Installation & Operating Instructions
Maverick
IP Sensor Appliance
Model IP-PC-101-44-VDC
Baird House, Units 6&7
Pensnett Estate • Kingswinford
West Midlands • DY6 7YA • United Kingdom
01384-271113 • Fax 01384-271114
RoHS
8189 Century Blvd. • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com • www.mamacsys.com
4 Arminger Court, Unit 2
Holden Hill • S.A. 5088 • Australia
08-8395-4333 • Fax 08-8395-4433
® Registered trademark MAMAC SYSTEMS, Inc.
155 McIntosh Drive, Units 5&6 • Markham
Ontario • L3R ON6 • Canada
905-474-9215 • Fax 905-474-0876
No. 22 Lorong 21A Geylang # 11-02
Prosper Industrial Building
Singapore • 388421
656-3927273 • Fax 656-3927276
TABLE OF CONTENTS
SECTION 1: Maverick Overview
1.0.0: Conformance and Testing
1.1.0: Specifications
1.2.0: Appliance Overview
1.3.0: Installation
1.4.0: Wiring
SECTION 2: Initial Configuration
2.0.0: Initial Configuration
2.1.0: Internet Protocol
2.2.0: Network & Email Configuration - Static IP
2.3.0: Network & Email Configuration - DHCP
2.4.0: Password/Clock Configuration
2.5.0: Sensor Inputs, Email Alert & Setpoint Control Configuration
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 9
Page 10
Page 11,12
2.6.0: Output Configuration
2.7.0: Data Logging
SECTION 3: Operation
3.0.0: Network Configuration - Static IP
3.0.1: Network Configuration - DHCP IP
3.1.0: Main Page
3.1.1: Manual Control
3.1.2: Data Logging
3.2.0: Reset Button
3.3.0: XML
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 20
® Registered trademark MAMAC SYSTEMS, Inc.
1 of 20
© Copyright 2008 DN IS-IPPC101.1
SECTION 1 - Conformance & Testing
1.0.0
1.0.1
FCC Testing -
- Rule Part 15, Subpart B - Unintentional Radiators Class B Limits 15.107 & 15.109.
EMC/EMI Testing -
- BS EN 55022:1998, CISPR 22:1997 Amendments 1 & 2.
- BS EN 55024:1998 CISPR 24:1997 Amendments 1 & 2.
- EN 61000-3-3: Limitations of voltage fluctuations and flicker in low-voltage supply systems <16A.
- EN 61000-4-2: Electrostatic Discharge (ESD).
- EN 61000-4-3: Radiated, radio frequency, Electromagnetic field immunity test.
- EN 61000-4-4: Electrical Fast Transient/burst immunity test (EFT).
- EN 61000-4-5: Surge Immunity Test (Mains).
- EN 61000-4-6: Immunity to conducted disturbances induced by radio frequency fields.
- EN 61000-4-11: Voltage dips, short interruptions and voltage variations immunity test.
1.0.2
RoHS Compliant -
MAMAC Systems, Inc. products designated “RoHS Compliant” comply with the European
Union’s Directive on the Restriction of the Use of Hazardous Substances 2002/95/EC
(”RoHS”). These products do not contain Joint Industry Guide (JIG) - 101 Level A substances
above threshold limits, except lead in RoHS exempt applications 5, 7a and 7c. These products
do not contain perfluorooctane sulfonates (PFOS).
- Cadmium (Cd) < 100 ppm
- Mercury (Hg) < 100 ppm
- Lead (Pb) < 1000 ppm
- Polybrominated Biphenyls (PBB) < 1000 ppm
- Polybrominated Diphenyl Ethers (PBDE) < 1000 ppm
- Hexavalent Chromium (CrVI) < 1000 ppm
® Registered trademark MAMAC SYSTEMS, Inc.
2 of 20
© Copyright 2008 DN IS-IPPC101.1
SECTION 1 - Specifications
1.1.0
Anyone who can surf the web now can do sensor monitoring, control,
data logging, and email alerts without any training or custom software.
All you need is a web browser running on any laptop, PDA, or cell
phone anywhere in the world.
The
Maverick IP Sensor Appliance incorporates a web server,
analog/digital inputs and relay outputs. Power the appliance with
any 24VAC transformer, plug it into a hub/router, launch any web
browser, punch in the default IP and connect. No custom software to
load, no discovery routines, no custom cables, or training.
The IP Sensor Appliance serves up static web pages with dynamic
data updates every second or two. Most users can set up and utilize
the appliance without any training or support in less than 5 minutes
due to the innovative and familiar web browser based configuration.
