The Following Recommendations for the Location of Fire and Burglary Detection Devices Help
Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72
noted below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of each
separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The
installation of smoke detectors
recommended.
• For additional protection the NFPA recommends that you install heat
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the
sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could
prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
DINING
in kitchens, attics (finished or unfinished), or in garages is not normally
or smoke detectors in the living room,
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
BEDROOMBEDROOM
TV ROOM
KITCHEN
DINING
LIVING ROOM
BEDROOM
BEDROOM
BEDROOMBEDROOM
KTCHN
BEDROOM
CLOSED
.
DOOR
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
GARAGE
01000-002-V0
LIVING ROOM
BEDROOM
LIVING
ROOM
TO
BEDROOM
BASEMENT
Recommendations For Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multi-level
building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm
signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm
signals are normally sent over the phone lines, if connected to an alarm monitoring station).
- 2 -
Table of Contents
SYSTEM FEATURES ..................................................................................................................................5
MOUNTING THE CONTROL.....................................................................................................................6
LIMITATIONS OF THIS SYSTEM STATEMENT..................................................................................75
UL NOTICES..............................................................................................................................................76
SIA QUICK REFERENCE GUDE ............................................................................................................76
SUMMARY OF CONNECTIONS DIAGRAM ..........................................................................................87
-3-
- 4 -
LYNXR-2 Series Installation and Setup Guide
System Features
LYNXR-2 Series is not intended for UL985 Household Fire applications unless a 24-hour backup battery
UL
UL
ULUL
The LYNXR-2 Series control is a self-contained, rechargeable wireless control/communicator that features
easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module (if provided) allows the LYNXR-2 Series to communicate with
the Central Station via the Internet. The following illustration highlights the main features of this system.
• Up to 24 wireless zones
(5800 Series transmitters)
• Up to 16 wireless button zones
• Up to 8 powerline carrier devices
• Supports wireless keypads
8 USER CODES
• Installer code
• Master code
• 5 Secondary codes
• Duress code
• 3 Panic functions
(P/N LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed.
Powerline Carrier Devices have not been evaluated by UL.
ZONES and DEVICES
• Real-time clock display and Fixed-Word display
• Message center (for user recorded messages)
• Voice announcement of system and zone status
• Voice chime
• Alarm clock
• Reminder
• X10 sched uling
• Latch key reports
• Automatic stay arming
• Remote phone control
• “Follow me” reminder and system Announcements
FEATURES
SYSTEM POWER
• Primary Power: Ademco K10145X10
plug-in transformer, 110VAC to
9VAC, 25VA output (K10145CN in
Canada)
controlled via IBM-compatible
computer using Compass
downloader software and specified
HAYES modem or via capable GSM
or IP communications module
• Voice prompt programming mode
ARMED
READY
OFF
1
2
3
PLAY
VOLUME
6
TEST
BYPASS
8
9
CODE
CHIME
0
FUNCTION
AUX
SELECT
STAY
DELETE
ESCAPE
AWAY
ADD
RECORD
45
LIGHTSON
7
LIGHTSOFF
STATUS
NODELAY
OTHER FEATURES
• Exit error feature (detects difference between an
actual alarm and exit alarm caused by leaving a door
open after the exit delay expires)
• Event log stores up to 84 events
• Macro/ 1-button paging
• RF jam detection
• Remote phone control
• Compatible with encrypted (high-security) devices
ALARM OUTPUT
• Built-in sounder
• Piezo output
(30mA max.)
• Bell output
(120mA max.)
• Steady output for
burglary/panic
• Temporal pulse
output for fire alarms
• Long range
radio/audio alarm
verification
SPECIAL FEATURES
• Two-way voice communication
• Speaker phone operation
• Supports AlarmNet remote
services
- 5 -
LYNXR-2 Series Installation and Setup Guide
Mounting the Control
Wall Mounting
The illustration below shows the front assembly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the
front assembly board.
!
1. Release the front assembly from the back
plate by depressing the two locking tabs
at the top of the unit with the blade of a
medium size screwdriver.
2. Once these tabs have been released,
insert the screwdriver in the side of the
case and release the side locking tabs by
gently twisting.
3. Carefully disconnect the ribbon cable from
the front assembly, leaving the ribbon
cable connected to the terminal block
PC board. The back plate contains the
terminal block for making wiring
connections.
LOCKING
TABS
4. Mount the back plate to a sturdy wall,
feeding the field wiring through the
appropriate openings in the back plate.
5. After wiring connections are made,
carefully reconnect the ribbon cable to
DISCONNECT
THIS END ONLY!
the front assembly PC board connector
(properly aligning the red wire).
6. Snap the front assembly to the back plate
so it is secured by the locking tabs.
Desktop Mounting
For desktop use the optional mounting base (model LYNX-DM, purchased separately) must be used.
1. Slide the control panel onto the mounting
base locking tabs.
2. Bring all wiring through the bottom of the
mounting base, using one of the three
wire entry locations, before making
connections to the control panel.
3. Use tie-wraps to secure the wiring to the
built-in wire loops as needed. Use the two
supplied screws to secure the control
panel to the mounting base.
ESCAPE
AWAY
ADD
STAY
DELETE
AUX
STATUS
SELECT
OFF
LIGHTSOFF
LIGHTSON
7
1
VOLUME
RECORD
4
5
TEST
8
CODE
0
NODELAY
FUNCTION
LOCKING TABS
RED WIRE
MARKING
ARMED
READY
2
3
PLAY
6
BYPASS
9
CHIME
LOCKING
TABS
09012-002-V0
WIRE ENTRY
KNOCKOUT
(1 of 3)
09015-002-V0
- 6 -
LYNXR-2 Series Installation and Setup Guide
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the
Summary of Connections diagram on the inside back cover when making connections.
UL
UL
ULUL
External sounders have not been evaluated by UL.
TERMINAL
STRIP
TELEPHONE
CONNECTIONS
COMMUNICATIONS
LRR/IP
PORT
GSML/GSMVL
COMMUNICATIONS
PORT
HIGH-CAPACITY
BATTERY CONNECTOR
STANDARD
SUPER HIGH-CAPACITY
BATTERY CONNECTOR
LOCAL
SOUNDER
DISABLE
09012-009-V0
Wiring Connections
1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground
for the lightning transient protective devices in this product to be effective. The following are examples of good earth
grounds available at most installations:
Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically
connected and secured to which the ground lead is electrically connected and secured.
AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or
equivalent, available at most electrical supply stores.
a. Connect terminal 1 to a good earth ground.
2. Make Phone Line Connections - For local or full line seizure follow the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the 8-position jack or terminals 2 (TIP) and 3 (RING) on the Lynx.
b. Connect the handset phone lines to either the RJ11 jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord
directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line
usage by the premises phones if the plug needs to be removed.
c. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X
terminals 4 (red) and 5 (green).
d. Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.
e. Wire the flying leads of a Direct Connect Cord to the control’s phone terminals as shown in the diagram or plug into
the 8-position jack.
f. Plug the Direct Connect Cord into the RJ31X jack.
- 7 -
LYNXR-2 Series Installation and Setup Guide
Wiring Connections
45
GREY
3
2
1
RJ31X
OR
OR
6
7
8
DIRECT
CONNECT
CORD
INCOMING
PHONE LINE
RING
TIP
GREENRED
TO
PREMISES PHONES
RING
TIP
BROWN
RED
GREEN
TIP RING TIP RING
}
INCOMING
PHONE LINE
BROWN
}
TO
PREMISES
PHONES
GREY
8-POSITION
JACK
01000-008-V0
Full Line Seizure Connections
UL
UL
ULUL
3. Make External Sounder Connections - The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
4. Disable Local Sounder Option - If required the Master Keypad’s built-in piezo sounder can be disabled.
5. Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using
Do not remove the local sounder shorting jumper (shunt).
External sounders and powerline carrier devices have not been evaluated by UL
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by removing the
shorting jumper (shunt) on the terminal board. If disabled, however, no sounding will occur upon AC loss,
since the external sounder does not operate when AC power is lost.
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX).
a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
a. Remove the shorting jumper (shunt) on the terminal board.
these devices, they must be connected to the K10145X10 transformer, as shown in the SUMMARY OF
CONNECTIONS diagram.
a. Connect the com/data/sync/ lines from the transformer to terminals 9, 13, and 14, respectively.
If not using the supplied connection cable, you may need to reverse the black and yellow wire connections.
Refer to the ✻✻✻✻80 Device Programming Menu Mode section for details on programming Powerline Carrier
Devices.
- 8 -
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
General
This LYNXR-2 Series supports central station reporting via the internet using wireless (GSM) and hardwire
(IP) communications modules. It also supports upload/download programming capability via the Internet or
a Private local area network (Intranet). This allows site maintenance independent of central station
monitoring, and modification to sites globally via the Internet or through a private LAN. Refer to the
instructions provided with the LRR/IP Communications Device being installed for additional information
regarding its installation, programming, and registration.
LYNXR-2 Series does not support the 7845i-ENT remote access feature.
Connecting Long Range Radio and Internet Communication Devices
Connect and configure the communications device as follows (refer to the Installation Instructions for device
that you are installing for additional information):
The wire run between the LYNXR-2 Series and the Communications Device must not exceed ten (10) feet.
UL
UL
ULUL
The 7845i-ENT has been evaluated by UL for Household Burglary installations but has not been evaluated
for Household Fire installations.
AlarmNet 7847i-L* Communications Device
1. Install the module into the LYNXR-2 Series back plate and secure it with the two provided screws. Refer to the diagrams
that follow.
2. Connect the provided ribbon cable between the module and the PC board. This cable provides DC power and ground for
the module and data in/data out connections.
3. Connect the device to the Internet via a cable/DSL modem and router or to an Intranet (LAN) via the appropriate Ethernet
connection.
* When available. The 7847i-L module has not been evaluated by UL.
CABLE
7720P
PROGRAMER
CONNECTION
SCREW (2)
RJ45
(FOR INTERNET CONNECTION)
LRR / IP
COMMUNICATION
PORT
09012-008-V1
Installing the 7847i-L Communications Module
- 9 -
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
AlarmNet 7845GSM, 7845i-GSM*, 7845i-ENT, 7845i or 7847i-E* Communications Device
The 7845i-ENT and 7845i cannot be used for installations requiring 24-hour standby.
!
1. Connect the 4-wire communications cable to the LRR/IP Communications port on the LYNXR-2 Series.
2. Connect the four wires to the specific Communications device as shown in the accompanying figures.
3. If you are installing a 7845GSM or 7845i-GSM you must also install a jumper between terminals 2 and 3 on the
communications device.
4. Connect the device to the Internet via a cable/DSL modem and router or to an Intranet (LAN) via the appropriate Ethernet
connection, if applicable.
UL
UL
ULUL
AlarmNet 7845GSM and 7845i-GSM modules have not been evaluated by UL.
* When available
7845GSM /
7845i-GSM
ECP (+) VOLTAGE INPUT
Z1/Z2 OR DATA IN
Z3 OR DATA OUT
GND
TB1
1
2
4
3
4
5
5
6
CONTROL PANEL
RED
BLK
YEL
GRN
GRN
BLK
RED
YEL
4-WIRE CABLE (N4632-4)
LRR/IP COMMUNICATIONS PORT
DATA IN
GND
+12 VDC
NC
DATA OUT
REQUIRED FOR
24-HR BACKUP
Connecting AlarmNet 7845GSM / 7845i-GSM
LYNX
STANDARD
CAPACITY
BATTERY
(OPTIONAL)
LYNX
SUPER HIGH
CAPACITY
BATTERY
09012-018-V0
7845i-ENT / 7845i
(+) VOLTAGE INPUT
GND
DATA OUT
DATA IN
TB 1
CONTROL PANEL
RED
BLK
GRN
YEL
GRN
BLK
RED
YEL
4-WIRE CABLE (N4632-4)
LRR/IP COMMUNICATIONS PORT
DATA IN
GND
+12 VDC
NC
DATA OUT
Connecting AlarmNet 7845i-ENT/7845i/7847i-E*
- 10 -
LYNX
STANDARD
CAPACITY
BATTERY
09012-019-V0
LYNXR-2 Series Installation and Setup Guide
Connecting/Configuring Communication Modules
AlarmNet GSML/GSMVL Communications Device
1. Install the module into the control back plate and secure it with the three provided screws.
2. Connect the antenna to the GSML/GSMVL module.
3. Insert the antenna into the retaining slots in the control back plate.
4. Use double-stick tape to secure antenna to the control back plate.
5. Connect the provided communications cable between the GSML/GSMVL module and the control’s PC board. This cable
provides DC power and ground for the module and data in/data out connections.
6. If using the GSMVL, connect the provided shielded audio cable between the GSMVL module and the control’s PC board.
SCREW (3)
COMMUNICATIONS
AUDIO CABLE
(GSMVL ONLY)
ANTENNA
GSML/GSMVL
CABLE
09012-017-V1
Installing the GSML/GSMVL Communications Module
LRR/IP Communications Device 24-Hour Standby Power
If you are installing the AlarmNet 7845GSM/7845i-GSM or 7847i-L, and require 24-hour standby, you must
install the Super High Capacity battery P/N WALYNX-RCHB-SHA in the control.
The 7845i-ENT and 7845i can not be used for installations requiring 24-hour standby.
!
Configuring Long Range Radio and Internet Communication Devices
1. Enable the communications device in programming field *55 and configure alarm reporting and module supervision in
programming field *77.
2. Program the device as required using the 7720P programmer (refer to the Installation Instruction for the device that you
are installing for additional information). Note that the device address must be set to 3.
The device must be registered before downloading or alarm reporting can take place.
- 11 -
LYNXR-2 Series Installation and Setup Guide
AC Power and Backup Battery
The system is powered by a 9VAC, 25VA Plug-in Transformer, ADEMCO K10145X10 (K10145CN in
Canada). Refer to the wiring table below for wire gauge and length.
Distance from Transformer to Control
Wire Gauge
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Use only the provided ADEMCO K10145X10 or K10145CN Transformer. Wiring to the AC Transformer
must not exceed 300 feet using 16-gauge wire. The voltage reading between terminals 15 and 16 of the
control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery
In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
“low battery” message is displayed and a report is sent to the central station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1. Connect wires from the K10145X10 (K10145CN) in
Canada) AC Transformer to terminals 15 and 16 as
shown in the wiring diagram.
2. Remove battery retainer.
3. Peel the backing from tape on the back plate.
4. Insert battery pack into back plate.
5. Install battery retainer.
6. Connect battery connector to receptacle on terminal
block PC board.
7. After all wiring connections have been made, snap the
front assembly to the back plate and plug the
transformer into a 24-hour, 110VAC unswitched outlet.
Note: Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should clear
within four hours or by entering Test Mode.
BATTERY
PACK
RETAINER
TAPE
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
Ensure the cover is snapped closed prior to applying AC power.
- 12 -
BATTERY
RECEPTACLE
WIRING
TERMINALS
09012-003-V0
LYNXR-2 Series Installation and Setup Guide
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR-2 Series is equipped with an integral, replaceable, rechargeable battery packrated at 7.7Vdc.
Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack.
Model/Part Number Battery StandbyTime
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion
LYNXRCHKIT-HC 24-hours (minimum) At least 1-hour before battery depletion
LYNXRCHKIT-SHA 24-hours (minimum) At least 1-hour before battery depletion
Replacing the Rechargeable Battery
1. When battery replacement is required,
unplug the transformer from the wall outlet,
and open the control panel cover.
2. Remove the battery retainer and disconnect
the battery pack connector from the
receptacle on the terminal block PC board.
3. Remove the battery pack from the back
plate.
4. If required, replace the tape that secures the
battery pack.
5. Install a replacement battery pack (P/N
LYNXRCHKIT-SC, LYNXRCHKIT-HC or
LYNXRCHKIT-SHA) into the back plate.
6. Install the battery retainer.
7. Connect the battery connector to the
receptacle on the terminal block PC board.
8. After the wiring connection has been made,
snap the front assembly to the back plate.
9. Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
10. Rechargeable batteries may take up to 48hours to fully charge. The “LOW BAT”
message should clear within four hours or
by entering Test Mode.
Low Battery Notification
RETAINER
BATTERY
PACK
BATTERY
CONNECTOR
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
BATTERY
CONNECTOR
BATTERY
RECEPTACLE
RETAINER
BATTERY
PACK
LYNXRCHKIT-SHA
TAPE
TAPE
BATTERY
RECEPTACLE
Ensure the control panel assembly is snapped closed prior to applying AC power.
- 13 -
09012-004-V1
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless
buttons.
Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of
200 feet.
Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the
system using the ✻56 or ✻83 interactive mode, or input to the control via the downloader. 5800 Series
transmitters (except the 5800RL, which is described separately) do not have DIP switches. Each
transmitter's zone number is programmed into the system in ✻56 mode. Some transmitters, such as the
5816 and 5817, can support more than one "zone" (referred to as loops or inputs). On the 5816, for
example, the wire connection terminal block is loop 1; the reed contact is loop 2. Each loop must be
assigned a different zone number.
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring and the loop wiring must
UL
UL
ULUL
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to
each individual button used on the transmitter. Each button on the transmitter also has a pre-designated
loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV Wireless Keypad with the system, you must program a House ID
Code (01–31) in field ✻24 to establish proper communication, and the keypad must be set to the same ID.
House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800 Series
transmitters; the entry should be left at “00” (default) in those cases.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV, and
5804E), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period,
the "missing" transmitter number(s) and "FAULT" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises (5801, 5802MN) may be turned off by
entering it as a "UR" (unsupervised RF) type, as described in the ✻56 Enhanced Zone Programming Mode
section. 5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition
if covers are removed.
Transmitter Input Types
Each of the following transmitters has one or more unique factory-assigned input (loop) ID codes. Each of
the inputs requires a programming zone
be entered as one of the following types
"RF" (Supervised RF)
"UR" (Unsupervised RF)
"BR" (Unsupervised Button RF)
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage,
and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well
as large swings in temperature may all reduce the actual battery life in a given installation. The wireless
system can identify a true low battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point within the system.
not exceed 3 feet.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5814, 5816TEMP, 5819, 5819S(WHS &
BRS), 5828/5828V and 5850(GBD) transmitters have not been evaluated by UL.
(e.g., a 5804's four inputs require four button zones). Transmitters can
(see transmitter’s instructions for appropriate input type):
Type Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals.
The transmitter must remain within the receiver's range.
Sends all the signals that the "RF" type does, but the control does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
These only send fault signals. They do not send low battery signals until they are
activated. The transmitter may be carried off-premises.
- 14 -
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
• Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN, 5802MN2,
5804, 5804BD, 5804BDV, and 5804E button transmitters have replaceable batteries.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all transmitters have been properly
programmed.
1. Enter Installer code (4112) + [#] + 3.
Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer
mode. If so, wait a few minutes and try again.
2. The keypad will display all zone numbers, which have a non-zero Zone Type (even if serial numbers
were not learned yet). Fault each transmitter in turn, causing each one to send a signal. As the system
receives a signal from each of the transmitters, the zone number of that transmitter will disappear
from the display. The transmitters may be checked upon installation, or in an installed system.
3. When all transmitters have been checked, exit Sniffer mode. Enter Installer Code (4112) + OFF.
Notes: (1) Sniffer mode does not automatically expire. You must manually exit (Installer Code + OFF) Sniffer
(2) All BR-type units must physically be activated to clear the display, since they do not automatically send
(3) When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that
(4) Any transmitter that is not “entered” will not turn off its zone number.
(5) For SIA installations, the following devices may be used as specified for panic (24-hour) alarm response:
mode to return to normal operation.
check-in signals.
transmitter are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
• wireless keys which have two-button panic pairs available (e.g., 5804BDV), on which only the two-button
panic pairs may be programmed for any 24-hour alarm response
• wireless keypads (e.g., 5828/5828V) keypads that have a two-second delay on the special function keys, or
two-button panic pairs
• built-in keypad’s two-button panic pairs
Go/No Go Test Mode
5804E encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode.
Refer to the transmitter’s installation instructions for complete details. The system will confirm
enrollment of the encrypted device by beeping two times.
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and
allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This
will enable you to make sure that the RF signal from each transmitter is received with sufficient signal
amplitude when the system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire to be
run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter.
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, press-
ing a button will take the system out of the Go/No Go Test mode causing the programmed action to occur.
