Addition to the
installation and operating instructions
CAPAFLUX IFM 5080 K / CAP-EEx
CAPAFLUX IFM 5080 K / CAP i-EEx
Compact electromagnetic
flowmeters
...with non-contact and capacitive electrodes
WARNING!
Be sure to follow these instructions !
IMPORTANT!
These additional instructions are an extension to the Installation and Operating Instructions and only
apply to the EEx version of the CAPAFLUX IFM 5080 K / CAP-EEx or IFM 5080 K / CAP i-EEx
electromagnetic compact flowmeter. All technical information described in the “Installation and
Operating Instructions” are applicable, when not specifically excluded, completed or replaced by the
instructions in these additional instructions.
Contents
1 System components 3-6
1.1 General information 3-4
1.2 IFC 090 / CAP … -EEx signal converter 5
1.2.1 Electronics compartment 5
1.2.2 Terminal compartment 5
1.3 Electronics unit 6
2 Electrical connection 7-17
2.1 Equipotential bonding system 7
2.2 Connecting cables 7
2.3 Connection diagram 8
2.4 Regular IFC 090 / CAP - EEx electronics unit 9
2.5 Modis version IFC 090 / CAP i-EEx electronics unit 10
2.6 Connection diagrams MODIS 11-17
3 Operation of the signal converter 18
4 Maintenance 18
5 Service 19-24
5.1 General information for replacements 19
5.2 Replacement of electronics unit 20
5.3 Replacement of power fuse(s) 21-23
5.4 Changing power supply voltage 24
6 Declarations of conformity 25
7 EC-type examination Certificates 26-30
No changes regarding safety may be made to the devices. Unauthorized changes
might affect the explosion safety of the devices.
• The prescriptions and regulations as well as the electrical data described in
the EC-type examination certificate must be obeyed.
• Beside the instructions for electrical installations in non-hazardous
locations according to the applicable national standard (e.g. IEC 364),
especially the regulations in EN 60079-14 "Electrical installations in
hazardous locations" or equivalent national standard must be followed.
• Installation, establishment, utilization and maintenance are only allowed to
be executed by personnel with an education in explosion safety!
This compact flowmeter complies with the European Directive 94/9/EC (ATEX 100a) and has been
approved for hazardous classified locations of Zone 1 and 2 under EC-type Examination Certificate
number:
KEMA 01 ATEX 2232 X
The compact flowmeter is available in two types, namely:
• IFM 5080 K/CAP i-EEx, MODIS version. This type has intrinsical safe signal output circuits, which
are provided by two MODIS modules that are installed on the IFC090 K/CAP/i-EEx electronics unit.
Temperature classification
The regular IFM 5080 K/CAP-EEx compact flowmeter is designed for ambient temperatures (Ta) of
-20°C (special -40°C) up to +60°C.
The allowed process liquid temperature is a.o. limited by the maximum occuring surface temperature of
systems components in the combustible atmosphere that (possibly) surrounds the apparatus (first
column of the table). For dusts the second column of the table applies. Details see following table.
Max. surface
class
(for gases)
T6
T5
T4
The IFM 5080 K/CAP…-EEx compact flowmeter consists of the IFC 090 / CAP/…-EEx signal converter
unit, which is screwed on top of the IFS 5000 CAP-EEx primary head (i.e. measuring unit). The regular
compact flowmeter is marked with one of the following codes below, depending on the type of
protection of the terminal compartment:
temperature
(for dusts)
T 85°C 60°C 55°C not allowed
T 100°C 75°C 75°C 75°C
T 115°C 115°C 115°C 75°C
II 2 GD EEx d IIC T6…T4 (EEx d terminal compartment) or
II 2 GD EEx de IIC T6…T4 (EEx e terminal compartment)
In case of the MODIS version IFM 5080 K/CAP i-EEx, the electronics unit of type IFC 090 / CAPi-EEx
is provided with protective modules, which provide intrinsical safe output signals of category "ia". The
flowmeter is then marked with the codes:
II 2 GD EEx d [ia] IIC T6…T4 (EEx d terminal compartment) or
II 2 GD EEx de [ia] IIC T6…T4 (EEx e terminal compartment)
For details see the EC-type Examination Certificate in
instructions.
