Honeywell CT5OC User Manual

Honeywell
Heating, Air Conditioning or
Heating/Air Conditioning
Thermostats

INSTALLATION INSTRUCTIONS

The CT50A is for most ^as and oil
heating-on(y systems.
The CT50C is lor most electric air conditio/irng-only systems.
The CT51A is lor most gas, oil, or electric heating/electric air condillorring systems,
The CT53A is for milMvoltage heating systems,
DO'it-yourself models
CT50A,C; CT51A; CT53A

PREPARATION

Proper installation of your
new thermostat will occur
if you follow instructions STEP-
BY-STEP. tt is recommended that as you read, understand and complete each step, you check I ^ I it off with pencil or pen.

CT51A shown

If you are unsure about wiring procedures, please calf a qualified service technician for assistance.
X—
SPIPIT LEVEL OR PLUMB BOB AUO LINE
YOUR NEW THERMOSTAT
Your new Honeywell CT50A Heating Thermostat will replace most 15 to 30 V, 2-wire healing system thermostats. The CT50A is suitable only for gas or oil heating systems (NOT lor air conditioning, heating/air conditioning, heat pump or
electric heating systems). Your new CT50C Cooling
Thermostat will replace most 15
Chec)( thermostat
suitability for your home’s
system by reviewing YOUR NEW
THERMOSTAT section, above.
Ш
га
to 30 V, 3'Wire air conditioning
system thermostats (NOT for
heating, heating/air conditioning or heat pomp systems}.
Your new CT51A Heating/Cooling Thermostat will
replace most 15 tg 30 Y, 4-wire, heating/cooling system thermostats. The CT51A is
suitable for gas, oil or electric heating/electric air conditioning systems (NOT for heat pumps}.
Your new CT53A Heating Thermostat is suitable for 250. 500 or 750 millivolt (mV) heating systems only.
Assemble tools required,
ID
as shown left, r
Make certairt that your burner/air conditioner (where applicable) áre working,
especially if they hâve been
inoperative for any length of time. If either does rot work, contact your local heating/air conditioning dealer. Do NOT operate the air conditioning system if outdoor temperature is below 30® F [10° C],
Carefully unpack your
new thermostat. Remove
and discard the packing insert
under the cover.
Save package ol screws
and instruction pages.
CON
PREPAI
THERM
REMONi
WIRE A
CHECK
THERM
TROUB
RECALI
THER
, . FE
anticipator adjustment
mechanism, (See last i illustration tinder step 4 to 'i help you recognize the heat
ahticipator.) Make a note i here 1 [ of that
anticipator setting for future
reference. The heat anticipator pointer, if adjustable, will be set at one ota series of numbers representing the (electrical)
, current rating of the pritnary ! control of your system In
amps. The number will range from 0,1ft to 1,0. If no heat antidi pato r/ i n dr cat¡0 n (s
,i showing, do hot be
cortcerried; move on to the
next step.
Loosen screws
I ■ holding thermostat
¡ báselo Buitoase qr wall, and
Lliftaway,
....
....
j.".
Disconnect wires
from old thermostat or
subbase. If your therrnostat
has more than 2 wires, as you disconnect each wire, tape the end and label it with the letter of the terminal designation to make reconnection to new thermostat easier. Take care that these wires do not fall back into the wall opening.
Keep the old thermostat for reference purposes until
i your new thermostat is
functioning smoothly.
WIRE AND
MOUNT
THERMOSTAT
For CT50A: Connect each
wire from the wall to
either terminal on the back of the thermostat. Tighten the screws.
For CT60C or CT51A:
Connect wires
from the wall to matching terminals on back of thermostat. Tighten the screws,
NOTE: If terminal designations on old thermostat do not match
those on new thermostat, refer to chart below.
OLD THERMOSTAT
TERMINAL MARKED e or F Fan
YorC
! Wor H Heati ng W
HC, V, VC or В
1 HH. M, VR, 4. A or R
i'flitriing CT51A for ELECTRIC furni
need to instali a jumper between t
and 2: If your old subbaSe ts a Q5v : Q634G, you need the jumper. If in I base number, see section 3. If jurr i not installed, the furnace could 6v ; hazard. Use T ft gauge insulated I installing, :
FUNCTION
Cooling Y
Power You have a 5-wire
:i, Power
NEW THERMOSTAT
TERMINAL MARKED
G
system, and cannot use this thermostat; we recommend a CT87B instead.
R
ace systems, you may herrrrostat termirials J;;
9G, Q539U,: Q634D or ' dbUbt аЬо1й cfld siib-
ipef is needed and is
érhéat; саиШд a firè::
fire; strip ends before.
CONTENTS STEP
PREPARATION 1 THERMOSTAT FEATURES REMOVING OLD THERMOSTAT WIRE AND MOUNT NEW THERMOSTAT 4 CHECK OUT THE THERMOSTAT 5 THERMOSTAT SETTING TROUBLESHOOTING RECALIBRATE THERMOMETER 8
LIMITED oiii-VEAR WARfi^TY '
ly^^-iHaRfiywell iWMntbffie prediicttebt.free frcrndvlecl^m .
tom ttiB Oawol puvcbaw by Ih* mnaLmef-fl. SAanfUrine-duiliiS It4 wyrcnty.Ht-'.Vn*■ Чь’‘ДTpat^'WW;i repair or «place 1Ца1Нопву»1в11>пй*а|Т1и|1Г|1Г1а1ввввГгаЫе|йв<1®<3 •ci'iirw.' . ' •••'.• ; •' . ' Д' •'.■ '
Л' Ц№ар1ы1ис1 isOetecIffe. : . ■‘■■■■ ■■■у.- ■ ■ .:■■■■.'■.■. -■ '■-■ •:•'
. a. irtLun it, wiha ЬЙсЛ iJiitoe pfMT^pWCltaSi, balhpdaAl« eriinh'Aijiei.jrm.'^fiich.jHbJ '•'.
b. pfectUQp H tafpftiiry.iietsi a м ort ван». rei»i)tqro»w'iiarwiEiri4f9<jitir»4rt, !iriJj'atwn to!S^i^'efMWri4iii^ '
F'latA.pasbfia praiïaitii. 1c»tl№ гсй1оч1П0в<Нгм4:
.HonayiwH.ftfc. ,. . ■ :
2 3
6 7
ITHa'vïFrsn^ PPW'TK^ <№W lainicHtAL !ôr rplnetattsllofi ЮЙ9, .Thrs iiVmMiiÿ.flliâ.wtdpp^ 1Г Й je'atiPIAA .Çry.HpiicifMll.Ctl^ Itü ül
Ri8t|ufie<N]H’ir9e caMM" by<toriÙ3p'iii|h|dbócQÌRod ivhilBlhà pródiii;twy» liT1h*pMbae#№'iid»MilÌ*l'™r; .'' ' . .' ..' ' ' ' ' :
HD’^ÿwéli'B'eoiD «spowisitittiÿ'ilull jht.Éà tôpafr' w replocâ Biü;0T4dLjef-s*i^Mh.ttii'Æi^ni*'lbnid flÏKi''a- H^re^№LL $ниь reOT.&E'LlAHiE FOR «NV À»W h№t],'№CLIgC}iraG-МЧУ Ir^CtBEMIAL OR 03*{SE«ÏUENni4. С»1ИАЕЗ£$ RE£UL-mG.'DI(№^ iWHeÒTLY,.fiTOM.A«ire»jM3KÓP«tìÌr.MVAf^NrH^ IMPÜED.Ofl Vfi C>ThERFigBJJ|1&OF-.l>1l&'Wl0pLKi.i;.:.S^
oj^taaÓ^ltweKefgalen gr |liTiÌ№9fi.iKCPriBwviMSim»g«i, i4aré>À'£tÌÌ^№ T^ ' ' ' : '
ГИ1Й WAflEÎAWtV .rué,ONLY BtPflESS.'.àyWÏWMrr; HO^EVWeLL WAKES ON Tt^'.F^WÎOWCT. Tl« iKJilATlON .OF ANV IMPtIEO. WAFFWHT^S. |MC^ljïW*4T'œM««.RiWTié&Of.1WeflCrtÀNTi^ÜTSf At® FFmESe.'^^ purpose,« H«1E6Ylimited to
.Тне.С^'^ЕАР QOFiaTÌÒN .Ok'ÏHIS WARF^CTY. SCntt ^ras ifa ГКК atlj>i* rw 1ьп(1 ImpliQd warranty 1йз1г 9fp ibü aboi«
'Ц|т|11э1|[|11 ni^reili(iplj''|çi'yw..-.. .. • . ' . ' .... •'.••'• : • ' '
Tblawaiuiiiy gtv^ ypu 4>i]c^ lBgà>ii^M5'.;ii4(tyDU гт^Гна. (йЬ4г rliible i4t>icb:ii!«li|y rcoiRtilfltà lo . . '
"В^ heivg aftyqgprtbiiiVa^R*tHJ^ ieifrto^alMSb. Tri'l'?*jr£HJnw'r«r WÌ'*-0^!lt»^ ffcjn'^jYii^l lii^., llÿaaOciijÿasÛriiie M^ib;
vittrei.[«'i-scgr4«e-isiift'.-• .. ■ ..' ■ • •• • •
R.T,
•eeWriWlJ O&itfs ' .'T060
П|Л|1|)(Ж АНГв '5б441-'«4С1Г .. :
Velisf, UH'^A^>A38G;'№:£amib—ÌAòi*iey^lVLiiii|lad,'Nb'ri«yyiiea l^Tt)«IK.~4Ci 0l#:imére Foait ЗРОПнгкгдЬ, Qntam MlP£i^ c^l
9-9f7
ttù ËUaarnérô №»d ... - '. $üiiiliüf<№^.D^rtü'l4lfPSV9..
Ptinted in U.S.A.
Form Number 6S-S51J—2
©Honeywell Inc. 1ЭЭ7

