Honeywell CT8611 User Manual

CT8611
PROGRAMMABLE HEAT PUMP THERMOSTAT
INSTALLATION MANUAL
IMPORTANT:
before or after installation. Refer to Owner’s Guide, form 69-0398, for programming instructions.
12-93 • Form Number 69-0816
This thermostat may be programmed either
1 69-0816
Toll-free Customer Assistance
For all questions concerning this thermostat, please read and follow the instructions. If additional assistance is needed, call Honeywell Customer Assistance toll-free at 1-800-468-1502, Monday-Friday, 7:00 a.m.-5:30 p.m. Central Time.
Before you call, please have the following information available—thermostat model number and date code, kind of heating/cooling system (i.e., hot water, warm air, oil, gas, etc.), number of wires connected to the thermostat.
This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference
NOTICE
Regulations, CRC c. 1374.
2
1
PREPARATION
Your new thermostat provides energy saving control for a 24 Vac multistage heat pump heating/ cooling system direct from the control transformer.
The CT8611 includes SYSTEM and ENRG SAV LEDs located near the top of the thermostat face. The SYSTEM LED lights when the thermostat is signaling for heating or cooling. The ENRG SAV LED lights during the LEAVE and SLEEP periods.
The CT8611 also includes AUX. HT. and EM. HT. LEDs near the bottom center of the subbase. The AUX. HT. LED lights whenever the thermostat is calling for operation of the backup or auxiliary heater. Backup (auxiliary) heat is more expensive to operate than the heat pump and typically is used only when the heat pump is unable to handle the heating load. The EM. HT. LED lights whenever the thermostat system switch is in the EM. HT. position.
Heat and cool anticipation is fixed in all models; no adjustment is necessary. Cycle rates are adjust­able for auxiliary heating stage.
Any questions concerning your system’s com­patibility with your thermostat may be directed to Honeywell Customer Assistance at their toll-free number, 1-800-468-1502.
WARNING
This device is designed to operate on low voltage (20 to 30 Vac). The application of higher voltage is dangerous and may cause electrical shock, fire or personal injury.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the CT8611 Heat Pump Thermostat Wiring Guide, form 69-0817, to make sure the prod­uct is suitable for your application.
3. Allow thermostat to warm to room tempera­ture before operating.
4. After installation is complete, check thermo­stat operation as provided in these instructions.
3 69-0816
TOOLS REQUIRED FOR INSTALLATION
Assemble a flat blade screwdriver and other tools as needed (right).
Test to make certain that your heating and
cooling systems are working properly. If either does not work, contact your local heating/air condi­tioning dealer. To avoid compressor damage, do not operate the cooling system if outdoor tempera­ture is below 50° F [10° C].
TURN OFF POWER to the system at the heat
pump and at the fuse/circuit breaker panel.
Carefully unpack your new thermostat. Save
instructions, proof of purchase from packag­ing and original receipt.
FLAT BLADE SCREWDRIVER
WIRE CUTTER/STRIPPER OR SHARP KNIFE, IF NEEDED TO STRIP WIRES
SPIRIT LEVEL, IF NEEDED TO LEVEL THERMOSTAT FOR APPEARANCE
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED TO DRILL HOLES IN WALL
MASKING TAPE, IF NEEDED TO LABEL WIRES AS THEY ARE DISCONNECTED FROM OLD THERMOSTAT
M849
4
REMOVE OLD THERMOSTAT
2
WARNING
If your old thermostat is attached to a junction box in the wall, it is likely that 120V are present. To prevent electrical shock hazard, fied electrician.
do not proceed
. Call a quali-
Disconnect wires from old thermostat or sub
base. Always label all wires as you disconnect them from your old thermostat. Use the CT8611 Wire Tags provided to label each wire with the appropriate terminal designation as you remove it. It is important to note the terminal designation when removing wires. Not all thermostats are wired by color code.
Keep the wires from falling back into the wall by wrapping them around a pencil, as shown.
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. After wiring is complete, push excess wire back into the hole, and plug hole with nonhardening caulk, putty, or insu­lation to prevent drafts from affecting thermostat operation.
Remove cover from old thermostat. If it doesn’t snap off when pulled firmly from the bottom,
check for a screw that locks the cover.
Loosen screws holding thermostat to subbase, wallplate or wall, and lift away.
WIRES THROUGH WALL OPENING
M5136
5 69-0816
Do not discard your old thermostat until you
have thoroughly checked out system opera­tion with your new Honeywell CT8611 Heat Pump Thermostat installed. If your old thermostat con­tains mercury, do not dispose of it in the trash, see below.
