1
1000
I
R
5
1000
each
This makes 1000 + 250 = 1250 Ω.So the current will be 400 / 1250 =
0.32 A.
The voltage across R1 will be 0.32 .1000 = 320 V (V = I .R),so the
power in R1 will be 320 .0.32 = 102 W.
The voltage across the four parallel resistors is 0.32 .250 = 80 V,so the
power in each resistor is 80 .0.08 = 6.4 W.
Now it is seen that the smaller load (R1) is overloaded by a higher
voltage (320 instead of 230 V) and a higher current (0.32 A instead of
0.23 A).The higher load (R2 to R5) is greatly underloaded.
In practice the circuits are not that simple,but the essential aspect is
that in case of a floating neutral the smallest load will receive a higher
voltage and a higher current and so will be overloaded.
A second possibility of resonance has to do with the employment of
inductive and capacitive cir cuits in the same installation.In the capacitive
circuit,the impedance of the capacitor is twice the impedance of the
inductive ballast.So when an inductive and a capacitive circuit get in
series,the total impedance will be zero ,resulting in an unlimited current
(resonance).This can happen in a delta-network when one phase is
interrupted (Fig.120) or in a star-network with common neutral when
the neutral is interrupted (Fig.121).
Resonance problems can be prevented with special switch gear. If the
neutral in a star-network or a phase in the delta-network fails,such
special gear switches off the overall supply for the lighting installation.
B
Fig. 120. Resonance in a delta-network.
125
‘TL’D
‘TL’D
C
B
S
S
5
3.6 Neutral interruption and resonance
B
C
B
‘TL’D
S
‘TL’D
S
Fig. 121. Resonance in a star-network.
37
1) One lamp, inductive or compensated
with electronic or glow-switch starter
‘TL’, ‘TL’D, ‘TL’E,‘TL’U,PL-L, PL-T,
PL-T(S)(C) 4-pins
2) Two lamps, inductive or compensated
with electronic or glow-switch starter
‘TL’, ‘TL’D,PL-L
N
Electrical diagrams
L
N
L
N
B
C
B
C
V
La
V
La
V
La
3) One lamp, inductive or compensated
without starter
PL-S, PL-C, PL-T (starter incorporated)
N
126
B
L
C
La
5
3.7 Electrical diagrams
B
L
C
La
4) Two lamps, inductive or compensated
without starter
PL-S, PL-C (starter incorporated)
B
L
C
N
C
L
B
La
V
La
V
N
L
C
N
C
L
La
B
*
C
B
*
C
LaLa
V
LaLa
V
N
5) One or two lamps, inductive, capacitive or compensated with
electronic starter ES08; ‘TL’,‘TL’D
The capacitor C* must be of the X2 type 100 nF/250 V
6) Duo-circuit, two lamps, with
electronic or glow-switch starter
‘TL’D, ‘TL’E,‘TL’U,PL-L
7) Duo-circuit, four lamps, with
electronic or glow-switch starter
‘TL’D, PL-L
N
B
L
N
L
C
N
C
B
B
V
La
B
V
La
La
V
V
La
V
La
V
La
127
5
3.8 Mains voltage interruptions and short-circuiting
38
39
Mains voltage interruptions and short-circuiting
For various reasons,the supply voltage can be subject to deviations;
therefore a certain degree of deviation from the rated value has been
taken into account everywhere.With gas-discharge lamps deviations
of up to +/- 10 per cent of the rated supply voltage normally have no
detrimental effects.
Apart from such ‘normal’ variations, in practice three possible
uncontrolled effects can be distinguished:
1) Short-circuit of the mains voltage.
2) A dip in the power supply voltage.
3) Interruption in the power supply current.
These phenomena can occur during a thunderstorm,when switching
from one power supply source to another or when connecting heavy
loads to the mains,and are usually of very short duration.This is a
good thing too,since a single dip of 10 milliseconds (half a cycle) or
even less,can have a significant influence:the lamp will extinguish.
As the fluorescent lamp re-ignites in only a few seconds or even less,
these phenomena hardly give problems in practice (see also section
4.1.14:Effects of mains voltage fluctuations).
Harmonic distortion
All gas-discharge lamps stabilised by copper/iron ballasts have harmonics
in the lamp current.The first reason for this is that the lamp voltage
(= the voltage across the discharge tube) is more or less a squar e wave
of changing polarity every half cycle (see Fig.122).
This is graphically represented as a square wave voltage,made up by
Fourier analysis as the fundamental sine-wave of the mains supply and
a large number of odd harmonics (see Fig.123).
The voltage across the ballast is the vectorial difference between the
supply voltage and the lamp voltage,so the harmonics of the lamp
appear in the ballast voltage.As the ballast determines the current,
there will be only odd harmonics in the lamp current.Even harmonics
are not present.
Fig. 122. Square wave form of lamp
voltage.
128
V
m
V
l
I
5
3.9 Harmonic distortion
Fig. 123. Lamp voltage wave form constructed by the
odd harmonics from one to nine, according to
the formula:
f(t) = 4U/π (sin
ω
t + 1/3sin3ωt + 1/5sin5ωt + ....).
U
3
5
7
9
0
1
π
The second reason for the presence of harmonics in the lamp current
is the hysteresis of the ballast coil.With the aid of the relationship
between ballast voltage and ballast current (B-H curve of the ballast
coil,see Fig.124),the resulting current can be found for any ballast
voltage.Even with a pure sine-wave ballast voltage there will be some
harmonics in the ballast current,but this effect is small,compared with
the harmonics caused by the lamp.
The impedance of the coil becomes higher for higher frequencies,so
in practice only odd harmonics up to the seventh are of any importance
for the lamp current.
Practical values in percentage of the fundamental for most inductively
stabilised discharge lamps are:
fundamental:100 %
third harmonic:10 %
fifth harmonic:3 %
seventh harmonic:2 %
ninth and higher harmonics: 1 % or lower
When the supply voltage contains harmonics,these values can change
somewhat,but the ballast coil prevents dramatic increases.
2π
Fig. 124. Hysteresis cur ve of a typical
copper-iron ballast.
129
B,Φ,V
H,i
B,Φ,V
H,i
t
5
3.9 Harmonic distortion
International requirements have been made for the proportion of the
harmonics in supply mains currents.According to EN 60921,for lighting
equipment having an input power >25 W the maximum percentage of
harmonics for the input current are:
second harmonic: 5 %
third harmonic:30 .P.F. %,where P.F.= power factor of the circuit
fifth harmonic:7 %
seventh harmonic: 4 %
ninth harmonic:3 %
All Philips inductive compensated lighting circuits (P.F.= 0.5) comply
with this standard.The capacitive branch of a duo-circuit has higher
values,but as a whole the duo-circuit meets this standard.
To obtain a good power factor (0.9) of the system with gas-discharge
lamps,mostly parallel capacitors are used.In that case the effective
mains current will be nearly half,so the percentage harmonics
automatically will be doubled.
Again,there will be no problems in fulfilling the requirements.
A capacitor, however,has lower impedance for higher frequencies and
therefore the capacitor current is very sensitive to harmonics in the
supply voltage.
The quality of the supply source influences the amount of higher
harmonics in the mains voltage and consequently in the mains cur rent.
