ICP H9MPT100J16C1, H9MVX080J20A1, H9MVX100L20A1, T9MVX060F12A1 Installation Guide

4 (1)
90+ GAS FURNACE DIRECT OR NON-DIRECT VENT
Category IV Furnace
*9aPT Two-Stage Heating & Supports *9MPV 92% Variable Speed, Two-Stage Heating & Supports
Two-Stage Cooling Units
*9MVX 95% Variable Speed, Two-Stage Heating & Supports
Two-Stage Cooling Units
* Denotes Brands (C, H, T)
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol z_. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
INSTALLER: Affix these instructions
on or adjacent to the furnace.
Before puchasiag this appl{ance, read important energy cost end
efficiency information available from your retaJle£
International Comfort Products, LLC
Lewisburg, TN 37091 USA
1. Safe Installation Requirements .................. 5
2. Installation ................................. 6
3. Combustion &Ventilation Air ................... 10
4.Vent & Combustion Air Piping ................... 14
5. Concentric Vent Termination .................... 31
6. Gas Supply and Piping ........................ 34
7. Electrical Wiring ............................. 39
Table of Contents
8. DuctworkandFilter ......................... 41
9. ChecksandAdjustments ..................... 44
10. FurnaceMaintenance........................ 48
11. SequenceofOperation&Diagnostics*9MPT...... 49
12. WiringDiagram*9MPT ....................... 51
13. SequenceofOperation& Diagnostics*9MPV,*9MVX 52
14. WiringDiagram*9MPV,*9MVX ................. 54
CONSUMER: Retain these instructions for future reference.
15. ThermostatWiringGuide ..................... 55
ELECTRIC SHOCK HAZARD Failure to follow this warning
could result in personal injury and/or death.
Turn Off All Power Before Servicing.
CARBON MONOXIDE POISONING AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property dam-
age. This furnace is not designed for use in mobile
homes, trailers or recreational vehicles.
Portions of the text and tables are reprinted from NFPA 54 / ANSi Z223,1-2006(c_, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association,
Washington, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Specifications aresubject to change without notice. 44001 202401 Feb 2009
Required Notice for Massachusetts Installations
Important
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA-54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
(a)
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1,
INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment,
the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed, in addition, the installing plumber or gasfitter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified license
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period
of thirty (30) days to comply with the above requirement; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by
the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the
following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e)
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas
Fitters, 239 Causeway Street, Boston, MA 02114. 617-727-9952
44001 202401 Specificationsare subject to changewithoutnotice. 2
START-UP CHECK SHEET
For PSC Models *9MPT
(This sheet is optional. Keep for future reference.)
Date of Start-Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone: Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number: Serial Number:
Setup Checks Check the box when task is complete.
All Electrical Connections Tight? [U
Have hoses been relocated for furnace U/D/H application? [U
Condensate Drain Connected? [U
Condensate Drain Trapped? [U
Calculated Input (BTU) Rate: (See Checks
Adjustments Section).
Heating Check Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air: High Heat
Low Heat
Temperature of Return Air: Temperature Rise (Supply - Return)' High Heat __
Low Heat
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat:
The Blower Speed Tap used for:
Optional Check:
Cooling Check
Temperature of Supply Air: Temperature of Return Air:
Temperature Difference:
Supply Return
High Heat Low Heat
CO? CO2?
and
Manual Gas Shut-off Upstream of Furnace/Drip Leg [U
Gas Valve turned ON?
Type of Gas: Natural: [U
Filter Type and Size: Shade in Heating Fan "Time OFF" Setting and Thermostat
Type setting:
3 Specifications are subject to change without notice, 44001 202401
Propane: [U
Static Pressure (Ducts) Cooling:
The Blower Speed Tap used for:
Dealer Comments:
Supply Return
Cooling
START-UP CHECK SHEET
For Variable Speed Models *9MPV, *9MVX
(This sheet is optional. Keep for future reference.)
Date of Start-Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number: Serial Number:
Setup Checks Check the box when task is complete.
Calculated Input (BTU) Rate: (See Checks and
Adjustments Section).
Heating Check Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air:
Temperature of Return Air: Temperature Rise (Supply - Return)' High Heat __
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat: Supply
High Heat Low Heat
Low Heat
Return
All Electrical Connections Tight? Lj
Have hoses been relocated for furnace U/D/H application? Lj
Condensate Drain Connected? Lj
Condensate Drain Trapped? Lj
Manual Gas Shut-off Upstream of Furnace/Drip Leg Lj
Gas Valve turned ON?
Type of Gas: Natural: Lj Propane: Lj
Filter Type and Size: Shade in Final Furnace Settings Below:
123 ] 2345 678
J2
Optional Check:
Cooling Check
Temperature of Supply Air: Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) Cooling:
Dealer Comments:
CO? CO2?
Supply Return
lu o o nI ,11 I-_ AC/HPEfficiencySLOWER ADJUST HP Comfort
HP mode
select
44001 202401 Specificationsare subject to changewithoutnotice. 4
1. Safe Installation Requirements
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Improper adjustment, alteration, service, maintenance or installation could cause personal
injury, death and/or property damage. Installation or repairs made by unqualified persons
could result in hazards to you and others. Installation MUST conform with local codes or, in
the absence of local codes, with codes of all
governmental authorities having jurisdiction.
The information contained in this manual is
intended for use by a qualified service agency that is experienced in such work, is familiar with all
precautions and safety procedures required in such work, and is equipped with the proper tools
and test instruments.
NOTE: This furnace is design-certified by the CSA International
(formerly AGA and CGA) for installation inthe United States and Canada. Refer to the appropriate codes, along with this manual, for proper installation.
Use only the Type of gas approved for this furnace (see Rating Plate on unit). Overfiring will result infailure of heat
exchanger and cause dangerous operation. (Furnaces can be converted to Propane gas with approved kit.)
Install this furnace only in a location and position as
specified in "Installation" of these instructions.
Provide adequate combustion and ventilation air to the
furnace as specified in "Combustion and Ventilation Air" of these instructions.
Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as
specified in "Combustion and Ventilation Air, Horizontal
Venting and Masonry Chimney Venting" of these instructions.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for
the detection of leaks to check all connections, as specified in "Gas Supply and Piping, Final Gas Piping
Check" of these instructions.
Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range,
as specified in "Technical Support Manual" of these
instructions. See furnace rating plate.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in "Installation
Requirements" of these instructions.
This furnace is not to be used for temporary heating of buildings or structures under construction.
This furnace is NOT approved for installation in mobile homes, trailers or recreation vehicles,
Seal around supply and return air ducts.
Install correct filter type and size.
Unit MUST be installed so electrical components are protected from direct contact with water.
Safety Rules
Your unit is built to provide many years of safe and dependable
service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and
create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission encourages
installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The
sources could be gas-fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas-fired fireplaces, wood fireplaces.
Carbon monoxide can cause serious bodily injury and/or death. Carbon monoxide or "CO" is a colorless and odorless
gas produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
Therefore, to help alert people of potentially dangerous carbon monoxide levels, you should have a commercially available
carbon monoxide alarm that is listed by a nationally recognized testing agency in accordance with Underwriters Laboratories Inc. Standard for Single and Multiple Station
Carbon Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19-01 Residential Carbon Alarming Devices installed and maintained in the building or dwelling concurrently with the gas-fired furnace installation (see Note below). The alarm should be installed as recommended by the alarm
manufacturer's installation instructions.
B.
There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause serious bodily injury, death, and/or property damage. Therefore, in order to alert
people of potentially dangerous fire or smoke, you should have fire extinguisher and smoke alarms listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type of alarms.