The IFC 090 / CAP/…-EEx signal converter consists of a cylindrical housing of die-casted aluminum,
which has two separate compartments, divided from each other by an integrated wall with casted
flameproof terminal feed-through. The neck at the bottom of the housing contains a flameproof cable
feed-through. The signal converter housing is on both ends closed by a cylindrical threaded cover with
O-ring sealing. The housing has an ingress protection degree of IP 65 / IP 67 conform to EN 60529.
1.2.1 Electronics compartment
The electronics compartment accommodates the pre-certified IFC 090 / CAP…-EEx electronics unit
with approval number PTB 98 ATEX 2012 U. The electronics compartment is designed with type of
protection flameproof enclosure "d" according to EN 50018. It is closed by a threaded flameproof
display cover with glass window.
1.2.2 Terminal compartment
The terminal compartment has seven terminals for connection of the power supply and signal output
circuits. Sect. 2 (Connection diagram) shows the terminal arrangement for the regular and MODIS
version of the IFC 090 / CAP/…-EEx signal converter. The terminal arrangement of the MODIS version
(i.e. IFC 090 / CAP i-EEx) is shown in Sect. 2 (Modis Converter). Two of the terminals are used for
connection of the non-intrinsically safe power supply and four terminals (marked with "*") for the
intrinsically safe, category "ia" signal outputs of the MODIS modules. The non-intrinsically and
intrinsically safe terminals are separated from each other by a metal dividing plate, which is screwed to
the remaining (not connected) M4 terminal. The two non-intrinsically safe power supply terminals are
covered by an insulating plate.
The terminal compartment (with standard type of protection increased safety "e") is standard equipped
with two ATEX approved "EEx e" cable glands. The terminal compartment can also be provided as a
flameproof enclosure "d", in which case ATEX approved "EEx d" cable glands of size Pg13.5, Pg16 or
M20x1.5 are either factory installed or must be installed by the customer. For flameproof conduit
systems, the terminal compartment must have type of protection flameproof enclosure "d" according to
EN 50018. The conduits must be sealed by "EEx d" approved (within the ATEX 100a directive) sealing
devices (i.e. stopping box) directly at the conduit entrances of the as flameproof enclosure performed
terminal compartment.
This electromagnetic compact flowmeter can be equipped with the regular IFC 090 / CAP-EEx or with
the IFC 090 / CAP i-EEx electronics unit with intrinsically safe signal outputs (i.e. MODIS version). This
version is descripted in the following.
Regular IFC090-EEx electronics unit
The IFC 090 / CAP-EEx is used in the regular IFM 5080 K-EEx and can be equipped with one of the
following power supplies (depends on the area of application).
Electrical data for power supply
Power supply Terminal Function Electrical data
AC-versions
AC/DC-version
L
N
PE
L
L
FE
Live
Neutral
Protective Ground
Live
Neutral
Functional Ground
U
= 100/115/200/230 Vac -15/+10%
n
= approx. 10 VA, Um = 253 V
P
n
= 24 V ac/dc
U
n
AC: -15/+10%, P
DC: -25/+30%, P
= 253 V
U
m
=10 VA
n
=8 W
n
The IFC 090 / CAP-EEx electronics unit is equipped with the following in-/output circuits. Terminals B1,
B⊥ and B2 can be configured as status or pulse outputs or as control inputs via the software. See the
table below for the electrical data of these in-/output circuits.
