voltage equipment and trained in recognizing hazards in products
Part Number: 435256-004
User Guide
Abstract
This document includes installation, configuration, and operation information for the HP 3 Phase UPS. This document is for th
maintains power products. HP assumes you are qualified in the servicing of highwith hazardous energy levels.
warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall
not be liable for technical or editorial errors or omissions contained herein.
UPS front panel ......................................................................................................................................... 8
UPS front panel controls ............................................................................................................................. 9
UPS front panel LED indicators .................................................................................................................... 9
Preparing to install the hardware ............................................................................................................... 13
Tools and materials ........................................................................................................................ 13
Selecting a site .............................................................................................................................. 14
Readying the equipment ................................................................................................................. 14
Installing the mounting rails ...................................................................................................................... 14
Installing the UPS .................................................................................................................................... 17
Removing the UPS battery bracket ................................................................................................... 19
Installing the batteries .................................................................................................................... 19
Replacing the UPS battery bracket ................................................................................................... 20
Attaching the UPS front bezel .......................................................................................................... 20
Connecting the ground bonding cable ............................................................................................. 20
Connecting the REPO port .............................................................................................................. 21
Connecting the UPS to utility power ................................................................................................. 23
Switching on the UPS battery circuit breaker ..................................................................................... 24
Connecting devices to the UPS ........................................................................................................ 24
Charging the UPS batteries ............................................................................................................. 25
Powering up the standalone UPS ..................................................................................................... 25
Installing in a parallel configuration ........................................................................................................... 26
Installing the input and output wiring ................................................................................................ 26
Wiring the terminal block ............................................................................................................... 28
Connecting the ground bonding cable ............................................................................................. 29
Connecting the REPO port .............................................................................................................. 30
Connecting the UPSs to the Bus Bar ................................................................................................. 35
Switching on the UPS input circuit breaker ........................................................................................ 37
Switching on the UPS battery circuit breaker ..................................................................................... 37
Connecting devices to the UPS ........................................................................................................ 38
Charging the UPS batteries ............................................................................................................. 38
Powering up the parallel system ...................................................................................................... 39
Adding an HP 3 Phase UPS to a parallel configuration ................................................................................ 39
Disconnecting from utility power ...................................................................................................... 39
Installing the UPS ........................................................................................................................... 39
Preparing to install the hardware ............................................................................................................... 55
Tools and materials ........................................................................................................................ 55
Selecting a site .............................................................................................................................. 55
Contents 3
Readying the equipment ................................................................................................................. 56
Installing the mounting rails ...................................................................................................................... 56
Preparing the rails for integrated shipping .................................................................................................. 58
Switching off the UPS battery circuit breaker ............................................................................................... 59
Switching off the ERM circuit breaker ......................................................................................................... 59
Installing the ERM .................................................................................................................................... 60
Attaching the ERM front bezel ......................................................................................................... 62
Connecting the ERM to the UPS ....................................................................................................... 62
Switching on the ERM circuit breaker ............................................................................................... 63
Switching on the UPS battery circuit breaker ..................................................................................... 63
Charging the ERM batteries ............................................................................................................ 63
Modes of operation ................................................................................................................................. 64
Configuring the UPS ................................................................................................................................ 67
Changing the language.................................................................................................................. 67
Testing the front panel display ................................................................................................................... 71
Silencing an audible alarm ....................................................................................................................... 71
Verifying the REPO port connection ........................................................................................................... 71
Powering down the standalone UPS ........................................................................................................... 72
Powering down an individual paralleled UPS .............................................................................................. 72
Powering down the parallel system ............................................................................................................ 73
Communication .......................................................................................................................... 74
Installing communication options and control terminals ................................................................................. 74
Communication options ............................................................................................................................ 75
DB-9 communication port................................................................................................................ 75
Control terminals ..................................................................................................................................... 76
Power management ....................................................................................................................
