Honeywell CUL6438SR-CV1, STRYKER CVAHU ZIO CUL6438SR-CV1 Configuration Manual

Page 1
STRYKER CVAHU ZIO
CUL6438SR-CV1
CONFIGURATION GUIDE
Nov-2013
Page 2
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Table of Contents
Introduction ........................................................................................................................................................... 9
Description of Devices .............................................................................................................................. 9
Stryker™ Lon Configurable CVAHU Controller .............................................................................. 9
General ................................................................................................................................. 9
Features ................................................................................................................................ 9
Zio®/Zio Plus LCD Wall Modules ................................................................................................. 10
General ............................................................................................................................... 10
Features .............................................................................................................................. 10
Control Application ....................................................................................................................... 10
Control Provided .......................................................................................................................... 11
Products Covered ........................................................................................................................ 12
Organization of Manual ................................................................................................................ 12
Applicable Literature .................................................................................................................... 12
Product Names ............................................................................................................................ 12
Agency Listings ............................................................................................................................ 13
Abbreviations ............................................................................................................................... 14
Constructions of Controller and Wall Module ............................................................................... 14
Stryker CVAHU configuration by Zio wall module ........................................................................................... 15
Contractor Mode: Introduction ................................................................................................................ 15
Initial Power-Up ............................................................................................................................ 16
Contractor Mode: Configuration Steps ......................................................................................... 17
Set Home Screen ................................................................................................................ 17
Set View More ..................................................................................................................... 18
Parameters.......................................................................................................................... 20
Sensors ...................................................................................................................... 21
Status ......................................................................................................................... 22
Temp Sp ..................................................................................................................... 25
Override ..................................................................................................................... 28
Alarms ........................................................................................................................ 28
Snsr Calibration .......................................................................................................... 31
Wm Config ................................................................................................................. 31
Cnfg Ctl ................................ ...................................................................................... 35
Cnfg Ui ....................................................................................................................... 39
Cnfg Di ....................................................................................................................... 39
Cnfg In........................................................................................................................ 40
AO1 ............................................................................................................................ 44
2
Page 3
STRYKER CVAHU ZIO CONFIGURATION GUIDE
AO2 ........................................................................................................................... 44
AO3 ........................................................................................................................... 45
Cnfg Out .................................................................................................................... 46
Time .......................................................................................................................... 50
Set Time .................................................................................................................... 51
Set Date..................................................................................................................... 51
Schedule.................................................................................................................... 53
Tenant Mode: Introduction ..................................................................................................................... 54
Tenant Mode: View Steps ........................................................................................................... 54
Fan ..................................................................................................................................... 55
Override.............................................................................................................................. 56
System & View More .......................................................................................................... 57
3
Page 4
STRYKER CVAHU ZIO CONFIGURATION GUIDE
List of Figures
Figure 1: Stryker™ Lon Configurable CVAHU Controller ......................................................................................... 9
Figure 2: Zio/Zio Plus LCD Wall Modules............................................................................................................... 10
Figure 3: Typical Stryker CVAHU control application ............................................................................................. 11
Figure 4: Stryker CVAHU configuration by Zio wall module ................................................................................... 15
Figure 5: Key position of wall module ..................................................................................................................... 15
Figure 6: TR70 Series Wall Module - LCD screen ................................................................................................. 16
Figure 7: Model number and Sylk bus address ...................................................................................................... 16
Figure 8: Contractor mode default home screen .................................................................................................... 17
Figure 9: Home screen Roomtemp ........................................................................................................................ 17
Figure 10: Home screen Room Setpoint, Roomtemp............................................................................................. 17
Figure 11: Home screen Outside Room Temperature ........................................................................................... 18
Figure 12: Home screen Room, Room Setpoint Temperature ............................................................................... 18
Figure 13: Set View More First screen ................................................................................................................... 18
Figure 14: Parameter group Sensors ..................................................................................................................... 20
Figure 15: Parameters Sensors Zio Temp ............................................................................................................. 20
Figure 16: Parameters Sensors Zio Temp ............................................................................................................. 21
Figure 17: Parameter Status Htg Out ..................................................................................................................... 22
Figure 18: Parameter Status Clg Out ..................................................................................................................... 22
Figure 19: Parameter Status Damper .................................................................................................................... 22
Figure 20: Parameter Status Dmd Limit ................................................................................................................. 22
Figure 21: Parameter Status Trmnl Ld ................................................................................................................... 23
Figure 22: Parameter Status Aux Econ .................................................................................................................. 23
Figure 23: Parameter Status Free Mod .................................................................................................................. 23
Figure 24: Parameter Status Free Dtg ................................................................................................................... 23
Figure 25: Parameter Status Fan ........................................................................................................................... 24
Figure 26: Parameter Temp Sp Occ Clg ................................................................................................................ 25
Figure 27: Parameter Temp Sp Occ Htg ................................................................................................ ................ 25
Figure 28: Parameter Temp Sp Unoc Clg .............................................................................................................. 25
Figure 29: Parameter Temp Sp Unoc Htg .............................................................................................................. 25
Figure 30: Parameter Temp Sp Stby Clg ............................................................................................................... 26
Figure 31: Parameter Temp Sp Stby Htg ............................................................................................................... 26
Figure 32: Parameter Temp Sp Setpoint ................................................................................................................ 26
Figure 33: Parameter Temp Sp Frz Prtc ................................................................................................................ 26
Figure 34: Parameter Temp Sp Eff Sp ................................................................................................................... 27
Figure 35: Parameter Override Fan Ovrd ............................................................................................................... 28
Figure 36: Parameter Alarms Emrg Ovrd ............................................................................................................... 28
4
Page 5
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 37: Parameter Alarms Clg Ovrd .................................................................................................................. 28
Figure 38: Parameter Alarms Htg Ovrd .................................................................................................................. 29
Figure 39: Parameter Alarms Fan Ovrd.................................................................................................................. 29
Figure 40: Parameter Alarms Frost ........................................................................................................................ 29
Figure 41: Parameter Alarms Iaq Alm .................................................................................................................... 29
Figure 42: Parameter Alarms Invld Sp.................................................................................................................... 30
Figure 43: Parameter Alarms Spc Temp ................................................................................................................ 30
Figure 44: Parameter Snsr Cal Zio T Of ................................................................................................................. 31
Figure 45: Parameter Snsr Cal Zio H Of................................................................................................................. 31
Figure 46: Parameter Wm Config Units .................................................................................................................. 31
Figure 47: Parameter Wm Config Type .................................................................................................................. 31
Figure 48: Parameter Wm Config Cntr Sp .............................................................................................................. 32
Figure 49: Parameter Wm Config Cntsp Hi ................................ ............................................................................ 32
Figure 50: Parameter Wm Config Cntsp Lo............................................................................................................ 32
Figure 51: Parameter Wm Config Byps Min ........................................................................................................... 32
Figure 52: Parameter Wm Config Htgsp Hi ................................ ............................................................................ 33
Figure 53: Parameter Wm Config Htgsp Lo............................................................................................................ 33
Figure 54: Parameter Wm Config Clgsp Hi ............................................................................................................ 33
Figure 55: Parameter Wm Config Clgsp Lo ............................................................................................................ 33
Figure 56: Parameter Wm Config Efhtg HI ............................................................................................................. 34
Figure 57: Parameter Wm Config Efhtg Lo............................................................................................................. 34