Electrical data of in-/output circuits
Terminals Description Nominal voltage Maximum current
I+, I
B1, B⊥, B2
Current output 15 V 22 mA
Pulse, status, control in-/outputs 32 V 150 mA
IFC 090 / CAP i-EEx unit with MODIS modules
The IFC 090 / CAP i-EEx electronics unit is equipped with a pair of MODIS-modules. It is equipped with
one of the following power supplies.
Electrical data of IFC 090 / CAP i-EEx electronics unit
Power supply Terminals Function Electrical data
AC-version
AC/DC-version
L
N
PE
1L
0L
FE
Live
Neutral
Protective Ground
Live
Neutral
Functional Ground
U
= 100…230 Vac –15%/+10%
n
= 15 VA, Um = 253 V
P
n
= 24 Vac/dc
U
n
AC: -15%/+10% or 20.4…26.4 Vac
DC: -25%/+30% or 18…32 Vdc
= 10 W, Um = 253 V
P
n
Note
The mains fuses for both electronics units are listed in Sect. 6 of this manual.
All EEx and EEx/i flowmeters must always be incorporated into the equipotential bonding system of the
hazardous area. This connection can be achieved through the PE/FE conductor connected to the PE
terminal in the terminal compartment (see figure of terminal arrangement below) or through a separate
PE conductor, cross sectional area at least 4 mm
the converter housing.
2.2 Connecting cables
Note
The below described cables are shown in the following connection diagram.
Cable A:
Signal cable for current output and binary outputs (pulse and status output): The cable parameters must
be in accordance with the regulations in the EN 60079-14 "Electrical installations in hazardous
locations" or an equivalent national standard. For the MODIS version with IFC 090 / CAP i-EEx
electronics unit (right detail in connection diagram) the signal cable for the intrinsically safe signal in/outputs must also conform the requirements as specified in the relevant standard national code of
practice for the installation of electrical apparatus with type of protection Intrinsic Safety "i".
Cable B:
Power supply cable: The cable parameters must be in accordance with the regulations of the
EN 60079-14 "Electrical installations in hazardous locations" or an equivalent national standard.
The field cables that enter the terminal compartment of the IFC 090 / CAP-EEx signal converter unit (i.e.
power supply, current and binary outputs) are non-intrinsically safe. To connect external devices to the
signal output terminals, the wiring requirements for the type of protection of the compartment (standard:
increased safety "e", optional: flameproof "d") must be conform to the international or national standard
involved (e.g. EN 60079-14).
The terminal arrangement is shown below.
Terminal arrangement in terminal compartment
pulse and status
outputs or
control inputs
binary
outputs
current
output
100 - 240 V AC / 48 - 63 Hz
24 V AC / DC
PE Protective ground
FE Functional ground
Passive pulse/status output
I ≤ 150 mA
eiectronic
or electro mechanical
totalizer
I≤ 150 mA
≤ 32 V DC
U
ext
≤ 24 V AC
e.g.
signal
indicator
Active current output
R
≤ 500 Ω
i
Note
The binary outputs (terminals B1, B⊥ and B2) can only be configured as passive outputs,
the current output (terminals I+ and I) can only be configured as active output.
2.5 MODIS version IFC 090 / CAP i-EEx electronics unit
The field cables of the non-intrinsically safe power supply and the intrinsically safe, category "ia" signal
outputs enter the terminal compartment of the IFC 090 / CAP i-EEx signal converter unit via two
separate entrances. To connect external devices to the intrinsically safe signal output terminals, the
wiring requirements for their type of protection as well as of the compartment (standard: increased
safety "e", optional: flameproof enclosure "d") must be conform to the international or national standard
involved (e.g. EN 60079-14).