HP UPS Power Protection Agent overview ................................................................................................... 80
Features ................................................................................................................................................. 80
Configuring the Parallel UPS Card ............................................................................................................. 84
Contents 4
Replacing the batteries ............................................................................................................................. 87
Important battery safety information ................................................................................................. 87
Battery care and storage guidelines ................................................................................................. 87
Testing the new battery module ....................................................................................................... 89
Replacing the UPS ................................................................................................................................... 89
Replacing the ERM .................................................................................................................................. 90
Updating the UPS firmware ...................................................................................................................... 91
Verifying the HP UPS Management Module firmware version .............................................................. 91
Configuring a USB to serial converter ............................................................................................... 91
Reassigning the USB COM ports ..................................................................................................... 92
Battery test condition ................................................................................................................................ 96
Bypass is unavailable .............................................................................................................................. 96
Site wiring condition ................................................................................................................................ 99
UPS does not power down ....................................................................................................................... 99
UPS does not power up ............................................................................................................................ 99
UPS does not provide the expected backup time ....................................................................................... 100
UPS does not transfer to Auto-Bypass mode .............................................................................................. 100
UPS is on battery ................................................................................................................................... 100
UPS is on bypass................................................................................................................................... 100
Model list ............................................................................................................................................. 101
UPS spare parts list ................................................................................................................................ 106
Index ....................................................................................................................................... 113
Contents 6
Component identification
3 Phase UPS overview
The HP 3 Phase UPS protects your sensitive electronic equipment from the most common power problems
including power failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware - causing
hours of lost productivity and expensive repairs.
With the HP 3 Phase UPS, you can safely eliminate the effects of power disturbances and guard the integrity
of your equipment. The HP 3 Phase UPS is designed for critical applications such as ultra high—density blade
servers in a data center environment.
Providing outstanding performance and reliability, the HP 3 Phase UPS unique benefits include:
• Scalable to 60 kW (redundant N+1 configuration) by connecting up to six additional parallel UPS
modules.
Each UPS in the parallel system connects to a Power Bus Bar pre-installed in the rear of a rack. Racks
can be configured for bottom or top entry
A Parallel UPS Card in each paralleled UPS provides connectivity for system metering and operational
mode control. In a parallel system not fully loaded, the system will shift load to UPSs with the strongest
batteries or additional ERMs to maximize runtime when on battery. Parallel systems can be configured
for capacity or redundancy.
• 6U UPS height, 3U ERM height
• Normal operating mode that minimizes heat generation by operating at typically >98% efficiency
The UPS filters incoming AC power and provides consistent power to your equipment without draining
the battery.
• For utility line input that exceeds normal operating range, automatic transfer to an online,
double-conversion, high-frequency UPS design with pure sine wave output and power-factor correction
• EBM technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life
• Extended runtime with up to four ERMs per UPS
• Hot-swappable electronics module and batteries that simplify maintenance by allowing you to replace
them safely without powering down the critical load
• Emergency shutdown control through the REPO port
• HP UPS Management Module for network connectivity with monitoring and control
• Firmware that is service upgradeable through the standard DB-9 communication port
• Backed by worldwide agency approvals
Component identification 7
The Power Bus Bar for parallel systems, mounted in the rear of an HP rack, provides the required input and
LED display
output connections for the paralleled UPSs and has a single system-rated input connection. The parallel UPS
system can be installed with Output Power Modules or connected to rack-mounted power distribution
systems.
Note these guidelines when configuring the UPS standalone unit or parallel system:
• There is a maximum of four ERMs per UPS.
• Mount ERM(s) for a standalone UPS directly below the UPS or, with rack side panels removed, in an
adjacent rack to the left of the rack containing the UPS.
• Mount ERMs for a parallel system in an adjacent rack to the left of the rack containing the UPSs (rack
side panels removed).
• For consistent runtimes, each UPS in a parallel system should have the same number of ERMs.
• Some load equipment may require phase rotation or phase relationship coordination to ensure proper
operation. Review your equipment manufacturer’s power requirement documents to ensure that your
connected equipment operates correctly.
UPS front panel
Item Description
1
2
3
4
Battery compartment
Control buttons
Electronics compartment
Component identification 8
UPS front panel controls
Item Description Function
1
2
3
4
Left arrow or ESC Cancel/return to the previous menu
Up arrow Scroll through the menu structure
Down arrow Scroll through the menu structure
Right arrow or enter Select an option
UPS front panel LED indicators
Item LED description
1
2
Power On
On Battery
Component identification 9
Item LED description
Input/output power connectors
Output connector (only for use with output module)
3
4
Auto-bypass
Alarm
For more information, see "LED and audible alarm troubleshooting (on page 94)" .
