This documentation exclusively contains descriptions of the INTERBUS function modules
E82ZAFIC001 and E82ZAFIC010.
)Note!
This documentation supplements the mounting instructions supplied with the
function/communication module and the documentation of the used
standard device.
The mounting instructions contain safety instructions which must be
observed!
ƒ The features and functions of the function module are described in detail.
ƒ Typical applications are explained by means of examples.
ƒ Moreover, this documentation contains the following:
– Safety instructions which must be observed.
– The essential technical data of the function module
– Information on versions of the Lenze standard devices to be used
– Notes on troubleshooting and fault elimination
The theoretical concepts are only explained to the level of detail required to understand
the function of the function module.
Depending on the software version of the controller and the version of the »Engineer«
software installed, the screenshots in this documentation may deviate from the
»Engineer« representation.
This documentation does not describe any software provided by other manufacturers. No
liability can be accepted for corresponding data provided in this documentation. For
information on how to use the software, please refer to the host system (master)
documents.
All brand names mentioned in this documentation are trademarks of their respective
owners.
Validity information
The information given in this documentation is valid for the following devices:
Function moduleType designationFrom hardware versionFrom software version
INTERBUS
4
E82ZAFIC001
E82ZAFIC010
l
4A20
EDS82ZAFIC EN 2.0
Page 5
Target group
This documentation is intended for all persons who plan, install, commission and maintain
the networking and remote service of a machine.
ITip!
Information and auxiliary devices around the Lenze products can be found in
the download area at
http://www.Lenze.com
1.1Document history
VersionDescription
1.011/2002TD06First edition
2.002/2012TD17General revision
About this documentation
Document history
1
Your opinion is important to us!
These instructions were created to the best of our knowledge and belief to give you the
best possible support for handling our product.
If you have suggestions for improvement, please e−mail us to:
feedback−docu@Lenze.de
Thank you for your support.
Your Lenze documentation team
EDS82ZAFIC EN 2.0
l
5
Page 6
1
About this documentation
Conventions used
1.2Conventions used
This documentation uses the following conventions to distinguish between different
types of information:
Type of informationIdentificationExamples/notes
Spelling of numbers
Decimal separator
DecimalStandard notation For example: 1234
Hexadecimal0x[0 ... 9, A ... F]For example: 0x60F4
Binary
l Nibble
Text
Program name» «PC software
Icons
Page reference^Reference to another page with additional
PointIn general, the decimal point is used.
For instance: 1234.56
In quotation marks
Point
For example: ´100´
For example: ´0110.0100´
For example: »Engineer«, »Global Drive
Control« (GDC)
information
For instance: ^ 16 = see page 16
1.3Terminology used
TermMeaning
INTERBUSFieldbus system by PHOENIX CONTACT
Standard device
Controller
MasterINTERBUS node which takes over the master function in the fieldbus system.
SlaveINTERBUS node which represents a slave in the fieldbus system.
Code"Container" for one or several parameters used to parameterise or monitor the
SubcodeIf a code contains several parameters, they are stored in "subcodes".
POWProcess output data word
PIWProcess input data word
PCPPeripherals Communication Protocol
Lenze controllers the function module can be used with (8200 vector, 8200 motec).
controller.
In the documentation, the slash "/" is used to separate the code from the subcode
(e.g. "C00118/3").
6
l
EDS82ZAFIC EN 2.0
Page 7
1.4Notes used
The following pictographs and signal words are used in this documentation to indicate
dangers and important information:
Safety instructions
Structure of safety instructions:
} Danger!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous
situations)
Pictograph and signal wordMeaning
{ Danger!
} Danger!
(Stop!
About this documentation
Notes used
Danger of personal injury through dangerous electrical voltage.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of personal injury through a general source of danger.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of property damage.
Reference to a possible danger that may result in property
damage if the corresponding measures are not taken.
1
Application notes
Pictograph and signal wordMeaning
)Note!
ITip!
,
Important note to ensure troublefree operation
Useful tip for simple handling
Reference to another documentation
EDS82ZAFIC EN 2.0
l
7
Page 8
2
Safety instructions
General safety information
2Safety instructions
)Note!
It is absolutely vital that the stated safety measures are implemented in order
to prevent serious injury to persons and damage to material assets.
Always keep this documentation to hand in the vicinity of the product during
operation.
2.1General safety information
} Danger!
Disregarding the following basic safety measures may lead to severe personal
injury and damage to material assets!
ƒ Lenze drive and automation components ...
... must only be used for the intended purpose.
... must never be operated if damaged.
... must never be subjected to technical modifications.
... must never be operated unless completely assembled.
... must never be operated without the covers/guards.
... can − depending on their degree of protection − have live, movable or rotating parts
during or after operation. Surfaces can be hot.
ƒ All specifications of the corresponding enclosed documentation must be observed.
This is vital for a safe and trouble−free operation and for achieving the specified product
features.
The procedural notes and circuit details provided in this document are proposals which
the user must check for suitability for his application. The manufacturer does not
accept any liability for the suitability of the specified procedures and circuit proposals.
ƒ Only qualified skilled personnel are permitted to work with or on Lenze drive and
automation components.
According to IEC 60364 or CENELEC HD 384, these are persons ...
... who are familiar with the installation, assembly, commissioning and operation of
the product,
... possess the appropriate qualifications for their work,
... and are acquainted with and can apply all the accident prevent regulations, directives
and laws applicable at the place of use.
8
l
EDS82ZAFIC EN 2.0
Page 9
Device− and application−specific safety instructions
2.2Device− and application−specific safety instructions
ƒ During operation, the function module must be firmly connected to the standard
device.
ƒ With external voltage supply, always use a separate power supply unit, safely
separated to EN 61800−5−1 ("SELV"/"PELV"), in every control cabinet.
ƒ Only use cables corresponding to the given specifications (¶ 20).
,Documentation for the standard device, control system, system/machine
All other measures prescribed in this documentation must also be
implemented. Observe the safety instructions and application notes stated in
the documentation.
2.3Residual hazards
Safety instructions
2
Protection of persons
ƒ If the controllers are used on a phase earthed mains with a rated mains voltage
³ 400 V, protection against accidental contact is not ensured without implementing
external measures. (See chapter "4.3", ^ 14)
Device protection
ƒ The module contains electronic components that can be damaged or destroyed by
electrostatic discharge.
EDS82ZAFIC EN 2.0
l
9
Page 10
3
APPLICATION
010 / 3A22
Product description
Application as directed
3Product description
3.1Application as directed
The function module ...
ƒ is an accessory module for use in conjunction with the following Lenze standard
devices:
Product seriesDevice nameFrom hardware version
Frequency inverter
ƒ connects Lenze standard devices to the serial INTERBUS communication system.
ƒ is a device intended for use in industrial power systems.
Any other use shall be deemed inappropriate!
8200 vectorVx14
8200 motecVx14
3.2Identification
APPLICATION
010/3A22
Series
INTERBUS
Version
Variant
001: Coated version
010: PT version
Hardware version
Software version
L
Type
Id.-No.
Prod.-No.
Ser.-No.