Terminal arrangement in terminal compartment
NC = not connected
Metal dividing
plate IS / non-IS
terminals
Connecting terminals
for intrinsically safe
signal in-/outputs
*** *
NC 1L 0L 24 Vac/dc
L N 100…240 Vac
PE
terminals for
non-intrinsically
safe power supply
Protective Earth terminal
Connecting
Cable entrance for
intrinsically safe
signal cable
The non-intrinsically safe terminals for connection of the power supply (1L
connected according to the relevant standard code of practice for electrical apparatus intended for use
in potentially hazardous locations, type of protection Increased Safety "e" or type of protection
Flameproof Enclosure "d", depending on the type of protection of the terminal compartment of the signal
converter housing.
To gain access to the connection terminals of the power supply, the half-circular cover plate of
insulating material must be slightly lifted at one end and then rotated downwards, see the instruction on
the cover plate. After connection of the power supply cable, the half-circular cover plate must be
restored into its original position, so that the minimum clearances and creepage distances towards the
intrinsically safe signal in-/output terminals are maintained.
For details, see diagram on terminals compartment MODIS on next page.
Cable entrance for
non-intrinsically
safe power supply
cable
Terminal compartment MODIS version IFC 090 / CAP i-EEx
Insulating cover plate
Sticker with handling information
for insulating cover plate
Sticker indicating the intrinsically
safe signal in-/output circuits
The PE (or FE) conductor must be connected to the press-fitted M5 clamp terminal marked inside the
terminal compartment. This conductor must be guided through the rectangular opening in the metal
dividing plate that separates the non-intrinsically safe power supply terminals from the intrinsically safe
signal in-/output terminals.
2.6 Connection diagrams MODIS
Sect. 2.3 shows the block diagram of the EEx electromagnetic compact flowmeter. The power supply
(terminals 1L
ground conductor of the mains supply.
The IFC 090 / CAP i-EEx electronics unit is provided with intrinsically safe signal in-/output circuits due
to the installed pair of MODIS modules in accordance with the table below.
, 0L) is connected via cable B. The PE terminal must be connected to the protective
Overview of MODIS modules
Module Terminal designation Function / Intrinsically safe maximum data
Current output (0/4-20 mA), passive
U
P-SA
I ⊥, I
= 30 V, Ii = 250 mA, Pi = 1.0 W
i
C
= 5 nF, Li ≈ 0
i
Pulse (frequency) output or status in-/output, all passive
FA-ST
B1, B1⊥ or B2, B2 ⊥
The function can be set by software
= 30 V, Ii = 250 mA, Pi = 1.0 W
U
i
C
= 5 nF, Li ≈ 0
i
Fieldbus module, type Profibus system, passive
U
F-PA
D, D ⊥
= 30 V, Ii = 300 mA, Pi = 4.2 W
i
C
= 5 nF, Li ≈ 0
i
Fieldbus module, type Fieldbus Foundation, passive
U
F-FF
D, D ⊥
= 30 V, Ii = 300 mA, Pi = 4.2 W
i
C
= 5 nF, Li ≈ 0
i
Intrinsically safe voltage source for the passive module
P-SA or FA-ST, so that active operation is possible.
= 23.5 V, Io = 98 mA, Po = 0.6 W
U
o
= 132 nF, Lo = 4 mH
C
o
DC-I
I+, B1+
Note!
When modules P-SA (or FA-ST) and DC-I are connected in
series, the internal capacitance C
subtracted from the C
of 127 nF.
C
o
of 132 nF. So the data plate will list a
o
of 5 nF must be
i
Besides the shown intrinsically safe maximum values for voltages and current -which are based on
certain fault conditions as prescribed by the standard EN 50 020 - the nominal values for current and
voltage must also be respected otherwise a proper functioning of the modules is not guaranteed!
