GE Industrial Solutions FG600 User Manual

DEH41181
Rev01
g
SMR2 Modbus User Manual
Table of Contents
Introduction .......................................................................................................................2
RTU Transmission Mode .......................................................................................................................... 2
Message frame............................................................................................................................................ 2
RTU Mode Message Frames ...................................................................................................................... 2
Message Format.......................................................................................................................................... 2
Electrical Interface .............................................................................................................2
Communication Environment...........................................................................................3
Register Map .....................................................................................................................2
Fixed Value Registers ................................................................................................................................. 2
Dynamic Value Registers............................................................................................................................ 7
Interpretation of SOS values...................................................................................................................... 9
Setpoint Registers....................................................................................................................................... 9
Event Registers......................................................................................................................................... 13
Interpretation of Event Codes.................................................................................................................. 15
Bit position in Bit map............................................................................................................................. 16
i

Introduction

The SMR2 trip unit has an optional communications module that facilitates monitoring of the trip unit via a master Modbus device. Monitoring features include breaker settings and the breaker status. Communication with the SMR2 trip unit requires a FAMECM module powered externally that provides isolation and protection.
The Modbus communication protocol is a single master multi-slave protocol that is hardware independent and it interfaces with a 2-wire RS485 interface. A single master device initiates and controls all communication with the other slave devices on the network. A computer with a serial port and an external RS-232/RS-485 converter can be used as the master­monitoring device. The SMR II trip unit is always the slave and cannot initiate communication. The maximum number of devices on a Modbus network is 32, i.e. only 31 slave devices can be connected to a master.
MODBUS devices usually include a Register Map. MODBUS functions operate on Register map registers to monitor, configure, and control module I/O. You should refer to the Register map for your device to gain a better understanding of its operation.
The transmission mode defines the bit contents of the message bytes transmitted along the network, and how the message information is to be packed into the message stream and decoded.
Standard MODBUS networks employ one of two types of transmission modes:
i) ASCII Mode ii) RTU Mode The mode of transmission is usually selected along
with other serial port communication parameters (baud rate, parity, etc.) as part of the device configuration.

RTU Transmission Mode

In RTU (Remote Terminal Unit) Mode, each 8-bit message byte contains two 4-bit Hexadecimal characters, and the message is transmitted in a continuous stream. The greater effective character density increases throughput over ASCII mode at the same baud rate.

Message frame

A message frame is used to mark the beginning and ending point of a message allowing the receiving device to determine which device is being addressed and to
know when the message is completed. It also allows partial messages to be detected and errors flagged as a result.
A MODBUS message is placed in a message frame by the transmitting device. Each word of this message (including the frame) is also placed in a data frame that appends a start bit, stop bit, and parity bit.
In ASCII mode, the word size is 7 bits, while in RTU mode; the word size is 8 bits. Thus, every 8 bits of an RTU message is effectively 11 bits when accounting for the start, stop, and parity bits of the data frame.

RTU Mode Message Frames

RTU mode messages start with a silent interval of at least 3.5 character times. Implemented as a multiple of character times at the baud rate being used on the network. The first field transmitted is the device address. The allowable characters transmitted for all fields are hexadecimal values 0-9, A-F. A networked device continuously monitors the network, including the silent intervals, and when the first field is received (the address) after a silent interval of at least 3.5 character times, the device decodes it to determine if it is the addressed device. Following the last character transmitted, a similar silent interval of 3.5 character times marks the end of the message and a new message can begin after this interval.
The entire message must be transmitted as a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the frame (not a continuous stream), the receiving device flushes the incomplete message and assumes the next byte will be the address field of a new message.
In similar fashion, if a new message begins earlier than
3.5 character times following a previous message, the receiving device assumes it is a
continuation of the previous message. This will generate an error, as the value in the final CRC field will not be valid for the combined messages.

