• Reversible mounting facilitates use in either clockwise
(cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
(See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac applications.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
APPLICATION
The MS4120F, MS4620F, MS8120F, S2024-F, and S20230-F
Fast-Acting, Two-Position Actuators are spring return direct
coupled actuators (DCA) for on/off damper control. The
actuator accepts an on/off signal from a single-pole, singlethrow (spst) controller. Reversible mounting allows actuator to
be used for either clockwise (cw) or counterclockwise (ccw)
spring rotation.
Designed to operate reliably in smoke control systems
requiring Underwriter’s Laboratories Inc. UL555S ratings up to
350°F.
Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m).
Spring Return (minimum at 350°F): 175 lb-in. (20 N•m).
Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m).
350°F Minimum Driving: 175 lb-in. (20 N•m).
Design Life (at Rated Voltage): 30,000 full stroke cycles.
Minimum Damper Shaft Length:
1 in. (25 mm); 3-1/4 (83 mm) recommended.
Cycling Requirements:
Prolonged holding-period (1 year) testing of these actuators
has been performed with no spring return failures. The
actuator and the internal spring are designed to require no
special cycling during long-term holding.
Honeywell recommends following all local, state and national
codes for periodic testing of the entire smoke control
system. Refer to National Fire Protection Association
(NFPA) National Fire Codes®: NFPA90A, NFPA92A and
NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper
performance.
Two integral 3/8 in. flexible conduit connections.
Mounting: Self-centering shaft adapter.
Round Damper Shafts: 0.5 to 1.06 in.
Square Damper Shafts: 1/2 to 3/4 in.
Actuator can be mounted with shaft in any position.
IMPORTANT
• Honeywell does not recommend using linkages with
these actuators because side-loading of the output
hub reduces actuator life.
• 3/4 in. or greater shaft diameter recommended.
Noise Rating at 1m (Maximum):
Driving or Spring Return: 70 dBA.
Holding: 20 dBA (no audible noise).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury
and short equipment circuitry.
Disconnect power supply before installation.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Low voltage can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.
Determine Appropriate Mounting Orientation
See Fig. 2 for mounting orientation.
NOTES:
—Actuators are shipped in the fully closed position.
—An arrow molded into the hub points to tick marks
on the label to indicate the hub rotary position.
—See Fig. 3 for proper mounting to a square damper
shaft.
CCW TO CLOSE
(FAIL-SAFE
POSITION)
CW TO OPEN
Fig. 2. Spring Return DCA mounting orientation.
CW TO CLOSE
(FAIL-SAFE
POSITION)
CCW TO OPEN
M20052
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Location
The actuators are designed to open a damper by driving the
damper shaft in either a clockwise or counterclockwise
direction. The actuator housing has two slots on the
bottom, either of which, with a 205649 Mounting Bracket,
secures it flush to a damper box (see Fig. 2).
NOTE: When mounted correctly, these slots allow the
actuator to float without rotating relative to the damper
shaft.
CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can
damage actuator.
Mount actuator to allow it to float along its vertical axis.
Preparation
Before mounting the actuator onto the damper shaft, determine
the:
— Damper/valve opening direction for correct spring return
rotation. The actuator can be mounted to provide clockwise
or counterclockwise spring return.
— Damper shaft size (see Specifications section).
M21007
Fig. 3. Proper mounting to square damper shaft.
DAMPER SHAFT
Measure Damper/Valve Shaft Length
If the shaft is less than three inches in length, the shaft
coupling must be located between the damper/valve and
actuator housing. If the shaft length is more than three inches,
the shaft coupling may be located on either side of the actuator
housing.
If the coupling must be moved from one side of the actuator to
the reverse, follow these instructions (see Fig. 4):
1. Remove the retainer clip from the shaft coupling and set
it aside for later use.
2. Remove shaft coupling from one side of the actuator.
3. Replace the shaft coupling on the opposite side of the
actuator aligning it based on the stroke labelling.
4. Replace the retainer clip on the shaft coupling using the
groove of the coupling.
63-2584—74