The lamp is only responsible for roughly 20 per cent third harmonics
in the current of the phase-conductor.When the amount of seventh
or higher harmonics is too high,a solution could be found in connecting
filter coils in series with the capacitors.
But adding the filter coils will result in higher thir d and fifth harmonics,
because the total impedance for the combination of capacitor and
filter coil is lower for these frequencies than the impedance of only the
capacitor (see Fig.108 in section 5.3.3).So a filter coil does not help
to suppress third and fifth harmonics.
The presence of harmonics has consequences for the mains wiring.
For the various wiring diagrams,calculations of the currents and
harmonics can be made.In particular lighting installations connected
to three-phase supplies,having a common neutral conductor,need
attention.
The neutral conductor carries a current equal to the vector sum of
the currents through the three phase conductors.
In a well-balanced system (equal effective phase-currents) the
fundamental frequencies of these currents add up to zer o, but the third,
ninth and fifteenth harmonics are in phase and thus amplify each
other (see Fig.125).
The neutral therefore will carry at least about 3 .20 = 60 per cent of
the phase current.For that reason the neutral conductor must have
the same cross-section as each of the phase conductors.
In case of a poorly designed system,the current of the neutral can be
higher than one of the phase currents.
Also in case of a supply voltage containing some distortion,the current
through the neutral can grow rapidly due to higher capacitor
currents.This can be of great importance when the supply voltage is
coming from a separate generator.
130
5
3.9 Harmonic distortion
RST
(b)
Fig. 125. Fundamental and third
harmonic in a three-phase mains. R, S
and T are the fundamentals in the three
conductors. Owing to the phase shift,
this results in a zero current in the
neutral lead.
a) Third harmonic of a phase ,
b) Third harmonic of all three phases in
the neutral lead. The individual currents
reinforce each other.
310
(a)
0
60
120
180
240
300
360
Electromagnetic interference
Discharge lamps do not only emit visible radiation,they also generate
radio-frequency energy in the radio spectrum.This can cause disturbance
of the operation of electronic equipment such as computer keyboards,
television or radio receivers,hence the name radio interference.
As the luminaires in which the lamps are used should fulfil international
requirements such as EN 55015 (CISPR 15),the radio interference in
practice is sufficiently low to ha v e no harmful eff ects on the surrounding.
Products with the mark conform to VDE 875 part 1.
The generation of radio-interference radiation is normally caused by
lamp electrode oscillations.It has a broad-band character,usually with
frequencies of up to 1500 kHz,so FM and television receivers are not
affected.
The electromagnetic wa v es,which can have effects on the AM broadcast
band,are propagated in tw o ways: either directly through the mains into
the receiver,or via radiation picked up by the aerial.
The latter form of interference will seldom occur with discharge lamps,
as the ballast will suppress the broad-band signals.The radiation
produced by the lamp will nearly always remain below the threshold
value at which interference takes place,especially where the lamp is
at some distance from the aerial (more than,say,1 metre).
The supply cables can emit interference radiation when they are not
buried in the ground or laid in earthed steel piping,which is the best
screening against interference.However, it sometimes happens that an
interference signal reaches the receiver by way of its mains input.The
interference signal can consist of high-frequency harmonics of the mains
frequency or high amplitude pulses.The former are generally adequately
suppressed in the ballast.Experience has shown that interference may
be caused by fluorescent luminaires with external ballast where the
radiation from the supply wires is pick ed up b y telephone or other cables.
If external ballasts are used,the supply cables between ballast and
luminaire should be as short as possible.Ballast coils should be split
into two adjacent parts (split-windings type of ballast).In case of Class
I luminaires the supply wires should be shielded and this shielding
should be properly connected to the earth connection.
In practically all other cases it will be necessary to connect a delta filter
between the mains supply and the input to the lamp circuit.
131
5
3.10 Electromagnetic interference
Fig.126 shows an example of a delta filter used for suppressing radio
interference.The apex of the filter must be connected to the ground.
More complicated filters are used in three-phase networks.
Avoid earth looping (all earth terminals to one point) and create
maximum distance between audio and lighting cabling.If audio and lighting
cables have to cross each other, it should be done in a perpendicular
way. In sensitive applications screening of cabling is necessary.
L
5 nF
0.2 mF
Fig. 126. Delta filter used for
suppressing radio interference.
311
5 nF
N
Lifetime
When used within the specifications,the various circuit components
will last for many years with no more failures than approx.1 per cent
per year (except lamps and glow-switch starters).
Most of the time,failures in the gear components are caused by
external circumstances,such as wrong wiring or connections, shortcircuiting,extreme heat or humidity,mains voltage peaks, poor
maintenance and the like.
For example,capacitors for lighting installations with the VDE appro val
according to VDE 0560 must achieve a lifetime of 30 000 hours at their
marked voltage (250 or 450 V) and their maximum case temperature
(85 or 100 ºC).Higher voltages will shorten the capacitor life as follo ws:
Voltage
(times V
mark
Lifetime (h)850040002900200015001100780
A failure rate of 5 per cent is then accepted and the capacitance loss must
be less than 10 per cent for parallel and 5 per cent for series capacitors.
Temperatures above the marked maximum ca pacitor case temperature
will halve the lifetime of the capacitor for every 8 degrees increase.
Therefore,if there are too many failures with capacitors,the capacitors
may be too hot or the applied voltage is (temporarily) too high.
1.151.251.301.351.401.451.50
)
For glow-switch starters the number of switches is specified as 10 000
or more.Deviations are caused by the different starting curr ents of the
various lamp types.
For electronic starters,the most relevant factor is the allowed
ambient temperature or the maximum case temperature t
.
c
The specified temperature range is from -40 ºC till + 80 ºC.Exceeding
these temperature limits will shorten the lifetime dramatically.
132
5
312
3.12 Ambient and operating temperatures
Ambient and operating temperatures
Temperature is of prime importance for the proper functioning
of discharge lamps (Fig.127a/b).In general,fluorescent lamps are very
sensitive to changes in the ambient temperature (see section 3.6:
Effects of temperature).
Fig. 127a. Relative values of luminous flux (Φ),
lamp voltage (V
wattage (P
), lamp current (Il) and lamp
l
) as a function of lamp head
l
temperature, for a PL lamp.
Fig. 127b. Relative values of luminous flux (Φ)
as a function of the ambient temperature
and the burning position (PL lamp).
%
120
100
80
60
40
20
20
30
recommended
temperature range
40
50
lamp head temp. (˚C)
60
Φ (%)
100
I
l
80
P
l
Φ
60
V
l
40
20
0
0
20
40
70
-20
ambient temp. (˚C)
60
For the total system the ambient temperature also is of great
importance,due to the fact that certain minimum and maximum operating
temperatures are specified for the various components.
Minimum temperatures
1) Lamps
Supplied with the nominal voltage,fluorescent lamps will start quite
normally at temperatures down to approx.-20 ºC.The minimum
allowed temperature depends on lamp type and starting system,which
determines the maximum ignition time (ranging from 2 to 20 seconds).
Also the circuitry (leading or lagging) has influence on the ignition
process.Two lamps in series normally ignite less easily than the one lamp
circuitry.In the lamp data sheets the minimum temperature and the
resulting ignition time can be found for the various circuits.Below these
specified temperatures smooth ignition cannot be guaranteed.