Message Format

The Modbus RTU Protocol is strictly based upon a transaction scheme where a master device generates a query and a slave device replies with a response. Each query and response message transaction consists of the following four parts
2
MODBUS ADDRESSES
The master device addresses a specific slave device by placing the 8-bit slave address in the address field of the message (RTU Mode). The address field of the message frame contains two characters (in ASCII mode), or 8 binary bits (in RTU Mode). Valid addresses are from 1-247.
When the slave responds, it places its own address in this field of its response to let the master know which slave is responding.
MODBUS FUNCTIONS
The function code field of the message frame will contain two characters (in ASCII mode), or 8 binary bits (in RTU Mode) that tell the slave what kind of action to take. Valid function codes are from 1-255, but not all codes will apply to a module and some codes are reserved for future use.
MODBUS DATA FIELD
The data field provides the slave with any additional information required by the slave to complete the action specified by the function code. The data is formed from a multiple of character bytes (a pair of ASCII characters in ASCII Mode), or a multiple of two hex digits in RTU mode, in range 00H-FFH. The data field typically includes register addresses; count values, and written data. If no error occurs, the data field of a response from a slave will return the requested data. If an error occurs, the data field returns an exception code that the master's application software can use to determine the next action to take.
The resulting value is compared to the error check field.
Transmission errors occur when the calculated checksum is not equal to the Checksum stored in the incoming packet. The receiving device ignores a bad packet.

Electrical Interface

The electrical interface is 2-wire RS485 where data flow is bi-directional and half duplex. RS-485 lines from the master device should be connected to a FAMECM module, which is powered externally using a 19-29 VDC power supply. Refer Figure 1 and 2.
The following wire types are recommended for network wiring: Belden 3074F – Data Tray 600 V industrial twinax 18 AWG (7X26); or Belden 9841 – 300 V communication cable 24 AWG (7X32); or Alpha 6412 – 300 V Communication cable 24 AWG (7x32). Shielded wire should always be used to minimize noise. Polarity is important in RS485 communications and each '+' terminal of every device must be connected together for the system to communicate.
CRC Error Checking
RTU Mode message frames include an error checking method that is based on a Cyclical Redundancy Check (CRC). The error-checking field of a message frame contains a 16-bit value (two 8-bit bytes) that contains the result of a Cyclical Redundancy Check (CRC) calculation performed on the message contents.
The checksum field lets the receiving device determine if a packet is corrupted with transmission errors. In Modbus RTU mode, a 16-bit Cyclic Redundancy Check (CRC-16) is used. The sending device calculates a 16­bit value, based on every byte in the packet, using the CRC-16 algorithm. The calculated value is inserted in the error check field.
The receiving device performs the calculation, without the error check field; on the entire packet it receives.
Figure1. Connection between ETU and FAMECM module
2
The communication happens at 19200bps with a Modbus address of 100
Figure2. Connection between Breaker and FAMECM module