C.
To ensure safe and efficient operation of your unit, you should
do the following:
1.
Thoroughly read this manual and labels on the unit. This
will help you understand how your unit operates and the hazards involved with gas and electricity.
2.
Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas
control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases.
44001 202401 Specificationsare subject to changewithoutnotice. 5
FrozenWaterPipeHazard
WATER DAMAGE TO PROPERTY HAZARD
Failure to protect against the risk of freezing may result in property damage,
Do not leave your home unattended for long periods during freezing weather without turning off water
supply and draining water pipes or otherwise
protecting against the risk of frozen pipes and resultant damage.
Your furnace is designed solely to provide a safe and comfortable
living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety devices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
If your furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in serious water damage.
Ifthe structure will be unattended during cold weather you should
take these precautions.
1. Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate
areas.
-or-
2.
Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.
-or-
3.
Install a reliable remote sensing device that wilt notify somebody of freezing conditions within the home.
WinterShutdown
If you go away during the winter months and do not leave the heat on in your home, the plastic transition box and the condensate trap on the furnace must be protected from freeze damage.(See Figure 11 trough Figure 20)
1. Disconnect the 5/8" (15.9mm) OD rubber hose from the vent drain fitting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sanitary type (RV) antifreeze into the condensate trap. Reconnect the 5/8" (15.9mm) OD rubber hose to the stub on the vent drain fitting. Secure with the hose clamp.
2. Disconnect the 3/4" (19.1mm) OD rubber hose from the condensate trap. Insert a funnel into the hose and and pour
four(4) ounces of sanitary type (RV) antifreeze into the plastic Transition box. Squeeze the hose together near the
end and quickly reconnect the 3/4" (19.1mm) OD rubber hose to the stub on the condensate trap. Secure with the
hose clamp.
When you return home, your furnace will be ready to start, as it is
not necessary to drain the antifreeze from the furnace.
2. Installation
CARBON MONOXIDE POISONING HAZARD Failure to properly vent this furnace or other
appliances could result in personal injury or death. This furnace can NOT be common vented or
connected to any type B, BW or L vent or vent connector, nor to any portion of a factory-built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney
to prevent oversizing problems for the other
remaining appliance(s). See Venting and
Combustion Air Check in the Combustion &
Ventilation Air section. This furnace MUST be
vented to the outside.
InstallationPositions
This furnace can be installed in an upflow, horizontal (either left or
right) or downflow airflow position. DO NOT install this furnace on its back. For the upflow position, the return air ductwork can be
attached to either the left or right side panel and/or the bottom. For horizontal and downflow positions, the return air ductwork must be
attached to the bottom. The return air ductwork must never be attached to the back of the furnace.
Location and Clearances
Refer to Figure 1 or Figure 2 for typical installation and basic connecting parts required. Refer to Figure 3 for
typical horizontal direct vent installation and basic
connecting parts required. Supply and return air plenums and duct are also required.
2.
If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or
evaluate the existing location based upon the minimum clearance and furnace dimensions (Figure 4).
CARBON MONOXIDE POISONING HAZARD. Failure to follow this warning could result in
personal injury or death. Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air
evaluation and remedy.
FROZEN AND BURST WATER PIPE HAZARD Failure to protect against the risk of freezing may
result in property damage. Special precautions MUST be made if installing
furnace in an area which may drop below freezing.
This can cause improper operation or damage to
equipment. If furnace environment has the potential of freezing, the drain trap and drainline must be protected. The use of electric heat tape or
RV antifreeze is recommended for these installations. (See "Condensate Trap Freeze
Protection Section")
6 Specifications are subject to changewithout notice. 440012024 01
Typical Upflow Installation
Aluminumornon-rustingshieldrecommended.
*8.......... (SeeVentTerminationShieldingfordimensions)
tzu_ zmm]M n _ '
20' t6imi Max....................................................................................................................................................................;,\ / Couplingonendsof
\ " J " _ i,_ / _' exhaustppe Tota
in same ,, atmospheric ...._ (not usedon
zone I_i. . . / side structure = 8"
VentPipesMUSTbe supported
Horizontallyand
Vertically
J._ InletPipe pipe&couplingout-
SinglePipe (203.2mm)
%
_" model) /
"8" i203.2mm)Min. 20' (6.1m)Max.
insameatmosphericzone
* Increaseminimumfrom8"(203.2mm)to18"(203.2mm)forcoldclimates(sus- tainedtemperatures0°F(-17° C)andbelowfor24ormoreconsecutivehours).
25-23-33
Typical Downflow Installation
SeeVentTermination ShieldinginVentSection.
\
\ .restrainvent
InletPipe ,Y?]_ ] "8"(20&2mm)Min. \, xx
(not usedon_ i 20' (6.1m) Max. in \, // Single Pipe i_i>_,!_ same atmosphericzone / '
model)
ii"
VentPipesMUST i _ ;i besupportedHorizon-i
tally and Vertically i i_ i i
z_i
Coupling on inside andoutsideofwallto
pipe
8" Min.
"8" (203.2mm)Min 20';:(6.1m)Max.
in same
/?ospheric zone
6. Use a raised base for upflow furnace if the floor is damp or
wet at times.
7. For downflow installations, non combustible subbase must
be used under the furnace unless installation is on a non combustible floor surface. This requirement applies even
when a coil box or cabinet is used.
8. For horizontal installations, line contact is permissible only
between lines formed by intersection of back and two sides of furnace jacket, and building joists, studs or framing.
9. Residential garage installations require:
Burners and ignition sources installed at least 18" (457.2mm) above the floor.
Located or physically protected from possible damage by a vehicle.
10. Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in
attic application.
This furnace may be used for construction heat provided that all the following conditions are met:
The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products
into the structure.
The furnace iscontrolled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the
entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is
maintained between 55° F (13 ° C) and 80 ° F (27 ° C), with no evening setback or shutdown. The use of the furnace while
the structure is under construction is deemed to be
intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the
rating plate value.
The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting according to these instructions.
:;Discharge i
_r y
* Increaseminimumfrom8"(203.2mm)to18"(203.2mm)forcoldclimates(sus- tainedtemperatures0°F(-17°C)andbelowfor24ormoreconsecutivehours).
25-23-33a
InstallationRequirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of buildings or structures under construction.
3. Install furnace as centralized as practical with respect to the heat distribution system.
4. Install the vent pipes as short as practical, and in accordance to these instructions. (See Vent and Combustion Air Piping section).
5. Maintain clearance for fire safety and servicing. A front clearance of 24" (609.6mm) required and 30" (762mm) recommended for access to the burner, controls and filter. See clearance requirements in Figure 4.
44001 202401 Specificationsare subject to changewithoutnotice. 7
CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in
personal injury or death. Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air
evaluation and remedy.
FurnaceInstallationConsiderations
The installation ofthe furnace for agiven application will dictate the
position ofthe furnace, the airflow, ductwork connections, vent and combustion air piping. Consideration must be given to the
following:
CondensateTrap and Drain Lines
The supplied condensate trap must be attached to the furnace side
panel on either the left or right side. For horizontal installations, the drain trap is vertically attached to the side panel below the furnace.
A minimum clearance of 6" (152.4mm) below the furnace is
required for the condensate trap. Downward slope of the condensate drain line from the condensate trap to the drain location must be provided. Adequate freeze protection of the drain
trap and the drain line must be provided. See "Condensate Drain
Trap" section for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper drainage of the condensate from the furnace. The furnace must be level to within 1/4" (6.4mm) from front to back and from side to side
for upflow and downflow installations or top to bottom for horizontal
installations.
