Warning notices are used in this publication to emphasize that hazardous voltages, currents, or
other conditions that could cause personal injury are present in this equipment or may be
associated with its use.
Warning notices are also used for situations in which inattention or lack of equipment knowledge
could cause either personal injury or damage to equipment.
Caution notices are used for situations in which equipment might be damaged if care is not taken.
Notes call attention to information that is especially significant to understanding and operating the
equipment.
This document is based on information available at the time of its publication. While efforts have
been made to ensure accuracy, the information contained herein does not cover all details or
variations in hardware and software, nor does it provide for every possible contingency in
connection with installation, operation, and maintenance. Features may be described herein that
are not present in all hardware and software systems. GE Consumer & Industrial assumes no
obligation of notice to holders of this document with respect to changes subsequently made.
GE Consumer & Industrial makes no representation or warranty, expressed, implied, or statutory,
with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or
usefulness of the information contained herein. No warrantees of merchantability or fitness for
purpose shall apply.
The following are trademarks of GE Company:
EntelliGuard™, EntelliGuard Messenger™, Entellisys™
These instructions do not purport to cover all details or
variations in equipment or to provide for every possible
contingency to be met in connection with installation,
operation or maintenance. Should further information be
desired or should particular problems arise which are not
covered sufficiently for the Purchaser's purposes, the
matter should be referred to the General Electric
Company. These instructions are intended for use by
qualified personnel only.
ii
Entellisys Low Voltage Switchgear
Chapter 1. Introduction
1-1 General Information
This manual contains procedures for receiving, handling,
storage, equipment installation, operation, maintenance, and
service of Entellisys Low Voltage Switchgear.
NOTE: The personnel responsible for installing,
operating, and servicing this equipment should be
thoroughly familiar with the contents of this manual.
NOTE: La ou les personnes responsables de l’installation,
l’opération et du service d’entretien de cet équipement
devraient être pleinement familiers en ce qui concerne le
contenu de ce manuel.
Before any installation work is performed, thoroughly read
and understand the material in this instruction manual and
the drawings furnished with the equipment. The
documentation shipped with the equipment includes the
Summary, Front View, Elementary Diagram, Connection
Diagram and Instruction Book. This material is located in a
forward compartment tagged "INSTRUCTIONS IN THIS
COMPARTMENT." The documentation provides all of the
information necessary for installation of the switchgear.
When requesting information from the General Electric
Company, include the complete data appearing on the
equipment nameplate, requisition number, summary
number, and elementary diagram number. The nameplate is
located in the lower left, front corner of the lineup.
When requesting information concerning any specific item
furnished with the switchgear, refer to that item by
description, part number, its location within this manual,
and any applicable drawing number. Any material external
to the equipment, which may be required to meet local codes
(such as mats, screens, railings, etc.), is not furnished by the
General Electric Company.
If there are any questions or requirements not covered in this
manual or in the accompanying drawings, please contact the
local sales office of the General Electric Company.
1-2 Instruction Book Arrangement
Information and procedures in this instruction book are
divided into Chapters as follows:
•Chapter 1, Introduction, gives a brief account of the
equipment's function and provides for general
information, and applicable data for the equipment and
its components.
•Chapter 2, Receiving, Handling and Storage,
describes procedures required for receiving and handling
the equipment and how to prepare it for short- or longterm storage.
•Chapter 3, Description, describes the Entellisys Low
Voltage Switchgear and its various components.
Included are the section enclosure, breaker
compartment, circuit breakers, instrument panels and
instrument compartments, bus bar arrangement,
incoming cable and busway, ground and neutral bus, and
auxiliary section. This section also explains how the
electrical and mechanical components perform their
assigned functions.
•Chapter 4, Equipment Installation, provides the
information needed prior to installation, site location and
foundation requirements, and how to anchor the
equipment properly and safely. It also covers
installation of peripheral equipment and includes
information on electrical connections and mechanical
construction.
• Chapter 5, Installing and Removing Circuit
Breakers, gives a step-by-step procedure for lifting the
breaker from the floor, installing it on drawout rails, and
moving it into the connected position. A further
procedure is given to withdraw a breaker, remove it from
the drawout rails, and lower it to the floor. Also included
is a description of the rejection system provided to avoid
the inadvertent use of an incorrect breaker in a breaker
compartment.
•Chapter 6, Testing and Inspection, reviews items
that should be tested or inspected prior to energizing and
operating the switchgear.
•Chapter 7, Operating the Switchgear, covers how to
operate the breakers, and contains information
concerning draw-out provisions, doors, and various
accessories.
•Chapter 8, Energizing the Switchgear, outlines the
steps to be taken before and during the electrical
energization of the equipment.
•Chapter 9, Maintaining the Switchgear, provides
instructions for all preventive maintenance, servicing,
and lubrication information for the switchgear
equipment. Included is service and maintenance data for
the circuit breakers, instrument compartments,
instruments, bus bar joints, and cable and busway
connections. This section also includes paint refinishing
requirements.
•Appendices A through F, contain information
concerning screw and bolt torque values, circuit breaker
ratings, rejection features, accessory device ratings,
repetitive duty data, and fuse data.
1
Entellisys Low Voltage Switchgear
Chapter 1. Introduction
1-3 Related Publications
Service and maintenance publications are supplied
separately for circuit breakers and Entellisys
instrumentation not described in this instruction book.
In addition to instruction books, the following drawings will
be supplied as required for each order of Entellisys
switchgear equipment:
1. General arrangement drawings, including front view
and floor plan.
2. Elementary and connection drawings (or wiring routing
tables) which identify test and connection points
including terminal blocks, device studs, switch contact
developments, and remote connections.
3. Summary of all the components furnished with the
switchgear, including the breakers, identified by catalog
number.
These are all documents necessary to install, operate, and
maintain the equipment. One complete set of drawings and
select instruction books are shipped with the equipment.
Fig. 1-1. General Electric Entellisys Low Voltage Switchgear
2
Entellisys Low Voltage Switchgear
Chapter 2. Receiving, Handling, and Storage
2-1 Receiving
Equipment Packages
Every package leaving the factory is plainly marked with the
shop order number, requisition number, and customer's order
number. If the equipment has been split for shipment, the
section numbers of the equipment enclosed in each shipping
package are identified.
NOTE: To avoid the loss of any parts when unpacking,
the contents of each container should be carefully checked
against the packing list before discarding the packing
material.
NOTE: Le contenu de chaque conteneur devrait être
soigneusement vérifié avec la liste d’emballage avant de
décharger le matériel empaqueté, ceci dans le but d’éviter
la perte de pièces lors du déballage.
The contents of each shipping package are listed on the
Master Packing List. In addition, this list includes the
number of the shipping crate in which miscellaneous parts
needed to install and operate the equipment (such as
hardware, contact lubricant, touch-up paint, breaker closing
devices, etc.) are located. Normally, such devices are packed
in a cardboard carton and the carton secured in an empty
switchgear compartment. See Fig. 2-1. If such items are
packed in a switchgear section instead of a separate crate,
the list will indicate the appropriate section number in which
they are stored. Large items (such as hoist dollies and hoist
carriages used with indoor equipment) will always be shipped
in separate crates or cartons. See Fig. 2-2.
Inspecting for Damage
All equipment leaving the factory is carefully inspected and
packed by personnel experienced in the proper handling and
packing of electrical equipment. Upon receipt of any
equipment, immediately perform a visual inspection to
ascertain if any damage has been sustained in shipping or if
there are any loose parts.
Circuit breakers may be shipped separately in individual
containers with the breaker in the open position. Circuit
breakers should be unpacked and visually inspected for
damage or loose parts as soon as possible after they have
been received.
Be sure to inspect all devices mounted or packed inside
compartments of each section to see if any have been
dislodged or damaged.
Filing a Claim
If any damage is evident, or indication of rough handling is
visible, file a claim for damage at once with the
transportation company and notify the nearest General
Electric Company Sales Office immediately. Information on
damaged parts, part number, case number, requisition
number, etc., should accompany the claim.
1
2
3
1. Spare compartment
2. Carton containing loose material
3. Shipping label listing contents of carton
Fig. 2-1. Packaging of loose material for shipment
NOTE: It is preferable to leave the shipping skids in
place under the switchgear until it reaches its final
location. The equipment should be installed in its final
location prior to installing the circuit breakers.
NOTE: Il est préférable de laisser l’emballage
d’expédition en place sous le dispositif de commutation
jusqu’à ce qu’il atteigne son emplacement final.
L’équipement devrait être installé à son emplacement
final avant que ne soient installés les disjoncteur.
Lifting
The switchgear sections are best handled by lifting with a
crane as shown in Fig. 2-3. Removable lifting plates are
provided, as standard equipment, on the top of each
switchgear shipping section. To preserve the external
appearance of the equipment, it is suggested that the lifting
plates be left in place except where adjacent equipments
must be bolted together, i.e. shipping splits, etc.
Utilize four equal length cables and an overhead crane, each
with a minimum load rating of twice the weight of the
switchgear. Estimated weights for shipping splits appear on
the Front View drawings.
Example: Switchgear Section Weight = 5,000 pounds. The
crane and the four lift cables must have a minimum load
lifting capacity of 10,000 pounds.
NOTE: The angle between the cables and the top of the
equipment must be at least 45 degrees. If this is not
possible because of lack of headspace, spreader bars must
be used. Also, lift cables with greater load capability may
be necessary, depending upon the angle between the
cables and the crane hook.
NOTE: Il faut que l’angle entre les câbles et le haut de
l’équipement soit d’au moins 45 degrés. Si cela est
impossible à cause d’une insuffisance d’espace de
dégagement, il faut utiliser des barres d’extension. Il se
peut aussi que des câbles de levage ayant une capacité de
poids supérieure soient nécessaires dépendant de l’angle
entre les câbles et le crochet de la grue.
Connect a cable from the crane to the four lifting plates
located on the top-front and rear of the switchgear (Fig. 2-3).
WARNING ADVERTISSEMENT
WHEN LIFTING THIS
EQUIPMENT, USE LIFTING
HOLES PROVIDED. ANGLE
OF SLING MUST NOT BE
LESS THAN 45 DEGREES. IF
HEAD SPACE IS
INSUFFICIENT, USE A
SPREADER BAR.
Lorsque cet équipement
est levé, il faut utiliser les
trous de levage qui sont
fournis. Il ne fuat pas que
l’angle d’élinguje soit de
moins de 45 degrés.
Si l’espace de dégagement
est insuffisant utiliser une
barre d’écartement.
THIS LABEL IS LOCATED
ON EACH CORNER BY
THE LIFTING HOLE
Fig. 2-3. Recommended method of lifting Entellisys enclosure
4
Entellisys Low Voltage Switchgear
Chapter 2. Receiving, Handling, and Storage
Take up the slack in the lifting device very carefully and
manually stabilize the switchgear to prevent it from rotating.
WARNING: Do not stand under switchgear while it is
being moved. Serious injury may occur if the cables or
lifting device fail.
AVERTISSEMENT: Ne vous tenez pas sous le dispositif
de commutation lorsqu’il est bougé. Des blessures graves
peuvent survenir si les câbles ou l’appareil de levage
tombent en panne.
CAUTION: Gently lower the switchgear section onto the
level site location. If the switchgear is roughly handled or
jarred, it is possible to damage or misalign internal
components.
ATTENTION: Abaisser doucement la section du
dispositif de commutation sur l’endroit d’installation
nivelé. Une détérioration ou un désenlignement des
composantes internes sont possibles si le dispositif de
commutation est manipulé grossièrement ou soumis à des
vibrations.
Rollers
If crane facilities are not available, the equipment may be
moved into position by means of construction rollers placed
under the shipping skids. The switchgear may be raised
enough for the placement of rollers by means of a forklift or
jack.
There should never be less than four rollers under the
equipment unless the line-up is less than five feet long. Use
one roller for each 18 inches of equipment length.
Forklifts
When using a forklift to raise the line-up to position rollers
underneath, proceed as follows:
1. Expand forklift tines to their maximum (widest)
extension.
2. Carefully insert tines of forklift below one side of the
switchgear line-up at the approximate center of the
panel as shown in Fig. 2-4.
NOTE: Do not attempt to lift or move the equipment with
a forklift positioned in the front or rear of the equipment.
NOTE: Ne pas essayer de lever ou bouger cette pièce
d’équipement à l’aide d’un chariot élévateur placé à l’avant
ou à l’amère de celle-ci.
3. Raise equipment and position one roller under the skids
close to the raised end of the line-up.
4. Carefully lower the gear until it rests on the roller as
shown in Fig. 2-5.
5. Repeat the lifting process at the other end and place the
appropriate number of rollers under the skids spacing
them evenly across the width of the line-up.
Fig. 2-4. Placing forklift tines under Entellisys
equipment shipping skid
Fig. 2-5. Placement of rollers under shipping skid
6. Carefully lower the gear until it rests on the rollers
(Fig. 2-6).
NOTE: If shipping skids are removed prior to final
placement of equipment, rollers may only be used to move
the equipment in a direction parallel to the front.
NOTE: Si l’emballage d’expédition a été enlevé avant que
l’équipement ne soit rendu à son emplacement final,
l’utilisation de rouleaux pour bouger l’équipement n’est
permise qu’en direction parallèle à l’avant.
5
Entellisys Low Voltage Switchgear
Chapter 2. Receiving, Handling, and Storage
Fig. 2-6. Method of rolling equipment into place
7. While carefully pushing the switchgear to its final site
position, the rollers that are freed from the rear of the
switchgear are then repositioned at the forward end.
This procedure should be continued until the
switchgear is in its final location. See Fig. 2-6.
8. When the switchgear is in its final position, remove all
lag bolts holding the shipping skids to the switchgear
line-up.
9. Insert the tines of the forklift at one end of the line-up,
raise slightly, and remove the loose rollers.
10. Lower the end of the gear carefully to the floor.
11. Raise the other end of the line-up slightly and remove
the remaining roller at that end.
Jacks
Jacks may be used in place of forklifts to raise and lower
switchgear.
1. Place a jack under the front and rear corners of one end
of the line-up.
CAUTION: Do not place jacks in any other location other
than the front and rear corners of the switchgear. Doing so
may result in serious damage to the switchgear equipment.
ATTENTION: Il ne faut pas placer de vérins en aucun
endroit autre que les coins avants et arrières du dispositif
de commutation. L’équipement peut être sérieusement
endommagé si l’on ne respecte pas cette directive.
2. Raise the switchgear evenly and just enough to position
a roller beneath the equipment. Gently lower the
switchgear onto the roller. Repeat the procedure at the
opposite end of the switchgear, raising the gear far
enough to place the appropriate number of rollers under
the skids, spacing them evenly across the width of the
line-up. Gently lower the gear onto the rollers.
3. While carefully pushing the switchgear to its final site
position, the rollers that are freed from the rear of the
switchgear are then repositioned at the forward end.
This procedure should be continued until the switchgear
is in its final location.
4. When the switchgear is in its final position, remove all
lag bolts holding the shipping skids to the switchgear
line-up.
5. Place one jack at each corner, front and rear, of the
switchgear. Carefully raise the line-up evenly and
remove the rollers and the shipping skids. Evenly lower
the line-up to the floor and remove the jacks.
6
Entellisys Low Voltage Switchgear
Chapter 2. Receiving, Handling, and Storage
2-3 Storage
Switchgear
If it is necessary to store the switchgear equipment for any
length of time, the following precautions should be taken to
prevent corrosion or deterioration.
1. Remove protective covering. Check thoroughly for
damage.
2. Store in a clean, dry, rodent-free location with moderate
temperature and provide protective coverings to prevent
dirt, water, or other foreign substances from entering
the switchgear.
CAUTION: Remove all cartons, containers and any other
miscellaneous packaging and packing material from inside
the switchgear sections before energizing any internal
heaters. To prevent fire, remove any plastic or polyethylene
shrouding from the switchgear sections before energizing
any internal heaters.