E82AF000P0B201XX
E82ZAFX005
E82ZAFICxxxxxxx
10
l
EDS82ZAFIC EN 2.0
Page 11
3.3Connections and interfaces
E82ZAFIC001function module
Pos.DescriptionSee
ALED (yellow): Status of the INTERBUS communication
BLED (green): Connection status to the controller
C
DPlug connector X3.1
EPlug connector X3.2
FPlug connector X3.3
GNameplate^ 10
DIP switch S1
l Setting for the last node = OFF
l Setting for all other nodes = ON
DIP switches S2 ... S4
l Configuration of
– the process data words (PCD)
– the parameter data words (PCP)
– the ID codes
l Connection for external voltage supply of the function module
l Reference terminal GND1, e.g. for external voltage supply of the function
module
l Reference terminal GND2, e.g. for external supply of the controller inhibit
(CINH)
l Connection for
– INTERBUS
– controller inhibit (CINH)
– internal supply of the controller inhibit (CINH)
Product description
Connections and interfaces
^ 54
^ 29
^ 15
3
E82ZAFI004B
EDS82ZAFIC EN 2.0
l
11
Page 12
3
Product description
Connections and interfaces
Function module E82ZAFIC010 (PT version)
Pos.DescriptionSee
ALED (yellow): Status of the INTERBUS communication
BLED (green): Connection status to the controller
C
DPlug connector X3.1
EPlug connector X3.2
FPlug connector X3.3
GNameplate^ 10
DIP switch S1
l Setting for the last node = OFF
l Setting for all other nodes = ON
DIP switches S2 ... S4
l Configuration of
– the process data words (PCD)
– the parameter data words (PCP)
– the ID codes
l Connection for external voltage supply of the function module
l Reference terminal GND1, e.g. for external voltage supply of the function
module
l Reference terminal GND2, e.g. for external supply of the controller inhibit
(CINH)
l Connection for
– INTERBUS
– controller inhibit (CINH)
– internal supply of the controller inhibit (CINH)
^ 54
^ 29
^ 15
E82ZAFI014B
12
l
EDS82ZAFIC EN 2.0
Page 13
4Technical data
4.1General data
FieldValues
Order designationE82ZAFIC001 (coated)
Communication mediumRS485
Network topologyRing (go and return line in the same cable)
Number of bus nodesDependent on INTERBUS master (e.g. Phoenix Contact G4 master).
Communication timel Sum of the cycle time and the processing time in the bus nodes. The
Technical data
General data
E82ZAFIC010 (PT version)
For the following data, which depend on whether PCP communication is
used or not, always the smaller value applies:
l with PCP communication: max. 62 or
l without PCP communication: max. 256/number of PCDs
l With 1 word PCP: 227 (0xE3)
l Without PCP: 3 (0x03)
0 or 1 word
l Abort
l Status
l Identify
l Get−0V−long
l Read
l Write
times are independent of each other.
l Processing time in the standard device
– Parameter data (PCP): approx. 30 ms + 20 ms tolerance
– Process data (PCD): approx. 3 ms + 2 ms tolerance
4
EDS82ZAFIC EN 2.0
l
13
Page 14
4
Technical data
Operating conditions
4.2Operating conditions
Ambient conditions
Climate
Storage
TransportIEC/EN 60721−3−22K3 (−25 to +70 °C)
OperationCorresponding to the data of the Lenze standard device used (see documentation
PollutionEN 61800−5−1Degree of pollution 2
Degree of protectionIP20 (protection against accidental contact according to NEMA 250 type 1)
4.3Protective insulation
Insulation between incoming bus and ...Type of insulation (acc. to EN 61800−5−1)
l 8200 vector/motec power sectionReinforced insulation
l Reference earth / PEFunctional insulation
l Terminal X3.1/59Functional insulation
l Terminal X3.3/20Functional insulation
l Terminal X3.3/28Functional insulation
IEC/EN 60721−3−11K3 (−25 to +60 °C)
of the standard device).
Insulation between incoming bus and ...Type of insulation (acc. to EN 61800−5−1)
Outgoing busFunctional insulation
Insulation between outgoing bus and ...Type of insulation (acc. to EN 61800−5−1)
l 8200 vector/motec power sectionReinforced insulation
l Reference earth / PEFunctional insulation
l Terminal X3.1/59No electrical isolation
l Terminal X3.3/20No electrical isolation
l Terminal X3.3/28Functional insulation
14
l
EDS82ZAFIC EN 2.0
Page 15
Technical data
Connection terminals
4
4.4Connection terminals
Terminal
X3.1/
59External voltage supply of the function module
7GND1Reference potential for terminal X3.3/20
Terminal
X3.2/
7GND1Reference potential for terminal X3.3/20
39GND2Reference potential for controller inhibit (CINH) on terminal X3.3/28
Terminal
X3.3/
A/DO1
BDO1
C/DI1
DDI1
EGND3Reference potential for incoming data line
F/DO2
GDO2
H/DI2
JDI2
KGND1Reference potential for outgoing data line
+
28CINHController inhibit
20DC voltage source for internal supply of controller inhibit (CINH)
DesignationFunction / level
DesignationFunction / level
DesignationFunction / level
l U = 24 V DC (21.6 V − 0% ... 26.4 V + 0 %)
l Current consumption for 24 V DC: I = 90 mA
If the supply voltage is looped through to other bus nodes via terminal 59,
the current flowing must not exceed 3 A.
RS485 data line (incoming)
RS485 data line (outgoing)
Additional HF shield termination
l Input resistance: 3.3 kW
l Start = HIGH (+12 ... +30 V DC)
l Stop = LOW (0 ... +3 V DC)
l +20 V DC (reference: GND1)
l I
= 10 mA
max
EDS82ZAFIC EN 2.0
l
15
Page 16
4
Technical data
Communication time
Cycle time
4.5Communication time
4.5.1Cycle time
The cycle time of the communication system is the time required to exchange all process
data between the INTERBUS master and the nodes.
It depends on the data of the communication system and can be calculated e. g. for a baud
rate of 500 kbps as follows:
t
+ 3.35 @ 10*3(n ) 48 ) 3BK) ) 0.24L ) 0.2
zykl
t
cycl
nSum of all data bits in the INTERBUS ring
BTNumber of bus terminals
LLength of the remote bus cable [km]
Cycle time [ms]
The following diagram shows the relationship between the cycle time and the number of
connected bus nodes. The given values refer to the connection of Lenze controllers
(e. g. 82xx) with 48 bits (1 parameter data word + 2 process data words.
Cycle time
[ms]
12
10
8
6
4
2
1
10
Number of bus nodes
Fig. 4−1Relationship between cycle time and number of bus nodes
20
3040
5060
4.5.2Processing time 8200vector / 8200 motec
The processing time in the controller is added to the INTERBUS transmission time or cycle
time.
There are no dependencies between parameter data and process data.
ƒ Parameter data (PCP): approx. 30 ms + 20 ms tolerance
ƒ Process data (PCD): approx. 3 ms + 2 ms tolerance
16
l
EDS82ZAFIC EN 2.0
Page 17
Technical data
Dimensions
Processing time 8200vector / 8200 motec
4
4.6Dimensions
E82ZAFIC001function module
Function module E82ZAFIC010 (PT version)
E82ZAFI004B
E82ZAFI014B
EDS82ZAFIC EN 2.0
l
17
Page 18
5
Installation
Mechanical installation
5Installation
} Danger!
Inappropriate handling of the function module and the standard device can
cause serious injuries to persons and damage to material assets.
Observe the safety instructions and residual hazards included in the
documentation of the standard device.
(Stop!
The device contains components that can be destroyed by electrostatic
discharge!
Before working on the device, the personnel must ensure that they are free of
electrostatic charge by using appropriate measures.
5.1Mechanical installation
Follow the notes given in the Mounting Instructions for the standard device for the
mechanical installation of the function module.
The Mounting Instructions for the standard device ...
ƒ are part of the scope of supply and are enclosed with each device.
ƒ provide tips to avoid damage provide tips to avoid damage through improper
handling.
ƒ describe the obligatory order of installation steps.
18
l
EDS82ZAFIC EN 2.0
Page 19
Wiring according to EMC (CE−typical drive system)
5.2Electrical installation
5.2.1Wiring according to EMC (CE−typical drive system)
For wiring according to EMC requirements observe the following points:
)Note!
