KEYENCE FS-V34CP User Manual

Warning
* FS-V33 (P)/34(P) is a cable, and FS-V33C(P)/34C(P) is a M8 connector.
(1) 12-24 VDC
(FS-V33C/V33CP only)
(2) Control output 2
(3) 0 V (FS-V33C/V33CP only)
(4) Control output 1
Pin assignment of the
connector type
Black: control output 1 White: control output 2
0 V
12 to 24 VDC
Brown
*
Black/white
Sensor main circuit
Overcurrent protection circuit
Load
Blue
*FS-V33 only
Black: control output 1 White: control output 2
Brown
Blue
*
Black/white
0 V
12 to 24 VDC
Sensor main circuit
Overcurrent protection circuit
Load
*FS-V33P only
* FS-V33 only
* FS-V33P only
Pin and wire color table
Connected pin
No.
Core wi re
cover color
(1) Brown
(2) White
(3) Blue
(4) Black
OP-73880
OP-26751 (a set of two)
96M11292
DIGITAL FIBER SENSOR 2-OUTPUT TYPE
FS-V33(P)/V34(P)/V33C(P)/V34C(P)

Input Circuit Diagram

FS-V33/34
3.3 VDC
Pink (input)
(Short-circuit current 1 mA or less)
Sensor main circuit
Blue*
PLC, etc.
0 V
Instruction Manual
Read this manual before using the product in order to achieve maximum performance. Keep this manual in a safe place after reading it so that it can be used at any time.
• This product is just intended to detect the object(s). Do not use this product for the purpose to protect a human body or a part of human body.
• This product is not intended for use as explosion-proof product. Do not use this product in a hazardous location and/or potentially explosive atmosphere.
• This product is a sensor of DC power supply type. Do not apply AC power. The product may explode or burn if an AC voltage is applied.

Precautions on Regulations and Standards

UL Certificate
UL File No. E301717
Category NRKH,NRKH7
Enclosure Type 1 (Based on UL50)
Be sure to consider the following specifications when using this product as an UL/ C-UL Listed Product.
Use the power supply with Class 2 output defined in NFPA70 (NEC: National Electrical Code).
Power supply/ Control input/ Control output circuits shall be connected to a sin­gle Class 2 source only.
Use with the over current protection device which is rated 24V or more and not more than 2A.

Option (Sold Separately)

Mounting bracket End unit Socket cable (main unit)
OP-73880 OP-26751
(a set of two)

Part Names

1
2
DSC
12
Fiber lock lever
Operation status indicators (output 1) Operation status indicators (output 2) SET button (SET)
DSC indicator Digital monitor
Manual button
( )
Expansion protective cover
Expansion connector
Channel selection MODE button (MODE) Output selector (L/D ON)
Dust cover
(Displayed in green)
(Displayed in red)
*
Dedicated for FS-V33C(P)/34C(P)
OP-73864 (cable length: 2 m) OP-73865 (cable length: 10 m)
Setting value
Current value
2
1
DSC
1
2
FS-V33P/34P
12 to 24 VDC
Brown*
PLC, etc.
Pink (input)
Sensor main circuit
(Short-circuit current 2 mA or less)

Socket Cable (Sold Separately for FS-V33C (P)/V34C (P))

Connecting the Socket Cable
1 Connect the socket to the pin on the
amplifier.
412
3
2 Turn the fixing ring on the socket clockwise to fix the socket.

Mounting Unit

Mounting on a DIN Rail
1
Align the claw at the bottom of the main body with the DIN rail. While pushing the main body in the direction of the arrow 1, slant it in the direction of the arrow 2.
2
To dismount the sensor, raise the main body in the direction of the arrow 3 while pushing the main body in the direction of the arrow 1.
Installation on a Wall (Main Unit Only)
Attach the unit to the optional mounting bracket (OP-73880), mount them together, and secure them with two M3 screws as shown in the illus­tration.

Connecting Multiple Amplifiers

Up to 16 sub units can be connected to one main unit.
1 Remove the protection cover on the side of
the main unit.