ATTENTION: Enlever tous les cartons, contenants et tout
autre objet varié servant à l’emballage et au matériel
d’emballage de l’intérieur des sections du dispositif de
commutation avant de procéder à la mise sous tension de
tout radiateur interne. Pour éviter un incendie, enlever tout
résidu de plastique ou de polyéthylène des sections du
dispositif de commutation avant de procéder à la mise sous
tension de tous les radiateurs internes.
3. If dampness or condensation may be encountered in the
storage location, heaters must be placed inside the
switchgear sections to prevent moisture damage.
Approximately 250 watts of heat in each section is
required. Incandescent lamps may be used for this
purpose. These lamps should be located in the bottom
breaker compartment of each section and supported so
the bulbs will not touch adjacent materials.
CAUTION: If the space heaters are to be temporarily
energized from an external source, it is important to
remove the fuses on the secondary side of the control
power transformer. This precaution is to prevent a feed
back of higher voltage to other portions of the equipment
through the CPT primary.
ATTENTION: Il est important de retirer les fusibles du
côté secondaire du contrôle du pouvoir du transformateur
si les espaces des radiateurs doivent être temporairement
mis sous tension par une source externe. Cette précaution
prévient une rétroaction d’un voltage supérieur à d’autres
portions de l’équipement par le contrôle de pouvoir du
transformateur primaire.
Circuit Breakers
If circuit breakers are not to be placed into service at once,
remove them from their shipping cartons and thoroughly
inspect them for damage. If the breakers are in satisfactory
condition, replace the breakers in their shipping cartons for
storage. Do not remove the circuit breaker shipping members
at this time.
Store the circuit breakers in a clean, dry location in an
upright position. They must be properly supported to
prevent bending of the studs or damage to any of the breaker
parts. Do not remove any protective grease until the circuit
breakers are ready to be installed. A plastic or canvas-type
cover should be provided to reduce the possibility of damage
to the breakers due to dust and water.
7
Entellisys Low Voltage Switchgear
Chapter 3. Description
3-1 General
This section contains a description of the General Electric
Entellisys Low Voltage Switchgear. It also describes the
functions of the electrical and mechanical systems.
Fig. 3-1 is a side view of a typical section showing
compartmentalization.
3-2 Summary Description
General Electric Entellisys Low Voltage Switchgear is a
freestanding assembly of metal-enclosed sections containing
low-voltage power circuit breakers, bus bars, cable
termination provisions, and Entellisys instrumentation. It
may also be an integral part of a load center unit substation,
either single-ended or double-ended.
Fig. 3-1. Side-view of Entellisys Switchgear
8
Entellisys Low Voltage Switchgear
Chapter 3. Description
All of the primary circuit switching and protective devices,
Entellisys instrumentation, control fuses, and instrument
transformers are mounted in the enclosure. The breaker
compartments include drawout rails, stationary breaker
contacts, interlocks, and EntelliGuard Messengers. The
breakers are provided with self-aligning primary and
secondary disconnect contacts and a breaker mechanism
locking unit. The individual sections, compartments, and
devices are described in the following paragraphs.
Fig. 3-2 is an outline of a typical single-ended load center
unit substation illustrating the nomenclature used for all
equipment.
Fig. 3-2. Outline of a typical Entellisys Load Center Unit Substation
9
Entellisys Low Voltage Switchgear
Chapter 3. Description
3-3 Front Compartment Area
The front enclosure of each section is divided into individual
compartments. These compartments typically house
EntelliGuard low voltage power circuit breakers or Entellisys
instrumentation.
3-4 EntelliGuard Messenger
An EntelliGuard Messenger is mounted above each
EntelliGuard breaker. The Messenger provides an interface
between the breaker, the compartment, and the central
Entellisys system. See DEH-231 (Entellisys Low Voltage
Switchgear System User’s Manual) for further instructions.
Each Entellisys low voltage switchgear lineup contains
standard devices housed within the instrument
compartments. Two CPUs (Central Processing Units) provide
the processing capability to support all switchgear functions.
At least one HMI (Human-Machine Interface) provides user
access to the Entellisys system. Network switches provide
communication links between the CPU, the HMI, the
EntelliGuard Messengers, and the external world. A pair of
uninterruptible power supplies (UPSs) and control power
throwover relays supply highly reliable control power to these
system devices.
Fig. 3-3. EntelliGuard Messenger
10
Entellisys Low Voltage Switchgear
Chapter 3. Description
3-5 Breaker Compartment
Closed-door drawout circuit breaker compartments, Fig. 34, are standard construction with all Entellisys switchgear
equipment. The circuit breaker compartment doors
remain closed and latched while the breaker is racked out
from the connected position, through test, to the
disconnected position.
Breaker compartment doors do not have any ventilation
slots, thus protecting operators from hot ionized gases
2
that may be vented by the breaker during circuit
interruption.
Additionally, the breaker compartment, Fig. 3-5, is enclosed
by grounded steel barriers on the top, sides, bottom, and
front. In the back, a flame-retardant, track resistant, glassfilled polyester base minimizes the possibility of fault
communication between compartments or to the bus.
4. Primary disconnects – line 9. Secondary Disconnect
5. Current Transformers
Fig. 3-5 Circuit breaker compartment (22-inch)
8
3
2
12
Entellisys Low Voltage Switchgear
Chapter 3. Description
Fuses for the charge, close, and trip circuits of electrically
operated breakers are mounted in the upper left corner of the
breaker compartment behind the door. Fuses for the set and
reset coils of the optional Network Interlock breaker
accessory are mounted in the upper right corner of the
compartment.
Primary disconnect shutters are available as options to
provide protection against contact with the energized
stationary primary disconnects when the breaker is removed
from its compartment. Shutters are supplied as standard
components in the source (main, generator) and tie breaker
compartments of multi-source lineups. The shutters are
constructed from glass-reinforced polyester insulating
material.
1
2
5
Fig. 3-6. Circuit breaker compartment (30-inch wide) with shutters
NOTE: If a fuse rollout (FRE) carriage is used with an
EGF-32/40/50 circuit breaker whose compartment is
equipped with shutters, the FRE compartment will also be
equipped with shutters.
NOTE: Si on utilise un chariot porte-fusibles à roulettes
avec un disjoncteur EGS-32/40/50 dont les compartiments
sont munis de volets, le compartiment du porte-fusible à
roulettes sera aussimuni de volets.
The combination of the stationary and movable portions of
the shutters prevent frontal access to the primary disconnect
line and load power stabs.
1. Stationary barrier
2. Shutters (retractable barrier)
3. Operating lever
4. Operating lever springs
6
5. Drawout rails
6. Racking anchor pins
4
3
13
Entellisys Low Voltage Switchgear
Chapter 3. Description
The shutters are partially retracted when the breaker is in
the Disconnect Position. As the circuit breaker is racked from
the Disconnect Position to the Test Position, the rear of the
circuit breaker frame depresses the shutter operating lever
(3) to cause the shutters to fully retract. The operating lever
springs (4) cause the operating lever (3) to remain in contact
with the circuit breaker frame during operation. As the
breaker is racked from the Test Position to the Connected
Position, the shutters remain fully retracted.
Fig. 3-7 also shows the shutter assembly with the shutters
manually retracted to show the location of the primary
disconnect stabs (5) behind the shutter assembly.
1
2
Circuit breakers mounted in 22-inch wide compartments
(EG-08, EG-16, EG-20) are supported on drawout rails (7),
Fig. 3-5. Larger EG-32 and EG-40 circuit breakers and fuse
rollout carriages are installed in 30-inch wide compartments
and are supported on drawout rails (5), Fig. 3-6. The EG-50
circuit breaker is installed in a 38-inch wide compartment
and is supported on drawout rails (similar to Item 5, Fig. 3-
EntelliGuard breakers do not contain current transformers.
Instead, current transformers are mounted over the primary
disconnect stabs of all Entellisys breaker compartments.
Primary disconnects are equipped with short-circuit braces
when breakers are fused or when extra-deep breaker
compartments are used.
The breaker racking arm slots engage fixed racking anchor
pins (6), Fig. 3-6, mounted in the breaker compartment. As
the racking arms are rotated by operation of the breaker
racking crank, the breaker is pulled into the compartment,
and locked in its final connected position.
A breaker should always be OPEN when it is moved into or
out of the CONNECTED position. As a safeguard, the
drawout interlock (2), Fig. 3-8, will cause the breaker to open
before the primary disconnects lose contact if a closed
breaker is moved out of the CONNECTED position.
EntelliGuard circuit breakers having higher continuous or
interrupting current ratings may be substituted for those
having lesser ratings. The compartment, however, retains the
factory-configured ratings and protection settings.
Substitution of manual for electric or electric for manual
EntelliGuard breakers is not recommended.
1. Racking arm
2. Secondary disconnects
3. Racking screw
Fig. 3-9. EGS-40 circuit breaker
Each breaker compartment has four positions as described
below:
1. CONNECTED POSITION-The breaker is in operating
position, both primary and secondary contacts made,
and the door closed.
2. TEST POSITION-The secondary contacts are made, but
the primary contacts are not made. Any breaker test
that requires control power may be made in this
position.
3. DISCONNECTED POSITION-All primary power and
secondary control electrical circuits between the breaker
and the equipment are disconnected. The door may be
closed. The breaker may be stored in this position with
the door closed.
4. WITHDRAWN POSITION-The breaker is completely
out of its compartment ready for removal from the
equipment. The door must be open. The optional
primary disconnect shutters, positioned in front of the
primary stabs, would be closed with the breaker in the
WITHDRAWN position.
15
Entellisys Low Voltage Switchgear
Chapter 3. Description
Movement of the breaker between the CONNECTED, TEST,
and DISCONNECTED positions is performed by the use of a
racking crank that engages the racking mechanism mounted
on the breaker. Movement to the WITHDRAWN position is
manually performed after opening the compartment door.
These positions are illustrated and described more fully in
Chapter 5 of this instruction book.
CAUTION: The door should not be opened when the circuit
breaker is closed and in the CONNECTED position.
Although the breaker compartment door may be opened in
any position, it is recommended that the door only be
opened when the breaker is in the DISCONNECTED or
WITHDRAWN position.
ATTENTION: Il ne faut pas que la porte soit ouverte
lorsque le disjoncteur est fermé et branché. Bien que la
porte du compartiment du disjoncteur puisse être ouverte
lorsque le disjoncteur est en n’importe quelle position, il
est préférable que la porte ne soit ouverte que lorsque le
disjoncteur est en position débranchée ou retirée.
3-6 Circuit Breakers
The General Electric EntelliGuard Low Voltage Power
Circuit Breaker includes spring-operated, stored energy, close
and trip mechanisms for either manual or electrical
operation.
Six General Electric EntelliGuard Circuit Breakers form
the complete family of breakers used in the Entellisys
switchgear. These circuit breakers range from 800 to 5000
ampere frame sizes and are built with the following ratings
and characteristics:
EGS/EGH/EGX-08 Circuit Breaker
• 800-ampere frame size
• Standard 30,000-ampere interrupting and short-time
capability (480 volts)
• Four-high stacking, 22-inch wide sections
• Increased IC and short-time rating 42,000 amperes
(EGH-08) or 65,000 amperes (EGX-08) at 480 volts
EGF-08 Fused Circuit Breaker
• 800-ampere frame size
• 300- through 1600-ampere integral fusing
• 200,000-ampere interrupting rating
• Four-high stacking, 22-inch wide sections
EGS/EGH-16 Circuit Breaker
• 1600-ampere frame size
• Standard 50,000-ampere interrupting and short-time
capability at 480 volts
• Four-high stacking, 22-inch wide sections
• Increased IC and short time rating 65,000-ampere at 480
volts (EGH-16)
• Standard 85,000-ampere interrupting and short-time
capability at 480 volts
• One-high stacking, 38-inch wide sections
• Increased IC and short-time rating 100,000 amperes
(EGX-50) at 480 volts.”
3-7 Fuse Rollout Elements
When the system available short-circuit current exceeds the
unfused breaker ratings, current-limiting fuses can be used
in series with EGF-20, EGF-32, EGF-40, and EGF-50
breakers to increase the short-circuit rating of the
combination to 200,000 amps. When used, such fuses are
housed in a separate drawout compartment located adjacent
to the breaker compartment; they are mounted on a drawout
carriage similar to a breaker frame and referred to as a fuse
rollout element (FRE).
1. Protective hinged screen
2. Racking mechanism
3. Fuses
4. Secondary disconnects
Fig. 3-12. Fuse roll-out carriage
17
Entellisys Low Voltage Switchgear
2 1
Chapter 3. Description
3
1. Quarter-turn latch
2. Steel plate (future breaker cubicle)
Fig. 3-13. Future breaker compartment
3-8 Compartments for Future
Breakers
When specified, compartments may be supplied for future
addition of circuit breaker elements. These compartments
are fully equipped with drawout rails, primary
disconnects, and ancillary devices as required (i.e.
secondary disconnects, accessory devices, etc.) The
opening in the breaker compartment door (3), Fig. 3-13, is
closed with a bolted-on steel plate (2) to deter accidental
contact with energized electrical circuits. (I.e. primary
disconnect stabs).
3. Compartment door
3-9 Auxiliary/Transition Sections
Sections may be provided for any one or more of several
reasons including:
• Transition to a close-coupled transformer
• Incoming cable or busway when a main breaker
section is not provided
Auxiliary sections may be 22-inch, 30-inch, or 38-inch
wide as required to accommodate the space requirements.
The compartment doors on the front of the sections are
hinged and latched in the same manner as breaker
compartment doors.
Generally, transition sections will be 22-inches wide for
close-coupling to transformers.
Power company metering requirements generally require
either a 38-inch or 49-inch wide auxiliary section to
accommodate the current transformers, meters, test
switches, etc. as required by their individual practices,
tariff schedules, and/or regulatory commissions.
18
Entellisys Low Voltage Switchgear
Chapter 3. Description
3-10 Bus Area
The bus area, Fig. 3-14, contains the main horizontal bus and
vertical riser bus bars (1) for the particular section. The
vertical bus bars are supported at the breaker run-ins (2)
that are bolted to the molded bases (3) that form the rear
wall of the breaker compartment. The horizontal bus bars
are supported by the power connectors (4), which are bolted
to the vertical bus bars. All bolted supports and connections
are accessible from the rear for maintenance. The bus area is
fully isolated from the breaker, instrument and auxiliary
compartments by the molded bases or glass polyester sheet.
Busing System
Bus bars are fully tin-plated copper with bolted joints. The
standard construction is open bus. A barrier system (Bus
compartmentalization) that isolates the main and vertical
bus bars from the cable area is available as an option. All
run-backs (load-side power conductors) from the breaker
compartment to the cable termination area are covered with
non-PVC insulated tubing.
The typical arrangement is shown in Fig. 3-15.
The standard bracing is 65,000 amperes, RMS symmetrical.
Bracing for 100,000, 150,000 and 200,000 amperes, RMS
symmetrical is available as an option.
In general, when the switchgear equipment has no more than
four sections or does not exceed 10 feet in length, it will be
shipped as one complete lineup. In such cases, the only field
assembly would be to a close-coupled transformer if, the
switchgear were part of a Load Center Unit Substation. If,
because of shipping and/or handling considerations, the
equipment cannot be handled in one piece, it can be split into
two or more shipping sections at the factory. The individual
shipping splits require both mechanical and electrical
connections between sections to be made in the field. At
these shipping splits, provisions are made for bolting all
buses and making the necessary electrical and mechanical
connections. These are described in Chapter 4 of this
publication.
On main and tie breakers, the bus area, Fig. 3-15, is divided
into an upper (1) and lower (2) section by a glass reinforced
polyester isolation barrier (3). For typical unit substation
main circuit breakers, the upper section contains the
incoming line bus (4). The lower section of the bus area
contains the load side main bus (5) (protected by the main
breaker) that feeds all sections of the switchgear equipment.
Similarly, barriers at tie breakers isolate the two main bus
sections from each other.
1 Vertical riser bus
2. Run-ins to breaker compartment
3. Molded base
4. Power Connector
5. Run-backs from breaker compartment
6. Short-circuit brace
Fig. 3-14. Bus construction
19
Entellisys Low Voltage Switchgear
Chapter 3. Description
4
Insulated/Isolated Bus System
A bus insulation system, Fig. 3-16, that fully insulates each
phase of the horizontal main bus and isolates each phase of
the vertical bus, is optionally available for Entellisys
switchgear when specified. With the INSULATED/ISOLATED BUS system, there are no live connections
accessible in the rear of each section except the cable lugs.