ƒ Separate control cables/data lines from motor cables.
ƒ Connect the shields of control cables/data lines at both ends in the case of
digital signals.
ƒ Use an equalizing conductor with a cross−section of at least 16mm
(reference:PE) to avoid potential differences between the bus nodes.
ƒ Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.
Wiring procedure
Installation
Electrical installation
5
2
1. Observe the bus topology, do not use any stubs.
2. Follow the wiring notes given in the documentation for the control system.
3. Only use cables which comply with the specifications listed (¶ 20).
4. Observe the notes concerning the voltage supply of the function module (¶ 21).
EDS82ZAFIC EN 2.0
l
19
Page 20
5
Installation
Electrical installation
Wiring with a host (master)
5.2.2Wiring with a host (master)
1
3
GG
+
E82ZAFICxxx
222
400 m
400 m
No.ElementDescription
1HostE.g. PC or PLC with INTERBUS master interface module
2Bus cableConnects the INTERBUS master interface module to the function modules.
3INTERBUS slaveApplicable standard device (^ 10) with function module.
GG
+
E82ZAFICxxx
3
E82ZAFICxxx
l Set DIP switch S1 ( ^ 29):
GG
3
+
– Setting for the last node = OFF
– Setting for all other nodes = ON
E82ZAFI008
Specification of the transmission cable
General characteristics
Cable typeSold by the meter,
(e.g. PHOENIX CONTACT: IBS RBC Meter−T, Order No. 28 06 28 6)
Number of conductors3 × 2, twisted pairs, with shared shield
Conductor cross−section> 0.2 mm
DC cable resistance< 96 W/km
Impedance (characteristic)l 120 W ± 20 % (f = 64 kHz)
l 100 W ±15 W (f > 1 MHz)
Capacitance per unit length< 60 nF/km (f = 800 Hz)
2
20
l
EDS82ZAFIC EN 2.0
Page 21
Installation
Electrical installation
Voltage supply
5
5.2.3Voltage supply
Internal DC voltage supply
The internal voltage ...
ƒ supplies the controller inhibit (CINH).
ƒ is available at terminal X3.3/20.
External voltage supply
)Note!
Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.
External voltage supply of the communication module is required if communication via
the fieldbus is to be maintained even when the power supply of the standard device fails.
)Note!
With external voltage supply of the function module, the active bus
terminating resistor is fed independently of the operation of the standard
device. In this way, the bus system remains active even when the standard
device is switched off or fails.
EDS82ZAFIC EN 2.0
l
21
Page 22
5
Installation
Electrical installation
Voltage supply
Supply of controller inhibit (CINH)
Supply via the internal voltage source (X3.3/20)Supply via the external voltage source
GND1
5959
X3.1
ABCDE FGHJ K ++28 20
X3.3
7
GND1
X3.2
GND3GND1
GND2
77
39
+20V
E82ZAFI001E82ZAFI002
GND1
7
5959
X3.1
ABCDE FGHJ K ++28 20
X3.3
Minimum wiring required for operation
Supply of function module and controller inhibit (CINH) via external voltage source
GND1
7
5959
X3.1
+
ABCDEFGHJK+ 28 20
X3.3
GND1
X3.2
_
+
GND3GND1
GND2
39
77
_
+
+20V
GND1
GND2
39
77
X3.2
GND3GND1
_
+
+20V
E82ZAFI003
Minimum wiring required for operation
22
l
EDS82ZAFIC EN 2.0
Page 23
Installation
Electrical installation
Terminal assignment
5
5.2.4Terminal assignment
Terminal
X3.1/
59External voltage supply of the function module
7GND1Reference potential for terminal X3.3/20
Terminal
X3.2/
7GND1Reference potential for terminal X3.3/20
39GND2Reference potential for controller inhibit (CINH) on terminal X3.3/28
Terminal
X3.3/
A/DO1
BDO1
C/DI1
DDI1
EGND3Reference potential for incoming data line
F/DO2
GDO2
H/DI2
JDI2
KGND1Reference potential for outgoing data line
+
28CINHController inhibit
20DC voltage source for internal supply of controller inhibit (CINH)
DesignationFunction / level
DesignationFunction / level
DesignationFunction / level
l U = 24 V DC (21.6 V − 0% ... 26.4 V + 0 %)
l Current consumption for 24 V DC: I = 90 mA
If the supply voltage is looped through to other bus nodes via terminal 59,
the current flowing must not exceed 3 A.
RS485 data line (incoming)
RS485 data line (outgoing)
Additional HF shield termination
l Input resistance: 3.3 kW
l Start = HIGH (+12 ... +30 V DC)
l Stop = LOW (0 ... +3 V DC)
l +20 V DC (reference: GND1)
l I
= 10 mA
max
EDS82ZAFIC EN 2.0
l
23
Page 24
5
Installation
Electrical installation
Cable cross−sections and screw−tightening torques
5.2.5Cable cross−sections and screw−tightening torques
E82ZAFIC001function module
RangeValues
Electrical connectionTerminal strip with screw connection
12.Enable the standard device via terminal 28 (CINH).
l Set terminal 28 to HIGH level.
13.Select setpoint.
l The master transmits the setpoint via the selected process output data
word.
14.Change to the READY TO START state:
l The master transmits the DRIVECOM control word:
0000 0000 0111 1110
15.The standard device is in the READY TO START state.
l The master receives the DRIVECOM status word:
xxxx xxxx x01x 0001
16.Change to the OPERATION ENABLED state.
l The master transmits the DRIVECOM control word:
0000 0000 0111 1111
17.The drive starts up.
bin
bin.
bin
(007E
(007F
hex
hex
).
).
Detailed
information
INTERBUS
communication
manual
^ 42
28
l
EDS82ZAFIC EN 2.0
Page 29
6.3Configuring Host (master)
For communication via the function module, first the host (master) must be configured.
Master settings
The configuration of the INTERBUS requires the device description file (EDS file) for the
communication module to be imported to the master configuration software.
The EDS file can be downloaded in the download area on http://www.Lenze.com.
6.4Setting for last bus node
DIP switch 1
ON
Commissioning
Configuring Host (master)
6
1ON234
OFF
)Note!
ƒ DIP switch 1 must only be set to OFF for the last physical node.
ƒ Lenze setting: all switches OFF
PositionNotes
OFFStandard device with function module is the last bus node
ONStandard device with function module is not the last bus node.
E82ZAFI009
EDS82ZAFIC EN 2.0
l
29
Page 30
6
Commissioning
Defining the user data length
6.5Defining the user data length
The number of process data words (PCD) and parameter data words (PCP) can be set via
code C1515 or via the DIP switches S2 ... S4.
)Note!
ƒ Sum of all data words (PZD + PCP): max. 4 words
ƒ Switch off the voltage supply of the function module and the controller and
then on again to activate the changed settings.
Settings via DIP switches S2 ... S4
ON
1ON234
ƒ If one of the DIP switches S2 ... S4 is set to OFF, the configurations resulting from all
OFF
E82ZAFI009
switch positions are active at switch−on.
ƒ If the switch positions are invalid, the Lenze setting is activated:
– DIP switches S2 ... S4 = OFF (2 PCD words + 1 PCP word)
ƒ Code C1525 displays the current settings of the DIP switches S2 ... S4.
DIP switch
S2S3S4
OFFOFFOFF021227
ONOFFOFF131227
OFFOFFON4203
ONOFFON5403
ONONONCode C1515 active.
ValueNumber of process data
words (PCD)
Number of parameter
data words (PCP)
ID code
30
l
EDS82ZAFIC EN 2.0
Page 31
Defining the user data length
Settings via code
ƒ DIP switches S2 ... S4 = ON
ƒ Set the number of data words (PCD + PCP) via C1515.