Communication Environment

The trip unit is always the slave and cannot initiate communication
All the registers are read-only
Hardware layer
RS485: Data moves serially on a 2-wire differential line (used for TX as well as Rx i.e.; half- duplex) N-8-1, no parity, 1 start bit, 8 data bits & 1 stop bit (10 bits per character)
Communication Protocol
RTU Modbus Master-Slave protocol Command­response (half-duplex) Min delay between messages is
3.5 char time Max delay within message is 1.5 char time. Slave Response time: minimum 3.5 char; maximum 50mS + 1mS per register Register order: MSB first, then LSB
In the presence of a communication module on Trip unit
A pair of rotary switch decides the Modbus address (0 to 255) A pair of slide switch decides the baud rate (2400, 4800, 9600 or 19200bps). These switches are available on the backside of the module
In the absence of a communication module on Trip unit
Figure3. Communication modules used with trip unit
Modbus Message Frames
Master’s Query
Data
Start
Data
Byte1
(n bytes)
(n bytes)
No. of
Registers
(2 bytes)
(n bytes)
Byte2
No. of
Registers
(2 bytes)
..
CRC
(2 bytes)
(2bytes)
Byte n
CRC
bytes)
CRC
(2
Slave
Address
(1 byte)
Function
Code
(1 byte)
Address
(2 bytes)
Slave’s Response
Slave
Address
(1byte)
Functio
n Code
(1 byte)
Number
of Bytes
(1 byte)
Examples :
Read Holding Registers (Function Code 03)
Use this command to read setpoint or fixed value registers. It specifies the starting register and the number of registers to be read. Read the registers 3010­3012 from device 100:
Slave
Addres
s
(1
byte)
Function
Code
(1 byte)
Data
Start
Address
(2
bytes)
3
A
A
64h
Response: (register contents: 3010 = 022Bh, 3010 = 0000h, 3012 = 0066h)
Slave
Addres
s
(1byte)
64h
Read Input Registers (Function Code 04) Use this command to read dynamic value or event registers. Read the registers 1058 – 1060 from device 100:
Query:
Slave
Address
(1 byte)
64h
Response: (register content: 1058 = FFFFh, 1059 = A01Ah, 1060 11B1h)
Slave
Addres
s
(1
byte)
64h
Force Single Coil (Function Code 05) Use this command to perform remote control. This command sets a single coil to enter ON or OFF. Force coil 4 of device 100 ON (FF00h force on, 0000h force off)
Query:
Slave
Address
(1 byte)
Functio
n Code
(1 byte)
03h
Function
Code
(1 byte)
Function
Code
(1 byte)
04h
Function
Code
(1 byte)
03h
04h
0Bh C2h
Numbe
r of
Bytes
(1byte)
06h
02h 2Bh 00h
Data
Start
Address
(2 bytes)
04h 22h 00h 03h
Number of Bytes
(1 byte)
06h
FFh FFh A0h
Data
Coil
Address
(2 bytes)
00h 03h
Data
(n bytes)
Byte1
Byte2
00h 00h 66h
(n bytes)
No. Of
Registers
(2 bytes)
Data
(n bytes)
Byte2
-------
Byte1
1Ah 11h B1h
(n bytes)
Data
(2 bytes)
CRCl
CRCh
CRC
-------
(2
bytes
Byte n
)
CRCl
CRC
h
CRC
(2 bytes)
CRCl
CRCh
CRC
(2
bytes)
Byte n
CRCl
CRCh
CRC
(2 bytes)
64h
05h
00h 04h FFh 00h
CRCl
CRCh
Response: (echo query message)