RECYCLING THERMOSTAT
If this thermostat is replacing a
thermostat that contains mercury in
not
a sealed tube, do
place your old thermostat in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of your old thermostat.
If you have questions, call Honeywell Inc. at
1-800-468-1502.
MERCURY SWITCH
ANTICIPATOR SCALE
COILED BIMETAL
Typical location of a mercury switch
ANTICIPATOR SETTING LEVER
in a thermostat.
M3376
6
3
MOUNT THERMOSTAT SUBBASE
The subbase does not require leveling for proper operation; level it for appearance only.
Thread wires through the center opening of the subbase. Then, mount the subbase using
the two screws provided. Gently tighten the screws,
Remove thermostat from subbase (Fig. 1).
level the top surface of the subbase and then se­curely tighten the screws.
Mount the subbase directly onto the wall with
the screws included in the package. Use the subbase as a template, and with a pencil, mark the two mounting screw positions (Fig. 2). Use 3/16 in. bit to drill holes for anchors. Gently tap anchors into holes until they are flush with the wall surface.
. HT HEAT OFF COOL
Fig. 1—Removing thermostat from base. Fig. 2—Mounting subbase on wall.
F
A
N
O
N
A
U
T
O
A
U
X
.
H
E
A
T
M9073
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
SUBBASE
7 69-0816
WALL
MOUNTING SCREWS (2)
MOUNTING HOLES
M5175
WIRE THERMOSTAT TERMINALS
4
NOTE: All wiring must comply with local codes and
ordinances. If unsure about household wiring procedures, call Honeywell Customer Assistance with your questions Monday-Friday, 7:00 a.m.­5:30 p.m., Central time, 1-800-468-1502.
Refer to the CT8611 Heat Pump Thermostat Wiring Guide, form 69-0817, and to the wire labels you applied when you removed the old thermostat. Match the letter from your old ther­mostat wire with the appropriate letter on your new thermostat. Follow any special instructions provided in the Wiring Guide. Wire only those terminals shown with lines connecting them. Some terminals on the thermostat may not be used.
RESTRICT WIRING TO THIS AREA
WIRING TO BE BELOW THIS SURFACE
FOR STRAIGHT INSERTION – STRIP 5/16 in. [8 mm]
FRONT VIEW OF
TERMINAL AREA
FOR WRAPAROUND – STRIP 7/16 in. [11 mm]
TOP SURFACE OF SUBBASE
For each wire, loosen the terminal screw, slip the wire beneath its matching terminal, and
tighten the screw.
The shape of the terminal barrier allows straight
or conventional wraparound wiring connections.
NOTE: Keep all wiring restricted to ribbed area
surrounding terminals (Fig. 3) to assure thermo­stat/subbase contact.
CROSS-SECTIONAL VIEW OF
TERMINAL AREA
Fig. 3Keep wiring restricted to ribbed area surrounding terminals.
8
M3062
Figs. 4 and 5 illustrate typical hookups for the CT8611 heat pump thermostat.
CT8611R
R
C
W1
L
Y1
P
E
DEFROST CONTROL
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
COMPRESSOR CONTACTOR
MONITOR
EM. HT. RELAY
W2
G
AUX. HT. RELAY
O
B
FAN
C/O RELAY
HEAT
Fig. 4Typical hook up of CT8611 with jumper intact.
C/O RELAY
COOL
1
(HOT)
M9077
CT8611R
R
C
W1
L
Y1
P
E
MONITOR
DEFROST CONTROL
L2
L1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1ST STAGE HEAT RELAY
1ST STAGE COOL RELAY
W2
G
AUX. HT. RELAY
EM. HT. RELAY
O
B
C/O RELAY
HEAT
C/O RELAY
FAN
COOL
M9076
1
(HOT)
L2
L1
Fig. 5Typical hook up of CT8611 with jumper removed.
9 69-0816
5
COMPLETE INSTALLATION
ADJUST CYCLE RATE
1st stage heating and 1st stage cooling cycle rates are factory-set for heat pumps. The heat pump compressor cycle rate cannot be adjusted.
To customize the thermostats performance to different types of heating equipment, however, a cycle rate adjustment screw is provided on the back of the thermostat to control the auxiliary heat cycle rate. Correct setting of the screw will provide opti­mum savings, See Fig. 6.