Nominal voltage and current values for the MODIS modules
MODIS module Nominal values for voltage and current
P-SA
(passive current output )
Current: 4 ... 20 mA
Working voltage: 8 ... 30V
Voltage drop : 8V at 4mA
FA-ST
(frequency / pulse / status output
or control input)
Working voltage: 6 ... 30V
Working current: < 110 mA
Voltage drop: in ON-state: < 2V at 110 mA
Leakage current in OFF-state: < 900 µA at 30V
Control input:
Input voltage LOW level: < 3V
Input voltage HIGH level: > 7V
Frequency range : 0 .. 12 KHz
DC-I
(active voltage source)
Voltage: 20V
Current 30 mA
Internal resistance: 260 Ω
The active module DC-I is needed in the 24 Vac/dc power supply version to form an active current or
pulse output in combination with one of the passive modules P-SA or FA-ST. Due to limited space it is
not available for 100...230 Vac supply versions.
Possible combinations of the installed MODIS modules for the 24 Vac/dc power supply
version of the IFC 090 / CAP i-EEx
IFC 090 /
Part No. MODIS modules Terminal designation
CAP i-EEx
version
Possible combinations of the installed MODIS modules for the 100-230 Vac power supply
version of the IFC 090 / CAP i-EEx
IFC 090 /
Part No. MODIS modules Terminal designation
CAP i-EEx
version
Ex-i1
Ex-i2
Ex-i4
Ex-i6
Ex-i7
Ex-i8
Due to mechanical and electrical limitations, only the listed pairs of MODIS modules are possible. The
two modules each use two terminals of the bottom four terminals of the flameproof terminal feedthrough in the dividing wall between the electronics and terminal compartment of the signal converter
housing, except for the combination with module DC-I (only applicable for 24 Vac/dc versions), where
only two of the four terminals are used. Interconnection of the two modules, P-SA with DC-I or FA-ST
with DC-I is made internally.
The flameproof terminal feed-through has seven terminals in total, the top two terminals are used for
connection of the power supply, the third one is only used for mounting of a metal dividing plate with
insulating cover plate. The remaining four are used for the intrinsically safe signal in-/output circuits of
the installed MODIS modules.
The metal dividing plate and the insulating cover plate warrant the required separation distances (i.e.
clearances, creepage distances and distances through insulation) between the non-intrinsically safe
power supply terminals and the intrinsically safe signal in-/output circuits. The insulating cover plate is
provided with a sticker that contains important instructions how to remove and re-install the cover plate
and the conditions under which it should be established (circuits not live !).
Carefully follow the instructions on the sticker that is glued to the top of the insulating
cover plate that covers the non-intrinsically safe power supply terminals !
For the connection diagrams of the intrinsically safe signal in-/outputs of the installed MODIS modules in
the IFC 090 / CAP i-EEx electronics unit (see figures on the following pages). It has to be noted that the
intrinsically safe signal in-/outputs may only be connected to the following listed apparatus' (registering
devices like amp-meters, pulse counters, etc.):
EEx-approved intrinsically safe apparatus;
EEx-approved associated apparatus;
Passive apparatus as defined in your national standard for installation of electrical apparatus in
hazardous locations (e.g. EN 60079-14).
Other types of apparatus may only be connected to the intrinsically safe signal in-/outputs through EExapproved safety barriers, isolating interface units and the like. These barriers or units are not depicted in
the connection diagrams for reasons of readability. It is assumed that they are an integrated part of the
registering devices or as separate devices connected in series with them. The registering devices may
only be installed in the hazardous location if they also have a type of protection for explosion safety
according to the European Standards of the EN 500xx series, or if they are constructed as prescribed in
your standard national code of practice.
When the intrinsically safe signal in-/outputs are connected to other intrinsically safe or associated
apparatus, the maximum safety values (i.e. entity parameters) of all intrinsically safe circuits have to be
considered.
Important !
The 100…230 Vac power supply versions of the IFC 090 / CAP i-EEx signal
converter electronics unit with MODIS modules can only be equipped with passive
outputs. Therefore the connection diagrams with the numbers 2, 4, 5, 7, 9, 11 and 12
are applicable for the 100…230 Vac power supply versions.
The compact flowmeters are always equipped with magnet sensors. In that way it is possible to change
the settings of the converter with aid of the magnet-bar without the necessity to open the flameproof
converter housing in the hazardous area.
