LG ABUQ24GGLA0, ABUQ18GHLA0 INSTALLATION MANUAL

0 (0)

INSTALLATION MANUAL

AIR CONDITIONER

Please read this installation manual completely before installing the product.

Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

www.lg.com

P/NO : MFL67448509

Single A Air Conditioner Installation Manual

CONTENTS

Safety Precautions ..............................................................................................

3

Installation of Outdoor Unit................................................................................

6

Wiring Connection...............................................................................................

9

Connecting Pipes ..............................................................................................

12

Leakage test and Evacuation ...........................................................................

15

Test running .......................................................................................................

17

Function..............................................................................................................

19

Self-diagnosis Function....................................................................................

20

Installation Guide at the Seaside.....................................................................

21

2 Air Conditioner

LG ABUQ24GGLA0, ABUQ18GHLA0 INSTALLATION MANUAL

Safety Precautions

Safety Precautions

To prevent the injury of the user or other people and property damage, the following instructions must be followed.

νBe sure to read before installing the air conditioner.

νBe sure to observe the cautions specified here as they include important items related to safety.

νIncorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.

This symbol indicates the possibility of death or serious injury.

This symbol indicates the possibility of injury or damage to properties only.

ν The meanings of the symbols used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

ν Installation

Always perform grounding.

Donʼt use a power cord, a

 

plug or a loose socket which

 

is damaged.

• Otherwise, it may cause electri-

• Otherwise, it may cause a fire

cal shock.

or electrical shock.

Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.

If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.

Always install an air leakage breaker and a dedicated switching board.

No installation may cause a fire and electrical shock.

For installation of the product, always contact the service center or a professional installation agency.

Otherwise, it may cause a fire, electrical shock, explosion or injury.

Do not keep or use flammable gases or combustibles near the air conditioner.

Otherwise, it may cause a fire or the failure of product.

Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.

Do not disassemble or repair the product randomly.

• It may cause injury or an accident.

• It will cause a fire or electrical shock.

Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.

• There is the risk of death, injury, fire or explosion.

Installation Manual 3

Safety Precautions

Do not install the product at a place that there is concern of falling down.

• Otherwise, it may result in personal injury.

Use caution when unpacking and installing.

• Sharp edges may cause injury.

ν Operation

Do not share the outlet with other appliances.

It will cause an electric shock or a fire due to heat generation.

Do not use the damaged power cord.

Otherwise, it may cause a fire or electrical shock.

Do not modify or extend the power cord randomly.

Otherwise, it may cause a fire or electrical shock.

Take care so that the power cord may not be pulled during operation.

Otherwise, it may cause a fire or electrical shock.

Unplug the unit if strange sounds, smell, or smoke comes from it.

Otherwise, it may cause electrical shock or a fire.

Keep the flames away.

• Otherwise, it may cause a fire.

Take the power plug out if

Do not use the power cord

necessary, holding the head

near the heating tools.

of the plug and do not touch

 

it with wet hands.

 

• Otherwise, it may cause a fire

• Otherwise, it may cause a fire

or electrical shock.

and electrical shock.

Do not open the suction inlet of the indoor/outdoor unit during operation.

Otherwise, it may electrical shock and failure.

Do not allow water to run

Hold the plug by the head

into electrical parts.

when taking it out.

• Otherwise, it may cause the

• It may cause electric shock

failure of machine or electrical

and damage.

shock.

 

Never touch the metal parts of the unit when removing the filter.

They are sharp and may cause injury.

Do not step on the indoor/outdoor unit and do not put anything on it.

It may cause an injury through dropping of the unit or falling down.

Do not place a heavy object on the power cord.

Otherwise, it may cause a fire or electrical shock.

When the product is submerged into water, always contact the service center.

Otherwise, it may cause a fire or electrical shock.

Take care so that children may not step on the outdoor unit.

Otherwise, children may be seriously injured due to falling down.

4 Air Conditioner

Safety Precautions

ν Installation

Install the drain hose to ensure that drain can be securely done.

• Otherwise, it may cause water leakage.

Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.