1
1
5
1. Upper section vertical bus-incoming line
2. Lower section vertical bus-load side
3. Barrier between upper and lower vertical
bus sections
4. Incoming bus connections
5. Main horizontal bus connections
Fig. 3-15. Main breaker bus arrangement
2
3
1. Vertical riser bus covers
2. Run-backs to feeder cables
3. Horizontal main bus
4. Lower neutral bus with 4th wire
sensors
Fig. 3-16. Insulated/Isolated-Bus system
2
3
4
20
Entellisys Low Voltage Switchgear
Chapter 3. Description
A vertical barrier (2), Fig. 3-17, between the transition
section (1) and the first breaker section is always
furnished.
The buswork in the device/auxiliary/transition sections is
not insulated at the termination points to the other
connected equipments such as transformers, busway, or
existing equipments.
the bus bars. (The top portion of the vertical bus is shown
with the cover removed.)
The phase isolation barriers and riser bus covers are
constructed from insulating material. Insulation of the
horizontal main bus bars (5) is achieved by an oven cured
coating of epoxy.
1. Transition compartment
2. Barrier
3. Main incoming bus
4. Neutral bus
5. Ground bus
Fig. 3-17. Transition section
Insulation and isolation of the vertical riser bus bars (2),
Fig. 3-18, is provided by installing phase isolation barriers
(3) between the bus bars and by mounting covers (4) over
1. Molded base
2. Vertical riser buses (cover removed to show bus
location)
3. Phase isolation barriers
4. Covers over riser bus
5. Insulated horizontal main buses
6. Covers for vertical/horizontal bus joints
7. Insulated run backs
Fig. 3-18. Bus insulation system
21
Entellisys Low Voltage Switchgear
Chapter 3. Description
Fig. 3-19 illustrates the various components comprising the
insulation/isolation system for the horizontal main bus bars.
The horizontal bus bars (2) are insulated with an epoxy
coating applied by a fluidized bed process. The vertical/
horizontal bus bar joints are covered with collars (3) and caps
(4) held in place with nylon thumb screws (5). The collars
and caps are constructed from insulating material.
3-11 Feeder Cable and Busway
Compartment
The rear cable and terminal compartment, Fig. 3-20, provides
for cable installation and terminations. The cable bending
space meets the requirements of the 2005 National Electric
Code. Various arrangements of single or double cable
terminals are provided, depending upon the purchaser's
requirements.
1. Vertical bus barrier
2. Insulated bus bar (powder coated)
3. Joint collars
4. Joint caps
5. Nylon thumbscrews
Fig. 3-19. Horizontal bus insulation system
1. Support rack for customer's feeder cables
2. Cable lugs - mechanical type
3. Cable lugs - compression type
Fig. 3-20. Cable termination provisions
When specified, racks (1), Fig. 3-20, for the support of feeder
cables are located in the cable compartment. The actual
support of the cables is provided by lashing them to these
racks.
A neutral bus, insulated from ground, is provided in the bus
area on switchgear designed for four-wire systems. The
neutral bus is located near the top of the cable compartment.
It includes provisions for terminating the neutral conductor
of four-wire feeder cables and also direct mounting of the
neutral CT as required for those feeder system circuit
breakers having an integral ground fault trip function.
22
Entellisys Low Voltage Switchgear
Chapter 3. Description
3-12 Ground Bus
All General Electric Entellisys switchgear sections are
grounded to the internal equipment ground bus (4), Fig. 3-21,
located at the bottom of the cable compartment.
1
2
1. Feeder runbacks
2. Vertical riser bus covers
3. Horizontal main bus
4. Ground bus
Fig. 3-21. Cable termination compartment
3
4
23
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
4-1 General
This chapter contains complete instructions for installing
General Electric Entellisys Low-Voltage Switchgear.
CAUTION: Personnel installing this equipment must be
thoroughly familiar with this instruction manual and all
articles of the National Electrical Code applicable to the
installation of this switchgear. In addition, all drawings,
both mechanical installation and electrical, must be
understood and strictly followed to prevent damage to the
switchgear or equipment being protected by the
switchgear.
ATTENTION: La ou les personnes procédant à
l’installation de cet équipement doivent être tout à fait
familier avec ce livre d’instruction ainsi que tous les
articles du Code national d’électricité s’appliquant à
l’installation de ce dispositif de commutation. De plus, tous
les dessins se rapportant tant à l’installation mécanique
qu’électrique doivent être compris et suivis à la lettre afin
de prévenir des dommages au dispositif de commutation ou
à l’équipement protégé par celui-ci.
NOTE: Before installation work is started, it is important
to review all of the drawings provided, including the
General Electric equipment arrangement drawings, site
installation drawings, elementary and remote connection
drawings, mechanical connection drawings, and the
summary of equipment list.
NOTE: Il est important de reviser tous les dessins fournis,
incluant les dessins de disposition de l’équipement de
General Electric, les dessins d’installation du site, les
dessins de raccords élémentaires et à distance, les dessins
de raccords mécaniques et le sommaire de la liste
d’équipement avant que ne débutent les travaux
d’installation.
All expendable hardware for shipping purposes only, is
painted yellow or tagged with yellow adhesive and may be
discarded at completion of the installation phase.
Site Location
In general, the location of the switchgear equipment will
have been predetermined during the specification and/or
procurement of equipment phases. Indoor locations within
buildings impose certain requirements that must be met so
that the switchgear may operate efficiently with a minimum
of maintenance.
In locating the Entellisys Switchgear, adequate aisle space
must be provided at the front and rear of the equipment to
ensure proper ventilation of the equipment and to allow
service and maintenance of the equipment with the front and
rear doors open. The recommended aisle space is shown on
the floor plan supplied with the equipment drawings.
The switchgear equipment should be placed in an area where
clean, dry air is free to circulate around and above it. Since
air is taken into the equipment at the bottom of each section
and exhausted at the top, a location with good airflow must
be provided for efficient operation. A minimum of 30 inches
of clear space above the equipment is recommended.
Foundation Requirements
For optimum performance of your General Electric
switchgear equipment, the foundation requirements
expressed in this chapter should be strictly adhered to.
NOTE: The foundation for the outdoor switchgear must
provide proper drainage of ground and/or surface water
accumulations away from the equipment.
NOTE: La fondation du dispositif de commutation situé à
l’intérieur doit être en mesure de drainer correctement les
accumulations d’eau du sol et de surface loin de
l’équipement.
The foundation must be strong enough to prevent sagging
due to the weight of the switchgear structure and to
withstand the shock stress caused by the opening of the
breakers under fault conditions. The shock loading is
approximately 1-1/2 times the static load.
The foundation must be flat and level in all planes. Refer to
Fig. 4-1 for definition of flat and level.
Fig. 4-1. Definition of flat and level
Foundation Preparation
Refer to Fig. 4-2 along with the owner's foundation
construction drawings, and the General Electric supplemental installation drawings. Although the indoor
switchgear equipment can be mounted directly on a smooth,
level floor, it is recommended that recessed steel channels be
installed for supporting the equipment. Anchor bolts and
channels are to be provided by the purchaser.
24
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
NOTE: When the equipment is installed on a surface
subject to impact (shock) loads due to operating
conditions or environmental seismic (earthquake)
conditions, the anchor bolts should be fabricated of
medium carbon steel (grade 5 load rating).
NOTE: Lorsque l’équipement est installé sur une surface
sujette à des charges d’impact (choc) causées par les
conditions d’opération ou des séismes environnementaux
(tremblements de terre), les boulons d’ancrage devraient
être fabriqués d’acier à moyenne teneur en carbone
(spécification de charge classe 5).
The floor channels under the front and rear switchgear
anchor points (see Fig. 4-2) should be embedded in a level
concrete slab with their top surfaces flush with the finished
floor. It is essential that these steel channels be level and
aligned with each other prior to final anchoring, to prevent
distortion of the switchgear structure, to assure proper
mechanical and electrical connections between shipping
splits, and to assure proper interfacing to other close-coupled
equipments.
Entellisys Switchgear and Load Center Substations are
frequently mounted on steel floors and/or structural steel in
industrial installations (such as a mezzanine) to minimize
usage of production floor space. Regardless of the type of
mounting surface, the requirements for a smooth level
surface remain.
Fig 4-2. Location of equipment anchor points
25
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
If studs or anchor bolts are to be used, they should be
installed in the foundation as it is poured. It is important
that the studs or bolts are spaced to agree with
dimensions given on the General Electric job drawings.
The dimensions between anchor bolts for a particular
installation are dependent upon the configuration of
equipment ordered. The dimensions shown on Fig. 4-2
cover all of the standard enclosures available for
Entellisys Switchgear.
Fig. 4-3 illustrates the space available for conduit and/or
cable entrance through the bottom or top of each
equipment section. The space required for control wiring
entry to the optional wiring trough is also shown.
NOTE: BUS COMPARTMENT
BARRIER LOCATION - WHEN
THIS OPTION IS PROVIDED, IT
REDUCES AVAILABLE SPACE FOR
CABLES ABOVE BY (5) INCHES
Fig 4-3. Floor plan and cable entry space
Equipment
Depth “A”
60” non-fused or Below 19
67” with fused EGF-08/16 Above 24
67” non-fused or Below 26
74” with fused EGF-08/16 Above 31
74” non-fused or Below 33
81” with fused EGF-08/16 Above 38
Direction
of Leads
26
B
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
4-2 Assembly and Installation of
Switchgear Equipment
General Requirements
Before assembling or installing the switchgear equipment, all
components should be available at the site location. This will
facilitate switchgear component identification as well as
installation. The foundation should be prepared in
accordance with the instructions in Sections 4-1 and 4-2, and
all embedded conduits installed and capped.
NOTE: If rollers are to be used for movement of the
equipment to its permanent installation, it is
recommended that the shipping skid not be removed until
the equipment is placed in position over the anchor bolts.
NOTE: Au cas où l’utilisation de rouleaux s’avérerait
nécessaire afin d’apporter l’équipement à son
emplacement permanent, nous recommandons que
l’emballage d’expédition ne soit pas enlevé tant que
l’équipement n’est pas positionné au dessus des boulons
d’ancrage.
If a transformer is not part of the installation, and/or the
equipment has been split for shipment, place the center
section on the foundation first. Assemble the remaining
sections outward from the center section, in each direction.
If the switchgear equipment is part of a Load Center Unit
Substation, the transformer section should be set on its pad
first in accordance with the instructions furnished with the
transformer. All remaining sections of the switchgear should
then be installed.
NOTE: Before assembling and installing the switchgear
equipment, the foundation must be absolutely level and
clear of debris to prevent damage and possible
misoperation of the switchgear equipment.
NOTE: Il faut avant de procéder à l’assemblage et à
l’installation s’assurer que la fondation soit absolument
au niveau et exempte de débris afin de prévenir des
dommages à l’équipement du dispositif de commutation.
Detailed Assembly and Installation
Instructions
The recommended procedure for installation of a switchgear
or Load Center Unit Substation is as follows:
1. POSITION THE EQUIPMENT-Position the equipment
or sections of the complete equipment in their final
location.
Fig. 4-4. Lifting plate location
NOTE: If the equipment line-up was split into shipping
sections, the lifting plates on corners of adjacent sections
shown in Fig. 4-4 must be removed. Failure to remove
these plates will interfere with mating adjacent sections
and prevent installation of bus splice plates, structure tie
plates, etc.
NOTE: Si l’ensemble de l’équipement a été séparé en
sections pour l’expédition, il faut que les plaques de
soulèvement aux coins des sections adjacentes montrées à
la Fig. 4–4 soient enlevées. L’omission d’enlever ces
plaques viendra en interférence avec les sections barres
omnibus, de l’attache de la structure des plaques, etc.
Once the lifting plates have been removed, they may be
discarded.
NOTE: In the event the lifting plates must be
reassembled on the equipment for lifting purposes, they
must be moved to locations where unused screw holes are
avail-able, generally achieved by shifting the plate
horizontally on the mounting surface one bolt hole from its
previous location. When remounting the lifting plates,
torque the mounting bolts to 7-9 ft-lbs.
NOTE: Dans l’éventualité où les plaques de levage doivent
être réassemblées sur l’équipement à des fins de levage,
elles doivent être déménagées aux endroits où il y a des
trous de boulons inutilisés, on y arrive habituellement en
décalant la plaque horizontalement sur la surface de
montage d’un trou de boulon de son emplacement
précédent. Lors du remontage des plaques de levage,
serrer les boulons d’assemblage à un couple de 7–9 livrespied.
27
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Fig. 4-5. View showing method of attaching equipment to shipping
skids
NOTE: All mating sections of the equipment line-up
(including transformer, if applicable) must be securely
fastened together prior to tightening anchor bolts
fastening the equipment to the mounting surface.
NOTE: Toutes les sections se rapportant à la disposition
de l’équipement (incluant le transformateur si tel est le
cas) doivent être retenues ensembles solidement avant de
resserrer les boulons d’ancrage qui retiennent
l’équipement à la surface de montage.
2. REMOVE THE SHIPPING SKIDS-The equipment is
fastened to the shipping skids with 3/8-3 lag screws
through the equipment anchoring holes. See Fig. 4-5.
Equipment shipping sections up to 10 feet long will be
fastened to the skids with four lag screws, one in each
corner. Longer sections will have two additional lag screws
which are located near the middle of the equipment. The
shipping skid and lag screws are expendable material and
may be disposed of at the purchaser's discretion.
3. FASTEN SECTIONS TOGETHER-After placement of
the equipment and installing the anchor bolts loosely,
the various shipping sections must be rigidly fastened
together. Through-bolts fasten each section of the
switchgear equipment to the adjacent section. Fig. 4-6
shows the location of the through-bolts.
Fig. 4-6 Location of through-bolts
28
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Fig. 4-7 illustrates the installation of the through-bolts. The
through-bolts are in the front and rear compartments. The
nut and bolt assembly should be tightened with a torque of
25-30 ft-lbs.
survenir si l’on omet de mettre l’équipement à la terre
correctement.
Fig. 4-8 illustrates the general location of the buses that
must be spliced across the shipping splits.
Fig. 4-7. Through-bolt installation
All of the hardware required for assembling the equipment
across the shipping splits is furnished with the equipment. If
a transformer is included in the line-up of equipment, the
transformer flange should be aligned with the opening in the
side of the transition compartment and fastened together
using the 3/8-16 bolts, nuts and washers supplied with
switchgear. The fastener assembly should be tightened with
a torque of 25-30 ft-lbs.
4. COMPLETE THE ELECTRICAL
INTERCONNECTIONS - After completing the
mechanical connections between the several sections of
equipment, the electrical interconnections should be
completed. This includes the installation of splice
plates for the main bus bars, the neutral bus, and the
ground bus in addition to the Entellisys control and
communication circuitry.
WARNING: All switchgear equipment must be
adequately grounded for safety. Failure to ground
equipment properly may result in serious injury.
ADVERTISSEMENT: Tout l’équipement du dispositif de
commutation doit être mis à la terre adéquatement de
manière sécutaire. Des blessures sérieuses peuvent
Fig. 4-8. Typical location of buses at shipping split
29
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
The ground bus is mounted directly on the rear upright
channels.
NOTE: It is particularly important that the ground bus be
connected first since it provides an integral ground for all
the equipment. It must also be connected to the station
ground prior to proceeding with the installation.
NOTE: Il est particulièrement important que la barre
omnibus de mise à la terre soit branchée en premier, étant
donné qu’elle fournit une mise à la terre intégrale à tout
l’équipement. Elle doit aussi être branchée à la mise à la
terre du poste avant de procéder à la installation.
A 4/0 AWG cable connector is located in the bottom of the
transition section (or in the incoming line compartment if a
transition section is not included) for terminating the
purchaser's cable connection to ground. The specific location
of the station ground connection is shown on the site floor
plan drawing and in the frontview drawings supplied with
the equipment. All grounding of the switchgear should be in
accordance with National Electrical Code.
