Honeywell MS8120S, MS4120S User Manual

MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F Fast-Acting, Two-Position Actuators

FEATURES

• 175 lb-in. (20 N•m) minimum driving torque at 350°F (176°C).
• Reversible mounting facilitates use in either clockwise (cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding. (See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac applications.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.

APPLICATION

The MS4120F, MS4620F, MS8120F, S2024-F, and S20230-F Fast-Acting, Two-Position Actuators are spring return direct coupled actuators (DCA) for on/off damper control. The actuator accepts an on/off signal from a single-pole, single­throw (spst) controller. Reversible mounting allows actuator to be used for either clockwise (cw) or counterclockwise (ccw) spring rotation.
Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350°F.
• Housing design allows flush mounting to damper.
• Self-centering shaft adapter (SCSA), patent pending.
• Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350°F.

MS4120F, MS4620F, MS8120F

• High temperature Teflon® lead wires.
• Models available with integral high temperature (350°F) SPST position-indicating switches (7°, 85° stroke).
PRODUCT DATA

APPLICABLE LITERATURE

— Specification Data Sheet 63-2592 — Motor/Actuator Selection Guide
for Damper Applications 63-8419
— Engineering Manual of Automatic Control
(also called The Gray Manual) 77-1100
— Direct Coupled Actuator
Quick Selection Guide 63-8553
— Damper Torque Calculator 63-8437

S2024-F, S20230-F, MS4620S, MS8120S

• Double-insulation rating.
• High-temperature, halogen-free, silicone-free leadwires.
• Models available with integral high temperature (350°F) SPDT position-indicating switches (7°, 85° stroke).
63-2584—7
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