In the table below, the ignition time of a PL-L 24 W lamp (in sec) is given
as a function of lagging or leading circuitry,nominal or sub-nominal
supply voltage,type of starter and ambient temperature.
CircuitLaggingLeading
Voltage NominalNominal -8%NominalNominal -8%
StarterS10ES08S10ES08S10ES08S10ES08
Ambient temp.ºC
Once ignited,the lamp warms up its surroundings and,after run-up,the
low ambient temperature has less influence on the electrical
performance.Still,the light output varies with the actual tube wall
temperature.Capacitive circuits give less light at lo w temperatures than
inductive circuits due to the constant-current characteristic of the
capacitive circuit.
2) Gear
The minimum temperature for some electronic components and for
compensating capacitors is -25 ºC.The capacitance of capacitors, for
instance,declines steeply below that temperature.For that reason
gear should be installed at places where the ambient temperature will
not fall below -25 ºC.
3) Luminaires
In general the construction of the luminaires and optics is not affected
by low ambient temperatures down to -25 ºC.Of course plastic parts
such as clips are more brittle at low temperatures and should then be
handled with care.
Fig. 128.The maximum recommended
ambient temperature at which an SL lamp
can operate is 55 ºC.The par t of the lamp
with the highest temperature is a 5 mm
wide section around the circumference of
the housing. The temperature measured in
this region, on the surface of the housing,
is about 150 ºC. Exceeding this
temperature can result in reduction of
lamp life.
Maximum temperatures
1) Lamps
For fluorescent lamps the temperature of the glass tube wall is of
prime importance, especially with regard to the applied phosphors.It
will be clear that the actual lamp temperature very much depends on
the luminaire in which the lamps are placed.Lamps must only be used
in luminaires which are constructed for that particular type of lamp.
For some lamp types absolute maximum temperatures of a specified
spot are given (see SL,Fig. 128).With this in mind, also see maximum
and ambient temperatures under point 3) Luminaires.
5 mm
warmest region
of the housing
134
5
3.12 Ambient and operating temperatures
2) Gear
a) Ballasts
The main ballast temperature parameters t
coil temperature) and ∆t (coil temperature rise in standard test) are
described in section 5.1.6.Ballasts are normally mounted directly inside
a luminaire.The actual ballast coil temperature in practice depends on
the cooling properties of the ballast surroundings,e.g.material of
mounting surface,type of fixing,standing air or ventilation.For that
reason it is impossible to predict the actual ballast coil temperature
without doing a temperature test in practical circumstances.Of course
a ballast normally will be cooler when it has lower losses and/or a
lower ∆t value and/or larger dimensions.
Connections to a ballast are in many cases made by means of a
terminal block.These terminal blocks have their own temperatur e limits,
usually 100 to 120 ºC,which should not be exceeded.
b) Starters
Since they incorporate semi-conductors and capacitors,electronic
starters have a maximum permissible temperature.This value is
marked on the starter and is usually 80 or 90 ºC.In most applications
the starter case temperature will not exceed this limit,as the starters
hardly produce heat by themselves.
But if the starter is incorporated in the luminaire or placed near the hot
ballast,its temperature can rise considerably. It is advisable to mount
the starter on the coolest spot possible.
(maximum permissible
w
c) Capacitors
Capacitors hav e a maximum permissible temperature,which is marked
on the case and is usually 85 or 100 ºC.Above this temperature they
can break down or lose capacitance.They hardly produce heat by
themselves and must be placed away from the hot ballast.Additional
temperature measures are advisable when the capacitor case
temperature is unknown and can be critical.
3) Luminaires
Professional luminaires are,like ballasts,designed and constructed to
have (under standard conditions) an average lifetime of at least 10 years
in continuous operation with the appropriate (maximum) lamp type.
The volume of the luminaire,the choice of materials,the cooling
properties,etc.,are chosen in such a way that,at an ambient temperature
of 25 ºC in indoor applications,no part of the luminaire exceeds its
maximum specified temperature.In practice this ambient temperature
limit is sufficient to cope with most applications and non-nominal
circumstances,as long as the latter are within the specifications. In cases
where the ambient temperature is (temporarily) higher than 30 ºC,
the most critical part of the luminaire may exceed its maximum
specified temperature.This, of course,shortens lifetime, but to what
extent is in general hard to say. It depends on the part in question
(e.g.luminaire housing,mirror optics,cabling,lamp tube, lamp base, etc.).
135
5
3.12 Ambient and operating temperatures
In outdoor applications a natural air circulation around the luminaire
is assumed,which gives a cooling effect of about 10 ºC.The same
luminaire with an indoor ambient temperature limit of 25 ºC,will in
practice have an outdoor ambient temperature limit of 35 ºC.If for
outdoor luminaires an ambient temperature t
is given,it refers to the
a
outdoor situation.
Special lamps,luminaires and electrical circuits have been developed
for use in hot,cold,humid or potentially explosive environments.
Amalgam lamps - and to a lesser extent also krypton-filled (‘TL’D)
lamps - are not susceptible to the drop in light output at high ambient
temperatures experienced by normal fluorescents.When normal
lamps are operated on inductive ballasts,these may well overheat due
to the increase in the lamp current brought by the higher operating
temperature (see Fig.129).
However,where the decrease in light output and luminous efficacy can
be tolerated,and provided proper measures are taken to prevent
overheating of the circuitry, tube wall temperatures of up to about 90 ºC
are acceptable.
The use of properly ventilated luminaires will,in most environments,
obviate any heat problems.An air stream through the luminaire is an
effective way of removing the heat generated by the lamp and ballast.
Fig. 129. Influence of temperature
increase on lamp current (I), lamp
voltage (V), lamp power (P) and luminous
flux (
Φ
) for a 40 W fluorescent lamp on
inductive and capacitive ballasts.
313
%
120
100
80
60
40
20
0
20
40
60
I
ind
I
cap
P
ind
V
ind
P
cap
V
cap
Φ
ind
Φ
cap
80
100
t (˚C)
Effects of mains voltage fluctuations
The lamp voltage of a fluorescent lamp mainly depends on the lamp
construction (length and diameter) and the gas filling.It hardly
changes as a consequence of voltage variations in the mains,which
means that fluctuations of the mains supply must be compensated for
by the ballast.An increasing mains voltage results in a higher ballast
current,as the impedance of the ballast is nearly constant (see section
5.1.2:Stabilisation).As the ballast current equals the lamp current,the
power in the lamp and so the light output of the lamp increases at
rising mains voltage.
Supplies with wide mains voltage deviations will lead to considerable
deviations in luminous flux.Deviations of less than 5 per cent in
conjunction with the normal ballast will keep the values within acceptable
limits.The lumen level will not show fluctuations of more than 10 per
cent.When the mains voltage constantly differs more than 5 per cent
from the ballast rated voltage,the appropriate ballast should be applied.
136
5
3.13 Effects of mains voltage fluctuations
Due to the constant-current characteristic of the capacitive circuit, the
influence of mains voltage deviations is less than with the inductive
circuit (see Fig.130).
Fig. 130. Influence of variation of the supply
voltage on a PL-L 18 or 24 W lamp operated
in a lagging (inductive) circuit (Fig. 130a) and
in a leading (capacitive) circuit (Fig. 130b).
