Honeywell MS4104, MS4109, MS4604, MS4609, MS8104 Data Sheet

...
63-2740-05
N314
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators
FOR FIRE/SMOKE CONTROL APPLICATIONS
PRODUCT DATA

FEATURES

• 30 lb-in. (3.4 N•m) or 80 lb-in. (9 N•m) minimum driving torque at 350°F (176°C).
• Reversible mounting facilitates use in either clockwise (cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding. (See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows flush mounting to damper.
The MS4104, MS4109, MS4604, MS4609, MS8104 and MS8109 Fast-Acting, Two-Position Actuators are spring return direct coupled actuators (DCA) for Fire and Smoke dampers (on/off control). The actuator accepts an on/off signal from a single-pole, single-throw (SPST) controller. Reversible mounting allows actuator to be used for either clockwise (cw) or counterclockwise (ccw) spring rotation.
• Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350°F.
• Models available with SPST position-indicating switches (7°, 85° stroke).
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Operation .......................................................................... 6
Checkout .......................................................................... 6
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

SPECIFICATIONS

Models: See Table 1.
Table 1. Models.
Model
(Vac)
MS4104F1010 120 None
MS4104F1210 120
MS4109F1010 120 None
MS4109F1210 120
MS4604F1010 230 None
MS4604F1210 230
MS4609F1010 230 None
MS4609F1210 230
MS8104F1010 24 None
MS8104F1210 24
MS8109F1010 24 None
MS8109F1210 24
Voltag e
a
Internal switches are designed to pass UL555S
requirements (at 350°F for 30 minutes) and are intended for use as position indication.
Dimensions: See Fig. 1.
Internal Auxiliary
Switches
2 SPST
2 SPST
2 SPST
2 SPST
2 SPST
2 SPST
a
a
a
a
a
a
Mounting: Round 1/2 inch shaft adapter with 1/4 inch set
screws. Threads: ¼-20 UNC-2A Material: Alloy Steel hardened to HRC 45-53 Thread Lock: Nylon Patch
IMPORTANT
Honeywell does not recommend using linkages with these actuators because side-loading of the output hub reduces actuator life.
Temperature Ratings:
Ambient: 0°F to 130°F (-18°C to 55°C). Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
IMPORTANT
The actuator is designed to meet UL555S standards at 350°F (176°C). The actuator must be tested with the damper to achieve this rating.
Humidity Ratings: 5% to 95% RH noncondensing.
Noise Rating (Maximum):
Driving Open: 75 dBA at 1m. Holding: 20 dBA at 1m (no audible noise).
Controller Type:
MS4104, MS4109: Line voltage (120 Vac),
two-position, SPST (Series 40).
MS4604, MS4609: Line voltage (230 Vac),
two-position, SPST (Series 40).
MS8104, MS8109: Low voltage (24 Vac),
two-position, SPST (Series 80).
Minimum Damper Shaft Length: 2 in. (51 mm).
Device Weight: 5 lb (2.3 kg).
Stroke: 95° ± 3°, mechanically limited.
Electrical Ratings: See Table 2.
Electrical Connections:
Power Lead Wires:
MS410xF and MS460xF: 32 inches (0.8m), 18 AWG
MS810xF: 39 inches (1m), 18 AWG
Switch Lead Wires: 18 inches, 18 AWG, 2 color coded leads
Table 2. MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 DCA Models.
Model
Power Consumption Torque
in lb-in.
(Nm)
Voltage
Input
in VacRunning Holding
MS4104F 0.18A, 18W 0.11A, 9W 30 (3.4) 120 ±10%,
MS4109F 0.25A, 23W 0.13A, 7W 80 (9)
50/60 Hz
MS4604F 0.13A, 18W 0.10A, 11W 30 (3.4) 230 ±10%,
MS4609F 0.13A, 23W 0.09A, 7W 80 (9)
50/60 Hz
MS8104F 16 VA 8 VA 30 (3.4) 24Vac/dc +20%,
MS8109F 23 VA 7 VA 80 (9)
-10%, 50/60 Hz
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2740—05 2
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS
Torque Rating (at rated voltage):
Spring Return:
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m). MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).
Stall Maximum:
MS4104F, MS4604F, MS8104F: 150 lb-in. (17 N•m). MS4109F, MS4609F, MS8109: 240 lb-in. (27 N•m).
350°F Driving:
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m). MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).
Timing (At Rated Torque and Voltage):
Drive Open: 15 seconds typical. Spring Close: 15 seconds typical.
Cycling Requirements:
The actuator and the internal spring are designed to require no
special cycling during long-term holding.
Honeywell recommends following all local, state and national
codes for periodic testing of the entire smoke control sys­tem. Refer to National Fire Protection Association (NFPA) National Fire Codes®: NFPA90A, NFPA92A and NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper perfor­mance.
Design Life (at Rated Voltage): 30,000 full stroke cycles.
Approvals: See Table 3.
90
2 (51)
1 (25)
11/16
°
2 (51)
4 (102)
(17)
°
0
6-3/8 (161)
8-15/16
(227)
1/16
(2)
9/16 (14)
3-1/4 (83)
Environmental Protection Ratings: See Table 4.
Accessories:
205649 Mounting Bracket (not supplied with actuator).
Table 3. Approvals.
MS4104F,
MS4109F
MS4604F,
MS4609F
MS8104F,
MS8109F
UL/cUL X X X
UL60730 X X X
CE X X X
C-Tick X X X
Table 4. Environmental Ratings.
MS4104, MS4109, MS4604,
MS4609, MS8104 and
All Devices
MS8109
NEMA1 IP40
5-1/8 (130)
M34622
Fig. 1. MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 dimensional drawing in in. (mm).
3 63-2740—05
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS
WARNING
CAUTION
CAUTION
M34623
ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.
ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH THE ACTUATOR.
1
1
2
90
°
2

