Abbreviations surrounded by broken circle:
Connection optional or required, depending on model
G 7826 AV
Steam/Electric (D/EL)
Notes on supply connections:
Cold, hot and demineralised water, high-pressure steam, condensate and compressed air
supplies can be routed through the ceiling or, alternatively, through the floor. A combination of
the two is not possible.
Electrical
connection
Connection cable, min. cross-section mm² 5 × 2.5
Connection cable, min. length From top edge of MAV panelling if supply lines
Above finished floor if supply lines pass through
Country variations:
Rated load kW 10,0
Fuse rating A3 × 16
1. Voltage
pass through ceiling
floor
2. Voltage
Rated load kW 10.0
Fuse rating A3 × 16
Connection cable, min. cross-section mm² 5 × 2.5
Voltage V/Hz 3 AC 230/50
Rated load kW 10.0
Fuse rating A 3 × 30
Connection cable, min. cross-section
3. Voltage
Rated load kW 10.0
Fuse rating A3 × 30
Connection cable, min. cross-section mm² 4 × 4
V/Hz 3N AC 400-415/50
m 4.0
m 1.5
V/Hz 3N AC 400/50
mm² 4 × 4
convertible
V/Hz 3 AC 230/50
Voltage V/Hz 3N AC 400/50
Rated load kW 10.0
Fuse rating A 3 × 16
Connection cable, min. cross-section
4. Voltage
Rated load kW 10.0
Fuse rating A3 × 30
Connection cable, min. cross-section mm² 4 × 4
Voltage V/Hz 3N AC 380/60
Rated load kW 10.0
Fuse rating A 3 × 16
Connection cable, min. cross-section
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 7
mm² 5 × 2.5
convertible
V/Hz 3 AC 220/60
mm² 5 × 2.5
convertible
Page 8
V/Hz 3N AC 380/60
5. Voltage
Rated load kW 10.0
Fuse rating A3 × 16
Connection cable, min. cross-section mm² 5 × 2.5
Plug and socket connection recommended to facilitate
Connection
module
output signals
Voltage V/Hz 3 AC 220/60
Rated load kW 10.0
Fuse rating A 3 × 30
Connection cable, min. cross-section
6. Voltage V/Hz 3 AC 208/60
Rated load kW 10.0
Fuse rating A3 × 30
Connection cable, min. cross-section mm² 4 x 10
7. Voltage V/Hz 3 AC 200/50
Rated load kW 10.0
Fuse rating A3 × 30
Connection cable, min. cross-section mm² 4 × 4
8. Voltage V/Hz 3 AC 200/60
Rated load kW 10.0
Fuse rating A3 × 30
Connection cable, min. cross-section mm² 4 × 4
accessibility for electrical safety tests.
Socket must be accessible after installation. Connection to
electrical supply should be in accordance with valid
regulations and safety standards. Observe correct phase
sequence (clockwise). Supply lead should not be in direct
contact with any source of heat.
The use of a current-operated ELCB is recommended!
Potential-free contacts (NO contacts):
A maximum of 9 contacts are available, possible assignment:
mm² 4 × 4
convertible
Max. contact load:
TA OPERATION Contact closed during drying block V/A/Hz 200-240/1/50-60
PRG RUNNING Contact closed during washing, drying and cool-down V/A/Hz 200-240/1/50-60
OPERATION Contact closed while machine is running V/A/Hz 200-240/1/50-60
FAULT Contact closed when fault occurs V/A/Hz 200-240/1/50-60
PRG END Contact closed between end of programme and door opening V/A/Hz 200-240/1/50-60
PAUSE w. WASH Contact closed during 'Pause with wash action' stage V/A/Hz 200-240/1/50-60
DRAIN STD Contact closed during drainage V/A/Hz 200-240/1/50-60
DRAIN RECY. Contact closed during drainage (water recycling drain pump) V/A/Hz 200-240/1/50-60
COLD Contact closed during cold water intake V/A/Hz 200-240/1/50-60
HOT Contact closed during hot water intake V/A/Hz 200-240/1/50-60
DEMIN. COLD Contact closed during cold demineralised water intake V/A/Hz 200-240/1/50-60
DEMIN. HOT Contact closed during hot demineralised water intake V/A/Hz 200-240/1/50-60
DOS1-EXT Control signal for external dispenser pump 1 V/A/Hz 200-240/1/50-60
DOS2-EXT Control signal for external dispenser pump 2 V/A/Hz 200-240/1/50-60
DOS3-EXT Control signal for external dispenser pump 3 V/A/Hz 200-240/1/50-60
DOS4-EXT Control signal for external dispenser pump 4 V/A/Hz 200-240/1/50-60
Module input
signals
SLA HZG Peak-load negotiation - Heating V/Hz 200-240/50-60
DOS-EXT Fill level of external dispenser canister V/Hz 200-240/50-60
MEDIUM Medium dispensing active, signal for flow and volume control V/Hz 200-240/50-60
Control voltage
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 8
Page 9
Cold water Max. temperature °C 20
Max. water hardness °dH 4
Min. flow pressure kPa 200
Max. pressure kPa 1000
Throughput l/min 15
On-site connection thread according to DIN 44 991 Inch 3/4" external thread
Water connection Australia:
To prevent back-syphonage, the water connection must be
via an approved Dual-Check-Valve supplied with the
machine.
