Honeywell LYNXR-2 User Manual

LYNXR-2 Series
Security Systems
K15011 7/08 Rev. A
AUX
SELECT
STAY
DELETE
ESCAPE
AWAY
ADD
OFF
LIGHTS ON
LIGHTS OFF
STATUS
1
2
VOLUME
RECORD
45
TEST
7
8
CODE
0
NO DELAY
FUNCTION
ARMED
BYPASS
9
CHIME
READY
3
PLAY
6
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors recommended.
For additional protection the NFPA recommends that you install heat dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps.
Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.
Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used.
Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
DINING
in kitchens, attics (finished or unfinished), or in garages is not normally
or smoke detectors in the living room,
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
BEDROOMBEDROOM
TV ROOM
KITCHEN
DINING
LIVING ROOM
BEDROOM
BEDROOM
BEDROOMBEDROOM
KTCHN
BEDROOM
CLOSED
.
DOOR
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
GARAGE
01000-002-V0
LIVING ROOM
BEDROOM
LIVING ROOM
TO
BEDROOM
BASEMENT
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).
- 2 -
Table of Contents
SYSTEM FEATURES ..................................................................................................................................5
MOUNTING THE CONTROL.....................................................................................................................6
WIRING CONNECTIONS...........................................................................................................................7
CONNECTING/CONFIGURING COMMUNICATIONS DEVICES ........................................................9
AC POWER AND BACKUP BATTERY....................................................................................................12
INSTALLING WIRELESS ZONES...........................................................................................................14
MECHANICS OF PROGRAMMING ........................................................................................................17
ZONE RESPONSE TYPE DEFINITIONS ...............................................................................................19
DATA FIELD DESCRIPTIONS ................................................................................................................21
56 ENHANCED ZONE PROGRAMMING MODE ................................................................................37
80 DEVICE PROGRAMMING MENU MODE ......................................................................................41
81 ZONE LIST MENU MODE................................................................................................................45
83 ENHANCED SEQUENTIAL MODE ................................................................................................47
84 ASSIGN ZONE VOICE DESCRIPTORS ..........................................................................................50
85 RECORD CUSTOM VOICE DESCRIPTORS...................................................................................52
REMOTE PROGRAMMING/CONTROL (DOWNLOADING) ................................................................53
SYSTEM OPERATION ..............................................................................................................................55
KEYPAD FUNCTION SUMMARY ...........................................................................................................60
TESTING THE SYSTEM ..........................................................................................................................61
SYSTEM COMMUNICATION..................................................................................................................62
TROUBLESHOOTING GUIDE ................................................................................................................65
PROGRAMMING DEFAULT TABLES....................................................................................................68
LYNXR-2 CONTROL DEFAULTS .....................................................................................................68
LYNXR-2SIA CONTROL DEFAULTS...............................................................................................70
REGULATORY AGENCY STATEMENTS ..............................................................................................74
LIMITATIONS OF THIS SYSTEM STATEMENT..................................................................................75
UL NOTICES..............................................................................................................................................76
SIA QUICK REFERENCE GUDE ............................................................................................................76
CONTACTING TECHNICAL SUPPORT.................................................................................................77
INDEX.........................................................................................................................................................83
SPECIFICATIONS.....................................................................................................................................86
SUMMARY OF CONNECTIONS DIAGRAM ..........................................................................................87
-3-
- 4 -
LYNXR-2 Series Installation and Setup Guide
System Features
LYNXR-2 Series is not intended for UL985 Household Fire applications unless a 24-hour backup battery
UL
UL
ULUL
The LYNXR-2 Series control is a self-contained, rechargeable wireless control/communicator that features easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each zone. An internal module (if provided) allows the LYNXR-2 Series to communicate with the Central Station via the Internet. The following illustration highlights the main features of this system.
Up to 24 wireless zones (5800 Series transmitters)
Up to 16 wireless button zones
Up to 8 powerline carrier devices
Supports wireless keypads
8 USER CODES
Installer code
Master code
5 Secondary codes
Duress code
3 Panic functions
(P/N LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed. Powerline Carrier Devices have not been evaluated by UL.
ZONES and DEVICES
Real-time clock display and Fixed-Word display
Message center (for user recorded messages)
Voice announcement of system and zone status
Voice chime
Alarm clock
Reminder
X10 sched uling
Latch key reports
Automatic stay arming
Remote phone control
“Follow me” reminder and system Announcements
FEATURES
SYSTEM POWER
Primary Power: Ademco K10145X10 plug-in transformer, 110VAC to 9VAC, 25VA output (K10145CN in Canada)
Backup battery: Rechargeable nickel-metal hydride battery pack rated at 7.7Vdc.
COMMUNICATION
Ademco Low Speed
Sescoa/Radionics
Ademco Express
Ademco Contact ID
Paging feature
Internet central station
communication
GSM cellular central station communication
PROGRAMMING
Options stored in EEROM
Can be uploaded, downloaded or
controlled via IBM-compatible computer using Compass downloader software and specified HAYES modem or via capable GSM or IP communications module
Voice prompt programming mode
ARMED
READY
OFF
1
2
3
PLAY
VOLUME
6
TEST
BYPASS
8
9
CODE
CHIME
0
FUNCTION
AUX
SELECT
STAY
DELETE
ESCAPE
AWAY
ADD
RECORD
45
LIGHTS ON
7
LIGHTS OFF
STATUS
NO DELAY
OTHER FEATURES
Exit error feature (detects difference between an actual alarm and exit alarm caused by leaving a door open after the exit delay expires)
Event log stores up to 84 events
Macro/ 1-button paging
RF jam detection
Remote phone control
Compatible with encrypted (high-security) devices
ALARM OUTPUT
Built-in sounder
Piezo output
(30mA max.)
Bell output (120mA max.)
Steady output for burglary/panic
Temporal pulse output for fire alarms
Long range radio/audio alarm verification
SPECIAL FEATURES
Two-way voice communication
Speaker phone operation
Supports AlarmNet remote
services
- 5 -
LYNXR-2 Series Installation and Setup Guide
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the front assembly board.
!
1. Release the front assembly from the back plate by depressing the two locking tabs at the top of the unit with the blade of a medium size screwdriver.
2. Once these tabs have been released, insert the screwdriver in the side of the case and release the side locking tabs by gently twisting.
3. Carefully disconnect the ribbon cable from the front assembly, leaving the ribbon
cable connected to the terminal block PC board. The back plate contains the
terminal block for making wiring connections.
LOCKING
TABS
4. Mount the back plate to a sturdy wall, feeding the field wiring through the appropriate openings in the back plate.
5. After wiring connections are made, carefully reconnect the ribbon cable to
DISCONNECT
THIS END ONLY!
the front assembly PC board connector (properly aligning the red wire).
6. Snap the front assembly to the back plate so it is secured by the locking tabs.
Desktop Mounting
For desktop use the optional mounting base (model LYNX-DM, purchased separately) must be used.
1. Slide the control panel onto the mounting base locking tabs.
2. Bring all wiring through the bottom of the mounting base, using one of the three wire entry locations, before making connections to the control panel.
3. Use tie-wraps to secure the wiring to the built-in wire loops as needed. Use the two supplied screws to secure the control panel to the mounting base.