Relative values of luminous flux (
current (I
), lamp wattage (Pl) and lamp
l
Φ
), lamp
voltage (V
Ambient temperature: 25 ºC , burning position:
base up.
314
%
130
120
110
100
90
).
l
80
70
90
100
110
a)
relative supply voltage (%)
%
130
I
l
P
120
l
Φ
110
100
V
l
90
80
70
120
b)
90
100
relative supply voltage (%)
Electrical wiring
The electrical wiring in a luminaire must be such as to ensure its
electrical safety.This necessitates great care both in the choice of wire
used and in its manner of installation.
There are a great many different types of wire available,in both
single-core (solid) and multi-core (stranded) versions (Fig.131).There
is a wide variety in wire materials and diameters,as well as in thickness
and quality of insulating cladding material.
110
I
l
P
l
Φ
V
l
120
Fig. 131.Types of wire used in luminaires.
From left to right: solid core (3), stranded (3),
with heat-resistant insulation (3) and high-
voltage ignition cable (1).
Whether the wire is single-core or stranded makes no difference as
far as its electrical characteristics are concerned.Mechanically,however,
things are quite different.
Single-core wire is much stiffer than stranded wire,which means that
fewer cable fasteners are needed to hold it in position.It is also easier
to strip,after which it can be pushed into self-clamping connector
blocks without further preparation.It is therefore more suitable than
stranded wire for the internal wiring in a luminaire (Fig.132).
Single-core wire is,however, not suited for use in luminaires that are
subjected to vibrations and shock.The vibrations can be transmitted
along the wire,causing fixing screws to be loosened or the wire to
fracture and break.Here, stranded wire must be used. Being more
flexible,it is able to absorb vibrations harmlessly.Stranded wire is also
necessary in those situations where the wire must be able to bend in
use - as in a spotlight,for example (Fig.133).
137
5
Fig. 132. Solid-core wire inside a
luminaire for fluorescent lamps.White
wires are used where the wiring is
visible from below.
3.14 Electrical wiring
The diameter (or rather the cross-sectional area) of the wire must be
matched to the strength of the current flowing through it.A wire whose
area is too small has a resistance that is too high and it will become
warm,the resulting heat loss reducing the efficiency of the luminaire.
A minimum nominal cross-sectional area of 0.5 mm
IEC 598,although this may be reduced to 0.4 mm
where space for internal wiring is severely restricted
(see IEC 598,section 5.3.1).
2
is laid down in
2
in certain cases
Of particular importance with regard to insulation material and
thickness is,of course,its temperature resistance.Here it must be borne
in mind that it is not only the temperature of the air in the luminaire
that matters,but also that of components with which the insulation
may come in contact,such as ballast and lampholders.The insulation of
the wire used must be resistant to all such temperatures,not only
under normal conditions of operation,but also in the presence of a
fault condition.
Not all sorts of insulation are suitable for use in luminaires.For example,
simple PVC (polyvinyl chloride) insulation is only heat-resistant up to
90 ºC.It contains a softener,which can vaporise, making the insulation
brittle and therefore prone to damage.Moreover, the evaporated
softening agent attacks a number of plastics used in the manufacture
of luminaire housings.There is,howev er,an inexpensive PVC insulation
that is heat-resistant up to a temperature of 105 ºC,and which is safe
in this respect.Where temperatures in excess of 105 ºC can arise,yet
another kind of PVC insulation is usually employed,one that is resistant
up to 115 ºC.
Where still higher temperatures may be encountered,as in floodlights
for example, siliconerubber (170 ºC to 200 ºC) and PTFE
(polytetrafluorothene) (250 ºC) insulating materials are available.Extra
Fig. 133. Flexible stranded wire inside
the pivoting base of a spotlight.
138
5
3.14 Electrical wiring
protection can be obtained by covering the insulation with a glass-fibre
sleeve.
In order to keep the chances of heat damage to the insulation to a
minimum,the wiring run is so chosen as to avoid as far as possible any
‘hot spots’ in the luminaire,such as ballast or lampholders.
The cable fasteners used to hold the wiring in place should allow it
some slight freedom of movement,for the insulating covering of wire
that is under mechanical strain will have a lower heat resistance than
that specified by the manufacturer.
There is an internationally standardised colour coding for electrical
wiring,namely that specified by the IEC:brown for live,blue for neutral
and yellow/green for earth.
The only time when a departure from this colour coding is permissible,
is in the case where luminaires have internal wiring that is visible
when the unit is in use.A white insulation is then often used so as to
blend in with the white of the housing.The proviso here is that the
connection block is clearly labelled.
315
Hum
In general,lamps,ignitors,capacitors and even luminaires do not pr oduce
any disturbing noise level when correctly used in their application.
Sometimes during the starting process some hum or rustling can be
noticed,especially with glow-switch starters.If hum is noticeable,it
almost always comes from the ballasts. Anyhow,when used in indoor
applications,e.g.shops,the hum level caused by control gear should
be as low as possible.
The electric current passing through the coil of a ballast causes
a magnetic field,which arranges the disorderly arranged elementary
magnetic particles of the ballast iron.So we find in the iron
magnetostriction and magnetic poles.
The ordering of the elementary magnets causes a certain deformation
of the iron (magnetostriction),resulting in the iron expanding in certain
directions.This process is repeated every half cycle if alternating
current is used and results in a noise of 100 Hz and higher harmonics.
The magnetic poles exert forces of attraction in the air gap of the
ballast core,also resulting in a noise of 100 Hz and higher harmonics.
The generation of these magnetic vibrations can be suppressed to a
high degree by means of a suitable design of the ballast.In particular,air
gap filling and ballast encapsulation can contribute to low noise levels.
But the magnetic field also spreads outside the magnetic core.All
magnetic metal parts in the immediate surroundings of the ballast,such
as the ballast case,the sheet-steel of the luminaire,etc., are subject to
forces in this magnetic field and can cause noise.
To avoid unpleasant ‘humming’ noise, constructions for the ballast
mounting,as well as the ballast mounting itself,must be as rigid as
possible.The hum will be more pronounced if the ballast is mounted
on a resonant surface.Avoid loose metal parts and create distances
between ballasts and metal parts.
139
5
316
3.16 Dimming
Dimming
Dimming can be defined as the reduction of the luminous flux of a lamp,
either continuously or in steps,by reducing the operating current.This
is not always possible without adversely affecting the performance of
the lamp.
Basically,dimming is achieved in one of the following ways (see Fig. 134):
- by switching a (variable) resistor or inductive coil in series with the
lamp(s),
- by running the lamp(s) from a variable transformer,
- by suppressing the AC wav eform of the supply current during part of
the cycle by means of an electronic element (thyristor); such a device
is also called a ‘chopper circuit’,
- by increasing the frequency of the supply current of an inductive
coil,thereby increasing the impedance of this.
Fig. 134. Four basic ways of dimming.
a) by a variable resistor,
b) by a variable transformer,
c) by a thyristor circuit,
d) by frequency regulation.
L
N
a)
L
N
c)d)
L
N
b)
L
N
Resistors are now rarely used for dimming purposes,because they
are inefficient and produce a lot of heat.
Variable transformers are appreciated because of their high power
handling capacity,but at the same time they are heavy and expensive.