Figure 58: Parameter Wm Config Efclg HI ............................................................................................................. 34
Figure 59: Parameter Wm Config Efclg Lo ............................................................................................................. 34
Figure 60: Parameter Cnfg Ctl Hp Type ................................................................................................................. 35
Figure 61: Parameter Cnfg Ctl Clg Type ................................................................................................................ 35
Figure 62: Parameter Cnfg Ctl Clg Tr ..................................................................................................................... 35
Figure 63: Parameter Cnfg Ctl Clg It ...................................................................................................................... 36
Figure 64: Parameter Cnfg Ctl Htg Type ................................................................................................ ................ 36
Figure 65: Parameter Cnfg Ctl Htg Tr ..................................................................................................................... 37
Figure 66: Parameter Cnfg Ctl Htg It ...................................................................................................................... 37
Figure 67: Parameter Cnfg Ctl Fan Mode............................................................................................................... 38
Figure 68: Parameter Cnfg Ctl Oc Snorp................................................................................................................ 38
Figure 69: Parameter Cnfg Ui Ui 1 ......................................................................................................................... 39
Figure 70: Parameter Cnfg Di Di 1 ......................................................................................................................... 39
Figure 71: Parameter Cnfg In Spe Temp................................................................................................................ 40
Figure 72: Parameter Cnfg In Spe Rh .................................................................................................................... 40
Figure 73: Parameter Cnfg In Spe CO2 .................................................................................................................. 41
Figure 74: Parameter Cnfg In Dischair ................................................................................................................... 41
Figure 75: Parameter Cnfg In Mixedair................................................................................................................... 42
5
Page 6
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 76: Parameter Cnfg In Od Temp ................................................................................................................. 42
Figure 77: Parameter Cnfg In Occ Snsr ................................................................................................................. 43
Figure 78: Parameter Cnfg In Window ................................................................................................................... 43
Figure 79: Parameter AO1 Range.......................................................................................................................... 44
Figure 80: Parameter AO2 Range.......................................................................................................................... 44
Figure 81: Parameter AO3 Range.......................................................................................................................... 45
Figure 82: Parameter Cnfg Out Clg Stg1 ............................................................................................................... 46
Figure 83: Parameter Cnfg Out Clg Stg2 ............................................................................................................... 46
Figure 84: Parameter Cnfg Out Clg Stg3 ............................................................................................................... 47
Figure 85: Parameter Cnfg Out Hp Chang ................................................................ ............................................. 47
Figure 86: Parameter Cnfg Out Htg Stg1 ............................................................................................................... 48
Figure 87: Parameter Cnfg Out Htg Stg2 ............................................................................................................... 48
Figure 88: Parameter Cnfg Out HtgStg3 ................................................................................................................ 49
Figure 89: Parameter Cnfg Out Fan Out ................................................................................................................ 49
Figure 90: Parameter Cnfg Out Damper ................................................................................................................ 50
Figure 91: Parameter Time Time ........................................................................................................................... 50
Figure 92: Parameter Set Time Hours ................................................................................................................... 51
Figure 93: Parameter Set Time Min ....................................................................................................................... 51
Figure 94: Parameter Set Date Year ...................................................................................................................... 51
Figure 95: Parameter Set Date Month ................................................................................................................... 51
Figure 96: Parameter Set Date Day ....................................................................................................................... 52
Figure 97: Parameter Schedule ............................................................................................................................. 53
Figure 98: Parameter Schedule Monday ................................................................................................................ 53
Figure 99: Parameter Schedule Monday Mon E1 .................................................................................................. 53
Figure 100: Tenant mode home screen ................................................................................................................. 54
Figure 101: Tenant mode Fan Auto ....................................................................................................................... 55
Figure 102: Tenant mode Fan On .......................................................................................................................... 55
Figure 103: Tenant mode Fan Off .......................................................................................................................... 55
Figure 104: Tenant Override .................................................................................................................................. 56
Figure 105: Tenant System and View More Sys mode .......................................................................................... 57
Figure 106: Tenant mode Room Temp .................................................................................................................. 57
Figure 107: Tenant mode Rh ................................................................................................................................. 57
Figure 108: Tenant mode Oat ................................................................................................................................ 58
Figure 109: Tenant mode Eff Sp ................................................................................................ ............................ 58
Figure 110: Tenant mode Cntr Sp .......................................................................................................................... 58
Figure 111: Tenant mode Time .............................................................................................................................. 58
Figure 112: Tenant Mode Hours ............................................................................................................................ 59
Figure 113: Tenant Mode Min ................................................................................................................................ 59
Figure 114: Tenant Mode Year .............................................................................................................................. 59
6
Page 7
STRYKER CVAHU ZIO CONFIGURATION GUIDE
List of Tables
Table 1: Stryker reference documents...................................................................................................................... 9
Table 2: Zio reference documents .......................................................................................................................... 10
Table 3: List of applicable literature ................................................................ ........................................................ 12
Table 4: Agency listing ........................................................................................................................................... 13
Table 5: TR values used by the space cooling pid control...................................................................................... 35
Table 6: IT values used by the space cooling pid control. ...................................................................................... 36
Table 7: TR values used by the space heating pid control. ................................................................ .................... 37
Table 8: IT values used by the space heating pid control. ...................................................................................... 37
7
Page 8
STRYKER CVAHU ZIO CONFIGURATION GUIDE
8
Page 9
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Form No.
Title
63-452903
Stryker™ Lon Configurable VAV/CVAHU Controller Specification Data
62-202902
Stryker™ Lon Configurable VAV/CVAHU Controller Installation Instructions
INTRODUCTION
Description of Devices
Stryker™ Lon
Configurable CVAHU Controller
Figure 1: Stryker™ Lon Configurable CVAHU
Controller
Features
Uses the Echelon® LONWORKS® network
protocol.
Free Topology Transceiver (FTT) high-speed
78 kilobits communications network.
Capable of stand-alone operation, but may
also use LONWORKS® bus network communications.
Sylk™ bus for use with Sylk-enabled sensors.  120 controllers per Q7751A, B router when
configured as a repeater.
Field configurable for control, input, and output
functions using the NIAGARA FRAMEWORK® software.
Built-in zone control functions include a remote
wMarkall module interface and a scheduler.
All wiring connections are made to removable
terminal blocks to simplify controller installation and replacement.
For more information, refer below mentioned documents as shown in Table 1:
Table 1: Stryker reference documents
General
The CUL6438SR-CV1 is part of the Stryker family. The controllers are Free Topology Transceiver (FTT) LONMARK®-certified devices designed to control HVAC equipment. This is advanced system feature that allows state-of-the-art, commercial building control. Each controller is configurable using the NIAGARA FRAMEWORK® software.
The Stryker controllers require the Stryker feature to be licensed in the WEBpro workbench tool and the WEBs AX JACE Controller for programming. It can download to any brand of the Niagara Workbench or JACE controller.
Controllers are used in VAV (Variable Air Volume) and CVAHU (Constant Volume Air Handling Unit) control applications. Each controller contains a host microcontroller to run the main HVAC application and a second microcontroller for LONWORKS® network communications. Each controller provides flexible, universal inputs for external sensors, digital inputs, and a combination of analog outputs and digital outputs.
9
Page 10
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Form No.
Title
63-132202
Zio®/Zio Plus LCD Wall Modules Wall Module Specification Data
62-0271-07
Zio®/Zio Plus LCD Wall Modules Wall Module Installation Instructions
63-2719
LCD Wall Modules Wall operating guide
Note: Refer to the Zio/Zio plus LCD Wall
Modules Operating Guide (form 63-
2719) for information about customizing the wall module configuration in the WEBs-AX Workbench, such as modifying the default Home screens or creating your own application.
Zio®/Zio Plus LCD Wall Modules
Figure 2: Zio/Zio Plus LCD Wall Modules
General
The TR70 Series Zio (TR70/TR70-H, TR71/TR71­H) and Zio Plus (TR75/TR75-H) are 2-wire, non­polarity sensitive, and Sylk bus communicating wall
modules for use with Spyder® and Comfort Point™
programmable controllers. All models have a space-temperature sensor,
network bus jack, and an LCD panel with three soft keys and two Up/Down adjustment keys. The TR7­H, TR71-H and TR75-H models include an on­board humidity sensor.
Features
The TR70 Series wall modules include: Ability to control tenant access to controller
parameters via password protection.
Ability to assign labels for enumerated values.  Customized parameter access, by using the
Honeywell WEBs-AX Workbench tool.
Ability to link setpoint limits to a network
variable.
Programmable for: home screen options,
tenant access, contractor access, optional password protection to contractor mode,
access to controller parameters, Setpoint, override, fan, and other parameters.
Ability to access and adjust most parameters in
the programmable controller.
TR75 can access and adjust the controller
schedule.
Ability to balance the VAV system from the wall
module.
Home screen can display one out of three
following parameters: temperature setpoint, room temperature, room humidity, outdoor humidity, outdoor temperature, and time, or virtually any one of parameters in the controller.
Network bus jack.  Simple 2-wire terminal connection to the
programmable controller (includes power) and an optional 2-wire terminal connection for the network. All connections are polarity insensitive.
Permanent retention of user configuration,
including Setpoints after a power outage.
For more information, refer below mentioned documents as shown in Table 2
Table 2: Zio reference documents
Control Application
Stryker CVAHU systems in commercial buildings typically incorporate a packaged air handler system that delivers a constant volume of air at preconditioned temperatures to the zone being served. Each zone is usually serviced by a separate AHU; however, sometimes two or more AHUs service the same zone. The Stryker CVAHU can control staged or modulating heating and cooling coils, mixed air economizer dampers, and the system fan. Control of heat pump units, where the compressor(s) is used for both cooling and heating, is also provided. The zone the Stryker CVAHU services can use a TR71/75 for space temperature sensing and an S-bus and LON bus network access for users via Zio and front end graphics respectively.
10
Page 11
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 3 shown below is typical Stryker CVAHU control application.