Vent and CombustionAir Connections
For venting information literature, call 931.270.4100 with the complete model and serial number of the furnace.
Special Venting Requirements for Installations in Canada Installation in Canada must conform to the requirements of CSA B149 code. Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC $636. The special vent
fittings and accessory concentric vent termination kits and
accessory external drain trap have been certified to ULC $636
for use with those IPEX PVC vent components which have
been certified to this standard. In Canada, the primer and cement must be of the same manufacturer as the vent system -
IPEX System 636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and IPEX System 636(1)TM,PVC Cement for Flue
Gas Venting, rated Class IIA, 65 deg C. must be used with this
venting system - do not mix primers and cements from one
manufacturer with a vent system from a different manufacturer. Follow the manufacturer's instructions in the use of primer and
cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC $636, of the vent
system is based on following these installation instructions, the
vent system manufacturer's installation instructions, and proper
use of primer and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be consulted before installation to determine the need to obtain a
permit.
Consignes sp6ciales pour rinstallation de ventillation au Canada
L'installation faite au Canada dolt se conformer aux exigences du code CSA B149. Ce syst_me de ventillation dolt se
composer de tuyaux, raccords, ciments et appr_ts conformes au ULC $636. La tuyauterie de ventillation des gaz, ses accessoires, le terminal concentrique mural ainsi que
I'ensemble du drain de condensat exterieur ont et6 certifies ULCS 636 pour I'application des composantes IPEX PVC qui
sont certifiees & ce standard. Au Canada I'appr_t et le ciment
doivent _tre du m_me manufacturier que le syst_me de ventillation - IPEX Systeme 636, Appr_t PVC/CPVC. Mauve Violette pour conduit en evacuation des gaz et IPEX Systeme
636(1)TM,ciment pour PVC pour conduit en evacuation des gaz,
6val'u_ CLASSE IIA, 65 deg. C. doit _tre utilise avec ce
systeeme d'evacuation - ne pas melanger I'appr_t et le ciment
d'un manufacturier avec le syst_me de ventillation d'un autre
manufacturier. Bien suivre les indications du manufacturier Iors
de I'utilisation de I'appr_t et du ciment et ne pas utiliser ceux-ci
si la date d'expiration est atteinte.
L'operation securitaire, tel que definit par ULC $636, du
systeme de ventilation est base sur les instructions d'installation
suivantes, ainsi que I'usage approprie de I'appr_t et ciment. Tout arret feu et solin de toit utilises avec ce systeme doivent
_tre des materiaux listes UL. L'acceptation du standard
Canadien CSA B419 est directement relie & I'installation
conforme aux instructions ci- haut mentionnees. Le standard
Canadien recommande I' inspection par un personel qualifie et
ce, une fois par annee.
Les autoritees ayant juridiction (inspecteurs de gas, inspecteurs en b&timents, departement des incendies, etc) devraient _tre consultees avant I'instatlation afin de determiner si un permis est requis.
(1) System 636 is a trademark of IPEX Inc.
On the Dual Certified furnace, the vent and combustion air pipes attach to the furnace through the top panel for the upflow and
horizontal installations. For the downflow installation, the vent and combustion air pipes attach to the furnace through the alternate locations on the furnace side panels.
Note: On the Direct Vent furnace, the vent pipe attaches to the furnace through the side panels. The combustion air pipe attaches to the top panel or to the alternate location on the side panel.
On the Single Pipe furnace, the vent pipe attaches to the furnace through the furnace side panels.
Note: Repositioning of the combustion blower is required for the vent pipe connection to the furnace through the "right side" panel.
See "Vent and Combustion Air Piping" section for further details.
HorizontalFurnaceInstallation
Typical Horizontal Installation
This furnace can be installed horizontally in an attic, basement,
crawl space, alcove, or suspended from a ceiling ina basement or
utility room (See Figure 3). Do not install furnace on itsback or in the reverse airflow positions as safety control operation will be
adversely affected.
If the furnace is to be suspended from the floor joists in a crawl
space or the rafters in an attic, it is necessary to use steel pipe
straps or an angle ironframe to rigidly attach the furnace to prevent
movement. These straps should be attached to the furnace bottom
side with sheet metal screws and to the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the
rafters or joists.
Ifthe furnace is to be installedin a crawl space, consult local codes. A suitable concrete pad or blocks are recommended for crawl
space installation on the ground.
NOTE: 6" (152.4mm) bottom clearance required for condensate trap.
24" (609.6mm) inches between the front of the furnace and
adjacent construction or other appliances MUST be maintained for
service clearance. [30" (762mm) inches is required to remove furnace].
Keep all insulating materials clear from Iouvered door. Insulating
materials may be combustible. The horizontal furnaces may be installed directly on combustible
wood flooring or supports as long as all required furnace
clearances are met. See Figure 3. This furnace MUST NOT be installeddirectly on carpeting or tile or
other combustible material other than wood flooring or supports.
For horizontal installation over a finished living space. A field fabricated auxiliary drain pan with drain pipe is required to prevent
damage by overflow due to blocked condensate drain.
8 Specifications are subject to changewithout notice. 440012024 01
Dimensions and Clearances
.........F i.........
.................................................................................i i i .......A,R,NT KE
TOP ...................................I
a
LEFTSIDE +8611116,i ELECTRICAL
TRAP(COU.TE+LO ...............................
A R NTAKE(KO) S _ .................i..............................i / (347'7) (ALTERNATE) .... 4Y£i16 _J! i . i i +,;_ 11/1L
TRAP(KO) (122.2) ' +; b _ !3::P) i '%_
UPFLOW/HORIZONTAL.... _+ +" +' t'_!8 + t_297 '
...... THERMOSTAT f" i ..........7 .......i 28314 i
21/_ _ 177,8 i (730.3) :
i J 611.2)
13114 i i (439 7) i (603.2)
(336.6) ; i 111/1 i
+; .................+++ ++ _ i+ :
, , 21618 ++ 47/8., +
t7/8 | (849,3)24 (12331i
(47,6) (609,6)
D _i
Capacity
*RMPT050F12
*RMPT075F14
*9MPT100J16
*RMPT125L20
*9MPV050F12
*9MPV075F12
*RMPVl00J20
*RMPV125L20
*9MVX040F12
*9MVX060F12
*RMVX080J20
*RMVX100L20
* Denotes Brand
j (KO) 42,9 t
Unit
A B c D
19t/8 175/8 2t/8 143/4
(485.8} (477.7) (54) (374,7)
191/8 17518 21/8 143/4
(485.8) (477.7) (54) (374,7)
223/4 21114 115/16 18314
(577.9) (539.8) (49.2) (476,3)
241/2 23 7/16 23
(522.3) (584.2) (11.1) (584,2)
191/8 17518 21/8 14314
(485.8) (447.7) (54) (374,7)
191/8 17518 21/8 143/4
(485.8) (447.7) (54) (374,7)
223/4 21114 115/16 18314
(577.9) (539.8) (49.2) (476,3)
241/2 23 7/16 23
(522.3) (584.2) (11.1) (584,2)
191/8 17518 21/8 14314
(485.8) (447.7) (54) (374,7)
191/8 17518 21/8 143/4
(485.8) (447.7) (54) (374,7)
223/4 21114 115/16 18314
(577.9) (539.8) (49.2) (476,3)
241/2 23 7/16 23
(522.3) (584.2) (11.1) (584,2)
i
[ ii775) i 11
-_L__,_ '_/
GAS ........................i ::
VENT............. \/:' i / 1_11/
+ i i lS
i /!4 Vt6t _ i 17=/6 i 1913116
Drawing is representative, but some models may vary
ALL DIMENSIONS: in (mm)
Cabinet Bottom
E F G H
43/8 4112 21/2 9112
(tt1,1) (tt4.3) (6&5) (241.3)
4318 4112 21/2 9112
(tt1,1) (tt4.3) (6&5) (241.3)
43/8 4t12 25/8 113/8
(tt1,1) (tt4.3) (56,7) (288.9)
43/8 4t/2 21/4 12114
(tt1,1) (tt4.3) (57,2) (311.2)
43/8 4t/2 21/2 9t/2
(tt1,1) (tt4.3) (5&5) (241.3)
43/8 4t/2 21/2 9t/2
(tt1,1) (tt4.3) (5&5) (241.3)
43/8 4t/2 25/8 113/8
(tt1,1) (tt4.3) (56,7) (288.9)
43/8 4t/2 21/4 12114
(tt1,1) (tt4.3) (57,2) (311.2)
43/8 4t/2 21/2 9t/2
(tt1,1) (tt4.3) (5&5) (241.3)
43/8 4t/2 21/2 9t/2
(tt1,1) (tt4.3) (5&5) (241.3)
43/8 4t/2 25/8 113/8
(tt1,1) (tt4.3) (56,7) (288.9)
43/8 4t/2 21/4 12114
(tt1,1) (tt4.3) (57.2) (311.2)
- A +=i
B
FRONT
Top
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS - in (mm)
REAR 0 FRONT (combustion air openings in 3" (76.2)
furnace and in structure)
Required For Service
ALL SIDES Of SUPPLY PLENUM
SIDES VENT TOP OF FURNACE
"24" (609.6) 1" (25.4)
0 0
1" (25.4)
"30" (762mm)clearancerecommendedforfurnaceremoval.
