Mitsubishi MSC-A07YV, MSC-A09YV, MSC-A12YV User Manual

SERVICE MANUAL
HFC
utilized
R410A
SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
E1
E1
E1
(WH)
(WH)
(WH)
MSC-A07YV ­MSC-A09YV ­MSC-A12YV -
No. OB329
Indication of model name
MSC-A07YV ­MSC-A09YV ­MSC-A12YV -
NOTE:
•This manual describes technical data of indoor units.
•As for outdoor units MU-A07/A09/A12YV - , refer to the service manual OB330.
•As for outdoor units MUH-A07/A09/A12YV - , refer to the service manual OB331.
•As for outdoor units MUX-A10/A19/A20/A25/A26WV - , refer to the service manual OB307 REVISED EDITION-A.
•As for outdoor units MUX-A22WV - , refer to the service manual OB318.
•As for outdoor units MXZ-A18/A26/A32WV - , refer to the service manual OB319.
E1 E1 E1
E1
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································3
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. MICROPROCESSOR CONTROL ······················9
9. SERVICE FUNCTIONS ····································17
10. TROUBLESHOOTING ······································19
12. PARTS LIST······················································28
E1
1
TECHNICAL CHANGES
MSC-A07WV- ➔MSC-A07YV-
MSC-A09WV- MSC-A09YV­MSC-A12WV- MSC-A12YV-
1. Design of front panel has changed.
2. Air filter has changed to the catechin air filter.
2
MSC-A07YV ­MSC-A09YV ­MSC-A12YV -
PART NAMES AND FUNCTIONS
E1
E1
E1
E1E1
E1E1
E1E1
INDOOR UNIT
Air cleaning filter (white bellows type)
Panel
Catechin air filter (With deodorizer)
Air outlet
Vertical vanes
Fan
Horizontal vane
Operation section
(When the front panel is opened)
Front panel Air inlet
to Breaker
Power supply cord
Remote control receiving section
Remote controller
Display section
Emergency operation switch
Operation indicator lamp Remote control
receiving section
3
MSC-A07YV-
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 16 mm Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Air cleaning filter
1 5 1 2 2 1 1 1
<Indoor unit>
1
2
3
4
5
6
7
8
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET
CLOCK
HEAT /FAN
/
Open the front lid.
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
Indication of remote controller model is on back.
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE CONTROL button
CLOCK SET button
MSC-A09YV­MSC-A12YV-
E1 E1 E1
ACCESSORIES
REMOTE CONTROLLER
4
3
Indoor model
Function
Indoor unit power supply
Air flow(High/Med. /Low ) Power outlet Running current Power input Power factor Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level(High/Med. /Low ) Fan speed(High/Med. /Low ) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Remote controller model
K /h
A
A W %
A
"
mm
kg
dB
rpm
k" k"
MSC-A07YV -
E1
Single phase
230V,50Hz
10
0.17 35 90
0.17
RC4V19-LA WHT-BLK 413 BLK-RED 334 815O278O244
9 5
3 10 10
KP1A or KG3A
Cooling
474/372 /276
36/31 /25
900/750 /600
Heating
510/420 /342
36/31 /25
950/820 /700
MSC-A09YV -
E1
Single phase
230V,50Hz
10
0.17 35 90
0.17
RC4V19-LA WHT-BLK 413 BLK-RED 334 815O278O244
9 5
3 10 10
KP1A or KG3A
Cooling
474/384 /306
36/31 /25
900/770 /650
Heating
588/456 /342
39/32 /25
1,050/870 /700
MSC-A12YV -
E1
Single phase
230V,50Hz
10
0.19 40 92
0.19
RC4V19-KA WHT-BLK 316 BLK-RED 299 815O278O244
10
5
3 10 10
KP1A or KG3A
Cooling
582/444 /324
40/33 /26
930/760 /600
Heating
606/498 /396
39/33 /26
960/830 /700
Electrical
data
Fan
motor
Special
remarks
Capacity
ww
ww
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
SPECIFICATION
NOTE: 1. Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C Outdoor DB35°C WB24°C OutdoorDB 7°C/WB 6°C Indoor-Outdoor piping length 5m
2.Remote controller model KP1A and KG3A are the same in terms of specification. W Reference value
5
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19: Heating : DB20: WB -:
MSC-A07YV- E1
COOL
High
FUNCTIONFAN SPEED
36
HEAT
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19: Heating : DB20: WB -:
MSC-A09YV- E1
COOL
High
FUNCTIONFAN SPEED
36
HEAT 39
SPL(dB
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19:
MSC-A12YV- E1
COOL
FUNCTIONFAN SPEED
40
HEAT
High
39
SPL(dB
(A)) LINE
INDOORUNIT
WALL
MICROPHONE
0.8m
1m
NOISE CRITERIA CURVES
6
5
OUTLINES AND DIMENSIONS
MSC-A07YV ­MSC-A09YV -
INDOOR UNIT
278
60
58
162
E1
E1
Installation plate
Indoor unit
783
815
606
149
19
Power supply cord Lead to right 1.0m Lead to left 0.3m
81.5
41
81.5
Air in
30
Air out
326326
242 5
7 or more
90
110
244
133.5
231.5
42
2.5
81.5
Wall hole
Installation plate
Liquid line Gas line
{
Insulation
Drain hose (Connected part O,D)
Insulation
[65
[6.35-0.5m
[9.52-0.43m
[37 O.D
[21 I.D
[16
[28
4.5
271
Unit: mm
Wireless remote controller
MSC-A12YV -
INDOOR UNIT
278
60
58
162
E1
Installation plate
783
815
606
19
Indoor unit
41
Air in
149
Power supply cord Lead to right 1.0m Lead to left 0.3m
30
Air out
242
7 or more
244
326326
5
Installation plate
Liquid line Gas line
{
Insulation
90
110
161.5161.5
17.5
258
218.5
42
2.5
81.581.5 Wall hole
[9.52-0.43m
Drain hose (Connected part O,D)
Insulation
[65
[6.35-0.5m
[37 O.D
[21 I.D
[16
[28
Wireless remote controller
7
6
SYMBOL
NR11 RT11 RT12
SR141
NAME