Data
Coil
(n bytes)
Data
(2 bytes)
CRC
CRCl
(2 bytes)
CRCh
Slave
Address
(1 byte)
64h
Function
Code
(1 byte)
05h
Address
(2 bytes)
00h 04h FFh 00h
Preset Single Register (Function Code 06) Use this command to write to a register. This presets a value into a single holding register. Preset register 0002 to 00 03 hex in slave device 17.
Query:
Data
Slave
Address
(1 byte)
11h
Function
Code
(1 byte)
06h
Register
(2 bytes)
00h 02h 00h 03h
(n bytes)
ddress
No. of
Registers
(2 bytes)
CRC
(2 bytes)
CRCl
CRCh
Response (echo query message)
Data
Slave
Address
(1 byte)
Function
Code
(1 byte)
Register
(2 bytes)
(n bytes)
ddress
No. of
Registers
(2
(2 bytes)
CRC
bytes)
11h
06h
00h 02h 00h 03h
CRCl
CRCh
Retransmit Last Message (Function Code 56) Query:
Slave Address
(1 byte)
64h
Function Code
(1 byte)
38h
CRCl CRCh
CRC
(2 bytes)
Response
Slave Function
Data
(n bytes)
CRC
4
Addres
s
(1
byte)
64h
Code
(1 byte)
38h
Previous transmitted data
xxh xxh xxh xxh xxh xxh xxh xxh xxh
(2 bytes)
CRCl
CRCh
Exception Response
If the slave receives a message without a communications error, but is unable to process it, the slave will return an exception response to inform the master of the error. The high order bit will be set in the function code and returned with the characterizing exception response code:
01h - Invalid Function Code The Function Code is not recognized or defined by the SMR2.
02h - Invalid register The Register address is not recognized or defined by the SMR2
05h – Acknowledge The SMR2 has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the master.
06h - Slave busy
Function Code
Command Purpose Register Group
The SMR2 is busy processing a long duration command. The master should retransmit the message latter when the slave is free.
84h - Partial register access error Command reads or writes to a register that represents only part of the SMR2 register address. The multiple register addresses must be read or written together. Example: Long Time SOS consumes 2 register addresses, thus both must be read together.
85h - Write protect violation Command writes to a valid Register, which is defined as Read Only.
88h - Invalid coil The Coil address is not recognized or defined by the SMR2.
Function Codes
The Modbus functions listed in below are supported:
03 Read Holding Registers Reading the setpoint
registers
04 Read Input Registers Reading actual value
registers
05 Force Single Coil Setting the signal coil or
executing single command
06 Preset Single Register Write Data into single
Register
16 10 hex
56 Retransmit last message Retransmit last message N/A
Preset Multiple Registers Write Data into multiple
Registers
5
Setpoint registers, Fixed value registers
Actual value registers and event registers
Command coils
Setpoint registers, Fixed value registers
Setpoint registers, Fixed value registers