(USA: 11.5 NH)
Hot water
Water connection Australia:
Final rinse water
Heating steam
Condensate On-site connection thread Inch 1/2" ext. thread
Compressed air
Max. temperature °C 60
Max. water hardness °dH 4
Min. flow pressure kPa 200
Max. pressure kPa 1000
Throughput l/min 15
On-site connection thread according to DIN 44 991 Inch 3/4" external thread
To prevent back-syphonage, the water connection must be
via an approved Dual-Check-Valve supplied with the
machine.
Water quality defined by cleaning requirements, e.g. reverse
osmosis, demineralised water, ultra-purified water, etc.
Max. conductivity (e.g. for surgical instruments) µS/cm 15
Min. flow pressure kPa 200
Max. pressure kPa 1000
Throughput l/min 15
On-site connection thread according to DIN 44 991 Inch 3/4" external thread
Steam pressure kPA 250-1000
Temperature °C 140-180
Rated capacity kg/h 50
On-site connection thread Inch 1/2" ext. thread
Capacity Qn m³/h 0.12
Supply pressure kPa 600-1.200
Connection thread (on site) Inch 1/2" ext. thread
(USA: 11.5 NH)
(USA: 11.5 NH)
Cooling circuit
feed line
(optional)
Cooling circuit
return pipe
(optional)
Waste water
Floor tray drain
Steam condenser (DK, optional) can be connected to a
cooling circuit. Connect to cold water if cooling circuit is not
available.
Max. cooling capacity kW 3.5
Max. pressure – Cooling circuit kPa 800
Pressure loss – Steam condenser kPa 30-50
Throughput "Wash", adjustable on site l/min 1.0-4.0
Throughput "Dry", adjustable on site l/min >4.0
Hose connector – Steam condenser (ext. dia. × l) mm 14 x 25
Stopcock and supply line filter to be provided on site!
Necessary to connect steam condenser to cooling circuit
Hose connector – Steam condenser (ext. dia. × l) mm 14 × 25
Stopcock to be provided on site!
Max. temperature °C 93
Connection DN 50
Max. peak delivery l/min 150
Fit odour trap on site
Max. temperature °C 70
Connection DN 50
Fit odour trap on site
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 9
Page 10
Vented
Machine-side connection (ext. dia. × wall thickness) mm 125 x 1.25
Air extracted from the 'unclean' side of the operation should
be replenished by ensuring sufficient air intake.
I. Vent to atmosphere. Vent multiple washer-disinfectors
individually (do not use manifold):
Vent air throughput m³/h 250
Temperature - Mean value / peak max. °C 70/95
Rel. humidity - Mean value / peak max. % 80/100
Max. permissible pressure loss in vent duct Pa 700
II. Connection without steam condenser to external fanassisted vent:
Min. throughput capacity of on-site vent in washing cycle m³/h 100
Min. throughput capacity of on-site vent in drying cycle m³/h 350
Temperature - Mean value / peak max. °C 70/95
Rel. humidity - Mean value / peak max. % 80/100
III. Connection with steam condenser to external fan-assisted
vent:
Min. throughput capacity of on-site vent in washing cycle m³/h 100
Min. throughput capacity of on-site vent in drying cycle m³/h 350
Temperature - Mean value / peak max. °C 28/32
Rel. humidity - Mean value / peak max. % <70/100
Prevent condensate backflow into washer-disinfector. Pitch
vent ducting and discharge condensate at lowest point.
Machine feet
Fasteners
Heat dissipation
to room
Machine data
Installation should only be carried out by authorised fitters in accordance with valid regulations!
Observe installation instructions when installing machine! All rights reserved! Measurements in mm
Height-adjustable mm 10
Foot diameter mm 25
Parts supplied with plinth/floor tray:
Adhesive anchors (4 off) mm M 8 × 150
Hole diameter mm 8
Unclean side kW 0.5
Clean side kW 0.5
Load on removal kW 0.8
Height incl. plinth/floor tray mm 1974
Height incl. plinth/floor tray and top-box panelling mm 2404
Width mm 900
Depth mm 750
Net weight incl. plinth/floor tray kg 417
Net weight incl. plinth/floor tray, top-box panelling and steam
condenser, etc.