ESCAPE
AWAY
ADD
STAY
DELETE
AUX
STATUS
SELECT
OFF
LIGHTSOFF
LIGHTSON
7
1
VOLUME
RECORD
4
5
TEST
8
CODE
0
NODELAY
FUNCTION
LOCKING TABS
RED WIRE MARKING
ARMED
READY
2
3
PLAY
6
BYPASS
9
CHIME
LOCKING
TABS
09012-002-V0
WIRE ENTRY
KNOCKOUT
(1 of 3)
09015-002-V0
- 6 -
LYNXR-2 Series Installation and Setup Guide
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on the inside back cover when making connections.
UL
UL
ULUL
External sounders have not been evaluated by UL.
TERMINAL
STRIP
TELEPHONE
CONNECTIONS
COMMUNICATIONS
LRR/IP
PORT
GSML/GSMVL
COMMUNICATIONS
PORT
HIGH-CAPACITY
BATTERY CONNECTOR
STANDARD
SUPER HIGH-CAPACITY
BATTERY CONNECTOR
LOCAL
SOUNDER
DISABLE
09012-009-V0
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth grounds available at most installations:
Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically connected and secured to which the ground lead is electrically connected and secured.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
2. Make Phone Line Connections - For local or full line seizure follow the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the 8-position jack or terminals 2 (TIP) and 3 (RING) on the Lynx.
b. Connect the handset phone lines to either the RJ11 jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line usage by the premises phones if the plug needs to be removed.
c. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X
terminals 4 (red) and 5 (green).
d. Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.
e. Wire the flying leads of a Direct Connect Cord to the control’s phone terminals as shown in the diagram or plug into
the 8-position jack.
f. Plug the Direct Connect Cord into the RJ31X jack.
- 7 -
LYNXR-2 Series Installation and Setup Guide
Wiring Connections
45
GREY
3
2 1
RJ31X
OR
OR
6
7
8
DIRECT CONNECT CORD
INCOMING
PHONE LINE
RING TIP
GREENRED
TO
PREMISES PHONES
RING TIP
BROWN
RED
GREEN
TIP RING TIP RING
}
INCOMING
PHONE LINE
BROWN
}
TO
PREMISES
PHONES
GREY
8-POSITION
JACK
01000-008-V0
Full Line Seizure Connections
UL
UL
ULUL
3. Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
4. Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
5. Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
Do not remove the local sounder shorting jumper (shunt). External sounders and powerline carrier devices have not been evaluated by UL
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding will occur upon AC loss, since the external sounder does not operate when AC power is lost.
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX). a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
a. Remove the shorting jumper (shunt) on the terminal board.
these devices, they must be connected to the K10145X10 transformer, as shown in the SUMMARY OF CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the transformer to terminals 9, 13, and 14, respectively.
If not using the supplied connection cable, you may need to reverse the black and yellow wire connections. Refer to the ✻✻✻80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.
- 8 -
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
General
This LYNXR-2 Series supports central station reporting via the internet using wireless (GSM) and hardwire (IP) communications modules. It also supports upload/download programming capability via the Internet or a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN. Refer to the instructions provided with the LRR/IP Communications Device being installed for additional information regarding its installation, programming, and registration.
LYNXR-2 Series does not support the 7845i-ENT remote access feature.
Connecting Long Range Radio and Internet Communication Devices
Connect and configure the communications device as follows (refer to the Installation Instructions for device that you are installing for additional information):
The wire run between the LYNXR-2 Series and the Communications Device must not exceed ten (10) feet.
UL
UL
ULUL
The 7845i-ENT has been evaluated by UL for Household Burglary installations but has not been evaluated
for Household Fire installations.
AlarmNet 7847i-L* Communications Device
1. Install the module into the LYNXR-2 Series back plate and secure it with the two provided screws. Refer to the diagrams that follow.
2. Connect the provided ribbon cable between the module and the PC board. This cable provides DC power and ground for the module and data in/data out connections.
3. Connect the device to the Internet via a cable/DSL modem and router or to an Intranet (LAN) via the appropriate Ethernet connection.
* When available. The 7847i-L module has not been evaluated by UL.
CABLE
7720P PROGRAMER CONNECTION
SCREW (2)
RJ45 (FOR INTERNET CONNECTION)
LRR / IP
COMMUNICATION
PORT
09012-008-V1
Installing the 7847i-L Communications Module
- 9 -
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
AlarmNet 7845GSM, 7845i-GSM*, 7845i-ENT, 7845i or 7847i-E* Communications Device
The 7845i-ENT and 7845i cannot be used for installations requiring 24-hour standby.
!
1. Connect the 4-wire communications cable to the LRR/IP Communications port on the LYNXR-2 Series.
2. Connect the four wires to the specific Communications device as shown in the accompanying figures.
3. If you are installing a 7845GSM or 7845i-GSM you must also install a jumper between terminals 2 and 3 on the communications device.
4. Connect the device to the Internet via a cable/DSL modem and router or to an Intranet (LAN) via the appropriate Ethernet connection, if applicable.
UL
UL
ULUL
AlarmNet 7845GSM and 7845i-GSM modules have not been evaluated by UL.
* When available
7845GSM / 7845i-GSM
ECP (+) VOLTAGE INPUT
Z1/Z2 OR DATA IN
Z3 OR DATA OUT
GND
TB1
1
2
4
3
4
5
5
6
CONTROL PANEL
RED
BLK
YEL
GRN
GRN
BLK
RED
YEL
4-WIRE CABLE (N4632-4)
LRR/IP COMMUNICATIONS PORT
DATA IN
GND
+12 VDC
NC
DATA OUT
REQUIRED FOR
24-HR BACKUP
Connecting AlarmNet 7845GSM / 7845i-GSM
LYNX
STANDARD
CAPACITY
BATTERY
(OPTIONAL)
LYNX
SUPER HIGH
CAPACITY
BATTERY
09012-018-V0
7845i-ENT / 7845i
(+) VOLTAGE INPUT
GND
DATA OUT
DATA IN
TB 1
CONTROL PANEL
RED
BLK
GRN
YEL
GRN
BLK
RED
YEL
4-WIRE CABLE (N4632-4)
LRR/IP COMMUNICATIONS PORT
DATA IN
GND
+12 VDC
NC
DATA OUT
Connecting AlarmNet 7845i-ENT/7845i/7847i-E*
- 10 -
LYNX
STANDARD
CAPACITY
BATTERY
09012-019-V0
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
AlarmNet GSML/GSMVL Communications Device
1. Install the module into the control back plate and secure it with the three provided screws.
2. Connect the antenna to the GSML/GSMVL module.
3. Insert the antenna into the retaining slots in the control back plate.
4. Use double-stick tape to secure antenna to the control back plate.
5. Connect the provided communications cable between the GSML/GSMVL module and the control’s PC board. This cable provides DC power and ground for the module and data in/data out connections.
6. If using the GSMVL, connect the provided shielded audio cable between the GSMVL module and the control’s PC board.
SCREW (3)
COMMUNICATIONS
AUDIO CABLE
(GSMVL ONLY)
ANTENNA
GSML/GSMVL
CABLE
09012-017-V1
Installing the GSML/GSMVL Communications Module
LRR/IP Communications Device 24-Hour Standby Power
If you are installing the AlarmNet 7845GSM/7845i-GSM or 7847i-L, and require 24-hour standby, you must install the Super High Capacity battery P/N WALYNX-RCHB-SHA in the control.