UPS rear panel
Item Description
1
2
3
4
5
6
7
8
9
10
11
NOTE: For proper UPS operation, be sure that the terminal block jumpers are inserted as shown.
Ground bonding screw
DB-9 service port
REPO port (NO and NC)
REPO port
WARNING: The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit
must be separated from any hazardous voltage circuits by reinforced insulation.
Component identification 10
CAUTION:
48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46:
• Do not connect the REPO port to any utility connected circuits. Reinforced insulation to the
utility is required. The REPO switch must have a minimum rating of 24 Vdc and 20 mA and be
a dedicated latching-type switch for the 3 Phase UPS only, no other device or circuit including
a single phase UPS. The REPO signal must remain active for at least 250 ms for proper
operation.
• To ensure that the UPS stops supplying power to the load during any mode of operation, the
input power must be disconnected from the UPS when the EPO function is activated.
NOTE: For Europe, the emergency switch requirements are detailed in Harmonized document
HD-384Isolation and Switching.”
The UPS includes an isolated REPO port. When properly wired, the REPO feature allows the power at the
UPS output receptacles to be switched off from a remote location. When REPO is activated, the UPS powers
down all converters, de-energizes all system relays, trips the UPS battery circuit breaker, and powers down
within 10 to 15 seconds. However, the unit continues to have logic power (the display is still active) and is
not fully powered down until input power is disconnected from the unit. This feature can be used for powering
down the load and the UPS by thermal relay, for example in the event of room overtemperature.
To use this feature, the REPO port must be connected to a remote switch (not supplied). The REPO switch is
used in conjunction with a main disconnect device that removes the AC source from the input of the UPS.
When the switch is activated:
• The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
• The REPO feature shuts down UPS units operating under either utility or battery power.
Keep the REPO connector installed in the REPO port on the UPS even if the REPO function is not needed. The
REPO connection are listed below:
Wire function Terminal wire size rating Suggested wire size
L1
L2
There are two REPO positions, normally-open (NO) or normally-closed (NC). The pins on the NC REPO
connector are connected together. When this connection is open, the logic circuitry completely shuts down
the UPS, thus preventing the power from supplying the load. To use NC REPO, remove the jumper wire and
connect an NC external switch. To use NO REPO, connect an NO external switch. For REPO locations, see
Connecting REPO port
.
NOTE: If the UPS was operating on battery power when the remote switch was closed, no power
is available to the load devices until utility power is restored and the UPS has been manually
powered up.
To restore power to the load devices after the REPO feature is activated, press the Power On button after the
AC source is reconnected to the UPS.
IMPORTANT: Pressing and holding the Power On button without utility present normally initiates
a battery start and the UPS assumes the load. However, if the Power On button is pressed and a
REPO is detected, battery start is inhibited and the UPS is not able to assume the load. The
electronics module fan spins and the Alarm LED and an audible alarm are active as long as the
Power On button is held.
Circuit breaker
ERM input connector (from another ERM output)
ERM output connector (to the UPS or another ERM)
Component identification 12
UPS installation
A risk of personal injury from electric shock and hazardous energy levels exists. The
Precautions
Save these instructions. This document contains important safety instructions that should be followed during
installation, operation, and maintenance of the UPS and batteries.
WARNING:
installation of options and routine maintenance and service of this product must be performed by
individuals who are knowledgeable about the procedures, precautions, and hazards associated
with AC power products.
This symbol indicates that the UPS exceeds the recommended weight for one individual
140 kg
307 lb
to handle safely.
WARNING: To reduce the risk of personal injury or damage to the equipment, observe
local occupational health and safety requirements and guidelines for manual material
handling.
This symbol indicates that the ERM exceeds the recommended weight for one individual
77 kg
170 lb
to handle safely.
WARNING: To reduce the risk of personal injury or damage to the equipment, observe
local occupational health and safety requirements and guidelines for manual material
handling.
WARNING: To prevent personal injury from earth conductor leakage current:
• Do not operate the UPS while disconnected from the utility power source.
• Disconnect load devices before disconnecting the UPS from the utility power source.
Preparing to install the hardware
Before installing the hardware:
1. Be sure the necessary tools and materials (on page 13) are available.
2. Select an installation site ("Selecting a site" on page 14).
Tools and materials
3. Prepare the equipment ("Readying the equipment" on page 14) for installation in the rack.
The following tools are required for installation:
• Phillips screwdriver
• 10-mm hex-nut wrench
• T-25 Torx driver
A cage nut-fitting tool is supplied with the rack.