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment circuitry.
Disconnect power supply before installation.
Electrical Shock or Equipment Damage Hazard. Low voltage can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Location and Mounting

The actuators are designed to open a damper by driving the damper shaft in either clockwise or counterclockwise
direction. The actuator housing has two slots on the bottom that, with a 205649 Mounting Bracket, secure it flush to a damper box (see Fig. 2). When mounted correctly, these slots allow the actuator to float without rotating relative to the damper shaft.
Fig. 2. Mounting actuator to damper housing.

Preparation

Before mounting the actuator onto the damper shaft, determine the:
— Damper/valve opening direction for correct spring
return rotation. The actuator can be mounted to provide clockwise or counterclockwise spring return.
— Damper shaft size (see Specifications section).
Equipment Damage Hazard. Tightly securing actuator to damper housing can damage actuator.
Mount actuator to allow it to float along its vertical axis.
63-2740—05 4
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS
CAUTION
CAUTION
WARNING
CAUTION
M34624
24 VAC
BLACK
RED
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
BLUE
WHITE
BLACK
GREEN
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
120 VAC
M34625
M34626
BLUE
BROWN
GREEN
230 VAC
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH

Installation

Device Malfunction Hazard. Improper set screw tightening causes device malfunction.
Ensure damper blade is in the correct position and tighten set screws with proper torque to prevent damper shaft slippage.
Actuator Damage Hazard. Using actuator as shaft bearing causes device damage.
Use actuator only to supply rotational torque. Avoid any side loads to actuator output coupling bearings.
To install actuator, proceed as follows:
1. Place actuator over damper shaft; and hold mounting bracket in place. See Fig. 2.
2. Mark screw holes on damper housing.
3. Remove actuator and mounting bracket.
4. Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).
5. Turn damper blades to desired normal (closed) position.
6. Place actuator and mounting bracket back into position
and secure bracket to damper box with sheet metal screws.
7. Tighten set screws securely into damper shaft using min­imum 100 lb-in., maximum 130 lb-in. torque. Use 1/4 in. wrench (see Specifications for details) to tighten set screws.
IMPORTANT
1. All wiring must comply with local electrical codes, ordinances and regulations.
2. Voltage and frequency of transformer must corre­spond with the characteristics of power supply and actuator.
3. Use wires rated for at least 75°C (167°F).
4. The conduit fittings are designed for use with 3/8 in. reduced-wall steel or aluminum flexible conduit.
Fig. 3. Typical 24 Vac wiring.

Wiring

See Fig. 3 through 5 for typical wiring diagrams.
Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment circuitry.
Disconnect power supply before installation.
Electrical Shock or Equipment Damage Hazard. Low voltage can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Fig. 4. Typical 120 Vac wiring.
Fig. 5. Typical 230 Vac wiring.
5 63-2740—05

OPERATION

CHECKOUT

The MS4104, MS4109, MS4604, MS4609, MS8104 and MS8109 DCA are designed for use in Smoke Control Systems. If power fails, the actuator spring returns to the 0° position. The actuator mounts flush with the damper box. The actuator drives from 0° to 95° and spring returns back to 0°.
The actuators are operated by an spst two-position controller. When using an spst two-position controller, the actuator drives to the damper fully open position when controller contact makes and spring returns to the damper fully closed position when controller contact breaks. The actuator drops to holding power level on detection of stall, independent of hub position.

Cycling

The actuator and the internal spring are designed so that no special cycling during long-term holding is required. Honeywell recommends following all local, state, and national codes for periodic testing of the entire smoke control system. Refer to National Fire Protection Association (NFPA) National Fire
®
Codes application.
NOTE: The actuator is designed to operate for 30 min-
: NFPA90A, NFPA92A, and NFPA92B for your
utes during a one-time excursion to 350°F (176°C).

MS4104F, MS4109F (120 Vac model)

1. Check damper position.
2. Connect 120 Vac to the black and white leadwires to
drive the damper to the open position. The actuator should drive the damper.
3. If the actuator does not spring return, verify that the actu­ator is properly installed. See Installation section.
4. If the actuator is correctly installed but neither runs nor spring returns, replace the actuator.

MS4604F, MS4609F (230 Vac model)

1. Check damper position.
2. Connect 230 Vac to the blue and brown leadwires to
drive the damper to the open position. The actuator should drive the damper.
3. If the actuator does not spring return, verify that the actu­ator is properly installed. See Installation section.
4. If the actuator is correctly installed but neither runs nor spring returns, replace the actuator.

MS8104F, MS8109F (24 Vac model)

1. Check damper position.
2. Connect 24 Vac to the red and black leadwires to drive
the damper to the open position. The actuator should drive the damper.
3. If the actuator does not spring return, verify that the actu­ator is properly installed. See Installation section.
4. If the actuator is correctly installed but neither runs nor spring returns, replace the actuator.
National Fire Codes® is a registered trademark of the National Fire Protection Association (NFPA).
63-2740—05 6
7 63-2740—05
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark © 2013 Honeywell International Inc. 63-2740—05 M.S. Rev. 12-13 Printed in United States
Loading...