Figure 3: Typical Stryker CVAHU control application
Control Provided
The Stryker CVAHU Controller is designed to control a single air handler to maintain the unit’s space temperature at the current Setpoint. Heating and cooling control are provided for either staged or modulating equipment. Up to three stages of mechanical cooling and up to three stages of heating are allowed. Modulating outputs can be either floating type such as a series 60 control, or pulse width modulated (PWM) control. The economizer dampers can be controlled directly with floating or PWM outputs, or indirectly using a digital output as an enable/disable signal to a packaged economizer controller. The economizer enable function, determines when to allow outdoor air for free, cooling, can be configured, to one of the strategies based on the inputs. When the economizer position is controlled from the Stryker CVAHU, the minimum position setting (for ventilation requirements) is adjusted based on
indoor air quality (IAQ) needs in the space. IAQ monitoring is provided through either a CO2 sensor or a digital input from a space-mounted IAQ limit switch.
For heat pump configurations, up to three compressors can be controlled, along with up to three stages of auxiliary heat, and a heat/cool change over valve. Including the supply fan, a combination of these items may not exceed eight outputs in a Stryker CVAHU. The Stryker CVAHU Controller can monitor a space-mounted occupancy sensor, and a door/window contact. These inputs affect the operational mode of the controller.
The Stryker CVAHU Controller allows other controllers in the system to use the physical inputs and outputs. A digital input and an analog input can be configured to read switch states and voltage sensor values, respectively, and send them out over the S and LON-bus network.
11
Page 12
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Form No.
Title
63-452903
Stryker™ Lon Configurable VAV/CVAHU Controller Specification Data
62-202902
Stryker™ Lon Configurable VAV/CVAHU Controller Installation Instructions
63-132202
Zio®/Zio Plus LCD Wall Modules Wall Module Specification Data
62-0271-07
Zio®/Zio Plus LCD Wall Modules Wall Module Installation Instructions
63-2719
LCD Wall Modules Wall operating guide
209541B
LONWORKS® Bus Wiring Guidelines/ Termination Module Installation Instructions
Note:
All models have a space-temperature sensor, network bus jack, and an LCD panel with three soft keys and two up/down adjustment keys. The TR70-H, TR71-H and TR75-H models include an onboard humidity sensor.
Products Covered
This System Engineering Guide describes how to configure Stryker CVAHU controller via TR71/75 Zio wall module.
Stryker CVAHU Controllers and related accessories to typical applications are as follows:
Stryker CVAHU controller.  TR71/75 wall modules.  209541B FTT termination module.
Organization of Manual
This manual is divided into two basic parts: introduction and configuration.
The Introduction provides information for Stryker LON configurable CVAHU controller and TR70 series Zio/Zio Plus LCD wall modules, control application, control provided, product covered, and abbreviations.
Configuration steps provide information for the engineering of Stryker LON configurable CVAHU controller by TR70 series Zio/Zio Plus LCD wall modules using its various function keys.
The organization of the manual assumes a project is being engineered from installation to finish.
Applicable Literature
List of documents containing information related to the configurable lighting controllers as shown in
Table 3.
Table 3: List of applicable literature
For additional CVAHU Stryker and Zio wall module latest documents and updates visit
http//www.customer.honeywell.com
And search for CVAHU Stryker and Zio wall module respectively.
Product Names
Stryker LON CVAHU controller is available as one model.
CUL6438SR-CV1: Constant volume air handling unit controller from Stryker LON family.
The TR70 series Zio wall module is available in four models:
TR70  TR70H  TR71  TR71H
The TR70 series Zio Plus wall module is available in two models.
TR75  TR75H
Other products:
Q7751A, B: Router (configured as a repeater) Q7752A, B: Serial interface adapter 209541B: Termination module.
12
Page 13
Device
Agency
Comments
CUL6438SR-CV1
controller
UL
Tested and listed under UL916 (Standard for open energy management equipment) with plenum rating. File number ­E87741
cUL
Listed (E87741).
CSA
LR95329-3 listed.
FCC
Meets FCC Part 15, Subpart B, Class B (radiated emissions) requirements.
Meets Canadian standard C108.8 (radiated emissions).
CE
Conforms to the following requirements per European Consortium standards: EN 61000-6-1; 2001 (EU immunity) EN 61000-6-3; 2001 (EU emissions)
Zio®/Zio Plus LCD
wall modules
TR70, TR71, TR75
with Sylk® bus
UL
(Not applicable.)
cUL
(Not applicable.)
CSA
(Not applicable.)
FCC
(Not applicable.)
CE
(Not applicable.)
Agency Listings
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Table 4: Agency listing
13
Page 14
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Abbreviations
AHU: Air Handling Unit. The central fan system includes the blower, heating equipment, cooling equipment, ventilation air equipment, and other related equipment.
CO: Carbon Monoxide. Occasionally used as a measure of indoor air quality.
CO2: Carbon Dioxide. Often used as a measure of indoor air quality.
CPU: Central Processing Unit cUL: Underwriters Laboratories Canada CVAHU: Constant Volume Air Handling Unit; refers to
a type of air handler with a single-speed fan that provides a constant amount of supply air to the space it serves.
Echelon: The Company that developed the LON® bus and the Neuron® chips used to communicate on the E-bus.
Economizer: Mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor conditions, fresh air is used to supplement the mechanical cooling equipment. Since this action saves energy, the dampers are often referred to as economizer dampers.
EMI: Electromagnetic Interference. Electrical noise that can cause problems with communications signals.
EMS: Energy Management System; refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building.
Enthalpy: The energy content of air measured in BTUs per pound (Kilojoules per Kilogram).
Firmware: Software stored in a nonvolatile memory medium such as an EPROM.
Floating Control: Floating Control utilizes one digital output to pulse the actuator open, and another digital output to pulse it closed.
FTT: Free Topology Transceiver. IAQ: Indoor Air Quality. It refers to the quality of the
air in the conditioned space, as it relates to occupant health and comfort.
I/O: Input/Output; the physical sensors and actuators connected to a controller.
I * R: I times R or current times resistance; refers to
Ohm’s Law: V = I x R. K: Degrees Kelvin. NV: Network Variable; a Stryker CVAHU parameter
that can be viewed or modified over the Lon/S-bus network.
PWM: Pulse Width Modulated output; allows analog modulating control of equipment using a digital output on the controller.
RTD: Resistance Temperature Detector; refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.
TPT: Twisted Pair Transceiver. VA: Volt Amperes; a measure of electrical power
output or consumption as applied to an AC device. Vac: Voltage alternating current; AC voltage rather
than DC voltage. VAV: Variable Air Volume; refers to either a type of
air distribution system, or VAV Box Controller that controls a single zone in a variable air volume delivery system.
Constructions of Controller and Wall Module
For more details, refer to the following literature: 63-452903: Stryker™ Lon Configurable
VAV/CVAHU Controller Specification Data 62-202902: Stryker™ Lon Configurable
VAV/CVAHU Controller Installation Instructions 63-132202: Zio®/Zio Plus LCD Wall Modules Wall
Module Specification Data 62-027107: Zio®/Zio Plus LCD Wall Modules Wall
Module Installation Instructions
63-2719: LCD Wall Modules Wall operating guide. 209541B: LONWORKS® Bus Wiring Guidelines/
Termination Module Installation Instructions
14
Page 15
STRYKER CVAHU ZIO CONFIGURATION GUIDE
STRYKER CVAHU CONFIGURATION BY ZIO WALL MODULE
Figure 4: Stryker CVAHU configuration by Zio wall
module
Strykers are configured by the new TR71/75 wall modules. Nearly every configuration parameter is available at the Zio wall module, so configuration and even balancing is done by simply powering up the controller, connecting a Zio and then configuring the parameters available. After configuration is done via the Zio, an Integrator perform an upload and the configuration is added to the WEBs-AX station database.
Since Stryker has the capability to utilize Zio, an installer uses a conventional sensor on all installed Stryker units, and then uses a single Zio to configure as many Stryker’s as desired. Since the Zio’s program and configuration are stored in the Stryker, each time the Zio is connected to a new Stryker, it gets its program from that device.
This document serves as a configuration guide for an installer who is configuring a Stryker CVAHU controller via a TR71 or TR75 wall module. Parameters are grouped into logical categories rather than on a large list. To access the “contractor” mode for configuration, press the up, down and middle keys simultaneously. During this time the model number and firmware revision of the TR71/75 are displayed. You are then prompted to enter a password (default
0000).
Compatibility
The TR70 Series LCD Wall Modules operate with the Sylk Enhanced Stryker controller. The TR71/TR75 can replace a TR70 in an installation where an upgrade to WEBs- AX or Stryker or reprogramming is not desired. Features like scheduling, additional memory, etc. are not available. Likewise, a TR71 is replaced by another TR71 or TR75 without reprogramming required. A TR75 can only be replaced with a TR75 where no reprogramming is desired.
