Nordyne M1M, M1G, M1B, M1S User Manual 2

Downflow, Direct Vent (Sealed Combustion) Forced Air Gas and Oil Furnaces
Owners Manual/Installation Instructions
Series M1B, M1G, M1M and M1S
For installation in:
1. Manufactured Homes
2. Recreational Vehicles, Park Models, Manufactured Buildings
3. Modular Homes/Buildings
!
WARNING:
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
– Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appli­ance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your build­ing.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fire department.
– Installation and service must be per-
formed by a qualified installer, ser­vice agency or the gas supplier.
!
WARNING:
!
WARNING:
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical sup­ply.
Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Re­fer to this manual. For assistance or additional information consult a quali­fied installer, service agency or the gas supplier.
LEAVE THESE INSTRUCTIONS WITH THE HOMEOWNER.
TABLE OF CONTENTS
1. SPECIFICATIONS ...................................................................................3
2. OWNERS INFORMATION ....................................................................... 3
3. MANUFACTURER WARRANTY, OWNER RESPONSIBILITY .................3
4. INSTALLATION STANDARDS ................................................................. 5
5. UNIT LOCATION .....................................................................................6
6. MINIMUM CLEARANCES ........................................................................ 6
7. RETURN AIR PROVISIONS .................................................................... 6
8. AIR DISTRIBUTION SYSTEMS .............................................................. 8
9. ROOF JACK SELECTION ....................................................................... 8
10. DUCT CONNECTOR SELECTION ........................................................... 9
11. INSTALLATION ..................................................................................... 11
12. INSTALLATION OF TRANSIT-MODE VENTING SYSTEM ................... 14
13. ELECTRICAL WIRING ........................................................................... 15
14. FUEL PIPING ........................................................................................ 16
15. FLUE GAS SAMPLING.......................................................................... 19
16. LIGHTING AND FURNACE SHUT DOWN .............................................. 20
17. SERVICE GUIDE ................................................................................... 25
18. MAINTENANCE ..................................................................................... 30
19. OPTIONAL ACCESSORIES .................................................................. 31
20. WIRING DIAGRAMS ......................................................................... 34-39
21. EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES .......................... 40
M 1 M B - 056 A - B W
Application
M-Manufactured Home
Furnace Series
Fuel, Type of Combustion
G-Gas, Direct Vent, Pilot Burner Natural or Forced Draft M-Gas, Direct Vent, HSI, Forced Draft B-Gas, Direct Vent, Gun Burner S-Oil, Direct Vent, Gun Burner
Comfort Model
H - Heating A - Heating, A/C Ready B - A/C Ready, 3 Ton C - A/C Ready, 4 Ton D - A/C Ready, 5 Ton
2
Door Color
W - White G - Gray
Cabinet Dimensions
A - 56" x 19-3/4" x 23-3/4” B - w/Coil Cavity, 76" x 19-3/4" x 23-3/4"
Electrical Code
A - 1PH, 60 Hz, 120 VAC
Heating Capacity
Input, BTUH (000’)
Table 1. Model Identification
!
WARNING:
Do not use this appliance if any part has been submerged under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been submerged underwater.
NOTICE TO INSTALLER
Installer is advised to follow carefully all instruc­tions and warnings in this manual to insure maximum performance, safety, and operating efficiency of these appliances. Improper instal­lation may create hazardous conditions, and will void the appliance warranty.
1.SPECIFICATIONS
General Description
M1 Series gas and oil furnaces are listed direct vent (sealed combustion), downflow heating appliances for manufactured (mobile) homes, recreational vehicles, and for use in residential/ modular/commercial construction. The furnace must be located so that venting can be properly achieved.
Air conditioning may be added to structures with M1 series furnaces using Platinum series air conditioning or conventional units. This Instal­lation Instruction manual includes special re­quirements for incorporation of air conditioning equipment to the M1 series of furnaces.
Multi-speed blower assemblies as shown in Table 3 have been certified for field installation in M1 Series furnaces. An air conditioner can be easily field installed with M1GH Series furnaces if used in conjunction with certified 2-wire relay box, p/n 903092A or 4/5 wire relay box 902898A.
2. OWNER INFORMATION ABOUT YOUR CENTRAL FURNACE SYSTEM
NORDYNE has been involved in the design of products for the manufactured home industry since the first manufactured home or trailer was built.