Otherwise, it may cause dispute with the neighbors.

Always inspect gas leakage after the installation and repair of product.

• Otherwise, it may cause the failure of product.

Keep level parallel in installing the product.

Otherwise, it may cause vibration or water leakage.

ν Operation

Avoid excessive cooling and perform ventilation sometimes.

• Otherwise, it may do harm to your health.

Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.

The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.

Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles.

Do not place obstacles around the flow inlet or outlet.

• Otherwise, it may damage your properties.

Otherwise, it may cause the failure of appliance or an accident.

Installation Manual 5

Installation of Outdoor Unit

Installation of Outdoor Unit

1. Installation Places

If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.

Ensure that the spaces indicated by arrows around front, back and side of the unit.

Do not place animals and plants in the path of the warm air.

Take the air conditioner weight into account and select a place where noise and vibration are minimum.

Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

 

Sunroof

More than

 

300mm

 

Fence

More than

300mm

 

or

 

obstacles

More than 600mm

 

 

More than 700mm

 

Unit : mm

2. Piping length and the elevation

FREE JOINT SINGLE OUTDOOR

 

 

Pipe Size

Length A(m)

Elevation B(m)

Additional

Model

Capacity

 

 

 

 

 

 

Refrigerant

Gas

Liquid

Standard

Max.

Standard

Max.

 

 

(g/m)

 

 

 

 

 

 

 

 

 

AUUQ18GH1

5kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

AUUQ21GH1

6kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

AUUQ24GH1

7kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AUUQ36GH1

10kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AUUQ42GH1

12.5kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AUUQ48GH1

13.4kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AUUQ54GH1

15.8kW

Ø19.05(3/4)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

Ceiling Cassette

 

 

Pipe Size

Length A(m)

Elevation B(m)

Additional

Model

Capacity

 

 

 

 

 

 

Refrigerant

Gas

Liquid

Standard

Max.

Standard

Max.

 

 

(g/m)

 

 

 

 

 

 

 

 

 

ATUQ18GPLE3

5kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

ATUQ21GPLE3

6kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

ATUQ24GNLE3

7kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ATUQ36GMLE3

10kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ATUQ42GMLE3

12.5kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ATUQ48GMLE3

13.4kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ATUQ54GMLE3

15.8kW

Ø19.05(3/4)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

6 Air Conditioner

Installation of Outdoor Unit

Ceiling Suspended Air conditioner

 

 

Pipe Size

Length A(m)

Elevation B(m)

Additional

Model

Capacity

 

 

 

 

 

 

Refrigerant

Gas

Liquid

Standard

Max.

Standard

Max.

 

 

(g/m)

 

 

 

 

 

 

 

 

 

AVUQ18GJLA0

5kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

AVUQ21GJLA0

6kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

 

 

 

 

 

 

 

 

 

AVUQ24GJLA0

7kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AVUQ36GKLA0

10kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AVUQ42GLLA0

12.5kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AVUQ48GLLA0

13.4kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

AVUQ54GLLA0

15.8kW

Ø19.05(3/4)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

Ceiling Concealed Duct

Ceiling Concealed Duct – Low static

Model

Capacity

Pipe Size

Length A(m)

Elevation B(m)

Additional

 

 

 

 

 

 

 

Gas

Liquid

Standard

Max.

Standard

Max.

(g/m)

 

 

 

 

 

 

 

 

 

 

 

ABUQ18GHLA0

5kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

ABUQ18GL2A0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABUQ21GHLA0

6kW

Ø12.7(1/2)

Ø6.35(1/4)

7.5

30

5

15

20

ABUQ21GL2A0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABUQ24GGLA0

7kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

ABUQ24GL3A0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABUQ36GGLA0

10kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ABUQ42GRLA0

12.5kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ABUQ48GRLA0

13.4kW

Ø15.88(5/8)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

ABUQ54GRLA0

15.8kW

Ø19.05(3/4)

Ø9.52(3/8)

7.5

50

5

30

40

 

 

 

 

 

 

 

 

 

Installation Manual 7