1A 1B
NOT USED
AUXILIARY HEAT
1B
CYCLE RATE
IN
OUT 1/2
M9075
Fig. 6Cycle rate adjustment.
TURN
3 CPH
6 CPH
SLOWER CYCLING
FASTER
CYCLING
NOTE: MOST APPLICATIONS DO NOT REQUIRE
A CHANGE IN CYCLE RATE.
The room air temperature normally varies slightly from the comfort temperature setting with the cycling of the heat pump or auxiliary heater.
INSTALL BATTERIES
Three AAA alkaline batteries are included with the thermostat to prevent program loss in case of power outage. Install batteries in back of thermo­stat as shown in Fig. 7. Without battery backup, the
BATTERY PLACEMENT (NOTE CORRECT PLUS AND MINUS DIRECTION)
10
M3058
Fig. 7Battery placement.
program will remain for only about 20 seconds in the event of power loss.
When batteries are first installed, the display
will flash 1:00 PM and 32°. When the batteries are low, the display will flash REPL BAT. You have 20­30 seconds to replace batteries after removing them from the thermostat. After 20-30 seconds, you will have to reprogram. REPL BAT indication will disap­pear when the thermostat is mounted back onto the powered subbase.
If batteries are completely dead, the display will go blank when the thermostat is removed from the subbase. After replacing the battery in this case, reprogramming is necessary.
MOUNT THE THERMOSTAT
With system switch set to OFF, hang the ther­mostat on the tabs at the top of the subbase (Fig. 8A). Swing down and press on lower edge until thermostat snaps in place (Fig. 8B). Open cover and tighten the captive mounting screws (Fig. 8C).
A.
N
A
F
O
T
U
A
N
O
L
O
O
C
F
F
O
T
A
E
H
T H .
M
E
T
A
E
. H
X
U A T
A
E
. H
M
E
SYSTEMENRG. SAVE
M
C.
P
S
E
T
P
R
E
S
E
N
T
D
A
Y
/T
IM
E
H
O
L
D
T
E
M
P
H
E
P
ROOM
MON
HEAT ON
MORNIMG
T
E
M
P
E
R
A
T
U
R
E
P
R
E
S
E
N
R
U
N
R
O
G
R
A
M
P
E
R
D
A
Y
W
A
K
E
S
E
T
S
L
E
E
P
A
T
/C
O
O
L
T
S
E
T
T
IN
G
IO
D
T
IM
E
S
K
IP
L
E
A
V
R
E
T
U
R
N
E
X
E
N
T
A
H
E
A
D
W
A
R
M
E
R
P
E
R
IO
D
C
H
A
N
G
E
B
A
C
K
C
O
O
L
E
R
T
O
L
A
S
T
P
E
R
IO
D
B.
MORNIMG
SYSTEMENRG. SAVE
PM
ROOM
MON
HEAT ON
A
U T
O
M9074
Fig. 8Mounting the thermostat on subbase.
11 69-0816
SET DAY AND TIME
Restore 24V power to the thermostat. When power is applied, the display will read 1:00 PM and indicate the room temperature. It will go off for a few seconds, then begin to flash on and off. Set the present day and time.
Press
Press
.
DAY/TIME
to set the current day. Each press of the
DAY
SET
PRESENT
DAY key advances the display one day.
BACK
Press TIME
AHEAD
or
to set the current time.
If the display will not come on: check the mounting of the thermostat to the
subbase. If loose or misaligned, remove thermo­stat and reinstall on the subbase, making sure it is firmly attached.
check to see that system power is on. check voltage between R and C; it should be 20
to 30 Vac.
12
CHECK THERMOSTAT OPERATION
6
CAUTION
Do not check the heating system op­eration by jumpering thermostat termi­nals at the primary control. This will damage the thermostat.
To avoid possible compressor damage, do not operate the cooling system if the outside temperature is below 50° F [10° C]. See compressor manufacturer’s instructions for further information.
During cold weather, some heat pumps will require that the crankcase heater be energized several hours before op­erating the heat pump. Refer to the manufacturers recommendations.
Restore the power to the system.
CHECK HEATING OPERATION
Move the system switch to HEAT and the fan
switch to AUTO. Press WARMER key until the set­ting is about 10° F [6° C] above room temperature.
Heating should start and the fan should run (there may be a delay of 5-10 minutes before heat turns on). Press COOLER key until the setting is about 10° F [6° C] below room temperature. The heating equipment and fan should shut off.
During checkout, the backup heat will come on immediately. During normal operation, the backup heat will come on after a delay.