Contractor Mode: Introduction
Contractor mode: You can navigate to the desired
category of parameters. You can then begin configuring and viewing information from the device.
Each screen below has a brief explanation of the data; values within the contractor mode are only visiable in English (U.S.) units of measure. Temperatures however can be shown on the home screen as C or F.
Contractor mode allows access to the Setup function of the wall module. To enter and exit the setup function – press the up and down arrow keys and the middle soft key all at the same time (see key positions of wall module as shown in Figure 5).
Figure 5: Key position of wall module
Contractor mode allows advanced options (such as modifying configured parameters) using the soft keys. Contractor mode also allows for customizing the
tenant’s view including setting the tenant’s Home
screen and controlling the tenant’s “view more
access, which can provide the tenant with a view of the configured parameters.
15
Page 16
STRYKER CVAHU ZIO CONFIGURATION GUIDE
IMPORTANT:
1. Make sure the TR70 Series wall module is properly mounted and properly wired and connected to the programmable controller.
2. Refer to the Zio™ LCD wall modules TR70 Series with Sylk™ bus – installation instructions, form no. 62 – 0271, for specific installation requirements.
Initial Power-Up
Upon initial power-up before configuring the wall module, the LCD screen of the wall module will display status as “PLEASE LOAD”. As shown in
Figure 6, the startup screen of the wall module where
the status is displayed. And also illustrates all the possible LCD Wall Module
display elements. Only those elements pertinent to the current configuration and status actually display.
Controller features not supported by Zio configuration
Network functionality  Accessory loops  Custom sensors  Local sensor (UI 1-4) calibration
CVAHU controller default configuration
Wall module: Zio  Center setpoint source: Zio  Center setpoint: disabled (controller ignores
center setpoint value
Center setpoint high limit: 100  Center setpoint low limit: –10  Room temperature source: Zio (TR71/75)
Figure 6: TR70 Series Wall Module - LCD screen
This phrase alternates with any onboard sensor display such as temperature. The TR71/TR75 also display the firmware revision number, model number and Sylk bus address as shown in Figure 7.
Figure 7: Model number and Sylk bus address
On power-up, screen displays revision and Zio model number.
16
Page 17
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Contractor Mode: Configuration Steps
The Contractor Mode screen as shown in Figure 8
Figure 8: Contractor mode default home screen
The three soft keys on the contractor home screen provide the following three options
1. Set home screen
2. Set view more
Figure 9: Home screen Roomtemp
Home screen: ROOMTEMP Description: Default home screen displays room
temperature (setpoint is not adjusted from this home screen as shown in Figure 10)
3. Parameters
Set Home Screen
SET HOME SCREEN allows the contractor to choose among multiple home screen options for the tenant.
The tenant’s home screen choices are created by the configuration wizard and downloaded to the wall module. Each wall module may have different home screen choices. The contractor, using the soft keys, may choose which home screen is to be used. He may configure the Tenant view to show a subset (or none) of the configured parameters.
When the contractor clicks the SET HOME SCREEN soft key, the display changes as shown in the Figure 9 to Figure 12. The soft keys change to DONE, CANCEL, and NEXT as per configuration requirement.
Click NEXT soft key to cycle through the
configured home screens.
Click DONE soft key when the desired home
screen to be set as default home screen for Tenant view.
The CANCEL soft key exits the home screen
display without saving any changes.
Figure 10: Home screen Room Setpoint,
Roomtemp
Home screen: ROOM SETPOINT, ROOMTEMP Description: Displays room temperature and
effective room temperature setpoint (setpoint is not adjusted from this home screen)
17
Page 18
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note: Click NEXT, DONE, and CANCEL to do
YES or NO configuration for below mentioned parameters.
Figure 11: Home screen Outside Room
Temperature
Home screen: OUTSIDE ROOMTEMPERATURE Description: Displays outside air temperature and
room temperature (setpoint is not adjusted from this home screen)
Figure 12: Home screen Room, Room Setpoint
Temperature
Home Screen: ROOM, ROOM SETPOINT
TEMPERATURE Description: Displays room temperature and room
setpoint temperature (setpoint is adjusted from this home screen)
Set View More
SET VIEW MORE allows the contractor to provide parameter access (view only or adjustable) to the tenant’s VIEW MORE soft key.
Click SET VIEW MORE soft key to display the first configured parameter as shown in Figure 13.
Figure 13: Set View More First screen
The soft keys changes to DONE, CANCEL, and NEXT as per configuration requirement.
The Up and Down arrow keys switch the
parameter between YES and NO (view or no view in tenant mode). o YES means that the tenant has access to
the parameter on the VIEW MORE screen.
o NO means that the tenant does not have
access to the parameter.
o If NO is selected for all parameters, then the
VIEW MORE soft key does not display in
tenant mode.
Click NEXT soft key to cycle through the
configured VIEW MORE screen’s next parameter or category
Click DONE soft key to save configuration
changes.
Click CANCEL soft key to exit VIEW MORE
without saving any changes.
18
Page 19
STRYKER CVAHU ZIO CONFIGURATION GUIDE
After clicking NEXT on particular screen, parameters are displayed in following order.
1. ZIO HUM
2. ROOMTEMP
3. RH
4. CO2
5. DISCHRG
6. OAT
7. OAH
8. OCC SNSR
9. WINDOW
10. MON SWTH
11. MON MODU
12. CLG STG
13. HTG STG
14. DAMPER
15. DMD LIMT
16. TRMNL LD
17. AUX ECON
18. FREE MOD
19. FREE DIG
20. FAN
21. OCC CLG
22. OCC HTG
23. UNOCC CLG
24. UNOCC HTG
25. STBY CLG
26. STBY HTG
27. SETPOINT
28. FRZ PRTC
29. EFF SP
30. FAN OVRD
31. EMRGOVRD
32. CLG OVRD
33. HTG OVRD
34. FAN OVRD
35. FROST
36. IAQ ALM
37. INVLD SP
38. SPCTEMP
39. ZIO T OF
40. ZIO H OFF
41. UNITS
42. TYPE
43. CNTR SP
44. CNTSP HI
45. CNTSP LO
46. BYPS MIN
47. HTGSP HI
48. HTGSP LO
49. CLGSP HI
50. CLGSP LO
51. EFHTG HI
52. EFHTG LO
53. EFCLH HI
54. EFCLG LO
55. HP TYPE
56. CLG TYPE
57. CLG TR
58. CLG IT
59. HTG TYPE
60. HTG TR
61. HTG IT
62. FAN MODE
63. OC SNROP
64. UI1
65. UI2
66. UI3
67. UI4
68. UI5
69. UI6
70. DI1
71. DI2
72. DI3
73. DI4
74. SPC TEMP
75. SPC RH
76. SPC CO2
77. DISCHAIR
78. MIXEDAIR
79. OD ETMP
80. OCC SNSR
81. WINDOW
82. RANGE (for AO1)
83. RANGE (for AO2)
84. RANGE (for AO3)
85. CLG STG1
86. CLG STG2
87. CLG STG3
88. HP CHANG
89. HTG STG1
90. HTG STG2
91. HTG STG3
92. FAN OUT
93. DAMPER
94. TIME
95. HOURS
96. MIN
97. YEAR
98. MONTH
99. DAY
100. SCHEDULE
19
Page 20
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Parameters
PARAMETERS allow the contractor to monitor and/or adjust parameters in the programmable controller.
Click PARAMETERS soft key on contractor mode default home screen to display the first configured category as shown in Figure 14.
The soft keys changes to DONE, EDIT, and
Click the EDIT soft key to display the parameter
Figure 14: Parameter group Sensors
NEXT as per configuration requirement.
list for the selected category. It displays the first parameter in that category (For example ZIO TEMP parameter in the SENSORS category as
shown in Figure 15.
Click NEXT on SENSORS parameter group screen. Other parameter group screens are displayed in following order.
1. Status
2. Temp SP
3. Override
4. Alarms
5. Snsr Cal
6. Wm Confg
7. Confg Ctl
8. Confg Ui
9. Confg Di
10. Confg In
11. AO1
12. AO2
13. AO3
14. Cnfg Out
15. Time
16. Set Time
17. Set Date
18. Schedule
Figure 15: Parameters Sensors Zio Temp
If the parameter is configured as adjustable by
the tenant, the up and down arrow keys adjust the value of the parameter.
Click NEXT soft key to display the next
parameter or category.
Click DONE soft key to save configuration
changes.
Click CANCEL soft key to the exit PARAMETER
group or PARAMETER without saving any changes.