THERMOSTAT

FEATURES

ostat.
not match
MOSTAT
MARKED
5-wire I cannot rmostat; lend a ead-
fou may binais 1 I 634D or jid sub i and is;i ig a fire s before
■. ■: :■
Terminal Screws (CT51A shown)
Top Mounting Hole (the-rmOstat to wail or outlet box)
Adjustable Heat Artiejpator Setting Lever (CT50A, CT51A only)
Mounting ClipE itor cover)
Fan Switch fCTSIA only)
Systeni Switch (CT51A only)
Bottom Mounting Hole
Temperature Setting Leuer
For CT53A:
Connect wires to R and W for
750 mV systems. Connect to R and Y
tor 250 or 500 mV systems. Tighten the
screws.
Push excess wire back into wall and plug hole with nonflammable
insulation to prevent drafts from affecting
thermostat operation.
Grasp the thermostat cover at the top and bottom with one hand. Pull Outward on the bottom edge
of the thermostat cover until it snaps
free of the thermostat base.
Fasten thermostat to wall or vertical outlet box with □ screw through the top mounting hole.
See step 2 for hole location.
REMOVING OLD
THERMOSTAT
II you have an electric furnace, you
need to determine how your
fan is controlled. Turn it on
and adjust your present
thermostat so the heat comes on, while observing
whep tbe ian comes on it the fan comes on immediately you need to add the jumper noted in section 4 between terminals 1 & 5, If there is a noticeable detay before the fan comes on, there is no need to add the jumper because your furnace controls the far.
Begin by turning off power to the heating/air conditioning system at the main fuse panel. Most residential
systems have a separate switch box or
circuit breaker for disconnecting power
to the furnace.
Remove cover of old thermostat
cover normally snaps otf when
pulled firmly from the bottom. If it resists,
check for a screw that locks the cover or. For CT50A or CT51A installation,
before removing the old thermostat from the wall, look at it
carefully to locate the heat
Place a bubble level or plumb line against the ther mostat to find the ievel position. Start a screw in the center of the bottom mounting hole. Move the temper
ature setting lever if necessary to uncover the mounting
hole,
a..rK.:,
‘ Bubble Level
..
.
Plumb Line
Plumti Bob or
■ Weight
SJ&jU < ÇQÎiIitiVBdjl
WIRE ANO MOUNT THERMOSTAT (continued)
Recheck for level positioning, and firmly
tighten both mounting screws.
If installing CTSOA or CT51A, make sure you have the current (anticipator setting) for your system Ttiis is the number you wrote in
the box in step 3. If you were unable to find the current draw for step 3, this information can be found printed on the primary control at the iumace. The primary control is usually a gas vatve. zone valve, or a relay or burner control box with the thermostat wires connected to it. For electric heat, you need to add tine f. n relay current, usually 0 2 to 0.4 A.
OIL BURHEh CONTROL
CHECKOUT THE

