Panasonic CZ-RWSD2U installation

Installation Instructions Wireless Remote Controller
Model No.
CZ-RWSD2U
1-1.
Part Names
(2) Emergency operation button
Starts/Stops emergency operation.
(1) Light receiving section
Receives signals.
Safety Precautions
Read before installation
Read the Installation Instructions carefully
to install the remote controller correctly and
safely.
Be sure to read the Safety Precautions in
particular before installation.
After the installation is complete, perform
test operation to conrm that no abnormality is present.
We assume no responsibility for accidents
or damages resulting from methods other than those described in the installation instructions or methods without using
specied parts.
Malfunctions that occurred due to the
unauthorised installation methods are not
covered by the product warranty.
Read the installation instructions supplied
with indoor units as well.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal
injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or
product or property damage.
85464369842010
WARNING
• Turn o the circuit breaker of the units before installation.
• Ask your dealer or professionals for installation and electric work.
• This controller shall be installed in
accordance with National Wiring
Regulations.
• Connect and x the specied cables for wiring securely.
• Do not allow the connection to be exposed to the external force of the cables.
• Choose an installation location that suciently supports the weight of the remote controller.
CAUTION
Do not use the remote controller at the
following locations.
• Location where condensation occurs
• Location where ammable gases, etc. may
leak
• Location where corrosive gases, etc. may
leak
• Location with lots of water or oil droplets
(including machine oil)
• Location where voltage uctuation
frequently occurs
• Location where there is a machine
producing electromagnetic radiation
• Location where droplets of organic
solvents spread
• Location where acidic or alkaline solutions
or special sprays are frequently used
Do not operate with wet hands.
Do not wash with water.
Printed in Japan DC0815-0 CV 6233317731
(3) Indication lamp
Indicates operation status.
1-2. Supplied accessories
Supplied accessories
Wireless Remote
Controller
(1)
Remote Control
Holder
(1)
AAA Size
Battery
(2)
1-3. Settings
Before installing the receiver, see the

sections on “Wiring for the Receiver” and
“Setting Address Switches”. Then check the setting of the [S003] DIP switch on the receiver’s PCB.
* Remove the cover from the receiver when
performing the PCB settings.
Operating
Instructions
(1)
Set its address
(1) to (3)
Wood Screw
(2)
All set at OFF
when shipped
from the factory.
↑ON
Main/Sub selector
switch for remote
controllers (4) OFF: Main ON: Sub
Clamper
(1)
- 1 -
1-4. Wiring for the Receiver
Wiring Diagram
Receiver PCB
CN001
2P white
Terminals for RC wiring
Indoor unit
1 2
How to Connect the Wires
Connect the wires from the receiver to the terminals for RC
wiring
on the indoor unit. (No polarity)
Installation Location for the Reciver
The wireless remote controllers use a very weak infrared light for its signal, which can result in the signal
not being received because of the following inuences, so take care in where the unit is installed.
• Inverter or rapid-start type uorescent lights (Models without glow lamps)
• Plasma display or LCD televisions
• Direct sunlight or other sources of bright light
Attention
Multiple wireless remote controllers cannot be used simultaneously for a single indoor unit.

Be careful not to connect cables to other terminals of indoor units (e.g. power source wiring terminal). Malfunction may occur.

Do not bundle together with the power source wiring or store in the same metal tube. Operation error may occur.