Note: On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a
button will take the system out of the Go/No Go Test mode and cause the programmed action to occur.
a. The keypad will beep three times indicating signal reception and will display the appropriate zone
number.
b. If the keypad does not beep, reorient or move the transmitter to another location. Usually a few
inches in either direction is all that is required.
3. If each transmitter produces the proper keypad response when it is faulted, you can then permanently
mount each of the transmitters according to the instructions provided with them.
4. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
- 15 -
LYNXR-2 Series Installation and Setup Guide
Installing Wireless Zones
5800 Series Transmitter Loop Numbers
(Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop
designations.
5801
5809
5819
"RF"
"RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 1
(TERMINALS)
LOOP 1
5802MN
ENROLL AS
"UR" OR "RF"
LOOP 1
5814
ENROLL
AS
"RF"
LOOP 2
(REED)
LOOP 3
LOOP 1
(INTERNAL
SHOCK
SENSOR
5819S (WHS & BRS)
ENROLL AS
"RF"
LOOP
5800CO
ENROLL AS "RF"
LOOP
1
5802MN2
ENROLL AS
"UR" OR "RF"
LOOP 2
(REED)
LOOP 1
(TERMINALS)
5816
ENROLL AS
"RF"
1
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
ALTERNATE
FOR LOOP 2
POSITION
5800Micra
ENROLL AS "RF"
O
N
O
F
F
5804/5804E
ENROLL AS "BR"
LOOP 2
(REED)
LOOP 1
(TERMINALS)
5816MN
ENROLL AS
"RF"
LOOP 3
LOOP 2
LOOP 1
5800RL
SET
HOUSE ID
LOOP 2
LOOP
•
3
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5804BD/5804BDV
ENROLL AS
5816TEMP
ENROLL AS
"BR"
LOOP 1
(TEMP
SENSOR)
"RF"
PROGRAM HOUSE ID
LOOP 4
YOU MUST
ENROLL
THIS BUTTON
LOOP 1
5800SS1
ENROLL AS "RF"
ON
OFF
1
2
3
4
5805-6
ENROLL AS
5817
ENROLL AS
"RF"
"BR"
LOOP 1
(PRIMARY)
LOOP 2
(AUX.
CENTER)
LOOP 3
(AUX.
RIGHT)
5800WAVE
PROGRAM
HOUSE ID
5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
"RF"
LOOP 1
5818
ENROLL AS
"RF"
YOU MUST
LOOP 1
(TERMINALS)
(TERMINALS)
LOOP 4
ENROLL
THIS
BUTTON
LOOP 2
(REED)
LOOP 3
LOOP 1
ENROLL AS
"UR OR"RF"
ENROLL AS
ENROLL AS
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
AWAY
1
3
5878
ENROLL AS
STAY
4
2
SERIAL #1
LOOP 2
SERIAL #1
LOOP 1
SERIAL #2
LOOP 2
"BR"
5800-002-V0
5820/5820L
ENROLL AS
5890/5890PI
ENROLL AS
"RF"
LOOP 1
(MOTION)
"RF"
5821
ENROLL AS
"RF"
5894PI
ENROLL AS
ARMED
READY
5828/5828V
PROGRAM
HOUSE ID
"RF"
MIC
MESSAGE
LOOP 1
(SOUND)
(Green)
(Red)
(Yellow)
5849
ENROLL AS
5897
ENROLL AS
"RF"
"RF"
5850 (GBD)
ENROLL AS
"RF"
5853
ENROLL AS
"RF"
Notes: (1) Loop 4 must be enrolled on the 5801, 5804, 5804BD, 5804BDV and 5804E transmitters, whether or not the
loop is used.
(2) 5804E encrypted (High-Security) devices must be activated while the system is in Go/No Go Test Mode. Refer
to the transmitter’s installation instructions for complete details. The system will confirm enrollment of the
encrypted device by beeping two times.
(3) The 5806 smoke detector must be used in SIA applications.
UL
UL
ULUL
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5814, 5816TEMP, 5819, 5819S(WHS & BRS),
5828/5828V and 5850(GBD) wireless transmitters
have not been evaluated by UL.
- 16 -
LYNXR-2 Series Installation and Setup Guide
Mechanics of Programming
General Programming Information
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The
system can be programmed at any time, even at the installer's premises prior to the actual installation.
Simply apply power temporarily to the Control and then program the unit as desired. There are four
programming modes:
• Data field programming (used for setting various system options).
• Interactive menu mode programming (used for programming zone information, programming
Powerline Carrier Devices, and for entering transmitter serial numbers).
• Voice Prompt programming (used for setting various system options).
• Pass-Thru programming (used for programming connected LRR/IP Communications Device).
The system can also be programmed remotely, using an IBM Personal Computer, and Compass
Downloader and modem or via capable GSM or IP communications modules. See the Remote Programming/Control (Downloading) section.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to
clearly hear the feedback announcements or system beeps in the Programming Mode, of the system’s built-in
speaker. To adjust the volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the
system will reset the volume to the default value (mid level).
Entering Program Mode
Use one of the following methods to enter Programming Mode:
1. Press both the [✻] and [#] keys at the same time, within 50 seconds after power is applied to the
Control or from exiting Programming mode, OR
2. After power-up, enter the Installer Code (4112) + 800 to enter Expert Programming mode (This
method disabled if Program mode is exited using ✻98). OR enter Installer Code (4112) + 888 to
enter Voice Prompt Programming mode.
If a different Installer Code has been programmed, use that code to enter the Programming mode.
3. Upon entering programming mode, the control will display “--” for up to two seconds indicating it is
communicating with the LRR/IP devices.
4. Once you have entered the Program mode, data field “20” (the first data field in the system) will be
displayed and both keypad LEDs will flash. If you have entered the Voice Prompt Programming mode.
“Pro” will be displayed.
Programming a Data Field
1. Press [✻] + Field No. (for example, ✻21), followed by the required entry.
2. When you have completely programmed a data field, the keypad will “beep” three times and then
automatically display the next data field in sequence. To go to a different field, press [✻] plus the
desired field number.
3. If the number of digits that will be entered in a data field is less than the maximum number of digits
available (e.g. phone number field), enter the desired data, then press [✻] to advance to the next data
field.
4. If a nonexistent field has been entered, the keypad will display “EE”. Simply re-enter [✻] plus a valid
field number.
To view a data field without making changes:
To delete an entry in a field:
Enter [✻] + Field No. + [✻]. (Applies only to fields ✻40–✻44, ✻88 and ✻94).
Enter [#] + Field No. Data will be displayed for that field.
- 17 -
LYNXR-2 Series Installation and Setup Guide
Mechanics of Programming
Interactive Menu Mode Programming(✻56, ✻80, ✻81, ✻83, ✻84, ✻85)
[✻] + interactive mode No. (i.e., ✻56). The keypad will display the first of a series of prompts. A detailed
Press
procedure (with displays of prompts) is provided in later sections of this manual.
✻
56 Enhanced Zone Programming Mode
Interactive menu mode used for programming zone attributes and report codes. Refer to the ✻56
Enhanced Zone Programming Mode section for procedure.
✻
80 Device Programming Menu Mode
Interactive menu mode for programming Powerline Carrier Devices. Refer to the ✻80 Device
Programming Menu Mode section for detailed procedure.
✻
81 Zone Lists Menu Mode
Interactive menu mode for programming zone lists for Powerline Carrier Devices. Refer to the ✻81
Zone List Menu Mode section for detailed procedure.
✻
83 Enhanced Sequential Mode
Interactive menu mode used to enter RF transmitter serial numbers. Refer to the ✻83 Enhanced
Sequential Mode section for detailed procedure.
✻
84 Assign Zone Voice Descriptors
Interactive menu mode used to assign descriptors to each zone. These descriptors will be announced
whenever the system announces an event involving a zone.
✻
85 Record Custom Voice Descriptors
Interactive menu mode used to record custom descriptors for use with each zone.
✻
96 Initialize Download ID and Subscriber Account Number for Downloading
Entering ✻96 resets all subscriber account numbers and CSID in preparation for an initial download.
Loading Factory Defaults
✻
97 To load the factory defaults, enter ✻97, then press number 1, 2, 3, or 4 to select from default tables
or press “0” if you are not selecting a default table. Refer to the Programming Default Tables section of this
manual to view the tables.
If a default table is loaded, any data that has already been programmed into the system will be changed
according to the default table selected!
1-4,
Exiting Program Mode
✻98 Exits program mode and inhibits re-entry into the Expert or Voice Prompt Programming modes using
the Installer Code.
✻99 Exits program mode but allows re-entry into the Expert Program mode using Installer Code (4112) +
800 or into the Voice Prompt Programming mode using Installer Code (4112) + 888.
Note: After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset
delay, press [#] + [0].
Pass-Thru Programming
This mode allows the Installer to use the LYNXR-2 Series keypad and display to program the
communications device that is connected to the LYNXR-2 Series. Refer to the communications device’s
installation instruction to determine whether this feature is supported.
Entering Pass-Thru Programming mode
1. After power-up, enter the Installer Code (4112) + 899.
2. Once you have entered Pass-Thru Programming mode “PtP” will be displayed on the keypad.
3. Refer to the Installation Instructions for the LRR/IP Communications Device being installed for
additional programming information.
LYNXR-2 Series will abort this mode:
• When it receives an abort command from the new communications device.
• If it fails to communicate with a communications device after 20 attempts.
• 30 minutes after the last key has been pressed.
- 18 -
LYNXR-2 Series Installation and Setup Guide
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type 00
Zone Not Used
Type 01
Entry/Exit
Burglary #1
Type 02
Entry/Exit
Burglary #2
Type 03
Perimeter
Burglary
Type 04
Interior,
Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour
Silent Alarm
Type 07
24-hour
Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Zone type 00 is used to program a zone that is not used.
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit doors.
Zone Characteristics:
• Entry delay #1 is programmable (field
• Exit delay is independently programmable (field
• Exit and entry delays when armed in AWAY or STAY mode.
• No entry delay when armed in STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Zone type 02 is usually assigned to sensors or contacts on secondary entry and exit doors that
might be further from the keypad (typically used for a garage, loading dock, or basement door).
Zone Characteristics:
• Entry delay #2 is programmable from (field
• Exit delay is independently programmable from (field
• Secondary entry delay, if armed in the AWAY or STAY mode.
• No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
• Exit delay begins regardless of the arming mode selected.
Zone type 03 is usually assigned to all sensors or contacts on exterior doors and windows.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY mode.
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or hallway)
that one must pass upon entry (after faulting the entry/exit zone) to reach the keypad. It provides
an instant alarm if the entry/exit zone is not violated first, and protects an area in the event an
intruder has hidden on the premises before the system is armed, or gains access to the premises
through an unprotected area.
Zone Characteristics:
• Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or interior-
with-delay (type 10) zone is faulted first.
• Instant alarm in all other situations.
• Active when armed in AWAY or AWAY NO DELAY mode.
• Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Zone type 05 is usually assigned to a zone that contains foil-protected doors or windows or covers a
sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on a sensor or contact in
an area where immediate notification of an entry is desired.
Zone Characteristics:
• Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY (night)
mode.
• Provides a latched trouble sounding from the keypad and, if desired, a central station report
during the disarmed state (day).
Zone type 06 is usually assigned to a zone containing an Emergency button (silent emergency).
Zone Characteristics:
• Sends a report to the central station but provides no keypad display or sounding.
Zone type 07 is usually assigned to a zone containing an Emergency button (audible emergency).
Zone Characteristics:
• Sends a report to the central station, and provides alarm sounds externally and at the keypad.
Zone type 08 is usually assigned to a zone containing a button for use in personal emergencies
or to a zone containing monitoring devices (i.e.: water or temperature sensors, etc.).
Zone Characteristics:
• Sends a report to the central station and provides an alarm sound at the keypad. (No bell
output is provided and there is no keypad timeout.)
✻35).
✻34).
✻36).
✻34).
- 19 -
LYNXR-2 Series Installation and Setup Guide
Zone Response Type Definitions
Type 09
Supervised Fire
Type 10
Interior with
Delay
Type 14
24-hour Carbon
Monoxide
Monitor
ZT16 is only available on the LYNXR-2SIA version of the control panel.
Type 16
Supervised Fire
with Verification
Type 20
Arm–Stay
Type 21
Arm–Away
Type 22
Disarm
Type 23
No Alarm
Response
Type 24
Silent Burglary
Zone type 09 can be assigned to any wireless zone used as a fire zone. This zone type
is always active and cannot be bypassed.
Zone Characteristics:
• Bell output will pulse when this zone type is alarmed.
Zone type 10 is bypassed when the panel is armed in the STAY or STAY NO DELAY mode.
Zone Characteristics:
• Entry delay #1 (with programmed entry time) when armed in the AWAY mode.
• Entry delay begins whenever sensors in this zone are violated, regardless of whether an
entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY NO DELAY mode.
• Exit delay regardless of the arming mode selected.
Zone type 14 can be assigned to any wireless zone with a carbon monoxide detector. This zone type
is always active and cannot be bypassed.
Zone Characteristics:
Bell output will pulse when this zone type is alarmed.
Zone type 16 can be assigned to any wireless zone. It can not be used with heat detectors,
combination heat/smoke detectors, wireless sensors or fire pull stations. This zone type is always
active and can not be bypassed.
Zone Characteristics:
• Provides a fire alarm when zone is alarmed, but only after the alarm has been verified.
• System verifies alarm by delaying reporting and control panel alarm sounding for 30 seconds
after alarm is detected. If the zone remains faulted after 30 seconds a fire alarm is provided. If
any other fire zone is faulted during the 30 second delay window a fire alarm is immediately
provided for that zone. An alarm for original fire zone will also be provided if that zone is still
faulted afterward. If there are no fire alarms after the 30 second delay expires, the system will
open a 60 second window. If any fire zone is faulted during that window a fire alarm will
immediately be provided for that zone.
• Bell output will pulse following alarm verification
Zone type 20 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Zone Characteristics:
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or disarming.
Zone type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Zone Characteristics:
• System is armed in the AWAY mode when the zone is activated.
• Zone number is sent to the central station as a user number when arming or disarming.
Zone type 22 is a special-purpose zone type used with 5800 series wireless pushbutton.
Zone Characteristics:
• Disarms the system when the zone is activated.
Zone type 23 can be used on a zone when a Powerline Carrier Device (e.g., X10) action is desired,
but with no accompanying alarm (e.g., front door light).
Zone type 24 is usually assigned sensors or contacts on exterior doors and windows where bells
and/or sirens are NOT desired.
Zone Characteristics:
• Instant alarm, with NO audible indication when is armed in the AWAY, STAY, STAY NO
DELAY, or AWAY NO DELAY mode.
• Report sent to the central station.
Note: The Keypad beeps if the zone is faulted when system is disarmed and Chime mode is on.
- 20 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Specific fields include options for programming that are unique to
the LYNXR-2SIA version. Note that both keypad LEDs flash while in Programming mode. The LYNXR2SIA version validates the data entry for the Fields listed below. If data entered is not within valid range,
the control will emit a long beep indicating that entry is rejected and will substitute the default value for the
invalid entry. The default value will be displayed on the keypad, and the control advance to the next field.
Note: Entering a number other than the one specified will give unpredictable results.
✻20 Installer Code
Enter 4 digits (0-9)
✻21 Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
✻22 Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
✻23 Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted) zones
✻24 RF House ID Code
00 = disable all wireless keypad usage
01-31 = House ID
✻25 Powerline Carrier Device
(X10) House ID
0 = A 4 = E 8 = I # + 12 = M
1 = B 5 = F 9 = J # + 13 = N
2 = C 6 = G # + 10 = K # + 14 = O
3 = D 7 = H # + 11 = L # + 15 = P
✻26 Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter zone
when Chime mode is activated)
1 = yes (chimes on fault of those zones assigned to Zone
List 3 when Chime mode on)
✻27 Real Time Clock Display
0 = do not display the time
1 = display the time
The Installer Code is used to enter the 4-digit Master Security
Code. See "Master Code" in the System Operation section for
procedure.
Note: LYNX-2SIA does not allow duplication of Installer code. If a
duplicate code is entered the entry is rejected and LYNX issues
single long beep indicating rejection. The old installer code remains
unchanged.
If enabled, security code is not required to arm the system. The
user simply presses and holds down the AWAY or STAY key to
arm.
This option allows the choice of either always backlighting the
keypad or turning the backlighting off after 10 seconds of
keypad inactivity.
All zones bypassed by this function will be displayed after the
bypass is initiated.
UL installations: must be 0 (no forced bypass)
The House ID identifies receivers and wireless keypads.
If a 5804BD/5804BDV Transmitter is to be used, a House ID
Code MUST be entered, and the keypad should be set to the
same ID.
Powerline Carrier Devices require a House ID. This field
identifies this House ID to the Control. The Powerline Carrier
Devices are programmed in field ✻80.
This option allows the installer to define the specific zones
intended to chime when faulted while the system is in Chime
mode. If enabled, these zones are defined in zone list 3 (see
✻81 Zone List Menu Mode).
Refer to the User’s Manual for setting the clock time and date.
- 21 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻29 Daylight Savings TimeStart/
End Month
0 = do not display the time
1 = display the time
✻30 Daylight Savings Time Start/
End week
0 = disable
1 = first weekend of month
2 = second weekend
3 = third weekend
4 = fourth weekend
5 = last weekend
6 = next to last
rd
7 = 3
from last
✻31 Single Alarm Sounding Per Zone
(per armed period)
LYNXR-2 SELECTIONS
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for a
given zone
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
Enter the appropriate start and end weekend of the month.
This field applies only to burglary zones (zone response types
1-5, 10), and affects long range radio reporting but does not
affect central station reporting.
Note: This field applies only to the bell and does not affect keypad
sounds.
UL installations: must be 0 (no limit)
LYNXR-2SIA SELECTIONS
0 = Alarm Sounding Per Zone will be the same as the
Swinger Shutdown” set in field *92
1 = limit alarm sounding to once per arming period for a
given zone
✻32 Sounder Timeout
0 = yes, sounder timeout after time programmed in field ✻33
1 = no sounder timeout; continue sounding until manually
turned off
This Control complies with NFPA requirements for temporal
pulse sounding of fire and carbon monoxide (CO) notification
appliances.
Temporal pulse sounding for a fire alarm consists of the
following: 3 pulses – pause – 3 pulses – pause – 3 pulses. . .
Temporal pulse sounding for a CO alarm consists of the
following: 4 pulses – pause – 4 pulses – pause – 4 pulses –
pause. . .
This field determines whether the external sounder will shut
off after time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
Fields ✻34–✻36: Fields *34, *35 and *36 are used to program different options in the LYNXR-2 and LYNXR2SIA controls. Please be sure that you use the correct field for the control being installed.
Note: The LYNXR-2 SIA control validates the data entered in fields *34 - *36. If the selection is not valid the control will emit a
single long beep indicating that the selection has been rejected. The control replaces the selection with the default
value which is displayed on the keypad.
✻34Exit Delay
LYNXR-2 SELECTIONS
00-99 = exit delay time in seconds
LYNXR-2SIA SELECTIONS
Entries from 45-97
Entered Value Delay in Seconds
45-96 45-96
97 120
The system will wait the time entered before sounding an
alarm if the exit door is left open after the system has been
armed.
UL installations: must be set for a maximum of 60 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep
indicating that the selection has been rejected. The control replaces
the selection with the default value “60”, which is displayed on the
keypad, and advances to the next field.
SIA: Exit Delay must be set to a minimum of 45 seconds.
- 22 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻35Entry Delay 01
LYNXR-2 SELECTIONS
00-99 = entry delay time in seconds.
LYNXR-2SIA SELECTIONS
Entries from 30-99
Entered Value Delay in Seconds
30-96 30-96
97 120
98 180
99 240
✻36 Entry Delay 02
LYNXR-2 SELECTIONS
00-99 = entry delay time in seconds.
LYNXR-2SIA SELECTIONS
Entries from 30-99
Entered Value Delay in Seconds
30-96 30-96
97 120
98 180
99 240
The system will wait the time entered before sounding alarm
upon entering if system is not disarmed.
UL installations: must be set for a maximum of 45 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep
indicating that the selection has been rejected. The control
replaces the selection with the default value “30”, which is
displayed on the keypad, and advances to the next field.