If a GE transformer (rated above 750 kVA) is present in the
line-up, a ground bar located in the transition compartment,
Fig. 4-10, is provided for connection of the transformer
ground pad to the equipment ground termination point.
Fig. 4-9. Plan view of ground bus splice installation
Fig. 4-9 illustrates the installation of the ground bus splice
plate across a shipping split. In addition to the bolted
fastening of the splice plate to the two ends of the ground
bus, self-tapping 1/4-20 bolts pass through the splice plate
and ground bus stubs, and thread into the equipment frame.
These bolts should be fastened with a torque of 7-9 ft-lbs.
Fig. 4-10. Flange opening on a transition section to a GE transformer
(above 750 kVA)
As shipped, the ground bar is mounted so it does not protrude
beyond the outer surface of the equipment. When the
equipment is installed in its final location, the ground bar
must be reassembled using the outer bolt holes in the
horizontal ground bus spanning the width of the transition
compartment. In this mounting location, the offset portion of
the ground bar will permit connection to the transformer
ground pad with the 1/2-13 bolt assembly supplied with the
switchgear equipment. If an optional floor plate is supplied
for the transition compartment, it will be necessary to remove
the floor plate to permit relocation of the ground connection
bar.
30
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
All bolted bus joints should be made using the proper torque
as shown in Table A-1 in Appendix A of this manual.
Transformers not manufactured by General Electric may
require special mounting and bus connection hardware.
The neutral bus may be insulated from the grounded frame of
the switchgear equipment; thus, it is mounted on insulators
throughout the equipment. Installation of the neutral bus
splice plate across a shipping split is similar to the ground
bar splice except that the splice plate is not bolted to the
equipment frame. Fig. 4-11 illustrates the installation of the
neutral splice plate.
Fig. 4-11. Plan view of neutral bus splice installation
The installation of the horizontal bus splice bars is with
bolted joints.
Figs. 4-12 and 4-13 illustrate the assembly of the main bus
splice plates on the bolted bus system. Copper bus systems
are normally supplied with flat washers and lock washers.
Fig. 4-12 shows the rear view of the main bus area with the
installed splice bus indicated with cross-hatching.
Fig. 4-13 shows that a spacer is used both between the
busbars when more than one bar is used per phase (normally
the 2500 ampere and larger main bus ratings) and over the
outer bars of a single or multiple bar joint.
After assembly of the splice plates and spacers, the 1/2-13
bolts should be tightened to a torque of 35-40 ft-lbs.
Fig. 4-12. Rear view of main bus at a shipping split
Fig. 4-13. Plan view of a two bar main bus connection
31
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
After completing the installation of the main bus splice bars,
the joint covers may be mounted and secured by a 3/8-16
nylon bolt and polyester flat washer if the bus insulation
option has been supplied with the equipment.
5. CONNECT THE TRANSFORMER SECONDARY - The
connection of the transformer secondary to the incoming
bus bars in the transition is made using the flexible
connection straps supplied with the transformer. These
connections are always bolted joints.
The recommended torque for tightening the ½-13 bolts
fastening the transformer connection straps to the incoming
bus bars is 35-40 ft-lbs.
6. INTERCONNECT ENTELLISYS CONTROL AND
COMMUNICATION WIRING - Interconnection of
control wiring across shipping splits is accomplished by
connecting to terminal blocks located in the crosssection wiring trough on top of the equipment shown in
Fig. 4-14. Ethernet cables are connected by similarly
routing them across the top of the equipment and down
the gear, between the compartment side sheets.
If terminal blocks are provided, each wire must be attached
to the correct point on the terminal block, following the
circuit identification number attached to each wire.
Fig. 4-14. Interconnect control wiring and Ethernet cables in the wiring trough
on top of the equipment
32
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Anchoring Switchgear Equipment
Correct anchoring of the switchgear equipment to the
foundation is very important. After completion of reassembly of the equipment at the shipping splits, the
equipment anchoring procedure should be completed.
1. ANCHORING BY ANCHOR BOLTS – Equipment is
normally secured to its final mounting surface by
anchor bolts threaded into the embedded channel sills.
The bolts were loosely threaded into place before
reassembling the equipment shipping splits and
connecting to the close-coupled transformer, if
appropriate.
The anchor bolts should now be tightened with a torque of
35-40 ft-lbs.
2. ANCHORING BY WELD - An alternate method of
anchoring the equipment to its foundation is to weld
the equipment to floor sills (or the floor itself if
constructed of steel). Several methods, shown on Fig. 415, are available to the purchaser for welding the
equipment to the channel sills.
a. The front of the equipment is attached to the
embedded channel sills (1), Fig. 4-15, by two 3/16inch fillet welds (2). It is recommended that two
welds, each 2-1/2 inches long (min.), be used for each
section to firmly tie the bottom width post (3) to the
channel sill.
b. The rear of the equipment may be anchored by one of
three procedures:
• The first method is by plug welds (4), Fig. 4-15, using the
anchor bolt holes in the rear sill angle (5). The plug weld
should receive a minimum 1/2-inch bead around the
entire circumference of the anchor bolt hole.
• A second method of securing the rear sill angle (5) to the
channel sill (1) is the use of two linear fillet welds (2) for
each section. It is recommended that each weld be 2-1/2
inches long (min.) with a 3/16-inch fillet (min.).
• A third method for anchoring the rear of the equipment is
to remove the rear sill angle (5) from the switchgear and
weld the rear bottom width post (6) to the channel sill (1).
These welds (2) should, like the front welds, have a 3/16inch(min.) fillet and each have a minimum length of 2-1/2
inches.
CAUTION: If the equipment is to be subjected to
operational or environmental (seismic) shock loading, the
factory must be consulted for anchoring recommendations.
ATTENTION: Si l’équipement doit être assujetti à une
charge de choc opérationnelle ou environnementale
(sismique), il faut consulter le manufacturier afin d’obtenir
des recommandations d’ancrage.
33
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
1. Channel sill
2. 3/16-inch fillet weld
3. Front width post
4. Plug weld in anchor bolt hole
5. Rear sill angle
6. Rear width post
Fig. 4-15. Equipment weld anchoring
34
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Busway Connections
Busway runs must be aligned with openings in the
equipment and connected to the mating components
electrically and mechanically. A collar is mounted on the top
of the equipment cable compartment to which is bolted the
busway housing. See Fig. 4-16. The 1/4-20 NC bolts,
washers, and nuts for this mechanical connection are
supplied with the busway stub. The bolts should be
tightened with a torque of 7-9 ft-lbs.
Control Wire Connections
For external control wiring, refer to Fig. 4-17 for switchgear
cable area dimensions, and connect the control wires to the
switchgear section as follows:
1. When control conduits enter the switchgear from below,
they should not extend more than one inch above the
floor. The control wires may be pulled through the
conduits before or after the switchgear is installed.
The power conductors in the busway stub are designed to bolt
directly to power connector blocks mounted on the switchgear
riser bus bars. These connections are made with 1/2-13NC
bolts supplied with the switchgear equipment.
NOTE: To maintain the minimum contact resistance
across bolted bus joints, it is recommended that the joint
contact surfaces be coated with a film of GE lubricating
grease D6A15A2. A can of this grease is supplied with the
equipment. Do not put grease on the bolt threads, as this
will affect the clamping force exerted by the bolt.
NOTE: Afin de maintenir une résistance de contact
minimale à travers les joints vissés des barres omnibus,
nous recommandons que les surfaces du joint de contact
soient unduites d’une pellicule de graisse lubrifiante GE
D6A15A2. L’équipement est fourni avec une boîte de cette
graisse. Il ne faut pas graisser les fils des boulons car la
force de serrage exercée par le boulon en sera affectée.
The recommended torque for tightening the 1/2-13 NC bolts
connecting the busway stub conductions to the riser bus
power connectors is 35-40 ft-lbs.
Fig. 4-17. Floor plan and cable entry space
2. Route the control wires from the conduits through the
wiring trough (cross-hatched area- 2" x 7"-shown on
Fig. 4-17) at the side of the cable compartment.
Connect the cables to the terminal blocks in accordance
with the connection diagrams for the equipment. Refer
to the equipment frontview / floorplan drawings for
location of terminal blocks for external control wiring.
3. If the control conduits enter from above, remove the
top plate from the switchgear and drill the top cover
within the available space indicated. See Fig. 4-17.
Control wires should be routed to the wiring trough
and connected to the terminal blocks as described
previously.
35
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Power Cable Connections
Connect the main cables to the main lugs. Before any
main cable connections are made, the cables should be
identified to indicate their phase relationship with the
equipment. Adequate electrical and mechanical
clearances must be provided between conduit, cables, and
bus. Where the cables enter the section, they can be
lashed to optional cable supports at the rear of the cable
compartment as required. (See Fig. 3-20.)
Mechanical cable terminals are normally included with
the switchgear (compression terminals are supplied when
ordered) and are mounted at the ends of the breaker
runbacks in the cable compartment. Carefully follow the
cable manufacturer's recommendations for installation of
cable.
Install the cables in the proper path to the terminals,
using temporary lashing if required. Cut the cables to the
proper length. Strip the insulation to the desired
dimension, being careful not to damage any strands.
For copper cables, coat the wires with GE lubricating
grease D6A15A2, insert the cables into the terminals, and
tighten the set screws in accordance with torque values
shown in the torque value table for cable terminals in the
addendum of this manual. See Appendix A, Table A-2.
For aluminum cables, wire brush the wire strands
thoroughly. Immediately after wire brushing, coat the
cable strands with a quality oxide inhibiting compound
such as Penetrox A. Insert exposed wires into the
terminals and tighten the set screws in accordance with
values shown in the torque Table A-2 in Appendix A of
this Instruction Book.
CAUTION: The torque values shown in the table are
for dry threads only. Do not grease or otherwise
lubricate the threads on the cable terminals, as this
will permit over-tightening of the screw and possible
damage to the terminal or cable.
ATTENTION: Les valeurs de couple indiquées dans le
tableau ne sont valables que pour des filets secs
uniquement. Il ne faut pas graisser ou librifier
autrement les filets des câbles terminaux, car cela
produira un serrage excessif de la vis et possiblement
des dommages au terminal ou au câble.
This should result in the oozing of compound material
from between individual strands. Wipe off any excess
compound.
Bolt the cable terminal connectors to the ends of the bars
in the cable compartment. Non-oxidizing grease, such as
GE lubricating grease D6A15A2 furnished with each
lineup, should be used at these connection surfaces. The
bolts should be tightened with a torque of 35-40 ft-lbs.
Lash the cables securely to the cable support, if present, to
take their weight off the runbacks and to brace them
against short circuit forces in the event of a fault.
36
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
Breaker Hoist
Fig. 4-18 shows the breaker hoist assembled on a switchgear
lineup. The hoist is shipped in a separate carton completely
assembled, Fig. 4-19.
Before attempting to install the hoist assembly on the
switchgear equipment, it is necessary to remove the runner
guide from the hoist carriage as shown in Fig. 4-20. Do not
dispose of this guide since it must be reinstalled after
mounting the hoist on the equipment.
NOTE: Maximum recommended lifting capacity is 700
lbs.
NOTE: La capacité maximale recommandée de
soulèvement est de 700 livres.
The hoist should be lifted into position on top of the
switchgear so that the end with two rollers is toward the rear
of the equipment, Fig. 4-21.
Fig. 4-21. Location of hoist rear rollers
The rear wheels can then be hooked under the channel and
the front wheels can be positioned on the front track. See
Fig. 4-22. The runner guide at the rear should then be
reassembled, Fig. 4-23. Stop clips are provided at each end of
the front track to prevent the hoist from rolling off the ends of
the track.
Fig. 4-22. Front rollers positioned on front track
Fig. 4-23. Replacing the runner guide after completion of hoist
installation
Fig. 4-24. Removing the bracket locking the hoist dolly
If the equipment has been shipped in sections, run the hoist
carriage over the assembled shipping split to check the
alignment of the hoist rail and runner. If necessary, adjust
the rail and/or runner for smooth operation of the rollers on
the hoist carriage.
On seismic rated equipment, it is necessary to remove the
bracket locking the hoist dolly on the carriage before the
hoist can be used, Fig. 4-24. Replace the bracket after
breaker installation or removal is complete.
Final Inspection
Make a final inspection to see that no tools, construction
materials, or other foreign matter have been left in the
switchgear equipment.
38
Entellisys Low Voltage Switchgear
Chapter 4. Equipment Installation
4-3 Installation of Wall-Mount HMI
General Requirements
Before installation, ensure the surface to which the enclosure will
be mounted is capable of safely supporting 85 lb.
proper sealing and enclosure protection rating, use
the provided sealing washers. Install the sealing
washers inside the enclosure with the tapered cone
against the enclosure and then add the flat washers
as shown in Figs. 4-26 and 4-27.
4. Attach a suitable conduit fitting to the hole from
Step 1. Run conduit to the enclosure as necessary.
Fig. 4-25. Wall-mount HMI enclosure
Enclosure Installation
The recommended procedure for installation of a wall-mount
HMI is as follows:
1. Add a conduit connection hole in either the top or
bottom wall of the enclosure. Do not position the hole
less than 1.5 inches from the edges of the enclosure.
See Fig. 4-28 for area suitable for conduit hole.
2. Four mounting holes are provided in the back of the
enclosure. Drill an identically spaced pattern of holes
in the surface to which the enclosure will be mounted
according to the drawing supplied with the enclosure.
3. Attach the enclosure to the wall or other structure
using 3/8 inch bolts, flat washers, and, if the bolts are
not self-threading, lock washers and nuts. To ensure
Fig. 4-26. Mounting the enclosure with bolts and nuts
Fig. 4-27. Mounting the enclosure with self-threading bolts
Device Wiring
The recommended procedure for connecting the HMI power
and communication cables is as follows:
1. Connect 120VAC line, neutral, and ground wires to
terminal block as shown in the wiring diagram
included with the assembly.
2. Connect incoming Ethernet cable to the port on the
side of the HMI. Secure the wires to HMI and
enclosure with cable ties.
3. If the enclosure is equipped with a power supply and
RS232/RS485 converter, connect the incoming
RS485 cable to converter terminals RX+ and RX-.
39
Entellisys Low Voltage Switchgear
Terminal Block
Power Supply
Areas suitable for
Chapter 4. Equipment Installation
Ethernet port
conduit hole
RS232/RS485
Converter
Fig. 4-28. HMI enclosure and devices
40
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
5-1 General
Inspection and Preparation of Circuit
Breakers
Before installing, operating, or removing a circuit breaker,
refer to the breaker instruction manual for preparation,
inspection, and test. Check thoroughly for damaged or loose
parts and for any dirt or foreign matter that may be in the
breaker. Be sure that a thin film of GE lubricating grease
D6A15A2 is present on primary disconnects of the switchgear
before installing the breaker.
Circuit Breaker Installation
To install a circuit breaker, proceed as follows:
1. Before installing a breaker, check the tightness of the
bolted joints in the primary disconnect bars. Refer to
torque value table, Appendix A, Table A-1, in this
manual for the proper torque values. Also check the
contact areas on each primary disconnect bar or cluster
of fingers for foreign matter that may have accumulated.
Clean these areas if necessary. Be sure that a thin film
of GE lubricating grease D6A15A2 covers the contact
areas before putting a breaker in the compartment.
2. Check to see that the breakers match their respective
compartments. Each breaker is assigned a part or mark
number. This number is shown on the breaker sheets of
the summary, the front view drawings, the breaker
nameplate, and on the identification card on the breaker
shipping carton. The breaker may also be identified
using the 8 digit catalog number.
3. To locate the breaker in the proper compartment, refer
to the breaker location list on the front view drawing.
Find the proper breaker by the identification card on the
breaker carton or the mark number on the breaker
nameplate. All identical breakers will have the same
mark and catalog number.
