This thermostat provides electronic control of 24 VAC single-stage heating and cooling systems, or 750 mV heating systems.
System Types
•Gas, oil, or electric heat with air
conditioning
•Warm air, hot water, high-efficiency
furnaces, heat pumps, steam, gravi-
Power Options
•Battery power only
•Common wire only
•Common wire with battery backup
ty
Changeover Options
•Heat only — two-wire systems,
power to open and close zone
valves (Series 20), and normallyopen zone valves
•Heat only with fan
•Cool only
•750 mV heating systems
•Selectable manual or
auto-changeover modes
System Settings
•Heat, Off, Cool,Auto
Fan Settings
•Auto, On
Must be installed by a trained, experienced technician
•Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
•Check the ratings in this booklet to verify that this product is suitable for your
application (see page 13).
•Always test for proper operation after installation (see page 9).
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
.
In Installer Setup, set system type to Heat Pump & changeover valve to 0 or B.
Remove jumper
Wiring diagrams
Typical 1H/1C heat pump systemTypical heat-only system
Installation Guide
Wiring diagrams
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Optional 24VAC common connection.
In Installer Setup, set system type to Heat Only
In Installer Setup, set system type to Heat Pump & changeover valve to 0 or B.
Typical heat-only system with fanHeat-only system (Series 20)
.
Typical cool-only systemHeat-only system (normally open zone valve)
6
FocusPRO™TH6110D Programmable Thermostat
7
AC Power
The thermostat can be powered by 24
VAC power, or by batteries.
To wire the thermostat for AC power,
connect the common side of the
cooling transformer to the “C” terminal
as shown at left.
IImmppoorrttaanntt::
Remove R/Rc jumper for
2-transformer systems only. (See wiring
diagram on page 5.)
Connect common
side of transformer
to “C” terminal
Install batteries in back of thermostat
(optional if AC powered).
Battery Power
The thermostat can be powered by
batteries alone or,if used with AC
power, can provide backup power.
During power interruptions the
batteries will save time/day settings
and power the display.
After installation, batteries can be
changed without removing the thermostat from the wall (see page 11).
To Mount Thermostat
Align the 4 tabs on the wallplate with
corresponding slots on the back of the
thermostat, then push gently until the
thermostat snaps in place.
Jumper
Power options & mounting
Installation Guide
Installer setupInstaller system test
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
To begin, pr
buttons until the display changes
ess and hold the and
FFAANN
Setup FunctionSettings & Options
1
System type
2
Changeover valve
(O/B terminal)
3
Fan control
(heating)
5
Heating cycle rate
(CPH: cycles/hour)
9
Compressor
cycle rate (CPH)
12
System setting
adjustment
13
Adaptive Intelligent Recovery
14
Temperature
display
15
Compressor
protection
16
Schedule format
0 Gas, oil or electric heat with air conditioning
1 Heat pump
2 Heat only (2-wire systems/power to open & close zone valves/
normally open zone valves)
3 Heat only with fan
4 Cool only
0 Changeover valve (O/B terminal energized in cooling)
1 Changeover valve (O/B terminal energized in heating)
0 Gas or oil furnace — equipment controls fan in heating
1 Electric furnace — thermostat controls fan in heating
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Function 1 or 3
is set to “1” (see page 8).
0 Compressor and fan turn off.
1 Compressor and fan turn on.
0 Fan turns off.
1 Fan turns on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System TestSystem Status
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
Follow the procedure below to test the heating, cooling and fan.
Installation Guide
Auto Changeover (Setup Function 12)
Auto Changeover is a feature used in
climates where both air conditioning and
heating are used on the same day.When the
system is set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature.
Heat and cool settings must be at least 3
degrees apart.The thermostat will automatically adjust settings to maintain this 3-degree
separation (called “deadband”).
The 3-degree separation between heating
and cooling set temperatures is fixed, and
cannot be changed.
Set Clock/Day/
Schedule
Fan
Auto
System
Auto
Adaptive Intelligent Recovery™(Setup Function 13)
Adaptive Intelligent Recovery eliminates guesswork when setting your schedule. It
allows the thermostat to “learn” how long your furnace and air conditioner take to
reach the temperature you want.
Just set your program schedule to the time you want the house to reach your
desired temperature.The thermostat then turns on the heating or cooling at just the
right time to reach your scheduled temperature at your scheduled time.
For example:Set the Wake time to 6 am, and the temperature to 70°.The heat will
come on bef
ore 6 am, so the temperature is 70° by the time you wake at 6.