20
Page 21
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Sensors
(CVAHU sensor value display) Click the PARAMETERS soft key to display the first
configured category SENSORS. Within this category, one sample Zio display is shown for reference and the remaining parameters are available for view only as per the following order.
Following is the path to access the screen as shown in Figure 16:
CONTRACTOR>PARAMETERS>SENSORS>ZIO TEMP
Figure 16: Parameters Sensors Zio Temp
Click CANCEL to return to SENSORS. SENSOR
is parameter group for this parameter.
Click NEXT to access parameters in the following
sequence.
ZIO TEMP: Display Zio temperature which corresponds to the onboard temperature sensor and is an output of the Sbus wall module function block.
ZIO HUMIDITY: Displays Zio humidity (%) sensor from wall module
ROOMTEMP: Displays room temperature and is an input to the Sbus wall module function block.
RH: Displays room relative humidity (%) and is an input to the Sbus wall module function block.
CO2: Displays room CO Sbus wall module function block.
(PPM) and is an input to the
2
DISCHRG: Displays discharge air temperature and is an input to the Sbus wall module function block.
OAT: Displays outside air temperature and is an input to the Sbus wall module function block.
OAH: Displays outside air humidity (%) and is an input to the Sbus wall module function block.
OCC SNSR: Displays occupancy sensor and is an input to the Sbus wall module function block.
Status is displayed as follows OCC, UNOC, BYPS, STBY, UNDEFINED Configuration settings in program are as follows: 0 = OCC (Occupancy Mode) 1 = UNOC (UN occupancy Mode) 2 = BYPS (Bypass Mode 3 = STBY (Standby Mode) 4 = UNDEFINED
WINDOW: Displays window open/closed contact status and is an input to the Sbus wall module function block.
Status is displayed as follows: CLOS, OPEN, UNDEFINED Configuration settings in program are as follows: 0 = CLOS (Window close status) 1 = OPEN (Window open status) 2 = UNDEFINED
MON SWTH: Displays monitory switch and is an input to the Sbus wall module function block.
Status is displayed as follows: OFF, ON, UNDEFINED Configuration settings in program are as follows: 0 = OFF 1 = ON 255 = UNDEFINED
MON MODU: Displays mon modulation and is an input to the Sbus wall module function block.
21
Page 22
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Status
(CVAHU parameter status display)
Figure 17: Parameter Status Htg Out
HTG OUT: Displays cooling output signal.
Figure 19: Parameter Status Damper
DAMPER: Displays damper (%) output signal.
Figure 18: Parameter Status Clg Out
CLG OUT: Displays heating output signal.
Figure 20: Parameter Status Dmd Limit
DMD LIMIT: Displays demand limit setpoint shift
status as ON or OFF Configuration settings in program are as follows: 0 = OFF, 1 = ON, 255 = OFF
22
Page 23
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 21: Parameter Status Trmnl Ld
TRMNL LD: Displays effective terminal load (%) on
the controller. Its value ranges from 160% to 160%. A positive value indicates a cooling load and a negative value indicate heating load.
Figure 23: Parameter Status Free Mod
FREE MOD: Displays configured free modulating1
(%) output signal. Its value ranges from 0% to 100%. It is controlled by network command.
Figure 22: Parameter Status Aux Econ
AUX ECON: Displays auxiliary economizer status as
ON or OFF Configuration settings in program are as follows: 0 = OFF, 1 = ON, 255 = UNDEFINED
Figure 24: Parameter Status Free Dtg
FREE DTG: Displays configured free digital1
command status as ON or OFF. It is controlled by network command.
Configuration settings in program are as follows: 0 = OFF, 1 = ON, 255 = UNDEFINED
23
Page 24
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 25: Parameter Status Fan
FAN: Displays fan digital output status as ON or OFF.
Configuration settings in program are as follows: 0 = OFF, 1 = ON, 255 = UNDEFINED
24
Page 25
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Temp Sp
(CVAHU temperature setpoint configuration)
Figure 26: Parameter Temp Sp Occ Clg
OCC CLG: Displays and allows modification of
occupied cooling setpoint. Its value ranges from EFCLG LO to EFCLG HI.
Figure 28: Parameter Temp Sp Unoc Clg
UNOC CLG: Displays and allows modification of
unoccupied cooling setpoint. Its value ranges from STBY CLG to 90.
Figure 27: Parameter Temp Sp Occ Htg
OCC HTG: Displays and allows modification of
occupied heating setpoint. Its value ranges from EFHTG LO to EFHTG HI.
Figure 29: Parameter Temp Sp Unoc Htg
UNOC HTG: Displays and allows modification of
unoccupied heating setpoint. Its value ranges from 50 to STBY HTG.
25
Page 26
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 30: Parameter Temp Sp Stby Clg
STBY CLG: Displays and allows modification of
standby cooling setpoint. Its value ranges from OCC CLG to UNOC CLG.
Figure 32: Parameter Temp Sp Setpoint
SETPOINT: Displays and allows modification of
centre setpoint read from wall module. Its value ranges from CNTSP LO to CNTSP HI.
Figure 31: Parameter Temp Sp Stby Htg
STBY HTG: Displays and allows modification of
standby heating setpoint. Its value ranges from OCC HTG to UNOC HTG.
Figure 33: Parameter Temp Sp Frz Prtc
FRG PRTC: Displays and allows modification of
Space freeze protection setpoint. Its value ranges from 30 to 70. The space heating setpoint is shifted to this value when a window is opened.
26
Page 27
Figure 34: Parameter Temp Sp Eff Sp
EFF SP: Displays room temperature effective
setpoint. Its value ranges from 40 to 100.
STRYKER CVAHU ZIO CONFIGURATION GUIDE
27
Page 28
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Override
(CVAHU override used for fan)
Figure 35: Parameter Override Fan Ovrd
FAN OVRD: Displays and allows modification of
supply fan override command as ON, OFF or UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 0 = OFF, 1 = ON, 255 = UNDEFINED
Alarms
(CVAHU parameter alarms)
Figure 36: Parameter Alarms Emrg Ovrd
EMRG OVRD: Displays smoke detector status as
TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 37: Parameter Alarms Clg Ovrd
CLG OVRD: Displays cooling override status as
TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
28
Page 29
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 38: Parameter Alarms Htg Ovrd
HTG OVRD: Displays heating override status as
TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 40: Parameter Alarms Frost
FROST: Displays frost override status as TRUE,
FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 39: Parameter Alarms Fan Ovrd
FAN OVRD: Displays fan override status as TRUE,
FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 41: Parameter Alarms Iaq Alm
IAQ ALM: Displays IAQ alarm override status as
TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
29
Page 30
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 42: Parameter Alarms Invld Sp
INVLD SP: Displays invalid setpoint override status
as TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 43: Parameter Alarms Spc Temp
SPC TEMP: Displays space temperature override
status as TRUE, FALS or UNDEFINED. Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
30
Page 31
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Snsr Calibration
(CVAHU sensor calibration)
Figure 44: Parameter Snsr Cal Zio T Of
ZIO T OF: Displays and allows modification of Zio
temperature offset. Its value ranges from –100 to +100.
Wm Config
(CVAHU wall module configuration)
Figure 46: Parameter Wm Config Units
UNITS: Displays and allows modification of units to
be displayed for temperature parameters as C, F, UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 0 = F (Deg. F), 1 = C (Deg. C), 255 = UNDEFINED
Figure 45: Parameter Snsr Cal Zio H Of
ZIO H OF: Displays and allows modification of Zio
humidity (%) offset. Its value ranges from –100 to +100.
Figure 47: Parameter Wm Config Type
TYPE: Displays and allows modification of type for
wall module to be used as NONE, TR20, ZIO, UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 0 = NONE (No wall module) 1 = TR20 (Conventional wall module TR20) 2 = ZIO (ZIO TR71/TR75) 255 = UNDEFINED
31
Page 32
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 48: Parameter Wm Config Cntr Sp
CNTR SP: Displays and allows modification of centre
setpoint as FALS, TRUE, UNDEFINED. This parameter defines whether centre Setpoint is to be used or not.
Default configuration: UNDEFINED Configuration settings in program are as follows: 0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 49: Parameter Wm Config Cntsp Hi
CNTSP HI: Displays and allows modification of centre
setpoint high limit. Its value ranges from CNTSP LO to +100.
Figure 50: Parameter Wm Config Cntsp Lo
CNTSP LO: I Displays and allows modification of
centre setpoint low limit. Its value ranges from –10 to CNTSP HI.
Figure 51: Parameter Wm Config Byps Min
BYPS MIN: Displays and allows modification of wall
module bypass time setpoint in minutes. Its value ranges from 0 to 1092.