In the case of fluorescent lamps operated on electromagnetic gear
dimming is mostly achieved by the extra inductive coil in series or by
the thyristor circuit (Fig.135). In both cases only inductive circuits are
allowed and the parallel compensating capacitor must be placed before
the dimming device.Capacitive or duo-circuits are not allo wed because:
- with the extra series impedance the total impedance for stabilising
would become lower instead of higher,
140
5
3.16 Dimming
Fig. 135. Dimming with an extra inductive
coil in series and by a thyristor.
extra
coil
L
CC
N
L
N
BB
- with the thyristor circuit the moment of current suppressing must
be different for the inductive and the capacitive branch due to the
phase shift,which is impossible to realise in one and the same device.
During dimming only the lamp current will decrease and the capacitor
current will remain the same.The result is that the power factor will
become capacitive and will shift to lower values.
Inductive coils,in the form of an extra ballast,are used to reduce the
light output of street lanterns after a certain hour.This is done either
by switching the extra ballast in series with the principal one,or by
using two ballasts of half the nominal pow er rating in parallel,switching
one off when dimming is required.
Thyristor dimmers are by far the most popular nowadays,because
they are small and inexpensive.
Dimming to give half the light output is nearly always possible. By using
thyristor dimmers practically any type of fluorescent lamp can be
dimmed down to about 50 per cent of the nominal lamp current,which
roughly corresponds to a 50 per cent reduction in light output (so-called
‘top dimming’).For indoor installations,however,top dimming is of
limited practical use and at ambient temperatures below 5 ºC kryptonfilled lamps,like the Philips ‘TL’D may become unstable when dimmed.
The disadvantage of thyristor dimming where lamp circuits
incorporating glow-discharge starters are concerned,is that the dimmed
lamp will cause the starter to become conductive.At what degree of
dimming this will happen is difficult to predict,but the result is that
the starter will make repeated attempts to ignite the lamp.This is the
main reason why dimming of fluorescent lamps in a glow-switch
starter circuit is discouraged.
When dimming to below 50 per cent of the nominal current,the
discharge will no longer provide sufficient heat to keep the electrodes
at the proper emission temperature and continuous electrode heating
becomes necessary.The heating current must be independent of the
lamp current,thus a separate heating transformer will be required.
Lamps operated in this mode can be dimmed to give almost zero light
output (but not entirely, unless a switch is provided).They can also be
started from a dimmed position.These dimming installations almost
invariably operate at high frequency to prevent disturbing flicker at low
lighting levels.
Frequency regulation is the most recent technology, and is employed
in the Philips HF electronic light regulation ballast.With this ballast
the lamp current can be regulated down to about ten per cent of the
nominal value.Dimming is here achieved by increasing the frequency
of the supply current.
141
5
317
3.17 Stroboscopic effect and striations
Stroboscopic effect and striations
For this subject,see also section Lamps,3.10.
1.A fluorescent lamp operating on an alternating current will exhibit a
fluctuating light output,because the lamp extinguishes and restrikes
every half cycle of the supply. So this light ripple has a fixed (mains)
frequency and can cause the stroboscopic effect.It mainly depends
on the used phosphors of the lamp:the use of phosphors exhibiting
little or no afterglow may result in more pronounced fluctuations.
The use of inductive (Fig.136a) and capacitive circuits together in a
duo or ‘lead-lag’ combination reduces the light ripple (Fig. 136b) In
an inductive circuit the lamp current will lag behind the supply
voltage by approx.60º,while in the capacitive circuit the current will
be ahead of the voltage by approx.60º.This means that the light
output of a twin-lamp duo-circuit has two components mutually
shifted by 120º.
The best solution for preventing the stroboscopic effect is spreading
the lighting over the three phases of the supply (Fig.136c),where the
minimum light output of one lamp coincides with high light outputs
of the two other lamps.
Fig. 136. Prevention of the stroboscopic
effect by using combined inductive and
capacitive circuits (‘lead-lag’ or duo-circuit)
and by spreading the lighting over the
three phases of the supply.
˚˚˚˚˚
0
90
a)
˚˚˚˚˚
0
90
b)
˚˚˚˚˚
0
90
c)
1 cycle
180
1 cycle
180
1 cycle
180
270
270
270
360
360
360
142
5
3.17 Stroboscopic effect and striations
2.The light ripple can also have an effect on the quality of camera
pictures.This phenomenon may become apparent when CCD colour
cameras operate in auto-shutter mode and the lighting of the area
is predominantly with fluorescent lamps,
The auto-shutter mode is normally selected when cameras are
equipped with manual or fixed iris lenses and the automatic light
response is controlled by an electronic shutter system in the camera.
The more light is exposed to the camera,the shorter the shutter
time.This means: the shorter the light integration in the sensor takes
place.For example, with a shutter time of 1/1000th of a second the
light integration of the CCD sensor is 1 msec only.Within the normal
CCIR scanning period of 20 msec (50 Hz) the 1/1000th of a second
the light intergration time is just a snap-shot in the normal frame
scanning period.In this manner the sensitivity of the camera is reduced.
As described before,the light output of fluorescent lamps varies
continuously from minimum (at zero crossing) to maximum during
the positive and negative phases of the mains voltage,twice during
one mains voltage cycle.In other words:the fluorescent lamp is
flashing 100 times per second.Due to the lag of our eye,viewing a
scene illuminated with ‘TL’ lamps,gives the impression of a white
and continuous light output.
At the dip of the light output,the excitation of the fluorescent
powders is with minimum energy.At this point, the light output is
therefore not white,the colour depending on the properties of the
non-saturated excitation of the fluorescent powders in the lamp.
As the human eye works as an integrator,this effect cannot be
noticed.The light ripple of a ‘TL’ lamp is illustrated in Fig. 137.
When the automatic shutter in the camera is switched off,the two
light ripples of a ‘TL’ lamp are integrated during the normal 20 msec
frame integration time of the sensor and consequently the light
impression is white.This is illustrated in Fig. 138.
Using the automatic shutter in sufficiently illuminated scenes,the
shutter speed increases and consequently light integration in the
sensor takes place during a short period of time.Depending on the
position where the light integration (snap-shot) takes place with
respect to the mains phase (light ripple),it is now possible that a TV
Fig. 137. Colour shift during the 100 Hz
light ripple of a fluorescent lamp
non-saturated
phosphors
momentary light output
143
white light
yellowish light
reddish light
5
Fig. 138.The 20 msec frame integration
time of a CCD colour camera with the
automatic shutter switched off, compared
with the 100 Hz fluorescent light ripple.
3.17 Stroboscopic effect and striations
100Hz fluorescent
light ripple
20 ms
normal shutter time
frame is shot during the non-saturated excitation of the fluorescent
light,see Fig.139.
It can be said,that the light at this point in time is not white and the
light output is less.If the phase of the camera shutter remains constant
with respect to the mains phase,the automatic light control and the
white balance circuits in the camera will compensate for these
effects and stable pictures are produced.This situation is obtained by
locking the camera frame synchronisation to the mains (mains lock).
When there is no fixed phase relation between the scanning
frequency of the camera (free running) and the mains frequency,the
camera will take a snap-shot of the scene at varying phases of the
fluorescent lamp light output.This causes a colour fading to become
visible.The extent of colour fading is depending on the lighting
design of the area.