The
Maverick is an ideal low cost solution for light commercial,
residential and remote monitoring applications. The appliance can
also be used to enhance existing HVAC control systems by adding
email alerts and data logging to critical points.
SPECIFICATIONS:
Supply Voltage: 24 VAC/VDC Data Logging: 2048 samples each input
Supply Current: 250 mA (6 VA)
Input Impedance: 125K ohms (VDC or
Digital) 250 ohms (4-20 mA)
Digital Input: 10.00 VDC maximum
Output Relay Rating: 250 VAC @ 5.0 Amps
UL Listed
Ethernet: 10-Base T
IP Assignment: Static or DHCP
Logging Interval: 1.0 second to 99.99 hours
Environmental: 10-90%RH non-condensing
Operating Temp: -40˚F-125˚F (-40˚C-52˚C)
Storage Temp: -40˚F-150˚F (-40˚C-66˚C)
Enclosure: UL 94V-5-O Polycarbonate plastic
Termination: Removable terminal blocks 16
Ga max, RJ-45 Ethernet jack
Email: SMTP to two email addresses
® Registered trademark MAMAC SYSTEMS, Inc.
Weight: 0.5 lbs. (.25 kg)
© Copyright 2008 DN IS-IPPC101.1
3 of 20
1.2.0
SECTION 1 - Appliance Overview
Figure 1
Lan
Link
Heart Beat
Power
LEDs
Reset
Button
LEDs
Out 1 NC
Out 1 COM
Out 1 NO
Out 2 NC
Out 2 COM
Out 2 NO
Out 3 NC
Out 3 COM
Out 3 NO
Out 4 NC
Out 4 COM
Out 4 NO
Output 1
Output 2
Output 3
Output 4
MAMAC SYSTEMS
24 VAC/VDC
Neutral/Com
Ground/Earth
Input 1
Common
Input 2
Common
Input 3
Common
Input 4
Common
® Registered trademark MAMAC SYSTEMS, Inc.
4 of 20
© Copyright 2008 DN IS-IPPC101.1
SECTION 1 - Installation
1.3.0
1.3.1
INSPECTION:
Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
REQUIREMENTS:
• Tools (not provided)
- Digital Volt-ohm Meter (DVM).
- Appropriate screwdriver for mounting screws.
- Appropriate drill and drill bit for mounting screws.
• Four #6 sheet metal screws.
• Training: Installer must be a qualified, experienced technician.
Warning:
• Disconnect power supply before installation to prevent electrical shock and
equipment damage.
• Make all connections in accordance with national and local electrical codes. Use copper
conductors only.
Caution:
• Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and
wiring to prevent equipment damage.
• Avoid locations where severe shock or vibration, excessive moisture or corrosive fumes
are present.
• Do not exceed ratings of the device.
1.3.2
MOUNTING:
The Maverick IP Sensor Appliance must be mounted on a flat surface with four #6 sheet
metal screws (not provided) as shown in fig. 2.
Figure 2
4.50”
3.60”
(114 mm)
(91 mm)
4.00”
(102 mm)
4x 0.156” use #6 sheet
metal screws (not
included), to mount
MAMAC SYSTEMS
3.70”
(94 mm)
appliance
® Registered trademark MAMAC SYSTEMS, Inc.
5 of 20
© Copyright 2008 DN IS-IPPC101.1
SECTION 1 - Wiring
1.4.0
1.4.1
Terminate the IP Sensor Appliance as shown in fig. 3.
Use a UL rated 24VAC class-2 transformer or a UL rated 24VDC power supply with
transformer isolation.
WARNING:
Maximum supply voltage MUST NOT EXCEED 35VAC/35VDC.
CAUTION:
The appliance and all sensors connected must be wired with all neutral/common
connections with the same polarity. All sensors and the appliance neutral/common must
terminate at the transformer/power supply neutral/common.
Figure 3
Signal
Common
Supply
Sensor “n”
MAMAC SYSTEMS
Note: Use 18 gauge conductor
for ground.
Note:
Always disconnect
power from unit before
wiring a sensor.
Signal
Common
Supply
Sensor 2
1.4.2
Signal
Common
Supply
Sensor 1
Digital inputs are terminated as shown in fig. 4.
Figure 4
Digital
Input #1
Digital
Input #2
WARNING: Digital Input
must not exceed 10.0 VDC.
24 VAC/VDC
TRANSFORMER/POWER SUPPLY
Neutral/Common
24 VDC/VAC
MAMAC SYSTEMS
® Registered trademark MAMAC SYSTEMS, Inc.
6 of 20
© Copyright 2008 DN IS-IPPC101.1