87
65
The Self-Diagnosis Function Display and What is Detected
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote
controller is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for
the indoor unit or to Test Run or servicing materials.
●
: Off / ○: On / ◎: Blinking (0.5 sec. intervals)
Common to All Models
The indoor unit and the wireless remote controller are equipped with
indoor temperature sensors. The sensing of indoor temperature works
via one of them.
When the unit is shipped, it is set to the indoor unit, but to switch to
the remote controller, press the sensor button (diagram at right) inside
the remote controller’s cover and then check to make sure that Main
Sensor on the LCD screen goes off.
<Note> Even when the sensor switch has been set to the remote
controller, if the unit does not receive any room temperature
data from the remote controller for ten minutes, it
automatically switches back to the indoor unit sensor, so be
sure to install the remote controller facing the receiver.
Error Detected WL Remote Control LED Display
Alarm Display Run Timer Standby Blinking
Communication error in the remote control
circuit
E01–E03, E08–E14, E17, E18
◎●●
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16, E19–E31
●●◎
Operation of indoor protection device P01, P09–P14
●◎◎
Alternately
Operation of outdoor protection device P02–P08, P15–P31
◎●◎
Alternately
Error in the indoor thermistor F01–F03, F10–F11
◎◎●
Alternately
Error in the outdoor thermistor F04–F09, F12–F28
◎◎○
Alternately
Error in the indoor EEPROM F29
◎◎●
Simultaneously
Error in the outdoor EEPROM F30, F31
◎◎○
Simultaneously
Error related to the compressor H01–H31
●◎●
Error in indoor settings L01–L03, L05–L09
◎●◎
Simultaneously
Error in outdoor settings L04, L10–L31
◎○◎
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model without
auto-temp settings)
○◎◎
Alternately
Oil Alarm (Same as operation of outdoor protection device)
◎●◎
Alternately
Test Run
◎◎◎
Simultaneously
Room Temperature Sensor Settings
Sensor Button
Setting Up Remote Control Functions
The functions of the wireless remote can be set on site.
(These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are
changed, the settings do not revert to the defaults.)
<Note> The operation of the air conditioner can be impacted, depending on the settings made, so only service
personnel should make the settings.
Furthermore, making changes to these settings may cause actual operation to deviate from what is
printed in the Operating Instructions, so be sure to explain this to the customer fully.
Making Settings (Do with unit stopped.)
1. Holding down the Swing/Wind Direction + OFF Timer + Mode Select buttons at the same time for 4 or more
seconds makes the display switch to the setting screen. (See Diagram Below.)
2. Use the Temperature setting buttons,
/ , to select the number of the item to be set.
3. Use the ON Timer buttons,
/ , to change settings.
4. The settings are saved with the Once/Every Day button. When this is done, the settings display of the LCD
changes from blinking to light.
5. If other settings are to be changed as well, repeat steps 2 to 4.
6. When all settings have been made, press the Start/Stop button.
Example: Operation mode setting screen
Note 1 While the unit is in the swinging mode (Swing/Wind Direction), the fl ap cannot be stopped in a desired
position.
Note 2 When Setting OFF is selected, “°C” is displayed on the LCD screen.
Note 3 You can toggle between ON and OFF by pressing Ventilation for 4 seconds or more.
Note 4 If the Heater Max ON/OFF setting is not changed to EP (ON), the setting change will not be refl ected.
Note 5 This is the number of addresses that can be set in the address change mode. Do not set it to 07 or
above.
Item Number & Setting Item Setting Content Setting when
Shipped
1
Operation Mode
2
Flap Display
3
Select Fan Speed
4
Display of Set
Temperature
°F
Setting Off (Note 2) °C °F
5
Time Display AM/PM
24 Hour (No Display) AM/PM
6
Ventilation Fan ON/OFF Off (No Display)
On OFF
(Note 3)
7
Cool temp Max 41 – 95°F 86°F
8
Cool temp Min 41 – 95°F 64°F
9
Heat temp Max 41 – 95°F 78°F
(Note 4)
10
Heat temp Min 41 – 95°F 60°F
11
Dry temp Max 41 – 95°F 86°F
12
Dry temp Min 41 – 95°F 64°F
13
Auto temp Max 41 – 95°F 80°F
14
Auto temp Min 41 – 95°F 62°F
16
Address Setting Max
Value
00 (ALL only)
01 – 31 06 (Note 5)
17
Heat temp Max ON/OFF JP (Heater Max Temp Change Off)
EP (On)
JP
1
4
3
2
6
(Note 1)
(No Display)
(No Display)
Item
Number
Printed in Japan
85464369520011