Register Map

While modbus communication with Target Communication Accessory module, all the registers are read only registers. None of them can be written. But while Modbus communication with Test Kit, most of the Fixed value & Setpoint registers can be read as well as written.
Fixed value registers start at 0000 and are read by Function Code 03. Actual value registers start at 1000 and are read by Function Code 04.
Register address 0000 Product Id 0-65535
0001 ETU Serial Number
0002 ETU Serial Number
0003 ETU Date Code
0004 ETU Date Code low 0-9999
0005
0006
Contents Range Type R/W Format
0-65535
high
0-65535
low
0-9999
high
Frame Size 1 to 3
Amp Rating 1 to 13 Normal
Event registers start at 2000 and are read by Function Code 04. Setpoint registers start at 3000 and are read by Function Code 03.
Writing to the Coil registers, implement supervisory control through remote commands
All registers composed of 16 bit integers, values less than 256 stored in lower byte

Fixed Value Registers

Fixed value registers address starts at 0000, read by Function Code 03. Written with Function code 06/16 (decimal) The data stored in these registers are the data stored during trip unit optioning.
Normal mode –RO Test mode
--- RW Normal mode -- RO Test mode --
- RW Normal mode --- RO Test mode
--- RW Normal mode --- RO Test mode
--- RW Normal mode --- RO Test mode
--- RW Normal mode --- RO Test mode
--- RW
mode--- RO
Unsigned Int
Unsigned Int
Unsigned Int
Unsigned Int
Unsigned Int
Unsigned Int 1 G400 2 G630 3 K Unsigned Int 1 7/7 2 25/25 3 60/63 4 125/125
2
0007
0008
0009
0010
Information Memory Option Byte 1
Software revision number Product revision number
Max Number of events stored
Bitmappe d 0 to FFFFh
0000 to 9999 0000 to 9999
Always 8 RO Unsigned Int