32
Page 33
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 52: Parameter Wm Config Htgsp Hi
HTGSP HI: Displays and allows modification of
heating setpoint high limit. Its value ranges from HTGSP LO to +100.
Figure 54: Parameter Wm Config Clgsp Hi
CLGSP HI: Displays and allows modification of
cooling setpoint high limit. Its value ranges from CLGSP LO to +100.
Figure 53: Parameter Wm Config Htgsp Lo
HTGSP LO: Displays and allows modification of
heating setpoint low limit. Its value ranges from 0 to HTGSP HI.
Figure 55: Parameter Wm Config Clgsp Lo
CLGSP LO: Displays and allows modification of
cooling setpoint low limit. Its value ranges from 0 to CLGSP HI.
33
Page 34
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 56: Parameter Wm Config Efhtg HI
EFHTG HI: Displays effective heating high setpoint.
Figure 58: Parameter Wm Config Efclg HI
EFCLG HI: Displays effective cooling high setpoint.
Figure 57: Parameter Wm Config Efhtg Lo
EFHTG LO: Displays effective heating low setpoint.
Figure 59: Parameter Wm Config Efclg Lo
EFCLG LO: Displays effective cooling low setpoint.
34
Page 35
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Type
Without
Economizer
TR
With
Economizer
TR
Mod 5 NA
1stg 3 5
2stg 5 7
3stg 7 9
4stg 9 11
Note:
1. Modulating cooling not compatible with Econo_Type = 1 Packaged.
2. Modulating compressor is not supported for heat pump control.
3. Automatic Gain Selection feature is enabled when Throttling Range (TR) is 0. Default TR is 0.
Cnfg Ctl
(CVAHU configuration for control)
Figure 60: Parameter Cnfg Ctl Hp Type
HP TYPE: Displays and allows modification of heat
pump type selection as; CON, GSHP, ASHP. Default configuration: CON
Configuration settings in program are as follows: 0 = CON (Conventional control) 1 = GSHP (Water Source Heat Pump, WSHP. Heat Pump Control with water status enable signal) 255 = ASHP (Air Source Heat Pump, ASHP. Heat pump control without water status enable signal)
Figure 62: Parameter Cnfg Ctl Clg Tr
CLG TR: Displays and allows modification of space
cooling PID control throttling range. Its value ranges from 0 to 30 ∆F.
Throttling Range (TR):
When TR is nonzero, this value of TR is used by the space cooling PID control.
Auto Gain Selection:
When TR is 0, Table 5 shows the TR values are used by the space cooling PID control.
Table 5: TR values used by the space cooling pid
control
Figure 61: Parameter Cnfg Ctl Clg Type
CLG TYPE: Displays and allows modification of
number of cooling/heat pump stages as: NONE, 1STG, 2STG, 3STG, 4STG, ANA.
Default configuration: 2STG Configuration settings in program are as follows: 0 = NONE, 1 = 1STG, 2 = 2STG, 3 = 3STG,
4 = 4STG, 10 = ANA
35
Page 36
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Type
Without
Economizer IT
With
Economizer IT
1stg
3333
2000
2stg
2000
1429
3stg
1429
1111
4stg
1111
909
Note:
1. Modulating heating is not supported for heat pump auxiliary heat.
2. Automatic Gain Selection feature is enabled when Throttling Range (TR) is 0.
Figure 63: Parameter Cnfg Ctl Clg It
CLG IT: Displays and allows modification of cooling
PID control integral time. Its value ranges from 0 to 5000 sec.
Integral Time (IT):
When TR is nonzero, this value of IT is used by the space cooling PID control.
Auto Gain Selection:
When TR is 0, Table 6 shows the IT values are used by the space cooling PID control.
Table 6: IT values used by the space cooling pid
control.
Figure 64: Parameter Cnfg Ctl Htg Type
HTG TYPE: Displays and allows modification of
heating output type for conventional or heat pump auxiliary heat as: NONE, 1STG, 2STG, 3STG, 4STG, ANA.
Default configuration: 2STG Configuration settings in program are as follows: 0 = NONE, 1 = 1STG, 2 = 2STG, 3 = 3STG,
4 = 4STG, 10 = ANA
36
Page 37
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Type
TR
1stg 3 2stg 5 3stg 7 4stg
8
Type
IT
1stg
3333
2stg
2000
3stg
1429
4stg
1111
Figure 65: Parameter Cnfg Ctl Htg Tr
HTG TR: Displays and allows modification of space
heating PID control throttling range. Its value ranges from 0 to 30 ∆F.
Throttling Range (TR):
When TR is nonzero, this value of TR is used by the space heating PID control.
Auto Gain Selection:
When TR is 0, Table 7 shows the TR values are used by the space heating PID control.
Table 7: TR values used by the space heating pid
control.
Figure 66: Parameter Cnfg Ctl Htg It
HTG IT: Displays and allows modification of heating
PID control integral time. Its value ranges from 0 to 5000 sec.
Integral Time (IT):
When TR is nonzero, this value of IT is used by the space heating PID control.
Auto Gain Selection:
When TR is 0, Table 8 shows the IT values are used by the space heating PID control.
Table 8: IT values used by the space heating pid
control.
37
Page 38
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note:
1. If an occupancy sensor is configured and the space is scheduled for occupied and the occupancy sensor is inactive, the mode switches to standby.
2. Manual override commands have priority over the schedule and the occupancy sensor.
3. Occupancy Sensor Behavior a. 1 – No occupancy detected (inactive)
b. 0 – Occupancy detected (active)
Figure 67: Parameter Cnfg Ctl Fan Mode
FAN MODE: Displays and allows modification of fan
mode to be used for CVAHU. This can be changed as CONT, AUTO, FAN, and UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 0 = CONT (Fan runs continuously when the
effective occupancy is OC OCCUPIED or OC BYPASS. The fan cycles on and off with demand for cooling and may cycle with heating if FanOnHeat is TRUE during OC UNOCCUPIED or OC STANDBY modes.)
1 = AUTO (Fan cycles on and off with demand
for cooling and may cycle with heating if FanOnHeat is TRUE. This is known as the
intermittent mode of operation.) 2 = FAN (Enable local fan switch) 255 = UNDEFINED
Figure 68: Parameter Cnfg Ctl Oc Snorp
OC SNORP: Displays and allows modification of
occupancy sensor operation status. This can be changed as CLN, CONF, TNNT, and UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 1 = CLN (Unoccupied Cleaning Crew, when
scheduled to be unoccupied and the occupancy sensor is active, switch to standby for the comfort of the cleaning crew)
2 = CONF (Conference Room, when scheduled to
be unoccupied stay unoccupied independent of the occupancy sensor activity)
3 = TNNT (Unoccupied Tenant, when scheduled
to be unoccupied and the occupancy sensor is active, switch to occupied for the comfort of the tenant.)
255 = UNDEFINED
38
Page 39
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Cnfg Ui
(Configuration of CVAHU universal inputs)
Figure 69: Parameter Cnfg Ui Ui 1
UI 1: Displays and allows modification of input type
for universal input 1. This can be changed as: NTC, TR T, TRAB, TRRL, DGNO, and DGNC.
Default configuration: NTC Configuration settings in program are as follows: 0 = NTC (20 KNTC) 1 = TR T (TR2x 20KNTC) 2 = TRAB (TR2x Setpoint Absolute) 3 = TRRL (TR2x Setpoint Relative) 14 = DGNO (Digital Normally Open) 15 = DGNC (Digital Normally Closed)
Clicking NEXT the following parameters are available with configuration settings similar to UI1:
UI2 = Universal Input2 UI3 = Universal Input3 UI4 = Universal Input4 UI5 = Universal Input5 UI6 = Universal Input6
Cnfg Di
(Configuration of CVAHU digital inputs)
Figure 70: Parameter Cnfg Di Di 1
DI 1: Displays and allows modification of input type
for digital input 1. This can be changed as: DGNO, DGNC, and UNDEFINED.