Drawout breakers of the same type and rating are interchangeable in their equipment compartments. Drawout
breakers of different frame size, type, or short-circuit rating
are intentionally made non-interchangeable to prevent
inserting the wrong type breaker into a drawout
compartment; unique "rejection hardware" is affixed to each
breaker and its compartment. When the wrong type breaker
is inserted into a cell, the pins on the breaker and the pins in
the cell interfere, thus preventing the wrong breaker from
being racked onto the primary stabs.
EXCEPTION: A breaker with a higher short-circuit rating
will fit into a compartment keyed for a lower short-circuit
rating. For example, an EGH-08 breaker can be inserted
into an EGS-08 compartment. An EGH-08 compartment,
however, will reject an EGS-08 breaker.
EXCEPTION: Un disjoncteur ayant un calibrage éléve de
court-circuit accomodera un compartiment classifié d’un
calibrage moindre de court-circuit. Par exemple, un
disjoncteur EGH-08 peut être inséré dans un comparitment
EGS-08. Cependant un disjoncteur EGS-08 sera rejeté d’un
compartiment EGH-08.
Figs. 5-1 and 5-2 illustrate the rejection pin mounting used in
EGS-08, EGH-08, EGF-08, EGX-08, EGS-16, EGH-16, EGF16, EGS-20, and EGF-20 compartments.
EGX-08 SETTING
Fig. 5-1. Rejection pin mounting used in EG-08/16/20 compartments
Rejection Feature
EGX-08 SETTING
Fig. 5-2. Rejection pins used in EG-08/16/20 compartments
41
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
REJECTION
ANGLE
Fig. 5-3. Isometric view of rejection angle used in EG-32/40/50
compartments
NOTE: If a breaker is rejected by the rejection pins, check
the breaker type and rating against the job drawing.
NOTE: Si un disjoncteur est rejeté par les pins
coulissants, vérifier de quel type est le disjoncteur ainsi
que le calibrage en rapport avec le plan de la tâche.
The complete rejection pin pattern code is included in
Appendix B.
5-2 Installing EG-08/16/20 Circuit
Breakers
Prior to Installation
Prior to lifting a breaker to its intended compartment
location, observe the following precautions:
Precautions:
1. Check the compartment to ensure that it is free of
foreign objects.
2. Verify that the breaker is the correct type for that
compartment.
3. Ensure that the breaker is OPEN.
4. Apply a thin fresh coat of GE lubricating grease
D6A15A2 to the breakers primary disconnects.
5. Ensure that the racking forks on the breaker are
correctly positioned for initial engagement with the
pins in the compartment. To do this, insert the
racking handle and rotate it fully counterclockwise.
• Vérifier le compartiment afin de s’assurer qui’il est
libre d’objets étrangers.
• Vérifier que le disjoncteur est du genre correct pour ce
compartiment.
• Assurez-vous que le disjoncteur est en position OPEN.
• Appliquer une mince couche fraîche de graisse
lubrifiante GE D6A15A2 aux débranchements
primaires du disjoncteur.
• Assurez-vous que les cames de montage du disjoncteur
soient positionnées correctement en vue de
l’engagment initial avec les goujons du compartiment.
Pour ce faire, insérer la poignée de montage et lui faire
effectuer une rotation complète dans le sens des
aiguilles d’une montre.
Installation Procedures
To install the EntelliGuard circuit breaker, proceed as
follows:
1. Carefully place the breaker in front of the section in
which it is to be installed. See Fig. 5-4.
2. Open the breaker compartment door by rotating the
door latch assembly ¼ turn clockwise.
3. Using the switchgear hoist or a suitable lifting
mechanism and the appropriate spreader, raise the
breaker above the elevation of the rails. See Fig. 5-5.
The lifting spreader for 800A, 1600A & 2000A AKR
breakers cannot be used with 800A, 1600A & 2000A
EntelliGuard breakers.
WARNING: Do not stand under the circuit breaker
during the hoisting operation.
ADVERTISSEMENT: Il est interdit de se tenir sous le
disjoncteur durant l’opération de levage.
Précautions:
42
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
Fig. 5-4. Reel out hoist cable. Attach spreader bar assembly
to circuit breaker
Fig. 5-5. Hoist breaker above rails
Fig. 5-6. Pull rails out completely from the circuit breaker compartment
43
Fig. 5-7. Lower the breaker onto the rails of the cell.
Remove the spreader bar assembly
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
CAUTION: When using the switchgear hoist, do not unwind the cable completely from the drum. To lift the
breaker, turn the hoist operating crank clockwise. To
lower the breaker, turn the hoist operating crank counterclockwise.
ATTENTION: Il ne faut pas dérouler complètement le
câble du cylindre lorsque l’on utilisse le treuil du dispositif
de commutation. Tourner la manivelle opérant le treuil
dans le sens des aiguilles d’une montre pour soulever le
disjoncteur. Tourner la manivelle opérant le treuil dans le
sens contraire des aiguilles d’une montre pour abaisser le
disjoncteur.
4. Fully withdraw rails to stops.
5. Slowly lower and guide the breaker to allow the 4
breaker wheels to align with the rails. See Fig. 5-7.
Remove the lifting device. The breaker is now
positioned on the drawout rails.
6. Roll the breaker into the compartment until the racking
forks meet the racking pin, this is the DISCONNECT
position. If an incorrect breaker has been installed, the
interference pins on the breaker will interfere with the
rejection pins in the compartment prior to reaching the
DISCONNECT position. See Fig. 5-8. At this point, the
racking forks are contacting the fixed racking pins in
the compartment.
7. Slide rails back into compartment. Close the compartment door and rotate latch ¼ turn counterclockwise.
8. Engage the racking handle by pushing and holding the
trip button in the breaker escutcheon, sliding the cover
just below it to the right, releasing the trip button, and
inserting the handle on the jackshaft. See Fig. 5-9.
9. Rotate the handle clockwise as far as it will go. As you
rotate the handle clockwise, the breaker will travel from
the DISCONNECT, through the TEST position (you will
notice an audible click), and then into the CONNECT
position. The breaker position can be seen on the
indicator, located on the breaker escutcheon.
Fig. 5-8. Push the breaker in completely. Close the door.
Fig. 5-9. Engage the racking screw with the racking handle
44
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
5-3 Installing EG-32/40/50 Circuit
Breakers
WARNING: Do not stand under the circuit breaker
during the hoisting operation.
ADVERTISSEMENT: Il est interdit de se tenir sous le
disjoncteur durant l’opération de levage.
CAUTION: When using the switchgear hoist, do not unwind the cable completely from the drum. To lift the
breaker, turn the hoist operating crank clockwise. To lower
the breaker, turn the hoist operating crank counterclockwise.
ATTENTION: Il ne faut pas dérouler complètement le
câble du cylindre lorsque l’on utilisse le treuil du dispositif
de commutation. Tourner la manivelle opérant le treuil
dans le sens des aiguilles d’une montre pour soulever le
disjoncteur. Tourner la manivelle opérant le treuil dans le
sens contraire des aiguilles d’une montre pour abaisser le
disjoncteur.
Installation Procedure
To position the EGS-32/40/50 circuit breaker on the drawout
rails, proceed as follows:
1. Carefully place the breaker in front of the section in
which it is to be installed, See fig. 5-4.
2. Open the breaker compartment door by rotating the
door latch assembly ¼ turn clockwise.
3. Using the switchgear hoist or a suitable lifting
mechanism and the appropriate spreader for EG32/40/50, raise the breaker above the elevation of the
rails. See Fig. 5-5.
4. Pull the drawout rails all the way out to its WITHDRAWN limit. The rail pin will be positioned at the
back of the rail slot.
5. Slowly lower and guide the breaker to allow the 4
breaker wheels to align with the rails. See Fig. 5-7.
Remove the lifting device. The breaker is now
positioned on the drawout rails.
6. Roll the breaker into the compartment until the racking
cams touch the racking pin and the spring discharge
stop engages. This is the DISCONNECT position. At
this point, the racking cams are positioned to engage
the fixed racking pins in the compartment, ready to
begin the racking motion. If the incorrect breaker has
been installed, the interference pins on the breaker will
interfere with the rejection teeth in the compartment
prior to reaching the disconnect position (Fig. 5-10).
7. Slide rails back into compartment. Close the
compartment door and rotate latch ¼ turn counterclockwise.
8. With the EG-32/40/50 breakers rotate the racking
access cover in the door and engage the racking handle
9. Rotate the handle clockwise as far as it will go. As you
rotate the handle clockwise, the breaker will travel from
the disconnect, through the test position (you will notice
an audible click as the secondary disconnects engage),
and then into the connect position. The breaker
position can be seen on the indicator, located on the
breaker escutcheon.
Fig. 5-10. Rating rejection bracket on EG-32/40/50
Fig. 5-11. Spring discharge interlock used on manually and electrically
operated breakers
45
Entellisys Low Voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
5-4 Removing the EG-08/16/20 Circuit
Breakers
WARNING: Do not stand under the circuit breaker
during the lowering operation.
ADVERTISSEMENT: Il est interdit de se tenir sous le
disjoncteur durant l’opération de levage.
CAUTION: When using the switchgear hoist, do not unwind the cable completely from the drum. To lift the
breaker, turn the hoist operating crank clockwise. To
lower the breaker, turn the hoist operating crank counterclockwise.
ATTENTION: Il ne faut pas dérouler complètement le
câble du cylindre lorsque l’on utilisse le treuil du dispositif
de commutation. Tourner la manivelle opérant le treuil
dans le sens des aiguilles d’une montre pour soulever le
disjoncteur. Tourner la manivelle opérant le treuil dans le
sens contraire des aiguilles d’une montre pour abaisser le
disjoncteur.
To remove the EG-08/16/20 circuit breaker, proceed as
follows:
1. With the door closed and latched, press and hold the
trip button while sliding the racking cover open. Now
release the trip button.
2. Insert the racking handle and rotate it counterclockwise
until the breaker travels from CONNECT through
TEST to the DISCONNECT position, as shown by the
position indicator. This operation should be performed
with the door closed. If the breaker closing spring is
fully charged, it will be automatically discharged a few
turns before the end of racking action.
3. Open the compartment door and fully extend the drawout rails. Roll breaker out to rail stops. This is the
WITHDRAWN position.
4. Before proceeding, visually check the breaker's spring
charge and close indicators to verify that breaker is
open and the springs are discharged.
5. Attach the lifting device and raise breaker off drawout
rails.
6. Push the drawout rails back into the compartment.
7. Pull the breaker forward until the primary disconnects
clear the compartment.
8. Lower the breaker onto a flat surface free of protrusions
that could damage the breaker's internal parts. The
back of breaker will be resting on the interference pins
and guide.
5-5 Removing the EGS-32/40/50
Circuit Breakers
WARNING: Do not stand under the circuit breaker
during the lowering operation.
ADVERTISSEMENT: Il est interdit de se tenir sous le
disjoncteur durant l’opération de levage.
CAUTION: When using the switchgear hoist, do not unwind cable completely from the drum. To lift the breaker,
turn the hoist operating crank clockwise. To lower the
breaker, turn the hoist operating crank counter-clockwise.
ATTENTION: Il ne faut pas dérouler complètement le
câble du cylindre lorsque l’on utilisse le treuil du dispositif
de commutation. Tourner la manivelle opérant le treuil
dans le sens des aiguilles d’une montre pour soulever le
disjoncteur. Tourner la manivelle opérant le treuil dans le
sens contraire des aiguilles d’une montre pour abaisser le
disjoncteur.
To remove EGS-32/40/50 breakers, proceed as follows:
1. With the door closed and latched, trip the breaker.
2. Rotate the racking access cover in the door, insert the
racking handle and rotate it counterclockwise until the
breaker travels from CONNECT through TEST to the
DISCONNECT position, as shown by the position
indicator. This operation should be performed with the
door closed.
3. Open the door, depress the spring discharge lever (Fig.
5-11) to discharge breaker's closing springs and then
fully extend the rails. While holding this lever depressed, pull the breaker all the way out to its
WITHDRAWN position.
4. Before proceeding, visually check the breaker's spring
charge and close indicators to verify that the breaker is
open and the springs are discharged.
5. Attach lifting device to cutout notches in top wraparound frame of the breaker, using care to prevent
damage to the wiring.
6. Lift the breaker off the rails. Push the rails back into
the compartment.
7. Pull breaker forward until primary disconnects clear
the compartment. Lower breaker onto a flat surface
free of protrusions that could damage the breaker's
internal parts.
46
Entellisys Low Voltage Switchgear
1
Chapter 5. Installing and Removing Circuit Breakers
5-6 Installing and Removing EGF08/16 Fused Circuit Breakers
Except for the open fuse lockout device and the integrally
mounted fuses on the upper studs, the EGF-08 and -16
breakers are identical to the non-fused EGS-08 and -16
models. The procedural steps for installing and removing the
EGF-08/16 breakers from the Entellisys switchgear
equipment are the same as that described in paragraph 5-2
and 5-4 for non-fused EGS-08/16 breakers.
5-7. Installing Fuses on EGF-08/16
Circuit Breakers
The fuses on EGF-08/16 breakers are mounted on the line
side primary disconnect conductors. The Class L fuses are
mounted as shown in Fig. 5-12. Other than the 800A size,
which has a single mounting hole per tang, each Class L fuse
tang has two holes sized for one-half inch bolts.
Appendix G includes a tabulation of the range of fuse sizes
available for these breakers including catalog numbers of
Ferraz-Shawmut Fuses.
Class J fuses rated 300 through 600A have one mounting
hole per tang. The 300, 350 and 400A sizes require copper
adapter bars as shown in Fig. 5-13.
Fig. 5-13. Mounting for 300, 350, and 400-ampere Class "J" fuses on
EGF-08 breakers
A special fuse is available for use with EGF-16 breakers.
This fuse provides a melting time-current characteristic that
coordinates with 1600A trip electronics. Compared physically
with a 2500A, NEMA Class L fuse, the special fuse is more
compact (shorter) and its tangs are specially configured and
offset to achieve the required pole-to-pole fuse spacing. A
special primary disconnect assembly mounts directly on the
outboard tang of the fuse. Because of their unique mounting
provisions, the following procedure should be adhered to
when replacing these fuses (Fig. 5-14):
2
3
4
Fig. 5-12. Typical mounting for Class "L" fuse on EGF-08/16 breakers
1. Special 2500A fuse 3. Upper barrier
2. Disconnect key 4. Primary disconnect
Fig. 5-14. EGF-16 breaker with special 2500-ampere fuse
47
Entellisys Low-voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
1. Remove the primary disconnect assembly from the fuse
tang. This is accomplished by first loosening the two
keys (2), Fig. 5-14, via their holding screw and pulling
them upward and out. After the keys are removed, pull
the disconnect assembly off the end of the fuse tang.
NOTE: This removal does not disturb the disconnect's
clamping force adjustment.
NOTE: Ce retrait n’affecte pas l’ajustement de la force de
serrage du sectionneur.
2. Remove the upper barrier (3).
3. Detach the inboard end of the fuse by removing the two
½-13NC bolts. A ratchet and socket with a short
extension will be required.
4. Remove the fuse.
5. Install the new fuse by reversing the disassembly
procedure. Ensure that the mating face of the fuse is
clean.
CAUTION: When replacing the fuse in the right pole
(plan view) of the breaker, note particularly that this fuse
is mounted differently from the other two fuses. As shown
in Fig. 5-15, for this phase the fuse is rotated 180 degrees
about its axis so that its inboard tang is positioned
beneath the breaker stud. This tang is offset with respect
to the opposite end, (Fig. 5-16), so that rotating the fuse
does not alter the position of the primary disconnect.
ATTENTION: Lorsqu’on procède au remplacement d’un
fusible dans le pole droit (vue de plan) du disjoncteur,
prendre note que ce fusible en particulier est monté
différemment des deux autres fusibles. Tel que montré à la
Fig. 5–15 pour cette phase le fusible est tourné de 180°
autour de son axe de façon à ce que son axe intérieur soit
positionné sous le plot du disjoncteur. Cette queue est
déplacée en tenant compte du bout opposé (Fig. 5–16),
pour que le fusible en rotation n’altère pas la position du
débranchement primaire.