Dynamic Value Registers

Actual value registers start at 1000, read by Function Code 04.All the dynamic value registers are 32-bit in length. Hence, query of any variable results in two Modbus register reads, each of 16-bit length. Even numbered register holds upper-16 bits; Odd numbered register holds lower –16 bits
Test mode
-- RW
Normal mode--- RO
___________
Test mode
--- RW
RO 4 digit BCD
Normal mode --- RO Test mode
--- RW
Example: To find out Phase-A SOS, A Modbus query to read 1002 and 1003 registers need to be sent to SMR2 by the master.
There are 32 bits in this data. The upper-16 bits would appear in register 1002 and lower-16 bits in register 1003 as a part of the response.
5 150/160 6 250/250 7 400/400 8 600/630 9 800/800 10 1200/1250 11 1600/1600 12 350 13 500
b0 Instantaneous 0 enabled
1 disabled b1 Short Time 0 enabled 1 disabled b2 Long Time 0 enabled 1 disabled b3 Watchdog 0 enabled 1 disabled b4 Zone Select Interlock 0 enabled 1 disabled b5 50-60/400 Hz Operation 0 50/60 Hz 1 400 Hz b6 Thermal Watchdog 0 disabled 1-99 enabled b7 Unused
4 digit BCD
7
LT Accumulators (A, B, C & N) give normalized values and are typically max 1.25. Hence, they are multiplied
Reg. Contents Range Type
1000-01 Number of pending
0 - 4294967295 RO Unsigned Int
event 1002-03 SOS Current Phase A 0 - 4294967295 RO Unsigned Int 1004-05 SOS Current Phase B 0 - 4294967295 RO Unsigned Int 1006-07 SOS Current Phase C 0 - 4294967295 RO Unsigned Int 1008-09 SOS Current Phase N 0 - 4294967295 RO 1010-11 LT Accumulator A*1040 - 4294967295 RO Unsigned Int 1012-13 LT Accumulator B*1040 - 4294967295 RO Unsigned Int 1014-15 LT Accumulator C*1040 - 4294967295 RO Unsigned Int 1016-17 LT Accumulator N*1040 - 4294967295 RO Unsigned Int 1018-19 ST Accumulator 0 - 4294967295 RO Unsigned Int 1020-21

GF Accumulator

0 - 4294967295 RO Unsigned Int
1022-23 PL Accumulator 0 - 4294967295 RO Unsigned Int
1024-25 Breaker Status
Note:
If system is in pickup
corresponding bit is set to
1.
Battery status 1 indicates
healthy battery.
ZSI active is set 1 when
ZSI is ACTIVE.
When breaker is open
AUXS1bit is set to 1.
Bitmapped 0 to FFFFh
1026-27 Push-Button Status 0 - 1 RO Unsigned Int
1028-29 Measured ETU
0 - 100 RO Unsigned Int
Temperature 1030-31 ETU Trip Count 0-655350 RO Unsigned int 1032-33 LT Trip Count 0-65535 RO Unsigned int 1034-35 ST Trip Count 0-65535 RO Unsigned int 1036-37 Instantaneous Trip
0-65535 RO Unsigned int
Count 1038-39 GF Trip Count 0-65535 RO Unsigned int 1040-41 PL Trip Count 0-65535 RO Unsigned int 1042-43 Software Fault Trip
0-65535 RO Unsigned int
Count 1044-45 Remote Trip Count 0-65535 RO Unsigned int 1046-47 RP Missing Trip Count 0-65535 RO Unsigned int 1048-49 Flash Erased Count 0-65535 RO Unsigned int 1050-51 No module Trip Count 0-65535 RO Unsigned int 1052-53 Over temperature Trip
0-65535 RO Unsigned int
Count
with 10,000 and sent out on Modbus for reading purposes.
Format
R/W
Unsigned Int
RO B0: Unused
B1: ST Pickup B2: GF Pickup B3: PL Pickup B4 (unused) B5: LT 105 Pickup (PU >= 105) B6: LT 95 Pickup (95 <= PU < 105) B7: LT 75 Pickup (75 <= PU < 95) B8: LT 60 Pickup (60 <= PU < 75) B9: LM 1 B10: LM 2 B11: ZSI active B12: Battery Status B13: AUXS1 B14, B15 Unused
1 = Push button is pressed 0 = Push Button is released
8

Interpretation of SOS values

The Sum Of Squares values (SOS) of a phase is a measure of the RMS value of current flowing through that Phase.SMR2 calculates this values in every half cycle and use this value as a measure of current to perform the protection algorithm. The no. of current samples used for SOS calculation depends on the frequency.
When a current equal to sensor rating (I
) value is
CT
For 500A, 50Hz input current SOS value will be
equal to 1297350.

