DIN Track Mounted, Standard 17.5-mm Width Timer Range
• A wide AC/DC power supply range (24 to 230 VAC/ 24 to 48 VDC) reduces the number of timer models kept in stock.
(24 to 230 VAC/VDC with H3DS-XL@)
• Smart Dial/Selector-locking Mechanism: Prevents the dials and selectors on the Timer’s front panel from being inadvertently
operated or being operated without authorization. The lock can only be unlocked and locked with an optional pen-type Lock Key.
• Screw-Less Clamp type available. (H3DS-@LC)
• Sticker provided for easy timer identification and management.
• Terminal clamp left open when delivered (screw terminal type).
• Finger protection terminal block to meet VDE0106/P100.
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
Note: Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
B: Flicker OFF start (Signal or Power)
B2: Flicker ON start (Signal or Power)
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval (Signal or Power)
G: Signal ON/OFF-delay
J:One-shot (Signal or Power)
Screw terminal type:Clamps two 2.5-mm
Screw-Less Clamp type: Clamps two 1.5-mm
0.98 N·m max.
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5 A/AC-14; 250 V 1 A/AC-15; 250 V 1 A/DC-13; 30 V 0.1 A/
DC-14; 30 V 0.05 A)
A: ON-delay
B2: Flicker ON start
E: Interval
J:One-shot
2
max. bar terminals without sleeves.
2
max. bar terminals without sleeves.
A: ON-delay (fixed)
Timers
■ Time Ranges
Time scale displayTime range
0.1 s0.1 to 1.2 s
1 s1 to 12 s
0.1 m0.1 to 1.2 min
1 m1 to 12 min
0.1 h0.1 to 1.2 h
1 h1 to 12 h
10 h10 to 120 h
Note: When the time setting dial is set to “0” for any time scale, the output will operate instantaneously.
■ Ratings
Rated supply voltage
(see notes 1 and 2)
Operating voltage range85% to 110% of rated supply voltage
Power resetMinimum power-off time: 0.1 s
Reset voltage2.4 VAC/DC max.
Power consumption (see note 3)AC: 32 VA max./3.0 W max. (typical: 30 VA/2.7 W) at 230 VAC
Voltage inputMax. permissible capacitance between inputs lines (terminals B1 and A2): 2,000 pF
Control outputContact output: 5 A at 250 VAC with resistive load (cosφ = 1)
Ambient temperatureOperating: –10°C to 55°C (with no icing)
Ambient humidityOperating: 35% to 85%
Note: 1. DC ripple rate: 20% max.
2. Since an inrush current of 0.5 A will occur when using the power supply voltage at 24 VDC, pay careful attention when turning on or off
the power supply to the Timer with a solid-state output such as a sensor.
3. The power consumption is for mode A after the Timer counts the time-up time and for the AC input at 50 Hz. The power consumption of
the H3DS-ML includes the input circuit with the B1 and A1 terminals short-circuited.
24 to 230 VAC (50/60 Hz)/24 to 48 VDC
14 VA max./2.2 W max. (typical: 13 VA/2.1 W) at 100 to 120 VAC
DC: 0.7 W max. (typical: 0.6 W) at 24 VDC
1.4 W max. (typical: 1.3 W) at 48 VDC
Load connectable in parallel with inputs (terminals B1 and A1).
H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC
L-level: 0 to 2.4 VAC/DC
Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range)
Setting error±10% ±50 ms max. of FS
Signal input time50 ms min.
Influence of voltage±0.7% max. of FS (±0.7% ±10 ms max. at 1.2-s range)
Influence of temperature±5% max. of FS (±5%±10 ms max. at 1.2-s range)
Insulation resistance100 MΩ min. at 500 VDC
Dielectric strengthBetween current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.
Vibration resistanceMalfunction: 0.5-mm single amplitude at 10 to 55 Hz
Shock resistance
Impulse withstand voltage3 kV (between power terminals)
Life expectancyMechanical: 10 million operations min. (under no load at 1,800 operations/h)
EMC(EMI)EN61812-1
Case colorLight gray (5Y7/1)
Degree of protectionIP30 (Terminal block: IP20)
WeightApprox. 70 g
Note: For reference:
A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
Between control output terminals and operating circuit: 2,000 VAC for 1 min.
Between contacts not located next to each other: 1,000 VAC for 1 min.
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
2
Malfunction: 100 m/s
Destruction: 1,000 m/s
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Destruction: 8 kV
Electrical:100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
(see note)
Emission Enclosure:EN55011 Group 1 class B
Emission AC Mains:EN55011 Group 1 class B
Harmonic Current:EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS)EN61812-1
Immunity ESD:EN61000-4-2: 6 kV contact discharge (level 3)
Immunity RF-interference from AM Radio Waves:
Immunity Burst:EN61000-4-4: 2 kV power port and output port (level 3)
Immunity Surge:EN61000-4-5: 2 kV common mode (level 3)
The selectors can be turned clockwise and counterclockwise to
select the desired time scale, or operating mode.
Each selector has a snap mechanism that secures the selector at a
given position. Set the selector at a position at which it is secured. Do
not set it midway between two securing positions or a malfunction
could result from improper setting.
Selection of Operating Mode (except
for H3DS-AL)
The H3DS-ML/-SL can be set to any one of the operating modes A to
J. Turn the operating mode selector with a screwdriver until the
desired operating mode appears in the operating mode display window.
H3DS-ML (8 modes): A, B, B2, C, D, E, G, J
(In order of appearance)
H3DS-SL (4 modes): A, E, B2, J, E, E, J, J
(In order of appearance)
Note: Letters that appear more than once indicate exactly the same
operating mode.
Selection of Time Scale
The time scale is selected by turning the time scale selector. The
time scales will appear in the following order in the time scale display
window on the left of the selector:
1 s, 0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m, 0.1 m.
Note: The time scale “1h” appears twice. Both instances indicate ex-
actly the same time scale.
Locking/Unlocking of Selectors and
Time Setting Dial
The time setting dial, time scale selector, and operating mode selector can be locked using the Y92S-38 Lock Key, a special pen type
tool that is sold separately. To lock the dial or selectors, insert the
Lock Key in the keyhole to the lower right of the dial or selector and
turn it clockwise until the dial or selector is completely covered with
the red cover. To unlock, turn the Lock Key in the opposite direction.