UPS installation 13
Selecting a site
WARNING: To prevent fire or electric shock, install the unit in a temperature- and
When selecting a site, consider the following factors:
• Elevated operating ambient temperature—If the equipment is installed in a closed or multi-unit rack
• Reduced air flow—In the rack, the rate of air flow required for safe operation of the equipment must not
• Circuit overloading—Consideration should be given to the connection of the equipment to the supply
• Reliable earthing—Reliable earthing of rack-mounted equipment should be maintained. Particular
• Electrical requirements—All models require a dedicated (unshared) branch circuit, suitably rated for the
humidity-controlled indoor environment, free of conductive contaminants.
assembly, the operating ambient temperature of the rack environment might be greater than room
ambient temperature. Install the equipment in an environment compatible with the operating
temperature ("Environmental specifications" on page 103).
be compromised.
circuit and the effect that overloading of the circuits might have on overcurrent protection and supply
wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing
this concern.
attention should be given to supply connections other than direct connections to the branch circuit, such
as the use of power strips.
specific UPS as stated in "Input specifications" .
Readying the equipment
1. Check the battery recharge date specified on the label that is affixed to the shipping carton.
IMPORTANT: Do not use the battery if the recharge date has passed. If the date on the battery
recharge date label has passed without the battery being recharged, contact an HP authorized
2. Transport the packaged unit to its installation location.
3. Unpack the equipment near the rack where the unit will be assembled.
service representative for directions.
Installing the mounting rails
WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that:
• The leveling feet are extended to the floor.
• The full weight of the rack rests on the leveling feet.
• The stabilizing feet are attached to the rack if it is a single-rack installation.
• The racks are coupled together in multiple-rack installations.
• Only one component is extended at a time. A rack may become unstable if more than one
component is extended for any reason.
WARNING: A risk of personal injury or damage to the equipment exists. Uneven loading of
equipment in the rack might cause the rack to become unstable. Install the heavier components
first, and then continue to populate the rack from the bottom to the top.
UPS installation 14
CAUTION: Always plan the rack installation so that the heaviest item is on the bottom of the rack.
Install the heaviest item first, and continue to populate the rack from the bottom to the top.
NOTE: Mounting hardware for square- and round-holed racks is included in the UPS kit.
1. Select the proper holes in the rack for positioning the UPS in the rack.
The UPS rails are installed in positions 1 and 12.
2. Loosen the hex nuts, and extend the brackets to the desired length.
UPS installation 15
3.
Insert screws through the rack into the mounting rail and the front of each mounting bracket.
4. Install cage nuts or clip nuts into the rear of the rack.
UPS installation 16
5.
Insert screws through the mounting rail into the cage nuts or clip nuts.
6. Tighten the hex nuts.
IMPORTANT: If preparing the rails for integrated shipping, install the rear mounting brackets.
Installing the UPS
Before installing the UPS, review and observe all warnings in "Precautions (on page 13)."
WARNING: A risk of personal injury or damage to the equipment exists. Uneven loading of
equipment in the rack might cause the rack to become unstable. Install the heavier components
first, and then continue to populate the rack from the bottom to the top.
UPS installation 17
CAUTION: Always plan the rack installation so that the heaviest item is on the bottom of the rack.
Install the heaviest item first, and continue to populate the rack from the bottom to the top.
1. Install the mounting rails ("Installing the mounting rails" on page 56, "Installing the mounting rails" on
page 14).
2. With one person on each side of the carton, lift the chassis and lower it to the floor in front of the rack.
3. Install the mounting ears on the chassis using the screws provided.
4. With one person on each side, lift the chassis to rail level and slide the chassis on the mounting rails.
5. Attach the chassis to the rack using the supplied screws.
6. If using the rear mounting brackets, be sure that the bracket tabs are fully inserted into the rear panel
cutouts, then tighten the brackets.
UPS installation 18
Removing the UPS battery bracket
Be sure that all circuit breakers on the rear panel of the UPS are in the Off position.
Installing the batteries
WARNING: To prevent personal injury, prepare the area and observe all materials-handling
procedures when transporting a battery module. Battery modules weigh 20 kg (44 lb).