The 7845i-ENT and 7845i can not be used for installations requiring 24-hour standby.
!
Configuring Long Range Radio and Internet Communication Devices
1. Enable the communications device in programming field *55 and configure alarm reporting and module supervision in programming field *77.
2. Program the device as required using the 7720P programmer (refer to the Installation Instruction for the device that you are installing for additional information). Note that the device address must be set to 3.
The device must be registered before downloading or alarm reporting can take place.
- 11 -
LYNXR-2 Series Installation and Setup Guide
AC Power and Backup Battery
The system is powered by a 9VAC, 25VA Plug-in Transformer, ADEMCO K10145X10 (K10145CN in Canada). Refer to the wiring table below for wire gauge and length.
Distance from Transformer to Control
Wire Gauge
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Use only the provided ADEMCO K10145X10 or K10145CN Transformer. Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery
In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a “low battery” message is displayed and a report is sent to the central station. In addition, the system will beep once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the K10145X10 (K10145CN) in Canada) AC Transformer to terminals 15 and 16 as shown in the wiring diagram.
2. Remove battery retainer.
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
6. Connect battery connector to receptacle on terminal block PC board.
7. After all wiring connections have been made, snap the front assembly to the back plate and plug the transformer into a 24-hour, 110VAC unswitched outlet.
Note: Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should clear within four hours or by entering Test Mode.
BATTERY
PACK
RETAINER
TAPE
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
Ensure the cover is snapped closed prior to applying AC power.
- 12 -
BATTERY
RECEPTACLE
WIRING
TERMINALS
09012-003-V0
LYNXR-2 Series Installation and Setup Guide
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR-2 Series is equipped with an integral, replaceable, rechargeable battery pack rated at 7.7Vdc.
Select the appropriate battery pack, based on the installations requirement, and install the battery pack.
Model/Part Number Battery StandbyTime
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion
LYNXRCHKIT-HC 24-hours (minimum) At least 1-hour before battery depletion
LYNXRCHKIT-SHA 24-hours (minimum) At least 1-hour before battery depletion
Replacing the Rechargeable Battery
1. When battery replacement is required, unplug the transformer from the wall outlet, and open the control panel cover.
2. Remove the battery retainer and disconnect the battery pack connector from the receptacle on the terminal block PC board.
3. Remove the battery pack from the back plate.
4. If required, replace the tape that secures the battery pack.
5. Install a replacement battery pack (P/N LYNXRCHKIT-SC, LYNXRCHKIT-HC or LYNXRCHKIT-SHA) into the back plate.
6. Install the battery retainer.
7. Connect the battery connector to the receptacle on the terminal block PC board.
8. After the wiring connection has been made, snap the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC unswitched outlet.
10. Rechargeable batteries may take up to 48­hours to fully charge. The “LOW BAT” message should clear within four hours or by entering Test Mode.
Low Battery Notification
RETAINER
BATTERY
PACK
BATTERY
CONNECTOR
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
BATTERY CONNECTOR
BATTERY
RECEPTACLE
RETAINER
BATTERY
PACK
LYNXRCHKIT-SHA
TAPE
TAPE
BATTERY
RECEPTACLE
Ensure the control panel assembly is snapped closed prior to applying AC power.
- 13 -
09012-004-V1
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the system using the 56 or 83 interactive mode, or input to the control via the downloader. 5800 Series transmitters (except the 5800RL, which is described separately) do not have DIP switches. Each transmitter's zone number is programmed into the system in 56 mode. Some transmitters, such as the 5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number.
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring and the loop wiring must
UL
UL
ULUL
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input number, which is automatically displayed.
House Identification If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House ID Code (01–31) in field 24 to establish proper communication, and the keypad must be set to the same ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800 Series transmitters; the entry should be left at “00” (default) in those cases.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV, and 5804E), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the "missing" transmitter number(s) and "FAULT" will be displayed. The supervision for a particular transmitter in the system that may also be carried off the premises (5801, 5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type, as described in the 56 Enhanced Zone Programming Mode section. 5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition if covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes. Each of the inputs requires a programming zone be entered as one of the following types
"RF" (Supervised RF)
"UR" (Unsupervised RF)
"BR" (Unsupervised Button RF)
Transmitter Battery Life
Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system.
not exceed 3 feet. The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5814, 5816TEMP, 5819, 5819S(WHS &
BRS), 5828/5828V and 5850(GBD) transmitters have not been evaluated by UL.
(e.g., a 5804's four inputs require four button zones). Transmitters can
(see transmitters instructions for appropriate input type):
Type Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The transmitter must remain within the receiver's range.
Sends all the signals that the "RF" type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises.
These only send fault signals. They do not send low battery signals until they are activated. The transmitter may be carried off-premises.
- 14 -
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, and 5804E button transmitters have replaceable batteries.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all transmitters have been properly programmed.
1. Enter Installer code (4112) + [#] + 3.
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer
mode. If so, wait a few minutes and try again.
2. The keypad will display all zone numbers, which have a non-zero Zone Type (even if serial numbers were not learned yet). Fault each transmitter in turn, causing each one to send a signal. As the system receives a signal from each of the transmitters, the zone number of that transmitter will disappear from the display. The transmitters may be checked upon installation, or in an installed system.
3. When all transmitters have been checked, exit Sniffer mode. Enter Installer Code (4112) + OFF.
Notes: (1) Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer
(2) All BR-type units must physically be activated to clear the display, since they do not automatically send
(3) When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that
(4) Any transmitter that is not “entered” will not turn off its zone number. (5) For SIA installations, the following devices may be used as specified for panic (24-hour) alarm response:
mode to return to normal operation.
check-in signals.
transmitter are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
wireless keys which have two-button panic pairs available (e.g., 5804BDV), on which only the two-button panic pairs may be programmed for any 24-hour alarm response
wireless keypads (e.g., 5828/5828V) keypads that have a two-second delay on the special function keys, or two-button panic pairs
built-in keypad’s two-button panic pairs
Go/No Go Test Mode
5804E encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode. Refer to the transmitter’s installation instructions for complete details. The system will confirm enrollment of the encrypted device by beeping two times.
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter.
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results. On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, press-
ing a button will take the system out of the Go/No Go Test mode causing the programmed action to occur.
Note: On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a
button will take the system out of the Go/No Go Test mode and cause the programmed action to occur.
a. The keypad will beep three times indicating signal reception and will display the appropriate zone
number.
b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a few
inches in either direction is all that is required.
3. If each transmitter produces the proper keypad response when it is faulted, you can then permanently mount each of the transmitters according to the instructions provided with them.
4. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
- 15 -
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
5800 Series Transmitter Loop Numbers
(Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.