It must be noted that the IFC 090 i/CAP-EEx versions Ex-i2 and Ex-i3, following menus do not apply.
(see also Sect. 4.4. "Table of settable functions" in the standard "Installation and operating instructions"
of the IFC090 K/F signal converter)
1.01 Æ VALUE P
1.06 Output/input B1
1.07 Output/input B2
1.06 PULS B1
1.06 STATUS B1
1.07 STATUS B2
1.06 CONTROL B1
1.07 CONTROL B2
3.02 Æ VALUE P
3.07 HARDWARE
Fct. Text Description and settings
1.00
3.00
3.02 FLOWMETER ...
3.07 HARDWARE
As a consequence, the chapters included in the standard Installations and operating instructions, giving
detailed descriptions of these menus, must be skipped.
1.00 OPERATION Operations menu
1.01 FULL SCALE ...
Æ VALUE P
1.06 Output/Input B1
1.07 Output/Input B2
1.06 PULS B1
1.06
1.07
1.06
1.07
3.00 INSTALL. Installation menu
STATUS B1
STATUS B2
CONTROL B1
CONTROL B2
Æ VALUE P
4 Maintenance
The IFM 5080 K/CAP/…-EEx electromagnetic compact flowmeters are maintenance free with regard to
the flowmetering properties. Within the scope of the periodical inspections, which are required for
electrical apparatus that are installed and used in hazardous classified locations, it is recommended to
check the flameproof enclosure on signs of damage or corrosion. This concerns the converter housing
and the primary head housings.
Contact your (local) KROHNE sales representative for the ordering information of spare parts or
replacements of IFC 090/CAP…-EEx electronics units and/or power fuses.
5.1 General information for replacements
IMPORTANT !
Before opening
• Make absolutely sure there is no explosion hazard!
• If necessary provide a ”Gas-free certificate” !
• Make sure that all connecting cables are safely isolated from the power supply !
When the instructions above are strictly followed, the cover (with glass window) of the electronics
compartment may be removed. First unscrew the recessed head screw of the interlocking device by a
hollow-head screw wrench size 3, until the cover can rotate freely. Unscrew the cover with the special
plastic wrench (black) that is supplied with the apparatus.
After opening
• The copper ground strip at the back of the electronics unit must be securely screwed to the housing
(back-end of electronics compartment) by screw SE (see figure below). The electronics unit is
screwed into the electronics compartment by two screws D. Before screws SE and D can be
accessed, the display unit must be removed via screws A.
• Before the cover is screwed back into the housing, the screw-thread must be clean and well-greased
with an acid and resin-free grease, e.g. silicone grease.
• Screw the cover as tight as possible into the housing by hand, until it cannot be opened by hand
anymore. Screw the recessed head screw of the interlocking device tight.
IFC 090 / CAP-EEx electronics unit after removal of display unit
Note:
SE
Safe earth
connection
The following instructions must be followed carefully, if the IFC 090 / CAP/…-EEx
signal converter housing has to be opened respectively closed again!
Refer to the standard Installation and
Operating Instructions for detailed
A
information about resetting and
reprogramming the new electronics unit
after replacement. The customer specific
data (like the value of the internal
totalizer) are stored in DATAPROM IC-18,
which must be transferred from the "old"
to the "new" electronics unit. See Sect.
8.7 of the standard Installation and
Operating Instructions for detailed
information.
A
Before commencing work, note the instructions in Sect. 5.1,
Then continue as follows:
1. Remove the display cover of the electronics compartment.
2. Unscrew the two screws A (M3) of the display unit (see figure above) and turn it carefully aside.
3. Disconnect the
circuit connector (item C). See figures in Sect. 5.1 and the following.