Output Circuit Diagram

FS-V33(C)/34(C)
FS-V33 (C)P/V34(C)P
123
2 Install the amplifier one by one on the DIN rail.
4
3 Engage the two claws of the child unit with the
recesses on the main unit side until you hear a click sound.
4 Attach the end units (option: OP-26751) to the
both ends of the connected amplifiers in the same way as in step (2).
5
Sandwich the amplifiers between the end units. Tighten the screws at the top (two screws x two units) with a Phillips screwdriver to fix the end units.
1

Connecting Fiber Unit

Note
Transmitter
Receiver
Single-core fiber
Multi-core fiber
Brown *
Blue *
Pink
+V
0V
FS-V33/V34 FS-V33P/V34P
Input OFF
Input ON
% calibration Display scaling
3 seconds
or less
Input OFF
Input ON
% calibration% calibration
3 seconds or more
DSC
2
1
Workpiece
DSC
When the setting is completed, the setting value is displayed.
2
1
DSC
2
1
3 sec or longer
Reflective
Thrubeam
DSC
2
1
Workpiece
When the setting is completed, the setting value is displayed.
DSC
2
1
Workpiece
DSC
2
1
When the setting is completed, the setting value is displayed.
Edge
Workpiece
1 Open the dust cover in the
direction shown by arrow 1.
2
Move down the fiber lock lever in the direction shown by arrow 2.
3
Insert a fiber unit into the fiber insertion holes to a length of the fiber insertion sign (i.e., approximately 14 mm).
4
Move down the fiber lock lever in the direction shown by arrow 4.
If a thin fiber unit is used, an adapter provided with the thin fiber unit will be required. Unless the right adapter is connected, the thin fiber unit will not detect targets correctly. (The adapter is supplied with the fiber unit.)
Cable outer dia. Adapter Appearance
φ1.3
φ1.0
Adapter A
(OP-26500)
Adapter B
(OP-26501)
• To connect the coaxial reflective type fiber unit to the amplifier, connect the sin­gle-core fiber to the transmitter side, and connect the multiple-core fiber to the receiver side.

External Input

1
Signals can be input externally by selecting an external input function (page 5, No. 5).
2
The signal can be accepted by short-circuiting the pink wire for 2 ms or more as shown below for each model (20 ms for OFF).
Fiber insertion sign

Making Sensitivity Settings

Two-point Calibration
In this mode, the setting value used will be the mean value of two sensing values obtained with and without a workpiece.
1
Press the SET button without any workpiece placed in front of the fiber unit.
2
Place a workpiece placed in front of the fiber unit, and press the SET button.
If the sensitivity difference does not have enough room, “

” flashes for about two seconds
after the calibration is complete. The set value is stored in memory even in that case.
Maximum Sensitivity Setting
Set the sensitivity without a workpiece in the case of the reflective model, and with a workpiece in the case of the through-beam or retro-reflective model.
Press the SET button for three seconds in the state as shown in the above figure. (Release the button when SET flashes.) The setting value is set slightly higher than the received light intensity at the time of setting the sensitivity.
Full Auto Calibration
In this mode, the setting value will be set to the mean value of the maximum and minimum incident values obtained within a certain period. Use this mode to detect moving workpieces.
1 Press the set button for a minimum of three seconds while the target
workpiece is passing the sensing area of the fiber unit.
• While the set button is pressed, the sensitivity of the sensor will be set according to the incident values.
* FS-V33/V33P only. * Setting using an external input is up to 1 million times. * No inputs are accepted while setting each mode.
Brown *
Pink
Blue *
+V
0V
When external calibration is selected, the operation is the same as with the SET button.
Special Function
By performing the following operation, both sensitivity setting and scaling can be per­formed using external input.Select external calibration (page 5, No. 5) and display scaling (page 6, No. 7).The following is the example when using the % calibration.
• After the setting is completed, the setting value is displayed on the digital monitor.
Positioning Calibration
1
Press the SET button without any workpiece placed in front of the fiber unit.
2 Place a workpiece on the position where you want to perform positioning.
Press the SET button for 3 seconds or longer until the display flashes.

Fine-adjusting Sensitivity

The setting value can be directly changed by pressing the manual button.
DSC
1
122
When extended display (page 6, No. 9) is set for the number of digits to be displayed for the received light intensity
1
Press the manual button quickly once, and check that the setting value flashes.
2
While the setting value is flashing, change the setting value with the Manual button.
2

Percentage Calibration

DSC
122
1
Press
Press (2) within 5 seconds after pressing (1).
(1)
(2)
122
When Area, Limit setting, Counter, or Alarm is selected, the selection options are NO and NC.
DSC
1
DSC
122
1
This is a calibration method that can set the setting value by percentage with ref­erence to the received light intensity at the time of sensitivity setting. For example, if the target value is set to -10P, the setting value is determined 10% lower than the received light intensity when the SET button is pressed.
1 When selecting the sensitivity setting method (page 5, No. 2), select the %
calibration, and set the target value of calibration.
2 Taking the desired light intensity as a reference (normally without a
workpiece), press the SET button.
While the % calibration is in use, other calibrations (sensitivity setting) cannot be used.
*

Output Selection

Either light-ON mode or dark-ON mode is selectable.