Commissioning
6
Code
C1515
SubcodeLenzeValuesAccessData type
−0
ValuesDescription
0, 1, 4, 5The configuration resulting from the values corresponding to the set DIP switch
11 ... 14l No PCP
21 ... 23l 1 word PCP
Name
Process/parameter data specification
0, 1, 4, 5
11...14
21...23
positions becomes active.
l 11 (1 word PCD) ... 14 (4 words PCD)
l 21 (1 word PCD) ... 23 (3 words PCD)
0x5A14 (23060)
Index
rwFIX32
EDS82ZAFIC EN 2.0
l
31
Page 32
6
6.6Connecting the mains voltage
Commissioning
Connecting the mains voltage
)Note!
If the external voltage supply of the function module is used, switch it on as
well.
ƒ The standard device is ready for operation approx. 1 s after switching on the supply
voltage.
ƒ The controller inhibit is active.
ƒ The green LED at the front of the function module is lit.
Protection against uncontrolled start−up
)Note!
Establishing communication
For establishing communication via an externally supplied function module,
the standard device must be switched on as well.
ƒ After communication has been established, the externally supplied module
is independent of the power on/off state of the standard device.
Protection against uncontrolled start−up
After a fault (e.g. short−term mains failure), a restart of the drive is not always
wanted and − in some cases − even not allowed.
The restart behaviour of the controller can be set in C0142:
ƒ C0142 = 0 (Lenze setting)
– The controller remains inhibited (even if the fault is no longer active).
– The drive starts in a controlled mode by explicitly enabling the controller:
LOW−HIGH edge at terminal 28 (CINH)
ƒ C0142 = 1
– An uncontrolled restart of the drive is possible.
32
l
EDS82ZAFIC EN 2.0
Page 33
7Process data transfer
INTERBUS transmits two different data types between the host (master) and the
controllers (slaves):
ƒ Parameter data
ƒ Process data
Process data
ƒ Process data is transmitted via the process data channel.
ƒ The process data serves to control the controller.
ƒ The host can directly access the process data. Data in the PLC, for instance, are
directly stored in the I/O area.
ƒ The data exchange between the master drive and the controller is required in the
shortest possible time. Here, small amounts of data can be transmitted cyclically.
Process data transfer7
ƒ Process data ...
– are not saved in the controller;
– are transmitted between the host system and the controllers in order that a
constant exchange between current input and output data takes place.
ƒ Process data are, for instance, setpoints and actual values.
Parameter data
ƒ Parameter data is transmitted via the parameter data channel (PCP channel).
ƒ The transmission of parameter data is usually not time−critical.
ƒ Parameter data are, for instance, operating parameters, motor data and diagnostic
information.
ƒ The access to all Lenze codes and indices is permitted.
ƒ When saving parameter changes, please observe the notes regarding code C0003.
EDS82ZAFIC EN 2.0
l
33
Page 34
7
Process data transfer
Lenze device control
Process data transfer
7.1Lenze device control
)Note!
Deactivate the DRIVECOM device control if you want to use the Lenze device
control.
For this purpose, use code C1510 / C1511.
7.1.1Process data transfer
Process data telegrams between the host (master) and the controllers (slaves) connected
to the INTERBUS are distinguished as follows with regard to their direction:
ƒ Process data telegrams from the master
The master transmits max. 4process output data words (POW) to the slave.
ƒ Process data telegrams to the master
The master receives max. 4process input data words (PIW) from the slave.
Via the free configuration of the process data, assign the max. 4 process data words of the
INTERBUS to the process data words of the controller. The assignments can be defined in
the codes C1511 (process output data) ad C1510 (process input data).
Process data telegram to the master
The function block to be used for the cyclic process data telegram from the drive to the
master is called AIF−OUT.
The status word (byte 1 and byte 2) contained in the process data telegram is sent to the
master via the AIF−OUT function block.
Process data telegram from the master
The function block to be used for the cyclic process data telegram from the master to the
drive is called AIF−IN.
The control word (byte 1 and byte 2) contained in the process data telegram is sent from
the master and is received in the controller via the AIF−IN function block.
34
l
EDS82ZAFIC EN 2.0
Page 35
Process data transfer
Lenze device control
Process data transfer
Selection of setpoint source
8200 vector / 8200motec controller
For these controllers, the selection of the setpoint source is defined using code C0001
(index: 0x5FFE). For evaluating the process data, the code C0001 has to be set to the
value"3" when the controller is operated with the function module. The setpoint source is
provided by the process data channel which describes the frequency setpoint (mapping to
C0046) and the control word (C0135).
In C0412/x, the assignment of the setpoint source to the desired analog signal can be
checked/changed.
)Note!
The selection of the setpoint source (C0001) must be set identically in all
parameter sets used in the controller.
7
EDS82ZAFIC EN 2.0
l
35
Page 36
7
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
7.1.2Process data signals for 8200 vector / 8200 motec
Configuring process output data
The assignment of the max. 4 process output data words (POW) of the master to bit control
commands or setpoints of the controller can be configured freely using C1511.
ƒ In order to activate the DRIVECOM device control, assign the DRIVECOM control
word to a POW (C1511/x = 17).
– The DRIVECOM control word is mapped to the FIF control word 1.
– The controller conforms to the DRIVECOM state machine (¶ 42).
ƒ The FIF control words can be used to set up an extended Lenze device control
(¶ 38).
)Note!
When C1511 is changed, the process output data is automatically locked to
ensure data consistency. Use C1512 to enable single or all POWs.
Configuration of the process output data
Code
C1511
SubcodeLenzeAccessData type
1POW117DRIVECOM control word (DRIVECOM−CTRL)rwFIX32
2POW23Setpoint 1 (NSET1−N1)rwFIX32
3POW34Setpoint 2 (NSET1−N2)rwFIX32
4PAW45Additional setpoint (PCTRL1−NADD)rwFIX32
þ Parameter set transfer
Name
Configuring process output data
0x5A18 (23064)
Index
ITip!
For a detailed description of the code, see ^ 59.
