MAMAC Systems HU-226 Data Sheet

RoHS
Model HU-226
Technical Information
TI.226-05
HUMIDITY / TEMP SENSOR
For Additional Information See HU-226 Data Sheet
HUMIDITY TRANSDUCER SPECIFICATIONS
Accuracy*: ± 2% / ±3% RH
Range: 0-100% RH
Hysteresis: ± 1%
Supply Voltage: 12-40 VDC
12-35 VAC (VDC output units only)
Compensated Temp Range: -30°F to 130°F (-35°C to 55°C)
Load Impedance: 1.5K ohms max. at 40 VDC (mA output units)
* Includes non-linearilty and non-repeatability
THERMISTOR SENSOR SPECIFICATIONS
Interchangeability: ± 0.2°C
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
Operating Temp Range: -30°F to 130°F (-35°C to 55°C)
ORDERING INFORMATION - HU-226-
ACCURACY
± 2%
± 3%
OUTPUT
mA
(4-20 mA 2-wire)
VDC
(0-5 VDC/0-10 VDC
field selectable)
HU-226
Duct Mount
1
2
3
4
5
7
8
10
12
13
14
15
TEMP SENSOR
100 ohm Platinum RTD
1,000 ohm Nickel RTD (5,000 PPM)
1,000 ohm Platinum RTD
1,000 ohm Nickel RTD (6,000 PPM)
1,000 ohm Balco RTD
10,000 ohm NTC Thermistor (Type III)
10,000 ohm NTC Thermistor (Carel)
3,000 ohm NTC Thermistor
10,000 ohm NTC Thermistor (Type II)
5,000 ohm NTC Thermistor
1,035 ohm Silicon PTC
100,000 ohm NTC
Thermistor
PLATINUM RTD SENSOR SPECIFICATIONS
Accuracy: 0.12% at 0°C
Resistance: 100 or 1,000 ohm at 0°C
Standard: DIN 43760
Heat Dissipation: 3.0 mW/°C
R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
Operating Temp Range: -30°F to 130°F (-35°C to 55°C)
GENERAL SPECIFICATIONS
Environmental: 10-90%RH Non-Condensing
Enclosure: 18 Ga C.R. Steel NEMA 4 (IP-65)
Finish: Baked on enamel - PMS2GR88B
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga maximum
Weight: Duct Mount: 1.0 lbs. (.45 kg)
CONFORMANCE & TESTING
RoHS Compliant EMC Testing: BS EN 55022:1998, BS EN 55024:1998,
EN 61000-3-3, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6 EN 61000-4-11
Ex: HU-226-2-mA-3 - Humidity/Temp Sensor, ±2%RH accuracy with 4-20 mA output and 1,000-ohm Platinum RTD.
For Resistance vs. Temperature Tables, please refer to TI.700.11
INSTALLATION
Inspection
Requirements
Warning:
Caution:
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
Appropriate accessories
Two #8 self-tapping mounting screws (not provided)
Training: Installer must be a qualified, experienced technician
Do not use on oxygen service, in an explosive/hazardous
environment, or with flammable/combustible media.
Disconnect power supply before installation to prevent
electrical shock and equipment damage.
Make all connections in accordance with the job wiring diagram
and in accordance with national and local electrical codes. Use copper conductors only.
Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMA Type 4 housings are intended for outdoor use primarily to provide a degree of protection against wind-blown dust, rain, and hose-directed water.
Do not exceed ratings of the device.
16
10,000 ohm NTC Thermistor (Eliwell)
20,000 ohm NTC Thermistor
17
2,252 ohm NTC Thermistor
18
1,800 ohm NTC Thermistor
21
Page 2 of 4
RoHS
Model HU-226
Technical Information
TI.226-05
HUMIDITY / TEMP SENSOR
Mounting
Wiring
HU-226 (DUCT) - Refer to Figure 6 for mounting dimensions.
1. Drill 5/8” hole in appropriate location.
2. Mount transducer on a vertical surface with two #8 self-tapping screws (not provided).
3. Pull wires through knockout and make necessary connec­tions (see wiring diagrams).
4. Replace cover and tighten Philips screws.
Use maximum 12 AWG wire for wiring terminals. Refer to Figures 1, 2, 3, & 4 for wiring information and Figure 5 for dip switch designations.
mA Output
Wiring HU-226 Units with mA Output
HU-226 Humidity Transducer with mA Output
TYPICAL APPLICATIONS (wiring diagrams)
Figures 1 & 2 illustrate typical wiring diagrams for the HU-226, 4-20 mA,
two-wire humidity transducers.
Figure 1 - Wiring for mA Output Humidity Transducer with External DC Power Supply
mA Output Transducer Only
Humidity
Temp
Figure 2 - Wiring for mA Output HumidityTransducer where Controller or Meter has Internal DC Power Supply
+
12-40 VDC Power Supply
+
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
Temp
Input
HU-226 humidity transducers are 4-20 mA output units powered with a 12-40 VDC supply.
The following describes the proper wiring of these humidity and temp sensors with mA output:
HUMIDITY SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+] and [-] terminal markings on the board.
3. Attach the supply voltage to the [+] lead.
4. Connect the 4-20 mA output ([-] terminal) to the controller’s input terminal.
5. Ensure that the power supply common is attached to the common bus of the controller.
6. Re-insert the terminal block to the circuit board and apply power to the unit.
7. Check for the appropriate output signal using a DVM set on DC milliamps connected in series with the [-] terminal.
TEMP SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Use shielded 18-22 AWG wire to connect temp sensor as shown in Figures 1 & 2.
mA Output Transducer Only
Humidity
Temp
Caution: If you are using grounded AC, the hot wire must be on the [+] terminal. Also, if you are using a controller without built-in isolation, use an isolation transformer to supply the HU-226 transducer.
Caution: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies.
Caution: When multiple units are powered from the same transformer, damage will result unless all 24G power leads are connected to the same power lead on all devices. It is manda­tory that correct phasing be maintained when powering more than one device from a single transformer.
+
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
Temp
Input
Loading...
+ 2 hidden pages