In applications where the scene is illuminated with just one fluoresecent
lamp or other gas-discharge lamp,stabilised by conventional gear,
the colour fading risk is at its maximum.It is recommended that
cameras be locked to mains frequency and the phase of the camera
synchronisation be adjusted such that the camera signal output is
maximum.If mains lock is not possible in such an application,the lens
iris should be closed to the point where the colour fading just
disappears.Now the shutter speed is less (full frame integration)
and the additional benefit is that the sensor smear effect is less.This
solution cannot be used in applications that need short shutter speeds
to suppress movement blurr.
In all other cases (combination of inductive and capacitive circuits,
three-phase installation of high-frequency stabilised) this phenomenon
will not occur.
Fig. 139. Using the automatic shutter and
with the camera locked to mains
frequency,it is possible to shoot stable
and white pictures.
light integration
short shutter time
mains lock fase
20 ms
3.The movement of the arc on the electrode(s) (flicker) has no fixed
frequency and will only become noticeable in exceptional cases.It
144
5
3.17 Stroboscopic effect and striations
depends on several factors,including lamp position, supply voltage,
temperature,age of the lamp (electrode) and also of the lamp curr ent
wave form (peak factor).
4.Striations are noticeable as a pattern of more or less bright regions
in the long discharge tube of fluorescent lamps.The pattern can
move through the discharge tube.It can appear when the lamp is
cold or when the lamp is dimmed down to too low a level.
318
Circuit breakers, fusing and earth leakage
1 Standard conditions
Under normal conditions the highest current which can occur is the
current during the starting phase.When the starter is closed,
practically the entire supply voltage is across the ballast,resulting in a
high current and a low power factor.The fuses must be capable of
handling this high initial current for several minutes.For most of the
fluorescent lamps stabilised with copper/iron ballasts,this starting
current is about 1.5 times the normal operating current.
During switching on,a few other processes are going on as well:
- the (empty) parallel compensating capacitor will be charged with a
high inrush current,
- depending on the magnetic saturation of the ballast a voltage induction
will take place in the ballast,
- gas-discharge lamps can have some rectification or DC component
in the lamp current.
These phenomena occur in the very first 3 to 5 milliseconds and can
result in a peak current of 15 to 25 times the nominal current.This
surge current will depend on the lamp and ballast type and the number
of lamps per circuit as well as,of course, on the resistance and
impedance of the lamp and supply cables and the impedance of the
mains supply network.This latter part varies greatly in practice.It is
recommended that a surge current of 20 to 25 times the nominal
current during the first 3 milliseconds be used and 7 times the nominal
current for the first 2 seconds for parallel compensated circuits as a
guide for selecting fuse ratings.
In the duo-circuit the capacitor is connected in series with the coil,so
the very high surge currents cannot appear in this case.
Devices for switching and fusing must be capable of handling these
currents correctl y.This means that for fuses slow-acting gI types (normal
general purpose type for cable fusing) hav e to be used (German name:gL).
The main purpose of the fuse is to protect the cable and the distribution
part of the lighting installation from damage in case of a failure in the
installation.So the fuse rating is primarily related to the cable core used
in the installation.
As the various national electrical safety rules differ slightly, the
recommended fuse ratings for lighting equipment published b y the various
lamp,gear and fuse suppliers are not always the same.Moreover,there
are differences in the various brands of fuses.
As a guide,it is recommended to load gl-fuses to not more than
50 - 70 per cent of their rating.
145
5
3.18 Circuit breakers,fusing and earth leakage
The same applies to main circuit breakers (MCB’s).Although the
switching characteristics of MCB types are laid down in
recommendations like CEE-19-2
nd
edition,the various characteristics
of different types and brands can differ considerably.
Circuit break ers are tested and calibrated to carry 100 per cent of their
rated current in open air at a specified temperature,normally 25 ºC.
When mounted in an enclosure,the ambient temperature may be
higher.As a result,circuit breakers are permitted continuously to carry
only 80 per cent of their current rating.The manufacturer’s technical
information should be carefully reviewed to determine the exact
capabilities of a specific breaker.
Main circuit breakers work on two principles:
1) The thermal part, being a bi-metal strip, which is heated by the
passing current.The switching-off characteristic is similar to that of
a fuse and is influenced by time and current value.It is effective after
approx.minimum 2 to 5 seconds for the smaller overload currents.
2) The electr omagnetic part,being a magnet coil,which is effective for the
high overload currents and reacts within milliseconds (see Fig. 140).
Fig. 140. Switching characteristics
of various types of main circuit
breakers.
switching time (s)switching time (s)
10000
1000
100
10
0.1
0.01
0.001
1
0.5
1
3
2
7
5
10
20
L-curve
U-curve
K-curve
305070
100
According to CEE-19-2ndedition (L, U and K)
10000
1000
100
10
1
0.1
0.01
1
200
300
1.5
According to EN 60898 / VDE 0641 (B, C and D)
BCD
4
3
5
6
2
8
10
20
30
15
multiple of nominal currentmultiple of nominal current
For lighting applications the less sensitive types of circuit breakers are
advised,such as the U-,K-,C- or D types.
Taking the 10 A MCB type C as a r ef er ence (with a load assumed to be 1),
then the other types can handle loads as shown in the following table:
Information on what lighting load a certain MCB can handle may be
given by the MCB supplier, provided information about the cabling
lay-out,lamp type and circuit is available.As a guide,a practical value for
the figure (1) of the 10 A MCB type C represents 1500 W lighting
load with the conventional gear.
2 Non-standard conditions
A fluorescent lamp circuit normall y consists of four parts:lamp,ballast,
starter and compensating capacitor.
The effects of short-circuiting one of these parts are:
1) Short-circuiting of the lamp
This has been described above:in the inductive circuit the mains current
will be approx.1.5 times the nominal value, which means an extra
temperature rise of the ballast and cabling by a factor 1.5
immediate damage or danger and the situation can continue to exist
for days.Tested in a complete luminaire at 110 % V
temperature must be low er than 232 ºC,which guarantees a minimum
lifetime of the ballast of 20 days in this situation.In most cases the
mains fuse will not blow and the situation can only be solved by good
maintenance.
In a capacitive circuit the current is even lower than the nominal value
when the lamp is short-circuited.So then the described effects are not
noticeable.
mains
2
.There is no
the ballast
2) Short-circuiting of the ballast
As there is no current limit in this case,the lamp current will rise
immediately to an undefined high value in the inductive circuit.If the
current is not switched off by the mains fuse,the lamp will normally
become an open circuit because (one of) the lamp electrodes will
melt.In most cases this process is so quick that there will be no extra
danger or damage.In practice, however, it happens that the ballast is
partly short-circuited inside the copper coil,for example at the end
of the ballast lifetime.This results in a higher ballast temperature and
a higher lamp power.This process is cumulative and normally the
mains fuse will not blow,while the ballast gets hotter and hotter until
a fatal earth or winding breakdown occurs.For this reason,the ballast
must be mounted in such a way that it can cause no danger during
end-of-life failure.
Good maintenance can prevent blo wn-up lamps and burned-out ballasts.