36
l
EDS82ZAFIC EN 2.0
Page 37
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
7
Master
INTERBUS
PAW 1
PAW 2
PAW 3
PAW 4
C1511/1
C1511/2
C1511/3
C1511/4
C1511/x = 17
C1511/x = 1
C1511/x = 2
C1511/x = 3
C1511/x = 4
C1511/x = 5
C1511/x = 6
C1511/x = 7
C1511/x = 9
C1511/x = 10
C1511/x = 11
C1511/x = 13
C1511/x = 14
C1511/x = 15
C1511/x = 16
DRIVECOM
CTRL
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5, 6
Byte 7, 8
Byte 9, 10
Byte 11, 12
Byte 13, 14
Byte 15, 16
Byte 17, 18
Byte 19, 20
Byte 21, 22
Byte 23, 24
Byte 25, 26
Byte 27, 28
Byte 29, 30
Byte 31, 32
FIF-CTRL.B0
FIF-CTRL.B1
FIF-CTRL.B2
FIF-CTRL.B3
FIF-CTRL.B4
FIF-CTRL.B8
FIF-CTRL.B9
FIF-CTRL1
FIF-CTRL.B10
FIF-CTRL.B11
FIF-CTRL.B12
FIF-CTRL.B15
FIF-CTRL.B16
FIF-CTRL.B17
FIF-CTRL.B30
FIF-CTRL2
FIF-CTRL.B31
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
FIF-IN.W1
16 Bit
FIF-IN.W2
16 Bit
FIF-IN.W3
16 Bit
FIF-IN.W4
…
…
…
FIF-IN
DCTRL
QSP
DCTRL
CINH
TRIP-SET
TRIP-RESET
FIF-NSET1-N1
FIF-NSET1-N2
FIF-PCTRL1-NADD
FIF-PCTRL1-ACT
FIF-PCTRL1-SET1
FIF-RESERVED
FIF-MCTRL1-MSET
FIF-MCTRL1-VOLT-ADD
FIF-MCTRL1-PHI-ADD
FIF-RESERVED
FIF-IN.W1. B0 … FIF-IN.W1.B15
FIF-IN.W2. B0 … FIF-IN.W2.B15
FIF-IN.W1
FIF-IN.W2
FIF-IN.W3
FIF-IN.W4
C0410/x
200
C0412/x
200
C0415/x
C0417/x
C0418/x
C0419/x
C0421/x
Interne
Digitalsignale
Interne
Analogsignale
Digitalausgänge
Digitalsignale
auf Bus
Analogausgänge
Analogsignale
auf Bus
EDS82ZAFIC EN 2.0
Fig. 7−1Free configuration of the 4 process output data words of the INTERBUS
l
E82ZAFI022/023
37
Page 38
7
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
FIF control word 1 (FIF−CTRL1)FIF control word 2 (FIF−CTRL2)
6UP function of motor potentiometer (MPOT1−UP)6CCW rotation/quick stop (QSP) (DCTRL1−CCW/QSP)
01Not active
Active
7DOWN function of motor potentiometer (MPOT1−DOWN)7X3/E1 is digital frequency input (DFIN1−ON)
01Not active
Active
8
Reserved
9Controller inhibit (FIF−CTRL1−CINH)9
01Controller enabled
Controller inhibited
10External fault (FIF−CTRL1−TRIP−SET)10
11Reset fault (FIF−CTRL1−TRIP−RESET)
0 Þ 1Bit change resets TRIP
12 / 13Parameter set changeover
(DCTRL1−PAR3/4 | DCTRL1−PAR2/4)
Bit 13 12
0001PAR1
1101PAR3
PAR2
PAR4
14DC injection brake (MTCRL1−DCB)
01Not active
Active
15
Reserved
Tab. 7−1Parameter structure of FIF control word (FIF−CTRLx)
01Not active
Active
1Switch off I−component of process controller
(PCTRL1−I−OFF)
01Not active
Active
01Not active
Active
3
Reserved
Do not write to this bit!
01Not active
Active
01Not active
Active
01Not active
Active
01Not active
Active
8
11
12
13
14
15
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
38
)Note!
Use of bit 5 and bit 6 in FIF control word 2
Set codes C0410/22 (DCTRL1−CW/QSP) and C0410/23 (DCTRL1−CCW/QSP) to
"200".
l
EDS82ZAFIC EN 2.0
Page 39
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
Configuring process input data
The assignment of the bit status information or actual values of the controller to the max.
4 process input data words (PIW) of the master can be configured freely:
ƒ In order to access DRIVECOM−compliant status information, assign the DRIVECOM
status word to a PIW (C1511/x = 18).
ƒ The FIF status word1 is mapped to the DRIVECOM status word.
Configuration of the process input data
7
Code
C1510
SubcodeLenzeAccessData type
1PIW118DRIVECOM status word (DRIVECOM−STAT)rwFIX32
2PIW23Output frequency with slip (MCTRL1−NOUT+SLIP)rwFIX32
3PIW34Output frequency without slip (MCTRL1−NOUT)rwFIX32
4PIW45Apparent motor current (MCTRL1−IMOT)rwFIX32
þ Parameter set transfer
Name
Configuring process input data
0x5A19 (23065)
ITip!
For a detailed description of the code, see ^ 58.
Index
EDS82ZAFIC EN 2.0
l
39
Page 40
7
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
Fig. 7−11Free configuration of the 4 process input data words of the INTERBUS
l
EDS82ZAFIC EN 2.0
Page 41
Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
FIF status word 1 (FIF−STAT1)FIF status word 2 (FIF−STAT2)
BitAssignmentBitAssignment
0Current parameter set bit 0 (DCTRL1−PAR−B0)0Current parameter set bit 1 (DCTRL1−PAR−B1)
01Parameter set 1 or 3 active
Parameter set 2 or 4 active
1Pulse inhibit (DCTRL1−IMP)1TRIP, Q
01Power outputs enabled
Power outputs inhibited
2I
limit (MCTRL1−IMAX)
max
(If C0014 = 5: Torque setpoint)
01Not reached
Reached
3Output frequency = frequency setpoint
(DCTRL1−RFG1=NOUT)
01False
True
4Ramp function generator input 1 = ramp function
(NSET1−RFG1−I=O)
01False
5Q
01Not reached
generator output 1
True
threshold (PCTRL1−QMIN)5C0054 < C0156 and NSET1−RFG1−I=O
min
Reached
6Output frequency = 0 (DCTRL1−NOUT=0)6LP1 warning (fault in motor phase) active
01False
True
7Controller inhibit (DCTRL1−CINH)7f < f
01Controller enabled
Controller inhibited
11...8Device status (DCTRL1−STAT*1 ... STAT*8)8TRIP active (DCTRL1−TRIP)
Bit 11 10 9 8
00000100Controller initialisation
00011010Operation inhibited
0101 DC−injection brake active
00111101Operation enabled
1000 Fault active
1111 Communication with basic device not
Switch−on inhibit
Flying−restart circuit active
Message active
possible
12Overtemperature warning (DCTRL1−OH−WARN)12
01No warning
− 10 °C reached
J
max
13DC−bus overvoltage (DCTRL1−OV)13
01No overvoltage
Overvoltage
14Direction of rotation (DCTRL1−CCW)14C0054 > C0156 and NSET1−RFG1−I=0
01CW rotation
CCW rotation
15Ready for operation (DCTRL1−RDY)15
01Not ready for operation (fault)
Ready for operation (no fault)
Tab. 7−2Parameter structure FIF status word (FIF−STATx)
01Parameter set 1 or 2 active
Parameter set 3 or 4 active
or pulse inhibit active (DCTRL1−TRIP−QMIN−IMP)
min
01False
True
2PTC warning active (DCTRL1−PTC−WARN)
01False
True
3
Reserved
Do not write to this bit!
4C0054 < C0156 and Q
(DCTRL1−(IMOT<ILIM)−QMIN)
01False
True
(DCTRL1−(IMOT<ILIM)−RFG−I=O)
01False
True
(DCTRL1−LP1−WARN)
01False
True
(NSET1−C0010 ... C0011)
min
01False
True
01False
True
threshold reached
min
9Motor is running (DCTRL1−RUN)
01False
True
10Motor is running clockwise (DCTRL1−RUN−CW)
01False
True
11Motor is running counter−clockwise (DCTRL1−RUN−CCW)
01False
True
Reserved
Reserved
(DCTRL1−(IMOT>ILIM)−RFG−I=O)
01False
True
Reserved
7
EDS82ZAFIC EN 2.0
l
41
Page 42
7
Process data transfer
DRIVECOM control
DRIVECOM state machine
7.2DRIVECOM control
7.2.1DRIVECOM state machine
The control information is provided by the function module via the control word.
ƒ The controllers have standardised device states according to DRIVECOM Profile 20.
ƒ Information on the current device status is stored in the DRIVECOM parameter
"status word".
ƒ Commands in the DRIVECOM parameter "control word" can change the device
status. These commands are represented by arrows in the following diagram.