Example: SOS to current conversion

flowing through the breaker, a SOS value of 830304 will be displayed if supply frequency is 50 Hz. For 60 Hz, This value will be 691920.
ICT _SOS_Value for 50 Hz = ICT _SOS_Value for 60 Hz =
830304 691920
Using this value we can calculate SOS value for any current or current for any given SOS value.
For given current , SOS value can be calculated using the following equation:
SOS value = (input current/sensor rating)
2
x
ICT _SOS_Value
For given SOS value ,Current amplitude can be calculated using the following equation:
Input current = (SOS Value /
ICT _SOS_Value
0.5
)
x Sensor Rating

Example: Current to SOS conversion

sensor rating = 400A Input current=500A Frequency =50Hz
select
ICT _SOS_Value
based on frequency
If SOS Value= 7472736 for 50 Hz , then
corresponding current is 1200A
Note:
UL/IEC bit (Bit 0) in Control Byte (Modbus Address
3012) is monitored and ETUs operating frequency is determined based on this bit.

Setpoint Registers

Setpoint registers start at 3000, read by Function Code 03
Reg. Contents Range Type R/W Format 3000 Hour 0 - 23
3001 Minute 0 - 59
Normal mode - RO Test mode RW Normal mode - RO Test mode RW
SOS value = (input current/sensor
2
x
rating)
ICT _SOS_Value
= (500/400)2 x 830304 = 1297350
Sensor rating = 400A SOS Value= 7472736 Frequency =50Hz
Select
ICT _SOS_Value based on frequency
Input current = (SOS Value /
_SOS_Value
0.5
)
= (7472736/830304) = 1200 A
UL/IEC bit (Bit
0) in Control byte
0 - UL 60 Hz
1 - IEC 50 Hz
Unsigned int (Unused)
Unsigned int (Unused)
x Sensor Rating
Line Frequency
ICT
0.5
x 400
9
3002 Seconds 0 - 59
3003 Long Time Pickup 0-15 Normal
3004 Long Time delay 0-6 Normal
3005
3006 Short Time delay 0-9 Normal
3007 Ground Fault pickup 0-8 (in GF
Short time pickup 0-9 Normal
module 0-9 (in GFA module)
Normal mode - RO Test mode RW
Mode--RO
_________
Test Mode
RW
Mode--RO _________
Test Mode RW
Mode--RO
---------------------­Test Mode RW
Mode--RO
_________
Test Mode
RW
Normal Mode--RO
_________
Test Mode
RW
Unsigned int (Unused)
Unsigned int 0 0.625 1 0.65 2 0.675 3 0.7 4 0.725 5 0.75 6 0.775 7 0.8 8 0.825 9 0.85 10 0.875 11 0.9 12 0.925 13 0.95 14 0.975 15 1.0 Unsigned int 0 Line 1.25
1. Line 2.5
2. Line 5
3. Line 10
4. Motor 20
5. Motor 30
6. Unsigned int
Value second I2T 0 40ms No 1 120ms No 2 210ms No 3 310ms No 4 420ms No 5 420ms Yes 6 310ms Yes 7 210ms Yes 8 120ms Yes 9 40ms Yes Unsigned int
0 0.2X 1 0.3X 2 0.4X 3 0.5X 4 0.6X 5 0.7X 6 0.8X 7 0.9X 8 1.0X
10
3008 Ground Fault delay 0-9 Normal
Mode
RO
_________
Test Mode
RW
3009 Inst. Pickup 0-9 Normal
Mode--RO
_________
Test Mode RW
3010 Module Address 0 - 240
3011 Last Trip Data Bitmap
0 - 255
3012 Control Byte Bitmap
0-255
3013 Protection Multiplier 64-100 Normal
3014 Neutral Protection 0-100 Normal
3015 Temperature Limit 0-100 degree C Normal
3016 Product Reject Code Key 0 - 65535 RO 3017 Rating Plug Serial Number
high
3018 Rating Plug Serial Number
low
0-9999 RO
0-9999 Normal
Normal Mode - RO Test mode RW Normal Mode--RO _________ Test Mode RW Normal Mode--RO _________ Test Mode RW
Mode --RO _________ Test Mode RW
Mode RO _________ Test Mode RW
Mode RO _________ Test Mode RW
mode - RO
9 GFA Reset (In GFA module
only)
Value second I2T 0 40ms No 1 120ms No 2 210ms No 3 310ms No 4 420ms No 5 420ms Yes 6 310ms Yes 7 210ms Yes 8 120ms Yes 9 40ms Yes Unsigned int Refer to the table
64% 100%
0%, 50%, 100%
11
Test mode
RW
3019 Rating Plug Date Code
high
3020 Rating Plug Date Code low 0-9999
3021 Rating Plug LT Settings 0 - 255
3022 Number of Data bits 0-1
3023 Number of Stop bits 0-1
3024 Parity 0-2
3025 Baud Rate 0- 3
3026 Modbus Address 1-247 Normal
3027 LM1 Pickup 0-9
3028 LM2 Pickup 0-9
0-9999
Normal mode – RO Test mode RW Normal mode - RO Test mode RW Normal mode - RO Test mode RW Normal mode RO Test mode RW Normal mode – RO Test mode RW Normal mode - RO Test mode RW Normal mode - RO Test mode RW
mode - RO
Normal mode
- RO
Normal mode
- RO
0 7-bits 1 8-bits
0 1-stop bit 1 2-stop bits
0 No parity 1 Even Parity 2 Odd Parity
0 2400 1 4800 2 9600 3 19200
ETU is known by this slave address in the communication network and communicates over this address.
0 0.55 1 0.6 2 0.65 3 0.7 4 0.75 5 0.8 6 0.85 7 0.9 8 0.95 9 1.0 0 0.55
1. 0.6
2. 0.65
3. 0.7
4. 0.75
5. 0.8
6. 0.85
7. 0.9
8. 0.95
9. 1.0
12
3029 Flag Cleared Byte 00 &
0xFF
3030 Test Kit Modbus Address 0 - 255 Normal
3031 Test Kit Baud Rate 0 - 3 Normal
3032 Ammeter Display Current 0 - 9999 Test mode
3033 Ammeter Display Current
Pushbutton
0 - 9999

