Honeywell TH6000 Series Installation Guide

Installation Guide
FocusPRO® Wi-Fi TH6000 Series Programmable Thermostat
This manual covers the following models
• TH6320WF: For up to 3 Heat/2 Cool systems
System Types
• Gas, oil, or electric heat with air conditioning
• Warm air, hot water, high-efficiency furnaces, heat pumps, steam, gravity
• Heat only with fan
• Cool only
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions
Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502
® U.S. Registered Trademark. Patents pending.
Copyright © 2012 Honeywell International Inc.
All rights reserved.
69-2738EFS-03
Wallplate installation
1. Separate wallplate from thermostat.
2. Mount wallplate as shown below.
Insert reference card after wallplate is mounted (see instructions, below).
M29433
Drill 3/16" holes for drywall. Drill 7/32" holes for plaster.
MCR29434
Wall anchors
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
69-2738EFS—03 2
Wire hole
Mounting screws
Wallplate
MCR29435
WR
3
Wiring
Wiring guide — conventional systems
1H/1C System
(1 transformer)
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common W Heat relay G Fan relay
Heat-only System
Rc Power [1] R [R+Rc joined by jumper] C 24VAC common W Heat relay
1H/1C System
(2 transformers)
Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] Y Compressor contactor C 24VAC common [4] W Heat relay G Fan relay
Heat-only System with Fan
Rc Power [1] R [R+Rc joined by jumper] C 24VAC common W Heat relay G Fan relay
C
RcYWG RC
MCR29439
Rc
MCR29440
RcYWG RC
M2944
RcWG RC
MCR29444
Cool-only System
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common G Fan relay
2H/2C System
(1 transformer) [6]
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24VAC common W Heat relay (stage 1) G Fan relay W2 Heat relay (stage 2) Y2 Compressor contactor (stage 2)
2H/2C System
(2 transformers) [6]
Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] Y Compressor contactor (stage 1) C 24VAC common [4] W Heat relay (stage 1) G Fan relay W2 Heat relay (stage 2) Y2 Compressor contactor (stage 2)
See [notes] below
MCR29445
MCR29446
M29447
RcYG RC
RcYWGW2Y2 RC
RcYWGW2Y2 RC
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
[1] Power supply. Provide disconnect means and
overload protection as required.
[2] Remove jumper for 2-transformer systems. [4] Common connection must come from cooling
transformer.
[5] In Installer Setup, set system type to Heat Only.
[8] In Installer Setup, set system type to
2Heat/1Cool Heat Pump.
[9] In Installer Setup, set system type to
2Heat/2Cool Heat Pump.
[10] In Installer Setup, set system type to
3Heat/2Cool Heat Pump.
[6] In Installer Setup, set system type to
2Heat/2Cool Conventional.
[7] In Installer Setup, set changeover valve to O
or B.
3 69-2738EFS—03
GR
LR
LR
LR
LR
Wiring
Wiring guide — heat pump systems
1H/1C Heat Pump System
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common O/B Changeover valve [7] G Fan relay
2H/1C Heat Pump System
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay
2H/1C Heat Pump System
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay
2H/2C Heat
C
MCR29448
Rc Power [1]
C
MCR29451
RcYGY2
Pump System
RcY
R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24 VAC common O/B Changeover valve [7] G Fan relay Y2 Compressor contactor (stage 2)
E
MCR29449A
Pump System
Rc Power [1]
E
MCR29452
RcYGAux
CY2
3H/2C Heat
RcYGAux
C
R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24VAC common O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay Y2 Compressor contactor (stage 2)
E
MCR29450
RcYGAux
C
See [notes] below
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
[1] Power supply. Provide disconnect means and
overload protection as required.
[2] Remove jumper for 2-transformer systems. [4] Common connection must come from cooling
transformer.
[5] In Installer Setup, set system type to Heat Only. [6] In Installer Setup, set system type to
2Heat/2Cool Conventional.
69-2738EFS—03 4
[7] In Installer Setup, set changeover valve to O
or B.
[8] In Installer Setup, set system type to
2Heat/1Cool Heat Pump.