SIA The Entry delay must be set to a minimum of 30 seconds. The
sum of entry delay 1 entered in Field ✻35 and the burglary abort
window entered in ✻50 should not exceed 1 minute.
The system will wait the time entered before sounding alarm
upon entering if the system is not disarmed.
UL installations: must be set for a maximum of 45 seconds
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep
indicating that the selection has been rejected. The control
replaces the selection with the default value “30”, which is
displayed on the keypad, and advances to the next field.
SIA The Entry delay must be set to a minimum of 30 seconds. The
sum of entry delay 2 entered in Field ✻36 and the burglary abort
window entered in ✻50 should not exceed 1 minute.
AUDIBLE EXIT WARNING/QUICK EXIT (✻37)
Note: This field is not available on the LYNXR-2SIA control.
✻37 Audible Exit Warning/Quick Exit
Exit Warning Quick Exit
0 = no exit warning sound 0 = no quick exit
1 = provide exit warning sound
when armed AWAY
1 = allow quick exit
✻38 Confirmation of Arming Ding
LYNXR-2 SELECTIONS
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or RF
keypad only
LYNXR-2SIA SELECTIONS
0 = no arming confirmation ding after arming system by
LYNXR keypad or RF keypad
1 = arming confirmation ding after arming system by LYNXR
keypad or RF keypad
2 = arming confirmation ding after arming from RF keypad
only
Exit Warning: Sound consists of slow continuous beeps until
last 5 seconds, when it changes to fast beeps. The warning
sound will end at the termination of exit delay.
Quick Exit: If enabled, user can restart the exit delay time
after arming in STAY mode by entering the user code and
pressing the STAY key, or by pressing the STAY key if Quick
Arm is enabled. This avoids having the user disarm then rearm the system after allowing someone to enter or exit
LYNXR-2
Confirmation of arming is provided by a 1/2 second external
sounder “ding” that sounds when closing report is sent, or at
the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs
immediately after the system receives the RF transmission.
LYNXR-2SIA
Confirmation of arming is provided by a 1/2 second external
sounder “ding” .The confirmation ding only sounds when
LYNX is Armed Away or disarmed after being Armed Away.
If Option 1 is selected, confirmation of arming is provided by a
1/2 second sounder “ding” that sounds when closing report is
sent, or at the end of exit delay.
If Option 2 is selected the external sounder “ding” occurs
immediately after arming from an RF keypad.
Note: If LYNXR-2SIA is armed by RF button (key fob), a confirmation
ding occurs immediately after arming regardless of field *38
settings. If LYNX is disarmed by RF button (key fob), additional
disarming confirmation ding is provided. The ding occurs
immediately after disarming and is longer than arming
confirmation ding.
- 23 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
Field ✻39: Field *39 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls.
Please be sure that you use the correct field for the control being installed.
✻39 Power Up In Previous State
Note: This field applies only to the LYNXR-2 control.
LYNXR-2 SELECTIONS
0 = always power up in a disarmed state
1 = assume the system status prior to power-down
DIALER PROGRAMMING (✻40–✻50)
Fields ✻40,✻41,✻42: Enter up to the number of digits shown. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13
for a pause
controls. Please be sure that you use the correct field for the control being installed.
(2 seconds).
Field *40 is used to program different features in the LYNXR-2 and LYNXR-2SIA
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted, and any bypassed zones will be
unbypassed.
Note: If the previous state was armed AWAY or STAY, the system will
not respond to sensor changes for 1 minute, which allows time for
sensors such as PIRs to stabilize.
UL installations: must be 1 (power up in previous state)
Sets the maximum amount of time in which two cross zones
must be tripped in an armed system to send an alarm message
to the Central Station. If only one cross zone is tripped during
this time, a trouble message (CID code 380) for that zone is
sent to the Central Station. Program Zone list 2 (using *81
Zone List Menu Mode) with the two zones that are to be cross
zoned.
Notes: (1) If option ✻39 is set to “0” (no cross zoning) then Zone List 2
can be used for other purposes.
(2) Cross zoning will be disabled during entry and exit delays, if
there is already an alarm in the system, if one or both of the 2
cross zones is bypassed.
If one of the 2 cross zones faults and remains faulted after the
cross zone time interval, the second cross zone can go into
alarm immediately, even after the cross zone time. This is to
detect scenarios involving multiple break-ins of a premises.
UL This option is not for use in UL installations.
Notes: Whenever AAV is used, primary (field ✻41) and secondary (field ✻42) phone numbers should be preceded with the
call waiting disable command. Otherwise, there is the possibility of connection of the third party to LYNXR-2 Series
during AAV mode. The
PABX phone number entered in field ✻40 is not dialed on GSM/IP (Digital Communication
with AAV). However, it is used for dialing on Telco Line.
✻40 PABX Access Code/Call Waiting
Disable
LYNXR-2 SELECTIONS
PABX Access Code
Enter up to 6 digits if PABX is needed to access an outside
line.
LYNXR-2SIA SELECTIONS
PABX Access Code/Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an outside
line.
or
Enter“# + 11 + 7 + 0” to program the touch-tone sequence
“*70” and cancel call waiting.
If fewer than 6 digits need to be entered, exit by pressing [✻].
To clear entries from field, press ✻40✻.
LYNXR-2SIA ONLY
Call Waiting: If the subscriber’s phone service has “call
waiting” (and is not using PABX), enter the touch-tone
sequence“*70” (or similar depending on the phone service). By
programming “# + 11 + 7 + 0” as the PABX entry to disable
“call waiting” during control panel calls. You must also enable
the Call Waiting Cancel option in field *47.
If the subscriber does not have “call waiting” and is not using
PABX, make no entry in this field.
Important Note:
Note: PABX number and operation of the control panel with a PBX
system cannot be used if the Call Waiting Cancel Disable option
has been enabled in Field ✻47.
If Call Wait Cancel is disabled in Field
Disable command is entered in Field ✻40, this will
prevent successful communication to the central station
when used on a non-call waiting line.
✻47, and Call Wait
- 24 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
If the GSM/IP (Digital Communication with AAV) feature is used (options 5 and 7 in *55), there may be restrictions when
dialing the numbers entered in *41, *42 and *46 (i.e.; #, ✻, pause may not be allowed, or phone number extensions may
not be dialed, etc) depending on the service provider.
✻41 Primary Phone No.
Enter up to 20 digits.
✻42 Secondary Phone No.
Enter up to 24 digits.
All four digits of the Subscriber Account number must be entered in Fields ✻43 and ✻44. If ten-digit format is
selected in ✻48 (option 5), all ten digits of the Subscriber Account number must be entered.
Fields ✻43 and ✻44:
Enter [✻] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as
the first digit of a 4-digit account number for Nos. 0000–0999. Enter [✻] as the fifth digit if a 4-digit account
number (for 4+1, 4+2 CID®) is used. Exit field by pressing [✻] if only 3 digits are used. To clear entries from
field, press ✻43
✻ or ✻44✻
. See blank Programming Form for examples of account number entries. If using
the paging feature, do not enter a leading 0 in the subscriber account number, and do not use digits A-F
anywhere in the number. Some paging systems provide voice mail capability, which is activated by a leading
0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; or # +15=F.
✻43Primary Subscriber Account No.
Enter a four or ten digit account number.
✻44 Secondary Subscriber Account No.
Enter a four or ten digit account number.
Field ✻46: Enter up to 24 digits. Do not fill unused spaces. Enter 0-9, #+11 for ‘*’; #+12 for’#’; #+13 for a
pause (2 seconds).
✻46“Follow Me Reminder” Phone No.
Enter up to 24 digits.
If fewer than 20 digits entered, exit by pressing [✻]. To clear
entries from field, press ✻41✻.
Note: Backup reporting (8 attempts are made to the secondary phone
number if no kissoff is received after 8 attempts to the primary
number) is automatic only if there is a secondary phone number
(field ✻42).
If fewer than 24 digits entered, exit by pressing [✻]. To clear
entries from field, press ✻42✻. See backup reporting note for
field ✻41. If using the paging feature, enter the pager phone
number here.
Enter the primary subscriber account number.
✻43✻
To clear entries from field, press
Enter the primary subscriber account number.
To clear entries from field, press
This option allows the user to schedule a time driven message.
When activated the system will dial the phone number
programmed and deliver a voice message (custom words 72, 73
and 74). This option is only supported when the pager or follow
me feature is enabled in field
If using the Follow Me Reminder feature, enter the phone
number here. If fewer than 24 digits are entered, exit by
pressing [
The telephone message can be terminated (acknowledged) by
pressing any key on the telephone keypad. Pressing any key
on the local LYNXR-2 Series keypad will terminate
(acknowledge) both the follow me and the local reminder
announcements.
Note: The follow me reminder announcement will be terminated if
any other event requires the system to dial out or if an audible
alarm has occurred.
✻
]. To clear entries from the field press ✻46✻.
✻
.
✻44✻
.
49 (option 6-9 or 10-13).
- 25 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
Fields ✻47:Field *47 is used to program different options in the LYNXR-2 and LYNXR-2SIA controls. Please
be sure that you use the correct field for the control being installed.
✻47 Phone System Select
LYNXR-2 SELECTIONS
Central Dialing Mode
Station Pulse Tone Pulse Tone
No
WATS
WATS 2 = No
0 = No
Speaker
Phone
Speaker
Phone
1 = No
Speaker
Phone
3 = No
Speaker
Phone
4 = With
Speaker
Phone
6 = With
Speaker
Phone
5 = With
Speaker
Phone
7 = With
Speaker
Phone
LYNXR-2SIA SELECTIONS
Central Dialing Mode
Station Pulse Tone Pulse Tone
No
WATS
WATS 2 = No
No
WATS
WATS 10 = No
0 = No
Speaker
Phone
Call Wait
Cancel
Disabled
Speaker
Phone
Call Wait
Cancel
Disabled
8 = No
Speaker
Phone
Call Wait
Cancel
Enabled
Speaker
Phone
Call Wait
Cancel
Enabled
1 = No
Speaker
Phone
Call Wait
Cancel
Disabled
3 = No
Speaker
Phone
Call Wait
Cancel
Disabled
9 = No
Speaker
Phone
Call Wait
Cancel
Enabled
11 = No
Speaker
Phone
Call Wait
Cancel
Enabled
4 = With
Speaker
Phone
Call Wait
Cancel
Disabled
6 = With
Speaker
Phone
Call Wait
Cancel
Disabled
12 = with
Speaker
Phone
Call Wait
Cancel
Enabled
14 = With
Speaker
Phone
Call Wait
Cancel
Enabled
5 = With
Speaker
Phone
Call Wait
Cancel
Disabled
7 = With
Speaker
Phone
Call Wait
Cancel
Disabled
13 = With
Speaker
Phone
Call Wait
Cancel
Enabled
15 = With
Speaker
Phone
Call Wait
Cancel
Enabled
✻48 Report Format for Primary/
Secondary
Primary Secondary
See choices below See choices below
0 = 3+1; 4+1 ADEMCO Low Speed Standard
1 = 3+1; 4+1 Radionics Standard
2 = 4+2 ADEMCO Low Speed Standard
3 = 4+2 Radionics Standard
5 = ADEMCO Contact ID® Reporting with 10-digit subscriber
account number
6 = 4+2 ADEMCO Express
7 = ADEMCO Contact ID® Reporting with 4-digit subscriber
This option is used to enter the correct type of phone dialing
(pulse or tone), and to select the correct WATS line option for
the Central Station. This option is used to activate the Speaker
Phone option. For the LYNXR-2SIA it is also used to disable
call waiting.
Note: If using pulse dialing, you must enter the numbers slowly in
order to allow the pulse dialer time to operate.
LYNXR-2SIA ONLY
Call waiting warning tones can interfere with Central stations
reporting. The Call Waiting Cancel option should be selected if
the reporting phone line has call waiting service. The Call
Waiting Cancel command must also be programmed in Field
✻
40. If the Call Waiting Cancel feature is enabled, make sure to
enter Call Waiting Cancel command in Field
✻
40. The command
depends on a telephone service provider.
Important
Note: If Call Wait Cancel is disabled in Field
✻47, and
Call Waiting Disable command is entered in Field
✻40, this will prevent successful communication
to the central station when used on a non-call
waiting line.
Note: PABX number and operation of the control panel with a
PBX system cannot be used if the Call Waiting Cancel
option has been enabled in Field ✻47.
Enter ✻ as the 4th digit of ✻43 through ✻44, if 3+1 dialer
reporting is to be used. (For an explanation of these formats, see
the System Communication section of this manual.)
Notes: (1) The maximum number of alarm and alarm restore
reports during one armed period is determined by field
✻
(2) If Option 5 is selected a 10-digit account number must
92.
be entered in Fields ✻43 or ✻44.
(3) Option 5 or 7 (ADEMCO Contact ID® Reporting) must
be selected for AAV.
- 26 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻49 Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary fails,
1 = Alarms, Restore,
Cancel
2 = All except Open/Close,
Test
3 = Alarms, Restore,
Cancel
4 = All except Open/Close,
Test
5 = All reports All
To Primary To Paging Number
6 = All reports except
Open/Close
7 = All reports Alarms, Troubles
8 = All reports Alarms, Open/Close ‡,
9 = All reports except
Open/Close
To Primary
10= All reports except
Open/Close
11 = All reports Alarms, Troubles
12= All reports Alarms, Open/Close ‡,
13= All reports except
Open/Close
*Recent close report is sent to primary number
‡
Will report Users 0, 5-8, and, if using wireless button-type
devices, will report the zone number of the arm or disarm
button 26-33. All other zones and users are not reported.
then all
Others
Open/Close, Test
All
All
Alarms, Open/Close ‡,
Troubles
Troubles
Open/Close ‡
To Follow Me System
Phone Number
Alarms, Open/Close ‡,
Troubles
Troubles
Open/Close ‡
This field is used to select a reporting option as follows:
Enter: 0 - 5 when reporting to telephone receivers.
6 - 9 when reporting to a pager is desired.
10 - 13 when reporting to an aux telephone receiver.
Note: If you are installing a communications module that has
voice communications capability (i.e.; GSMVL), refer to
Field *55 notes for additional information.
Pager Report Format
Options 6-9 send reports to the primary phone number, in a
format defined in Field ✻48, and send reports to a pager, which
has its phone number entered as the secondary phone number
in Field ✻42. The pager report is a 7-digit code, with optional
16-digit prefix, in the following format:
AAAAAAAAAAAAAAAA-EEE–0NNN where:
AAA = Optional 16 digits for PIN number, etc. See Field ✻88 for full
EEE = 3-digit Event Code as follows:
911 = Alarm (NN = zone number)
101 = Open, system disarmed (NN = user no.)
102 = Close, system armed (NN = user no.)
811 = Trouble (NN = zone no.)
0 = Always displayed before 3-digit user/zone no.
NNN = 3-digit user number or zone number, depending on the type of
description of these characters.
event (EEE) that occurred.
Follow Me System Report Format
Options 10-13 send reports to the primary phone number, in a
format defined in Field ✻48, and sends voice message to the
secondary phone number entered in Field ✻42.
The message is a repeatable system status announcement. If
the manual paging option has been programmed in Field ✻87,
the message will repeat “system, system…..”.
The message can be terminated by pressing any key on the
telephone keypad.
Field ✻50: Field *50 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls.
Please be sure that you use the correct field for the control being installed.
✻50 15-Second Dialer Delay (Burglary)
Note: This field applies only to the LYNXR-2 control.
LYNXR-2 SELECTIONS
0 = no dialer delay
1 = provide 15-second delay of burglary alarm report when
armed away
If enabled, provides delay of burglary report to the central
station, and allows time for the subscriber to avoid a false
alarm transmission. The delay applies only to zone type 3 and
5 alarms and not to zone type 24 alarms (silent burglary) or to
24-hour zone types 6, 7, and 8 (silent panic, audible alarm,
auxiliary alarm), which are always sent as soon as they occur.
UL installations: must be 0 (no delay)
This provides the option for an Abort Window for Burglary
zone types that report to the central station. This feature
allows time for the subscriber to avoid a false alarm
transmission. This feature does not apply to zone type 9 or 16
alarms (Supervised Fire) or to 24-hour zone types 6, 7, and 8
(silent panic, audible alarm, auxiliary alarm), which are
always sent as soon as they occur.
SIA The burglary abort window must be set to a minimum of 15
seconds. The sum of the burglary abort window entered in
✻50 and the entry delays entered in either Field ✻35 or ✻36
should not exceed 1 minute.
Note: The LYNXR-2SIA control validates the data entered in this
field. If the selection is not valid the control will emit a single long
beep indicating that the selection has been rejected. The control
replaces the selection with the default value “2”, which is
displayed on the keypad, and advances to the next field.
- 27 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻51 Periodic Test Report
0 = no test report
1 = once every 24 hrs
2 = weekly
3 = once every 30 days
✻52 First Test Report Offset
0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
0 = Disabled 4 = 90 days
1 = 1 day 5 = 180 days
2 = 7 days 6 = 365 days
3 = 27 days
Note: There is no local annunciation indicating that this
report has been sent to the Central Station.
Test report code entered in field ✻64 is sent.
Select the time for the first report following programming or
downloading.
If disabled, selects Radionics, which uses hexadecimal 0-9, B-F
reporting.
If enabled, selects Sescoa, which uses only numeric reporting (0-
9). Select 0 for all other formats.
If enabled, notifies the central station if an end user is not
operating their security system by sending a System Inactivity
report 654. The report will be sent only to the Primary phone
number and only if Contact ID® format was selected.
Note: The report will follow the ✻49 = 0 rules, no matter which
selection was made in ✻49.
Field ✻55: If AAV is enabled in *91, depending on Communication Channels programmed in *55, only the
Reporting options from the table below are available. They should be programmed as described in Dynamic
Signaling (field *77). If AAV is disabled in field *91, reporting options 5 and 7 are not available.
If Follow Me System or Pager features are selected, AAV will not be available even if enabled in *91 UNLESS
option 5 is selected in *55 (Radio only). If option 5 is selected in *55, AAV will be established on the primary
channel because Follow me System and Pager are not available on the radio’s audio channel.
The following table shows the only valid combinations of communication channels and reporting options. It
is the responsibility of the installer to ensure that a valid combination is programmed.
Reporting Option
Primary Phone only Y/N 0 = Telco Line only (no radio) (see Note 1)
Redundant reports to both channels Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
Primary Phone is the preferred channel Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
LRR/IP is the preferred channel Y/N 1 = LRR/IP (Digital Communication only) and Telco Line (see Note 1)
LRR/IP Only N 3 = LRR/IP (Digital Communication only) (no Telco Line) (see Notes 2 & 3)
Y 5 = LRR/IP (Digital Communication w/AAV) (Telco Line connections for 2-way
NOTES
1. AAV mode can be established only on Telco Line.
2. Follow me System, Follow me Reminder and Pager features are not supported. These features will not work if selected in *49.
3. Speaker Phone and Remote Phone Access are not available. These features should be disabled in *47 and *91. Download over the
Phone Line feature is also unavailable.
4. AAV mode can be established only on LRR/IP (Digital Communication with AAV Capabilities)
Legend
LRR/IP (Digital Communication only) = Digital GSM Communication Channel
LRR/IP (Digital Communication with AAV) = GSM Communication Channel with voice capabilities (a radio with voice capabilities is required
to use the voice capabilities)
Telco Line = Land Phone Line
AAV
Enabled? *55 Communication Channel
voice session only, if applicable) (see Notes 2, 3, 4)
- 28 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻55 Reporting Channels
0 = Telco Line (no Radio)
1 = LRR/IP(Digital Communication only) and Telco Line
3 = LRR/IP (Digital Communication only) (no Telco Line)
5 = LRR/IP (Digital Communication with AAV) (Telco Line
Connections for 2-way voice seesion only, if
applicable)
This option is used to enable/disable Central Station reporting via
the LRR/IP Communications Device (See Field *77). Upload/
download via the Internet IP module is not affected by this entry.
The option specifies the channel that the control will use when
sending reports to the Central Station (Follow Me phone, and
Pager). Select some or all channels as required.
IMPORTANT NOTE
Make sure that selected channels are physically available and
functional.
Note: Zone 103 can not be bypassed.
Field ✻57: Field *57 only applies to the LYNXR-2SIA control.
✻57 False Alarm Options
Note: This field applies only to the LYNXR-2SIA control.