NAME NAME INDOOR FAN CAPACITOR FUSE(3.15A) INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR
VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR SOLID STATE RELAY
TERMINAL BLOCK
SYMBOL
C11 F11
MF
MV
SYMBOL
TB
T11
TRANSFORMER
CIRCUIT BREAKER
SR141
C11
RED
WHT
3
6
5
BRN
YLW
GRY
BLK
4
3
2
1
MF
121
CN
1 3 5
111
CN
112
CN
RT12
RT11
NR11
F11
ELECTRONIC CONTROL P.C. BOARD
CN211
TAB12 CN201
3 2 1
CN202
2 1
151
CN
5
5
BRN RED
BLU
WHT BLK
BLU
BRN
TB
L 3 N 2 1
12V
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD ~/N 230V 50Hz
GRN/YLW
POWER MONITOR, RECEIVER P.C.BOARD
REMOTE CONTROLLER
MV
FOR MUH OR MXZ TYPE
FOR MU OR MUX TYPE
12V
PE
101
CN
T11
GRN
LD103
WIRING DIAGRAM
MSC-A07YV - MSC-A09YV - MSC-A12YV -
INDOOR UNIT
MODELS WIRING DIAGRAM
E1E1E1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
7
MSC-A07YV - MSC-A09YV -
INDOOR UNIT
Indoor heat exchanger
REFRIGERANT SYSTEM DIAGRAM
E1E1
Refrigerant pipe [9.52 (with heat insulator)
Indoor coil thermistor RT12
Flared connection
MSC-A12YV -
INDOOR UNIT
Indoor heat exchanger
Room temperature
Room temperature thermistor RT11
Refrigerant flow in cooling
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
thermistor RT11
8
E1
Indoor coil thermistor
Refrigerant flow in cooling
Refrigerant pipe [12.7 (with heat insulator)
RT12
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Unit:mm
8
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET
CLOCK
HEAT /FAN
/
Open the front lid.
ON/OFF
TOO COOL
PM
AM
TOO
WARM
Signal transmitting section
Operation display section
OPERATE /STOP (ON /OFF)button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE CONTROL button
CLOCK SET button
MICROPROCESSOR CONTROL
MSC-A07YV ­MSC-A09YV ­MSC-A12YV -
E1
E1
E1
Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
WIRELESS REMOTE CONTROLLER
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
• The following indication does not depend on the shape of lamp.
Operation Indicator
lighted not lighted
Difference between target
Operation stateIndication
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
temperature and room temperature
Approx. 2 :  or more
8-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature
Room temperature minus set temperature : 0.3 : or more················································ON Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of thermostat’s OFF-ON.
In Auto the fan speed is as follows.
Room temperature minus set temperature : 1.7 degrees or more·······························High Room temperature minus set temperature : Between 1 and 1.7 degrees···················Med. Room temperature minus set temperature : less than 1 degree··································Low
This shows that the room temperature is approaching the
Approx. 2 :  or less
target temperature.
Initial temperature difference Thermostat
Difference between room temperature and set tem­perature during operation
Set temperature
-0.3 :
0.3 :
Difference between room
Initial temperature difference
9
Fan speed
temperature and set tem­perature during operation
3 deg.
1.7 deg.
1 deg.
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and initial room temperature in dry mode
:
3. Coil frost prevention
Temperature control
When the indoor coil thermistor RT12 reads 4°C or below(MSC-A07/A09YV) / 0°C or below(MSC-A12YV) for 5 minutes, the coil frost prevention mode starts.
The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if RT12 still reads below 4°C (MSC-A07/A09YV) / 0°C (MSC-A12YV), this mode is prolonged until the RT12 reads over 4°C (MSC-A07/A09YV) / 0°C (MSC-A12YV).
Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes. The indoor fan operates at the set speed. a. Compressor has been continuously operating. b. Indoor fan speed is Low or Med. c. Room temperature is below 26°C. When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 26°C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed.
Operation chart
Example
ON
ON
Compressor
OFF
Outdoor fan
ON
Indoor fan
( continuously at set speed)
8-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select DRY mode with the OPERATION SELECT button. (3) The microprocessor reads the room temperature and determines the set tem-
perature. Set temperature is as shown on the right chart.
DRY operation will not function when the room temperature is 13°C or below. (4) When DRY operation functions the fan speed is lower than COOL operation
except at (fan speed) Low.
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Initial temperature difference Thermostat Room temperature minus set temperature : 0.3 : or more················································ON Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. In Auto fan speed becomes Low.
3. The operation of the compressor and indoor / outdoor fan <MU-A07/A09/A12YV, MUH-A07/A09/A12YV, MUX-A10/A19/A20/A22/A25/A26WV>
Compressor operates by room temperature control and time control. Indoor fan and outdoor fan operate in the same cycle as the compressor.
When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
OFF
10
Difference between room temperature and set tem­perature during operation
Set temperature
-0.3 :
0.3 :
Loading...
+ 22 hidden pages