Switch on device
NOT READY TO SWITCH ON
Status word xxxx xxxx x0xx 0000
Automatically when
initialisation is
completed
SWITCH−ON INHIBIT
Status word xxxx xxxx x0xx 0000
9
Inhibit voltage
xxxx xxxx xxxx xx0x
READY TO SWITCH ON
Status word xxxx xxxx x01x 0001
8
Standstill
xxxx xxxx xxxx
x110
3
Switch on
xxxx xxxx xxxx x111
SWITCHED ON
Status word xxxx xxxx x01x 0011
2
Standstill
xxxx xxxx xxxx x110
FAULT REACTION ACTIVE
Status word xxxx xxxx x0xx 1111
FAULT
Status word xxxx xxxx x0xx 1000
Inhibit voltage
10
xxxx xxxx xxxx xx0x
7
Quick stop
xxxx xxxx xxxx x01x
6
Standstill
xxxx xxxx xxxx x110
13
Fault recognised
Automatically when
fault reaction is completed
14
Reset fault
xxxx xxxx 0xxx xxxx
xxxx xxxx 1xxx xxxx
12
Inhibit voltage
xxxx xxxx xxxx xx01
or
quick stop completed
42
45
Enable operation
xxxx xxxx xxxx 1111 and
act. speed value <> 0*
OPERATION ENABLED
Status word xxxx xxxx x01x 0111
Inhibit operation
xxxx xxxx xxxx 0111 or
act. speed value = 0 *
QUICK STOP ACTIVE
Status word xxxx xxxx x01x 0111
11
Quick stop
Inhibit RFG is mapped to
quick stop
xxxx xxxx xxxx x01x
Fig. 7−2Status diagram of DRIVECOM device control
*only effective for 821X, 8200 vector when the automatic DC injection brake is active (C0106,
C2106 <> 0)
l
EDS82ZAFIC EN 2.0
Page 43
Process data transfer
DRIVECOM control
DRIVECOM control word
7
7.2.2DRIVECOM control word
BitMeaning
0"Switch on" command
0 "Standstill" command active
1 "Switch on" command active
1"Inhibit voltage" command
0 "Inhibit voltage" command active
1 "Inhibit voltage" command not active
2"Quick stop (QSP)" command
0 "Quick stop (QSP)" command active
1 "Quick stop (QSP)" command not active
3"Enable operation" command
0 "Inhibit operation" command active
1 "Enable operation" command active
4"Inhibit RFG" command
Inhibits the ramp function generator (NSET1−RFG1). The quick stop function (QSP) is activated; the
device status of the drive does not change.
Mapping to FIF control word 1 (FIF−CTRL1), bit 3 negated (FIF−CTRL1−QSP)
0 "Inhibit RFG" active
1 "Inhibit RFG" not active
5"RFG stop" command
Ramp function generator output (NSET1−RFG1) is "frozen"; the device status of the drive does not
change.
Mapping to FIF control word 1 (FIF−CTRL1), bit 4 negated (NSET1−RFG1−STOP)
0 "RFG stop" active
1 "RFG stop" not active
6"RFG zero" command
Sets ramp function generator input (NSET1−RFG1) to 0. Þ Controlled deceleration via the ramp set
under C0013; the device status of the drive does not change.
Mapping to FIF control word 1 (FIF−CTRL1), bit 5 negated (NSET1−RFG1−0)
0 "RFG zero" active
1 "RFG zero" not active
7TRIP reset
Resets fault (TRIP)
0 Þ 1 Bit change resets TRIP
8DRIVECOM reserved
9DRIVECOM reserved
10DRIVECOM reserved
11Mapping to FIF control word 1 (FIF−CTRL1), bit 10 (FIF−CTRL1−TRIP−SET)
12Mapping to FIF control word 1 (FIF−CTRL1), bit 12 (DCTRL1−PAR2/4)
13Mapping to FIF control word 1 (FIF−CTRL1), bit 13 (DCTRL1−PAR−3/4)
14Mapping to FIF control word 1 (FIF−CTRL1), bit 14 (MCTRL1−DCB)
15Not used
Tab. 7−3Parameter structure of "DRIVECOM control word" (DRIVECOM−CTRL)
EDS82ZAFIC EN 2.0
l
43
Page 44
7
Process data transfer
DRIVECOM control
DRIVECOM status word
7.2.3DRIVECOM status word
BitMeaning
0Device status "Ready to switch on"
01Status less than "Ready to switch on"
Status at least "Ready to switch on"
1Device status "Switched on"
01Status less than "Switched on"
Status at least "Switched on"
2Device status "Operation enabled"
01Status less than "Operation enabled"
Status "Operation enabled"
3Device status "Fault"
01No fault (TRIP)
Fault (TRIP) active
4Status "Inhibit voltage" command
01Command applied
Command not applied
5Status "Quick stop (QSP)" command
01Command applied
Command not applied
6Device status "Switch−on inhibit"
01Status "Switch−on inhibit" not active
Status "Switch−on inhibit" active
7Collective warning
01No warning
Warning (overtemperature) active
8Collective message
Automatic setting and resetting of pulse inhibit (IMP) in the device status "Operation enabled".
Possible causes: Undervoltage, overvoltage or overcurrent
01No message
Message IMP active
9Bus access right
1 Always
10Status speed/frequency deviation
01RFGon tu RFG
RFGon = RFG
11
12Mapping of FIF status word 1 (FIF−STAT1), bit 0 (DCTRL1−PAR−B0)
13Mapping of FIF status word 2 (FIFSTAT2), bit 0 (DCTRL1−PAR−B1)
14Mapping of FIF status word 1 (FIFSTAT1), bit 2 (MCTRL1−IMAX)
15Mapping of FIF status word 1 (FIF−STAT1), bit 5 (PCTRL1−QMIN)
Status DRIVECOM speed limitation
0
Always
off
off
44
l
EDS82ZAFIC EN 2.0
Page 45
7.2.4Bit control commands
Process data transfer
DRIVECOM control
Bit control commands
7
Bit control commands
CommandMeaning76543210
StandstillFrom different device states ð "Ready to switch
Switch on
Enable operationTransition ð"Operation enabled"
Inhibit operation
Inhibit voltageTransition ð "Switch−on inhibit"
Quick stop (QSP)
Reset faultReset fault
on"
Transition ð "Switched on"xxxxx111
The controller inhibit (CINH) is deactivated.
Transition ð "Switched on"
The controller inhibit (CINH) is activated.
The controller inhibit (CINH) is activated.
Transition ð "Switch−on inhibit"
If the drive has been enabled ð controlled
deceleration via the quick stop ramp.
If the fault has been removed, automatically ð
"Switch−on inhibit".
Reset fault
RFG zero
RFG stop
Inhibit RFG
Enable operation
Quick stop (QSP)
Inhibit voltage
Switch on
The bit control commands of the control word depend on other bit
settings. The command is executed only for the following bit patterns:
Bits of the control wordNote
xxxxx110
xxxx1111
xxxx0111
xxxxxx0x
xxxxx01x
0ð1xxxxxxx
1: Bit set
0: Bit not
set
x: Any bit
status
EDS82ZAFIC EN 2.0
l
45
Page 46
7
Process data transfer
DRIVECOM control
Status bits
7.2.5Status bits
Status bits
Device statusMeaning6543210
Not ready to switchonController is being initialised and is not yet ready
Switch−on inhibit
Ready to switch onController inhibited (CINH).
Switched on
Operation enabledController enabled (CINH).
Fault reaction active
FaultController is in the device status "Fault".0xx1000
Quick stop (QSP)
active
to operate.
After initialisation automatically ð "Ready to
switch on"
Controller inhibited (CINH).
Waiting for "Standstill" command
Waiting for "Switch−on" command
Controller inhibited (CINH).
Waiting for "Operation enabled" command.
Pulse inhibit can be set automatically
Fault (TRIP) recognised, a time−based,
fault−dependent reaction is executed.
Then automatically ð "Fault"
"Quick stop (QSP)" command has been sent in the
device status "Operation enabled" ð controlled
deceleration via the quick stop ramp.