SPECIFICATIONS

Models: See Tables 1, 2, and 3.
Table 1. Models.
Model
MS4120F1006 120 None
MS4120F1204 120
MS4620F1005 230 None
MS4620F1203 230
MS8120F1002 24 None
MS8120F1200 24
S2024-F (MS8120S1006) 24 None
S20230-F (MS4620S1009) 230
S2024-F-SW2 (MS8120S1204) 24
S20230-F-SW2 (MS4620S1207) 230
a
Internal switches are designed to pass UL555S requirements (at 350°F).
Dimensions: See Fig. 1.
Device Weight: 7 lb (3.2 kg).
Stroke: 95° ± 3°, mechanically limited.
Voltage
in Vac
Internal Auxiliary
2 SPST
2 SPST
2 SPST
2 SPDT
Switches
a
a
a
a
Timing (At Rated Torque and Voltage):
Drive Open: 15 seconds typical. Spring Close: 15 seconds typical.
Auxiliary Switches:
Ratings (maximum load): 250 Vac, 5A resistive, 3A inductive. Settings (fixed): 7° nominal stroke, 85° nominal stroke.
Torque Rating (at Rated Voltage):
Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m). Spring Return (minimum at 350°F): 175 lb-in. (20 N•m). Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m). 350°F Minimum Driving: 175 lb-in. (20 N•m).
Design Life (at Rated Voltage): 30,000 full stroke cycles.
Minimum Damper Shaft Length:
1 in. (25 mm); 3-1/4 (83 mm) recommended.
Cycling Requirements:
Prolonged holding-period (1 year) testing of these actuators
has been performed with no spring return failures. The actuator and the internal spring are designed to require no special cycling during long-term holding.
Honeywell recommends following all local, state and national
codes for periodic testing of the entire smoke control system. Refer to National Fire Protection Association (NFPA) National Fire Codes®: NFPA90A, NFPA92A and NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper performance.
Electrical Ratings:
Power Input:
MS4120F: 120 Vac ±10%, 60 Hz. MS4620F,S; S20230-F: 230 Vac ±10%, 50/60 Hz. MS8120F,S; S2024-F: 24 Vac +20%, -10%, 50/60 Hz
(Class 2).
Power Consumption:
MS4120F: Driving: 0.35A, 35W. Holding: 0.15A, 10W. MS4620F,S; S20230-F:
Driving: 0.20A, 35W. Holding: 0.14A, 10W.
MS8120F,S; S2024-F: Driving: 45 VA. Holding: 10 VA.
Electrical Connections:
Lead Wires:
MS4120F, MS4620F, MS8120F: 1m Teflon wire. MS4620S, MS8120S, S2024-F, S20230-F: 1m halogen-
free, silicone-free wire.
Two integral 3/8 in. flexible conduit connections.
Mounting: Self-centering shaft adapter.
Round Damper Shafts: 0.5 to 1.06 in. Square Damper Shafts: 1/2 to 3/4 in. Actuator can be mounted with shaft in any position.
IMPORTANT
• Honeywell does not recommend using linkages with these actuators because side-loading of the output hub reduces actuator life.
• 3/4 in. or greater shaft diameter recommended.
Noise Rating at 1m (Maximum):
Driving or Spring Return: 70 dBA. Holding: 20 dBA (no audible noise).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2584—7 2
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS
S
Temperature Ratings:
Ambient: -40°F to 130°F (-40°C to 55°C). Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
IMPORTANT
The actuator is designed to meet UL555S standards at 350°F (176°C). The actuator must be tested with the damper to achieve this rating.
NOTE: The actuator is designed to operate for 30 minutes
during a one-time excursion to 350°F (176°C).
Humidity Ratings: 5% to 95% RH noncondensing.
Environmental Protection Ratings:
NEMA2 and IP54 when mounted on a horizontal shaft.
Accessories:
205649 Mounting Bracket (not supplied with actuator).
Approvals: See Table 4.
Controller Type:
MS4120F: Line voltage (120 Vac), 2-position, spst (Series 40). MS4620F,S; S20230-F: Line voltage (230 Vac), 2-position, spst
(Series 40).
MS8120F,S; S2024-F: Low voltage (24 Vac), 2-position, spst
(Series 80).
Table 2. Actuator
election (MS Series).
M Electrical Motor
S Fail Safe Function (Spring Return)
41 120 Vac 2-position Control; Reversible Mount Spring Return
46 230 Vac 2-position Control; Reversible Mount Spring Return
81 24 Vac 2-position Control; Reversible Mount Spring Return
20 175 lb-in. (20 N•m)
F Fire and Smoke (US)
S Fire and Smoke (EU)
1 No Feedback
0 No Auxiliary Switches
2 Two Auxiliary Switches
XX System Controlled Numbers
MS 41 20 F 12 XX
Table 3. Actuator Selection (S20 Series).
S Fail Safe Function (Spring Return)
20 20 N•m (175 lb-in.)
24 24 Vac 2-position Control; Reversible Mount Spring Return
230 Vac 2-position Control; Reversible Mount Spring
230
Return
F Fire and Smoke Actuator
No Auxiliary Switches
-SW2 Two Auxiliary Switches
S2024-F -SW2
Table 4. Approvals.
S20230-F,
S2024-F,
MS4120F
MS4620F,
MS8120F
MS4620S,
MS8120S
UL/cUL X X
UL873 Plenum Rating,
XX
File No. E4436; Guide No. XAPX.
a
CE X X
C-TICK X X
a
Plenum applications require that conductors be enclosed in conduit (see Wiring section for conduit details).
3-15/16 (100)
2 (50)
1-9/16
(40)
8-5/8 (220)
10-11/16
(271)
M20051
2-15/16 (75)1/4 (6)
Fig. 1. Dimensional drawing of actuator in inches (mm).
3 63-2584—7
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment circuitry.
Disconnect power supply before installation.
CAUTION
Electrical Shock or Equipment Damage Hazard. Low voltage can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Determine Appropriate Mounting Orientation
See Fig. 2 for mounting orientation.
NOTES:
Actuators are shipped in the fully closed position. — An arrow molded into the hub points to tick marks
on the label to indicate the hub rotary position.
See Fig. 3 for proper mounting to a square damper
shaft.
CCW TO CLOSE (FAIL-SAFE POSITION)
CW TO OPEN
Fig. 2. Spring Return DCA mounting orientation.
CW TO CLOSE (FAIL-SAFE POSITION)
CCW TO OPEN
M20052
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.

Location

The actuators are designed to open a damper by driving the damper shaft in either a clockwise or counterclockwise
direction. The actuator housing has two slots on the
bottom, either of which, with a 205649 Mounting Bracket, secures it flush to a damper box (see Fig. 2).
NOTE: When mounted correctly, these slots allow the
actuator to float without rotating relative to the damper shaft.
CAUTION
Equipment Damage Hazard. Tightly securing actuator to damper housing can damage actuator.
Mount actuator to allow it to float along its vertical axis.

Preparation

Before mounting the actuator onto the damper shaft, determine the: — Damper/valve opening direction for correct spring return
rotation. The actuator can be mounted to provide clockwise or counterclockwise spring return.
— Damper shaft size (see Specifications section).
M21007
Fig. 3. Proper mounting to square damper shaft.
DAMPER SHAFT
Measure Damper/Valve Shaft Length
If the shaft is less than three inches in length, the shaft coupling must be located between the damper/valve and actuator housing. If the shaft length is more than three inches, the shaft coupling may be located on either side of the actuator housing.
If the coupling must be moved from one side of the actuator to the reverse, follow these instructions (see Fig. 4):
1. Remove the retainer clip from the shaft coupling and set
it aside for later use.
2. Remove shaft coupling from one side of the actuator.
3. Replace the shaft coupling on the opposite side of the
actuator aligning it based on the stroke labelling.
4. Replace the retainer clip on the shaft coupling using the
groove of the coupling.
63-2584—7 4