When in a capacitive circuit the ballast is short-circuited,the lamp
is only stabilised by the series capacitor. In most cases the lamp will
extinguish,as the remaining impedance is too high (
In those cases where the lamp continues to work,the high capacitive
peak currents through the lamp,will rapidly damage the lamp
electrodes.The lamp will blacken at the lamp ends and sooner or later
a lamp electrode will break,resulting in an open circuit.
Z
= 2.lZ
c
l
l
).
L
l
147
5
3.18 Circuit breakers,fusing and earth leakage
3) Short-circuiting of the ignitor
At the end of the lifetime of a glow-switch starter the bimetal electrodes
will stick together and will not re-open again.Then the short-circuit
current will continuously flow through the lamp electrodes,resulting in
strong lamp end blackening and a hot ballast.This effect often can be
found in practice if the maintenance of the installation is not well done.
It is advisable to renew also the glow-switch starter at lamp replacement.
4) Short-circuiting of the parallel compensating capacitor
This results in a complete short-circuit of the mains,so the mains fuse
will react.In fact,short-circuiting of the capacitor will not occur in
practice as capacitors for lighting applications must have a switch-off
mechanism that results in an open circuit during excessive capacitor
currents.In that case the circuit is not compensated, so the mains
current will rise.
Regular control of mains current and/or power factor is advisable.
5) Short-circuiting of the series capacitor
In fact there are no visible signs or critical effects when the series
capacitor is short-circuited.The lamp circuit will function normally, but
only the power factor will change and will shift.
3 Earth leakage
There are two different official earth classifications:
1) Protective earth (PE) with symbol ,which must ensure safety in
case of (human) contact with accessible metal parts that can become
live,e.g.at the end of the life of a component.
2) Functional earth with symbol , necessary to connect for reasons
other than safety.
With electromagnetic lamp control gear we only have to deal with
protective earthing,which is permissible by mounting the gear to an
earthed metal component.
Capacitors in metal housings can often be mounted by means of a
metal stud (see Fig.141).
Fig. 141.Typical capacitor with metal
stud fixing.
148
5
3.18 Circuit breakers,fusing and earth leakage
Earth leakage currents in lighting circuits depend on the quality of all
system components and on the circumstances (humidity, dust,age).
With respect to luminaires,IEC 598 restricts these currents to 0.5 or
1 mA,depending on the insulation classification.The earth connection
may consist of an earth lead or the capacitance between the luminaire
and its surroundings.
The earth leakage current of a ballast normally is very low:all ballasts
undergo a high-voltage insulation test of 2500 V to check their
insulation resistance.This can be checked in practice with a Megger
(Megohm meter) of minimum 500 V DC,resulting in an insulation
resistance of more than 2 Megohm.Tests with burning lamps can give
earth leakage currents of about 1 to 2 mA per lamp circuit.In older
installations these values can be somewhat higher due to humidity, dust,
cable capacity or during the starting period.But the earth leakage current
never should be higher than 5 mA per lamp circuit.
There are two different applications for earth leakage devices:
1) to protect people from direct contact with live parts,reacting to the
current through the human body;there are 10 and 30 mA devices,
2) to protect people and grounded installations,reacting to the direct
current to earth;there are devices of 300 mA and higher.
319
Fault finding
When a lighting installation becomes inoperative,a complex, thorough,
trouble-shooting procedure may prove overly time-consuming.In many
cases,a simple check of the power switches,lamps and gear may
provide the quick est response to the problem.In some cases,however,
it may be necessary to isolate the problem systematically and perform
complete electrical tests in order to restore the lighting properly.
Besides,it is important to know if the installation or individual isolated
lighting points did function well before the failure.
There are four basic causes of failures:
A:lamp-related:not starting,cycling, too bright or dim,
B:gear-related:too hot or damaged ballast,capacitor, starter,
C:installation-related:cable too hot, terminals or lampholder damaged,
blown fuses,contactors or circuit breakers switched,
D:supply-voltage-related:too high,too low,wrong frequency ,bad voltage
waveform.
There are also four basic trouble-shooting methods:
1.visual inspection,
2.quick fix for restoring lighting,
3.trouble-shooting checklist,
4.electrical tests.
1A:Visual inspection of lamps
End-of-life of lamps is characterized by low light output and/or different
colours.Visual signs include blackening at the ends of the arc tube and
electrode tip deterioration.
Additional checks:
- broken lamp pins,
- broken or loose electrodes in lamp tube,
149
5
3.19 Fault finding
- tube blackening,
- lamp type and wattage must correspond to that required by ballast
label,
- lamp orientation designation incorrect for application (base up,base
down).
1B:Visual inspection of components
- damaged ballast,starter or capacitor,
- evidence of moisture or excessive heat,
- loose,disconnected,pinched or frayed leads,
- incorrect wiring,
- ballast,starter and capacitor must correspond with lamp type and
lamp wattage for the actual mains supply voltage.
1C:Visual inspection of installation
- incorrect wiring,
- blown fuses,switched circuit breakers or contactors,
- hot cables,
- damaged lampholders.
1D:Visual inspection of mains supply
Verify that the correct line voltage is being supplied and that phase and
neutral are connected in accordance with the the wiring diagram.
2:Quick fix for restoring lighting
After the visual inspection and repair, replace any defective component,
starting with the lamp and glow-switch starter.
3:Trouble-shooting checklist
When,after following points 1 and 2,a failure still exists, some tests will
have to be carried out.
Fault I:lamp shows bright flash and does not ignite again.
• Possible cause:
- no ballast,incorrect ballast,short-circuited ballast,
- capacitor across the lamp instead of across the mains.
Fault II:newly replaced lamp does not ignite.
• Action:
- disconnect starter and measure mains voltage and open-circuit voltage
at the lampholder.These must both be equal in case of a linear coil,
- if equal,replace the starter,
- if not equal,replace the ballast,
- if equal and not igniting with new starter and lamp,check lampholder
and circuit contacts.
Fault III:lamp remains in glow stage,does not ignite properly or only
lamp ends (electrodes) do emit some light.
• Possible cause:
- lamp was damaged in previous overload,
- starter defect or short-circuited.
150
5
3.19 Fault finding
Fault IV:lamp flickers.
• Possible cause:
- lamp operating voltage too high,end of lamp life,
- low supply voltage,check ballast connection,
- burning position out of specification.
Fault V:strong blackening of lamp,light output reduction.
• Possible cause:
- overload operation,
- wiring / ballast defect,
- capacitor across lamp instead of mains,
- end of lamp life.
Fault VI:fuse acting shortly after switch-on.
• Possible cause:
- fuse rating too low or not slow-acting type,
- wiring defect,overload operation.
Fault VII:colour differences in lamp colour.
• Possible cause:
- strongly varying burning positions in an installation,
- underload,
- lamps of different operating age or different suppliers,
- lamps of different colours used.
4:Electrical tests
Voltage and current measurements present the possibility of exposure
to hazardous voltages and should be performed only by qualified
personnel.To measure the correct effective values,true RMS voltmeters
have to be used.Measurements with non-true RMS meters can give
up to 50 per cent lower values,especially during measurements of the
lamp voltage or other non-sine-wave voltages (see table below).
DescriptionWaveformTrue RMSPeak RMS Average RMS
Sine wave100100100
Square wave10071111
Triangular wave10012096
calibratedcalibrated
Single-phase
electronic load 10020050
current
Single-phase
electronic plus 10016683
30 % linear load
The parallel compensating capacitor can be measured in two ways:
1) Measure mains current and lamp current.