After deceleration automatically ð "Switch−on
inhibit"
Switch−on inhibit
Quick stop (QSP)
Inhibit voltage
Fault
Operation enabled
Switched on
Ready to switch on
The current device status is unambiguously coded in the bits 0 ... 6 of
the status word:
Bits of the status wordNote
0xx0000
1xx0000
01x0001
01x0011
01x0111
0xx1111
00x0111
1 Bit set
0 Bit not
set
x Any bit
status
46
l
EDS82ZAFIC EN 2.0
Page 47
Parameter data transfer
Configure parameter data channel (PCP communication)
8Parameter data transfer
8.1Configure parameter data channel (PCP communication)
Access to the codes of the controller
The parameter data channel (PCP) ...
ƒ enables parameter setting and diagnostics of the controller;
ƒ permits access to Lenze parameters (codes);
ƒ is built up identically for both transfer directions.
The parameter data is addressed via codes that can be found listed in a code table in the
documentation of the controller.
The drive parameters to be changed are included in the Lenze controllers as codes.
The codes of the controller are addressed by the index while being accessed via the
function/communication module.
8
The index for Lenze code numbers is within 16576 (0x40C0) and 24575 (0x5FFF).
Conversion formula:
Index[dez] + 24575 * Lenze−Codestellennummer
Example for code C0001 (operating mode):
Decimal notationHexadecimal notation
Index = 24575 − LENZE CODE NOIndex
Index = 24574 (= 24575 − 1)Index
= 0x5FFF − LENZE CODE NO
hex
= 0x5FFE (= 0x5FFF − 1)
hex
hex
Value range of the Lenze parameters
The value range of the Lenze codes can be obtained from the "Code table" in the
documentation of the controller.
The data of the Lenze parameters is mainly represented in a fixed point format of
INTEGER32 data type with four decimal decimal positions. This means that the parameter
value from the documentation has to be multiplied by 10000.
Example for code C0039 (JOG) = 150.4 Hz
Parameter value multiplied by factor: 150.4 x 10000 =
ƒ 1504000 (decimal notation)
ƒ 0x0016F300 (hexadecimal notation)
EDS82ZAFIC EN 2.0
l
47
Page 48
8
Parameter data transfer
Configure parameter data channel (PCP communication)
Parameter sets for 8200 vector controller
8.1.1Parameter sets for 8200 vector controller
The 8200 vector controller has four parameter sets the parameters of which can be directly
addressed via the INTERBUS.
Addressing
Addressing is carried out with a code offset:
ƒ Offset "0" addresses the parameter set 1 with the codes C0000 ... C1999.
ƒ Offset "2000" addresses the parameter set 2 with the codes C2000 ... C3999.
ƒ Offset "4000" addresses the parameter set 3 with the codes C4000 ... C5999.
ƒ Offset "6000" addresses the parameter set 4 with the codes C6000 ... C7999.
If a parameter is only available once (see documentation of the controller), use the code
offset "0".
Example
Addressing of the code C0011 (maximum field frequency) in different parameter sets:
ƒ C0011 in parameter set 1: Code no. = 11
ƒ C0011 in parameter set 2: Code no. = 2011
ƒ C0011 in parameter set 3: Code no. = 4011
ƒ C0011 in parameter set 4: Code no. = 6011
)Note!
Automatic saving of the changed parameter data is activated (Lenze basic
setting, can be switched off via C0003).
48
l
EDS82ZAFIC EN 2.0
Page 49
Parameter data transfer
Initialise PCP communication
CRL entries
8
8.2Initialise PCP communication
8.2.1CRL entries
In order that communication between the host (master) and the function/communication
module can take place, the following entries in the communication relation list (CRL) of the
master have to be set:
Field nameEntry
Communication reference2
Connection typeMaster/slave acyclic
Connection attributeDefined
Max−PDU Sending−High−Prio0
Max−PDU Sending−Low−Prio64
Max−PDU Receiving−High−Prio0
Max−PDU Receiving−Low−Prio64
Supported Services Request0x803000
Supported Services Response0x000000
Maximum SCC1
Maximum RCC1
Maximum SAC1
Maximum RAC1
8.2.2Available PCP services
The PCP services (PCP = Peripherals Communication Protocol) serve to transmit
parameters via the PCP channel.
Lenze controllers support the following PCP services:
ƒ "Initiate": Establishing connection from the master to the controller (¶ 50)
ƒ "Abort": Aborting connection (¶ 50)
ƒ "Read": Reading parameters (¶ 51)
ƒ "Write": Writing parameters (¶ 51)
ƒ "Get−OD": Reading out the object directory (OD) (¶ 51)
ƒ "Identify": Identification of the controller (¶ 52)
ƒ "Status": Reading the status of the controller (¶ 53)
In the following, only those parameters and their contents are shown which are returned
by the Lenze controllers. All other transfer parameters of the given PCP services can be
obtained from the corresponding descriptions of the master.
EDS82ZAFIC EN 2.0
l
49
Page 50
8
Parameter data transfer
Initialise PCP communication
Available PCP services
Initiate
The "Initiate" PCP service establishes a logic connection between the master and the
function/communication module. The controller provides the following parameters:
DesignationValueMeaning
Profile number0x21DRIVECOM profile of version 1
Password0Password function of INTERBUS is not supported.
Access groups0No access groups exist.
Access protection supportedTRUEAccess protection is supported.
OD version0Version of the object directory
Abort
The "Abort" PCP service aborts a logic connection between the master and the
function/communication module.
50
l
EDS82ZAFIC EN 2.0
Page 51
Parameter data transfer
Initialise PCP communication
Available PCP services
Read and Write
The "Read" PCP service reads parameters from the controller. The controller outputs the
requested parameter or an error message.
The "Write" PCP service writes on parameters of the controller. The controller outputs a
positive or negative feedback or an error message.
The following error messages can occur
Error class Error code Additional code Meaning
630x00No access authorisation
650x10Impermissible job parameter
650x11Invalid subindex
650x12Data length too big
650x13Data length too small
660x00Object is no parameter
670x00Object does not exist
680x00Data types do not comply with each other
800x00Job cannot be executed
800x20Job cannot be executed at the moment
800x21Cannot be executed because of local control
800x22Cannot be executed because of device status
800x30Quit value range/parameter can only be changed if controller is
inhibited (CINH)
800x31Value of the parameter too high
800x32Value of the parameter too low
800x33Sub parameter outside the value range
800x34Value of the sub parameter too high
800x35Value of the sub parameter too low
800x36Maximum value is lower than minimum value
800x41Communication object cannot be displayed on process data
800x42Length of the process data exceeded
800x43General collision with other values
8
EDS82ZAFIC EN 2.0
Get−OD
The "Get−OD" PCP service reads out the object description for every parameter and data
type.
l
51
Page 52
8
Parameter data transfer
Initialise PCP communication
Available PCP services
Identify
The "Identify" PCP service provides information on how to identify the controller. The
controller provides the following parameters:
DesignationValueMeaning
Name of device
manufacturer
Device nameVisible string with 15
Device versionVisible string with 15
"Lenze" (as visible string)Company name
characters
characters
Device name for controller and
function/communication module
Software version of the device
Device name
Composition of the visible string:
ƒ Characters 1 ... 5: Name of the controller
– 4 characters of device name
– 1 space
ƒ Characters 6 ... 10: Name of the function/communication module
– 4 characters of device name
– 1 space
ƒ Characters 11 ... 15: No name
– 5 space
If no function/communication module is available, the corresponding area is filled with
spaces.