THERMOSTAT

CAUTtON
To prevent possible com pressor damage, do not operate air conditioning if outdoor temperature is below 50° F [10° C], Once the air conditioner is off. do not turn it on for S minutes; this action will prevent compressor damage.
On the CT51A, the system
switch controls as follows:
HEAT—heating system only
operates.
OFF—heating and air condi
tioning systems are dis connected
COOL—air conditioning sys
tem only operates.
The tan switch controls as follows:
AUTO—Ian operates wheri
heating or air conditioning system operates.
ON—fan operates continu
ously.
NOTE: In the following instruc
tion. disregard healing or air conditioning directions if not applicable to your system.
Turn on power to the
П
heating/air conditioning
system,
Observe system operation
for at least one cycle on
both heating and air conditioning.
To observe; Place the system switch
at HEAT position and fan
switch at AUTO. Move the temper
ature setting lever t0° F ¡6° C] above room temperature. The heatirig equipment should turn on. A short warm-up period may be required before the system fan turns on,
Place system switch at
COOL position and move
temperature setting lever 10° F
[6° C] below room temperature. The air conditioning equipment should turn on and the system fan should turn on.
NOTE; Some systems have a time
delay that can prevent opera tion up to 5 minutes.
Turn the fan switch to ON.
The system fan should turn on. and operate continuously.
The system blower should con tinue to operate at any system switch or thermostat setting.
On the CT50A or CT51A, set heat
anticipator indicator at rating printed on
primary control.
□ Press the thermostat cover firmly onto the
mounting clips
CAUTION
If your anticipator is set too low, it may burn out. Shorting out your valve or control could cause your anticipator to bum out.
THERMOSTAT SETTING
On CT51A, place the sys
tem and fan switches at
the desired settings for operation.
On all models, move the
temperature setting lever
to the desired temperature com
fort level

TROUBLESHOOTiNG

Your Honeywelf thermostat requires little or no attention. Most problems car generally be traced to the following:
NOTE: If your system is heating-only or air conditioning-only, disregard sections not applicable to your system.
SYMPTOM
No heat
Furnace turns on and off.
Major swings in temperature (greater than 2° F [1'" C| when out side temperature is stable).
PROBLEM
System switch at OFF or COOL Position.
Blown fuse or tripped circuit breaker.
Furnace power switch is on OFF.
No pilot name.
Improper connections to
thermostat.
Defective thermostat. (Here’s how you teil: Remove the thermostat trom the wall. Discon nect wire from W ter minal, Touch W wire to R terminal. The thermo stat is detective if the burner comes on.)
Other,
Burner ON period is too short.
Burn er ON is too long
period
CORRECTIVE ACTION
Move switch to HEAT position.
Replace fuse or reset circuit breaker.
Switch to ON.
Relight pilot flame per furnace manufacturer’s instructions,
With power to furnace OFF, tighten at I mounting and terminal screws. Re pair frayed or broken wires.
Exchange the thermostat (see Warranty).
Contact a qualified service technician for assistance.
Remove the thermostat cover and move the heat anticipator lever COUNTER CLOCKWISE one scale mark. Replace the cover and ivait several hours for the system to stabilize.
Remove the thermostat cover and move the heat anticipator lever CLOCK WISE one scale mark. Replace the cover
and wait several hours for the system to stabilize.
SYMPTOM PROBLEM CORRECTIVE ACTION
Thermostat setting and thermometer reading disagree.
No air condition ing.
Thermostat is not level.
Thermostat affected by drafts or radiant heal.
Thermostat is out of cali bration.
Thermometer is out of calibration.
System switch in in OFF or HEAT position.
Blown fuse or tripped circuit breaker.
Compressor switch (lo cated outdoors} is turned OFF
Improper connections to thermostat
Defective thermostat.
(Here’s how you tell:
Remove the thermostat from wall Disconneci wire from V terminal Touch Y wire to terminal R. The thermostat is de­feclive if the compressor starts. Some systems have a time delay, so allow at least 5 minutes,) See caution in section 6.
Other
Recheck the ihermostat position on wall. Use a bubble level to make sure it's level. See step 4,
Contact a qualified service technician to change the location. The thermostat should be about 5 ft [1.5 m] above the floor and on an inside wall.
Contact a qualified service technician to recalibrate the thermostat-
Recalibrate See step 8.
Move switch to COOL position.
Replace fuse or reset circuit breaker.
Move switch to ON posi
tion.
With power to furnace OFF, tighten all mounting and terminal screws, Re pair broken wires.
Exchange the thermostat. See Warranty.
Contact service techni­cian for assistance.
RECALIBRATE THERMOMETER
If the ihermostat set point and the thermometer reading do not agree, the thermometer may need recalibration. Follow the procedure below.
Remove thermostat cover.
Set the cover on a table rear an accurate thermometer.
After allowing 5 or 10 minutes for stabilization, compare the read-
ings.
It the readings are the same, replace cover and put the system into operation.
If the readings are different, insert a hex-head wrench in the ther mometer shaft and turn it until the
thermometers have the same reading. Replace cover and put the system
into operation.
Loading...