NORDYNE originated the sealed combustion system, which separates the furnace combus­tion system from the living area of the home, now a standard for the manufactured home industry.
NORDYNE engineers developed the first cen­tral heating system and the first central air conditioner for manufactured homes.
NORDYNE is dedicated to bringing to its cus­tomers the finest heating and cooling comfort possible. NORDYNE constantly seeks to fur­ther refine its products to continuously provide exceptional comfort.
Follow the instructions in this booklet carefully and this appliance will provide many years of superior performance.
If you wish to cool your home automatically with a central air conditioning system investigate the excellent NORDYNE cooling systems avail­able from your heating and cooling contractor. These systems are designed to work best with your NORDYNE furnace and have been care­fully engineered to deliver optimum performance when mated with NORDYNE manufactured home furnaces.
NORDYNE also offers water heaters, fire­places and ventilating systems specifically de­signed for manufactured housing applications. Check with your manufactured home retailer, your heating and cooling contractor or your distributor for information. Write directly to the factory (PO Box 46911, St. Louis, MO 63146) if you are not able to locate a source for NORDYNE manufactured housing products in your area.
3. MANUFACTURER WARRANTY, OWNER’S RESPONSIBILITIES
It is the sole responsibility of the homeowner to make certain the gas furnace has been cor­rectly set up and converted to the proper fuel (L.P. gas or Natural gas) and adjusted to oper­ate properly. All gas furnaces are manufac­tured for Natural gas and must be field con­verted when using L.P. gas.
A warranty certificate with full details is included with these instructions. However, NORDYNE will not be responsible for any costs found
3
necessary to correct problems due to improper setup, improper installation, furnace adjust­ments, improper operating procedure on the part of the user, etc.
5. Correcting problems due to improper gas
supply pressure to the furnace.
6. Providing instructional training on how to
light and operate the furnace.
7. Furnace problems caused by installation of
Some specific examples of service calls which cannot be included in warranty payments are:
an air conditioner, heat pump or other air comfort devices.
8. Adding a Roof Jack extension because of
1. Converting the furnace to use another type of gas.
2. Repairing duct work in the home found to be faulty.
3. Correcting wiring problems in the electrical circuit supplying the furnace.
unusual wind and/or snow conditions.
9. Revising installation of the furnace flue as­sembly (Roof Jack).
10. Adjusting or calibrating of thermostat.
11. Any construction debris which falls into flue system.
4. Resetting circuit breakers, blown fuses or other switches.
Furnace Input Output Orifice No E.S.P. Pilot Ignitor Comb. Motor A/C Ready
Model No MBtu/h MBtu/h Nat. LP In WC Burner Direct Blower Hp Tons
M1GH 056 56 45 29 45 0.3 x 1/8 2* M1GB 056 56 45 29 45 0 .3 x 1/4 3 M1GC 056 56 45 29 45 0.3 x 1/2 4 M1GD 056 56 45 29 45 0.3 x 3/4 5 M1GH 070 70 57 24 42 0.3 x 1/5 2½* M1GB 070 70 57 24 42 0 .3 x 1/4 3 M1GC 070 70 57 24 42 0 .3 x 1/2 4 M1GD 070 70 57 24 42 0 .3 x 3/4 5 M1GH 077 77 62 21 40 0 .3 x x 1/4 3* M1GB 077 77 62 21 40 0.3 x x 1/4 3 M1GC 077 77 62 21 40 0 .3 x x 1/2 4 M1GD 077 77 62 21 40 0 .3 x x 3/4 5 M1GH 090 90 72 17 36 0 .3 x x 1/4 3* M1GB 090 90 72 17 36 0.3 x x 1/4 3 M1GC 090 90 72 17 36 0 .3 x x 1/2 4 M1GD 090 90 72 17 36 0 .3 x x 3/4 5 M1MA 056 56 46 29 45 0.3 x x 1/8 2 M1MB 056 56 46 29 45 0.3 x x 1/4 3 M1MC 056 56 46 29 45 0.3 x x 1/2 4 M1MD 056 56 46 29 45 0.3 x x 3/4 5 M1MA 070 70 57 24 42 0.3 x x 1/5 2½ M1MB 070 70 57 24 42 0.3 x x 1/4 3 M1MC 070 70 57 24 42 0.3 x x 1/2 4 M1MD 070 70 57 24 42 0.3 x x 3/4 5 M1MB 077 77 62 21 40 0.3 x x 1/4 3 M1MC 077 77 62 21 40 0.3 x x 1/2 4 M1MD 077 77 62 21 40 0.3 x x 3/4 5 M1MB 090 90 72 17 36 0.3 x x 1/4 3 M1MC 090 90 72 17 36 0.3 x x 1/2 4 M1MD 090 90 72 17 36 0.3 x x 3/4 5