If both are the same,the capacitor is open-circuit and has to be
replaced.
151
5
3.19 Fault finding
If the mains current is about half the lamp current,the capacitor is
in order, resulting in a power factor of approx.0.9.
2) Disconnect capacitor from circuit and discharge by short-circuiting
terminals.
Check capacitor with ohmmeter set at highest resistance scale.
If the meter indicates a very low resistance which then gradually
increases,the capacitor is in order.
If the meter indicates a very high resistance which does not diminish,
the capacitor is open-circuit and should be replaced.
If the meter indicates a very low resistance which does not increase,
the capacitor is short-circuited and should be replaced.
This method can also be used for the series capacitors.
Measurement of the starting pulse voltage of a starter is beyond the
capability of most instruments available in the field,due to the high
peak voltages.The practical way is to replace the suspect starter by
another one.
Measurements on the ballast can be done in two steps after
disconnecting the ballast from the circuit:
1) Check with ohmmeter on the terminals.Values should be low (15 to
200Ω,depending on lamp power).If the value is high,the ballast is
open-circuit.
2) Connect ballast on the mains supply (well fused!) and measure the
short-circuit current.This should be approx.1.5 times the nominal
lamp current.
Measurements of the lamp electrodes can be done at the 4-pin
versions with a standard ohmmeter.The resistance of the electrodes
varies for the different lamp types,but is less than 50 Ω when cooled
down.
Measurements on the lamp in operation can only be done if the starter
is not operative.As the lamp voltage is not a sine wave and subject to
the tolerances in the total circuit,measured lamp voltages only give a
rough indication of correct functioning.The lamp current can be
measured rather accurately.
Measurements of the mains supply normally involve the effective value
of the supply voltage and mains current and sometimes the frequency.
When pulses,interruptions,harmonics (wave form) can play a role,
‘laboratory’ instruments are necessary,preferably during a longer period
while storing or noting the readings.
It is advisable to measure the various phase currents in an installation,
in order to check the balance of the load.Also the measurement of
the current in the neutral in a star network gives an indication of the
quality of the total system.Due to harmonics in the lamp current,the
current in the neutral is not zero,but should be 50....70 per cent of
the phase currents.If the current in the neutral is higher than in the
phases,the balance in the load is not correct or the mains supply
waveform does not have a good sine wave.This can lead to overload
of the neutral cable.
152
5
320
3.19 Fault finding
For safety and good ignition,earthing of the luminaires and the electrical
system can be essential.Check the system’s current to real earth (see
section 5.3.18:Earth leakage).The voltage between real earth and the
neutral conductor is not limited by safety regulations,but lies normally
between 0 and 6 V.
Apart from these electrical tests,it has to be checked that all
components are used within their specifications,with special attention
to the maximum temperature.
Installation aspects
- The live side of the mains must be connected to the ballast.As most
ballasts are symmetrical there is no marked indication at the ballast
terminals for the mains and lamp connection.Mixing up the ballast
terminals can slightly influence the radio-interference level.
- In the total circuit,however, interchanged connection of phase and
neutral terminals can cause higher radio interference,higher earth
leakage currents and/or ignition problems.
- It is recommended that the bottom plate of the ballast be
connected to earth,for example via a metal part of the luminaire. In
case of end-of-life of the ballast,short-circuiting of the ballast
windings to the metal laminations of the ballast will result in a blown
mains fuse.The ballasts do not have a separate earth contact:
earthing-while-mounting.
- In two- or three-phase networks with a neutral conductor,this
neutral wire must have the same cross-section as the phase wires.
- Use stranded wire in places that are subjected to vibrations or where
the wire must be able to bend in use,as in a spotlight.
- Most ballasts,starter- and lampholders are equipped with either single
or double insert contacts,suited for solid core wire of 0.5 - 1.0 mm
which should be stripped properly.
- At ambient temperatures below 10 ºC closed luminaires should be
used to avoid too low lighting levels.
- Circuits with glow-switch starters require long starting times at low
temperatures.An earthed metal shield near the lamp will improve
the starting process,shortening the starting time and increasing
lamp life.This earthed metal shield can be the mounting plate for the
ballast.
- Mount the ballast as close as possible to the lamp.Although the
starter peak initially has a high value,its energy content is restricted.
Due to the high ohmic resistance of long installation wires,the
starter energy can easily be lost.This can happen in particular in series
circuits with two ‘TL’ 4-6-8 W lamps.
- Preferably mount ballasts on metal surfaces for good heat transmission.
If the ballast has to be mounted on heat-isolating material (wood),
the type ballast should be used.
- In outdoor applications SL lamps should be used inside an enclosed
luminaire.This is to prevent moisture from creeping into the lamp.
- SL lamps cannot be dimmed as this will reduce lifetime considerably.
Also,the dimming circuit in which the lamps are used can be
damaged.
2
,
153
5
321
3.21 Non-standard supply voltages
Non-standard supply voltages
In combination with the correct gear, fluorescent lamps can function
perfectly on a wide range of supply voltages.The luminaire itself is not
limited to certain supply voltages either.
For non-standard voltages appropriate gear components should be
selected:
- Ballasts have to be designed for the proper suppl y voltage and frequency
and for the chosen lamp type.So ballasts for a mains supply frequency
of 50 Hz are different from those for 60 Hz,even if the mains
voltage and the lamp type are the same.If the desired ballast type is
not in the standard Philips range,information can be obtained from
the local Philips organisation.
- Starters are related to lamp type,ballast and supply voltage.The Philips
range of starters cannot be used for other voltages than those for
which they are specified.All starters are suited for 50 and 60 Hz.
- Capacitors are specified by their voltage and capacitance (in µF).As
long as the voltage is lower than the marked capacitor voltage,the
capacitor can be used.There is no difference in the capacitor for
50 or 60 Hz supply voltage frequency.The necessary capacitance can
be calculated and is,for example in the case of parallel compensation,
5/6 smaller for 60 Hz supplies than for 50 Hz supplies.
- Filter coils are related to a capacitance (in µF) and a frequency.As
long as the power supply voltage is lower than the marked filter coil
voltage,the filter coil can be used.
- In large lighting installations,in most cases there is a possibility to
transform the non-standard voltage centrally into a standard voltage.
In small projects a local solution has to be found.
- If the power supply voltage for fluorescent lamp circuits is generated
by a separate motor/generator set (e.g.for emergency lighting),
special attention must be paid to the right choice of the generator/
alternator type.Not all types of generators can correctly handle the
changing power factor and/or the harmonics in the phase and
neutral current.Minimum requirements can be supplied on request.
322
Maintenance
Gear components are in fact designed to be maintenance-free.
Regularly checking the tightness of the screw terminals can prevent
problems caused by open circuits or sparking.Loose mounting screws
at the ballasts can cause hum.In very dusty surroundings the ballast
can become overheated and should be cleaned.
It is advisable to renew the glow-switch starter(s) at the moment of
lamp replacement.
The voltage required for ionization during the starting process may
be affected by dirty lamps,excessive moisture or a combination of
both.In installations with considerable dust accumulation,the lamps
have to be cleaned regularly for reliable starting.Also clean the
equipment at lamp replacement.