Built-in compressor protection (Setup Function 15)
AM
System
Cool
Setting
75
Cool On
Cool
This feature helps prevent damage to the
compressor in your air conditioning or heat
°
pump system.
Damage can occur if the compressor is restarted too soon after shutdown.This feature
forces the compressor to wait for a few
minutes before restarting.
During the wait time, the message Cool On
or Heat On (heat pumps only) will flash on
the display.When the safe wait time has
elapsed, the message stops flashing and the
compressor turns on.
10
Inside
°
75
Set Clock/Day/
Schedule
Message flashes until safe
restart time has elapsed
6:30
Fan
Auto
Inside
Heat
Setting
75
6:30
AM
75
WakeWed
Heat On
Fan
Auto
System
Heat
Set Clock/Day/
Schedule
°
°
Replace Battery
FocusPRO™TH6110D Programmable Thermostat
11
Quick reference to controls
Digital display screenBattery holder (see page 7)
Temperature buttons
Press to adjust temperature
settings
Hold button
Press to override programmed
temperature control
Function buttons
Press to select the function displayed just above each button.
(Functions change depending on the task.)
Quick reference to display screen
Current inside temperature Low battery warning Current time/day
Current program period
Wake/Leave/Return/Sleep
Temperature setting
System status
On when “calling” for
heating or cooling;
flashes when waiting for
compressor restart.
System setting
(Heat/Cool/Auto/Off)
Fan setting
(Auto/On)
Function buttons
Press the button beneath each function to view or change
settings. (Functions change depending on the task.)
Battery replacement
Press and pull to removeInsert fresh AA
alkaline batteries,
then reinstall
battery holder
Set Clock/Day/Schedule
Press to set time, day or
program schedules.
Installation Guide
In case of difficulty
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank • Check circuit breaker and reset if necessary.
• Make sure power switch at heating & cooling system is on.
• Make sure furnace door is closed securely.
• If thermostat is battery powered, make sure fresh AA alkaline batteries
are correctly installed (see page 7).
Temperature
settings do not
change
Heating system
does not respond
(“Heat On”
appears on
screen)
Cooling system
does not respond
(“Cool On”
appears on
screen)
Fan does not
turn on in a call
for heat
Make sure heating and cooling temperatures are set to acceptable ranges:
• Heat: 40° to 90°F (4.5° to 32°C).
• Cool: 50° to 99°F (10° to 37°C).
• Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
• Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the heating
equipment.
• Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
• Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling
equipment.
• Check Installer Setup, Function 3 (Fan Control), to make sure the fan
control is properly set to match the type of system (see page 8).
Heat pump
issues cool air
in heat mode,
or warm air in
cool mode
Heat/cool both
on at same time,
or heat does
not turn off
• Check Installer Setup, Function 2 (Changeover Valve), to make sure it is
properly configured for your system (see page 8).
• Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating/cooling equipment (see page 8).
• Check to make sure heating and cooling wires are not shorted together.
12
FocusPRO™TH6110D Programmable Thermostat
13
In case of difficulty
“Cool On” or
“Heat On”
is flashing
• Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
Heating equipment is running
in cool mode
• Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating/cooling equipment (see page 8).
Cannot change
system setting
to “Heat”
• Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating equipment (see page 8).
• Change Installer Setup, Function 12 (System Setting) to Manual
or Auto
Changeover (see page 8).
Cannot change
system setting
to “Cool”
• Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed cooling equipment (see page 8).
• Change Installer Setup, Function 12 (System Setting) to Manual
or Auto
Changeover (see page 8).
“Heat On” is
not displayed
• Change the System Setting to Heat
, and set the temperature level above
the current room temperature.
“Cool On” is not
displayed
• Change the System Setting to Cool, and set the temperature level below
the current room temperature.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Battery holder ......................................................Part Number 50007072-001
Cover plate assembly ........................................Part Number 50002883-001
(Use to cover marks left by old thermostats.)
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Shipping Temperature
• -20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 3-9/16” H x 5-13/16” W x 1-1/2” D
• 91 mm H x 147 mm W x 38 mm D
Electrical Ratings
TerminalVoltage (50/60Hz) Running Current
W (O/B) Heating20-30 Vac0.02-1.0 A
(Powerpile)750 mV DC100 mA DC
Y Cooling20-30 Vac0.02-1.0 A
G Fan20-30 Vac0.02-0.5 A
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley,MN 55422