[9] In Installer Setup, set system type to
2Heat/2Cool Heat Pump.
[10] In Installer Setup, set system type to
3Heat/2Cool Heat Pump.
Wiring
W2
AUX/E
G W
G O/B
Y2
Y2
Terminal Designations
Conventional Terminal Letters:
Y2 2nd stage compressor contactor. W2 2nd stage heat relay. K Optional wirer save module. Rc Cooling power. Connect to secondary side
of cooling system transformer. R Heating power. Connect to secondary side
of heating system transformer.
W 1st stage heat relay. Y 1st stage compressor contactor. G Fan relay. C Common wire from secondary side of
cooling transformer (if 2 transformers).
C
YR RCK
C
YRRCK
CONVENTIONAL
HEAT PUMP
MCR33878
Heat Pump Terminal Letters:
Y2 2nd stage compressor contactor. Aux/E Auxiliary/Emergency heat relay. K Optional wirer save module. Rc Cooling power. Connect to secondary side
of cooling system transformer.
R Heating power. Connect to secondary side
of heating system transformer.
O/B Changeover valve for heat pumps. Y 1st stage compressor contactor. G Fan relay. C Common wire from secondary side of
cooling system transformer.
5 69-2738EFS—03
Installer setup
1 Press Fan and s simultaneously and hold for
approximately 3 seconds. The screen will change to display two numbers and the button designations will be Done, Back, blank, Next.
2 Press Next until you see the function number—the
larger number on the left—you want to set.
3 Change options for any function by pressing s or
t until the correct option (smaller number on right)
is displayed.
4 Repeat Steps 2 and 3 until you have set all
functions that you wish to change.
5 When you have made all changes, press Done to
save and exit.
Function Settings & Options
Select System
1
Type
Heat Pump
2
Changeover Valve (for heat pumps only)
Heating Fan
3
Control
Heating Cycle
5
Rate
Heating Cycle
6
Rate Stage 2
Heating Cycle Rate
7
Auxiliary
1st stage compres-
9
sor cycle rate
0 Heat/cool: Gas, oil or electric heating with central air conditioning. 1 Heat pump: Heat pump without backup or auxiliary heat. 2 Heat only: Gas, oil or hot water heat without central air conditioning. 3 Heat only with fan: Gas, oil or electric heat without central air
conditioning.
4 Cool only: Central air conditioning only. 5 Heat pump: Heat pump with backup or auxiliary heating. 6 Heat/Cool Multiple stages: 2 heat stages, 2 cooling stages. 7 Heat/Cool Multiple stages: 2 heat stages, 1 cooling stage. 8 Heat/Cool Multiple stages: 1 heat stage, 2 cooling stages. 9 Heat Pump Multiple Stages: 2 heat stages, 2 cool stages. 10 Heat Pump Multiple Stages: 3 heat stages, 2 cool stages.
0 Cooling changeover valve: Use this setting if you connected a wire
labeled “O” to the O/B terminal.
1 Heating changeover valve: Use this setting if you connected a wire
labeled “B” to the O/B terminal.
0 Gas or oil heat: Use this setting if you have a gas or oil heating system
(system controls fan operation).
1 Electric heat: Use this setting if you have an electric heating system
(thermostat controls fan operation).
5 Gas or oil furnace: Standard gas/oil furnace (less than 90% efficiency). 9 Electric furnace: Electric heating systems. 3 Hot water or high-efficiency furnace: Hot water system or gas furnace
(more than 90% efficiency).
1 Gas/oil steam or gravity system: Steam or gravity heat systems. [Other options: 2,4,6,7,8,10,11,12]
3 Recommended for most compressors [Other options: 1, 2, 4, 5 or 6 CPH]
HOLD
MCR33893A
HOLD
MCR33884
2nd stage com-
10
pressor cycle rate
69-2738EFS—03 6
System setup
Function Settings & Options
Manual/Auto
12
Changeover
Adaptive Intelligent
13
Recovery (AIR)
Temperature For-
14
mat (°F/°C)
Compressor
15
protection
Schedule Options
16
Auxiliary Control
26
Heat temperature
27
range stop
Cool temperature
28
range stop
Temperature
32
display offset
Device Name
36
This name will identify the thermostat when you view it remotely.