0 = no jam detection
1 = RF jam detection with event logging, but no central
station report
2 = RF jam detection with event logging and with central
station report (if trouble/restore report is enabled in
fields ✻60, ✻71)
Note: The LYNXR-2SIA control validates the data entered in this field. If the
selection is not valid the control will emit a single long beep indicating
that the selection has been rejected. The control replaces the selection
with the default value “7”, which is displayed on the keypad, and
advances to the next field.
Cancel Alarm Display
This option enables the display of aborted and cancelled alarms on the
LYNXR-2SIA keypad. “CA” will be displayed.
Notes: 1. An abort occurs if the alarm panel is disarmed before it dials the
2. A cancel occurs if the alarm panel is disarmed after the alarm is
3. Zone types 5, 6 and 7 (panic zone types) and 24 (silent burglary)
Auto Stay Arming
If this feature is enabled and the control panel has been armed “Armed
Away” at the LYNX keypad or RF keypad, the system will switch to the
“Armed Stay” mode if the Exit Time has expired and no exit has been made.
Exit Time Restart-Exit Delay Restart/Reset
This option allows the systems to restart the exit delay time
after arming in STAY mode by entering the User Code and pressing the
STAY key (if quick arming is disabled) or by pressing the STAY key (if
quick arming is enabled). This option also enables automatic exit delay
reset, which resets exit delay if the entry/exit door is re-opened and closed
before exit delay time expires after arming.
Notes: 1. This avoids the need to disarm and then re-arm the system after
2. Automatic Exit Delay Reset occurs only once during an armed
For Event Logging, Option 2 must be selected.
If the control detects an RF Jam condition, a “FAULT” message appears for
zone 90. The Contact ID® code for RF Jam is 344.
alarm report to the central station.
reported.
cannot be cancelled.
allowing someone to enter or exit.
period.
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (✻59 – ✻76, & ✻89)
Program Report Codes using the interactive *56 Enhanced Zone Programming Mode, or codes can be entered in data
fields *59-*76 and *89. Use the following guidelines when programming report codes. The actual report code digits
entered depend upon the particular installation, and should be in agreement with you and the central station office
receiving the signals.
Field *59 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls. Please be sure
that you use the correct field for the control being installed.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A
(reports a “0” on some receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the
first box will disable a report. Entering "0" in the second box results in automatic advance to the next field.
- 29 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above.
Entering "0" in the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for
that report.
With ADEMCO Contact ID® Reporting: Enter a digit in the first box to enable the zone to report. Use a different
digit for each zone until you have used up available digits. If the number of zones exceeds the number of available
digits, begin with digit 1 again. This is an "enabling" code only and is not the actual code sent to the central station
office. Entries in the second boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all
the system conditions you want to send to the central station. A "0" in the first box disables the report.
For the LYNXR-2SIA control the *59 Exit Error Report Code and *68 Cancel Report Code options are always enabled. A report
code can be entered if reporting formats other than Contact ID
SYSTEM STATUS REPORT CODES (✻59–✻68)
✻59 Exit Error Report Code
LYNXR-2SIA ONLY
Always enabled, a report code can be entered if reporting
formats other than Contact ID ® are used.
(See notes above)
✻60Trouble Report Code
(See notes above)
✻61Bypass Report Code
If the system is armed and an entry/exit or interior zone is still open after
the exit delay time has expired, an alarm will sound at the keypad and
external sounder. If the system is disarmed before the end of the entry
delay that immediately follows, the alarm sounding will stop and no
message will be sent to the central station. The keypad will display “CA
(CANCELED ALARM).”
If the system is not disarmed before the end of the entry delay mentioned
above, and an entry/exit or interior zone is still open, an “exit alarm”
message will be sent to the central station if an Exit Error report code is
selected in this field. The keypad will display “EA (EXIT ALARM),” and the
alarm sounding will continue until the system is disarmed (or timeout
occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay, and an
“Exit Alarm” message will be sent to the central station.
If Contact ID® format has been programmed, the message will contain the
zone number and error code 374 (Trouble–Exit Error). If 4+2 format is
used, the digit entered in this field will be sent followed by the second digit
of the programmed alarm code for that zone. If 3+1 or 4+1 format is used,
only the digit entered in this field will be sent. This message will go to the
primary phone no. Under any of these conditions, no restore message will
be sent.
If “0” is entered in this field, no special message will be sent, only the
regular alarm and alarm restore code for the zone.
LYNXR-2SIA ONLY
If the system is armed and an entry/exit or interior zone is still open after
the exit delay time has expired, an alarm will sound at the keypad and
external sounder (the keypad will also display “EA”) , and the entry delay
begins. If the system is disarmed before the end of the entry delay that
immediately follows, the alarm sounding will stop and no message will be
sent to the central station. The keypad will display “CA “(CANCELED
ALARM) if the cancel display option was enabled in field ✻57.
If the system is not disarmed before the end of the entry delay mentioned
above, and an entry/exit or interior zone is still open, an “Exit Alarm”
message and a “Zone Alarm” message will be sent to the central station.
The keypad will display “EA (EXIT ALARM),” and the alarm sounding will
continue until the system is disarmed (or timeout occurs).
If Contact ID® format has been programmed, the message will contain the
zone number and error code 374 (Alarm–Exit Error).
Note: The LYNXR-2SIA control validates the data entered in this field. If the
This will be sent if a zone goes into trouble.
This will be sent when a zone is manually bypassed.
(See notes above)
® are used.
selection is not valid the control will emit a single long beep indicating
that the selection has been rejected. The control replaces the selection
with the default value “1”, which is displayed on the keypad, and
advances to the next field.
- 30 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻62 AC Loss Report Code
(See notes above)
✻63 Low Battery Report Code
(See notes above)
✻64 Test Report Code
(See notes above)
✻65 Open Report Code
(See notes above)
✻66 Arm Away Report Code
(See notes above)
✻67 RF Transmitter Low Battery
Report Code
Timing of this report is random with up to a 4-hour delay. If AC restores
before the report goes out, there is no AC restore report.
This will be sent when a low battery condition exists in the system’s
standby battery.
This is sent periodically to test that the communicator and phone lines are
operational (frequency of report is selected in field ✻51).
Note: The LYNXR-2SIA control validates the data entered in this field. If the
selection is not valid the control will emit a single long beep indicating
that the selection has been rejected. The control replaces the
selection with the default value “10”, which is displayed on the
keypad, and advances to the next field.
This is sent upon disarming of the system. 2nd digit = user number, if
expanded or 4+2 reporting is selected.
This option allows for independent programming of AWAY and STAY
reports. 2nd digit of report is user number if expanded or 4+2 reporting is
selected.
Note: OPEN reports are not sent if the associated closing report is not
enabled.
This is sent in the event that a wireless transmitter low battery condition
exists.
(See notes above)
✻68 Cancel Report Code
(See notes above)
LYNXR-2SIA ONLY
Always enabled, a report code can be entered if reporting
formats other than Contact ID ® are used.
This is sent upon disarming of the system after an alarm condition was
reported.
Note: The LYNXR-2SIA control validates the data entered in this field. If the
selection is not valid the control will emit a single long beep indicating
that the selection has been rejected. The control replaces the
selection with the default value “10”, which is displayed on the
keypad, and advances to the next field.
Field ✻69: Field *69 only applies to the LYNXR-2SIA control.
✻69 Recent Closing Report
LYNXR-2SIA ONLY
(This feature is always enabled. A report code can be
entered if formats other than Contact ID
® are used)
Sent when an alarm occurs within two minutes after exit delay expires.
Disarming the system within the two minutes stops the alarm sound and
the keypad displays the faulted zone number (and will display “CA” if
cancel display option in field *57 is enabled.) No messages are sent to the
Central Station.
If the system is not disarmed within two minutes, the alarm sound
continues and a “Recent Closing” and a “Zone Alarm” message are sent to
the Central Station (after dial delay expires).
Note: The LYNXR-2SIA control validates the data entered in this field. If the
selection is not valid the control will emit a single long beep indicating
that the selection has been rejected. The control replaces the
selection with the default value “1”, which is displayed on the keypad,
and advances to the next field.
RESTORE REPORT CODES (✻70–✻76)
✻70 Alarm Restore Report Code (1st
Digit)
(See notes above)
✻71 Trouble Restore Report Code
Sent when the zone that caused an alarm is restored to its non-faulted
condition. 2nd digit is automatically sent as the 2nd digit of the zone
alarm report code programmed in field ✻56, if expanded or 4+2 reporting
is selected.
Sent when a trouble in a zone is restored.
(See notes above)
✻72Bypass Restore Report Code
(See notes above)
✻73 AC Restore Report Code
(See notes above)
✻74 Low Battery Restore Report Code
(See notes above)
Sent when a zone that has been bypassed is unbypassed.
Sent when AC power has been restored after an AC power outage.
Sent when a system low battery condition is restored to normal.
- 31 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻75 RF Transmitter Low Battery
Restore Report Code
(See notes above)
✻76 Test Restore Report Code
DYNAMIC SIGNALING DELAY/DYNAMIC SIGNALING PRIORITY FIELD ✻77
Two report channels are used by the LYNXR-2 Series to support the LRR/IP communications device and
dynamic signaling. For the primary channel the device can communicate via AlarmNet GSM/IP or Cellular
communications devices. Secondary phone is not affected by dynamic signaling scheme. Two programming
options are used to define dynamic signaling behavior. Field *55 is used to enable/disable the LRR/IP
communications device and allows it to supervise the communications module. The two-digit option
programmed in Field *77 defines how dynamic signaling will function. The Dynamic signaling options are
shown as follows
Primary Phone only
Report is sent to Primary phone with No Dynamic Signaling
Delay
LRR/IP only
Report sent to communications device with No Delay
Redundant reports to both channels
Report independently goes to the Primary phone and LRR/IP
communications device with No Delay
Primary Phone is the preferred channel
First report is sent to the primary phone. If primary phone
fails to deliver report within the delay window defined in *77
all following reports go to both primary phone and
communications device with no delay. When report goes
through the primary phone, the control stops reporting to
communications device.
Note: The delay must be set to at least 30 seconds if Remote
LRR/IP is the preferred channel
First report is sent to the communications device. If device
fails to deliver report within to deliver report within the time
window defined in *77 all following reports go to both LRR/IP
device and primary phone with no delay. When report goes
through the LRR/IP device, the control stops reporting to
primary phone.
(See notes above)
To ensure that the LYNXR-2 Series properly transmits its reports to the Central Station via the proper channel you must
program a Primary Phone Number in Field *41 and/or activate/deactivate the LRR/IP Communications Module in Field *55.
The 15-Second Dialer Delay (Burglary), programmed in Field in *50 is independent of the delay selected in Field *77 and
applies to both telephone and communications device.
:
Reporting Option Enable/Disable
Phone Control and/or AAV is enabled.
Sent when a transmitter that previously sent in a “low battery”
message has sent a message indicating it no longer has a low battery
condition.
Sent when the test mode is exited. A restore code entered here will
cause a restore message to be sent when Test mode is exited.
Note: The LYNXR-2SIA validates the data entered in this field. If the
0 = Telco Line only
3 = LRR/IP (Digital
5 = LRR/IP (Digital
1 = LRR/IP (Digital
1 = LRR/IP (Digital
1 = LRR/IP (Digital
selection is not valid the control will emit a single long beep
indicating that the selection has been rejected. The control
replaces the selection with the default value “10”, which is
displayed on the keypad, and advances to the next field.
Device (Field *55)
(no Radio)
Communication
only) (no Telco
Line) OR
Communication
w/Voice
Capabilities)
(no Telco Line)
Communication
only) and Telco
Line
Communication
only) and Telco
Line
Communication
only) and Telco
Line
Dynamic Signaling Delay/Dynamic Signaling
(Field *77)
1st Entry
* = enter a delay for the first entry
2nd Entry
0 = Primary phone only
1st Entry
* = enter any non zero digit as a first entry
2nd Entry
2 = LRR/IP reporting only
1st Entry
0 = Redundant reporting on dialer and
communication device
2nd Entry
* = enter any number as a second entry
1st Entry
* = enter a delay for the first entry
2nd Entry
0 = Primary Dialer is the preferred channel
1st Entry
* = Enter any delay for the first entry
2nd Entry
1 = LRR/IP is the preferred channel
- 32 -
1. If the LRR/IP communications device is selected as the preferred channel option and the APX32EN detects a
communication failure or supervision failure, reports will be sent to the Primary Phone without any delay.
2. If AAV is selected and LRR/IP communications device is enabled, you must enter "0" (primary dialer preferred
channel) as the second entry in Field *77.
✻77Dynamic Signaling Delay/ Dynamic
Signaling Priority
1st Entry (delay before switching Central Station reporting
path)
0 = Aux key performs defined function (macro)
1 = Aux key sends predefined message to pager or a voice
message to Follow Me system phone number
✻88 Pager Characters
Enter up to 16 digits that will appear in front of the 7-digit
pager message.
Enter [#] + [11] for “*”
Enter [#] + [12] for “#”
Enter [#] + [13] for 2-second pause
Note: Verify that the pager supports [*] and [#] characters
before using them. Some pagers require an
additional delay [pause] in order to receive the entire
message
✻89 Event Log 80% Full Report Code
(See notes above)
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
Intended for use with LRR/IP communication device reporting.
This field’s 1st Entry allows you select the time-out period the panel will
wait for acknowledgment from the first reporting destination (preferred
channel) before it attempts to send a message to the second destination.
This delay is per message. The 2nd entry allows you to select the
(Dynamic Signaling Priority) preferred reporting channel.
Notes: (1) You must also enable/disable LRR/IP Device in field *55.
(2) If Remote Phone Access is enabled, and Primary Phone is used
(3) For UL installations Dynamic Signaling Delay cannot exceed 15
1st Entry
Enables Dynamic Signaling Delay. The entry of digits 1-9 or #10-#15.
Delays can be selected from 0 to 225 seconds, in 15-second increments. If
0 is entered, the control panel will send redundant reports to both
Primary Dialer and the LRR/IP communications device.
2nd Entry
The second entry determines the alternate Central Station
communication path that will be initiated after the time-out period.
This field is used to set the time delay between when a connection is
established on a Radio (digital communication with voice capabilities)
session to when the 2100 Hz “training” tone is terminated. Enter any
digit between 00 and 99.
Note: This field only applies when a GSMVL radio is installed in the
Enable if using AlarmNet Remote Services e-mail notification (multimode) feature. The address(es) used must also be enabled in the
AlarmNet communication device. For more information refer to the
instructions provided with the Communications Device being installed.
If “0” is entered, user can define a macro function for the AUX key. See
user manual for description of the use of this key.
If “1” is entered, you must also select an option in field ✻49. The options
are 6-9 for the pager or 10-13 for the follow me system announcement.
The actual pager message is 999-9999. Note that the hyphen may not be
displayed, depending on the pager service. The manual follow me system
announcement is a repeatable “System, System…..”.
Note: A macro cannot be run from the Test mode.
If entered, these digits will appear in front of the 7-digit pager message
sent by the control (either upon a system event or upon pressing the
AUX key [if programmed for paging]), and during latch key report (if
enabled during scheduling). These digits can consist of a PIN number,
account number, pauses or special digits needed by the pager (these
types of characters are not displayed), or any other characters the user
chooses that will be displayed (e.g., using a character code to distinguish
between control panel messages and other pager messages).
You do not need to fill all 16 digits. Press [✻] + next field number to exit
the field. To clear the field, press ✻88✻.
See field ✻87 to select the AUX key Paging feature. See field ✻49, which
must have an option 6-9 selected to enable paging messages, for
description of the pager message.
If an Event Logging selection is made in field ✻90, a message can be sent
to the central station receiver when the log is 80% full. If the log becomes
full, a new message will overwrite the oldest message in the log.
Note: All control and readout from the log, aside from the selection made
as a Preferred Channel, Dynamic Signaling Delay should be at
least 30 sec in order to prevent duplicate reports.
sec. If Primary Phone is used as a Preferred Channel, duplicate
reports may sent.
control. Otherwise, enter “00” to disable.
by the installer in field ✻90, is accomplished via the downloader.
- 33 -
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
✻90 Event Logging Options
0 = No event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of entries)
✻91 Audio Alarm Verification (AAV)/
Remote Phone Control
0 = none
1 = AAV and remote phone control
2 = remote phone control only
4 = AAV only
Notes: (1) For UL installations Audio Alarm Verification
(2)Audio Alarm Verification will only function when
(3) AAV and Remote Phone Control features can
cannot be used.
Contact ID® is selected.
only be used if the central station or remote
phone supports DTMF commands.
Example: To select “Alarm/Alarm Restore” and “Open/Close,” enter 9 (1
+ 8); to select all events, enter #15.
Default “3” = alarm/alarm restore (1) plus trouble/trouble restore (2).
The system has the ability to record various events in a history log (84event capacity). The types of events to be logged can be selected as
indicated. At any time, the downloader operator can then upload the
log and view or print out all or selected categories of the log. The log can
also be cleared by the download operator.
The display/printout at the central station will show the date, time,
event, and description of the occurrences.
Note: System messages are logged when any non-zero selection is
made.
This option is used to enable the Audio Alarm Verification and/or the
Remote Phone Control features.
Notes: (1) In order to activate the Remote Phone Control feature and
(2) Remote phone session will be terminated if a report must be
(3) Alarm Audio Verification will only function when Contact ID® is
(4) If an alarm will be reported to primary and secondary phone
(5) If an alarm will be reported to a pager (6-8 in field ✻49), or to
(6) If AAV is selected and LRR/IP communications device is
defeat an answering machine, ensure that the correct ring
detection count (“15”) has been programmed in field ✻95.
sent.
selected. AAV cannot be used for UL installations.
numbers, AAV can only function via the secondary number.
follow me phone number (10-12 in field ✻49) AAV cannot be
used.
enabled, you must enter "0" (primary dialer preferred channel)
as the second entry in Field *77
Field ✻92: Field *92 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls.
Please be sure that you use the correct field for the control being installed.
✻92 Number of Reports In Armed Period
Note: This field applies only to the LYNXR-2 control.
LYNXR-2 SELECTIONS
0 = reports limited to a total of 10
1 = unlimited number of reports
✻92 Swinger Shutdown
Note: This field applies only to the LYNXR-2SIA
control.
LYNXR-2SIA SELECTIONS
1 = shutdown after one alarm
2 = shutdown after two alarms
✻93 Flexible Callback
0 = no flexible callback
1 = last digit flexible
2 = last 2 digits flexible
3 = last 3 digits flexible
This option can be used to limit the number of messages (alarm & alarm
restore reports) sent by the LYNXR-2 to the central station in an armed
period.
UL installations: must be 1 (unlimited reports)
This option is used to define number of alarm reports sent for non-fire
zones, after which the LYNXR-2SIA ignores subsequent alarms of the
zone during the same armed period. The zone swinger counter is reset
after the zone alarm is erased from alarm memory (after two CODE +
OFF).
Note: The LYNXR-2SIA control validates the data entered in this field. If
the selection is not valid the control will emit a single long beep
indicating that the selection has been rejected. The control replaces
the selection with the default value “1”, which is displayed on the
keypad, and advances to the next field.
Note: This feature only applies to telephone downloading
If enabled, the control will ignore the last 1, 2, or 3 digits of the
programmed callback number (field ✻94) during a single download
session. This allows the download operator to temporarily change the
callback phone number by the number of digits selected, which allows
the control to call back similar, but different numbers during a single
session. For example, if downloading to a large number of controls, the
operator can command the controls to call back phone numbers 5551111, 555-1112, 555-1113, etc., thus spreading the communications
among several computers.
- 34 -
DOWNLOAD INFORMATION (✻94, ✻95)
✻94 Download Call Back Phone Number
Enter up to 20 digits as follows: 0–9, # +11 for “*”, # + 12
for “#”, # + 13 for a pause.
✻95 Ring Detection Count For
Downloading/ Remote Phone Control
0 = disable station initiated download and remote phone
1-14 = number of rings before control picks up phone line
15 = defeat answering machine
LYNXR-2 Series Installation and Setup Guide
Data Field Descriptions
This is the phone number the control will use to call back the
downloading computer.
Do not fill unused spaces. End field by pressing ✻. To clear entries from
field, press ✻94✻.