UPS installation 19
Replacing the UPS battery bracket
Attaching the UPS front bezel
1. Connect the cable to the electronics module.
2. Attach the UPS front bezel.
Connecting the ground bonding cable
The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable
if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal
parts.
UPS installation 20
The ground bonding cable is not included.
Connecting the REPO port
This UPS has two REPO ports, normally-open and normally-closed. Before connecting to a REPO port, review
and observe all warnings.
WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while
HP recommends using different colors for the positive and negative wires.
To avoid inadvertant EPO:
• Minimize wire strain while connecting the REPO port.
• Avoid allowing the wires to hang in the rear of the UPS.
• Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.
connecting the REPO port in parallel with other HP UPSs.
WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a
UPS installed in a computer equipment room must be connected to a REPO circuit.
NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or
equivalent).
For more information about the REPO port, see "REPO port (on page 10)" .
For information about verifying the REPO connection, see "Verifying the REPO port connection (on page 71)"
Connecting to a normally-open contact
.
IMPORTANT: The remote switch must be in the open position to enable power to the UPS output.
UPS installation 21
NOTE: The REPO wiring of a standalone UPS can be connected with the REPO wiring of a
parallel system if the same sense (NO or NC) contacts are used. Be sure to match the polarity for
parallel system if the same sense (NO or NC) contacts are used. Be sure to match the polarity for
the contacts.
1. Verify that the UPS is powered down and all power sources are removed. For more information, see
"Powering down the standalone UPS (on page 72)."
2. Mount the remote REPO switch. HP recommends mounting the REPO switch near the operator's
consoles or near the exit doors. For enclosure dimensions and wiring knockouts, see the REPO switch
manufacturer's installation instructions.
3. Connect the appropriate external switch to terminal block 4, normally-open REPO.
IMPORTANT: Always test the REPO function before applying the critical load to avoid accidental
load loss. For more information, see "Verifying the REPO port connection (on page 71)."
4. Reconnect terminal block 4, normally-open REPO, and then power on the UPS manually to restart. Pins
should remain open to keep the UPS running. Maximum resistance is 10 ohm.
5. Verify that the jumper is inserted in terminal block 5.
Connecting to a normally-closed contact
IMPORTANT: The remote switch must be in the closed position to enable power to the UPS
output.
NOTE: The REPO wiring of a standalone UPS can be connected with the REPO wiring of a
the contacts.
UPS installation 22
1. Verify that the UPS is powered down and all power sources are removed. For more information, see
"Powering down the standalone UPS (on page 72)."
2. Mount the remote REPO switch. HP recommends mounting the REPO switch near the operator's
consoles or near the exit doors. For enclosure dimensions and wiring knockouts, see the REPO switch
manufacturer's installation instructions.
3. Connect the appropriate external switch to terminal block 5, normally-closed REPO, and then discard
the jumper wire.
IMPORTANT: Always test the REPO function before applying the critical load to avoid accidental
load loss. For more information, see "Verifying the REPO port connection (on page 71)."
4. Reconnect terminal block 5, normally-closed REPO, and then power on the UPS manually to restart. The
pins must be shorted to keep the UPS running. Maximum resistance is 10 ohm.
Connecting the UPS to utility power
WARNING: To prevent injury from electric shock or damage to the equipment:
• Plug the input line cord into a grounded (earthed) electrical outlet that is installed near the
equipment and is easily accessible.
• Do not disable the grounding plug on the input line cord. The grounding plug is an important
safety feature.
Connect the UPS to a grounded utility power outlet.
• Do not use extension cords.
UPS installation 23
Switching on the UPS battery circuit breaker
When the UPS is plugged in and the battery circuit breaker is on, the UPS automatically enters Standby mode
and begins charging the batteries.
Connecting devices to the UPS
CAUTION: Do not plug laser printers into the UPS output receptacles. The instantaneous current
Before connecting devices, verify that the UPS will not overload by checking that the ratings of the devices do
not exceed the UPS capacity. If the equipment rating is listed in amps, multiply the number of amps by the
nominal AC source to determine the VA.
To provide additional receptacles:
• For the 8kVA models—Plug a PDU into the UPS output receptacle at the end of the power cord.
• For the 12kVA models—
drawn by this type of printer can overload the UPS.
a. Install the included output module on the rear rack frame.