If you register multiple thermostats, give each one a different name.
Wi-Fi On/Off
38
Wi-Fi Connection
39
Show period and
42
day of week
Restore Schedule
85
Defaults
Restore Original
90
Settings
7 69-2738EFS—03
0 Manual changeover (Heat/Cool/Off). 1 Automatic changeover (Heat/Cool/Auto/Off). Automatically turns on Heat
or Cool based on room temperature. Note: System maintains minimum 3°F difference between heat and cool settings.
1 On 0 Off
0 Fahrenheit 1 Celsius
5 5 minute compressor off time [Other options: 0, 1, 2, 3 or 4-minute off time]
1 Program schedule is on (7-day programmable). 0 Program schedule is off. Thermostat can not be programmed.
0 Comfort 1 Economy
90 Max. heat temperature setting is 90°F (32°C) [Other options: 40-89°F (4°C to 32°C)]
50 Min. cool temperature setting is 50°F (10°C) [Other options: 51-99°F (11°C to 37°C)]
0 Thermostat displays actual room temperature [Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]
52 = Thermostat
1 Basement 16 Exercise Room 30 Library 44 Porch 2 Bathroom 17 Family Room 31 Living Room 45 Rec Room 3 Bathroom 1 18 Fireplace 32 Lower Level 46 Sewing Room 4 Bathroom 2 19 Foyer 33 Master Bath 47 Spa 5 Bathroom 3 20 Game Room 34 Master Bed 48 Storage Room 6 Bedroom 21 Garage 35 Media Room 49 Studio 7 Bedroom 1 22 Great Room 36 Music Room 50 Sun Room 8 Bedroom 2 23 Guest Room 37 Nursery 51 Theater 9 Bedroom 3 24 Gym 38 Office 52 Thermostat 10 Bedroom 4 25 Kid's Room 39 Office 1 53 Upper Level 11 Boat House 26 Kitchen 40 Office 2 54 Utility Room 12 Bonus Room 27 Kitchen 1 41 Pantry 55 Walk In Closet 13 Computer Room 28 Kitchen 2 42 Play Room 56 Wine Cellar 14 Den 29 Laundry Room 43 Pool Room 57 Workshop
15 Dining Room
1 Wi-Fi is on and can be connected to a Wi-Fi network. 0 Wi-Fi is off. Thermostat cannot be connected to a Wi-Fi network. If you
are not connecting the thermostat to a Wi-Fi network this will remove the text Wi-Fi Setup from the messaging center.
1 Connected to Wi-Fi network. This is set automatically when the
thermostat is connected to the Wi-Fi network.
0 Set to 0 to disconnect from the Wi-Fi network.
0 Period and day are not shown on the home screen. 1 Period and day are shown on the home screen.
0 Continue using programmed schedule. 1 Restore thermostat program to energy saving settings
0 No 1 Disconnects thermostat from Wi-Fi and restores original settings (erases
customizations).
Installer system test
Test number System status
To begin, press and hold the s and
t buttons until the display changes.
System test System status
10 Heating system 0 Heat and fan turn off.
20 Emergency heating
system
30 Cooling system 0 Compressor and fan turn off
40 Fan system 0 Fan turns off
CAUTION: Compressor protection is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
1 Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1,
5, 9 or 10 OR Setup Function 3 is set to 1 **See page 6 2 Stage 2 heat turns on 3 Stage 3 heat turns on
0 Heat and fan turn off 1 Heat and fan turn on
1 Compressor and fan turn on 2 Stage 2 compressor turns on
1 Fan turns on
Press s / t to turn system on/off. Press NEXT to advance to next test. Press DONE to terminate system test.
10
0
MCR29455
69-2738EFS—03 8
Troubleshooting
Lost Signal
If the no-Wi-Fi indicator displays in place of the Wi-Fi strength indicator in the upper right hand corner of the home screen:
• Check another device to be sure Wi-Fi is working in your home; if not, call your Internet Service Provider.