5801
5809
5819
"RF"
"RF"
LOOP 3
LOOP 2 LOOP 1
LOOP 1
(TERMINALS)
LOOP 1
5802MN
ENROLL AS
"UR" OR "RF"
LOOP 1
5814
ENROLL
AS
"RF"
LOOP 2
(REED)
LOOP 3
LOOP 1
(INTERNAL
SHOCK
SENSOR
5819S (WHS & BRS)
ENROLL AS
"RF"
LOOP
5800CO
ENROLL AS "RF"
LOOP
1
5802MN2
ENROLL AS
"UR" OR "RF"
LOOP 2 (REED)
LOOP 1 (TERMINALS)
5816
ENROLL AS
"RF"
1
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
ALTERNATE
FOR LOOP 2
POSITION
5800Micra
ENROLL AS "RF"
O
N
O
F
F
5804/5804E
ENROLL AS "BR"
LOOP 2 (REED)
LOOP 1 (TERMINALS)
5816MN
ENROLL AS
"RF"
LOOP 3
LOOP 2
LOOP 1
5800RL
SET
HOUSE ID
LOOP 2
LOOP
3
5804BD/5804BDV
ENROLL AS
5816TEMP
ENROLL AS
"BR"
LOOP 1 (TEMP SENSOR)
"RF"
PROGRAM HOUSE ID
LOOP 4 YOU MUST ENROLL THIS BUTTON
LOOP 1
5800SS1
ENROLL AS "RF"
ON
OFF
1
2
3
4
5805-6
ENROLL AS
5817
ENROLL AS
"RF"
"BR"
LOOP 1 (PRIMARY)
LOOP 2 (AUX. CENTER)
LOOP 3 (AUX. RIGHT)
5800WAVE
PROGRAM
HOUSE ID
5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
"RF"
LOOP 1
5818
ENROLL AS
"RF"
YOU MUST
LOOP 1
(TERMINALS)
(TERMINALS)
LOOP 4
ENROLL
THIS
BUTTON
LOOP 2
(REED)
LOOP 3
LOOP 1
ENROLL AS "UR OR"RF"
ENROLL AS
ENROLL AS
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
AWAY
1
3
5878
ENROLL AS
STAY
4
2
SERIAL #1 LOOP 2
SERIAL #1 LOOP 1
SERIAL #2 LOOP 2
"BR"
5800-002-V0
5820/5820L
ENROLL AS
5890/5890PI
ENROLL AS
"RF"
LOOP 1 (MOTION)
"RF"
5821
ENROLL AS
"RF"
5894PI
ENROLL AS
ARMED
READY
5828/5828V
PROGRAM
HOUSE ID
"RF"
MIC
MESSAGE
LOOP 1
(SOUND)
(Green)
(Red)
(Yellow)
5849
ENROLL AS
5897
ENROLL AS
"RF"
"RF"
5850 (GBD)
ENROLL AS
"RF"
5853
ENROLL AS
"RF"
Notes: (1) Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV and 5804E transmitters, whether or not the
loop is used.
(2) 5804E encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode. Refer
to the transmitter’s installation instructions for complete details. The system will confirm enrollment of the encrypted device by beeping two times.
(3) The 5806 smoke detector must be used in SIA applications.
UL
UL
ULUL
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), 5828/5828V and 5850(GBD) wireless transmitters
have not been evaluated by UL.
- 16 -
LYNXR-2 Series Installation and Setup Guide
Mechanics of Programming
General Programming Information
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The system can be programmed at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired. There are four programming modes:
Data field programming (used for setting various system options).
Interactive menu mode programming (used for programming zone information, programming
Powerline Carrier Devices, and for entering transmitter serial numbers).
Voice Prompt programming (used for setting various system options).
Pass-Thru programming (used for programming connected LRR/IP Communications Device).
The system can also be programmed remotely, using an IBM Personal Computer, and Compass Downloader and modem or via capable GSM or IP communications modules. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to
clearly hear the feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the default value (mid level).
Entering Program Mode
Use one of the following methods to enter Programming Mode:
1. Press both the [] and [#] keys at the same time, within 50 seconds after power is applied to the Control or from exiting Programming mode, OR
2. After power-up, enter the Installer Code (4112) + 800 to enter Expert Programming mode (This method disabled if Program mode is exited using ✻98). OR enter Installer Code (4112) + 888 to enter Voice Prompt Programming mode.
If a different Installer Code has been programmed, use that code to enter the Programming mode.
3. Upon entering programming mode, the control will display “--” for up to two seconds indicating it is communicating with the LRR/IP devices.
4. Once you have entered the Program mode, data field “20” (the first data field in the system) will be displayed and both keypad LEDs will flash. If you have entered the Voice Prompt Programming mode. Pro will be displayed.
Programming a Data Field
1. Press [] + Field No. (for example, 21), followed by the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then automatically display the next data field in sequence. To go to a different field, press [] plus the desired field number.
3. If the number of digits that will be entered in a data field is less than the maximum number of digits available (e.g. phone number field), enter the desired data, then press [] to advance to the next data field.
4. If a nonexistent field has been entered, the keypad will display “EE”. Simply re-enter [] plus a valid field number.
To view a data field without making changes: To delete an entry in a field:
Enter [✻] + Field No. + [✻]. (Applies only to fields 40–✻44, 88 and 94).
Enter [#] + Field No. Data will be displayed for that field.
- 17 -
LYNXR-2 Series Installation and Setup Guide
Mechanics of Programming
Interactive Menu Mode Programming (56, 80, 81, 83, 84, 85)
[] + interactive mode No. (i.e., ✻56). The keypad will display the first of a series of prompts. A detailed
Press procedure (with displays of prompts) is provided in later sections of this manual.
56 Enhanced Zone Programming Mode
Interactive menu mode used for programming zone attributes and report codes. Refer to the ✻56
Enhanced Zone Programming Mode section for procedure.
80 Device Programming Menu Mode
Interactive menu mode for programming Powerline Carrier Devices. Refer to the ✻80 Device
Programming Menu Mode section for detailed procedure.
81 Zone Lists Menu Mode
Interactive menu mode for programming zone lists for Powerline Carrier Devices. Refer to the ✻81
Zone List Menu Mode section for detailed procedure.
83 Enhanced Sequential Mode
Interactive menu mode used to enter RF transmitter serial numbers. Refer to the ✻83 Enhanced
Sequential Mode section for detailed procedure.
84 Assign Zone Voice Descriptors
Interactive menu mode used to assign descriptors to each zone. These descriptors will be announced
whenever the system announces an event involving a zone.
85 Record Custom Voice Descriptors
Interactive menu mode used to record custom descriptors for use with each zone.
96 Initialize Download ID and Subscriber Account Number for Downloading
Entering ✻96 resets all subscriber account numbers and CSID in preparation for an initial download.
Loading Factory Defaults
97 To load the factory defaults, enter ✻97, then press number 1, 2, 3, or 4 to select from default tables
or press “0” if you are not selecting a default table. Refer to the Programming Default Tables section of this manual to view the tables.
If a default table is loaded, any data that has already been programmed into the system will be changed according to the default table selected!
1-4,
Exiting Program Mode
98 Exits program mode and inhibits re-entry into the Expert or Voice Prompt Programming modes using
the Installer Code.
99 Exits program mode but allows re-entry into the Expert Program mode using Installer Code (4112) +
800 or into the Voice Prompt Programming mode using Installer Code (4112) + 888.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset
delay, press [#] + [0].
Pass-Thru Programming
This mode allows the Installer to use the LYNXR-2 Series keypad and display to program the communications device that is connected to the LYNXR-2 Series. Refer to the communications device’s installation instruction to determine whether this feature is supported.
Entering Pass-Thru Programming mode
1. After power-up, enter the Installer Code (4112) + 899.
2. Once you have entered Pass-Thru Programming mode “PtP” will be displayed on the keypad.
3. Refer to the Installation Instructions for the LRR/IP Communications Device being installed for additional programming information.