Fig. 5-15. Plan view of EGF-16 breaker showing 2500-ampere fuse tang positions
48
Entellisys Low-voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
Fig. 5-16.Mounting for special 2500-ampere fuse on EGF-16 breaker
5-8 Installing and Removing Fuse
Rollout Elements (FRE)-30-38-inch
Wide Compartments
The FRE is racked into and out of its compartment just like a
breaker. However, the fuse and breaker compartments each
are equipped with keylocks to prevent racking the FRE when
its associated breaker is closed. The FRE also utilizes a
rejection pin scheme similar to that used on EGS-32/40/50
breakers, to prevent installation of an incorrect FRE.
All FRE models feature a hinged, perforated steel screen
panel in front of the fuses as shown in Fig. 5-17. This panel
can be opened to allow access to the fuses, Fig. 5-18, only
when the FRE is in the WITHDRAWN position. In all other
positions, an interference plate attached to the right side of
the panel prevents it from being opened. Operation of the
breaker compartment keylock is the same for all models.
With the breaker open, the key can be removed; this extends
the lock bolt, thereby maintaining the breaker in a trip-free
state while in the CONNECT position Fig. 5-20. The breaker
can be racked at will regardless of the keylock position.
Fig. 5-18. View showing perforated panel open to allow easy access to
fuses
The FRE compartment is KEY INTERLOCKED with the
associated breaker. The FRE is locked in the connect position
until a key is inserted in the FRE key interlock, Fig. 5-19, at
this time the FRE can be racked out.
49
Entellisys Low-voltage Switchgear
Chapter 5. Installing and Removing Circuit Breakers
The breaker is prevented from being closed until the key is
reinserted and captured in the breaker compartment key
interlock mechanism.
Secondary disconnects on the FRE provide the voltage signals
across each fuse to the OPEN FUSE LOCKOUT DEVICE on
the associated circuit breaker, Fig. 5-21.
Fig. 5-20. Key is captured in key interlock until breaker is opened
Fig. 5-21. View showing Open Fuse Lockout Device on the associated
breaker
50
Entellisys Low-voltage Switchgear
Chapter 6. Testing and Inspection
6-1 General
After the equipment has been installed and all connections
made, it must be tested and inspected before it is put in
service. Although the equipment and devices have been
tested at the factory, a final field test must be made to be sure
that the equipment has been properly installed and that all
connections are correct.
WARNING: The equipment must be completely deenergized while the tests are in progress.
ADVERTISSEMENT: L’équipement doit être
complètement désamorcé lorsque l’on procède à des tests.
Directions for testing Entellisys instrumentation is provided
in DEH-231 (Entellisys System User’s Manual) and DEH-233
(Entellisys System Test Kit User’s Manual.) The proper
settings of Entellisys instrumentation are normally
determined from a complete power system coordination study
performed by the purchaser or their consultant; therefore, the
settings of these devices must be made by the purchaser.
NOTE: The trip setting adjustment of the EntelliGuard
Messenger for each circuit breaker may be in any position
when shipped from the factory and must be correctly
positioned prior to energization of the equipment.
NOTE: Les ajustements des réglages du disjoncteur
peuvent être en n’importe quelle position lorsque celui-ci
est expédié de l’usine et ils doivent être positionnés
correctement avant que l’équipement ne soit mis sous
tension.
The extent of the tests on the equipment as a whole will
depend on the type and function of the equipment. Tests that
should be performed, however, include circuit breaker
operation, and switchgear meggering, phasing, and grounding
checks.
High-potential tests to check the integrity of the insulation
are not necessary if the installation instructions are carefully
followed. If local codes demand this test, or the purchaser
wishes to make high-potential tests, the voltage should not
exceed 75 percent of the IEEE factory test voltage.
For the power circuit, the IEEE factory test voltage is two
times switchgear rating plus 1,000 volts. See Table 6-1.
Potential and control power transformers must be
disconnected during high-voltage testing.
Switchgear
Voltage Rating
600V
480V
240V
ANSI
Test Voltage,
AC RMS
2200V
1960V
1480V
Field
Test Voltage,
AC RMS
1650V
1470V
1110V
Table 6-1
6-2 Key Interlocks
After initial installation of the switchgear equipment, all
necessary interlock keys should be inserted into the
appropriate locks and all spare keys should be stored in a
location in accordance with the owner's established
procedures.
CAUTION: Refer to the key interlock schematic included
in the summary furnished with the equipment to determine the sequence of operation and the correct number of
operating keys required. This precaution is necessary
since the improper use of spare keys will defeat the
interlocking scheme.
ATTENTION: Référez-vous au schéma des clés de
verrouillage inclus au sommaire fourni avec l’équipement
pour déterminer les séquences d’opération et le nombre
correct de clés d’opération requises. Cette précaution est
nécessaire étant donné qu’un mauvais usage des clés de
réserve rendra inopérant le programme de verrouillage.
6-3 Breaker Operation Test
All compartments housing EntelliGuard circuit breakers have
a TEST position in which the breaker primary contacts are
disconnected while the secondary contacts are still engaged.
This TEST position permits complete testing of the electrical
control circuit without energizing the primary power circuit.
When the breaker is first put into service, its control circuit
must be thoroughly tested while in this position to make sure
that all closing and tripping circuits are complete and
functioning properly.
The TEST position is not suitable for inspection and
maintenance of the breaker and should therefore be used only
for testing breaker operation.
Refer to the appropriate breaker instruction manual for other
pre-operational checks on the breakers. See DEH-201 or
DEH-202.
6-4 Entellisys System Test Kit
An Entellisys System Test Kit is required for testing
Entellisys Low Voltage Switchgear functionality. The system
test kit user manual is DEH-233.
51
Entellisys Low-voltage Switchgear
Chapter 6. Testing and Inspection
6-5 Final Steps to Be Taken Before
Energizing Equipment
The following steps should be taken before energizing the
equipment:
1. Manually exercise all switches, circuit breakers, and
other operating mechanisms to make certain they are
properly aligned and operate freely.
2. Conduct an electrical insulation resistance test to make
sure the switchgear is free from short circuits and
grounds. This should be done both phase-to-ground and
phase-to-phase with the switches or circuit breakers
both opened and closed. This test should be performed
with a 1000-volt megger. Disconnect all control circuits
before checking resistance.
3. Check for secure mounting and wiring connections at
Entellisys instrumentation.
4. Using the Entellisys HMI, exercise all EntelliGuard
breakers to determine all devices work correctly. See
DEH-231 for instructions on using the Entellisys HMI.
.
5. Test all protection functions using the Entellisys
System Test Kit. See DEH-233 for instructions.
6. Make certain that field wiring is clear of live bus and,
where necessary, physically secured to withstand the
effects of fault currents.
7. Check to determine that all grounding connections are
made properly.
8. Remove all debris, scrap wire, etc., from the switchgear
interior before closing the enclosure.
9. Install covers, close doors, and make certain that no
wires are pinched and that all enclosure parts are
properly aligned and tightened.
52
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
7-1 Circuit Breaker Operation
General
Included below are abbreviated operating instructions for
EntelliGuard circuit breakers. Before activation of the circuit
breakers or operation of the switchgear equipment,
thoroughly read, and be familiar with, the circuit breaker
manuals that will be supplied as supplementary information
to this manual. Publication numbers are: DEH-201 and
DEH-202.
Manually operated EntelliGuard breakers are equipped with
an integral charging handle and a push button marked
CLOSE on the front of the escutcheon. The spring must be
charged first.
1. FOR EG-08/16/20 BREAKERS - A complete charge is
accomplished by pulling the handle down about 90°
(until it stops) five-six times to fully charge the closing
springs. This will not close the breaker contacts. The
charge indicator will show CHARGED on a yellow
background.
2. FOR EG-32/40/50 BREAKERS - These breakers require
the handle to be pulled down eight times to fully charge
the springs. The charge indicator will show CHARGED
on a yellow background.
Opening Manually Operated EntelliGuard Breakers
A mechanically operated, double insulated open button,
mounted on the breaker escutcheon, operates the trip shaft to
open the breaker. The breaker many also be opened by the
Entellisys HMI.
Electrically Operated Breakers
The breakers may be closed by a mechanically operated, double
insulated push-button switch on the breaker escutcheon or by the
Entellisys HMI. Fuses are located in the breaker compartment,
just behind the door.
Electrically Opening EntelliGuard Breakers
Electrically operated EntelliGuard breakers are equipped with
both a shunt trip and a flux shifter for opening the breaker. A
normally open auxiliary switch “A” contact opens the shunt trip
control circuit after the breaker opens, preventing damage to the
device. The shunt trip and flux shifter operate in response to
OPEN and TRIP commands, respectively, from the HMI
breaker control screen.
7-2 Circuit Breaker Drawout
Operation
Breaker Positions
Refer to Fig. 7-1. The drawout operation features four
positions:
1. CONNECT - In the CONNECT position, the primary
and secondary disconnects are fully engaged. The
breaker must be opened before it can be racked out of
this position.
2. TEST - When in the TEST position, the primary
contacts are disconnected, but the secondary contacts
remain engaged. This allows complete breaker
operation without energizing the primary circuit.
3. DISCONNECT - In the DISCONNECT position, neither
primary or secondary contacts are made. Breakers may
be racked between these three positions with the
compartment door closed and latched.
4. WITHDRAWN - With the door open, the breaker can be
rolled out manually from the DISCONNECT to the
WITHDRAWN position. Here, the breaker is
completely out of its compartment, ready for removal.
Fig. 7-1. EntelliGuard circuit breaker
Shown in DISCONNECT position
53
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
Drawout Operation
All breakers are supported on the drawout rails mounted on
the sidewalls of the breaker compartments. On EntelliGuard
breakers, two wheels on each side of the breaker rest on each
drawout rail.
Motion is provided by a mechanism mounted on the breaker.
This mechanism drives racking cams that engage pins
anchored to each side of the compartment.
The cams are driven by a removable racking handle that
engages the mechanism. On small frame breakers, the
handle is inserted through an opening in the breaker
escutcheon; on large frame breakers, the handle is inserted in
an opening in the upper right side of the door.
Turning the handle in a clockwise direction drives the
breaker into the compartment. As the breaker disconnect
fingers engage the stationary studs, a high force will be felt.
Turn the racking handle as far as it will go to be sure the
disconnect fingers are completely engaged.
The position indicator in the breaker escutcheon gives the
position of the breaker as it moves through the door cutout.
4. Close the door.
7-3 Front Doors
Operation
The front access doors on all standard Entellisys Switchgear
are hinged and equipped with a ¼-turn latch, Fig. 7-3. To
open the door, rotate the knob clockwise ¼ turn.
Removal and Installation
Refer to Fig. 7-3 and remove/install switchgear front doors.
Door Removal
To remove the Entellisys Switchgear door, proceed as follows:
1. Open door.
2. Loosen the two screws holding the top hinge pin plate
and allow the pin to drop out of the hinge block. See Fig.
7-3.
3. Move the top of the door away from the switchgear,
avoiding the door stop and lift the door out of the lower
hinge pin socket. Retain the washer from the bottom
hinge pin.
Door Installation
To install the Entellisys Switchgear door, proceed as follows:
1. Insert washer, then place lower hinge pin into hinge pin
socket on switchgear. See Fig. 7-3.
2. Swing door open, position behind door stop and align
hinge pin socket.
3. Insert the hinge pin into the upper hinge block and
tighten the two screws.
Fig. 7-2. Entellisys switchgear front access doors are hinged with a
rotary-type latch
Fig. 7-3. Drawing showing front access details
54
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
7-4 Entellisys Switchgear
Accessories
Future Circuit Breaker Compartments
Breaker compartments designed for future use are complete
and ready to use. These breaker compartments have a steel
panel to cover the door cutout, Fig. 7-4. To prepare the
circuit breaker compartment for use, remove the steel outer
cover.
WARNING: Terminals behind the steel barrier may be
energized.
AVERTISSEMENT: Il se peut que les bornes à l’arrière
de la barrière d’acier soient sous haute tension.
bolt may be extended and the key removed. The
breaker will remain trip free in the CONNECT position
until the key is returned and the lock bolt is retracted.
Fig. 7-4. Future-use breaker compartments
Circuit Breaker Key Interlock
General
A circuit breaker key interlock is available to provide
protection against unauthorized operation. See Fig. 7-5.
The key interlock is mounted with two one-way screws and
lockwashers on the left side of the breaker compartment.
The interlock system is designed so that the key may be
removed from the lock only when the breaker is tripped and
the lock bolt is extended. With the bolt extended, the
breaker is rendered trip free only in the CONNECT position
in this compartment.
The breaker may be operated (open, trip, charge, close) in
the TEST position even when the lock bolt is extended and
the key removed.
Key Interlock Operation Check
The operation of the key interlock should be checked as
follows:
1. With the breaker in the CONNECT position, manually
trip the breaker. This then allows the interlock trip
slide to be pushed in. When the trip slide is in, the lock
Fig. 7-5. View showing circuit breaker key interlock to provide
protection against unauthorized operation
2. If desired, the breaker may be moved to either the
TEST position while the key is removed from the lock.
In these positions, the breaker can be operated for
checking or maintenance.
Test and Disconnect Padlock Device
General
WARNING: This padlock lockout does not provide
equipment de-energization, isolation and grounding
required for maintenance personnel safety. See
instruction book DEH-203 or DEH-204 for details.
AVERTISSEMENT: Le mécanisme de verrouillage à
cadenas ne fournit pas la mise hors tension adéquate de
l’équipement, l’isolation et las mise à la terre requis pour
assurer la sécurité du personnel de maintenance. Voir les
instructions DEH–203 ou DEH–204 pour les details.
A test and disconnect rackout mechanism padlock device is
available to prevent unauthorized racking of the breaker.
The rackout mechanism for circuit breakers and FRE may be
locked in either the DISCONNECT or TEST position.
55
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
2. The device will permit locking the breaker in the DISCONNECT or TEST position. Hasps, which pivot on
the corner post in combination with the circuit breaker
crank interlock, prevent movement of the breaker from
its locked position.
3. Align the appropriate hasp (front hasp for DISCONNECT position or rear hasp for the TEST position),
insert, and lock the padlock.
Fig. 7-6. Test & disconnect position padlock device (EG-08/16/20
breakers)
Padlocking the EG-08/16/20 Breakers. (See Fig. 7-6.)
To padlock these breakers, proceed as follows:
1. The circuit breaker compartment door must be opened
to put the padlock on; however, there is no interference
with the door after the padlock has been placed in
position.
2. With breaker moved to the appropriate position, push
down on the sliding lock plate until its holes are aligned
with those in the stationary plate. Insert and lock the
padlocks.
Padlocking the EG-32/40/50 Breakers & EG-32/40/50
FRE Fuse Rollout Element (See Fig. 7-7.)
1. The circuit breaker compartment door must be opened
to put the padlock on; however, there is no interference
with the door after the padlock has been placed in
position.
Padlocking the EG-08/16/20, EG-32/40/50, EG32/40/50 FRE Compartments (See Fig. 7-8.)
1. The circuit breaker compartment door must be opened
to put the padlock on; however, there is no interference
with the door after the padlock has been placed in
position.
2. Padlocks will prevent the acceptance of breakers or FRE
in the compartment
Installing and Removing Current
Transformers
WARNING: Do not operate any current transformer with
secondaries open-circuited. Be sure to short-circuit
secondary before moving a current transformer.
AVERTISSEMENT: Tout transformateur de courant ne
doit pas être opéré avec les secondaires dans un état de
circuits ouverts. Assurez-vous de court-circuiter les
secondaires avant de bouger un transformateur de
courant.
Phase current transformers (CT's) in Entellisys Low Voltage
Switchgear are mounted on the stationary primary
disconnect studs in the breaker compartment and are readily
accessible for inspection and replacement. Neutral current
transformers, if present, are located in the bus compartment
or in the transition section.
56
Entellisys Low Voltage Switchgear
9
12
13
7
Chapter 7. Operating the Switchgear
Care must be exercised when installing or removing phase
current transformer mounting screws so as not to strip the
holes in the plastic base. Do not torque screws over five
in/lbs.