Example:
8200 vector controller with communication module EMF2113IB: "8212 2113 "
Visible string
Device name
Standard device
Device name
Module
Space
16
82122113
1115
52
l
EDS82ZAFIC EN 2.0
Page 53
Parameter data transfer
Initialise PCP communication
Available PCP services
Device version
Composition of the visible string:
ƒ Characters 1 ... 5: Software version of the controller:
– 2 characters of basic version
– 2 characters of variant
– 1 character of version of variant
ƒ Characters 6 ... 10: Software version of the function/communication module
– 2 characters of basic version
– 2 characters of variant
– 1 character of version of variant
ƒ Characters 11 ... 15: No name
– 5 spaces
Example:
8200 vector controller (version V3.7; without variant and variant version) with
communication module (version V2.0; without variant and variant version):
"3700020000 "
8
Visible string
Device version
Standard device
Device version
Module
Space
16
3700200000
1115
Status
The "Status" PCP service provides status information on the controller. The controller
provides the following values:
StatusValueMeaning
Logical status0 = ready for communicationInformation on the current operating mode (C0001) of
Physical statusl 0 = ready for operation
Operating status "OPERATION
ENABLED"
l 1 = partly ready for operation
all other device states
Local detail"Status word" parameter24−bit value with:
the controller regarding communication
Information on the current operating status of the
controller.
(for device states, see ^ 42)
l Bit 0 ... 15: "Status word" profile parameter (index =
0x6041)
l Bit 16 ... 23: Value 0
EDS82ZAFIC EN 2.0
l
53
Page 54
9
Diagnostics
LED status displays
9Diagnostics
9.1LED status displays
LED
Pos.ColourCondition
AYellow
BGreen
E82ZAFIxxx, E82ZAFI014B
Description
OffNo communication with the INTERBUS master.
BlinkingCommunication to the INTERBUS master via the function module is
OnInternal error in the function module
Off
BlinkingThe function module is supplied with voltage but not connected to the
OnThe function module is supplied with voltage and is connected to the
established.
l The function module is not supplied with voltage.
l The standard device and/or the external voltage supply is/are
switched off.
standard device.
Causes:
l The standard device is switched off.
l The standard device is in the initialisation phase.
l The standard device is not available.
standard device.
54
l
EDS82ZAFIC EN 2.0
Page 55
Troubleshooting and fault elimination
9.2Troubleshooting and fault elimination
The following faults can occur with controllers interconnected via the INTERBUS:
FaultPossible causeRemedy
INTERBUS master reports
bus error.
Drive cannot be enabled.
l Short circuit / open circuitCheck INTERBUS ring circuit.
l The DIP switch has been set
incorrectly.
l No enable granted via the
control word.
l Controller inhibit (CINH) is still
active.
l No setpoint has been defined.
Diagnostics
Set DIP switch correctly.
Send 0x007F.
X3/28 = HIGH (+12 ... +30 V)
1. C0412/1 =200
INTERBUS must be set as setpoint
source.
2. Assign process output data in C1511 to
setpoint.
9
EDS82ZAFIC EN 2.0
l
55
Page 56
Codetabelle10
10Code table
Overview
CodeSubcodeIndexDesignationSee
C0002−0x5FFD
C1500−0x5A23
C1501−0x5A22
C15021 ... 40x5A21
C15031 ... 40x5A20
C1510−0x5A19
C1511−0x5A18
C1512−0x5A17
C1513−0x5A16
C1514−0x5A15
C1515−0x5A14
C15201 ... 100x5A0F
C15211 ... 100x5A0E
C15221 ... 160x5A0D
C15231 ... 160x5A0C
C1525−0x5A0A
C1530−0x5A05
C15311 ... 40x5A04
(24573)
(23075)
(23074)
(23073)
(23072)
(23065)
(23064)
(23063)
(23062)
(23061)
(23060)
(23055)
(23054)
(23053)
(23052)
(23050)
(23045)
(23044)
Parameter set management^ 67
Software ID^ 62
Software creation date^ 62
Display of the software ID^ 62
Display of the software creation date^ 62
Configuring process input data^ 58
Configuring process output data^ 59
Enable process output data^ 60
Response monitoring time of the PCD
communication
Monitoring response to PCD
communication fault
Process data specification^ 60
Display of all words to the master^ 63
Display of all words from the master^ 63
Display of all process data words to the
standard device
Display of all process data words from
the standard device
Display of the current setting of the DIP
switches S2 ... S4
INTERBUS diagnostics^ 66
Bus counter^ 66
^ 61
^ 61
^ 64
^ 65
^ 65
56
l
EDS82ZAFIC EN 2.0
Page 57
How to read the code table
ColumnMeaning
Code
SubcodeSubcode
NameDesignation of the Lenze code
IndexIndex under which the parameter is addressed.
Lenze
Values
AccessR = read access (reading permitted)
Data typel FIX32: 32−bit value with sign; decimal with 4 decimal positions
(Lenze) code
l The parameters of a configurable code marked with an asterisk (<Code>*) can only be accessed
via the communication module.
l The value of a configurable code marked with a double asterisk (<Code>**) is not transmitted
with the parameter set transfer.
Lenze setting of the code
gDisplay code
Configuration of this code is not possible.
Fixed values determined by Lenze (selection list) or a value range:
Minimum value[Smallest increment/unit]Maximum value
W = write access (writing permitted)
l U16: 2 bytes bit−coded
l U32: 4 bytes bit−coded
l VS: visible string, character string with defined length
Codetabelle10
EDS82ZAFIC EN 2.0
l
57
Page 58
10
Codetabelle
Communication−relevant Lenze codes
10.1Communication−relevant Lenze codes
C1510:
Configuring process input data
Code
C1510
SubcodeLenzeValuesAccessData type
1PIW118
2PIW23
3PIW34
4PIW 45
þ Parameter set transfer
Name
Configuring process input data
The assignment of the bit status information or actual values of the controller to the max.
4 process input data words (PIW) of the master can be configured freely.
)Note!
For reasons of compatibility, subcodes 5 and 6 can also be read and written
with modules from software version V3.0. However, this has no effect.
SelectionScaling
1FIF status word 1 (FIF−STAT1)16 bits
2FIF status word 2 (FIF−STAT2)16 bits
3Output frequency with slip (MCTRL1−NOUT+SLIP)±24000 º ±480 Hz
4Output frequency without slip (MCTRL1−NOUT)±24000 º ±480 Hz
5Apparent motor current (MCTRL1−IMOT)214 º 100 % rated device current
6Actual process controller value (PCTRL1−ACT)±24000 º ±480 Hz
9Device utilisation (MCTRL1−MOUT)±214 º ±100 % rated motor torque
10DC−bus voltage (MCTRL1−DCVOLT)16383 º 565 VDC at 400 V mains
11Ramp function generator input (NSET1−RFG1−IN)±24000 º ±480 Hz
12Ramp function generator output (NSET1−NOUT)±24000 º ±480 Hz
13FIF−OUT.W116 bits or 0 ... 65535
14FIF−OUT.W216 bits or 0 ... 65535
15FIF−OUT.W30 ... 65535
16FIF−OUT.W40 ... 65535
17DRIVECOM control word (DRIVECOM−CTRL)16 bits
18DRIVECOM status word (DRIVECOM−STAT)16 bits
0x5A19 (23065)
Index
see table belowrwFIX32
16383 º 325 VDC at 230 V mains
58
l
EDS82ZAFIC EN 2.0
Page 59
C1511:
Configuring process output data
Codetabelle
Communication−relevant Lenze codes
10
Code
C1511
SubcodeLenzeValuesAccessData type
1POW117
2POW23
3POW34
4POW 45
þ Parameter set transfer
Name
Configuring process output data
see table belowrwFIX32
0x5A18 (23064)
Index
The assignment of the max. 4 process output data words (POW) of the master to bit control
commands or setpoints of the controller can be configured freely using C1511.
)Note!
For reasons of compatibility, subcodes 5 and 6 can also be read and written
with modules from software version V3.0. However, this has no effect.