Horizontalposition:Linecontactis permissibleonlybetween linesformedbyintersectionsoftopandtwo sidesoffurnace
jacket,andbuildingjoists,studsorframing.
NOTE: Evaporator "A" coil drain pan dimensions may vary from furnace duct opening size. Always consult
evaporator specifications for duct size requirements. Furnace is designed for bottom return or side return. Return air through back of furnace is NOT allowed.
181/2
(469,9)
/
GAS (KO)\
413116
/ RIGHT SIDE
/
/ TRAP(KO)
//_(COUNTERFLOW)
ELECTRICAL(KO)
AIRINTAKE (KO) (ALTERNATE)
VENT (KO)
TRAP (KO)
UPFLOW/HORIZONTAL
21/41
THERMOSTAT(57.2)........................
13114
(336,6)
(609.6)
17/8 (47.6)
25-23-36b
44001 202401 Specificationsare subject to changewithoutnotice. 9
KnockOuts Hammer and Screwdriver Used
for Knockout
CUT HAZARD Failure to follow this caution may result in
personal injury. Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate clothing, safety glasses and gloves when handling parts and
servicing furnaces.
Use a hammer and screwdriver to strike a sharp blow (see Figure 5) directly to the knockout tie points or use a hammer inthe
upper left corner of the desired knockout. Remove any burrs and sharp edges.
25-40-06
NOTE: If a knockout does not come out after two sharp blows, pull and snip as needed to remove the knockout.
3. Combustion & Ventilation Air
For Single Pipe Installation (Non-Direct Vent)
CARBON MONOXIDE POISONING HAZARD Failure to provide adequate combustion and
ventilation air could result in personal injury or
death. Use methods described here to provide
combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or openings for supplying combustion and ventilation air must comply with National Fuel Gas Code, NFPA54/ANSI Z223.1, 2006 (or current edition) and applicable provisions of local building codes.
Note: The Combustion & Ventilation Air Section inthis document,
uses tables and information from the ANSI Z223.1/NFPA
54. For use in Canada, use CSA B149.1 for this information.
1. Section 9.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, National Fuel Gas Code (NFGC),
ANSI Z223.1-2006/NFPA 54-2006 in the U.S.,
2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1-05 in Canada,
3. Applicable provisions of the local building code.
This furnace can NOT be common vented or connected to any type
B, BW or L vent or vent connector, nor to any portion of a
factory-built or masonry chimney. Multistory venting is NOT
permitted. If this furnace isreplacing a previously common-vented
furnace, it may be necessary to resize the existing vent and
chimney to prevent oversizing problems for the other remaining appliance(s). See "Venting and Combustion Air Check" in this
section. This furnace MUST be vented to the outside.
When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting
And Combustion Air Check in "Gas Vent Installation" Section in this
manual.
OutdoorCombustionAir Method
A space having less than 50 cubic feet per 1,000 BTUH (4.8 cubic
meters per kW) input rating for all gas appliances installed in the space requires outdoor air for combustion and ventilation.
AirOpeningsand Connecting Ducts
1. Total input rating for all non direct vent gas appliances MUST be considered when determining free area of openings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, they MUST be no less than 1/4" (6.4mm) mesh.
4. The minimum dimension of rectangular air ducts MUST NOT be less than 3" (76.2mm).
5. When sizing grille or louver, use the free area of opening. If free area is NOT stamped or marked on grill or louver,
assume a 20% free area for wood and 60% for metal.
Confined SpaceInstallation
NOTE: A confined space is defined as an area with less than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per kW) input rating
for all gas appliances installed inthe area.
Requirements
1. Provide confined space with sufficient air for proper combustion and ventilation of flue gases using horizontal or vertical ducts or openings.
2. Figure6 illustrate how to provide combustion and ventilation air. A minimum of two permanent openings, one inlet and one outlet, are required.
a. One opening MUST commence within 12" (304.8mm) of
the floor and the second opening MUST commence
within 12" (304.8mm) of the ceiling.
b. Size openings and ducts per Table 1. c. Horizontal duct openings require 1 square inch of free
area per 2,000 BTUH (11 cm2/kW) of combined input for all gas appliances in the space (see Table 1).
d. Vertical duct openings or openings directly
communicating with the outdoors require 1 square inch of free area per 4,000 BTUH (5.5 cm2/kW) for combined input of all gas appliances in the space (see Table 1).
10 Specificationsare subject to changewithoutnotice. 440012024 01
Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
ThisinstallationNOTapprovedinCanada
Ga Ven
.__Gable Vent
fVentilated Attic_
/
f
Z
i
Air (1)
AlternateInletAir (1)
3•
One opening MUST be within 12" (304.8mm) of the floor and the second opening within 12" (304.8mm) of the ceiling•
a. 1 sq. in of free area per 3,000 BTUH (7 cm2/kW) for
combined input of all gas appliances in the space (see
Table 1) and
b. not less than the sum of the areas of all vent connectors
in the space.
The opening shall commence within 12" (304.8mm) of the top of the enclosure. Appliances shall have clearances of at least 1"
(25.4mm) from the sides and back and 6" (152.4mm) from the
front. The opening shall directly communicate with the outdoors or
shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the
outdoors.
4. Size openings and ducts per Table 1. a. Indoor openings that comply with the Indoor
Combustion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
_rnacl
OutletAir(1)
GasVent
........
Air
ou:
SoffitVent
MinimumOneInlet and One OutletAirSupply is Required May be in anyCombinationShown
InletAir Opening MustbeWithin12"(304.8mm)of floor
Inlet
OutletAir Opening MustbeWithin12"(304.8mm)of ceiling
Air (2)
(1) 1 SquareInch per4000 BTUH (2) 1 SquareInch per2000 BTUH
c•
Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion
Air Method.
2) Outdoor opening size reduction Factor is 1 minus
the Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method
above multiplied by reduction Factor.