M1BA 066 66 53 26 43 0.3 x x 1/5 2½ M1BB 066 66 53 26 43 0.3 x x 1/4 3
M1BC 066 66 53 26 43 0.3 x x 1/2 4
M1BB 086 86 68 18 37 0.3 x x 1/4 3
M1BC 086 86 68 18 37 0.3 x x 1/2 4
M1SA 066 66 54 M1SB 066 66 54
M1SC 066 66 54
M1SB 086 86 71
M1SC 086 86 71
.50 Gph
.50 Gph .50 Gph .65 Gph .65 Gph
0.3 x 1/5
0.3 x 1/4 3
0.3 x 1/2 4
0.3 x 1/4 3
0.3 x 1/2 4
Burner Model AF-10 Nozzle
Spray Angle
80° A
Electrical Supply - 120 volts, 60HZ, 1 Ph. Fuse or Breaker - 15 amps Temperature Rise - 45° to 75°F High Altitude - See Table 11. For Canadian High Altitude (2,000’ to 4,500’), reduce the gas manifold pressure to 3.0” W.C. for natural gas and to 8” W.C. for LP gas.
Table 2. M1 Furnace Specifications
4
Thermostat Circuit - 24 volts, 60HZ, 30 vac Normal Anticipator Setting - 0.4 Manifold Pressure - Natural Gas: 3.5” w.c. LP Gas: 10” w.c. *Blower capacity only - needs relay box for AC
Part No.
Blower / Motor Assembly
Blower Wheel Motor-Hp Ton
903773 10 x 8 1/4 2, 2½ & 3 903413 11 x 8 1/2 2, 2½, 3 & 4 903414 11 x 8 3/4 2, 2½, 3, 4 & 5
Table 3. Field Installation Blower Assemblies
Carefully review these responsibilities with your manufactured housing dealer, service com­pany or gas supplier so there will be no misun­derstanding at a later time.
6" (152 mm)
Top Clearance
A/C Capacity
!
CAUTION:
• Never attempt to alter or modify this furnace or any of its components.
• Never attempt to repair damaged or inoperable components. Such action could cause unsafe operation, explo­sion, fire and/or asphyxiation.
• If a malfunction has occurred, or if you feel that the furnace is not oper­ating as it should, contact a qualified service agency or gas utility for as­sistance.
4. INSTALLATION STANDARDS
Installer shall be familiar with and comply with all codes and regulations applicable to the instal­lation of these heating appliances and related equipment. In lieu of local codes, the installation shall be in accordance with the current provi­sions of one or more of the following standards.
0" Side Clearance to Furnace Cabinet
Figure 2. Alcove Installation
6" (152 mm)
Top Clearance
0" Side Clearance to Furnace Cabinet
Removable access panel should be installed above furnace door frame to access roof jack
18"
(457 mm)
Provide min. 235 sq. in. (1516 cm ) open free area in front or side wall
6"
(152 mm)
Nearest Wall or Partition
2
or In closet
door located at top, center or bottom
CLOSET DOOR
“A”- 56"
“A” Model­w/o Coil Cabinet
“B” Model­w/Coil Cabinet
19 3/4"
Figure 1. Overall Dimensions
“B”- 76"
23 3/4"
Figure 3. Closet Installation
6" (152 mm)
Top Clearance
0" Side Clearance to Furnace Cabinet
(25 mm)
Figure 4. Special 1” Clearance
Provide min. 250 sq. in. (1613 cm ) open free area in front or side wall
1"
2
or in closet door
a fully louvered door may be used
CLOSET DOOR
5
A Single trunk duct
B
Dual trunk duct w/crossover connector
C
Transition duct w/branches
a. Federal Manufactured Home Constructions
& Safety Standard (H.U.D. Title 24, Part
3280.707[a][2])
b. American National Standard (ANSI-119.2/
NFPA-501C) for all recreational vehicle in­stallations.
c. American National Standard (ANSI-Z223.1/
NFPA-54) and/or CAN/CGA B149 for all gas­fired furnace models.
d. American National Standard (ANSI-Z95.1/
NFPA-31) and/or CSA B139 for all oil-fired furnace models.
e. American National Standard (ANSI-C1/
NFPA-70) and/or CSA 22.1 Canadian Elec­tric Code Part 1 for all electrical field wiring.
f. Units have been investigated under stan-
dards UL 307A & B, UL727-1999, ANSI
21.47a - CAN/2.3a - 1995, and CSA B140.10.