If noise is induced to the unit power supply, attach a noise lter.
*Wiring shown below is prohibited.
Wired RC Receiver
1 2 1 2
RC wiring
R1 R2
Indoor unit Indoor unit Indoor unit
R1 R2 R1 R2
1 2
Receiver
- 2 -
1-5. Installing the Receiver
1 While spreading the tabs of the cover, pull it out from the panel to the front. (Fig. A) 2 When installing on the 1-WAY cassette (high-ceiling), pass the lead wire through the panel and
install the receiver in the hole in the panel. (The projecting parts of the receiver are xed in the hole in the panel.)
3 Route the lead wire from the receiver along the rib on the back of the panel. Pass it through the
cutout. (Fig. B) 4 Install the panel on the indoor unit. 5 Fasten the lead wire sticking out from the panel with the clamper in the indoor unit. (Fig. C)
6 Draw the lead wire into the electrical box through the hole on the bottom and connect it to the
remote controller terminal board.
When installing to the 1-WAY cassette (high-ceiling), fasten the wire at the latch of the fan
casing with the supplied clamper. (Fig. D)
Fig. A Fig. B
Spread
Pull out from the
panel.
Fig. C
1-WAY cassette
(high ceiling)
1-WAY cassette
Cover
Spread
Insert the lead
wire.
Fig. D
1-WAY cassette
(high ceiling)
( Back
Receiver
Rib
Cutout
Fan casing
of the
panel)
Insert the lead
wire.
1-WAY cassette
Rib
Receiver
Installation when setting Main/Sub for the remote controller and the receiver
 Using 1 indoor unit
Installation example
After installation, according to the “Settings” section, set one to [Main] and the other to [Sub]. Setting the wired remote controller to [Main] is recommended.
Note
Receiver (Sub) Receiver (Sub)
The remote controller and the receiver can be connected to any indoor unit for operation.
RC wiring
(eld supply)
No polarity
Wired RC (Main)
1 21 2
R1 R2
Indoor unit
Terminals for
 Using more than 1 indoor unit
1 2 1 2
RC wiring
Indoor unit Indoor unit Indoor unit Indoor unit
- 3 -
RC wiring (eld supply)
No polarity
Wired RC (Main)
R1 R2R1 R2R1 R2R1 R2
Fasten the wire
at the latch of the fan casing with supplied
Clamper
Fasten the lead wire securely so that it does not get wrapped up in the fan.
For more information about wiring and test operation, see the sections on “Wiring for the Receiver” and
clamper.
“Test Operation”.
- 4 -
1-6. Setting Address Switches
When more than 1 receiver is installed in the same room, setting addresses prevents
interference. For how to change addresses of wireless remote controllers, see the operating instructions of
wireless remote controllers.
To change the receiver’s address, remove the cover from the receiver’s PCB and set No.1 to
No.3 of the [003] DIP switch on PCB.
Remote Controller Address Display
Position of the receiver’s address switch
Address Address Address Address Address Address Address
ALL 1 2 3 4 5 6
Receipt is possible at all of the address positions
1234
1234
1234
1234
1234
1234
ON/OFF
States
OFF ON
1-7. Test Operation
Preparation:
1. To start test operation, press and hold the emergency operation button for 10 seconds.
2. The indication lamps (OPERATION, TIMER, STANDBY) blink during test operation.
3. To nish test operation, press and hold the emergency operation button for 10 seconds.
Attention
 Do not use this mode for purposes other than
the test operation. (To prevent overload of the units) Read the installation instructions supplied with the units.
Any of the Heat, Cool and Fan operations can
only be performed.
Turn on the circuit breaker of units and then turn the power on. After the power is turned on, remote controller operation is ignored for approx. 1 minute because setting is being made. This is not malfunction. (Contents received while setting are disabled.)
Temperature cannot be changed.  The test operation mode is automatically
turned o in 60 minutes. (To prevent continuous test operation) Outdoor units do not operate for approx. 3
minutes after the power is turned on or
operation is stopped.
1-8.
Self-diagnostics table and detected contents
 The “Alarm Display” shown in the table below expresses the alarm contents displayed when the
wired remote controller is connected. For how to handle the alarms, see installation instructions of indoor units or technical guide.
Detected contents Indication lamp on the receiver
Alarm Display
Communication error in the remote controller circuit
Communication error either in the in/ outdoor operation line or the sub-bus of the outdoor unit
Operation of indoor protection device
Operation of outdoor protection device P02–P08, P15–P31
Error in the indoor thermistor F01–F03, F10–F11
Error in the outdoor thermistor F04–F09, F12–F28
Error in the indoor EEPROM F29
Error in the outdoor EEPROM F30, F31
Error related to the compressor H01–H31
Error in indoor settings L01–L03, L05–L09
Error in outdoor settings L04, L10–L31 Error in the gas heat pump air
conditioner
Inconsistency in Cooling/Heating (Including an auto-temp setting for a model without auto-temp settings)
Oil alarm (Same as operation of outdoor protection device)
Test operation
: OFF : ON (Illuminated) : Blinking (0.5 seconds interval)
1-9.
Room Temperature Sensor Settings