Removing Shutter Units
Visual inspection of primary disconnects and CT's can be
made by first removing the breaker and opening the
shutters manually. This is done by pressing the left and
right hand actuating rollers toward the rear of the
compartment simultaneously. This is a two-handed
operation.
If it is necessary to perform work on the primary
disconnects or CT’s, it will be necessary to remove the
entire shutter unit.
WARNING: Unless the proper precautions are taken,
the removal of a shutter unit presents the hazard of
electrical shock and burn. Do not remove the shutter
unit unless the equipment has been de-energized.
Failure to do this can result in serious injury.
ADVERTISSEMENT: A moins que les précautions
nécessaires ne soient prises, l’installation d’une unité à
volet présente des risques de choc électrique ou de
brûlure. Il ne faut pas installer l’unité à volet à moins
que l’équipement ait été désamorcé. L’omission de ce
faire peut résulter en blessures sérieuses.
16
1
14
2
5
3
6
11
4
8
1. Frame assembly 7. Support block 13. Spring
2. Frame assembly 8. Support block 14. Complete upper shield
3. Shutter Actuator 9. Bottom shield assembly
4. Bottom shutter 10. Connector link 15. Shield cover
5. Support Block 11. Spring 16. Label
6. Center shield 12. Spring
Fig. 7-9. Entellisys circuit breaker shutter unit (EGS-08/16 breakers)
15
10
57
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
4
5
2
1
6
1. Side frame assembly (right) 4. Front shield
2. Side frame assembly (left) 5. Shutters
3. Movable shield assembly 6. Shutter actuator
Fig. 7-10. Entellisys circuit breaker shutter unit (EG-32/40/50 breakers)
Removing an EG-08/16/20-Shutter Unit
To remove these shutter units, proceed as follows:
1. The shutter unit frame is mounted on the vertical
stringers located at each side of the rear of the breaker
compartment. See Fig. 7-9. In extended
compartments, the shutter is mounted to extension
brackets.
2. If it is present, remove the Clamp Circuit, mounted on
the left hand side sheet. Remove the twelve wires from
the two terminal blocks, and then remove the ¼-inch
hex head screws from the enclosure.
3. Take out two 1/4-inch hex head screws on each side of
the frame. A socket wrench with a 3/8-inch driving
head with 4-inch extension will be needed.
4. Carefully remove the entire shutter frame.
5. The frame is then maneuvered forward past the cam
plates on each side, then upward and forward over the
cam pins.
Removing an EG-32/40/50 or Fuse Roll Out
Shutter Unit
To remove these shutter units, proceed as follows:
1. The shutter unit frame is mounted to the vertical
stringers located at each side of the rear of the breaker
compartment. See Fig. 7-10.
2. Take out 11 ¼-inch hex head screws from the frame. A
socket wrench with a 3/8-inch driving head with an 8inch extension will be needed. See Fig. 7-10.
3. Carefully remove the entire shutter frame.
3
58
Entellisys Low Voltage Switchgear
Chapter 7. Operating the Switchgear
Installing a Shutter Unit
WARNING: Unless the proper precautions are taken,
the installation of a shutter unit presents the hazard of
electrical shock and burn. Do not install the shutter
unit unless the equipment has been de-energized.
Failure to do this can result in serious injury.
ADVERTISSEMENT: A moins que les précautions
nécessaires ne soient prises, l’installation d’une unité à
volet présente des risques de choc électrique ou de
brûlure. Il ne faut pas installer l’unité à volet à moins
que l’équipement ait été désamorcé. L’omission de ce
faire peut résulter en blessures sérieuses.
Installing an EG-08/16/20 Shutter Unit
To install these shutter units, proceed as follows:
1. Carefully maneuver the shutter frame into the
compartment, first lifting it over the cam pins on
each sidewall and past the cam plates.
2. Position the rear flanges of the shutter frame against
the vertical stringers at the rear corners of the
compartment.
3. Align the holes in the flange and drive in four 1/4-
inch hex head screws using a 3/8-inch driver and a
socket wrench with a 4-inch extension.
4. If it was present, reinstall the Clamp Circuit.
Reconnect the 12 wires in the same positions as
they were before. Reattach the enclosure to the side
sheet using ¼”-inch hex head screws
5. Check the operation of the moveable shutters by
pressing the left and right hand actuating rollers
toward the rear of the compartment.
Installing an EG-32/40/50 or Fuse Rollout Shutter
Unit
To install these shutter units, proceed as follows:
1. Carefully maneuver the shutter frame into the
compartment.
2. Position the rear flanges of the shutter frame
against the vertical stringers at the rear corners of
the compartment.
3. Align the holes in the flange and drive in eleven
1/4-inch hex head screws using a 3/8-inch driver
and a socket wrench with 8-inch extension.
4. Check the operation of the moveable shutters by
pressing the left and right hand actuating rollers
toward the rear of the compartment.
59
Entellisys Low Voltage Switchgear
Chapter 8. Energizing the Switchgear
8-1 Before Energizing
Before switchgear is energized, a thorough final check should
be made using the following checklist: Refer to section 6-5 for
additional information.
• Breakers and other operating mechanisms exercised
• Electrical insulation resistance tested phase-to- phase
and phase-to-ground
• Entellisys instrumentation properly connected
• Electrically operated breakers and operating mechanisms
tested
• Ground fault protection system tested
• Protection settings properly set and tested.
• Field wiring secured and free of live bus
• Grounding connections made
• All debris, scrap wire, etc. removed
• All covers installed, doors closed and latched
8-2 Energizing Procedures
CAUTION: Energizing switchgear for the first time is
potentially dangerous. Therefore, qualified electrical
personnel should be present when the equipment is
energized. If problems caused by damage or poor
installation practices have not been detected in the
checkout procedure described previously, serious damage
can result when power is turned on.
ATTENTION: La mise sous tension pour la première fois
d’un dispositif de commutation est un acte potentiellement
dangereux. Il faut donc que du personnel qualifié en
électricité soit présent lorsque l’équipement est mis sous
tension. Si lors de la procédure de vérification décrite
précédemment des problèmes causés par des dommages ou
de mauvaises pratiques d’installation n’ont pas été
détectés, il peut en résulter des dommages sérieux lorsque
le contact est établi.
1. There should be no load on the switchgear when it is
energized.
2. Turn off all of the downstream loads, including those
such as motor control centers and other devices that
are remote from the switchgear.
3. The equipment should be energized in sequence by
starting at the source end of the system and working
toward the load end. In other words, energize the main
devices, then the feeder devices, and then the branchcircuit devices.
4. Turn the devices on using the Entellisys HMI.
60
Entellisys Low Voltage Switchgear
Chapter 9. Maintaining the Switchgear
9-1 Maintenance Requirements
General
A periodic maintenance schedule must be established to
obtain the best service from the switchgear. Under the
conditions of a clean and dry environment, a check of the
switchgear devices and all connections should be made once
every two years. Equipment subject to highly repetitive
operation or to a dusty or humid environment may require
more frequent maintenance.
A permanent record of all maintenance work should be kept.
The record should include a list of periodic checks and tests
made, the date they were made, the condition of the
equipment, and any repairs or adjustments that were
performed. Maintenance employees must follow all
recognized safety practices, such as those contained in the
National Electric Safety Code, ANSI C2-1981 and in company
or other safety regulations.
WARNING: Solid insulation surrounding an energized
conductor and power apparatus must never be relied upon
to provide protection to personnel.
ADVERTISSEMENT: Il ne faut pas se fier à une isolation
solide entourant un conducteur mis sous tension et à la
puissance de l’appareillage pour fournir une protection aux
membres du personnel.
For specific information regarding the maintenance of circuit
breakers and Entellisys instrumentation, refer to the
instruction book furnished with each device.
9-2 Breaker and Instrument
Compartments
Periodic inspection of the circuit breaker is recommended at
least once a year. More frequent inspections are
recommended where severe load conditions, dust, moisture or
other unfavorable conditions exist, or if the vital nature of
the load warrants it. Always inspect the breaker after a
short-circuit current has been interrupted.
Breakers
Test for Proper Operation
Test and inspect all circuit breakers for proper operation as
follows:
1. Operate each breaker while in the TEST position and
check all functions. This is particularly important for
breakers that normally remain in either the opened or
closed positions for long periods of time.
WARNING: Primary equipment must be completely deenergized while tests on control circuits, etc. are being
conducted. Be sure that all areas of feedback from
secondary circuits, as well as outside sources, are
disconnected.
ADVERTISSEMENT: Il faut que l’équipement primaire
soit complètement désamorcé lorsque des tests sont
effectués sur des circuits de contrôle, etc. Assurez-vous que
toutes les aires de rétroaction des circuits secondaires de
même que les sources extérieures soient débranchées.
2. Remove the breakers from their compartments to a
clean maintenance area. Close compartment door and
cover the breaker cutout to prevent access to live parts.
WARNING: De-energize equipment completely before
doing maintenance work on any devices, connections, bus
work, breaker or feeder cable compartments. This includes
de-energizing any connections to outside primary or
secondary sources, such as transformers, tie lines, etc.
ADVERTISSEMENT: Désamorcer complètement
l’équipement avant d’effectuer du travail de maintenance
dans les compartiments. Cela inclut le désamorçage de
toute connexion aux sources primaires et secondaires,
telles que les transformateurs et les interconnexions.
Checks After Breaker Is De-energized
At the time of inspection, the following checks should be
made after the breaker has been de-energized.
1. Manually operate the breaker several times, checking
for obstructions or excessive friction. Manual closing of
an electrically operated breaker may be performed by
the following two steps:
a. For the EG-32/40/50 frame breakers, raise the
breaker frame off the work surface to ensure the
spring discharge interlock is not depressed. To
charge the mechanism springs, pull the operating
handle down until it stops (about 90°) five-six times
for the EG-08/16/20 and eight times for the EG32/40/50 frame. The charge indicator will show
CHARGED on a yellow background.
b. Depress the CLOSE button on the front of the
breaker. The springs should discharge and, if the
Refer to circuit breaker instruction manuals for detailed
maintenance instructions and information for replacement of
parts. See DEH-203, DEH-204, DEF-004 or DEF-005.
latch is properly reset, the breaker will close.
2. Electrically operate the breaker several times to check
performance of the electrical accessories.
3. Visually check for loose hardware on the breaker. Also,
check the bottom of the compartment for any hardware
that has fallen from the breaker.
4. Remove and inspect the arc quenchers and contacts for
breakage or excessive burning.
5. Check insulating parts for evidence of overheating and
for cracks that indicate excessive thermal aging.
61
Entellisys Low Voltage Switchgear
Chapter 9. Maintaining the Switchgear
Lubrication
In general, the circuit breaker requires moderate lubrication.
Bearing points and sliding surfaces should be lubricated at
the regular inspection periods with a thin film of GE
lubricant D6A15A2. Before lubricating, remove any
hardened grease and dirt from latch and bearing surfaces
with mineral spirits then wipe with a clean rag.
CAUTION: All excess lubricant should be removed with a
clean cloth to avoid accumulation of dirt or dust.
ATTENTION: Il faut enlever complètement tout excès de
lubrifiant avec un linge propre afin d’éviter l’accumulation
de saletés ou de poussières.
On drawout breakers, the contact surface of the disconnect
fingers should be cleaned and greased with GE lubricant
D6A15A2 as well.
Entellisys Instrumentation and Instrument
Transformers
Check and inspect all devices to see that they are functioning
properly. Check that all electrical connections are tight.
Check mounting of the device.
Breaker Compartment Interiors
WARNING: De-energize equipment completely before
doing maintenance work in compartments. This includes
de-energizing any connections to outside primary or
secondary sources, such as transformers, tie lines, etc.
ADVERTISSEMENT: Mettre l’équipement complètement
hors tension avant d’entreprendre tout travail de
maintenance sur tout dispositif, raccordement, barres
omnibus ou les compartiments des câbles d’alimentation.
Cela inclut la mise hors tension des raccordements aux
sources primaires et secondaires tels que les
transformateurs et les interconnexions.
1. Thoroughly clean the interior of the breaker and
instrument compartments. Use a vacuum cleaner and
clean rags only. Do not use steel wool or oxide papers.
Blowing with compressed air is not recommended.
2. Check indicating devices, mechanical and key interlocks.
3. Check primary disconnecting device contacts for signs of
abnormal wear or overheating. Discoloration of the
silvered surfaces is not ordinarily harmful. These
contacts should be cleaned only by wiping with a lintfree cloth.
4. Clean the racking mechanism and lubricate with GE
lubricant D6A15A1.
5. Before replacing the breaker, wipe off the primary
disconnecting device contacts. Apply a thin coat of GE
lubricant D6A15A1 to the stationary studs and to the
primary disconnects on the breaker.
9-3 Bus Area
WARNING: De-energize equipment completely before
doing maintenance work on any devices, connections, bus
work, breaker or feeder cable compartments. This includes
de-energizing any connections to outside primary or
secondary sources, such as transformers, tie lines, etc.
ADVERTISSEMENT: Désamorcer complètement
l’équipement avant d’effectuer du travail de maintenance
dans les compartiments. Cela inclut le désamorçage de
toute connexion aux sources primaires et secondaires,
telles que les transformateurs et les interconnexions.
Inspect and check the bus area as follows:
1. Inspect the buses and connections carefully for evidence
of overheating or weakening of the insulating supports.
If bus insulation is present, remove the molded covers
over the main bus connection to expose joints for
inspection.
2. Check all connection bolts in the bus compartment and
all bracing bolts for tightness. See the Torque Table A-1
in Appendix A.
3. Vacuum and, with a clean rag, wipe the buses and
supports.
4. Visually inspect the insulation on the bars that run
from the breaker studs through the bus structure to the
cable area.
5. After cleaning, megger and record the resistance to
ground and between phases of all insulated bars and all
buses and connections. Disconnect all control circuits
before checking resistance. Do not apply greater than
1500 volts with the megger. Since definite limits cannot
be given for satisfactory insulation resistance values, a
record must be kept of the readings.
Weakening of the insulation from one maintenance period to
the next can be recognized from the recorded readings. The
readings should be taken under similar conditions each time,
if possible, and the record should include the ambient
temperature and humidity.
9-4 Cable and Busway Compartment
Inspect and check the cable and busway compartment as
follows:
1. Inspect all power cable connections for signs of
overheating and tighten all connections. If severe
discoloration or if damage is apparent, remove the
damaged portion of the cable.
CAUTION: Be sure the condition that caused the overheating has been corrected before energizing.
62
Entellisys Low Voltage Switchgear
Chapter 9. Maintaining the Switchgear
ATTENTION: Assurez-vous que la condition ayant causé
le surchauffement a été corrigée avant de mettre sous
tension.
2. Check all bolts that hold cable terminals to the
connection bars for tightness.
3. Check the neutral bus and ground bus connection and
mounting bolts for tightness.
4. Check that all secondary control wiring connections
are tight and that all control cabling is intact.
9-5 Overall Switchgear
Make the following checks on the complete switchgear
equipment.
1. Clean and inspect all painted surfaces and retouch
where necessary.
2. Check to see that all anchor bolts and other structural
bolts are tight.
3. Check that all breaker and instrument compartment
door latches operate properly.
4. If the switchgear is equipped with heaters, check to see
that all heaters are energized and operating.
5. For exterior vent openings in equipment furnished with
air filters, the foam filter elements should be removed
and washed in warm soapy water, rinsed, and
reassembled at least annually. Elements should be
inspected before re-assembly and replaced if any signs
of deterioration are evident.
9-6 Paint Refinishing
Indoor switchgear is finished with ANSI-61 gray acrylic
enamel paint. To refinish damaged areas, remove all loose
paint, rust, scale, oil or grease. Sand any scratches smooth
using 220 grit paper or finer.
—Apply a coat of acrylic enamel primer with a viscosity of
approximately 24-32 seconds using a #2 Zahn cup. Reduce
with thinner if needed. Air-dry the primer for a minimum of
30 minutes, and then apply the finish color coat of acrylic
enamel. The topcoat should be applied within 24 hours for
best adhesion.
—If the area is to be spray-coated, thin the acrylic enamel.