5•
Horizontal duct openings require 1 square inch of free area per 2,000 BTUH of combined input for all gas appliances in area (see Table 1).
6•
Vertical duct openings or openings directly to outside require 1 square inch of free area per 4,000 BTUH (5.5 cm2/kW) for combined input of all gas appliances in area (see Table 1).
Free Area
MinimumFreeAreaRequiredfor EachOpeningorDucttoOutdoors
BTUH(kW) TwoHorizontalDucts SingleOpening TwoVerticalDuctsorOpenings RoundDuct
InputRating BTUH(kW) BTUH(kW) BTUH(kW) BTUH(kW)
40,000(11.72) 20sq.in.(129cm2) 13.34sq.in.(86cm2) 10sq.in.(65cm2) 4" (101.6mm) 50,000(14.65) 25sq.in.(161cm2) 16.7sq.in.(108cm2) 12.5sq.in.(81cm2) 4" (101.6mm)
60,000(17.58) 30sq.in.(194cm2) 20sq.in.(129cm2) 15sq.in.(97cm2) 5" (127mm) 75,000(21.98) 37.5sq.in.(242cm2) 25sq.in.(161cm2) 18.75sq.in.(121cm2) 5" (127mm)
80,000(23.45) 40sq.in.(258cm2) 26.7sq.in.(172cm2) 20sq.in.(129cm2) 5" (127mm)
100,000(29.31) 50sq.in.(322cm2) 33.3sq.in.(215cm2) 25sq.in.(161cm2) 6"(152.4mm) 125,000(36.63) 62.50sq.in.(403cm2) 41.7sq.in.(269cm2) 31.25sq.in.(202cm2) 7" (177.8mm)
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000÷ 4,000) 32.5 Sq. In.Vertical
29.31 8.8 (38.11÷ .18) 210 cm2Vertical
Furnace Water Heater Total Input 100,000 + 30,000 = (130,000÷ 2,000) 65 Sq. In. Horizontal
29.31 8.8 (38.11÷ .09) 423 cm2Horizontal
44001202401 Specifications are subject to changewithout notice. 11
sq.in./2,000(1cm2/.09) sq.in./3,000(1cm2/.135) sq.in./4,000(1cm2/.18) sq.in./4,000(6.5cm2/.18)
IndoorCombustionAir (UnconfinedSpace)
Standardand Known-Air-Infiltration Rate Methods
© NFPA & AGA Indoor air is permitted for combustion and ventilation, if the
Standard or Known-Air-Infiltration Rate Method is used.
CARBON MONOXIDE POISONING HAZARD Failure to supply adequate combustion air could
result in personal injury or death. Most homes will require additional air from
outdoors for combustion and ventilation. A space with at least 50 cubic feet per 1,000 BTUH (4.8 cubic meters per kW) input rating or homes with tight construction may need outdoor air, supplied
through ducts, to supplement air infiltration for
proper combustion and ventilation of flue gases.
The Standard Method may be used, if the space has no less volume than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per
kW) ofthe maximum input ratings for atl gas appliances installed in
the space. The standard method permits indoor air to be used for
combustion and ventilation air.
The Known Air Infiltration Rate Method shall be used if the
infiltration rate isknown to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates
greater than 0.60 ACH shall not be used. The minimum required
volume of the space varies with the number of ACH and shall be
determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required
volume for the space.
CARBON MONOXIDE POISONING HAZARD Failure to supply additional air by means of
ventilation grilles or ducts could result in personal
injury or death.
An unconfined space or homes with tight
construction may not have adequate air infiltration
for proper combustion and ventilation of flue gases.
Most homes will require additional air.
The Known Air Infiltration Rate Method shall be used if the
infiltration rate is known to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates greater than 0.60 ACH shall not be used. The minimum required
volume of the space varies with the number of ACH and shall be
determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and
add the volumes together to get the total minimum required
volume for the space.
CARBON MONOXIDE POISONING HAZARD. Failure to supply additional air by means of
ventilation grilles or ducts could result in personal
injury or death.
An unconfined space or homes with tight
construction may not have adequate air infiltration
for proper combustion and ventilation of flue gases.
Most homes will require additional air.
MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS
OtherThanFan-AssistedTotal Fan-assistedTotal
30,000BTU
ACH
0,60 1,050 (29,7) 1,400 (39,2) 1,750 (49) 1,875 (52,5) 2,500 (70) 3,125 (87,5) 0,50 1,260 (35,3) 1,680 (47,04) 2,100 (58,8) 2,250 (63) 3,000 (84) 3,750 (105) 0,40 1,575 (44,1) 2,100 (58,8) 2,625 (73,5) 2,813 (78,8) 3,750 (105) 4,688 (131,3)
0,30 2,100 (58,8) 2,800 (78,4) 3,500 (98) 3,750 (105) 5,000 (140) 6,250 (175) 0,20 3,150 (88,2) 4,200 (117,6) 5,250 (147) 5,625 (157,5) 7,500 (210) 9,375 (262,5) 0,10 6,300 (176,4) 8,400 (235,2) 10,500 (294) 11,250 (315) 15,000 (420) 18,750 (525)
0,00 NP NP NP NP NP NP
ACH = Air Changes per Hour
NP = Not Permitted Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI
Z223.1/N FPA 54-2006, 9.3.2.2:
1. For appliances other than fan-assisted appliances (such
as a draft hood-equipped water heater), calculate using the following equation:
RequiredVolume other _ 59 m3 _ |other )
(8,790kW)
-- ACH 1000 BTUH
-- ACH .293 kW
40,000BTU 50,000BTU 75,000 100,000BTU 125,000BTU
(11,720kW) (14,650kW) (21,975kW) (29,300kW) (36,625kW)
50,000BTU (14,650kW)
ft3(m 3)
1,250(35) 1,500(42)
1,875(52,5)
2,500(70) 3,750(105) 7,500(210)
NP
2. For fan-assisted appliances (such as this furnace), calculate using the following equation:
RequiredVolume fan_ 15ft3 ( .fan )
ACH 1000 BTU H
! \
! \
RequiredVolume fan _ .42 m3 _, [ fan )
where:
[ other= all appliances other than fan-assisted input in BTUH [ fan = fan-assisted appliance input in BTUH
ACH = air change per hour (percent of volume of space
exchanged per hour, expressed as a decimal)
ACH .293 kW
12 Specificationsare subject to changewithoutnotice. 440012024 01
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
Adjoining rooms can be considered part of a space, if there are no closable doors between rooms.
An attic or crawl space may be considered a space that freely communicates with the outdoors provided there are adequate
ventilation openings directly to outdoors. Openings MUST
remain open and NOT have any means of being closed off.
Ventilation openings to outdoors MUST be at least 1 square
inch of free area per 4,000 BTUH (5.5 cm2/kW) of total input rating for all gas appliances in the space.
Combining spaces on the same floor level. Each opening shall have a free area of at least 1 in2/1,000 BTUH (22cm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in2 (645 cm2). One opening shall commence within 12" (304.8 mm) of the top and one opening shall commence within 12" (304.8mm) of the bottom of the enclosure. The minimum dimension of air openings shall be at
least 3" (76.2 mm).
Combining spaces on different floor levels. The volumes of spaces on different floor levels shall be considered communicating spaces if connected by one or more permanent openings in doors or floors having a free area ofat least 2 in2/1,000 Btuh (44 cm2/kW) of total input rating of all gas appliances.