Dynamic floor load N ~6524
Min. transport width incl. pallet mm 820
Min. transport height incl. pallet mm 2070
kg 496
Notes on supply connections:
Cold, hot and demineralised water, high-pressure steam, condensate and compressed air supplies
can be routed through the ceiling or, alternatively, through the floor. A combination of the two is not
possible. Connection of waste water and floor tray on dump valve (AV) models is only possible
through floor. Cooling circuit feed and return pipes for steam condenser (optional) through ceiling only.
Easily accessible central stopcock and main switch recommended.
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 10
Page 11
Preparatory work
Core-drilled access hole in floor according to drawings or template, Mat. no. 5488570, available from
Spares. Further access holes required for tubing and cabling if chemical product supply line access is
through the floor.
Recommended core-drilling diameters: Waste water connections 100 mm Ø
Chemical supply connections 230 x 170 mm (W x D)
Use directly abutting templates for run of machines. Template size corresponds to diaphragm wall cutout which is slightly larger than machines to allow for 5 mm gap between machines and 3 mm gap
between machine and diaphragm wall. These gaps are sealed on site using a suitable sealant.
Waste water connection:
Drain manifold (minimum diameter DN 100) to be installed under floor and fitted with odour trap on
site. Connections to manifold (DN 50) to be fitted vertically to extend to specified height above floor at
predetermined points. Hose sleeve of drain pipe for drip tray drain should end 35 mm above finished
floor level; hose sleeve of drain pipe for machine drainage should end at finished floor level. Additional
removable stub-out with slip joint to 200 mm above finished floor required for machine drainage. Stubout extensions to be cut to size and removed to facilitate machine handling. Stub-out extension fitted
after washer-disinfector has been positioned in the plinth/floor tray. If plinth/floor tray is planned later,
use pipe caps to close pipes.
Electrical connection:
Electrical supply lines can be routed through floor or ceiling. Min. cable length of 1500 mm above
finished floor surface required with access through floor. Min. cable length of 4000 mm from top edge
of top-box panelling required with access through ceiling.
Standard installation, chemical supply connections:
Install supply lines vertically from ceiling, adjust and locate. All pipework, including insulation, fittings
and valves with taps should be located within the designated area (520 mm × 130 mm). No part of the
installation should extend beyond this area.
Hot, cold and demineralised water lines, high-pressure steam and condensate lines end with a ¾" ext.
thread and compressed air lines with a ½" int. thread 2,224 mm above finished floor.
Miele recommends the installation of a check valve directly below the condensate trap in order to
prevent water hammer.
If washer-disinfector is installed with a steam condenser, install cooling circuit feed and return pipes
vertically from ceiling and secure. Both are connected to the steam condenser with a flexible hose (int.
diameter 14 mm) which is to be provided on site. In the absence of cooling circuit, connect steam
condenser to cold water.
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 11
Page 12
Alternative installation, chemical supply connections:
Route supply lines through floor to approx. 200 mm above finished floor and secure. Supply lines are
shortened after installation of plinth/floor tray. If plinth/floor tray is planned later, use pipe caps to close
pipes. Install floor tray horizontally using spirit level. Stopcocks in the chemical supply lines are
installed after the floor tray has been fitted. Install stopcocks for cold, hot and demineralised water,
high-pressure steam, condensate and compressed air according to drawings. Pipework and
stopcocks should rise by no more than 90 mm above finished floor and should on no account rise
above plinth/floor tray.
If washer-disinfector is installed with a steam condenser, install cooling circuit feed and return pipes
vertically from ceiling and secure. Both are connected to the steam condenser with a flexible hose (int.
diameter 14 mm) which is to be provided on site. In the absence of cooling circuit, connect steam
condenser to cold water.
Waste air installation:
In order to expel vapours, air throughput of 350 m³/h for each machine is required on the unclean side
of the operation.
Connection to external vent system with or without steam condenser:
Connection of the washer-disinfector to an external vent system is via an extractor canopy. An air gap
of at least 80 mm should be provided. A suitable vent canopy is provided with the washer-disinfector.
The use of a two-stage fan is recommended (cf. Technical Data Sheet 'Electrical connection' on fan
control). Laying a flexible duct to directly above the machine facilitates installation.
Venting to atmosphere:
The canopy provided should not be fitted if the washer-disinfector is vented directly to atmosphere.
Never merge vent ducts from multiple washer-disinfectors! Vent each machine separately!
Installationsplan G 7826 D/EL AV
Stand: 01.05.2005
Seite 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.