Enter “15” to select defeat answering machine mode. If an answering
machine is on the premises, you need to dial the premises and hang up
on the first ring. Wait at least five (5) seconds (but no more than 22
seconds) and dial the premises phone number again. The control will
pick up and announce “SYSTEM ENTER CODE” every three seconds.
Note: To enter a number higher than 9 you must first press the [#] key.
- 35 -
LYNXR-2 Series Installation and Setup Guide
✻
56 Enhanced Zone Programming Mode
This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes,
and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter
serial numbers.
Note: There are two methods for entering transmitter serial numbers. The first method is by using ✻56 Enhanced Zone
While in Program mode, press
Programming Mode (described below). The second method is by using ✻83 Enhanced Sequential Mode. Note that the
✻83 Enhanced Sequential Mode requires that all zone information first be entered using ✻56 Enhanced Zone
Programming mode.
✻56 to enter Zone Programming Menu Mode. You must refer to these
instructions or to the Program Form while programming the system because the keypad display does
not show prompt titles. Instead, prompts are indicated by a number/letter combination.
The prompts for
✻56 are as follows:
A 02 Zone Number -----------------------for entering the zone number
b Zone Type --------------------------for entering zone type
C Report Code -------------------------for entering the zone’s report code
d Input Type --------------------------for entering the transmitter’s input type
E Loop Number -----------------------for entering the transmitter loop number
F Delete Serial Number?-----------for deleting existing serial number
1A Enroll Mode? ------------------------selects serial number enroll mode
1b Serial Number----------------------for entering transmitter’s serial number
1d Descriptor 1 -------------------------for entering first descriptor word
1E Descriptor 2 -------------------------for entering second descriptor word
1F Descriptor 3 -------------------------for entering third descriptor word
- 36 -
LYNXR-2 Series Installation and Setup Guide
✻
56 Enhanced Zone Programming Mode
Refer to the zone assignment table for ✻56 on the separate programming form.
The following explains the
✻56 prompts in detail. The left column identifies the prompts and lists the
available entries for each. The right column provides a further explanation of the entries.
Note: You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to
clearly hear feedback announcements or system beeps.
ZT16 is only available on the LYNXR-2SIA version of the control panel.
A 02
Zone Number
02-41, 95, 96, 99 = Zone number
[✻] = continue
00 = exit Zone Programming mode
bzt
Zone Type
00-24 = zone type
[✻] = continue
[#] = return to previous prompt
Note: If 00 is accepted as a zone type, save
the 00 zone type and advance to the
confirm delete prompt (F).
C rc
Report Code
Enter the report code for this zone.
[✻] = continue
[#] = return to previous prompt
di
Input Type
3 =RF (supervised RF) – sends periodic
check-in signals, faults, restore and low
battery signals
4 = UR (unsupervised RF) – sends same as
“RF” type, but control does not supervise
the check-in signals
5 = BR (button type) – sends only fault and
low battery signals; does not send
restores or check-in signals
[✻] = continue
[#] = return to previous prompt
Enter the 2-digit zone number to be programmed and the Voice Descriptor for the
selected zone number will be announced, if it is programmed. Press [✻] to advance.
• Zones 02-25 = RF zones (only)
• Zones 26-41 = Button zones (only)
• Zone 92 = Duress
• Zones 95, 96, 99 = Panic zones
Pressing 00 exits mode, upon which the prompt “56” blinks, indicating the mode is
inactive. Press [✻] + any field number to go to that field.
Each zone must be assigned to a zone type, which defines the way in which the system
responds to faults in that zone. Enter the 2-digit zone type for this zone as follows:
00 = Not Used 09 = Fire without verification
01 = Entry/Exit #1 10 = Interior w/Delay
02 = Entry/Exit #2 14 = Carbon Monoxide
03 = Perimeter 16 = Fire with verification
04 = Interior Follower 20 = Arm–Stay
05 = Trouble Day/Alarm Night 21 = Arm–Away
06 = 24 Hr Silent 22 = Disarm
07 = 24 Hr Audible 23 = No Alarm Response
08 = 24 Hr Aux 24 = Silent Burglary
-
Notes: (1) ZT16 is only available on the LYNXR-2SIA version
(2) ZT16 is not for use with manually actuated devices including fire, keypad or
SIA ZT 16 must be used in SIA fire applications.
The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C", enter [0][3] for "3" and [1][2]
for "C".
If this is Zone 95, 96 or 99, the system skips to the VOICE DESCRIPTOR prompt (1C).
Enter the input type for the transmitter assigned to this zone. Refer to the
transmitter’s instructions for input types of each transmitter.
Notes: (1)RF type transmitters must remain within range of the receiver, otherwise a
(2) UR and BR type transmitters may be carried off premises (out of range
(3) Zones 2-25 should be assigned Input Type 3 or 4. Zones 26-41 should be
key fob zones, or fire pull stations, or for heat detectors.
supervision failure signal will occur.
without causing a supervision failure.
assigned Input Type 5 only.
- 37 -
LYNXR-2 Series Installation and Setup Guide
✻
56 Enhanced Zone Programming Mode
E l
Loop Number or Loop and
Serial Number
(if using RF Learning)
1-4 = loop number for the zone of the
transmitter being entered.
0 + [✻] = continue to DELETE ZONE
PARAMETERS CONFIRMATION
prompt (F)
[✻] = continue to the ENROLL MODE prompt
(1A) if not entered, or VOICE
DESCRIPTOR prompt if already entered
prompt (b), 00 will be retained and
system will advance to prompt (1C).
This prompt can be used to enroll loop number and serial number via RF transmission
or the loop number can be enrolled manually. If using the RF Learning Mode, there is
no need to manually enter a loop number. Proceed directly to RF Learning
Notes: (1) BR type devices cannot be enrolled by using UR or RF type. Likewise, UR or
(2) Once encrypted (high-security) devices have been enrolled they must be
RF Learning - Two (2) transmissions (2 key depressions) at least 5 seconds apart
will be required for BR type devices (device type 5). Two beeps will sound after the
second transmission, confirming that the loop number and serial number have been
learned.
For all other device types, four (4) transmissions are required (fault, restore and fault,
restore). A single beep will sound after the second transmission confirming that the
loop and serial number have been captured. Following the fourth transmission the
system will confirm that the loop number and serial number have been learned and
announce the Voice Descriptor for the zone, if it is programmed, followed by two
beeps.
Press [✻] to continue.
Manual Entry - Enter the desired loop number and press [✻] to continue (see the
transmitter’s Installation Instructions for specific loop designations).
Note: The loop number can be changed even if the zone has already been entered.
“L” indicates that the zone’s serial number has already been enrolled.
This function deletes either the serial number or all zone information that is
programmed for the zone.
If “00” was entered in the zone type, the confirmation of the delete request will delete
all information associated with the zone currently being programmed.
If “0” was entered in the loop number, the confirmation of the delete request will
delete the serial number of the zone currently being programmed.
RF type devices cannot be enrolled by using a BR type device. There is a 52second time-out for RF enrolling. At the end of the time-out, the system returns
to the INPUT TYPE prompt (d). If enrolled, loop number and “L” are displayed.
activated. Refer to the device’s Installation Instructions to activate the HighSecurity Mode.
Care should be taken when using this feature as it has the capability to make
zones inoperable by creating a mismatch of a working serial number/loop number
combination. This should be re-confirmed if the loop number is changed.
- 38 -
✻
56 Enhanced Zone Programming Mode
IA LC
Enroll Mode
0 = advance to the VOICE DESCRIPTOR
prompt (1C) and save all zone parameters.
1 = enter now and proceed to SERIAL
NUMBER prompt (1b).
2 = copy the last serial number entered into
local ram.
3 = view existing serial number.
9 = advance to F; delete existing serial
number.
[✻] = advance to the VOICE DESCRIPTOR
prompt (1C). This will save all zone
parameters.
[#] = return to the LOOP NUMBER prompt (E).
Notes:
(1) Option 1 is not applicable if the serial
number is already present.
(2) If Option 2 is entered and this is the 1st
zone, no serial will be in the buffer and the
panel will emit a long beep. Not valid if
serial number is already present.
(3) Options 3 and 9 are only valid if “L” is
displayed. If “L” is not displayed, panel will
emit a long beep.
Ib
Serial Number
Enter the transmitter’s 7-digit serial number.
[#] = return to prompt 1A and reject any serial
numbers entries that have been made.
[✻] = return to prompt 1A, (if a valid serial
number has been entered, the "L" is
displayed and the serial number will be
copied into EEROM from the last serial
entered into the buffer.)
IC
LYNXR-2 Series Installation and Setup Guide
If “L” is displayed, the serial number for this transmitter has already been entered. It
may, however, still be viewed, confirmed (only if in listen mode), or deleted.
View serial number
Enter “3”. Each digit will be redisplayed, and the keypad will beep once for digits 1-6,
and three times for the last digit.
Confirm serial number
The serial number/loop number combination can be confirmed after one transmission
from a BR type device or two transmissions (fault and restore) from a UR or RF type
device. If a transmission is received that matches the serial number and loop number
entered, the system will confirm the reception by announcing the Voice Descriptor for
the zone, if it is programmed, followed by three beeps, and a “C” will appear on the
display indicating the received serial number and loop number have been confirmed.
No further transmissions will be received.
Delete serial number
The serial number can be deleted by entering “9”.
If “L” is not displayed, the serial number for this transmitter has not been previously
entered. You may enter the serial number manually, copy the previous serial number,
return to Prompt (E) or enter the serial number later using the ✻83 Enhanced
Sequential Mode.
Manual entry
Enter "1" to advance to Serial number prompt (1b).
Copy the previous serial number
Enter “2” to copy the previous serial number entered.
Return to Prompt (E)
Enter “#” to return to Loop Number prompt (E).
Enter transmitter later
Enter “0” or “✻” if you wish to enter the transmitter later, using the ✻83 Enhanced
Sequential Mode described later in this manual.
Notes: (1) The panel will listen only when it is in the idle loop waiting for key entry and a
(2) A long beep indicates illegal entry or duplicate serial number/loop entry
(3) In order for all entered parameters to be accepted, you must advance to the
This prompt can be used only to manually enroll a serial number. RF enrollment will
be rejected and the current zone descriptor will be announced, followed by a single
long beep and the system will return to prompt (1A).
Enter the 7-digit serial number printed on the transmitter. If an incorrect digit is
entered, press the [#] key to backup to prompt (1A) and start over. When all 7 digits
are entered, press the [✻] key.
If 52 seconds passes and no entry has been made, the system returns to prompt (1A).
Notes: (1) If the serial and loop number combination is already present the keypad will
(2) If less than 7 digits have been entered, the keypad will emit a single long beep
(3) If more than 7 digits have been entered, the first 6 digits will be saved along
Each zone can have a voice descriptor of up to 3 words that will be announced
whenever the system announces status for that zone.
serial number has been entered. If a key is entered, the function must be
completed and the panel will listen again.
VOICE DESCRIPTOR prompt (1C).
emit a single long beep and the system will return to the (1A) prompt and “L”
will be displayed.
and return to the (1A) prompt without displaying the “L”.
with the last digit that was entered (entering 123456789 yields the serial
number 1234569).
Voice Descriptor
0 = skip to next zone (A)
1 = enter descriptor mode; existing descriptor
for this zone will be announced
- 39 -
LYNXR-2 Series Installation and Setup Guide
✻
56 Enhanced Zone Programming Mode
Id vi
Descriptor 1
Enter [#] + 2-digit vocabulary index number †
of first descriptor word for this zone.
6 = accept word and advance to descriptor 2
(descriptor 2 will be announced)
8 = accept word and advance to next zone
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word
IE vi
Descriptor 2
Enter [#] + 2-digit vocabulary index number †
of second descriptor word for this zone.
6 = accept word and advance to descriptor 3
(descriptor 3 will be announced)
8 = accept word and advance to next zone
(prompt A) – entire zone descriptor will be
announced
Press any other key to repeat the selected word
IF vi
Descriptor 3
Enter [#] + 2-digit vocabulary index number †
of third descriptor word for this zone.
6 or 8 = accept word and advance to next
zone (prompt A) – entire zone
descriptor will be announced
Press any other key to repeat the selected word
† see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press [#] +
desired 2-digit vocabulary index number.
If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to return to zone
number prompt.
† see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press [#] +
desired 2-digit vocabulary index number.
If descriptor 2 is not desired, enter [#] + 99 (blank), then press [8] to return to zone
number prompt.
† see ✻84 Assign Zone Voice Descriptors section for vocabulary index
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press [#] +
desired 2-digit vocabulary index number.
If descriptor 3 is not desired, enter [#] + 99 (blank), then press [8] to return to zone
number prompt.
- 40 -
✻
80 Device Programming Menu Mode
LYNXR-2 Series Installation and Setup Guide
Powerline Carrier Devices (e.g.; X10 brand devices) are programmable switches that can be used to perform
many different functions. They can be used to turn lights on and off, control sounders, or for status
indications. In this system, each device must be programmed as to how to act (ACTION), when to activate
(START), and when to deactivate (STOP). Each function is described below.
The K10145X10 transformer sends signals from the control panel through the premises AC wiring to the
Powerline Carrier Devices (which are plugged into AC outlets). Devices plugged into Powerline Carrier
Devices can then be made to perform various functions in response to commands entered at the keypads in
the security system. The control supports a total of 8 output devices.
This mode is also used to program Remote Services Multi-mode (e-mail) event triggers.
UL
UL
ULUL
Powerline Carrier Devices have not been evaluated by UL.
Programming Options Defined
The following will help you understand the programming of output devices when using ✻80 and ✻81 modes.
ACTION The "ACTION" of the device is how the device will respond when it is activated by the
"START" programming. There are four different choices of actions:
• ACTIVATE for 2 SECONDS and then reset.
• ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
• PULSE ON and OFF until stopped by some other event.
• NOT USED when the device is not used.
STARTThe "START" programming determines when and under what conditions the device will
be activated. The following START options are available:
Start by Event
An event is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone
list) in order to activate the device. These conditions apply only when a zone list is used. The
different choices for "EVENT" are listed below and in the “Programming Powerline Carrier
Devices” paragraph that follows.
• ALARM - Device activates upon any alarm in an assigned zone in the zone list.
• FAULT - Device activates upon any opening or short in an assigned zone in the zone list.
• TROUBLE - Device activates upon any trouble condition in an assigned zone in the zone list.
• NOT USED - Device action is not dependent upon one of the above events.
A zone list is a group of zones to which the “EVENT” applies in order to activate a
particular device. There are a total of 3 output device-related zone lists that can be
programmed in ✻81 menu mode. When the selected EVENT (alarm, fault or trouble)
occurs in any zone in the selected “Start” ZONE LIST (1, 2, or 3), activation of the
selected device will START.
Start by Zone Type or System Operation
•If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate
the device, the appropriate choice would also be entered under the “ZONE TYPE”
option. “ZONE TYPE” is used independently of the “EVENT/ZONE LIST”
combination.
•If a "ZONE TYPE" is chosen, any zone of that response type going into alarm,
trouble, or fault will cause the device to activate as selected in "ACTION.” If the same
“ZONE TYPE” is also chosen for the STOP programming, any zone of that type that
restores will de-activate the device.
•If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will
cause the device to activate as selected in "ACTION.” The different choices for
"ZONE TYPE" and "SYSTEM OPERATION" are listed in the “Start zone type”
paragraphs later in this section, and in the Programming Form.
- 41 -
LYNXR-2 Series Installation and Setup Guide
✻
80 Device Programming Menu Mode
STOP
The "STOP" programming determines when and under what conditions the device will be
deactivated. The following options are available:
Upon Restore of a Zone List
Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when
all the zones in that list restore from a previous fault, trouble, or alarm condition. This will
occur regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE
LIST" would normally only be used when a "ZONE LIST" is used to start the device.
Upon a Zone Type or System Operation
Zone Type/System Operation: Instead of using a "RESTORE ZONE LIST," a specific zone
(response) type or system operation action can be selected to de-activate the device.
•If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a
previous alarm, trouble, or fault condition will cause the device to de-activate.
•If a "SYSTEM OPERATION" is chosen, that operation will cause the device to de-activate.
During normal system operation, any devices may be manually started by keypad entry of: Code* + [#]
+ 4 + “n;” or manually stopped by keypad entry of: Code* + [#] + 7 + “n,” where “n” = the device number to
be controlled.
* Code is required for devices 7 and 8. For devices 1-6, code is not required. See User Manual for more
information.
Programming Powerline Carrier Devices
While in Program mode, press
program all output devices used in the system. Refer to the output device table for
separate programming form when programming output devices.
Note: The House ID of the Powerline Carrier Devices must be entered in data field ✻25.
The prompts for ✻80 are as follows:
80 Powerline Carrier Device Programming Main Menu prompt
A 01 Device Number --------------- for entering the device number
b Device Action ----------------- for defining the action the device will perform when active
C Start Event Type ------------ for assigning the event type to start the action
d Start Zone List --------------- for assigning the zone list to start the action
E Start Zone Type -------------- for assigning the zone type to start the action
F Stop Zone List ---------------- for assigning the zone list to stop the action
1A Stop Zone Type--------------- for assigning the zone type to stop the action
✻80 to enter Device Programming Menu Mode.This mode is used to
✻80 on the
- 42 -
✻
80 Device Programming Menu Mode
LYNXR-2 Series Installation and Setup Guide
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Note: Entering a number other than one specified will give unpredictable results.
ZT16 is only available on the LYNXR-2SIA version of the control panel.
80
Powerline Carrier Device
Entering “0” exits mode, upon which this prompt blinks, indicating that the mode is
inactive.
Entering “1” advances to the next prompt below.
Programming
0 = exit mode
1 = enter mode
A 01
Enter device numbers as 2-digit entries.
Device Number
01-08 = X10 device number to be
programmed
09-16 = Multi-mode (e-mail) event triggers
[✻] = continue
00 = exit Device Programming mode
b aa
Device Action
0 = No response
1 = Close for 2 seconds
2 = Close and Stay Closed
3 = Continuous Pulse on & off (1 sec ON, 1
sec OFF)
[✻] = continue
[#] = return to previous prompt
C et
Enter the 1-digit action (0-3) for the device being programmed (current action is
displayed).
Notes: (1) If “3” is entered (pulse), only up to 3 different devices can be pulsed if one of
(2) If using an X10 Powerhouse Security SH10A siren, you must:
Enter the 1-digit event type (0-3) to activate the device being programmed. A zone list
must be used in conjunction with an event. If a zone type/system operation is to be
used instead of an event, enter “0”.
the devices is a siren/horn (X10 Powerhouse Security model SH10A). In
addition, the siren/horn cannot be manually activated using the lights
on/lights off keypad commands.
• use device action “3.”
• change the device action default to “3” (if using default table 2 or 4).
Start Event Type
0 = Not used
1 = Alarm
2 = Fault
3 = Trouble
[✻] = continue
[#] = return to previous prompt
d zl
If a zone list will be used to start the device action, enter the zone list number at this
prompt.
Start Zone List
1-3 = zone list number (to be programmed in
field ✱81)
0 = zone list not used for this device
[✻] = continue
[#] = return to previous prompt
- 43 -
LYNXR-2 Series Installation and Setup Guide
✻
80 Device Programming Menu Mode
E zt
Start Zone Type
01-58 = zone type to start this device action
(select only those that are applicable
00 = zone type not used for this device
[✻] = continue
[#] = return to previous prompt
F zl
If a zone type or system operation will be used to start the device action, enter the
appropriate 2-digit code for the device being programmed (see table that follows).
Choices for zone types
00 = Not Used 07 = 24 Hr Audible
01 = Entry/Exit #1 08 = 24 Hr Aux
02 = Entry/Exit #2 09 = Fire without verification
03 = Perimeter 10 = Interior w/Delay
04 = Interior Follower 14 = Carbon Monoxide
05 = Trouble Day/Alarm Night 16 = Fire with verification
06 = 24 Hr Silent 24 = Silent Burglary
Choices for system operation
20 = Arming–Stay 38 = Chime
21 = Arming–Away 52 = Kissoff
22 = Disarm. (Code + OFF) 39 = Any Fire Alarm
31 = End of Exit Time 40 = Bypassing
32 = Start of Entry Time 42 = System Battery Low
33 = Any Alarm (except ZT 08,
09, 14 or 16)
36 = At Bell Timeout** 58 = Duress
** Or at Disarming (which ever occurs earlier)
SIA ZT 16 must be used in SIA fire applications.