4. Unscrew the two mounting screws D of the electronics unit and unscrew SE, which fixes the copper
ground strip to the back of the housing. A screwdriver with a long shaft (≥ 200 mm) is most suitable for
unscrewing screw SE (e.g. screwdriver type Philips No. 2).
5. Carefully remove the electronics unit of the converter housing (see the remark below).
6. Check if the voltage setting (only applicable for AC power supplies) and power fuse rating are correct
on the new electronics unit. If necessary, change the voltage setting or replace the power fuse (see
Sect. 5.3 and 5.4 of this manual).
7. Carefully insert the electronics unit (keep cables aside, see remark below). Then mount the unit
completely into the housing and fix the screws. First the two screws D, then screw SE and reconnect
the
2-pole
plugs on the electronics unit (see figure in Sect. 5.1).
8. Finally screw the display unit back on the frame of the electronics via the two screws A.
9. Screw the cover of the electronics compartment back into the housing.
Note the instructions of Sect. 5.1 ("After opening") during reassembling.
IMPORTANT !
2-pole
field circuit connector (item B in figure on last page) and the
field circuit connector B and the
Carefully keep the connecting cables of the field coil and electrode circuits to the
side of the housing, while removing respectively inserting the electronics unit into
the signal converter housing. This is to prevent damaging of the connecting
cables!
10-pole
“Before opening".
10-pole
electrode
electrode circuit connector C to the right counter-
The power fuse(s) of the different IFC 090 / CAP…-EEx electronics units (regular or MODIS) have a
different rating and are located on slightly different locations on the power supply printed circuit board.
Only the power fuse on the 100…230 Vac power supply version of the regular IFC 090 / CAP-EEx
electronics unit can be reached without removing the complete unit out of the housing (only the display
unit has to be unscrewed).
Regular IFC 090 / CAP-EEx with 24 Vac/dc power supply
Note
1. Remove the cover of the electronics compartment.
2. Unscrew the two screws marked with A of the display unit and turn it carefully aside.
3. Disconnect the
connector (item C). See figures in Sect.5.1 and 5.2.
4. Unscrew the two mounting screws D of the electronics unit and screw SE, which fixes the
copper ground strip to the integrated aluminum dividing wall at the back of the electronics
compartment. Use a screwdriver with a long shaft (≥ 200 mm) like type Philips No. 2 for
5. The defective power fuse(s) F1 and/or F2 (see following figure) can be replaced now. The 24 Vac/dc
6. Reassemble in reverse order (points 3 through 1).
IFC 090 / CAP-EEx electronics unit with 24 Vac/dc power supply
Before commencing work, read the instructions in Sect. 5.1 ("Before opening"). Then continue
as follows:
2-pole
field circuit connector (item B) as well as the
screw SE. Then take out the electronics unit, but be careful with the connecting cables, so that
they do not get damaged.
power supply uses two sub-miniature fuses type TR 5 that are rated T1.25 A in accordance with IEC
127-3 publication (part No. 5.09080.00.00).
Note
Read the instructions of Sect. 5.1 ("After opening") during reassembling.
Regular IFC 090 / CAP-EEx with 100 … 230 Vac power supply
Note
1. Remove the cover of the electronics compartment
2. Unscrew the two screws A of the display unit and turn the display unit carefully aside.
3. The fuse-holder, in which the power fuse in accordance with IEC 127-2 size Ø5 x 20 mm is
Note
4. Reassemble the unit in reverse order (points 2 and 1).
Note
Before commencing work, read the instructions in Sect. 5.1 ("Before opening").
Then continue as follows:
mounted, is now accessible to replace the defect power fuse F1 by a new fuse with the same
rating. The rating depends on the voltage setting of the power supply unit. The power supply of
100/115 Vac requires a fuse of T200mA (part No. 5.05678.00.00) and the 200/230 Vac requires a
fuse of T125 mA (part No. 5.06627.00.00).