LYNXR-2 Series will abort this mode:
When it receives an abort command from the new communications device.
If it fails to communicate with a communications device after 20 attempts.
30 minutes after the last key has been pressed.
- 18 -
LYNXR-2 Series Installation and Setup Guide
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below.
Type 00 Zone Not Used
Type 01 Entry/Exit Burglary #1
Type 02 Entry/Exit Burglary #2
Type 03 Perimeter Burglary
Type 04 Interior, Follower
Type 05 Trouble by Day/ Alarm by Night
Type 06 24-hour Silent Alarm
Type 07 24-hour Audible Alarm
Type 08 24-hour Auxiliary Alarm
Zone type 00 is used to program a zone that is not used.
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit doors.
Zone Characteristics:
Entry delay #1 is programmable (field
Exit delay is independently programmable (field
Exit and entry delays when armed in AWAY or STAY mode.
No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode.
Exit delay regardless of the arming mode selected.
Zone type 02 is usually assigned to sensors or contacts on secondary entry and exit doors that might be further from the keypad (typically used for a garage, loading dock, or basement door).
Zone Characteristics:
Entry delay #2 is programmable from (field
Exit delay is independently programmable from (field
Secondary entry delay, if armed in the AWAY or STAY mode.
No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
Exit delay begins regardless of the arming mode selected.
Zone type 03 is usually assigned to all sensors or contacts on exterior doors and windows.
Zone Characteristics:
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY mode.
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach the keypad. It provides an instant alarm if the entry/exit zone is not violated first, and protects an area in the event an intruder has hidden on the premises before the system is armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or interior- with-delay (type 10) zone is faulted first.
Instant alarm in all other situations.
Active when armed in AWAY or AWAY NO DELAY mode.
Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Zone type 05 is usually assigned to a zone that contains foil-protected doors or windows or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
Zone Characteristics:
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY (night) mode.
Provides a latched trouble sounding from the keypad and, if desired, a central station report during the disarmed state (day).
Zone type 06 is usually assigned to a zone containing an Emergency button (silent emergency). Zone Characteristics:
Sends a report to the central station but provides no keypad display or sounding.
Zone type 07 is usually assigned to a zone containing an Emergency button (audible emergency).
Zone Characteristics:
Sends a report to the central station, and provides alarm sounds externally and at the keypad.
Zone type 08 is usually assigned to a zone containing a button for use in personal emergencies or to a zone containing monitoring devices (i.e.: water or temperature sensors, etc.).
Zone Characteristics:
Sends a report to the central station and provides an alarm sound at the keypad. (No bell output is provided and there is no keypad timeout.)
35).
34).
36).
34).
- 19 -
LYNXR-2 Series Installation and Setup Guide
Zone Response Type Definitions
Type 09 Supervised Fire
Type 10 Interior with Delay
Type 14 24-hour Carbon
Monoxide Monitor
ZT16 is only available on the LYNXR-2SIA version of the control panel.
Type 16 Supervised Fire with Verification
Type 20 Arm–Stay
Type 21 Arm–Away
Type 22 Disarm
Type 23 No Alarm Response
Type 24 Silent Burglary
Zone type 09 can be assigned to any wireless zone used as a fire zone. This zone type is always active and cannot be bypassed.
Zone Characteristics:
Bell output will pulse when this zone type is alarmed.
Zone type 10 is bypassed when the panel is armed in the STAY or STAY NO DELAY mode. Zone Characteristics:
Entry delay #1 (with programmed entry time) when armed in the AWAY mode.
Entry delay begins whenever sensors in this zone are violated, regardless of whether an
entry/exit delay zone was tripped first.
No entry delay when armed in the AWAY NO DELAY mode.
Exit delay regardless of the arming mode selected.
Zone type 14 can be assigned to any wireless zone with a carbon monoxide detector. This zone type is always active and cannot be bypassed.
Zone Characteristics: Bell output will pulse when this zone type is alarmed.
Zone type 16 can be assigned to any wireless zone. It can not be used with heat detectors, combination heat/smoke detectors, wireless sensors or fire pull stations. This zone type is always active and can not be bypassed.
Zone Characteristics:
Provides a fire alarm when zone is alarmed, but only after the alarm has been verified.
System verifies alarm by delaying reporting and control panel alarm sounding for 30 seconds
after alarm is detected. If the zone remains faulted after 30 seconds a fire alarm is provided. If any other fire zone is faulted during the 30 second delay window a fire alarm is immediately provided for that zone. An alarm for original fire zone will also be provided if that zone is still faulted afterward. If there are no fire alarms after the 30 second delay expires, the system will open a 60 second window. If any fire zone is faulted during that window a fire alarm will immediately be provided for that zone.
Bell output will pulse following alarm verification
Zone type 20 is a special-purpose zone type used with 5800 Series wireless pushbutton units. Zone Characteristics:
Exit delay regardless of the arming mode selected.
System is armed in the STAY mode when the zone is activated.
Zone number is sent to the central station as a user number when arming or disarming.
Zone type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units. Zone Characteristics:
System is armed in the AWAY mode when the zone is activated.
Zone number is sent to the central station as a user number when arming or disarming.
Zone type 22 is a special-purpose zone type used with 5800 series wireless pushbutton. Zone Characteristics:
Disarms the system when the zone is activated.
Zone type 23 can be used on a zone when a Powerline Carrier Device (e.g., X10) action is desired, but with no accompanying alarm (e.g., front door light).
Zone type 24 is usually assigned sensors or contacts on exterior doors and windows where bells and/or sirens are NOT desired.
Zone Characteristics:
Instant alarm, with NO audible indication when is armed in the AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY mode.
Report sent to the central station.
Note: The Keypad beeps if the zone is faulted when system is disarmed and Chime mode is on.
- 20 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Specific fields include options for programming that are unique to the LYNXR-2SIA version. Note that both keypad LEDs flash while in Programming mode. The LYNXR­2SIA version validates the data entry for the Fields listed below. If data entered is not within valid range, the control will emit a long beep indicating that entry is rejected and will substitute the default value for the invalid entry. The default value will be displayed on the keypad, and the control advance to the next field.
Field Name Default Value Valid Range
*34 Exit Delay 60 45-97 *35 Entry Delay 01 30 30-99 *36 Entry Delay 02 30 30-99 *50 Burglary Dial Delay 2 1-3 *57 False Alarm Options 7 0-7 *59 Exit Error Report Code 1 1-F *64 Test Report Code 10 10-FF *68 Cancel Report Code 10 10-FF *69 Recent Closing Report Code 1 1-F *76 Test Restore Report 10 10-FF *92 Swinger Shutdown 1 1-2
Note: Entering a number other than the one specified will give unpredictable results.