Dynamic Sensitivity Correction (DSC) Function

DSC automatically corrects the setting value according to the changes in the received light intensity when there is no workpiece (output OFF). This function is effective when the light intensity difference is small when judging whether or not there is a workpiece. At Detection mode selection (page 5, No.4), select “Dynamic sensitivity correction mode” beforehand.* How to set the sensitivity is the same as in the normal mode.
The DSC indicator illuminates when the DSC function is set.
DSC indicator
DSC
1
* When Light ON is selected, the upper limit of the correctable range is twice as
much as the initial setting value. * The value is stored in memory even after the power is turned off. * The DSC indicator flashes when the light intensity during output OFF greatly
fluctuates or the L/D ON selection is inappropriate. In such a case, check the
setting again.
122

Area Detection Mode

This mode is suited to detecting the received light intensity only of a certain range. To set this mode, select the area detection mode at Detection mode selection (page 5, No.4).
OFF
ON
OFF
HI: Upper limit setting value
LO: Lower limit setting value
Received light
intensity
Set the value so that the upper limit setting value is larger than the lower limit set­ting value. The unit does not respond when the upper limit setting value is less than or equal to the lower limit setting value.
Even when the above condition is satisfied, the unit may not respond when the HI and LO values are close to each other because of hysteresis. Be sure to operate the unit to check whether the values are valid.
How to Switch the Upper Limit Setting Value (HI) and the Lower
Limit Setting Value (LO)
When the button is pressed, HI or LO and the setting value alternately flash. When the MODE button is pressed while the display alternately flashes, the HI or LO display changes. How to configure the sensitivity setting is the same as when in the normal detection mode.

Setting the Display Scaling

This is the function to adjust the current received light intensity to the ìscaling target value.
1 When selecting a display value correction function (page 6, No. 7), select the
display scaling function, and set the target value. (The explanation here deals with the case where the target value is set to 2000.)
2
During the normal display, press the SET button while pressing the MODE button.
(Scaling is performed for the current light intensity at this time.)
DSC
1
The display changes as follows, and the target value (which is 2000) to be set as a scale is displayed.
DSC
1
Ø
The scaled value is displayed.
122
122

Edge Detection Mode

This mode detects the change in the received light intensity during a given period of time. (Set at page 5, No. 4)
Rising edge detection Detects the increase (rising edge) of the
Falling edge detection Detects the decrease (falling edge) of the
Filter Setting
Basically, leave this setting as its initial value. If the passage interval of workpieces is too short for the unit to respond, strengthen the level and try again. The selectable filter level differs depending on the power modes.
Filter level HSP* FINE
Default state589999
Setting range 1 to 5 4 to 8 5 to 9 6 to 9 8 to 9 9 only
*HSP: HIGH SPEED As the number becomes smaller, the filter becomes stronger, which makes the unit difficult to respond to gradual changes in light intensity.
Making Sensitivity Settings
The sensitivity is set to maximum when the SET button is pressed quickly once. When the setting value is too low and the unit detects objects other than the work­piece, fine-adjust the setting value to a higher number.
Operation When Switching Outputs
Setting Operation
L-ON Normally OFF. Turns ON only when the light intensity changes.
D-ON Normally ON. Turns OFF only when the light intensity changes.
received light intensity
received light intensity
TURBO
SUPER ULTRA MEGA
The reference light intensity can be set in the following range in reference with the currently received light intensity:
Power mode Minimum value Maximum value
HIGH SPEED Approx. 1/20 times Approx. 16 times
FINE Approx. 1/20 times Approx. 16 times
TURBO Approx. 1/20 times Approx. 16 times
SUPER Approx. 1/40 times Approx. 8 times
ULTRA Approx. 1/160 times Approx. 2 times
MEGA Approx. 1/320 times Approx. 1 time
If the value exceeds the range,
'TT
is displayed
and scaling is performed up to the possible range.
• No value can be set when the Edge detection mode is selected.
• The value is stored in memory even after the power is turned off.
• External input can be used when using FS-V33(P)/34(P) (page 5, No.5).

Zero-shift Function

The Zero-shift function is used to forcibly set the current light intensity to zero.
1
At Display value correction function selection (page 6, No.7), select “Zero-shift function”.
2 When the SET button is pressed while the MODE button is pressed, the current
light intensity is forcibly set to zero.
DSC
1
• This function cannot be used when the Dynamic sensitivity correction (DSC) or Edge detection mode is selected.
• The value is stored in memory even after the power is turned off.
• External input can be used when using FS-V33(P)/34(P) (page 5, No.5).
3
122
Loading...
+ 5 hidden pages