Default configuration: UNDEFINED Configuration settings in program are as follows: 14 = DGNO (Digital Normally Open) 15 = DGNC (Digital Normally Closed) 255 = UNDEFINED
Clicking NEXT the following parameters are available with configuration settings similar to DI1:
DI2 = Digital Input2 DI3 = Digital Input3 DI4 = Digital Input4
39
Page 40
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Cnfg In
(Configuration of CVAHU inputs)
Figure 71: Parameter Cnfg In Spe Temp
SPC TEMP: Displays and allows modification of
logical input configuration /terminal assignment for space temperature. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, ZIO, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 7 = ZIO 255 = UNDEFINED
Figure 72: Parameter Cnfg In Spe Rh
SPC RH: Displays and allows modification of logical
input configuration /terminal assignment for space relative humidity. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, ZIO, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 7 = ZIO 255 = UNDEFINED
40
Page 41
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note:
1. Up to 5 Sbus sensor are supported. The Sbus address is fixed and the configuration enables addresses 8 through 12.
2. Bus address = DIPswitchVal + 8
3. Sbus address is fixed
Sensor #
Bus Address
DIP SW 123
0 8 000
1 9 100
2
10
010
3
11
110 4 12
001
Figure 73: Parameter Cnfg In Spe CO2
SPC CO2: Displays and allows modification of logical
input configuration /terminal assignment for space CO2. This can be changed as: UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 255 = UNDEFINED
Figure 74: Parameter Cnfg In Dischair
DISCHAIR: Displays and allows modification of
logical input configuration /terminal assignment for discharge air temperature. This can be changed as: UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10, SB11, SB12, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 21 = SB8 (C7400s temperature bus Address = 8) 22 = SB9 (C7400s temperature bus Address = 9) 23 = SB10 (C7400s temperature bus Address = 10) 24 = SB11 (C7400s temperature bus Address = 11) 25 = SB12 (C7400s temperature bus Address = 12) 255 = UNDEFINED
41
Page 42
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 75: Parameter Cnfg In Mixedair
MIXEDAIR: Displays and allows modification of
logical input configuration /terminal assignment for mixed air temperature. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10, SB11, SB12, and UNDEFINED
Default Parameter setting: UNDEFINED. Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 21 = SB8 (C7400s temperature bus Address = 8) 22 = SB9 (C7400s temperature bus Address = 9) 23 = SB10 (C7400s temperature bus Address = 10) 24 = SB11 (C7400s temperature bus Address = 11) 25 = SB12 (C7400s temperature bus Address = 12) 255 = UNDEFINED
Figure 76: Parameter Cnfg In Od Temp
OD TEMP: Displays and allows modification of logical
input configuration /terminal assignment for outside air temperature. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10, SB11, SB12, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 21 = SB8 (C7400s temperature bus Address = 8) 22 = SB9 (C7400s temperature bus Address = 9) 23 = SB10 (C7400s temperature bus Address = 10) 24 = SB11 (C7400s temperature bus Address = 11) 25 = SB12 (C7400s temperature bus Address = 12) 255 = UNDEFINED
42
Page 43
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 77: Parameter Cnfg In Occ Snsr
OCC SNSP: Displays and allows modification of
logical input configuration /terminal assignment for occupancy sensor. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, DI 1, DI 2, DI 3, DI 4, and UNDEFINED
Default Parameter setting: UNDEFINED. Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 47 = DI 1 48 = DI 2 49 = DI 3 50 = DI 4 255 = UNDEFINED
Figure 78: Parameter Cnfg In Window
WINDOW: Displays and allows modification of logical
input configuration /terminal assignment for window contacts. This can be changed as UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, DI 1, DI 2, DI 3, DI 4, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = UI 1 1 = UI 2 2 = UI 3 3 = UI 4 4 = UI 5 5 = UI 6 47 = DI 1 48 = DI 2 49 = DI 3 50 = DI 4 255 = UNDEFINED
43
Page 44
STRYKER CVAHU ZIO CONFIGURATION GUIDE
AO1
(Analog output1 range configuration)
Figure 79: Parameter AO1 Range
RANGE: Displays and allows modification of analog
output1 range. This can be changed as 0D10, 10D0, 2D10, 10D2, 0A20, 20A0, 0A22, 22A0, 4A20, 20A4, DIG, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = 0D10 (Analog voltage 0 to 10VDC direct
output) 1 = 10D0 (Analog voltage 0 to 10VDC reverse
output) 2 = 2D10 (Analog voltage 2 to 10VDC direct
output) 3 = 10D2 (Analog voltage 2 to 10VDC reverse
output) 4 = 0A20 (Analog current 0 to 20 mA direct output) 5 = 20A0 (Analog current 0 to 20 mA reverse
output) 6 = 0A22 (Analog current 0 to 22 mA direct output) 7 = 22A0 (Analog current 0 to 22 mA reverse
output) 8 = 4A20 (Analog current 4 to 20 mA direct output) 9 = 20A4 (Analog current 4 to 20 mA reverse
output) 10 = DIG (Analog as binary output) 255 = UNDEFINED
AO2
(Analog output2 range configuration)
Figure 80: Parameter AO2 Range
RANGE: Displays and allows modification of analog
output2 range. This can be changed as 0D10, 10D0, 2D10, 10D2, 0A20, 20A0, 0A22, 22A0, 4A20, 20A4, DIG, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = 0D10 (Analog voltage 0 to 10VDC direct
output) 1 = 10D0 (Analog voltage 0 to 10VDC reverse
output) 2 = 2D10 (Analog voltage 2 to 10VDC direct
output) 3 = 10D2 (Analog voltage 2 to 10VDC reverse
output) 4 = 0A20 (Analog current 0 to 20 mA direct output) 5 = 20A0 (Analog current 0 to 20 mA reverse
output) 6 = 0A22 (Analog current 0 to 22 mA direct output) 7 = 22A0 (Analog current 0 to 22 mA reverse
output) 8 = 4A20 (Analog current 4 to 20 mA direct output), 9 = 20A4 (Analog current 4 to 20 mA reverse
output) 10 = DIG (Analog as binary output) 255 = UNDEFINED
44
Page 45
STRYKER CVAHU ZIO CONFIGURATION GUIDE
AO3
(Analog output3 range configuration)
Figure 81: Parameter AO3 Range
RANGE: Displays and allows modification of analog
output3 range. This can be changed as 0D10, 10D0, 2D10, 10D2, 0A20, 20A0, 0A22, 22A0, 4A20, 20A4, DIG, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = 0D10 (Analog voltage 0 to 10VDC direct
output) 1 = 10D0 (Analog voltage 0 to 10VDC reverse
output) 2 = 2D10 (Analog voltage 2 to 10VDC direct
output) 3 = 10D2 (Analog voltage 2 to 10VDC reverse
output) 4 = 0A20 (Analog current 0 to 20 mA direct output) 5 = 20A0 (Analog current 0 to 20 mA reverse
output) 6 = 0A22 (Analog current 0 to 22 mA direct output) 7 = 22A0 (Analog current 0 to 22 mA reverse
output) 8 = 4A20 (Analog current 4 to 20 mA direct output) 9 = 20A4 (Analog current 4 to 20 mA reverse
output) 10 = DIG (Analog as binary output) 255 = UNDEFINED
45
Page 46
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Cnfg Out
(Configuration of CVAHU analog and digital outputs)
Figure 82: Parameter Cnfg Out Clg Stg1
CLG STG1: Displays and allows modification of
logical output configuration /terminal assignment for Cooling or Heat Pump stage 1 command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
Figure 83: Parameter Cnfg Out Clg Stg2
CLG STG2: Displays and allows modification of
logical output configuration /terminal assignment for Cooling or Heat Pump stage 2 Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
46
Page 47
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 84: Parameter Cnfg Out Clg Stg3
CLG STG3: Displays and allows modification of
logical output configuration /terminal assignment for Cooling or Heat Pump stage 3 Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
Figure 85: Parameter Cnfg Out Hp Chang
HP CHANG: Displays and allows modification of
logical output configuration /terminal assignment Heat Pump change over relay command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
47
Page 48
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 86: Parameter Cnfg Out Htg Stg1
HTG STG1: Displays and allows modification of
logical output configuration /terminal assignment for Heating stage 1 Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
Figure 87: Parameter Cnfg Out Htg Stg2
HTG STG2: Displays and allows modification of
logical output configuration /terminal assignment for Heating stage 2 Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
48
Page 49
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 88: Parameter Cnfg Out HtgStg3
HTG STG3: Displays and allows modification of
logical output configuration /terminal assignment for Heating stage 3 Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
Figure 89: Parameter Cnfg Out Fan Out
FAN OUT: Displays and allows modification of logical
output configuration /terminal assignment for Fan Start-Stop Command. This can be changed as AO 1, AO 2, DOC1, DOA1, DOA2, DOA3, DOB1, DOB2, DOB3, DOB4, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 2 = DOC1 (DO1) 3 = DOA1 (DO2) 4 = DOA2 (DO3) 5 = DOA3 (DO4) 6 = DOB1 (DO5) 7 = DOB2 (DO6) 8 = DOB3 (DO7) 9 = DOB4 (DO8) 10 = AO 3 255 = UNDEFINED
49
Page 50
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 90: Parameter Cnfg Out Damper
DAMPER: Displays and allows modification of logical
output configuration /terminal assignment for Damper control signal. This can be changed as AO 1, AO 2, AO 3, and UNDEFINED.