20 Installer Code
Enter 4 digits (0-9)
21 Quick Arm Enable
0 = do not allow quick arm 1 = allow quick arm
22 Keypad Backlight Timeout
0 = no timeout; always backlight keys 1 = turn backlighting off after inactivity
23 Forced Bypass
0 = no forced bypass 1 = provide automatic bypass of all open (faulted) zones
24 RF House ID Code
00 = disable all wireless keypad usage 01-31 = House ID
25 Powerline Carrier Device
(X10) House ID
0 = A 4 = E 8 = I # + 12 = M 1 = B 5 = F 9 = J # + 13 = N 2 = C 6 = G # + 10 = K # + 14 = O 3 = D 7 = H # + 11 = L # + 15 = P
26 Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter zone
when Chime mode is activated)
1 = yes (chimes on fault of those zones assigned to Zone
List 3 when Chime mode on)
27 Real Time Clock Display
0 = do not display the time 1 = display the time
The Installer Code is used to enter the 4-digit Master Security Code. See "Master Code" in the System Operation section for procedure.
Note: LYNX-2SIA does not allow duplication of Installer code. If a
duplicate code is entered the entry is rejected and LYNX issues single long beep indicating rejection. The old installer code remains unchanged.
If enabled, security code is not required to arm the system. The user simply presses and holds down the AWAY or STAY key to arm.
This option allows the choice of either always backlighting the keypad or turning the backlighting off after 10 seconds of keypad inactivity.
All zones bypassed by this function will be displayed after the bypass is initiated.
UL installations: must be 0 (no forced bypass)
The House ID identifies receivers and wireless keypads.
If a 5804BD/5804BDV Transmitter is to be used, a House ID Code MUST be entered, and the keypad should be set to the same ID.
Powerline Carrier Devices require a House ID. This field identifies this House ID to the Control. The Powerline Carrier Devices are programmed in field ✻80.
This option allows the installer to define the specific zones intended to chime when faulted while the system is in Chime mode. If enabled, these zones are defined in zone list 3 (see 81 Zone List Menu Mode).
Refer to the Users Manual for setting the clock time and date.
- 21 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
29 Daylight Savings Time Start/
End Month
0 = do not display the time 1 = display the time
30 Daylight Savings Time Start/
End week
0 = disable 1 = first weekend of month 2 = second weekend 3 = third weekend 4 = fourth weekend 5 = last weekend 6 = next to last
rd
7 = 3
from last
31 Single Alarm Sounding Per Zone
(per armed period)
LYNXR-2 SELECTIONS
0 = no limit on alarm sounding per zone 1 = limit alarm sounding to once per arming period for a
given zone
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
Enter the appropriate start and end weekend of the month.
This field applies only to burglary zones (zone response types 1-5, 10), and affects long range radio reporting but does not affect central station reporting.
Note: This field applies only to the bell and does not affect keypad
sounds.
UL installations: must be 0 (no limit)
LYNXR-2SIA SELECTIONS
0 = Alarm Sounding Per Zone will be the same as the
Swinger Shutdown” set in field *92
1 = limit alarm sounding to once per arming period for a
given zone
32 Sounder Timeout
0 = yes, sounder timeout after time programmed in field 33 1 = no sounder timeout; continue sounding until manually
turned off
This Control complies with NFPA requirements for temporal pulse sounding of fire and carbon monoxide (CO) notification appliances.
Temporal pulse sounding for a fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3 pulses. . .
Temporal pulse sounding for a CO alarm consists of the following: 4 pulses – pause – 4 pulses – pause – 4 pulses – pause. . .
33 Alarm Bell Timeout
0 = No timeout 1 = 4 minutes 2 = 8 minutes 3 = 12 minutes 4 = 16 minutes
This field determines whether the external sounder will shut off after time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
Fields ✻34✻36: Fields *34, *35 and *36 are used to program different options in the LYNXR-2 and LYNXR­2SIA controls. Please be sure that you use the correct field for the control being installed.
Note: The LYNXR-2 SIA control validates the data entered in fields *34 - *36. If the selection is not valid the control will emit a
single long beep indicating that the selection has been rejected. The control replaces the selection with the default value which is displayed on the keypad.
34 Exit Delay
LYNXR-2 SELECTIONS
00-99 = exit delay time in seconds
LYNXR-2SIA SELECTIONS
Entries from 45-97
Entered Value Delay in Seconds
45-96 45-96 97 120
The system will wait the time entered before sounding an alarm if the exit door is left open after the system has been armed.
UL installations: must be set for a maximum of 60 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep indicating that the selection has been rejected. The control replaces the selection with the default value “60”, which is displayed on the keypad, and advances to the next field.
SIA: Exit Delay must be set to a minimum of 45 seconds.
- 22 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
35 Entry Delay 01
LYNXR-2 SELECTIONS
00-99 = entry delay time in seconds.
LYNXR-2SIA SELECTIONS
Entries from 30-99
Entered Value Delay in Seconds
30-96 30-96 97 120 98 180 99 240
36 Entry Delay 02
LYNXR-2 SELECTIONS
00-99 = entry delay time in seconds.
LYNXR-2SIA SELECTIONS
Entries from 30-99
Entered Value Delay in Seconds
30-96 30-96 97 120 98 180 99 240
The system will wait the time entered before sounding alarm upon entering if system is not disarmed.
UL installations: must be set for a maximum of 45 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep indicating that the selection has been rejected. The control replaces the selection with the default value “30”, which is displayed on the keypad, and advances to the next field.
SIA The Entry delay must be set to a minimum of 30 seconds. The
sum of entry delay 1 entered in Field 35 and the burglary abort window entered in 50 should not exceed 1 minute.
The system will wait the time entered before sounding alarm upon entering if the system is not disarmed.
UL installations: must be set for a maximum of 45 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep indicating that the selection has been rejected. The control replaces the selection with the default value “30”, which is displayed on the keypad, and advances to the next field.
SIA The Entry delay must be set to a minimum of 30 seconds. The
sum of entry delay 2 entered in Field 36 and the burglary abort window entered in 50 should not exceed 1 minute.
AUDIBLE EXIT WARNING/QUICK EXIT (✻37)
Note: This field is not available on the LYNXR-2SIA control.
37 Audible Exit Warning/Quick Exit
Exit Warning Quick Exit
0 = no exit warning sound 0 = no quick exit 1 = provide exit warning sound
when armed AWAY
1 = allow quick exit
38 Confirmation of Arming Ding
LYNXR-2 SELECTIONS
0 = no ding 1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or RF
keypad only
LYNXR-2SIA SELECTIONS
0 = no arming confirmation ding after arming system by
LYNXR keypad or RF keypad
1 = arming confirmation ding after arming system by LYNXR
keypad or RF keypad
2 = arming confirmation ding after arming from RF keypad
only
Exit Warning: Sound consists of slow continuous beeps until last 5 seconds, when it changes to fast beeps. The warning sound will end at the termination of exit delay.
Quick Exit: If enabled, user can restart the exit delay time after arming in STAY mode by entering the user code and pressing the STAY key, or by pressing the STAY key if Quick Arm is enabled. This avoids having the user disarm then re­arm the system after allowing someone to enter or exit
LYNXR-2
Confirmation of arming is provided by a 1/2 second external sounder ding that sounds when closing report is sent, or at the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs immediately after the system receives the RF transmission.
LYNXR-2SIA
Confirmation of arming is provided by a 1/2 second external sounder ding .The confirmation ding only sounds when LYNX is Armed Away or disarmed after being Armed Away.
If Option 1 is selected, confirmation of arming is provided by a 1/2 second sounder “ding” that sounds when closing report is sent, or at the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs immediately after arming from an RF keypad.