In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion,
ventilation and dilution of flue gases. However, in buildings
with unusually tight construction, additional air MUST be provided using the methods described in section titled
Outdoor Combustion Air Method:
Unusually tight construction is defined as Construction with
1. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gasketed or sealed and
2. Doors and openable windows are weather stripped and
3. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
VentilationAir
Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as replacement air. Whichever method is used, the mixed return air
temperature across the heat exchanger MUST not fall below 60°
so that flue gases will not condense excessively in the heat exchanger. Excessive condensation will shorten the life of the heat exchanger and possibly void your warranty.
VentingandCombustionAir Check
NOTE: If this installation replaces an existing furnace from a commonly vented system, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized venting system may cause the formation of condensate inthe vent and the leakage or spillage of vent gases.
To make sure there is adequate combustion air for all appliances,
MAKE THE FOLLOWING CHECK.
Vent Check
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Vent Pipe----_ sDraft Hood
Typical Gas f "_ Water Heater [ _ _ j____ Match
I I v
I I
If flame pulls towards draft hood, this indicates sufficient venting.
The following information is supplied to allow the installer to make
adjustments to the setup of existing appliances, IF REQUIRED, based on good trade practices, local codes, and good judgement of the installer. Manufacturer does NOT take responsibility for modifications made to existing equipment.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation, could result in carbon monoxide poisoning or death:
The following steps shall be followed for each appliance
connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or CSA B149.1, Natural Gas and Pro- pane Installation Code and these instructions. Determine
that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe con-
dition.
3. As far as practical, close all building doors and windows
and all doors between the space inwhich the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they are operat- ing at maximum speed. Do not operate a summer exhaust
fan.
6. Followthe lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so ap-
pliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burn-
er operation. Use the flame of a match or candle. (Figure 7)
8. If improper venting is observed, during any of the above
tests, the venting system must be corrected in accor-
dance with the National Fuel Gas Code, ANSI
Z223. 1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance con- nected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning ap-
pliance to their previous conditions of use.
44001 202401 Specificationsare eubject to changewithout notice. 13
For Two Pipe Installation
(DirectVent)
This furnace can NOT be common vented or connected to any type
B, BW or L vent or vent connector, nor to any portion of a
factory-built or masonry chimney. If this furnace is replacing a
previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See "Venting and Combustion
Air Check" in this section. This furnace MUST be vented to the
outside.
4. Vent and Combustion Air Piping
CARBON MONOXIDE POISONING HAZARD Failure to properly vent this furnace could result in
personal injury or death. Use methods described here to provide combustion
and ventilation air.
DualCertified(*SMPT,*SMPV,*SMVXModels) Director Non-DirectVent
This furnace iscertified as a Category IV furnace. This furnace can
be installed as a direct vent furnace using outside air for combustion or the furnace can use air from inside the structure for
combustion. The INLET air pipe is optional. If combustion air comes from inside the structure, adequate make up air MUST be provided to compensate for oxygen burned. See Confined Space
Installation in the Combustion and Ventilation Air chapter. If
combustion air is drawn from outside the structure, it MUST be
taken from the same atmospheric pressure zone as the vent pipe.
ContaminatedCombustionAir
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the furnace.
The following areas or types of structures may contain or have
exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for
combustion.
Commercial buildings.
Buildings with indoor pools.
Furnaces installed in laundry rooms.
Furnaces installed in hobby or craft rooms.
Furnaces installed near chemical storage areas.
Permanent wave solutions for hair.
Chlorinated waxes and cleaners.
Chlorine based swimming pool chemicals.
Water softening chemicals.
De-icing salts or chemicals.
Carbon tetrachloride.
Halogen type refrigerants.
Cleaning solvents (such as perchloroethylene).
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid.
Sulfuric Acid.
Solvent cements and glues.
Antistatic fabric softeners for clothes dryers.
Masonry acid washing materials.
Ventand CombustionAir PipingGuidelines
This furnace is approved for venting with Schedule 40 PVC, CPVC, ABS fittings, and Cellular Core and SDR-26 PVC pipe.
Materials Pipe Pipe Core Fittings Primer Cement
ABS to
NOTE: 1) In Canada, all pipe, fittings & cements must
conform to applicable CSA standards or to local codes having jurisdiction.
with the specific venting material.
solvent cement that meets the requirements of ASTM D3138.
use for cementing plastic pipe and fittings.
NOTE: In order to create a seal that allows future removal of pipe,
RTV sealant MUST be used on the inlet pipe where itjoins to the furnace.
NOTE: All vent piping MUST be installed in compliance with local
codes or ordinances, these instructions, good trade practices, and
codes of country having jurisdiction.
ApplicableASTM Standardsfor Vent Materials
Sch.40 SDR Solv.
ABS D1527 F628 & -- D2235
PVC D1785 D224t F891 & F656 D2564
CPVC F44t F442 -- F438 -- F493
PVC
1. Determine the best routing and termination for the vent pipe
2. Determine the size required for the vent pipe and air inlet
3. Loosely assemble all venting parts without adhesive (pipe
4. Furnace shall be installed so asto prevent the accumulation
5. Use of vertical piping is preferred because there will be
6. The vertical vent pipe MUST be supported so that no weight
7. Exhaust vent piping or air inlet piping diameter MUST NOT
8. All exhaust vent piping from the furnace to termination
9. Use DWV type long radius elbows whenever possible, as
.......... D3138
2) Only use solvent cements that are marked for use
3) ABS to PVC transition joints REQUIRE a special
4) Refer to ASTM D2855 for general procedure to
and air inlet pipe by referring to all of the instructions and guidelines in this Section.
pipe.
joint cement) for correct fit before final assembly.
of condensate.
some moisture in the flue gases that may condense as it leaves the vent pipe (See Instructions For Horizontal
Vents).
is allowed to rest on the combustion blower.
be reduced.
MUST slope upwards. A minimum of 1/4" (6.4mm) per foot
(304.8mm) of run is required to properly return condensate
to the furnace drain system.
they provide for the minimum slope on horizontal runs and they provide less resistance in the vent system. If DWV elbows cannot be used, use two, 45 °elbows when possible. On horizontal runs the elbows can be slightly misatigned to provide the correct slope.
Cell
Pipe
D2468 D2661
D2466 D2665
14 Specificationsare subject to changewithoutnotice. 440012024 01
10. All horizontal pipe runs MUST be supported at least every five feet with galvanized strap or other rust resistant material. NO sags or dips are permitted.
11. All vertical pipe runs MUST be supported every six feet where accessible.
12. The maximum pipe length is 40' (12.2m) total in the inlet or outlet side of the system. Up to five, 90 ° elbows can be used
on the inlet or the outlet. With the Concentric Vent
Termination Kits (NAHA001CV or NAHA002CV), the
maximum pipe length is 35' (10.7m) with four 90° elbows. If more elbows are required, reduce the length of both the inlet and exhaust pipes 5' (1.5m) for each additional elbow used.
(See Table 3 or Table 4).
13. The minimum vent length is 5' (1.5m) of PVC.
14. The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing. It
can also be run in the same chase with avent from another 90+ furnace.
NOTE: In NO case can the piping be run in a chase where
temperatures can exceed 140 ° F (60 ° C). or where radiated
heat from adjacent surfaces would exceed 140° F(60 ° C).
15. The vent outlet MUST be installed to terminate in the same atmospheric pressure zone as the combustion air inlet.
16. The vent system can be installed in an existing unused chimney provided that:
Both the exhaust vent and air intake run the length of the chimney.
No other gas fired appliance or fireplace (solid fuel) is
vented into the chimney.
The top of the chimney MUST be sealed flush or crowned up to seal against rain or melting snow so ONLYthe piping protrudes.