If a zone list will be used to STOP, or restore, the device action, enter the zone list
number 1, 2, or 3 (to be programmed in ✻81 mode). If not used, enter “0”.
43 = Communications Failure
Stop Zone List
1-3 = zone list to stop this device action
0 = zone list not used
[✻] = continue
[#] = return to previous prompt
1A zt
Stop Zone Type
01-58 = zone type to stop this device action
(select only those that are applicable
00 = zone type not used for this device
[✻] = continue
[#] = return to previous prompt
If a zone type or system operation will be used to STOP the device action, enter the
appropriate 2-digit code (see the "ZT" choices listed above). If not, enter 00. The
display then returns to the DEVICE NUMBER prompt (A) so that you can enter the
next device number to be programmed, or enter [0][0] to end device programming
- 44 -
While in Program mode, press
for output devices (programmed in
The prompts for *81 are as follows:
✻81 to enter Zone List Menu Mode. This mode is used to program zone lists
✻80 Device Programming Menu Mode) or Chime-by-Zone in Zone List 3.
LYNXR-2 Series Installation and Setup Guide
✻
81 Zone List Menu Mode
81 Zone List Programming-------------------- Main Menu prompt
A 01 Zone List Number --------------------------- for entering the zone list number to be programmed
b Zone Entry to List --------------------------- for entering zones to the assigned zone list
C Delete Entire List? -------------------------- for deleting the entire zone list and its contents
d Delete Specific Zones From List?-------- Selects whether to delete zones or return to next zone
list number
E Delete Zones----------------------------------- for deleting specific zones from the current zone list
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Notes: (1) Any list may include any or all of the systems zone numbers
(2) A zone list can be assigned to more than one Powerline Carrier Device
(3) Entering a number other than one specified will give unpredictable results.
(4) Do not assign zones with zone types 20, 21 or 22 to a zone list.
(5) LYNXR-SIA ONLYZone List 2 should be used for Cross Zoning. When creating zone list 2 for cross zoning, include only 2
zones assigned to zone types 3, 4, or 5. If interior zones (zone type 4) are cross zoned, then both
zones in zone list 2 must be interior zones. Do not cross zone more than 2 zones, or zone types that
have delays (entry/exit zones, interior w/delay), or 24-hour zones, as these choices may produce
unpredictable operation and may not function as intended. If cross zoning is used, zone list 2 should
not be used for other purposes, such as triggering powerline carrier devices. If field ✻39 has been set
to “0” (no cross zoning), then Zone List 2 can be used for other purposes.
- 45 -
LYNXR-2 Series Installation and Setup Guide
✻
81 Zone List Menu Mode
81
Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating the mode is inactive.
Zone List Programming
0 = exit mode
1 = enter mode
Enter the Zone List Number 01, 02, or 03 to program (or 00 if no zone lists are used).
A 01
Zone List Number
01-03 = zone list number to be programmed
00 = exit Zone List mode
[✻] = continue
b zz
Zone entry to list
01-41, 95, 96, 99 = zone numbers to add to
zone list
[✻] = accept zone number and enter the next
zone number
00 = accept zone number(s) and continue to
next prompt
C
Delete Entire Zone List
0 = don’t delete; continue to next prompt
1 = delete the current zone list
d
Delete Zones from List?
1 = continue to delete zones prompt
0 = don’t delete; continue to next zone list
number prompt (A….01)
[#] = return to zone list number prompt (A 01)
E
Delete Zones
Enter each 2-digit zone number to be deleted
from the current zone list, followed by the [✻]
key.
[✻] = delete zone and enter next zone to be
deleted
00 = delete zone and return to next zone list
number prompt (A….01) desired)
Enter each zone number to add to the zone list by first entering the zone number,
then the [✻] key (for example, 01✻ 02✻ 03✻). The system will announce the Voice
Descriptor for the selected zone, if it is programmed. After all desired zones are
enrolled, enter “00” to advance.
Enter “1” to delete the zone list. All zones in the zone list will be deleted automatically
and programming will return to the ZONE LIST NUMBER prompt.
Enter “0” to save the zone list or delete specific zones from the list.
Enter “0” to save the entire zone list. Programming will return to the ZONE LIST
NUMBER prompt.
Enter “1” to delete a zone or zones in a zone list.
When deleting a zone(s) from the zone list, if the selected zone has a Voice Descriptor
programmed, upon deletion it will be announced as a confirmation that it has been
deleted. After all zones to be deleted are entered, enter “00” to return to the ZONE
LIST NUMBER prompt so that another list can be programmed, if desired.
- 46 -
LYNXR-2 Series Installation and Setup Guide
✻
83 Enhanced Sequential Mode
By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain
all other existing data that has been programmed for that zone. Note that the
mode requires that all zone information must first be entered using the
✻56 Enhanced Zone Programming
✻83 Enhanced Sequential
mode for all zones below zone number 26 (4 button key area).
Note: Any zone which already has a serial number learned in will not be accessible in ✻83 Enhanced Sequential mode!
Certain button-type transmitters have more than one button (e.g., 5804). Note that each button must be
assigned to a different zone. Similarly, the 5816 Transmitter has contact terminals and a reed switch for use
with a magnet. If using both, each must also be assigned to a different zone.
This means that the procedures that follow must be repeated for each button-type zone below zone number
26 or contact on the transmitter. Four zone button-type devices are held in zones 26 and above. They will be
started on boundaries of zones 26, 30, 34, and 38. These four zone button-type devices will have the option to
have all information entered in this field. One entry will set the loop number, report code, zone type, and
input device type for all 4 buttons, and a second entry will enter one serial number into four zones.
Note: Use this mode only after all other zone information has been programmed, including transmitter loop
numbers except for button-type zones over zone number 26. The panel will stop at zones 26, 30, 34
and 38 and zone data can be entered as a default here.
While in Program mode, press
✻83 to enter Enhanced Sequential Mode. The prompts for ✻83 are as follows:
A 02 Zone Number----------------------- for entering the zone number to be programmed
1A Enroll Mode------------------------- Selects method of serial number or viewing
1b Enroll Serial Number------------ for entering transmitter serial numbers
F Delete Serial Number ----------- for deleting existing serial numbers
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Notes: (1) Entry of a number other than one specified will give unpredictable results.
(2) In Enhanced Sequential Mode, 4 button type keys will always be enrolled simultaneously. They will be stopped at the 4 button
(3) You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly
boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a serial number
enrolled, the remaining keys cannot be programmed in sequential mode. In addition, if the zone has not been set up (duplicate
loop, missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.
hear feedback announcements or system beeps.
- 47 -
LYNXR-2 Series Installation and Setup Guide
✻
83 Enhanced Sequential Mode
A 02
Zone Number
Enter 2-digit zone number.
[✻] = continue; system searches for zones not
yet entered (for zones 2 through 25 a
zone type must be entered), then
advances to ENROLL SERIAL NUMBER
prompt “1b”
00 = exit Sequential mode
Enter the 2-digit zone number of the first transmitter to have its serial number
entered. The system will announce the Voice Descriptor for the selected zone number,
if it is programmed.
Press [✻] to continue. Starting with this zone number, the system will search for the
first transmitter that has all of the following attributes pre-programmed in ✻56
ENHANCED ZONE PROGRAMMING:
a) The appropriate input type was selected in ✻56 (RF, UR, or BR programmed)
b) The appropriate loop number was selected in ✻56.
c) No serial number has been programmed
d) Zone type
If the first zone number entered does not have one or more of the above attributes,
the system will search its database for the first zone that does, and will display it at
the enroll SERIAL NUMBER prompt (1b).
Enter 00 to exit. Prompt “83” blinks, indicating the mode is inactive.
Note: Two exceptions to the requirement above exist for keys. Four zone button type
devices (zone numbers 26, 30, 34, and 38) will be stopped only if there are no
serial numbers enrolled in all 4 zones of the key, regardless of the attributes that
have been entered. In addition, zone types are not required to be present. In this
IA zz
case, 1A, Option 4 must be selected prior to “Learn”.
If “L” is displayed, the serial number for this transmitter has already been entered,
however, it may still be confirmed, viewed or deleted. If the transmitter’s serial
number has not been previously entered, you may enter the enroll serial number
mode (1A) by entering “1”. Enter “2” to copy the last serial number that was entered.
IA LC
Enroll Mode
0 = advance to next zone to be enrolled
1 = enter now and proceed to SERIAL
NUMBER prompt (1b). For 4 button keys
(zones 26-29, 30-33, 34-37, & 38-41) the serial
number will be enrolled to all four buttons.
If enrolling a key, the panel will emit a long
beep when entering a 1 to indicate that the
present key set up is invalid.
2 = copy the previous serial number entry
from the buffer.
3 = view existing serial number.
4 = copy the 4 button key template that has
been set in zone numbers 26-29 (all zone
parameters except serial numbers). (Only
valid on zones 30-33, 34-37, & 38-41 that
do not have serial numbers enrolled.)
9 = delete existing serial. Go to the (1A)
prompt. For 4-button key, zones 26-29, 30-
33, 34-37, & 38-41 have serial numbers.
Delete all four at one time.
[✻] = advance to next zone to be enrolled
[#] = return to previous prompt (A)
A serial number must be entered in order to be copied. If no serial is stored in the
buffer and a copy is attempted the panel will emit a long beep indicating an invalid
operation.
If the transmitter’s serial number has been previously entered, you may, view the
present serial number by entering “3”. If view is selected each digit will be redisplayed, and the keypad will beep once for digits 1-6, and three times for the last
digit. Once the serial number has been entered by either selecting a “1” or a “2”, you
will return to this prompt with the “L” on the display. The serial number/loop number
combination that was entered can be confirmed by getting two transmissions (fault
and restore) from the RF or UR device or one transmission from the BR device. If a
transmission is received that matches the serial number and loop number entered,
the system will announce the Voice Descriptor for the loop followed by three beeps,
and a “C” will be displayed indicating that the received serial number and loop
number transmission has been confirmed to match. No further transmissions will be
received. When confirming a 4 button key, only the serial number is confirmed, since
it assumed that all loops are used. Pressing any key will allow a confirmation.
*Long beep indicates illegal entries, or duplicate serial number/loop entry*
When the last zone has been entered, the display will remain on that zone. To exit
this mode and return to data field program mode, enter 00 at the ZONE NUMBER
prompt.
When all zones have been programmed, test each zone using the system’s Test mode.
Do not use the Transmitter ID Sniffer mode for this, since it will only check for
transmission of one zone on a particular transmitter, and not the zones assigned to
each additional loop.
For Zones 26-29, 30-33, 34-37, and 38-41 any loop can be used for RF enrollment. If
enrolling via RF, it will be confirmed without additional transmissions.
Notes:
(1) A valid template or key has 4 existing zones, each with a zone type, unique loop
number.
(2) Option 2 is not applicable for 4 button key zones 26-29, 30-33, 34-37, & 38-41.
(3) If the display automatically returns to "1A" rather than "1b" the configuration of the key
is not valid. At that point copy template, skip, or return are the only legal entries.
(4) If option 3 or 9 is selected, the serial number can be viewed or deleted but only if “L”
is displayed. If the “L” is not displayed the panel will emit a long beep.
(5) If option 4 is selected template acceptance is indicated by two beeps after copying. A
single long beep, emitted when copying indicates the template is not valid.
- 48 -
LYNXR-2 Series Installation and Setup Guide
✻
83 Enhanced Sequential Mode
Ib zz
Ib
Serial Number
Enter transmitter’s 7- digit serial number via RF
learning or manually.
[#] = return to (1A) prompt and reject
whatever serial number entries have been
made.
[✻] = return to (1A) prompt (if a valid serial
number has been enrolled, “L” is
displayed and the serial number will be
copied into EEROM and the last serial
entered buffer.
the panel to return to prompt (1A)
regardless of the confirmation answer.
Note: In Enhanced Sequential Learn Mode, 4 button type keys will always be learned simultaneously. They will be stopped at the 4 button
boundaries of 26, 30, 34 and 38, provided the zone is free of a serial number. If the first zone of the key has a serial number learned,
the remaining keys cannot be programmed in sequential learn mode. In addition, if the zone has not been set up (duplicate loop,
missing zone type, etc.) only entries 0 (skip to the next zone) and 4 (copy the key template) will be allowed.
This prompt can be used to enroll the transmitter serial number via RF transmission
or manually. If using the RF Learning Mode there is no need to manually enter a
serial number. Proceed directly to RF Learning. Upon entering the Serial Number
mode, the Zone Descriptors will be announced.
Note: BR type devices can be enrolled only by transmission from BR devices. Likewise,
UR and RF devices can only be enrolled by transmission from a UR or RF device
RF Learning - Two (2) transmissions (2 key depressions) at least five seconds apart,
will be required for BR type or four (4) transmissions (fault, restore and fault, restore)
for UR or RF type. If the learned serial number has a different loop number than that
entered in ✻56 the system will announce the Voice Descriptor, if it is programmed,
followed by two beeps and will return to Prompt (1A) and “L” will be displayed.
If the loop number captured by RF transmission and that entered in ✻56 mode match,
the system will announce the Voice Descriptor, if it is programmed, followed by three
beeps and return to Prompt (1A) and “LC” will be displayed. No additional
transmissions are needed for confirmation.
Manual Entry - Enter the 7-digit serial number printed on the transmitter. If you
enter an incorrect digit, press the [#] key to backup to prompt (1A) and start over.
When all 7 digits are entered, press the [✻] key. If less than 7 digits are entered, the
keypad will emit a single long beep and return to the (1A) prompt without displaying
the “L”.
If more than 7 digits have been entered, the first 6 digits will be saved along with the
last digit that was entered (entering 123456789 yields the serial number 1234569).
Note: The system will return to prompt (1A) if an entry is not made within 52 seconds.
This function deletes only the serial number.
Entering a “9” at prompt (1A). Confirmation of the delete request will cause deletion
of the serial number pertaining to the zone being programmed.
- 49 -
LYNXR-2 Series Installation and Setup Guide
✻
84 Assign Zone Voice Descriptors
Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced
when the system announces any event involving a zone number. Each descriptor can consist of up to
3 words. To access this mode, Enter
The prompts for
✻84 are as follows:
✻84 while in Programming mode.
84 Voice Descriptors ------------------Main Menu prompt
A 02 Zone Number -----------------------for entering the zone number to be programmed
b Descriptor 1 -------------------------for assigning the first word of this zone’s descriptor
C Descriptor 2 -------------------------for assigning the second word of this zone’s descriptor
d Descriptor 3 -------------------------for assigning the third word of this zone’s descriptor
The following explains these prompts in detail. The left column identifies the prompts and lists the
available entries. The right column provides a further explanation of the entries.
Note: Entering a number other than the one specified will give unpredictable results.
84
Pressing 1 advances to the next prompt below.
Pressing 0 exits mode, upon which this prompt blinks, indicating the
mode is inactive.
Assign Zone Voice Descriptors
0 = exit mode
1 = enter mode
A zz
Enter the 2-digit zone number for which this descriptor is being
assigned, then press [✻]. The Voice Descriptor for the selected zone will
be announced, if it is programmed.
Zone Number
[✻] = continue to next prompt (any existing descriptors will
be announced, then descriptor 1 will be repeated)
00 = exit voice descriptor mode
b
vv
Descriptor 1
Enter [#] + 2-digit vocabulary index number of first
descriptor word for this zone.
6 = accept word and advance to descriptor 2 (descriptor 2
will be announced)
8 = accept word and advance to prompt (A) for next zone.
Press any other key to repeat the selected word.
Enter [#] + 2-digit vocabulary index number of first
descriptor word for this zone.
6 = accept word and advance to descriptor 2 (descriptor 2
will be announced)
8 = accept word and advance to prompt (A) for next zone.
Press any other key to repeat the selected word.
c
vv
Descriptor 2
Enter [#] + 2-digit vocabulary index number of second
descriptor word for this zone.
6 = accept word and advance to descriptor 3 (descriptor 3
will be announced)
8 = accept word and advance to prompt (A) for next zone.
Press any other key to repeat the selected word.
Enter [#] + 2-digit vocabulary index number of first
descriptor word for this zone.
6 = accept word and advance to descriptor 2 (descriptor 2
will be announced)
8 = accept word and advance to prompt (A) for next zone.
Press any other key to repeat the selected word.
Enter the first word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to
return to zone number prompt.
Enter the second word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply
press [#] + desired 2-digit vocabulary index number.
If descriptor 1 is not desired, enter [#] + 99 (blank), then press [8] to
return to zone number prompt.
- 50 -
LYNXR-2 Series Installation and Setup Guide
✻
84 Assign Zone Voice Descriptor
vv
Enter the last word of the descriptor for the selected zone.
Use the [6] or [8] key to advance as described.
To change the entered index number before pressing [6] or [8], simply press
[#] + desired 2-digit vocabulary index number.
If descriptor 3 is not desired, enter [#] + 99 (blank), then press [8] to return
to zone number prompt.
d
Descriptor 3
Enter [#] + 2-digit vocabulary index number of third
descriptor word for this zone.
6 or 8 = accept word and advance to prompt (A) for
next zone. Zone descriptor will be announced. Press
any other key to repeat the selected word.
00 ½ second pause
A
82 ALARM
32 ATTIC
B
01 BABY
33 BACK
34 BASEMENT
35 BATHROOM
36 BEDROOM
C
83 CHECK
D
37 DELAY DOOR
38 DEN
02 DETECTOR
03 DINING
39 DINING ROOM
04 DOOR
40 DOWNSTAIRS
05 DRIVEWAY
E
06 EAST
41 EIGHT
42 EMERGENCY
F
43 FAMILY ROOM
87 FIRE
44 FIRE DETECTION
07 FIRST FLOOR
45 FIVE
08 FLOOR
46 FOUR
47 FRONT
G
48 GARAGE
49 GUEST ROOM
09 GUN
H
50 HALL
I
10 INSIDE
K
51 KITCHEN
L
11 LAUNDRY
52 LAUNDRY
ROOM
12 LIBRARY
13 LIVING
53 LIVING ROOM
M
14 MAIN
15 MASTER
54 MASTER
BEDROOM
55 MEDICAL
84 MESSAGE
56 MOTION
DETECTOR
N
57 NINE
16 NORTH
58 NURSERY
O
59 OFFICE
60 ONE
17 OUTSIDE
Notes: (1) If button type device is used to Arm Away, Arm Stay, and disarm the system it is recommended to assign
“Check” and “Zones” voice descriptors to each of the three zones. This will allow the system to announce
“Check Zones” “Low Battery” if the button device has a low battery.
(2) If a Wireless Keypad is being installed along with this system, not all the voice descriptors shown on this list can
be announced by keypad. (Refer to the Wireless Keypad documentation for further information).
VOICE VOCABULARY INDEX
P
61 PATIO
62 POLICE
18 POOL
R
63 REAR
19 ROOM
S
64 SECOND FLOOR
65 SEVEN
20 SHED
21 SHOP
66 SIDE
67 SILENT POLICE
68 SIX
69 SLIDING
22 SMOKE
23 SOUTH
24 STORAGE
85 SYSTEM
T
25 THIRD FLOOR
75 THREE
76 TRANSMITTER
77 TWO
U
78 UPSTAIRS
26 UTILITY
79 UTILITY ROOM
W
27 WEST
80 WINDOW
Y
28 YARD
Z
81 ZERO
86 ZONES
ST
29 1
ND
30 2
3RD
31
70 Custom Word #1
71 Custom Word #2
72 Custom Word #3
73 Custom Word #4
74 Custom Word #5
99 Blank (for erasing
a previously
programmed
word)
SYSTEM WORDS
AC LOSS
ARMED
AWAY
BYPASSED
CARBON MONOXIDE
CHIME
DISARMED
DISARM SYSTEM
NOW
EXIT NOW
FAULT
INSTANT
LOW BATTERY
NOT
READY TO ARM
STAY
- 51 -
LYNXR-2 Series Installation and Setup Guide
✻
85 Record Custom Voice Descriptors
Use this mode to record up to 5 custom voice descriptors. To enter this mode, enter ✻85 while in
Programming mode.
Note: Entering a number other than one specified will give unpredictable results.
85
Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating the mode
is inactive.
Assign Custom Voice Descriptors
0 = exit mode
1 = enter mode
Record up to 5 custom words.