5. UNIT LOCATION
The furnace shall be appropriately located to the supply and return air distribution system. (See “AIR DISTRIBUTION”, Page 8) Sides and back of the furnace may be enclosed by wall framing. (See “Minimum Clearances,” Table 4, and Figures 2 through 5.)
The furnace installation is only intended for free air return through the furnace door louvers. DO NOT connect a ducted return air system di­rectly to the furnace. Improper installation may create a hazard and damage equipment, as well as void all warranties.
6. MINIMUM CLEARANCES
This heating appliance must be installed with clearances not less than the minimums shown in Table 4. This heating appliance must be installed with ample clearance for easy access to the air filter, blower assembly, burner assem­bly, controls, and vent connections.
a. Alcove installations (see Figure 2): minimum
18" clearance at front of furnace shall be provided for future servicing. A removable access panel should be installed between top of the furnace door frame and the ceiling.
b. Closet installations must use a louvered door
having a minimum free area of 235 sq. in. when located 6" from furnace (See Figure 3) or 390 sq. in. for 5 ton ready M1 furnaces. For special clearance between 1" and 6", re­quirements are a louvered door with a mini­mum of 250 sq. in. free area, with the open­ings in the closet door in line with the louvered openings in the furnace door . A fully louvered closet door may be used (See Figure 4 and section 7.i. to evaluate compliance with this requirement).
7.RETURN AIR PROVISIONS
U.S.A. home manufacturers shall comply with all of the following conditions to have acceptable return air systems for closet installed forced air heating appliances:
Furnace may be installed on combustible floor­ing when using NORDYNE Duct Connectors (see Section 10).
When installed in a residential garage, the fur­nace must be positioned so the burners and the source of the ignition are located no less than 18 inches above the floor and protected from physical damage by vehicles.
ALL MODELS CLOSET ALCOVE
Front 6" 18" Back 0" 0" Sides 0" 0" Roof Jack 0" 0" Top 6" 6" Top and Sides of Duct 0" 0" Bottom of Duct
B Cabinet 0" 0" A Cabinet (w/ coil box) 0" 0" A Cabinet (w/o coil box) 1/4" 1/4"
Table 4. Minimum Clearances
6
!
CAUTION:
HAZARD OF ASPHYXIATION: Nega­tive pressure inside the closet, with closet door closed and the furnace blower operating on high speed, shall be no more negative than minus 0.05 inch water column.
Figure 5. Non-Platinum
Supply Duct System
a. Regardless of the location, the return air
opening into the closet shall not be less than specified in the appliance’s listing.
b. Means shall be provided to prevent inadvert-
ent closure by a flat object placed over the return air opening when it is located in the floor of the closet (versus the vertical front or side wall).
c. The cross-sectional area of the return duct
system leading into the closet, when located in the floor or ceiling shall not be less than 235 square inches (or 390 square inches for 5 ton ready M1 Furnaces).
d. The total free area of openings in the floor or
ceiling registers serving the return air duct system must be at least 235 sq. in. At least one register should be located where it is not likely to be covered by carpeting, boxes and other objects.
e. Materials located in the return duct system
must have a flame spread classification of 200 or less. This includes a closet door if the furnace is in a closet.
f. Noncombustible pans having 1" upturned
flanges are located beneath openings in a floor duct system.
g. Wiring materials located in the return duct
system shall conform to Articles 300-22 of the National Electrical Code (ANSI C1/NFPA-
70).