Backup (auxiliary) heat is more expensive to operate than the heat pump and typically is used only when the heat pump is unable to handle the load.
CHECK EMERGENCY HEATING
OPERATION
Move the system switch to EM. HEAT and the fan switch to AUTO. Press WARMER key until the setting is about 10° F [6° C] above room tempera­ture. Heating should start and the fan should run.
CHECK COOLING OPERATION
Move the system switch to COOL and the fan switch to AUTO. Press COOLER key until the set­ting is about 10° F [6° C] below room temperature. Cooling should start and the fan should run. Press WARMER key until the setting is about 10° F [6° C] above room temperature. The cooling equipment and fan should shut off.
13 69-0816
ABOUT ADAPTIVE INTELLIGENT RECOVERY
People perceive temperature
TM
from a variety of sources, not only from the air in the room, but also from their surroundingswalls, windows and furnishings.
Human beings feel differences
in temperature
as slight as two degrees Fahrenheit.
Common household thermometers
thermostats
sense only air temperature, which
and standard
may or may not reflect how hot or cold the room
feels
actually
to a human being.
This thermostat reads the temperature of the wall as well as the airand responds to tem­perature changes as little as one degree Fahr­enheitso room temperature is more likely to feel right.
THE OPTIMUM COMFORT AND ENERGY SAVINGS SOLUTION
This thermostat is actually a small but powerful
computer
. When calculating the exact time to turn
Recovery Begins
REPL
AM
BAT
PM
SUN MON TUE WED THU FRI SAT COOL ON HEAT ON
TEMPERATURE
System Operating in Energy Savings Mode
AM PM
SUN MON TUE WED THU FRI SAT COOL ON HEAT ON WAKE LEAVE RETURN SLEEP TEMPORARY UNOCCUIPIED
WAKE LEAVE RETURN SLEEP TEMPORARY UNOCCUIPIED
REPL
SET PT
BAT
on your furnace or air conditioner, it considers (1) air temperature, (2) the temperature of the wall and (3) when you want the comfort temperature established.
During Adaptive Intelligent Recovery
mostat increases the control temperature gradually and turns the equipment on and off several times to save energy by avoiding “overshooting” the comfort temperature. See the current control temperature anytime during recovery by pressing the PRESENT SETTING key. On some models, both the SYSTEM and ENERGY SAVING lights may be lit at the same time during recovery.
This “smart” control learns from experience
day it checks how closely it hit the target and adjusts the recovery start time accordingly.
It typically takes four to eight days after installa­tion for this thermostat to adjust to the weather, life style, home construction and heating/cooling sys­tem. The thermostat calculates the LEAVE/RETURN recovery separately from the SLEEP/WAKE recovery.
System Operating in Comfort Mode
REPL
AM
SET PT
BAT
PM
SUN MON TUE WED THU FRI SAT COOL ON HEAT ON WAKE LEAVE RETURN SLEEP TEMPORARY UNOCCUIPIED
REPL
AM
SET PT
BAT
PM
SUN MON TUE WED THU FRI SAT COOL ON HEAT ON WAKE LEAVE RETURN SLEEP TEMPORARY UNOCCUIPIED
Recovery Continues
SET PT
TM the ther-
. Each
ENERGY SAVINGS PERIOD
THE THERMOSTAT USES THE SAME SCHEME TO RETURN GRADUALLY TO LOWER COMFORT TEMPERATURE DURING THE COOLING SEASON.
RECOVERY FROM ENERGY SAVINGS
TIME
14
COMFORT PERIOD
M171
IF ADDITIONAL ASSISTANCE IS NEEDED, PLEASE CONTACT HONEYWELL CUSTOMER ASSIS­TANCE AT 1-800-468-1502, MONDAY-FRIDAY, 7:00 AM-5:30 PM, CENTRAL TIME. BEFORE YOU CALL, PLEASE HAVE THE FOLLOWING INFORMATION AVAILABLE: TYPE OF HEATING SYSTEM, IGNITION TYPE, WHETHER GAS OR ELECTRIC AIR CONDITIONING, MODEL NUMBER OF OLD THERMOSTAT, NUMBER OF WIRES, AND TERMINAL DESIGNATIONS USED.
15 69-0816
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, Minnesota 55422 Scarborough, Ontario
M1P 2V9
Helping You Control Your World
G.S. 12-93 ©Honeywell Inc. 1993 Printed in Tiawan Form Number 69-0816
16
Loading...