The indoor unit and the wireless remote controller are equipped with
E01–E03, E08–E14, E17, E18
E04–E07, E15, E16, E19–E31
P01, P09–P14
A01-A31
OPERATION TIMER STANDBY
◎ ◎ ◎ ◎ ◎ ◎ ◎ ◎
◎ ◎
◎ ◎
Blinking
Alternately
Alternately
Alternately
Alternately
Simultaneously
Simultaneously
Simultaneously
Simultaneously
Simultaneously
Alternately
Alternately
Simultaneously
room temperature sensors. The sensing of room temperature works
via one of them.
When the unit is shipped, it is set to the indoor unit. To switch it to the
remote controller, press the sensor button (the gure on the right)
inside the remote controller’s cover and then check that Main Sensor
on the LCD screen goes o.
<Note> Be sure to install the remote controller so as to face the
receiver.
Sensor button
If the unit does not receive any room temperature data from
the remote controller for ten minutes even with its sensing function activated, the indoor unit sensor will automatically
start sensing the room temperature.
- 5 -
1-10.
Setting Up Remote Controller Functions
The functions of the wireless remote controller can be set on site. (These settings are saved in nonvolatile memory in the remote controller. Therefore, the settings do not revert to the defaults even when its batteries are changed.) <Note> Only service personnel should make the settings because the operation of the air
conditioner may be aected, depending on the settings made. Furthermore, making changes to these settings may cause actual operation to deviate from what is printed in the Operating Instructions, so be sure to fully explain this to the customer.
Making Settings (Do with unit stopped)
(1) Holding down the swing/ap ( ) + OFF timer ( ) + mode select ( ) buttons at the
same time for 4 or more seconds will open the setting screen. (See gure below.) (2) Use the Temperature setting buttons (3) Use the ON timer buttons
/ ( ) to change settings.
/ (
(4) The settings are saved with the once/every day button (
) to select the number of the item to be set.
). When this is done, the SET
displayed on the LCD changes from blinking to lighting. (5) If other settings are to be changed, repeat steps (2) to (4). (6) When all settings have been made, press the start/stop (
) button.
Operation procedure and function display
Factory
setting
AM/PM
86°F (30°C) 64°F (18°C) 86°F (30°C)
(*4) 60°F (16°C) 86°F (30°C) 64°F (18°C) 80°F (27°C)
62°F (17°C)
JP
(3)
(4)
Item Number
(6)
(2)
(1)
Detected contents Set Contents
1 Operation
Mode
2 Flap Display
3 Select Fan
Speed
4 Display of Set
Temperature 5 Time Display 6 Ventilation Fan
ON/OFF 7 Cool temp Max 41 to 95°F (05 to 35°C) 8 Cool temp Min 41 to 95°F (05 to 35°C) 9 Heat temp Max 41 to 95°F (05 to 35°C)
10 Heat temp Min 41 to 95°F (05 to 35°C) 11 Dry temp Max 41 to 95°F (05 to 35°C) 12 Dry temp Min 41 to 95°F (05 to 35°C) 13 Auto temp Max 41 to 95°F (05 to 35°C)
14 Auto temp Min 41 to 95°F (05 to 35°C)
16 Address Setting
Max Value
17 Heat temp Max
ON/OFF
(No Display)
(*1)
°F Setting O (*2) °C °F
AM/PM 24 Hour (No Display) OFF (No Display)
00 (ALL only) 01 to 031 06(*5)
JP (Heater Max Temp Change O)
EP (ON)
(No Display)
ON OFF (*3)
<Note 1> While the unit is in the SWING mode (swing/ap), the ap cannot be stopped in a
desired position. <Note 2> When Setting OFF is selected, “°C” is displayed on the LCD. <Note 3> You can toggle between ON and OFF by pressing ventilation “(
) button” for 4 seconds
or more. <Note 4> If the Heater Max ON/OFF setting is not changed to EP (ON), the setting change will
not be reected. <Note 5> This is the number of addresses that can be set in the address change mode. Do not
set it to 07 or above.
- 7 -
- 6 -
1-11.
Installing Wireless Remote Controller
Installation location for the Wireless Remote Controller
If a remote controller is to be operated from a remote control holder that is hung on a wall, turn on the lights in
the room as well as any electrical appliances and then check to make sure the air conditioner works with the
remote controller in the location where it will be installed. If it works, continue with installation.
If the main sensor is to be switched from the indoor unit to a remote controller, pay attention to the following
when installing.
Locate where no warm or cold air will aect it.
Locate in a place free from direct sunlight.
Locate where it will not be aected by any other heat/cold source.
1-12.
When installing the remote controller onto a wall, etc.
Screw the remote control
holder.
Remote control holder
Wireless Remote Controller
Dimensions
Weight 140g (Including batteries) Power Source Two AAA size batteries Clock Accuracy ±30 seconds / month (at 77°F (25°C))
Receiver
Dimensions
Weight 82g Power Source DC16V(supplied from indoor unit)
Installing the remote controller
2
Press
1
Insert
1-13.
Specications
(H) 7-11/64” × (W) 2-13/32” × (D) 47/64” ((H)182 mm × (W) 61 mm × (D)18.5 mm)
(H) 2-9/16” × (W) 5-1/8” × (D) 55/64” ((H) 65 mm × (W)130 mm × (D) 22 mm)
Press
on the wall, and check that normal
receiving is possible.
Remove the remote controller from the
remote control holder.
- 8 -
at the installation location
Loading...