ROOF JACK
SLANT DECK
PITCHED ROOF
CEILING CAVITY
"A"
CEILING
"B"
Furnace
FLASHING
"X" (SEE TABLE 1)
ROOF OPENING
Flue Pipe
Combustion
Air Pipe
56" or 76"
Approx. Length
Model Number Below Flashing
(F,S)AW(T)1523-(0,2,4)(A,S) 15" - 23"
(F,S)AW(T)2135-(0,2,4)(A,S) 21" - 35"
(F,S)AW(T)2747-(0,2,4)(A,S) 27" - 47"
(F,S)AW(T)3563-(0,2,4)(A,S) 35" - 63"
(F,S)AW(T)5195-(0,2,4)(A,S) 51" - 95"
F=S=FLAT FLASHING
SLANT FLASHING
AW= ALL WEATHER
SSAW
T
TYPE: BLANK=NON-TRANSIT T= TRANSIT MODE
27
MIN. ADJ. LENGTH
47 - 2
MAX. ADJ. LENGTH
All Weather Roof Jack Assemblies
MODEL APPROX . ADJ.
NUMBER LENGTHS*
FO1323 -5 13" - 23" FO2343 -5 23" - 43" SO1835 -5 18" - 35" SO2447 -5 24" - 47" SO3263 -5 32" -63"
SO4895 -5 48" - 95" SOT2442 -5 24" - 42" SOT2745 -5 27" - 45" SOT4581 -5 45" - 81" FOT2846 -5 28" - 46"
BELOW FLASHING
S O T 27 45 -5
S= SLAT FLASHING F= FLAT FLASHING
O= TYPE; STANDARD H= HIGH WIND A= ARCTIC ROOF JACK
T= TRANSIT
MODE TYPE
MAX. ADJ.LENGTH
MIN. ADJ. LENGTH
FLUE STEEL TYPE A= ALUMINIZED S=STAINLESS
FLASHING PITCH/12" RISE 0=FLAT 2=2.5/12 4=4/12
5 = 5" FLUE DIA.
Figure 6. Roof Jack Assemblies
ROOF JACK
SLANT DECK
PITCHED ROOF
FLASHING
"X" (SEE TABLE 6)
CEILING CAVITY
CEILING
ROOF OPENING
CEILING OPENING
Figure 7. Example of Flat Jack
with Flashing
OOF JACK WITH
1
/12 SLANT
2
LASHING
5/12 ROOF SLOPE
1
/12
2
2
SLANT DECK
Table 5. Roof Jack Assemblies
Figure 8. Example of 2½/12 Slant Jack
with Flashing
7
h. Gas piping is not run in or through the return
(
duct system.
i. Test the negative pressure in the closet with
the air-circulating fan operating at high speed and the closet closed. The negative pressure is to be no more negative than minus 0.05 inch water column.
j. Air conditioning systems may require more
duct register and open louver area to ob­tain necessary airflow. Use NORDYNE’s certiduct program to determine proper duct size for A/C.
8.AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system must be designed so that the static pressure measured external to the furnace does not exceed the listed static pressure rating shown on the furnace rating plate.
b. F=Flat Flashing; flexes from 0/12 to 1/12 roof
slope.
c. S=Slant Flashing. 2.5/12 Slope flexes from 1/
12 to 4/12 roof slope, 4/12 flexes from 3/12
to 5/12. d. Stainless steel roof jacks are available. e. If the roof jack crown is covered or blocked
with snow, the furnace will not operate prop-
erly. If the home is located in regions where
snow accumulation exceeds 7” (HUD
snowload zones) use an external roof jack
extension p/n 901937. f. M1 furnaces may be used with roof jacks as
tall as 170” (except M1M 056 & M1B 066
models, which are limited to 120”). An internal
roof jack extension (p/n 901935 - 10”, p/n
903107 - 18”) can be used to increase roof
jack height. All connections inside the home
must be made below the ceiling.
Location, size, and number of registers should be selected on the basis of best air distribution and floor plan of the home.
!
CAUTION:
HAZARD OF ASPHYXIATION: Do not cover or restrict return air opening.
9.ROOF JACK SELECTION
Note: Install only Roof Jack Assemblies listed in Table 5 on this heating appliance.
a. Determine depth of ceiling cavity from center
of roof opening to center of ceiling opening. (See Dimension “A” in Figure 6.)
b. Determine ceiling height and subtract height
of furnace. (See Dimension “B” in Figure 6.)
c. Add dimensions A + B (and X from Table 6 and
Figure 7 if slant deck flashing is used). The total length of (A + B + X) must be within the minimum and maximum range of one of the Roof Jacks listed in Table 5.
APPLICATION NOTES:
a. FAW, FAWT, SAW and SAWT Series Roof
Jacks with a 5" diameter inner vent pipe may be used with all models of M1 Series gas and oil furnaces.