Note: If LYNXR-2SIA is armed by RF button (key fob), a confirmation
ding occurs immediately after arming regardless of field *38 settings. If LYNX is disarmed by RF button (key fob), additional disarming confirmation ding is provided. The ding occurs immediately after disarming and is longer than arming confirmation ding.
- 23 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
Field ✻39: Field *39 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls. Please be sure that you use the correct field for the control being installed.
39 Power Up In Previous State
Note: This field applies only to the LYNXR-2 control.
LYNXR-2 SELECTIONS
0 = always power up in a disarmed state 1 = assume the system status prior to power-down
39 Cross Zone Timer
Note: This field applies only to the LYNXR-2SIA
control.
LYNXR-2SIA SELECTIONS
Value Time Window
0 = No Cross Zoning 1 = 15 seconds 2 = 30 seconds 3 = 45 seconds 4 = 60 seconds 5 = 1 minute, 15 seconds 6 = 1 minute, 30 seconds 7 = 1 minute, 45 seconds 8 = 2 minutes
9 = 2 minute, 15 seconds # + 10 = 2 minute, 30 seconds # + 11 = 2 minute, 45 seconds # + 12 = 3 minutes # + 13 = 3 minute, 15 seconds # + 14 = 3 minute, 30 seconds # + 15 = 3 minute, 45 seconds
DIALER PROGRAMMING (✻40–✻50) Fields ✻40, ✻41, ✻42: Enter up to the number of digits shown. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13
for a pause controls. Please be sure that you use the correct field for the control being installed.
(2 seconds).
Field *40 is used to program different features in the LYNXR-2 and LYNXR-2SIA
When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted, and any bypassed zones will be unbypassed.
Note: If the previous state was armed AWAY or STAY, the system will
not respond to sensor changes for 1 minute, which allows time for sensors such as PIRs to stabilize.
UL installations: must be 1 (power up in previous state)
Sets the maximum amount of time in which two cross zones must be tripped in an armed system to send an alarm message to the Central Station. If only one cross zone is tripped during this time, a trouble message (CID code 380) for that zone is sent to the Central Station. Program Zone list 2 (using *81 Zone List Menu Mode) with the two zones that are to be cross zoned.
Notes: (1) If option ✻39 is set to “0” (no cross zoning) then Zone List 2
can be used for other purposes.
(2) Cross zoning will be disabled during entry and exit delays, if
there is already an alarm in the system, if one or both of the 2 cross zones is bypassed.
If one of the 2 cross zones faults and remains faulted after the
cross zone time interval, the second cross zone can go into alarm immediately, even after the cross zone time. This is to detect scenarios involving multiple break-ins of a premises.
UL This option is not for use in UL installations.
Notes: Whenever AAV is used, primary (field 41) and secondary (field 42) phone numbers should be preceded with the
call waiting disable command. Otherwise, there is the possibility of connection of the third party to LYNXR-2 Series during AAV mode. The
PABX phone number entered in field ✻40 is not dialed on GSM/IP (Digital Communication
with AAV). However, it is used for dialing on Telco Line.
40 PABX Access Code/Call Waiting
Disable
LYNXR-2 SELECTIONS
PABX Access Code
Enter up to 6 digits if PABX is needed to access an outside line.
LYNXR-2SIA SELECTIONS
PABX Access Code/Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an outside
line. or Enter“# + 11 + 7 + 0” to program the touch-tone sequence “*70” and cancel call waiting.
If fewer than 6 digits need to be entered, exit by pressing [✻]. To clear entries from field, press ✻40✻.
LYNXR-2SIA ONLY
Call Waiting: If the subscribers phone service has “call waiting (and is not using PABX), enter the touch-tone sequence*70 (or similar depending on the phone service). By programming # + 11 + 7 + 0 as the PABX entry to disable call waiting during control panel calls. You must also enable the Call Waiting Cancel option in field *47.
If the subscriber does not have call waiting and is not using PABX, make no entry in this field.
Important Note:
Note: PABX number and operation of the control panel with a PBX
system cannot be used if the Call Waiting Cancel Disable option has been enabled in Field ✻47.
If Call Wait Cancel is disabled in Field Disable command is entered in Field 40, this will prevent successful communication to the central station when used on a non-call waiting line.
47, and Call Wait
- 24 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
If the GSM/IP (Digital Communication with AAV) feature is used (options 5 and 7 in *55), there may be restrictions when dialing the numbers entered in *41, *42 and *46 (i.e.; #, ✻, pause may not be allowed, or phone number extensions may not be dialed, etc) depending on the service provider.
41 Primary Phone No.
Enter up to 20 digits.
42 Secondary Phone No.
Enter up to 24 digits.
All four digits of the Subscriber Account number must be entered in Fields ✻43 and ✻44. If ten-digit format is selected in ✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
Fields ✻43 and ✻44:
Enter [✻] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000–0999. Enter [✻] as the fifth digit if a 4-digit account number (for 4+1, 4+2 CID®) is used. Exit field by pressing [✻] if only 3 digits are used. To clear entries from field, press ✻43
or ✻44✻
. See blank Programming Form for examples of account number entries. If using the paging feature, do not enter a leading 0 in the subscriber account number, and do not use digits A-F anywhere in the number. Some paging systems provide voice mail capability, which is activated by a leading 0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; or # +15=F.
43 Primary Subscriber Account No.
Enter a four or ten digit account number.
44 Secondary Subscriber Account No.
Enter a four or ten digit account number.
Field 46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*; #+12 for’#; #+13 for a pause (2 seconds).
46 Follow Me Reminder Phone No.
Enter up to 24 digits.
If fewer than 20 digits entered, exit by pressing [✻]. To clear entries from field, press ✻41✻.
Note: Backup reporting (8 attempts are made to the secondary phone
number if no kissoff is received after 8 attempts to the primary number) is automatic only if there is a secondary phone number (field ✻42).
If fewer than 24 digits entered, exit by pressing [✻]. To clear entries from field, press ✻42✻. See backup reporting note for field ✻41. If using the paging feature, enter the pager phone number here.
Enter the primary subscriber account number.
✻43✻
To clear entries from field, press
Enter the primary subscriber account number. To clear entries from field, press
This option allows the user to schedule a time driven message. When activated the system will dial the phone number programmed and deliver a voice message (custom words 72, 73 and 74). This option is only supported when the pager or follow me feature is enabled in field If using the Follow Me Reminder feature, enter the phone number here. If fewer than 24 digits are entered, exit by pressing [ The telephone message can be terminated (acknowledged) by pressing any key on the telephone keypad. Pressing any key on the local LYNXR-2 Series keypad will terminate (acknowledge) both the follow me and the local reminder announcements.
Note: The follow me reminder announcement will be terminated if any other event requires the system to dial out or if an audible alarm has occurred.
]. To clear entries from the field press ✻46✻.
.
✻44✻
.
49 (option 6-9 or 10-13).
- 25 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
Fields ✻47: Field *47 is used to program different options in the LYNXR-2 and LYNXR-2SIA controls. Please
be sure that you use the correct field for the control being installed.