The fuse rating is also shown by the yellow sticker that is glued on the mains transformer, which
can only be seen after the regular IFC 090 / CAP-EEx electronics unit is completely removed from
the flameproof signal converter housing. See the next figure.
In case of any doubt about the fuse rating or the voltage setting of the unit, remove the
complete unit from the housing as described in Sect. 5.2 and check in the following figure
depicted items. Change when needed !
Read the instructions of Sect. 5.1 ("After opening") during reassembling.
Before commencing work, read the instructions in Sect. 5.1 ("Before opening").
Then continue as follows:
1. Remove the cover of the electronics compartment
2. Unscrew the two screws A of the display unit and turn it carefully aside.
3. Disconnect the
2-pole
field circuit connector (item B) and the
10-pole
electrode circuit connector
(item C). See figures in Sect. 5.1 and 5.2 for details.
4. Unscrew the two screws D and screw SE by a screwdriver with a long shaft (200 mm). Take out the
electronics unit, but do not damage the connecting cables. See the note IMPORTANT.
5. The defective power fuse (see following figure) can be replaced now. Use a fuse rated at
T1.25H250V (part No. 5.06232.00.00) for the 24 Vac/dc power supply and a fuse rated at
T1.6H250V (Part No. 5.07823.00.00) for the 100…230 Vac power supply. Note that the locations are
slightly different (the 24 Vac/dc supply version is shown).
6. Reassemble in reverse order (points 4 through 1).
Note
Read the instructions of Sect. 5.1 ("After opening") during reassembling
.
Important!
Carefully keep the connecting cables of the field coil and electrode circuits to the side
of the housing, while removing or inserting the electronics unit into the signal converter
housing. This is to prevent damaging of the connecting cables!
IFC 090 / CAP i-EEx electronics unit (24 Vac/dc version is shown)
NOTE:
The power fuse on the 100…230 Vac version is located on a slightly different
position than the fuse of the 24 Vac/dc version ! See location "
5.4 Changing power supply voltage
This only applies to the regular IFC 090 / CAP-EEx electronics unit with 100-230 Vac power supply.
Note
1. Remove the cover of the electronics compartment.
2. Unscrew the two screws A of the display unit and turn the display unit carefully aside.
3. Unscrew the two mounting screws D of the electronics unit and screw SE, which fixes the copper
ground strip at the back of the housing. A screwdriver with a long shaft (200 mm) can best be used to
unscrew SE (e.g. screwdriver type Philips No. 2).
4. Disconnect the
5. The voltage setting of the power supply can be changed by turning the dummy dual-in-line block (i.e.
voltage selector, see last figure in Sect. 5.3) over 180° in its socket. The position of the notch on the
dummy dual-in-line block indicates the voltage setting. Also see the sticker that is glued on the mains
transformer.
6. Reassemble in reverse order (points 4 through 1).
7. Screw the cover of the electronics compartment back into the housing.
Note
IMPORTANT!
Before commencing work, read the instructions in Sect. 5.1 ("Before opening").
Then continue as follows:
2-pole
Note the instructions of Sect. 5.1 ("After opening") during reassembling.
Carefully keep the connecting cables of the field coil and electrode circuits to the
side of the housing, while inserting the electronics unit into respectively removing it
from the signal converter housing. This is to prevent damaging of the connecting
cables!
and
10-pole
connectors and carefully remove the electronics unit.
Algeria
Argentina
Bulgaria
Camaroon
Canada
Chile
Columbia
Croatia
Denmark
Ecuador
Egypt
Finland
French Antilles
Greece
Guinea
Hong Kong
Hungary
Indonesia
Ivory Coast
Iran
Ireland
Israel
Japan
Jordan
Kuwait
Marocco
Mauritius
Mexico
New Zealand
Pakistan
Poland
Portugal
Saudi Arabia
Senegal
Singapore
Slovakia
Slovenia
Sweden
Tai wan
Thailand
Turkey
Tunesia
Venezuela
Yugoslavia