These extensions are available as optional accessories and may be purchased through your NORDYNE distributor.
IF ROOF PITCH IS: FLASHING NO. "X" FACTOR IS:
2" in 12" 903893 (2.5/ 12) 2-1/8"
2-1/2" in 12" 903893 (2.5/12) 2-1/2"
3" in 12" 903894 (3/12) 2-7/8"
3-1/2" in 12" 903894 (3/12) 3-1/4"
4" in 12" 903895 (4/12) 3-5/8"
"S" Series Roof Jack (2. 5/12 Pi tch only)
4-1/2" in 12" 903895 (2.5/12) 2-1/8"
5" in 12" 903895 (2.5/ 12) 2-1/2"
5-1/2" in 12" 903894 (3/12) 2-7/8"
6" in 12" 903894 (3/12) 3-1/4"
6-1/2" in 12" 903895 (4/12) 3-5/8"
Optional Deck Flashings for Flat and 2.5/12 Pitch
(4/12 Pitch Roof Jacks not applicable.)
USE SLANT DECK
"F Series Roof Jack
Roof Jacks.
Table 6. Slant Deck Flashings
Use Duct Connector
If "X"
Floor Cavity) is:
English Metric (mm)
7/8" 22 901987 904008
2" 51 901988 904009 4-1/4" 108 901989 904010 6-1/4" 159 901990 904011 8-1/4" 210 901991 904012
10-1/4" 260 901992 904013 12-1/4" 311 901993 904014
Model Part Number:
Finger Tab Screw Down
Table 7. Floor Cavity Sizes
8
10. DUCT CONNECTOR SELECTION
PLATINUM SERIES
a. For Platinum ready construction use
the 14” round duct connector, p/n:
903896.
NON-PLATINUM SERIES
a. Determine depth of floor cavity from
surface of floor to top of supply air duct (See Figure 9).
FLOOR CAVITY (depth equal to "X" in Figure 11 and Table 7)
x
SUPPLY AIR DUCT
b. Select appropriate model from Table 7
which matches X-dimension of the floor cavity. To maximize air delivery, re­move reducer “C” (see Figure 11) to obtain the largest open area that will fit the duct/floor construction. Screw down duct connector opening to duct without reducer is 13” x 13”. With reducer it is 13” x 10-1/8”.
*FELT-SEAL
REDUCER
Figure 9.
19”
13 1/4"
10 1/4"
Figure 10.
C
Top View
of
Finger Tab
19"
Duct
Connector
*OPENING TO DUCT
WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4” x 13-1/4”
SPACERS
*INDICATES FINGER TAB DUCT CONNECTOR ONLY
Figure 11.
X
SEE
TABLE 7
9
LT. FUEL INE HOLES
C
L
SIDE WALL
FUEL LINE HOLE
CEILING AND ROOF OPENINGS
C
L
REAR W
FLOOR OPENING
ALL
10"
C
L
13-1/2"
23 -1/4"
C
L
24"
21-3/4"
23-1/4"
1-1/4" D.
ALT FUEL-LINE
14-1/2"
ENTRY
Figure 12. Closet or Alcove
20"
14-1/2"
C
L
REAR WALL OF CLOSET OR ALCOVE
FLOOR CUT-OUT
C
L
FOR DUCT CONN.
CEILING
CUT-OUT FOR
FLUE AND
ROOF JACK
(See Fig 12)
FLOOR CUT-OUT
FOR OPTIONAL COOLING COIL
FOR NON-PLATINUM
SERIES UNITS
C
L
12-7/8"
14-3/4"
15-1/2"
2-1/4"
C
L
10"
2-3/4"
13-1/2"
FURNACE OUTLINE
FUEL-LINE
3/4"
1-3/4"
FURNACE
OUTER DOOR
2"
10
Figure 13. Cut-Out Locations
11. INSTALLATION
REAR WALL
MOUNTING PLATE
FLOOR OPENING
FUEL LINE HOLES
SUPPLY AIR DUCT
CUT DUCT OPENING 1/16TH. LARGER THAN DUCT CONNECTOR
REAR WALL
SUPPLY AIR DUCT
FUEL LINE HOLES
M
OUNTING
PLATE
FLOOR OPENING
UNDER DUCT OPENING
Required floor, ceiling, and roof cut-out open­ings must be carefully located to avoid misalign­ment of the furnace and Roof Jack (see Figures 12 & 13). Installation procedures are suggested for typical furnace installations and need not be followed in the exact listed sequence.