47 Phone System Select
LYNXR-2 SELECTIONS
Central Dialing Mode
Station Pulse Tone Pulse Tone
No WATS
WATS 2 = No
0 = No Speaker Phone
Speaker Phone
1 = No Speaker Phone
3 = No Speaker Phone
4 = With
Speaker
Phone
6 = With Speaker
Phone
5 = With Speaker Phone
7 = With Speaker Phone
LYNXR-2SIA SELECTIONS
Central Dialing Mode
Station Pulse Tone Pulse Tone
No WATS
WATS 2 = No
No WATS
WATS 10 = No
0 = No Speaker Phone Call Wait Cancel Disabled
Speaker Phone Call Wait Cancel Disabled
8 = No Speaker Phone Call Wait Cancel Enabled
Speaker Phone Call Wait Cancel Enabled
1 = No Speaker Phone Call Wait Cancel Disabled 3 = No Speaker Phone Call Wait Cancel Disabled 9 = No Speaker Phone Call Wait Cancel Enabled 11 = No Speaker Phone Call Wait Cancel Enabled
4 = With
Speaker
Phone
Call Wait
Cancel
Disabled
6 = With
Speaker
Phone
Call Wait
Cancel
Disabled
12 = with
Speaker
Phone
Call Wait
Cancel
Enabled
14 = With
Speaker
Phone
Call Wait
Cancel
Enabled
5 = With Speaker Phone Call Wait Cancel Disabled 7 = With Speaker Phone Call Wait Cancel Disabled 13 = With Speaker Phone Call Wait Cancel Enabled 15 = With Speaker Phone Call Wait Cancel Enabled
48 Report Format for Primary/
Secondary
Primary Secondary See choices below See choices below
0 = 3+1; 4+1 ADEMCO Low Speed Standard 1 = 3+1; 4+1 Radionics Standard 2 = 4+2 ADEMCO Low Speed Standard 3 = 4+2 Radionics Standard 5 = ADEMCO Contact ID® Reporting with 10-digit subscriber
account number 6 = 4+2 ADEMCO Express 7 = ADEMCO Contact ID® Reporting with 4-digit subscriber
account number 8 = 3+1; 4+1 ADEMCO Low Speed Expanded 9 = 3+1; 4+1 Radionics Expanded
This option is used to enter the correct type of phone dialing (pulse or tone), and to select the correct WATS line option for the Central Station. This option is used to activate the Speaker Phone option. For the LYNXR-2SIA it is also used to disable call waiting.
Note: If using pulse dialing, you must enter the numbers slowly in
order to allow the pulse dialer time to operate.
LYNXR-2SIA ONLY
Call waiting warning tones can interfere with Central stations reporting. The Call Waiting Cancel option should be selected if the reporting phone line has call waiting service. The Call Waiting Cancel command must also be programmed in Field
40. If the Call Waiting Cancel feature is enabled, make sure to
enter Call Waiting Cancel command in Field
40. The command
depends on a telephone service provider.
Important
Note: If Call Wait Cancel is disabled in Field
47, and
Call Waiting Disable command is entered in Field
40, this will prevent successful communication
to the central station when used on a non-call waiting line.
Note: PABX number and operation of the control panel with a
PBX system cannot be used if the Call Waiting Cancel option has been enabled in Field 47.
Enter ✻ as the 4th digit of ✻43 through ✻44, if 3+1 dialer reporting is to be used. (For an explanation of these formats, see the System Communication section of this manual.)
Notes: (1) The maximum number of alarm and alarm restore
reports during one armed period is determined by field
(2) If Option 5 is selected a 10-digit account number must
92.
be entered in Fields ✻43 or ✻44.
(3) Option 5 or 7 (ADEMCO Contact ID® Reporting) must
be selected for AAV.
- 26 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
49 Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary fails,
1 = Alarms, Restore,
Cancel
2 = All except Open/Close,
Test
3 = Alarms, Restore,
Cancel
4 = All except Open/Close,
Test
5 = All reports All
To Primary To Paging Number
6 = All reports except
Open/Close 7 = All reports Alarms, Troubles 8 = All reports Alarms, Open/Close ‡,
9 = All reports except
Open/Close
To Primary
10= All reports except
Open/Close 11 = All reports Alarms, Troubles 12= All reports Alarms, Open/Close ‡,
13= All reports except
Open/Close
*Recent close report is sent to primary number ‡
Will report Users 0, 5-8, and, if using wireless button-type devices, will report the zone number of the arm or disarm button 26-33. All other zones and users are not reported.
then all Others
Open/Close, Test
All
All
Alarms, Open/Close ‡, Troubles
Troubles Open/Close ‡
To Follow Me System Phone Number
Alarms, Open/Close ‡, Troubles
Troubles Open/Close ‡
This field is used to select a reporting option as follows: Enter: 0 - 5 when reporting to telephone receivers.
6 - 9 when reporting to a pager is desired. 10 - 13 when reporting to an aux telephone receiver.
Note: If you are installing a communications module that has
voice communications capability (i.e.; GSMVL), refer to Field *55 notes for additional information.
Pager Report Format Options 6-9 send reports to the primary phone number, in a format defined in Field ✻48, and send reports to a pager, which has its phone number entered as the secondary phone number in Field ✻42. The pager report is a 7-digit code, with optional 16-digit prefix, in the following format:
AAAAAAAAAAAAAAAA-EEE0NNN where:
AAA = Optional 16 digits for PIN number, etc. See Field ✻88 for full
EEE = 3-digit Event Code as follows: 911 = Alarm (NN = zone number) 101 = Open, system disarmed (NN = user no.) 102 = Close, system armed (NN = user no.) 811 = Trouble (NN = zone no.) 0 = Always displayed before 3-digit user/zone no. NNN = 3-digit user number or zone number, depending on the type of
description of these characters.
event (EEE) that occurred.
Follow Me System Report Format
Options 10-13 send reports to the primary phone number, in a format defined in Field ✻48, and sends voice message to the secondary phone number entered in Field ✻42. The message is a repeatable system status announcement. If the manual paging option has been programmed in Field ✻87, the message will repeat system, system…..”. The message can be terminated by pressing any key on the telephone keypad.
Field ✻50: Field *50 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls. Please be sure that you use the correct field for the control being installed.
50 15-Second Dialer Delay (Burglary)
Note: This field applies only to the LYNXR-2 control.
LYNXR-2 SELECTIONS
0 = no dialer delay 1 = provide 15-second delay of burglary alarm report when armed away
50 Burglary Abort Window
Note: This field applies only to the LYNXR-2SIA
control.
LYNXR-2SIA SELECTIONS
1 = 15-second abort window 2 = 30-second abort window 3 = 45-second abort window
If enabled, provides delay of burglary report to the central station, and allows time for the subscriber to avoid a false alarm transmission. The delay applies only to zone type 3 and 5 alarms and not to zone type 24 alarms (silent burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon as they occur.
UL installations: must be 0 (no delay)
This provides the option for an Abort Window for Burglary zone types that report to the central station. This feature allows time for the subscriber to avoid a false alarm transmission. This feature does not apply to zone type 9 or 16 alarms (Supervised Fire) or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon as they occur.
SIA The burglary abort window must be set to a minimum of 15
seconds. The sum of the burglary abort window entered in 50 and the entry delays entered in either Field 35 or 36 should not exceed 1 minute.
Note: The LYNXR-2SIA control validates the data entered in this
field. If the selection is not valid the control will emit a single long beep indicating that the selection has been rejected. The control replaces the selection with the default value “2”, which is displayed on the keypad, and advances to the next field.
- 27 -
Loading...
+ 61 hidden pages