A 7d
Custom Descriptor Number
0 = exit mode
1 = enter mode
Enter 7 + d + [✻]
Note: d = 0-4, each representing custom word 70, 71,
72, 73, or 74, respectively. Any existing word will
be announced.
Press [#] to start recorder. Begin speaking
immediately after the third beep.
Speak the desired word clearly near the microphone.
Recording stops after 1.5 seconds.
6 = accept word and ready to record next descriptor
prompt (A….7d)
[#] = re-record descriptor
00 = exit Record mode after pressing 6 to accept word
Press any key to repeat the recorded word.
- 52 -
LYNXR-2 Series Installation and Setup Guide
Remote Programming/Control (Downloading)
General Information
The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), Compass
Downloader, a HAYES Modem or via a capable GSM or IP communications device.
UL
UL
ULUL
Downloading may only be performed if a technician is at the site.
Multiple security levels protect remote programming against compromise by attempts to defeat the system.
1. Security Code Handshake: An 8-digit download ID code must be matched between the Control and
downloader.
2. Site-Initiated Remote Programming: The installer or subscriber initiates the call from the subscriber
premises (by entering Installer Code + # + 1) while disarmed. All parameters can then be downloaded via
the phone lines using a personal computer.
3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the
download call. The Control hangs up and then calls back the PC via the preprogrammed telephone
number. The unit can then be uploaded, downloaded, or controlled from your office.
4. Telco Handoff: The installer or subscriber performs a download session on the call initiated from the
site or from local laptop computer (by entering Installer or Master Code + # + 1 at the control panel).
5. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is
very difficult for a foreign device tapped into the phone line to take over communication and substitute
system-compromising information.
Equipment required to download to a system at the premises
• An IBM PC compatible computer and appropriate interconnecting cables.
• Either a HAYES brand SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4
position DIP switch] internal style), a HAYES brand Optima 336 external, a HAYES brand Optima 24
Plus FAX96, or an Ademco CIA Modem or via a capable GSM or IP communications device.
• Compass Downloader for Windows (at revision level supporting LYNXR-2).
Initial Download: Enter Installer Code + # + 5. This sets field
✻95 to 4 rings, and system to “no call-back”
option. The download computer can then call the subscriber, make connection, and download all
programming data.
Flexible Callback: If enabled in field ✻93, the download operator can temporarily change the last 1, 2, or 3
digits (depending on selection) of the call back number. This allows the control to call back a computer other
than the one programmed, which may be helpful at times of high computer traffic. See field
description.
✻93 for a full
Remote Programming Information
If using Remote Programming, the LYNXR-2 Series must be connected to the telephone line or to the
Internet, as applicable.
The downloading system can perform many functions when in communication with the Control. Besides
uploading and downloading, the status of the system can be observed and various commands can be
initiated, as follows:
• Arm the system in the away mode; disarm the system.
• Bypass a zone.
• Force the system to accept a new program download.
• Shut down communication functions (for nonpayment of monitoring fees in an owned system).
• Shut down all security system functions (for nonpayment for a leased system).
• Inhibit local keypad programming (prevents account takeover).
- 53 -
LYNXR-2 Series Installation and Setup Guide
Remote Programming/Control (Downloading)
• Command the system to upload a copy of its resident program to the office.
• Set the time
• View/Modify
• X10/ Scheduling
• Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm,
zones currently in trouble, and RF sensors with low battery conditions; read control’s time.
Notes: (1) After the control and the PC have established valid communication, the keypad will become inactive and will
display “CC.”
(2) The keypad will become active after the download communication is terminated.
(3) The detailed operation of the download functions is covered in the installation instructions for the Compass
Downloader for Windows.
Remote Programming Advisory Notes
• Keypad entries are ignored during the time interval stated above.
• A copy of the program downloaded may be printed using the IBM PC-compatible computer’s internal
report generator, when an optional printer is connected (consult your PC manual for proper printer and
connections).
• Program upload or download time is approximately one minute, fifteen seconds for a complete program.
- 54 -
LYNXR-2 Series Installation and Setup Guide
System Operation
Keypad Operation
The keypad allows the user to arm and disarm the system, and perform other system functions, such as
bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed in the display window.
When an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be
displayed on the keypad. Pressing any key will silence the keypad sounder for 10 seconds (only once).
Disarming the system will silence both keypad and external sounders. When the system is disarmed, any
zones that were in an alarm condition during the armed period will be displayed (memory of alarm). To
clear this display, simply repeat the disarm sequence (enter the security code and press the OFF key). The
keypad also features chime annunciation, and 3 panic key pairs for silent, audible, fire or personal
emergency alarms. These keys can notify the central station of an alarm condition, if that service is
connected.
Panic Keys
There are three panic key pairs that, if programmed, can be used to manually initiate alarms and send a
report to the central station. Each can be individually programmed for 24-hour silent, audible, personal or
fire emergency responses. The panic function is activated when both keys of the appropriate key pair are
pressed at the same time. The panic functions are identified by the system as follows:
Keys Displayed as Zone
[1] & [✻]
[✻] & [#]
[3] & [#]
95
99
96
Important: For the silent panic functions
to be of practical value, the system must be
connected to a central station.
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4-1-1-2, but may be changed in field
only code that allows entry into Programming mode and also, in normal operation mode, is used to
enter the Master Code, which allows access to the normal functions of the system.
Master Code
In normal operation mode,the Installer Code is used to enter the 4-digit Master Security Code.
Enter/change the Master code by installer. At the keypad enter:
Change the Master code by master user. At the keypad enter:
Current Master Code + [CODE key] + [02] + new Master Code + new Master Code again
Secondary User Codes
In normal operation mode, the Master Security Code can be used to assign up to 6 secondary 4-digit security
codes, including a Babysitter Code and a Duress Code. The Master Code can also be used to remove
secondary codes from the system (individually).
Assign (or change) a secondary security code. At the keypad enter:
The system will emit a single beep when each secondary code has been successfully entered.
Delete a secondary security code. At the keypad enter:
Master Code + [CODE key] + User # (03–08)
✻20. The Installer Code is the
- 55 -
LYNXR-2 Series Installation and Setup Guide
System Operation
Security Code Notes
• The Master and Secondary security codes permit access to the system for arming, disarming, etc.
• The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot
disarm the system if it was armed by pressing and holding a Quick-Arm button.
• The Babysitter Code (User Code No. 7) can disarm the system only if it was used to arm it. In addition, the
Babysitter Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
• Duress code (User Code No. 8) sends a special code to the monitoring station when used to perform any system
operation. Instruct users to be careful not to use this code for normal usage. If the duress code is programmed, you
must enter a report code for Zone 92 (duress).
• If a secondary code is inadvertently repeated for different users, the lower user number will take priority.
• Opening/closing reports are sent for the Installer Code as No. 01, with the appropriate subscriber number. Master
Code and set of secondary user codes are sent as Nos. 02 and 03–08, respectively, in Contact ID® format (with the
appropriate user number); in 4+2, it is 1–8. Quick arming (and open/close executed by downloader) is reported as
user 00.
“Follow Me” Reminder Feature
This feature allows the user to schedule a time driven message. When activated the system will dial a phone
number that the installer programs in Field ✻46, and delivers a voice message (custom words 72, 73, and
74). The LYNXR-2 Series will immediately begin transmitting the voice message and will repeat the
message for 45 seconds. Pressing any touch-tone key on the answering phone will acknowledge the message
ending the session and preventing the system from redialing the programmed number. Delivery of a
reminder message on the local LYNXR-2 Series keypad will continue. If the message has timed out the
system will redial the programmed number a maximum of seven additional times or until it is
acknowledged. Pressing any key on the LYNXR-2 Series keypad will terminate (acknowledge) both the
follow me reminder and the local reminder announcements.
Notes: (1) This feature is only supported if programmed in field ✻49. (2) The follow me reminder will be terminated if any other event requires the system to dial out, or if an audible
alarm has occurred, however, delivery of the local schedule reminder message will continue.
“Follow Me” System Announcement Feature
This feature allows the LYNXR-2 Series to deliver a voice system message to the secondary phone number
programmed by the installer. The LYNXR-2 Series will first transmit reports to the Central Station and
after receiving its kiss-off the system will dial the secondary phone number and begin transmitting the voice
message. This message is a repeatable system status announcement. Like the Follow Me reminder, pressing
any key on the answering telephone or the local LYNXR-2 Series keypad will terminate (acknowledge) the
message. The system will dial the secondary phone number a maximum of eight times. The Follow Me alarm
functions may be triggered by a variety of events depending upon the selections made during programming
in field
Note: The follow me system announcement will be terminated if any other event requires the system to dial out or if an
✻49.
audible alarm has occurred.
Remote Phone Control Feature
The remote phone control feature, which must be enabled in field
system from any off-site touch-tone telephone. The control will pick up the incoming call, based on the ring
count specified in field
✻95, and will announce “SYSTEM ENTER CODE” every three (3) seconds for the
next eight (8) seconds. During this period the panel will wait for a valid User Code to be entered. If a valid
User Code is not entered or the eight (8) second period expires a modem tone will be generated for remote
programming (Compass Downloading). If a valid User Code has been entered, the control will announce the
current system status and/or beeping sounds.
- 56 -
✻91, allows the user to access the security
Remote Phone Control Keypad Functions
To remotely disarm system:
To remotely arm in AWAY mode:
To remotely arm in STAY mode:
+ [1]
+ [2]
+ [3]
To remotely arm in AWAY or STAY with no delay:
LYNXR-2 Series Installation and Setup Guide
System Operation
+ [2] or [3] + [0]
To remotely activate X10 devices 1-6:
To remotely activate X10 devices 7 & 8:
To remotely deactivate X10 devices 1-6:
To remotely deactivate X10 devices 7 & 8:
To remotely Bypass zones:
+ [6] + zone no.
To remotely activate Forced Bypass:
To remotely check system status:
To end remote phone control session:
[#] + [4] + (2-digit) device no.
+ [#] + [4] + (2-digit) device no.
[#] + [7] + (2-digit) device no.
+ [#] + [7] + (2-digit) device no.
+ [6] + [#]
[✻]
Hang Up or enter+ [9]
Powerline Carrier Devices (e.g. X10 devices)
If Powerline Carrier Devices are used, two keypad entries available to the user are included. They
can manually activate or deactivate the device(s) for starting or stopping some action, such as
turning lights on or off, etc.
*Code is required for devices 7 and 8. Code is not required for devices 1-6.
Exit Error Alarm Displays
The system will display the following if programmed in Field *59.
Display Meaning
CA
EA
Entering a second OFF sequence (Code + OFF ) will clear the display.
will appear along with a zone indication if an exit or interior zone contained a
fault during closing at the time the exit delay ended (e.g., exit door left open),
but the system was disarmed during the entry delay time. The alarm
sounder and keypad sound continuously, but stop when the system is disarmed.
No message will be transmitted to the central station.
will appear along with a zone indication if an exit or interior zone contained a
fault during closing at the time the exit delay ended, but the system was NOT disarmed during the entry delay time. The alarm sounder and keypad
sound continuously until the system is disarmed (or timeout occurs). An Exit
Alarm message is sent to the central station. OR
if an alarm from an exit or interior zone occurs within two minutes after the
end of an exit delay
- 57 -
LYNXR-2 Series Installation and Setup Guide
System Operation
System Displays
Display Meaning
PC
PH
AC
ALARM
AWAY
BYPASS One or more burglary protection zones have been bypassed.
CHIME
FAULT A malfunction is discovered in the system; or an open is detected in a fire zone; or a
FIRE
LOW BAT
INSTANT
MESSAGE A message has been recorded and has not yet been played back.
REC The system is in Recording mode.
STAY
TEST
UL
UL
ULUL
Audio alarm verification has not been evaluated by UL.
Audio Alarm Verification (Two-Way Voice Feature)
This feature allows the central station operator to listen, talk to or conduct a two-way conversation with an
individual(s) at the premises. It also assists the operator in gathering information about the nature and
location of the alarm that may be helpful in responding to police and fire departments. All LYNXR-2 Series
control panels are capable of supporting the Two-Way Voice feature. The LYNXR-2 Series does not make
system announcements when the Two-Way voice feature is active.
Remote Phone Control feature is active (Appears in place of the clock).
System Speaker Phone mode is active (Appears in place of the clock).
AC power is present. If not displayed, the system is operating on backup battery power.
System is armed and an intrusion has been detected (also appears during a
fire alarm or audible emergency alarm). Accompanied by the protection zone
that is in alarm.
All burglary zones, interior and perimeter, are armed.
Chime feature is activate
fault in a day/night burglary zone is discovered during a disarmed period.
Accompanied by a display of the zone number in trouble.
A fire alarm or fire fault is present. Accompanied by a display of the zone that
is in alarm
Low battery condition in a wireless sensor (if zone number is displayed) or low system
battery (if no zone number is displayed). If 00 is displayed, a wireless keypad has a low
battery condition.
Entry delay is turned off.
Perimeter Burglary zones, such as protected windows and doors, are armed
System is in Test mode.
Activation
Fire and CO alarms will not trigger an AAV session. A new Fire or CO alarm will end an AAV session that is
in progress.
The LYNXR-2 Series sends the “alarm message” followed by a “Listen-in-to-Follow message” (Contact ID®
code 606) to the Central Station. The Listen-in-to-Follow message causes the Central Station’s digital
receiver to temporarily hold the phone line for approximately 1-minute. When the LYNXR-2 Series receives
the “kissoff” from the central station, indicating that the alarm message has been received, the Two-Way
Voice (AAV) feature is activated in the (default) “Listen Mode” and sirens and keypad sounds are
discontinued. The LYNXR-2 Series transmits a beep acknowledgment to the Central Station, once per
second. The beep alternates between two tones and indicates that the LYNXR-2 Series is waiting for a
session command from the Central Station operator. Once a command is issued the beep acknowledgement
is discontinued, however, if a command is not issued within two minutes the system will “time out” and the
call will be terminated.
- 58 -
LYNXR-2 Series Installation and Setup Guide
System Operation
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV
commands shown in the table below. The session may be extended 5 minutes, without changing the
operating mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also
resets the session an additional 5 minutes. During the last minute of the 5 minute, session, the LYNXR-2
Series generates two beeps every 30 seconds to alert the Central Station operator that the session is about to
time out. The Central Station operator may then extend the session by pressing the [7] key on the touch-tone
phone. If the session is not extended the phone line is disconnected, and the session is ended. Sessions may
be ended at any time by pressing the [9] key on the touch-tone phone. The AAV modes are described as
follows:
Note: When entering AAV commands make sure the Central Station receiver has been disconnected from the
phone line, otherwise AAV commands may not go through.
KeyFunction
1 Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the
central station to the violated premises, and allows the operator to talk communicate through the LYNXR-2
Series speaker. In this mode the ARMED (red) and READY (green) LEDs blink alternately.
2 VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications
between the central station and the violated premises. In this mode the ARMED (red) and READY (green)
LEDs blink alternately.
3 Listen Mode: Pressing the [3] key on the touch-tone phone, enables one-way audio from the violated premises
to the central station. The Listen Mode is the start up default mode of the voice feature and allows the
operator to listen through the LYNXR-2 Series microphone. This mode does not affect the existing LED
pattern.
7 Extends the session 5 minutes without changing its operating mode.
9 Ends the session and disconnects the phone line.
- 59 -
LYNXR-2 Series Installation and Setup Guide
Keypad Function Summary
A summary of system functions is provided below. For more detailed information refer to the User Guide.
Security Functions
Checking system status:
To arm in STAY mode: ........................... + STAY (or installer code + [3])
To restart exit delay: ............................... STAY (applies only if system is armed in Stay mode)
To arm in AWAY mode: ........................... + AWAY (or installer code + [2])
To arm with NO DELAY:
To arm if Quick Arm is programmed:... AWAY or STAY (hold down for at least 2 seconds)
To disarm the system and silence alarms: +OFF
Note: LYNXR-2SIA ONLY - During Entry Delay or when an Alarm Condition exists the system can be disarmed by entering the User Code.
Entering the
To bypass a zone(s): ................................. + BYPASS + 2-digit zone number(s)
To turn Chime mode on or off: .............. FUNCTION +CHIME
Message Center
To record a message:.............................. FUNCTION + RECORD
To stop recording before end of 85 seconds:OFF
To play back a message: ........................ FUNCTION + PLAY
To skip a message: ................................[✻]
To delete all messages:..........................
Volume Control
To adjust message playback/system announcement volume:FUNCTION + VOLUME + [3] or [6]
To mute system announcements: ......... FUNCTION + VOLUME +OFF
To restore/unmute announcement & volume: FUNCTION + VOLUME + [3] or [6]
(Empty boxes represent the user’s security code)
......................... STATUS (high level messages); press STATUS again for secondary messages
........................ + AWAY or STAY + NO DELAY
OFF key is not required.
FUNCTION + DELETE (during message replay)
Other Functions
To set the time and date: ........................ + FUNCTION + [63]
To set the scheduling: ............................. + FUNCTION + [64]
To activate or deactivate X10 devices 1-6: FUNCTION +LIGHTS ON orLIGHTS OFF + (2-digit) device no.
To activate or deactivate X10 devices 7 & 8: + FUNCTION + LIGHTS ON or LIGHTS OFF + (2-digit) dev. no.
To add a user code: ................................. *+ CODE +user number + user’s code (*master code)
To delete a user code (except Master Code): *+CODE + user number (* master code)
To turn Test mode on: ............................. +TEST
To turn Test mode off: ............................. + OFF
To use the defined AUX function: Press and hold AUX key 2 secs (4 beeps) +
To define AUX function: + FUNCTION + AUX + action separated by+ AUX terminated by+ AUX + AUX
To send message to pager:Press and hold AUX key 2 seconds (4 beeps)
To program Follow Me Reminder telephone number: + FUNCTION + [65]
Speaker Phone Operation
To place a call or answer a call using the speaker phone:
[#] +AUX
To flash (switch between two calls using call waiting): AUX
The ARMED and READY LEDs blink
alternately when the Speaker Phone is active.
NOTE
To hang up and exit speaker phone mode:OFF
To enable/disable (toggle) ringer: [#] + VOLUME +AUX
To return the keypad to telephone mode after disarming the system: [#] +AUX
- 60 -
LYNXR-2 Series Installation and Setup Guide
Testing the System
Test Mode
After installation is completed, the security system should be carefully tested, as follows.
1. With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit,
press the [
READY LED lights. Fault and restore every sensor individually to assure that it is being monitored by
the system.
2. Enter the security code and press the TEST key. The outside sounder will sound for 1 second and all
the LED segments on the keypad display light for 3 seconds. LYNXR-2 Series announces the zone’s
voice descriptor (if programmed) followed by 3 beeps, each time a contact is faulted. A test report
should be transmitted (if programmed) to the central station immediately. If the backup battery is
discharged or missing, the sounder may not turn on and a LOW BATTERY report will be transmitted
with a TEST report. The keypad will beep once every 45 seconds as a reminder that the system is in the
Test mode.
3. To turn off the Test mode enter security code and press the OFF key.
Notes: (1) Triggering a zone set to Arm AWAY, Arm STAY, or Disarm will take the system out of Test and cause that action.
(2) BR type transmitters do not display during Test mode (keypad beeps only)
(3) Macros cannot be run from the Test mode.
(4) Test mode automatically ends after 4 hours.
LYNXR-2SIA ONLY
(5) During the final 5 minutes (after 3 hours 55 minutes of Test mode), “TEST” flashes on the keypad indicating that the end of
(5) Upon termination of a test mode all faulted 24-hour zones are treated as a trouble zones.
(6) Fire verification is disabled when the system is in Test mode.
Armed System Test
✻] key to display the faulted zone(s). Restore faulted zone(s), if necessary, so that the
Test mode is nearing.
Alarm messages will be sent to the central station during the following tests 1 and 2. Notify
them in advance that tests will be in progress.
1. Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected),
silence alarm sounder(s) by entering the code and pressing OFF. Check entry/exit delay zones.
2. Check the keypad-initiated alarms that are in the system by pressing the Panic key pairs. If the system
has been programmed for audible emergency, the keypad will emit a steady alarm sound, and
“ALARM” and zone number will be displayed. For LYNXR-2, silence the alarm by entering the
security code and pressing OFF. For LYNXR-2SIA, silence the alarm by entering the security code.