CUT OUT FLOOR OPENING & FUEL LINE HOLE a. Determine center of closet or alcove (Figure
13).
b. Locate center of the floor opening, measured
10" from the rear wall, and mark cut-out measuring approximately 14-1/2" by 14-1/2" (± 1”) for model duct connector used (refer to Figures 10 & 11).
c. Locate center of fuel line hole, measured 23-
1/4" from the rear wall and 6-5/8" to the left of center of the floor cut-out (See Figure 12) or
5-1/4" to the left of center of the floor cut-out, or for entry through right-side of furnace measured 9" to the right of center of the floor cut-out.
d. Cut out floor opening and one fuel line hole.
!
IMPORTANT:
Refer to the installation instructions provided with optional air conditioning packages when installing furnaces with optional cooling coil cabinet or with optional C***-series indoor coils.
CUT OUT CEILING AND ROOF OPENINGS a. Locate center of Roof Jack opening, mea-
sured 13 1/2" from the rear wall of closet or alcove along the center line of furnace and floor opening. (See Figure 13)
Non-Platinum Series
Figure 14. Mounting Plate
MOUNTING PLATE
DUCT CONNECTOR
Platinum Series
Figure 15. Duct Connector
SCREWS
FUEL
LINE
HOLES
14” SUPPLY CONNECTION
11
b. Cut ceiling and roof holes as follows:
Ceiling Hole = 8-3/4" (222 mm) diameter Roof Hole = 9-3/8" (238 mm) diameter
c. DO NOT ALLOW DEBRIS TO FALL INTO
THE FURNACE. THIS COULD CAUSE UNSAFE OPERATION AND VOIDS THE FURNACE WARRANTY. Use the top cap that comes with the furnace packaging (or alternate protector) to prevent debris from falling into the furnace before the final roof jack connection is made.
CUT DUCT OPENING (FINGER TABBED ONLY) a. Place duct connector through the floor open-
ing with bottom tabs resting on top of the supply air duct.
b. Center duct connector and push back against
rear edge of floor opening.
c. Mark cut-out location (tab area) and remove
duct connector.
d. Cut out duct opening 1/4" larger than area
marked.
INSTALLING FINGER TABBED DUCT CON­NECTORS a. Place duct connector through the floor open-
ing with bottom tabs extending through the
duct opening. (See Figure 15) b. Secure duct connector to floor. c. Bend bottom tabs under and up tightly against
the supply air duct (See Figure 16).
NOTE: The duct connector is designed for use on ducts 12" in width. When using the connector on 12" wide ducts, there may be insufficient clearance to bend the tabs on two sides of the duct connector. In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners. (See Figure 17).
If sealant, mastic, or tape is used to provide a better seal, it should be approved by applicable national or local codes.
ALTERNATE ATTACHMENT METHODS
INSTALL FURNACE MOUNTING PLATE a. Place mounting plate (supplied within duct
connector) at rear of the floor opening (See Figure 15).
INSTALLING PLATINUM SERIES 14” ROUND DUCT CONNECTOR a. Place duct connector through the floor open-
ing. (See Figure 15).
b. Secure duct connector to floor.
INSTALLING SCREW DOWN DUCT CON­NECTOR a. Apply a bead of caulking, mastic, or other
approved sealant around bottom side of 1/2” flange and restrictor plate, when applicable.
b. Locate the duct connector over duct and
carefully lower screw down duct connector into place.
c. Once duct connector is located on duct,
temporarily hold in place while fastening duct connector to the floor using flat head screws or nails. Be sure flanges of duct connector stay in contact with the duct.
d. Screw plenum to duct making sure a seal is
made between the duct and the duct connec­tor. Additional screws may be added if re­quired.
e. Cut away duct along edge of flange allowing
the center to drop into the duct. Remove section of duct with caution, as edges will be sharp.
This procedure may also be used to install a furnace duct connector to narrow metal ductwork where insufficient clearance prevents
TABS
DUCT
1. INSERT DUCT CONNECTOR INTO DUCT CUT-OUT.
TABS
DUCT
2. BEND BOTTOM TABS OVER AND ONTO THE UNDERNEATH DUCT SERVICE.
Figure 16. Installation of Duct Connector
Duct Connector
Narrow Duct
Duct
Figure 17.
12
Loading...
+ 28 hidden pages