Honeywell CTS-V SERIES, CTP-V SERIES Installation Instructions

0 (0)

Solid and Split Core 0-5/10Vdc

Output Current Sensors

CTS-V AND CTP-V SERIES

 

INSTALLATION INSTRUCTIONS

APPLICATION

densing

 

Operating Humidity Range: 0 to 95%, non-con-

The 0-5/10Vdc Output Solid and Split Core Current

Storage Temperature: 41 to 95°F (5 to 35°C)

Sensors are designed for use in any AC current

RH Range: 40% to 85% RH, non-condensing

monitoring application in which you are looking to

Wire Recommendations: 2 Conductor (Shielded

monitor a particular piece of equipment.

 

Cable)

SPECIFICATIONS

Wire Size:

18 to 24 AWG (0.823 mm2 to 0.205 mm) Copper

 

Wires only

Monitored Current Type: AC Current

Maximum AC Voltage: 600 VAC

Isolation Voltage: 2200 VAC

Supply Voltage:

Induced from the Monitored Conductor (Insulated Conductors only)

150-Amp Sensors: 0 to 10 VDC

Operating Temperature Range: 5 to 104ºF (-15 to 40ºC)

Terminal Block Torque Rating: 4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)

Minimum Mounting Distance:

1” (2.6 cm) between current sensor & other magnetic devices (Relays, Contactors, Transformers)

Agency Approvals:

UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE

STANDARD ORDERING

Table 1. Standard Ordering.

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Model #

Selectable Ranges

Measurement

AC Waveform

Solid-Core

Split-Core

Signal

CTS-V-50

0 to 10/20/50A

Average

Pure Sinusoidal

 

0 to 5 VDC

 

 

 

 

 

 

 

CTS-V-150

0 to 50/100/150

Average

Pure Sinusoidal

 

0 to 10 VDC

 

 

 

 

 

 

 

CTP-V-50

0 to 10/20/50A

Average

Pure Sinusoidal

 

0 to 10 VDC

 

 

 

 

 

 

 

CTP-V-150

0 to 50/100/150

Average

Pure Sinusoidal

 

0 to 10 VDC

 

 

 

 

 

 

 

WARNING

WARNING

This product is not intended to be used for

Electrical shock hazard.

Life or Safety applications.

Disconnect and lock out all power sources

This product is not intended for use in any

before installation as severe injury or death

hazardous or classified locations. The CTS-V

may result from electrical shock due to

and CTP-V Series Current Sensors must be

contact with high voltage wires.

used on Insulated Conductors Only!

 

20

31-00144-02

Honeywell CTS-V SERIES, CTP-V SERIES Installation Instructions

SOLID AND SPLIT CORE 0-5/10VDC OUTPUT CURRENT SENSORS

INSTALLATION

Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation. The current sensor will not require external power, since the power for the current sensor is induced from the conductor being monitored.

The current sensor may be mounted in any position using the two #8 x ¾” Tek screws and the mounting holes in the base, or snapped directly on to the 35mm DIN rail (See Fig. 1). Leave a minimum distance of 1” (3 cm) between the current sensor and any other magnetic devices such as contactors and transformers.

<![if ! IE]>

<![endif]>–

+

M37377

Fig. 1. Sensor Placed on Rail.

Latch Operation for CTP-V Series

Press down on the side tab and swing the top of the unit up to open the split core current sensor as shown in Figure 2. Press down firmly on the cover to close the current sensor. An audible “click” will be heard as the tab slides over the tongue on the base.

CAUTION

Mating surfaces of the magnetic core are exposed when the sensor is open.

Electrical contact grease, present on the cores to prevent corrosion, can capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good contact between pole pieces. Visually check the mating parts of the core before closing the current sensor.

M37359

Fig. 2. Opening CTP-V Series.

Current Sensor Setup

The amperage range selected represents the maximum current that can be applied to the conductor being monitored, Do not exceed! All current sensors with selectable ranges will have the range selection jumper factory set on the high range. For models with field selectable amperage ranges, select the correct amperage range using the range selection jumper.

WIRING

We recommend the use of a two conductor 16 to 22 AWG shielded cable, copper wire only, for all Analog current sensor installations. A maximum wire length of less than 30 meters (98.4 feet) should be used between the current sensors and the Building Management System or controller.

31-00144—02