UPS installation 24
b.
Plug the output module into the special UPS output receptacle, located on the rear of the UPS.
Item Description
1
2
3
4
5
6
Rack corner post
Mounting locations
Mounting top bracket
Output cord
Mounting bottom bracket
Input cord
Charging the UPS batteries
With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT: Charge the batteries for at least 48 hours before supplying backup power to
devices. The batteries charge to:
• 80 percent of their capacity within 5 hours
• 100 percent of their capacity within 48 hours
Powering up the standalone UPS
NOTE: Be sure that the total equipment ratings do not exceed the UPS capacity to prevent an
1. Switch the UPS input circuit breaker to the On position.
overload alarm.
2. Wait for the UPS front panel display to illuminate.
The Alarm LED flashes.
3. Check the UPS front panel display for active alarms or notices (other than "Batteries Disconnected").
Resolve any active alarms before continuing. For more information, see "Troubleshooting (on page
94)" .
4. Switch the UPS battery circuit breaker to the On position.
UPS installation 25
5.
If optional ERMs are installed, switch all ERM battery circuit breakers to the On position.
Be sure that the "Batteries Disconnected" alarm has cleared. Be sure that no other alarms appear on the
UPS front panel display. If the Alarm LED is flashing, do not proceed until all alarms clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
6. Press any button once and then press the left arrow button to select the TURN UPS ON/OFF menu.
7. Press the down arrow button to select the TURN UPS ON option. Press the left arrow button.
8. Confirm the selection. Press and hold the left arrow button for three seconds, until the UPS stops
beeping.
The UPS front panel display indicates "UPS starting..." while relays click and the fans start. The display
returns to the status menu.
Be sure that the Power On LED illuminates.
If the Alarm LED is flashing, do not proceed until all alarms are clear. Check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if necessary. The UPS should be in
Operate mode.
9. Switch the output circuit breaker to the On position.
10. To return to the default logo screen, press the ESC button.
Installing in a parallel configuration
WARNING: This equipment must be installed by a licensed electrician or trained service
A UPS connected to a Bus Bar with a paralleling line cord is identified as a member of the parallel system.
The Bus Bar connects the line and load to a common power bus. A parallel system can be configured for
capacity or redundancy.
The UPS models in a parallel configuration require a dedicated branch circuit that meets the following
requirements:
• Circuit with overcurrent protection, depending on parallel configuration:
Number of UPSs in parallel
system
3
4
5
6 (N+1 system)
• Three-phase, 4-wire plus ground, 208 Y/120 V nominal (NA) or 400 Y/230 V nominal, 380-415 VAC
personnel familiar with high-power circuitry
HP 3 Phase NA HP 3 Phase INTL
150 A 75 A
200 A 100 A
225 A 125 A
225 A 160 A
acceptable (INTL)
• 50/60 Hz
• The breaker must be wall-mounted and be readily accessible to the operator
• Flexible or rigid metal conduit
Installing the input and output wiring
Be sure that the UPSs are properly installed in individual rail kits in a rack containing a Bus Bar.
UPS installation 26
Bottom entry
1. Remove the UPS above the wireway. See "Replacing the UPS (on page 89)" .
2. Remove the eight screws on the wireway top cover and retain.
3. Slide the cover back and off the wireway and retain.
4. Remove the six screws on the conduit landing plate and retain.
5. Remove the plate and retain.
6. Use a Greenlee punch to provide one or more holes in the conduit landing plate to accommodate the
input and output wiring from the utility to the Power Bus Bar.
7. Replace the conduit landing plate.
8. Reinstall the UPS above the wireway.
UPS installation 27
Top entry
Top entry wiring does not interfere with access areas for the fans, connectors, breakers
Use a Greenlee punch to provide one or more holes in the top of the wireway. Install one or more holes in
the center rear of the top of the racks.
NOTE:
or X-Slot cards on any HP 3 Phase UPS. See the wireway label.
Wiring the terminal block
Connect the input, output and ground wires to the Power Bus Bar terminal block. Route the three input phases
and the input neutral through the ferrite assembly.
Wire gauge depends on overcurrent protection rating required. For more information, see "Installing in a
parallel configuration (on page 26)." Reference the NEC, NFPA 70, for wire sizing.
UPS installation 28
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.