The termination clearances shown in Figure8 are maintained.
17. Furnace applications with vertical vents requiring vent diameter increaser fittings must have increaser fittings installed in vertical portion of the vent. Condensate will be
trapped in the vent if the vent diameter is increased prior to
having an elbow turned upward. This could cause nuisance
tripping of the pressure switch.
CombustionAirandVent PipingInsulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. If Fiberglass or equivalent insulation is used it must have a vapor barrier. Use R values of 7 up to 10' (3.1m), R-11 if exposure exceeds 10' (3.1m). If Fiberglass insulation is used, exterior to the structure, the pipe MUST be boxed in and sealed against moisture.
1. When the vent or combustion air pipe height above the roof exceeds 30" (76.2mm), or if an exterior vertical riser is used on a horizontal vent to get above snow levels, the exterior portion MUST be insulated.
2. When combustion air inlet piping is installed above a suspended ceiling, the pipe MUST be insulated with
moisture resistant insulation such as Armaflex or other equivalent type of insulation.
3. Insulate combustion air inlet piping when run in warm, humid spaces.
SizingCombustionAir andVent Pipe
Consult Table 3 or Table 4 to select the proper diameter exhaust and combustion air piping. Exhaust and combustion air piping is sized for each furnace Btuh size based on total lineal vent length (on inlet or outlet side), and number of 90°elbows required.
1. Double Pipe Installation-If installing as a direct-vent appliance, consult Table 4 to select the proper diameter exhaust and combustion air piping. Exhaust and combustion air piping is sized for each furnace Btuh size based on total lineal vent length (on inlet or outlet side), and number of 90° elbows required.
2. Single Pipe Installation-If installing as a non-direct vent appliance, (single outlet pipe and no inlet pipe) refer to
Table 3. The table shows the maximum number of elbows
allowed with any given pipe diameter and length of run.
3. Use of Elbows-Two 45° elbows can be substituted for one 90° elbow. The elbow or elbows used for vent termination
outside the structure ARE counted, including elbows needed to bring termination above expected snow levels.
Pipe Diameter Table
Single Piping ONLY
40,000, 50,000, 60,000 & 75,000 Btuh Furnaces
40' (12.2m)& (5)90° elbowswith 2" (50.8mm)PVC pipe
80,000 & 100,000 Btuh Furnace
40' (12.2m)& (5)90° elbows with 3" (76.2mm) PVC pipe
125,000 Btuh Furnace
40' (12.2m)& (5)90° elbows with 3" (76.2mm) PVC pipe
The minimum vent length is 5' (1.5m) of PVC. Elbows are
DWV Long Radius Type for 2" (50.Smm) and 3" (76.2mm)
vents.
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5' (1.5m) for each additional elbow used. If less than five elbow are required, the length can be INCREASED by 5' (1.5m) for each additional elbow NOT used.
NOTE: It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters than shown.
Pipe Diameter Table
Dual Piping ONLY
40,000, 50,000, 60,000 & 75,000 Btuh Furnaces
40' (12.2m)& (5)90° elbows with 2" (50.8mm) PVC pipe
80,000 & 100,000 Btuh Furnace
40' (12.2m)& (5)90° elbowswith 3" (76.2mm)PVC pipe
125,000 Btuh Furnace
40' (12.2m)& (5)90° elbowswith 3" (76.2mm)PVC pipe
The minimum vent length is 5' (1.5m) of PVC. Elbows are
DWV Long Radius Type for 2" (50.Smm) and 3" (76.2mm)
vents.
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5' (1.5m) for each additional elbow used. If less than five elbow are required, the length can be INCREASED by 5' (1.5m) for each additional elbow NOT used.
* Feet of pipe is whichever pipe run is the longest, either inlet or outlet side.
For venting table, see"Concentric Termination Kit" in
this manual.
Vent Termination Clearances
CARBON MONOXIDE POISONING HAZARD
Failure to properly vent this furnace could result in
death and/or personal injury. Inlet and outlet pipes may NOT be vented directly
above each other.
1. Determine termination locations based on clearances specified in following steps and as shown in Figure 8,
Figure 9, Figure 22, through Figure 30.
For "Concentric Termination Kit" clearances, see Figure 32, Figure 33, Figure 34, Figure 35 and Figure 36 in this manual.
2. This furnace is Dual Certified and can be installed as a single pipe appliance (all combustion from inside the structure) or as a direct vent appliance where all
combustion air istaken from outside the structure.
3. For Single Pipe installation refer to Figure 9 for vent termination clearances.
4. For Direct Vent installation, refer to Figure 8 for vent termination.
44001 202401 Specificationsare subject to changewithoutnotice. 1 5
Figure 8 Direct Vent Termination Clearance
D VENTTERMINAL
Item Clearance Description Canadian Inslallafion (1) U.S. Installation (2)
A Clearance above grade, veranda, porch, deck, balcony, or 12 inches(30 cm) # 12 inches (30 cm)
anticipated snow level
B Clearance to a window or door that may be opened 12 inches (30 cm) for appliances > 10,000 Btuh (3 kW) 9 inches (23 era) for appliances > 1O,0O0 Btuh (3kW) and s
C Clearance to a permanently closed window
D Vertical clearance to a ventilated soffit located above [he
terminal within a horizontal distance of 2 feet(61em) from the centerline of the terminal
E Clearance to an unventilated soffit
F Clearance to an OL_side corner
G Clearance to an inside corner
H Clearance to each side of the centerline extended above 3 feet (91 cm) within 15 feet (4.5 m) above the meter/regulator 3 feet (9t cm) within 15 feet(4.5 m) above the
electrical meter or gas service regulator assembly assembly meter/regulator assembly
I Clearance to service regulator vent outlet 3 feet (91 cm)
J Clearance to non-mechanical air supply inlet to building or 12 inches (23 era) for appliances > 100,000 Btuh (3 kW) 9 inches (23 cm) for appliances > 10,000 Btuh (3kW) and
the combustion air inlet to any other appliance and s 100,000 Btuh (30 kW), 36 inches (30 cm) for _ 50,000 Btuh (15kW), 12 inches (30cm) for appliances
K Clearance to a mechanical air supply inlet 6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3re)horizontally
L Clearance under a veranda, porch, deck, or balcony 12 inches(30 cm) +
M Clearance to each side of the centerline extended above or 12 inches (30 em) 12 inches (30 cm)
below vent terminal of the furnace to a dryer or water heater vent, or other appliance's direct vent inlake or exhaust.
N Clearance to the vent terminal of a dryer vent, water heater 3 feet (91 cm) 3 feet (91 cm)
vent, or other appliances direct vent intake or exhaust.
Q Clearance from a plumbing vent stack 3 feet (91 cm) 3 feet (91 cm)
p Clearance above paved sidewalk or paved 7 feet (2.t 3m)**
driveway located on public property
(1.) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
(2.) In accordance with the cu trent ANSI Z223.1/NFPA 54, National Fuel Gas Code
# 18" (46 cm) above roof surface
+ Perrnitted only if veranda, porch, deck, or balcony is fully open on a mthimum of two sides beneath the floor.
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B t49.1, clearances shall be in accordance with local inetallation codes and the requirements of the gas supplier and the manufacturer's installation instructions
A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
Notes:
1,
The vent for this appliance shall not terminate
a. Over public walkways; or b. Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusalnee or hazard or property damage; or
e. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
2.
When locating vent terminations, consideration must be given to prevailing winds, location, and other conditionswhich may cause recirculation of the combustion products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
3.
Avoid venting under a deck or large overhang. Recirculation could occur and cause performance or system problems.