Event Registers

The trip unit stores up to eight events, with each event utilizing 8 registers to describe the details of the event. Last eight events are stored in chronological order, with EVENT 1 being the oldest event and EVENT n being
Normal mode - RO
mode - RO
mode – RO
RW
Normal mode - RO Test mode RW
Normal mode - RO
the newest. An event is automatically cleared once read by the host.
00 Cleared (trip history can
not be shown on Flag
Module LEDs) 0xFFFF Not Cleared (trip history can be shown on Flag Module LEDs) This is to test COMM switches. This returns the cumulative Modbus address set through two COMM switches. 00 – 2400 01 – 4800 02 – 9600 03 – 19200 This is to test DIP switches. This holds the value which is displayed on LCD display Value greater than 9999 will be displayed as “----“
Alternate value, which can be written while testing Ammeter module. As long as Select_Phase is pushed, this value gets displayed. Value greater than 9999 will be displayed as “----“
13
If another event occurs before the master reads all the existing events, the oldest event is lost, new event data will be placed in the EVENT 8 register, and the older event register contents are shifted. The total number of events since the last reset will be kept counted at register location 1000-1001. Events are read using Function Code 04.
Reg Contents Units/
2000 Event Code – Event 1 0-256 RO Unsigned int 2001 Hour 0 RO Unsigned int 2002 Minute 0 RO Unsigned int 2003 Second 0 RO Unsigned int 2004 Milliseconds 0 RO Unsigned int 2005 Event specific data 1 0 - 65535 RO Unsigned int 2006 Event specific data 2 0 - 65535 RO Unsigned int 2007 Event specific data 3 0 - 65535 RO Unsigned int 2008 Event code – Event 2 0-256 RO Unsigned int 2009 Hour 0 RO Unsigned int 2010 Minute 0 RO Unsigned int 2011 Second 0 RO Unsigned int 2012 Milliseconds 0 RO Unsigned int 2013 Event specific data 1 0 - 65535 RO Unsigned int 2014 Event specific data 2 0 - 65535 RO Unsigned int 2015 Event specific data 3 0 - 65535 RO Unsigned int … … … … 2056 Event code – Event 8 0-256 RO Unsigned int 2057 Hour 0 RO Unsigned int 2058 Minute 0 RO Unsigned int 2059 Second 0 RO Unsigned int 2060 Milliseconds 0 RO Unsigned int 2061 Event specific data 1 0 - 65535 RO Unsigned int 2062 Event specific data 2 0 - 65535 RO Unsigned int 2063 Event specific data 3 0 - 65535 RO Unsigned int
Range
Type R/W
Format
14

Interpretation of Event Codes

The following table describes the meaning of each event code Event
Code (Hex
)
1
2 Short Time O/C trip Fault SOS
3 Instantaneous O/C
4 Ground Fault Trip Fault SOS
5 Phase Loss Trip Phase Loss
6 Remote Trip Bitmap 16-bit 7 8 9 A B C D E Low Trip Voltage
F Software Fault 10 RAM Failure Bitmap 16-bit 11 ROM Failure Bitmap 16-bit 12 13 Rating Plug Missing Bitmap 16-bit 14 Short Time Switch
15
16 Instant Switch change Bitmap 16-bit 17 Module Switch/Type
18 Short Time Delay
19
1A Module Missing Trip
Meaning Register 1 Register 2 Register 3
Long Time Over­current Trip
Trip
Over-Temp Trip
Aux Switch Opened
Warning
Change
Long Time Switch Change
Change
Switch Change
Long Time Delay Switch Change
Fault SOS
Current
Current
Instantaneous
Fault Current
Current
Accumulator
Temperature
Bitmap 16-bit
Bitmap 16-bit
Bitmap 16-bit
Bitmap 16-bit
Bitmap 16-bit
Bitmap 16-bit
Bitmap 16-bit
Fault SOS Current
Fault SOS Current
Instantaneous Fault Current
Fault SOS Current
Phase Loss Accumulator
15

Bit position in Bit map

Bit Position in Bitmap Meaning Event code (Hex)
0
1 0 Aux Switch Open
2 0 No Low Trip Voltage Warning
3 0 No RAM Failure
4 0 No ROM Failure
5 0 No Rating Plug Missing
6 0 No Short Time Switch Change
7 0 No Long Time Switch Change
8 0 No Instant Switch change
9 0 No Module Switch/Type Change
10 0 No Short Time Delay Switch Change
11 0 No Long Time Delay Switch Change
12 0 No Missing Module
0 No Remote Trip 1 Remote Trip
1 Aux Switch Closed
1 Low Trip Voltage Warning
1 RAM Failure
1 ROM Failure
1 Rating Plug Missing
1 Short Time Switch Change
1 Long Time Switch Change
1 Instant Switch change
1 Module Switch/Type Change
1 Short Time Delay Switch Change
1 Long Time Delay Switch Change
1 Missing Module
6
C
0E
10
11
13
14
15
16
17
18
19
12
16
g
General Electric Company 41 Woodford Ave., Plainville, CT 06062
DEH41181 Rev01 © 2006 General Electric Company
GE Consumer & Industrial
17
Loading...