• Move the router.
• Restart the thermostat: remove it from the wallplate, wait 10 seconds, and snap it
back onto the wallplate. Return to Step 1 of Connecting to your Wi-Fi network.
Error Codes
For certain problems, the thermostat screen will display a code that identifies the trouble. Initially, error codes are displayed alone in the time area of the screen; after a few minutes, the home screen is displayed and the code alternates with the time.
Error Code Action
During Wi-Fi Setup, the router
E01
lost power.
• Ensureyourrouterhaspower.
• Iftryingtoconnecttoahiddenormanuallyaddednetwork,
confirm the router has power and is working.
Invalid Wi-Fi password. This
E02
code displays for 30 seconds, then the thermostat will re-enter Wi-Fi Setup mode.
Router is not issuing an IP ad-
E42
dress to the thermostat.
No internet connection. Thermo-
E43
stat cannot communicate to Total Connect Comfort.
General error Remove thermostat from wallplate for 10 seconds, then reconnect
E99
9 69-2738EFS—03
• Re-enterpasswordforyourhomeWi-Finetwork.
• Repeatsetupprocessandconfirmyourpasswordforyourhome
Wi-Fi network.
• Waitfor30minutes,
connection can take several minutes.
• Ifstillnoconnection,remove
thermostat from wallplate for 10 seconds, then reconnect it.
• Verifyyourrouteriscorrectly
setup to automatically give IP addresses.
• MakesuretheInternetcableispluggedin.
• Reboottherouter.
.
it
Troubleshooting
If you have difficulty with your thermostat, please try the following suggestions. Most problems can be corrected quickly and easily.
Display is blank
• Checkcircuitbreakerandresetifnecessary.
• Makesurepowerswitchatheatingandcoolingsystemison.
• Makesurefurnacedoorisclosedsecurely.
• MakesureCwireisconnected.
Fan does not turn on when heat is required
Cool On or Heat On is flashing
on the screen Heat pump
issues cool air in heat mode, or warm air in cool mode
Heating system is running in cool mode
Heating and cooling equipment are running at the same time
• CheckFunction 3: Heating Fan Control to make sure it is set to match the heating equipment.
• Compressorprotectionfeatureisengaged.Wait5minutesforthesystemto
restart safely, without damage to the compressor.
• CheckFunction 2: Heat Pump Changeover Valve to make sure it is properly configured for your system.
• CheckFunction 1: System Type to make sure it is set to match the heating and cooling equipment.
• CheckFunction 1: System Type to make sure it is set to match the heating and cooling equipment.
• Graspandpullthermostatawayfromwallplate.Checktomakesurebare
wires are not touching each other.
• Checkthermostatwiringiscorrect.
69-2738EFS—03 10
Special functions
Auto Changeover (Setup Function 12): When set to Auto, the thermostat automatically
selects heating or cooling depending on the indoor temperature. The thermostat will automatically adjust heat and cool settings to maintain a 3-degree separation (fixed). Note: If you select Auto Changeover Only, the System Setting on the thermostat will stay locked in the Auto position, preventing the user from changing it to Em Heat, Heat, Cool or Off.
Adaptive Intelligent Recovery™ (Setup Function 13): Allows the thermostat to “learn” how
long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes
before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate assembly* ................ Part Number 50002883-001
12 pack of medium cover plates* ........ Part Number 50007298-001
*Use to cover marks left by old thermostats.
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Shipping Temperature
• -20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 3-9/16" H x 5-13/16" W x 1-1/2" D 91 mm H x 147 mm W x 38 mm D
11 69-2738EFS—03
Electrical Ratings
Terminal Voltage (50/60Hz) Running Current
W Heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux/E) Heating 20-30 Vac 0.02-1.0 A Y Cooling 20-30 Vac 0.02-1.0 A Y2 Cooling 20-30 Vac 0.02-1.0 A G Fan 20-30 Vac 0.02-0.5 A
O/B Changeover 20-30 Vac 0.02-0.5 A
Loading...
+ 25 hidden pages