\\\\x
16
_X_ AIR SUPPLY INLET
and s 100,000 Btuh(30 kW), 36 inches 50,000 Btuh 15kW), 12 inches (30cm) for appliances >
(91 cm) for appliances > 100,000 Btuh (30 kW) 50,000 Btuh (ISkW
appliances > 100,000 Btuh (3 kW) > 50,000 Btuh (15kW)
Specifications are eubject to change without notice.
E_ AREA WHERE TERMINAL IS NOT PERMITED
440012024 01
Other than Direct Vent Termination Clearance
D VENT TERMINAL \_ _X_ AIR SUPPLY INLET
Item Clearance Descriptions
A Clearance above grade, veranda, porch, deck, balcony, or
anticipated snow level
B Clearance to a window or door that may be opened
Canadian Installation (t)
12 inches (30cm) #
6 inches (15 cm) for appliances -< 10,000 Btuh (3 kW) 12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kW0) and -< 100,000 Btuh (30 kW), 36 inches (91 cm) for appliances > 100,000 Btuh (30 kW)
E_ AREA WHERE TERMINAL IS NOT PERMITED
U.S. Installation (2)
12 inches (30 cm)
4 feet(1.2 m) below or to the side of the opening. 1foot(30 cm above the opening.
C Clearance to a permanently closed window
D Vertical clearance to a ventilated soffit located above the
terminal within ahorizontal distance of 2"(61cm) from the centerline of the terminal
E Clearance to an unventilated soffit
F Clearance to an outside corner
G Clearance to an inside corner
H Clearance to each side of the centerline extended above
electrical meter or gas service regulator assembly
I Clearance to service regulator vent outlet
J Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance
K
Clearance to a mechanical air supply inlet
L
Clearance under averanda, porch, deck, or balcony
M
Clearance to each side of the centerline extended above or below vent terminal of the furnace to a dryer or water heater
vent, or other appliance's direct vent intake or exhaust.
N Clearance to the vent terminal of a dryer vent, water heater
vent, or ether appliances direct vent intake or exhaust.
O Clearance from a plumbing vent stack
p Clearance above paved sidewalk or paved 7 feel (2.13m)**
driveway located on public property
(1.) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
(2.) In accordance with the currant ANSI Z223.1/NFPA 54, National Fuel Gas Code # 18'(46cm) above roof surface
3 feet (91 cm) within 15 feet(4.5 m) above the meter/regulator assembly
3 feet (91 cm)
6 inches (15 cm) for appliances -< 10,000 Btuh (3 kW) 12 inches ( 30 cm) for appliances > 10,000 Btuh (3 kW0)
and -< 100,000 Btuh (30 kW)
36 inches (91 cm) for appliances > 100,000 Btuh (30 kW)
6 feet(1.83 m)
12 inches(30 am) +
3 feet (91 cm) Within 15feet (4.5 m) above the meter/regulatol assembly
4 feet(1.2 m) below or to the side of opening: 1 foot (30 cm) above opening.
3 feet(91 cm) above if within 10 feet (3 m horizontally)
7 feet (2.13m)
+ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances shall be in accordance with local installationcodes and Ihe requirements of the gas supplier and the Manufacturer's installation instructions.
** A vent shall not terminate above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Notes:
1. The vent for this appliance shall not terminate a. Over publicwalkweys; or
b. Nears__itvents_rcraw_spacevents_r_therareaswherec_ndensate_rvap_rc_u_dcreateanusiance_rhazard_rpr_pertydamage;_r
c. Wherec_ndensatevap_rc_u_d_ausedamage_r_dbedetrimenta_t_t_e_perati_n_fregu_a_rs_re_iefva_ves_r_therequipment_
2. When locating vent terminations, consideration must be given to prevailing winds, location, and other c onditions which may cause recirculation of the cembustiob products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.
3 Avoid venting under a deck or large overhang. Recirculation could occur end cause performance or system problems. A05013
44001 202401 Specificationsare eubject to changewithout notice. 17
CondensateDrainTrap
This furnace removes both sensible and latent heat from the
products of combustion. Removal of the latent heat results in
condensation of the water vapor. The condensate is removed from the furnace through the drains in the plastic transition and the vent fitting. The drains connect to the factory installed internally
mounted condensate drain trap on the left or right side of the furnace.
The startup of a new furnace will involve a cycle or two of the furnace to properly prime the condensate trap with water. Until the trap is fully primed, some condensate will be pulled into the
combustion blower. The furnace may cycle on the pressure switch
connected to the plastic transition box due to condensate buildup. After the trap is primed, the condensate will start draining from the furnace. The combustion blower will clear out any remaining
condensate in the blower housing through the vent fitting
downstream of the blower. Note that the condensate trap can also
be primed by pouring water into the 1/2" (12.7mm) drain hose.
Remove the1/2'' (12.7mm) ID drain hose from either the gutter or the white PVC tee trap. Using a funnel pour eight (8) ounces of
water into 1/2" (12.7mm) ID drain hose. Water will flow through the
drain hose and into the condensate drain trap. This will prime both the vent and the transition sides of the trap. Reconnect the 1/2"
(12.7mm) ID drain hose to the original component, either the gutter
or the PVC tee trap. The condensate drain trap supplied with the furnace MUST be
used. The drain connection on the condensate drain trap is sized for 3/4" (19.1mm) PVC or CPVC pipe, however alternate 1/2"
(12.7mm) CPVC [nominal 5/8" (15.gmm) O. D.] or vinyl tubing with a
minimum inner diameter (I.D.) of 5/8"(15.gmm) may also be used,
as allowed by local codes. Alternate drain pipes and hoses may be
used as allowed by local codes. The drain line must maintain a 1/4" (6.4mm) per foot (304.8mm)
downward slope toward the drain. 1/4" (6.4mm) per foot (304.8mm)
is recommended. Installation of an overflow line is recommended
when the 1/4"(6.4mm) per foot (304.8mm) slope tothe condensate
drain cannot be maintained. A drain tube clip is included in the furnace to prevent kinking/buckling of the drain tube. The clip
should remain in the furnace (between the door switch plate and the blower shelf, Figure 10) during operation. See Figure 20 for
proper routing and installation of the overflow.
Fi_ _ !'i'111Drain Tube Clip Location
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace.
If possible, DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of
the condensate and possible property damage.
1. A condensate sump pump MUST be used if required by local codes, or if no indoor floor drain is available. The condensate pump must be approved for use with acidic
condensate.
2.
A plugged condensate drain line or a failed condensate pump will allow condensate to spill. Ifthe furnace is installed where a condensate spill could cause damage, it is recommended that an auxiliary safety switch be installed to prevent operation of the equipment in the event of pump failure or plugged drain line. If used, an auxiliary safety switch should be installed in the R circuit (low voltage)
ONLY.
3.
If the auxiliary switch in the condensate pump is used, the furnace may shut down due to a blocked condensate line or failed pump. To prevent frozen water pipes see the "Frozen Water Pipe Hazard" section of this manual.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in burst
water pipes and/or property damage. If a condensate pump is installed, a plugged
condensate drain or a failed pump may cause the furnace to shut down. Do not leave the home
unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
CondensateDrainTrap FreezeProtection
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the the furnace environment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot at 115 volt, 40 ° F (4°0) self-regulating shielded and waterproof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer's recommendations. Prime the
trap before furnace operation.
Drain Tube
Blower Shelf Door
Representative drawing only, some models may vary in appearance.
18 Specifications are eubject to changewithoutnotice. 440012024 01
f
Switch
Loading...
+ 40 hidden pages