Default Parameter setting: UNDEFINED Configuration settings in program are as follows: 0 = AO 1 1 = AO 2 10 = AO 3 255 = UNDEFINED
Time
(CVAHU controller time display)
Figure 91: Parameter Time Time
TIME: Displays current time in HH MM format.
50
Page 51
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Set Time
(CVAHU controller time configuration/settings)
Figure 92: Parameter Set Time Hours
HOURS: Displays and allows modification of time in
hours. Its value ranges from 0 to 11.
Set Date
(CVAHU controller date configuration/settings)
Figure 94: Parameter Set Date Year
YEAR: Displays and allows modification of date in
years. Its value ranges from 2008 to 2099.
Figure 93: Parameter Set Time Min
MIN: Displays and allows modification of time in
minutes. Its value ranges from 0 to 59.
Figure 95: Parameter Set Date Month
MONTH: Displays and allows modification of date in
months. Its value ranges from 0 to 12.
51
Page 52
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 96: Parameter Set Date Day
DAY: Displays and allows modification of date in
days. Its value ranges from 0 to 31.
52
Page 53
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Schedule
The Schedule option lets you modify the schedule and change CVAHU Stryker's time. The desired scheduling option (8 day, 7 days, etc.) is
setup in the Configuration Wizard (refer 63-2719: LCD Wall Module Wall Operating Guide). The option screens vary based on that selection.
Following example illustrates the steps for viewing/editing a schedule for Monday. You can similarly view/edit schedule for Saturday and any other holiday
Step 1: To access schedule parameter group refer section Parameters.
Step 2: Use the EDIT soft key to move to the next screen (e. g. Monday).
Figure 97: Parameter Schedule
Step 3: Use the EDIT soft key to move to the next screen (e. g. MON E1).
Figure 99: Parameter Schedule Monday Mon E1
Click the EDIT soft key to change the time and occupancy state for this event.
1. Use the up/down arrows to change the time.
2. When editing an event, use the NEXT soft key to toggle between editing the time and changing the occupancy state (i.e. OCC/UNOCC/STANDBY).
3. Use the up/down arrows to change occupancy state.
4. Click DONE soft key to apply changed time and occupancy state settings.
5. Click CANCEL soft key to exit the MON E1 screen display without saving any changes.
6. Click NEXT and follow above mentioned steps 1 to step 6, to view or edit next three events i. e. MON E2, MON E3, and MON E4.
To remove a programmed event, use the up/down arrow keys to scroll the time to either 12:00 p.m. or 12:00 a.m. Just before reaching 12:00 the time changes to four dashes (- - - -). Click the DONE soft key at this point to remove a programmed event.
In the 5-2 or 5-2-1 schedule options: “5” means Monday to Friday and Monday's
events are shown on the Zio.
Figure 98: Parameter Schedule Monday
“2” means Saturday and Sunday and Saturday's
events are shown on the Zio.
“1” means holiday. When Monday is changed, the TR75 copies that
event to Tuesday and so on till Friday. It updates this schedule into the controller for Monday through Friday. The same occurs for Saturday and Sunday when a change is made on Saturday. When a holiday is modified it is also updated into the controller.
53
Page 54
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note: Tenant mode default home screen may
be in any one of out of above mentioned four home screen set by the contractor. Refer Set Home Screen
Note:
1. The fan and override settings are optional for home screen setup.
2. If the system command option is not enabled, then the SYSTEM soft key does not display on the tenant’s home screen.
3. If there are no parameters configured for tenant’s access, the VIEW MORE soft key does not display on the tenant’s home screen
Note: Following parameters/home screen’s in
Tenant view/adjust mode are for reference only and may change as per configuration done in contractor mode.
Tenant Mode: Introduction
The tenant, using the soft keys and arrow keys, may change following features if these are configured.
1. Setpoints
2. Fan speed
3. System mode (heat/cool)
4. Initiate override
The tenant can change the Occupancy
Override parameter to Occupied, Unoccupied, or Standby. And, the override
can be timed in minutes, days, or be continuous.
Tenant Mode: View Steps
Tenant mode default home screen is as shown
Figure 100 for reference.
HOME SCREEN label: ROOMTEMP Description: Displays system status and room
temperature. By referring to Figure 100, Tenant mode home
screen, has the following three soft keys. They provide the following options which are explained below in detail:
1. Fan
2. Override
3. System and view mode
Figure 100: Tenant mode home screen
54
Page 55
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Fan
The tenant uses Fan to adjust the fan settings depending on the fan options. It has three possible positions (2, 3, or 5 position) configured.
Click the FAN soft key to change the fan icon to the following three positions as shown in Figure 101:
1. AUTO
Figure 101: Tenant mode Fan Auto
Description: Fan has three modes of operation:-
AUTO: Operates in Auto mode.Refer Figure 101.  ON: Operates in manual ON mode. Refer Figure
102.
OFF: Operates in manual OFF mode. Refer
Figure 103.
2. ON
3. OFF
Figure 103: Tenant mode Fan Off
Click the FAN softkey to toggle the fan icon
between ON and AUTO. If the fan is at 2 positions then each click on the FAN soft key, changes the fan icon display between: ON and AUTO.
At position number 5, Fan icon display changes
to one of the following two options:
o OFF o AUTO.
And Fan speed indicator is in one of the following
states:
o Low o Medium o High
Figure 102: Tenant mode Fan On
55
Page 56
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Override
Override allows the tenant to override the occupancy settings (see Figure 104)
Figure 104: Tenant Override
Description: Override is used to make CVAHU ON
before or after occupied schedule or time. Override remaining displays duration left (in hours and minutes) for the override.
For example, if occupied duration is 9:00 AM to 6:00 PM and override operation is configured for one hour, and if override is applied at 6 PM then override remaining will be 25 minutes at 6:35 PM.
Depending on the occupancy/override
configuration click the OVERRIDE soft key. The, occupancy icon changes to one of the following three modes:
o Standby o Occupied o Unoccupied
If an override is set by the tenant, the OVERRIDE
soft key changes to CANCEL OVERRIDE.
Click the CANCEL OVERRIDE soft key to cancel
the override.
56
Page 57
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Note: When the contractor configures a
parameter and selects the Editable by tenant check box, this enables the tenant to adjust the parameter’s value.
System & View More
Click the system & view more key to change the system state and view/adjust configured parameters (see Figure 105).
Figure 105: Tenant System and View More Sys
mode
Click the key. The first click displays the system
information. Click the up and down arrow keys. The system state can assume one of the following states:
o Off o Auto o Cool o Heat
If the contractor enables tenants access to a
parameter, then the tenant can use the up and down arrow keys to adjust the parameter’s value, otherwise the tenant is able to only view the parameter and its value.
Click DONE soft key to save configuration
changes.
Click the CANCEL soft key to exit the display
without saving any changes.
Click VIEW MORE soft key to display each
viewable parameter.
For example,
Figure 106: Tenant mode Room Temp
ROOM TEMP: Displays room temperature and is an
input to the Sbus wall model function block. Use the UP/DOWN arrow keys on Zio module to
increase or decrease the value or state for tenant adjustable parameters
Click DONE soft key to save configuration
changes.
Click the CANCEL soft key to exit the display
without saving any changes.
Click NEXT to access parameters in following
sequence.
Figure 107: Tenant mode Rh
RH: Displays room humidity and is an input to the
Sbus wall model function block.
57
Page 58
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 108: Tenant mode Oat
OAT: Displays outside air temperature and is an input
to the Sbus wall model function block.
Figure 110: Tenant mode Cntr Sp
CNTR SP: Displays and allows modification of centre
setpoint. It is both an input and output to the Sbus wall model function block.
Figure 109: Tenant mode Eff Sp
EFF SP: Displays effective setpoint and is an input to
the Sbus wall model function block.
Figure 111: Tenant mode Time
TIME: Displays controller time in HH:MM format.
58
Page 59
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Figure 112: Tenant Mode Hours
MIN: Displays and allows modification of time in
minutes. Its value ranges from 0 to 59.
Figure 113: Tenant Mode Min
HOURS: Displays and allows modification of time in
hours. Its value ranges from 0 to 11.
Figure 114: Tenant Mode Year
YEAR: Displays and allows modification of date in
years. Its value ranges from 2008 to 2099
59
Page 60
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Printed in U. S. A. on recycled paper containing at least 10% post-consumer paper fibers.
Neuron®, LONWORKS®, LONMARK® are registered trademarks of Echelon® Corporation.
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
http//www.customer.honeywell.com
® U.S. Registered Trademark © 2013 Honeywell International Inc
C.G. 11-2013
31-00023-01 Printed in United States
60
Loading...