If the system has been programmed for silent emergency, there will be no audible alarms or displays,
but a report will be sent to the central station.
3. If Powerline Carrier Devices have been installed, test their programmed action.
4. Notify the central station when all tests are finished, and verify results with them.
5. To test the wireless part of the system and the RF receiver, perform the two additional tests described
in the Installing Wireless Zones section: Sniffer mode and Go/No Go Test.
Note: System Test mode (installer/master code + test) and Go/No Go Test (installer code + # + 8) will be
automatically terminated after 3-1/2 to 4 hours if the installer or user does not manually terminate it. This ensures that fire and panic zones will not remain disabled. However, Sniffer mode (installer code + # + 3) does
not automatically expire. You must manually exit (Installer/User Code + OFF) Sniffer mode to
return to normal operation.
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to
continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the user
as well as acquainting the user with the proper operation and limitations of the alarm system and its component
parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the
system’s proper operation at all times.
TO THE INSTALLER
- 61 -
LYNXR-2 Series Installation and Setup Guide
System Communication
This section provides an explanation of formats this system accommodates for reporting alarms and other
system conditions to the central station. The process of a successful transmission consists of both the
method of communication between the control panel and the central station receiver, and the actual way the
information is sent and displayed at the central station.
Communication Overview
When the panel calls the central station receiver, it waits to hear a “handshake” frequency from the receiver
to confirm that the receiver is on-line and ready to receive its message. Once the panel hears the handshake
it is programmed to listen for, it sends its message. The panel then waits for a “kissoff” frequency from the
receiver acknowledging that the message was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its
message. Once the handshake frequency is received and understood by the panel, the panel will send its
message. If there is an error in the transmission (the receiver does not receive a “valid” message), the kissoff
frequency will not be given by the central station receiver.
The panel will make eight attempts to the primary telephone number and eight attempts to the secondary
telephone number (if programmed) to get a valid message through. If the panel is not successful after its
numerous attempts, the keypad will display “FC.” If the secondary number is a pager, “FC” displays after
the first 8 attempts to the primary number.
The following chart defines the (handshake/kissoff) frequencies that the panel supports, and the different
formats that can be sent for each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed
3+1
1400Hz
1900Hz (10PPS)
(Standard report)
1400Hz
Under 15 seconds
4+1
4+2
Sescoa/Radionics
3+1
2300Hz
1900Hz (20PPS)
(Standard report)
2300Hz
Under 10 seconds
4+1
4+2
Express
1400–2300HzDTMF (10 cps)
1400Hz
Under 3 seconds
4+2
Contact ID® 1400–2300HzDTMF (10 cps)
1400Hz
Under 3 seconds
Report Code Formats
3+1 and 4+1 Standard Formats
3+1 and 4+1 Expanded Formats
4+2 Format
ADEMCO Contact ID®
Reporting Format
Comprise a 3- (or 4-) digit subscriber number and a single digit report code
(e.g. alarm, trouble, restore, open, close, etc).
Comprise a 3- (or 4-) digit subscriber number, and a 2-digit report code. The
first digit is displayed on the first line, followed by a second line where the
first digit is repeated 3 (or 4) times and followed by the second digit. This is
the “expanded” digit.
Comprises a 4-digit subscriber number and 2-digit report code.
Comprises a 4-digit subscriber number, 1-digit event qualifier
(“new” or “restore”), 3-digit event code, and 3-digit zone number, user
number, or system status number (see the following page)
- 62 -
LYNXR-2 Series Installation and Setup Guide
System Communication
The following table shows the message formats for 3+1, 4+1 and 4+2 reports, where:
SSS or SSSS = Subscriber ID C = Close Code (1st Digit)
A = Alarm Code (1st digit) U = User Number (in hex)
Z = Typically Zone Number* (2nd digit) Gg = Test Code (1st & 2nd digits)
T t = Trouble Code (1st & 2nd digits) R = Alarm Restore Code
B b = Bypass Code (1st & 2nd digits) RTt = Trouble Restore Code (1st & 2nd digits)
AC Loss Code (1st & 2nd digits) RBb = Bypass Restore Code (1st & 2nd digits)
C =
Low Battery Code (1st & 2nd digits) RAA
B =
Report 3+1/4+1 Standard 3+1/4+1 Expanded 4+2
Alarm SSS(S) A SSS(S) A
AAA(A) Z
Trouble SSS(S) T SSS(S) T
TTT(T) t
Bypass SSS(S) B SSS(S) B
BBB(B) b
AC Loss SSS(S) E SSS(S) E
EEE(E) AC
Low Battery SSS(S) L SSS(S) L
LLL(L) LB
Open SSS(S) O SSS(S) O
OOO(O) U
Close SSS(S) C SSS(S) C
CCC® U
Test SSS(S) G SSS(S) G
GGG(G)g
Restore Alarm SSS(S) R SSS(S) R
RRR® Z
AC Restore SSS(S) RA SSS(S) R
RARARA(RA)Ac
Low Battery
Restore
Trouble Restore SSS(S) RT SSS(S) RT
Bypass Restore SSS(S) R
SSS(S) RL SSS(S) RL
RLRLRL(RL)LB
RTRTRT (RT)t
B
SSS(S) R
RBRBRB (RB)b
AC Restore Code (1st & 2nd digits)
C =
Battery Restore Code (1st & 2nd digits)
B =
SSSS AZ
SSSS Tt
SSSS Bb
SSSS EAC
A
B
SSSS LL
SSSS OU
SSSS CU
SSSS Gg
SSSS RZ
SSSSRA A
SSSS RLL
SSSS RTt
SSSS RBb
B
c
B
- 63 -
LYNXR-2 Series Installation and Setup Guide
System Communication
ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:
CCCC = Customer (subscriber) ID
Q = Event qualifier, where: E = new event, and R = restore
EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office
receiver manual)
GG = Always “00”
ZZZ = Zone/Contact ID® number reporting the alarm, or user number for open/close reports.
System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
CONTACT ID® EVENT CODES
Code Definition
110 Fire Alarm
121 Duress
122 Alarm, 24-hour Silent
123 Alarm, 24-hour Audible
131 Alarm, Perimeter
132 Alarm, Interior
134 Alarm, Entry/Exit
135 Alarm, Day/Night
146 Silent Burglary
150 Alarm, 24-Hour Auxiliary
162 Alarm, Carbon Monoxide Detector
301 AC Power
302 Low System Battery/Battery Test Fail
344 RF Jam Detected
353 ECP Communication/Supervision failure, case
tamper or low battery
373 Fire Loop Trouble
374 Exit Error Alarm
380 Global Trouble, Trouble Day/Night
Notes: (1) The following codes are logged in the event log upon occurrence, but are not reported:
305 = System Reset
627 = Keypad Program Mode Entry
(2) LRR/IP Communications Module Low Battery and Low Battery restore reports are sent real time. LRR/IP
Communications Module trouble restore report is sent after two CODE + OFF (only if physically restored)
Armed AWAY
403 Scheduled Auto Arm
406 Cancel by User
407 Remote Arm/Disarm (Downloading)
408 Quick Arm AWAY/NO DELAY
441 Disarmed/Armed STAY/NO DELAY, Quick Arm
STAY/NO DELAY
459 Recent Close
570 Bypass
602 Periodic Test
606 AAV to follow
607 System Test
623 Event Log 80% Full
654 System Inactivity
- 64 -
LYNXR-2 Series Installation and Setup Guide
Troubleshooting Guide
Trouble Conditions
The word “FAULT” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that
there is a trouble condition in the system. Pressing any key can silence the audible warning sound. Instruct
users to call for service immediately upon seeing any of the following messages.
System Trouble Displays
Display Meaning
FAULT
FAULT 103
LOW BAT
LOW BAT
bF
CA
CC
dI
EA
FC
90
No display
and one or more zone numbers indicates that a problem exists with the displayed
zone(s) and requires attention. After correcting the problem, the display can be cleared by
entering the security code plus the OFF key twice.
The fault condition may also be caused by some change in the environment that prevents
the built-in receiver from receiving signals from a particular wireless sensor.
Indicates one of the following:
• control panel lost communication with the communications module
with no zone number indicates that the system’s backup battery is weak.
with a zone number and a once-per-45 seconds “beeping” at the keypad indicates that a
low battery condition exists in the wireless sensor displayed (zone “00” indicates a wireless
button/keypad). If the battery is not replaced within 30 days, a “FAULT” display may occur.
Backup LRR/GSM/IP module communication failure (displayed on RF Keypad only)
appears if an exit or interior zone contained a fault during closing at the time the Exit
Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay
time. The alarm sounder and keypad sound continuously, but stop when the system is
disarmed. No message will be transmitted to the central station.
Modem Comm.:
system is communicating with the central station for change of function or status
verification.
Busy-Standby
displayed upon power-up. After approximately 1 minute* the green “READY” LED should
light. If the “dI” remains displayed for more than 1 minute, the system is disabled.
*To bypass the 1-minute delay, press [#] + [0].
Important: Do not try to bypass 1minute delay before “dI” is displayed!
appears when Exit Delay ends if an exit or interior zone contained a fault during closing.
The alarm sounder and keypad sound continuously until the system is disarmed (or
timeout occurs). An “Exit Alarm” message is sent to the central station. Also results if an
alarm from an exit or interior zone occurs within 2 minutes after the end of an Exit Delay.
communication failure has occurred. This message clears only when the system is
subsequently armed.
system has detected an RF jamming condition or excessive interference.
Power Failure
If there is no keypad display at all, and the LED indicators are not lit, operating power for
the system has stopped and the system is inoperative.
If the display is lit and the AC display is off, the system is operating on battery power only.
During an AC power loss, the backlighting will turn off and the indicators will flicker
slightly to minimize deep discharge of the battery.
- 65 -
LYNXR-2 Series Installation and Setup Guide
Troubleshooting Guide
System (including Wireless)
SYMPTOM POSSIBLE CAUSE REMEDY
1. Transmitter signal
not received at
control.
2. Transmitter zone
number appears
during Transmitter
Sniffer mode, but
does not clear.
3. Low battery message
on keypad.
3a. "Low Bat" (no zone Nos.)
3b. "Low Bat" + "00".
3c. "Low Bat" + "nn".
4. Periodic beep(s) from
keypad.
5. There is no response
to a transmitter in
normal operation,
although zone
number clears during
Transmitter Sniffer
mode.
6. Nuisance or phantom
alarm.
7. Intrusion alarm for
no apparent reason.
1a. Transmitter not properly powered.
1b. Transmitter is located too far from RF
receiver.
1c. There is metal shielding between
transmitter and RF receiver.
1d. Transmitter is malfunctioning.
1e. Transmitter No. (zone) is not
programmed.
2a. Transmitter zone type (ZT) is set to 00
(Not Used).
2b. Transmitter battery not installed.
2c. 5800 System transmitter not "entered" in
system.
3a. System battery is low or missing.
3b. Remote RF keypad/button battery is low.
3c. Transmitter for zone “nn” has a low
battery.
3d. Standard- or High-Capacity battery
connected to wrong receptacle.
4a. System is in Test mode.
4b. A transmitter low battery has occurred
and is displayed.
4c. A supervision fault has occurred.
4d. System low battery
Put control in Test mode. If zone does not
respond, try operating the tamper switch or
another input to the transmitter.
5a. If another input causes the zone to be
displayed, the wrong input was "entered"
when programming.
5b. If no response at all from this
transmitter, this physical transmitter
has not been entered by the system.
Transmitter Sniffer display is being
cleared by another unit programmed for
this zone.
6a. Sensors not properly installed, wired, or
monitored.
6b. Universal transmitter (5817)
programmed wrong.
7a. Protected door or window opened while
system armed.
7b. Improper user operation of exit/entry
delays.
7c. Magnets located too far from switches,
and/or doors and windows not properly
aligned.
1a Check or change transmitter's battery.
1b. Move transmitter or RF receiver.
1c. Check for large metal obstructions, then relocate
transmitter if necessary.
1d. Verify by activating control with another,
similar transmitter. If O.K. now, return
defective transmitter.
1e. Verify programming.
2a. Set ZT to a valid active zone type in field ✻56.
2b. Install proper battery.
2c. "Enter" unit in field ✻56 or ✻83.
3a. Replace system battery.
3b. Replace battery in the RF keypad.
3c. Replace the battery in the displayed
transmitter.
3d. Ensure that battery is properly connected.
4a. Enter Code + OFF to exit Test mode.
4b. Enter Code + OFF and replace the battery.
4c. Check the transmitter indicated. Restore
communication to the receiver to cancel the
condition.
4d. Replace system battery
5a. Delete input's serial number (not the zone), and
enter the proper input (see field ✻56).
5b. Determine which transmitter is programmed for
this zone and reprogram as necessary.
6a. Check installation to see if in accordance with
established procedure.
6b. Check programming switches on transmitter.
7a. Check with all occupants of protected home.
7b. Check setting of entry and exit delays.
7c. Check all openings for proper switch and
magnet orientation.
- 66 -
LYNXR-2 Series Installation and Setup Guide
Troubleshooting Guide
Control
SYMPTOM POSSIBLE CAUSE REMEDY
1. The word “AC” is not
displayed.
2. Digital communicator
message not being
received.
3. Does not arm
properly.
READY light not on.
4. System doesn't
respond to keystrokes
on keypad.
4a. "CC" displayed.
4b. "dI" displayed.
Smoke Detectors
SYMPTOM POSSIBLE CAUSE REMEDY
1. Detector alarms, no
apparent reason.
2. Detector's siren
sounds.
1a. Interrupted AC power supply.
2a. System in Test mode.
2b. Telephone connection not secure.
2c. Digital communicator malfunctioning.
2d. Telephone number in program needs
prefix or access code.
2e. Telephone call to central monitoring
station requires operator assistance.
Open or faulted zone(s)
4a. System is in communication with
downloader at central station.
4b. System has just been powered and is in
its one minute initialization.
1a. Dust, dirt in sensing chamber.
1b. Improper location.
1c. Unit malfunctioning.
2a. Unit not receiving required power.
2b. Unit malfunctioning.
1a. Check transformer connection and
powerline circuit breaker.
2a. Remove from Test mode.
2b. Check all connections.
2c. Check with a different CONTROL PANEL.
2d. Program prefix or access code into the
CONTROL PANEL.
2e. System cannot work in this situation.
Check for faulted zones and make intact, or use
Bypass arming, if desired.
4a. Wait until download session is finished.
4b. Wait for initialization to finish, or bypass
this time by pressing '#' + '0.'
1a. Clean unit's sensing chamber with vacuum
cleaner per unit's instructions.
1b. See unit's instructions for locations to avoid.
Relocate as necessary.
1c. Replace detector.
2a. Check for proper installation of battery. Try new
battery.
2b. Replace detector.
- 67 -
LYNXR-2 Series Installation and Setup Guide
Programming Default Tables
LYNXR-2 Control Defaults
(boldface indicates defaults that differ between tables)
*77 Dynamic Signaling Delay/ Dynamic Signaling Priority 0,0 0,0 0,0 0,0
*78 Programmable Tone Generation Time 0,0 0,0 0,0 0,0
*80 Powerline Carrier Devices See *80 table See *80 table --- See *80 table
*81 Zone lists for devices See *81 table See *81 table See *81 table See *81 table
*84 Assign zone voice descriptors Refer to *84 Programming
*86 Multi-mode (E-mail notification) 0 0 0 0
- 68 -
LYNXR-2 Series Installation and Setup Guide
Programming Default Tables
LYNXR-2 Control Defaults
(boldface indicates defaults that differ between tables)
*80 Powerline Carrier Devices See *80 table See *80 table --- See *80 table
*81 Zone lists for devices See *81 table See *81 table See *81 table See *81 table
- 70 -
LYNXR-2 Series Installation and Setup Guide
Programming Default Tables
LYNXR-2SIA Control Defaults
(boldface indicates defaults that differ between tables)
Function Table 1 Table 2 Table 3 Table 4
*84 Assign zone voice descriptors Refer to *84 Programming
NOTE: Zone 2 to 41 are RF zones; Zone 92 is Duress; Zone 99 is keypad panic
- 72 -
LYNXR-2 Series Installation and Setup Guide
Programming Default Tables
✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 1 and 2
(devices 01-07 have no default values, devices 09-15 have all default values set to 00)
Start Stop
Device Number
08** 2 33 36
16 2 33 36
✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4
(devices 02-07 have no default values, devices 10-15 have all default values set to 00)
Start Stop
Device Number
01 2 2 1 2
08** 2 33 36
09 2 2 1 2
16 2 33 36
** NOTE: If using an X10 Powerhouse Security SH10A siren as device 08, you must change the device action default to “3”.
✻81 ZONE LIST FOR OUTPUT DEVICES DEFAULT TABLE: Applies To Default Table 1 - 4.
Zone List 1 28, 32
Zone List 2 29, 33
Zone List 3 2, 3
Action
Action
Event Zone List
Event Zone List
Zone Type
System Operation
Zone Type
System Operation
Restore of
Zone List
Restore of
Zone List
Zone type
System operation
Zone type
System operation
- 73 -
LYNXR-2 Series Installation and Setup Guide
Regulatory Agency Statements
FCC STATEMENT
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1)
THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Federal Communications Commission (FCC) Part 15 Statement
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following
statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with
the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to
comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user or
installer may find the following booklet prepared by the Federal Communications Commission helpful: "Interference Handbook." This
booklet is available from the U.S. Government Printing Office, Washington, DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's
Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
Federal Communications Commission (FCC) Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC
registration number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when
requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs.
This equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets
telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment
Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer
should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made
by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to
disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal
metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection
authority, or electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of
terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of
devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
- 74 -
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a
variety of reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work
without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put
in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
•Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the
Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may
not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not
sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector,
for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke
detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire
and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to
allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams
of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion
or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows.
Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical
system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection
performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices are located on a different level of the residence from the
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing
traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond
appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to
last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad
(and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce
the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus
allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones
to learn about these developments.
LYNXR-2 Series Installation and Setup Guide
- 75 -
LYNXR-2 Series Installation and Setup Guide
1. For UL Residential Burglar Alarm installations with line security, total exit delay time must
not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit
delay time must not exceed 120 seconds.
2. Periodic testing (see scheduling mode) must be at least every 24 hours.
3. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations (Aux power 500mA max.).
4. Remote downloading without an alarm company technician on-site (unattended
downloading) is not permissible for UL installations.
5. Auto-disarming is not a UL Listed feature.
6. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial
and residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a
signal to a remote monitoring location, or to delay the energizing of a local alarm sounding
device to permit the alarm system user to enter and disarm the system, or to arm the system
and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote
monitoring location.
SIA Quick Reference Guide
1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the
same as the “number of reports in armed period” set in field *92 (1 if 1 report, 2 if 2 reports).
2. *34 Exit Delay: Options include 45-96 and 120 seconds. Minimum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Options include 30-96, 120, 180, and 240 seconds. Minimum
entry delay is 30 seconds. When added together the entry delay plus the dialer delay should
not exceed 1 minute.
4. *39 Cross Zone Timer: Options include No cross zoning or selections between 15 seconds and
3 minutes, 45 seconds (in 15 second increments). Default is “0” no cross zoning
5. *40 PABX Access Code/Call Waiting Disable: If call waiting is used, call waiting cancel
option in field *47 must be set.
6. *47 Phone system Select: If call waiting is used, Call Waiting Disable must be enabled.
7. *50 Burglary Abort Window: Options include 15, 30 and 45 seconds. Delay must be a
minimum of 15 seconds.
8. *57 False Alarm Options: Default is “7” cancel alarm display, auto stay arming and exit time
restart/reset enabled.
12. *92 Swinger Shutdown: Default is “1” shutdown after one trip.
UL NOTICES
- 76 -
Contacting Technical Support
PLEASE, before you call Technical Support, be sure you:
• READ THE INSTRUCTIONS!
• Check all wiring connections.
• Determine that the power supply and/or backup battery are supplying proper
voltages.
• Verify your programming information where applicable.
• Note the proper model number of this product, and the version level (if known) along
with any documentation that came with the product.
• Note your Honeywell customer number and/or company name.
Having this information handy will make it easier for us to serve you quickly and
effectively.
You may contact Technical Support via Toll Free Fax. Please include your return fax number. You
will receive a reply within 24 hours.