GE Industrial Solutions EP0300AC48TEZ User Manual

Product Description
The rectifier EP0300AC48TE is a compact, single phase, hot­pluggable, fan-cooled rectifier and battery charger for stand­alone use or for working in parallel as part of a DC power system equipped with advanced digital controller. The constant output power (300W i.e. 5.5A at 54V) characteristic supplies the specified power over the full output voltage range (48 to 58Vdc).
There is a digital communication (RS-485 bus) between rectifier and controller which allows flexible system design.
EP0300AC48TEZ
300W Output at 48-58Vdc
Key Features
Efficient rectifier
>90%
Rugged rectifier
Exclusively designed to take care of wide line fluctuations and harsh conditions
¾ Can withstand up to 300Vac (Line-Neutral) without any
damage
¾ Can work up to +75°C
Optimum power performance
Constant power between 90V … 290V ac
Compact and light
3 rectifiers can be accommodated in one row (19” shelf) with controller and distribution
Applications
The typical applications for this rectifier are both in indoor and outdoor environments and include:
SCADA/ DMS System EPBAX Broadband IP telephony Cable Television LTE GPON Enterprise solution
See reverse side for specifications
Technical Specifications
Input Parameters
Operating Voltage range
Full Power input voltage Range
Frequency 45 to 65Hz Maximum Current 4A (rms) 230Vac,100% load
Power Factor > 0.99 at 230Vac,100% load
Total Current Harmonic Distortion (THD)
Efficiency 90%. 230Vac,100% load Input protection In built surge protection (2kV/3kA) Inline fuse
90-290 Vac Disconnect: < 90Vac & > 290Vac No damage up to 300Vac 90-290 Vac
< 10% at 230Vac,100% load
Output Parameters
Voltage, nominal 48 Vdc
Voltage adjust range 42 … 57 Vdc (controller)
Rated output Power
300W
Output Current @...V 5.5A@54V
Maximum current 6.25A
Static Voltage regulation ±1% from 10% to 100% load
Noise (Ripple + spikes) 100 mV
rms
Load sharing 10%
I/P and O/P connector Rear side
Over voltage shutdown
Output protection
Note: As a result of continuous product improvement, all specif ications are subject to change without prior notice. All performance parameters are valid at Nominal input (230Vac) and nominal output
(48Vdc) conditions unless otherwise specified.
Blocking diode Short circuit proof Over temperature protection
Applicable Standards
Electrical safety IEC 60950-1 UL 60950-1 CSA 22.2 EMI As per CISPR-22 EMC IEC 61000-4-5, (Surge immunity limits) IEC 61000-4-6, (RF Conducted susceptibility immunity limits) IEC 61000-4-3, (Radiated Electromagnetic Field immunity limits) IEC 61000-4-4, (EFT/ Burst immunity limits) IEC 61000-4-2, (ESD Immunity limits) Harmonics EN 61000-3-2 Environment RoHS compliant
Ordering Information
Product Description Comcode EP0300AC48TEZ 48V, 300W rectifier 150022411
Country of Sale
South Asia India SE Asia ­NA ­CALA ­European -
Other Parameters
Isolation
Visual Indications
Operating temp -25°C to +75°C Power De-rating
Operating Humidity 5% to 95% RH non-condensing
MTBF
Audible Noise
Mechanical
Width 50.4 mm (2”)
Height 45 mm (1.75”)
Depth 228.6mm (9”)
Weight 0.5 kg (1.1 lbs)
3.0 kVac – I/P & O/P
1.5 kVac – input & earth
0.5 kVac – output & earth Normal LED (Green): 3 status (Blink, OFF, ON) Fault LED (Red): 3 status (Blink, OFF, ON)
+60°C to +75°C
> 150k hours Telcordia SR-332, Method 1, Case 3 (Ambient Temperature.: 25°C) < 60dBA at an ambient noise level of 45dBA, and at ambient temperature of 25°C
GE Critical Power reserves the right to make changes to the product (s) or information contained herein without notice. No liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s) or information.
© 2013 GE Critical Power (Bangalore, India) All Rights Reserved.
Document Rev No: R0.1 Date: 5
PDF name: EP0300AC48TEZ PDS.pdf
th
February 2013