This thinning should only be necessary if the paint was
received in a five-gallon drum or more. The recommended
viscosity for the enamel topcoat should be 24-32 seconds with
a #2 Zahn cup. Both the primer and paint should be applied
only when temperature is above 55 degrees Fahrenheit.
—Application of special paint will be per the manufacturer’s
Product Data Sheet that includes instructions on thinning
and application.
9-7 Circuit Breaker Lifting
Mechanism
Under normal conditions, no special maintenance procedures
or lubrication is required for this device. If the cable is
abraided under any condition, it should be inspected for
broken strands or other damage and replaced if necessary.
63
Entellisys Low Voltage Switchgear
Appendix A. Torque Values
Table A-1—Torque Values for Low- voltage Equipment
Electrical Joint Hardware other than Cable Terminals
(Copper, Tin or Silver Plated)
Hardware
Size
¼-20
3/8-16
½-13
5/8-11
*These torque values are for non-lubricated threads
Caution should be exercised when installing parts or
components to the compartment molded base. Torque 1/4inch screws slowly and do not exceed nine ft/lbs.
Torque*
(ft/lbs)
Standard Nut with
Conical Spring Washer
or Lock washer
7-10
25-30
35-40
45-55
Table A-2—Torque Values for Self-threading Screws in
*These torque values are for non-lubricated threads.
Torque*
(in/lbs)
100
125
150
200
250
300
400
500
64
Entellisys Low Voltage Switchgear
Appendix B. Circuit Breaker Rejection Features
General
In general, EntelliGuard breakers of the same type and
rating are interchangeable in their equipment compartments.
Similarly, breakers may be installed into equipment
compartments designed for breakers having lower ratings.
Breakers are intentionally made uninstallable into
compartments for breakers with higher ratings.. To prevent
inserting the wrong type breaker into a drawout
compartment, unique “rejection hardware” is affixed to each
breaker and its compartment. The rejection is accomplished
by tabs or pins on the bottom of the breaker backframe and
tabs or pins on the top of the pan in the equipment
compartment.
22-inch Wide Compartment
Figure B-1 (EG-08/16/20 breaker family) shows the breakermounted rejection tabs located on the bottom left side of the
backframe.
When a wrong type breaker is inserted into a compartment,
the breaker tabs and equipment pins interfere, preventing
the breaker from rolling into the DISCONNECT position.
Breakers may be interchanged in one direction only.
Specifically:
1. Any EG-08/16/20 breaker can be inserted into an
EGS-08 compartment.
2. An EGX-08, EGH-16, EGS-20 or EGF-20 can be
inserted into an EGH-08 compartment.
3. An EGS-20 or EGF-20 may be inserted into an EGX08 or EGH-16 compartment
4. An EGH-16, EGS-20, or EGF-20 may be inserted
into an EGS-16 compartment
Fig. B-1. Breaker-mounted rejection plate
5. An EGF-20 may be inserted in an EGS-20
compartment
The rejection hardware prevents the converse of the above.
Figure B-2 shows the rejection pin combinations employed for
¡ ¡ ¡ l ¡ ¡ ¡ ¡ l
¡ l ¡ l ¡ ¡ ¡ ¡ l
¡ l l l ¡ ¡ ¡ ¡ l
¡ l l l ¡ ¡ ¡ l l
l ¡ ¡ l ¡ ¡ ¡ ¡ l
l l ¡ l ¡ ¡ ¡ ¡ l
l
l
l l l l ¡ ¡ ¡ ¡ l
l l l l ¡ ¡ ¡ l l
l
l
Fig. B-2. Rejection pin pattern code for EG-08/16/20 breakers
Rejection Pin Position
¡
¡
l
l
The rejection tabs logic shown above is for EntelliGuard™
breakers only. Rejection pin patterns on the breakers
prevent their installation into AKD-10™ equipment
compartments. Likewise, rejection pins in Entellisys
equipment compartments prevent installation of WavePro™
breakers.
¡
¡
¡
¡
¡
¡
l
¡
l
l
66
Entellisys Low Voltage Switchgear
Appendix B. Circuit Breaker Rejection Features
30 & 38-inch Wide Compartment
EG-32/40/50 breakers and fuse rollouts for Entellisys
switchgear include means to prevent improper interchange of
these 3200-, 4000-, and 5000-ampere sizes. Interference
hardware on each breaker and in its compartment, cause the
compartment to accept the correct breaker type and reject
breakers with lower ratings.
Interchangeability within and between frame sizes is
prevented by the rejection system of Fig. B-3. When the
wrong type breaker is inserted into a compartment, the
breaker pins and the equipment tabs interfere. Breakers may
be interchanged in one direction only.
Specifically:
1. Any EG-32 or EG-40 can be inserted into an EGS-32
compartment.
2. An EGX-32 or EGX-40 can be inserted into an EGH32 compartment.
3. An EGX-40 can be inserted into an EGX-32
compartment.
4. An EGF-40 can be inserted into an EGF-32
compartment.
5. An EGX-40 or EGF-40 may be inserted into an EGS40 compartment.
6. An EGX-50 or EGF-50 can be inserted into an EGS50 compartment.
Figure B-3 shows the rejection pin combinations for 3200A,
4000A, and 5000A breakers and fuse rollout elements.
EGX-32 shown
Circuit
Breaker
Type OFLO Volts A B C D E F G H J K L M N
EGS-32 N 600Vac
EGH-32 N 600Vac
EGX-32 N 600Vac
EGF-32 Y 600Vac
EGS-40 N 600Vac
EGX-40 N 600Vac
EGF-40 Y 600Vac
EGS-50 N 600Vac
EGX-50 N 600Vac
EGF-50 Y 600Vac
EG-32 FRE - 600Vac
EG-40 FRE - 600Vac
EG-50 FRE - 600Vac
l = Tab
¡ = No Tab
¡ ¡ ¡ l ¡ l ¡ ¡ ¡ ¡ l l l
¡ l ¡ l ¡ l ¡ ¡ ¡ ¡ l l l
¡ l l l ¡ l ¡ ¡ ¡ ¡ l l l
l ¡ l l ¡ l ¡ ¡ ¡ ¡ l l l
¡ ¡ ¡ l ¡ l ¡ l ¡ ¡ l l l
¡ l l l ¡ l ¡ l ¡ ¡ l l l
l ¡ l l ¡ l ¡ l ¡ ¡ l l l
¡ ¡ ¡ l ¡ l ¡ l ¡ l l l l
¡ l l l ¡ l ¡ l ¡ l l l l
l ¡ l l ¡ l ¡ l ¡ l l l l
l ¡ ¡ l ¡ ¡ ¡ ¡ l ¡ ¡ l l
¡ l l ¡ ¡ ¡ ¡ ¡ l ¡ ¡ l l
¡ l l ¡ ¡ ¡ ¡ ¡ l ¡ ¡ l l
Fig. B-3. Rejection tab pattern code for EG-32/40/50 breakers and FRE
Rejection Tab Position
67
Entellisys Low Voltage Switchgear
Appendix B. Circuit Breaker Rejection Features
The rejection tab logic shown in Fig. B-3 is for EntelliGuard
breakers only. Rejection pin patterns on the breakers prevent
their installation into AKD-10™ equipment compartments.
Likewise, rejection pins in Entellisys equipment
compartments prevent installation of WavePro™ breakers
Figure B-4 shows the EG-32/40/50 rejection system.
Fuse rollout (FRE) elements used in conjunction with the
EGF-32 (3200 ampere), EGF-40 (4000 ampere), or EGF-50
(5000 ampere) breakers employ the same type drawout
mechanism as their companion breakers and utilize the same
type of rejection system. Only a 3200-ampere fuse rollout
element may be installed in a 3200-ampere fuse rollout
compartment; only a 4000-ampere fuse rollout element may
be installed in a 4000-ampere fuse rollout compartment; only
a 5000-ampere fuse rollout element may be installed in a
5000-ampere fuse rollout compartment. The rejection pin
pattern is shown on Fig. B-3.
68
Entellisys Low Voltage Switchgear
Appendix C. Circuit Breaker Ratings
System Three-phase Short Circuit Rating RMS Symmetrical kA
The Shunt Trip allows the breaker to be opened remotely by
the EntelliGuard Messenger™. It is always provided on
electrically operated breakers. The catalog number and
operating voltage for the Shunt Trip are listed in Table D-1.
For installation instructions see DEH168 or DEH169.
Breaker Rating Catalog Number Voltage Rating
800A – 2,000A WPS1SF60120 120 Vac, 60 Hz
3,200A – 5,000A WPS1LF60120 120 Vac, 60 Hz
Table D-1. Catalog number and electrical rating for the Shunt Trip accessory.
The Shunt Trip causes the circuit breaker to trip when its coil
is energized. An “A” auxiliary switch, which is closed when
the breaker is closed, is in series with the Shunt Trip coil, as
illustrated in Figure D-1. The external tripping source is
connected to positions 5 and 7 on the secondary disconnect.
5
Figure D-1. Shunt Trip connections to the Secondary Disconnect.
Charging Motor
The Charging Motor provides a means of electrically charging
the springs that close the breaker. The Charging Motor is
available only as a factory-installed option. It is always
provided on electrically operated breakers.
The circuit breaker closing springs are charged automatically
when 120Vac is applied to terminals 8 and 17 of the
secondary disconnect. When the springs are fully charged, a
cutoff switch automatically de-energizes the motor. The
closing springs will recharge automatically after the breaker
closes.
Breaker Rating
800A – 2,000A 568B596G5 104–127
3,200A – 5,000A 568B596G2 104–127
Catalog
Number
Voltage
Range, Vac
Remote Close
The Remote Close accessory provides a means of remotely
closing the circuit breaker after the closing springs have
been charged. It is always provided on electrically operated
breakers. The catalog number and operating voltage for the
Remote Close accessory are listed in Table D-2. For
installation instructions see DEH-172 or DEH-173.
Breaker Rating Catalog Number Voltage Rating
800A – 2,000A WPRCSF60120 120 Vac, 60 Hz
3,200A – 5,000A WPRCLF60120 120 Vac, 60 Hz
Table D-2. Catalog number and operating voltage for the Remote Close
accessory.
A circuit breaker equipped with the Remote Close accessory
can be closed remotely by applying control voltage to
terminals 9 and 18 of the secondary disconnect.
The Remote Close accessory is continuously rated and has an
antipump feature that prevents a motor-operated breaker
from repeatedly closing if the closing signal is maintained.
The closing control voltage must be removed for 1–2.5
seconds and then reapplied for each breaker closure.
Open-Fuse Lockout
The Open-Fuse Lockout is supplied on integrally fused
breakers or when the breaker is used in combination with a
Fuse Rollout Element. When any fuse blows, the Open-Fuse
Lockout trips the breaker to prevent single-phasing. This
accessory is available only as a factory-installed option.
The Open-Fuse Lockout contains an individual trip solenoid
for each pole, connected directly across the fuse in that
phase. When any fuse blows, its solenoid is energized and
trips the breaker. An indicator shows which fuse has blown.
The breaker is mechanically trip-free and cannot be reclosed
until the Open-Fuse Lockout is reset.
The Open-Fuse Lockout is internally wired to the fuses on
800- and 1,600-ampere frame breakers. On 2,000-, 3,200-,
4,000-, and 5,000-ampere frame breakers, the Open-Fuse
Lockout is wired to the secondary disconnect as illustrated in
Figure D-3. The Open-Fuse Lockout connects to the fuses in
a Fuse Rollout Element through the secondary disconnect.
70
Entellisys Low Voltage Switchgear
1
3
65
1
3
21
NI Reset
3 2 16 19 4 5
NI Status
Appendix D. Circuit Breaker Accessory Devices
22
OFLO
Phase A
2
23
Figure D-3. Open-Fuse Lockout (OFLO) connections to the Secondary Disconnect
for EGS-20,-32,-40, and -50 breakers.
Bell Alarm with Lockout
The Bell Alarm with Lockout prevents closing of the breaker
after a protection trip until the Bell Alarm with Lockout is
reset. It contains a set of switch contacts to remotely indicate
that the circuit breaker has tripped because of a protection
trip. Catalog numbers for the Bell Alarm with Lockout
module and kit are given in Table D-3. For installation
instructions and trouble-shooting, see DEH-238 or DEH-239.
Breaker Rating Kit Catalog
800A – 2,000A EGBLALMSFKIT
3,200A – 5,000A EGBLALMLFKIT
Table D-3. Catalog numbers for the Bell Alarm with Lockout module and kit.
The accessory is activated and its status circuit changes state
whenever the breaker is tripped by an overcurrent, ground
fault, or protective relay function via the EntelliGuard
Messenger™. The EntelliGuard Messenger continuously
monitors the state of the status circuit. The connections of
the Bell Alarm with Lockout to the secondary disconnect are
illustrated in Figure D-4. A trip caused by the manual OPEN
button or by the Shunt Trip does not activate the Bell Alarm
with Lockout.
The Bell Alarm with Lockout must be reset by manually
depressing the target on the breaker escutcheon. This will
return the Bell Alarm with Lockout status contact to its
normal configuration and allow the breaker to be closed.
24
Phase B
4
25
Number
OFLO
26
OFLO
Phase C
27
Module Catalog
Number
EGBLALMRPLC
Figure D-4. Bell Alarm with Lockout connections to the Secondary Disconnect.
14
Lockout
Trip Coil
2
6
The contact is shown in the reset state.
16
Status
4
Contact
19
Network Interlock
The Network Interlock provides a means of locking out a
breaker to coordinate its operation with other breakers in the
distribution network. When activated by the EntelliGuard
Messenger™, the Network Interlock prevents the breaker
from closing. When the EntelliGuard Messenger issues a
reset signal, the breaker is able to close either remotely or
locally. The Network Interlock contains a set of switch
contacts to remotely indicate the state of the lockout and,
thus, whether or not the breaker can be closed. Catalog
numbers and the operating voltage for the Network Interlock
are listed in Table D-4. For installation instructions and
trouble-shooting, see DEH-41119
Breaker Rating Kit Catalog
800A – 2,000A EGNTWKSFKIT EGNTWKSFRPLC
3,200A – 5,000A EGNTWKLFKIT EGNTWKLFRPLC
Table D-4. Catalog numbers and control voltage for the Network Interlock
The Network Interlock consists of a trip circuit, a reset
circuit, and a status circuit. The device connections to the
secondary disconnect are shown in Figure D-5. Note that a
Bell Alarm with Lockout and a Network Interlock cannot be
installed concurrently in a breaker.
Figure D-5. Network Interlock connections to the Secondary Disconnect
15
1
NI Set
Coil
Number
accessory.
20
Coil
Module Catalog
Number
Contact
71
Entellisys Low Voltage Switchgear
Appendix E. Circuit Breaker Weights
Net Weight, lb. (kg) Device Manual Electrical
EGS/EGH/EGX-08
EGF-08
EGS/EGH-16
EGF-16
EGS-20
EG-32
EG-40
EG-50
2000 Ampere
Fuse Rollout
3200-Ampere
Fuse Rollout
4000-Ampere
Fuse Rollout
5000-Ampere
Fuse Rollout
Table E-1. Circuit Breaker/Fuse Rollout Element Weights
188 (86)
233 (106)
198 (90)
243 (111)
203 (92)
455 (207)
560 (255)
600 (273)
250 (114)
350 (159)
400 (182)
450 (205)
193 (88)
238 (108)
203 (92)
248 (113)
208 (95)
470 (214)
575 (261)
615 (280)
-
-
-
-
Appendix F. Circuit Breaker Repetitive Duty Data
General
Circuit breakers are designed primarily to perform the
function of circuit interruption under short-circuit conditions.
Nevertheless modern circuit breaker mechanisms are capable
of many operations under full-load operation and in-rush
Circuit Breaker
Frame Size
(Amperes)
800
1600
2000
3000
4000
5000
*Refer to lettered paragraphs under NOTES.
Number of
Operations
Between
Servicing
1750
500
500
250
250
250
Rated Continuous
(1) (2) (3) (4) (5)
(6) (7) (8) and (10)
Table F-1. Repetitive Duty and Normal Maintenance
Notes
Power operated circuit breakers, when operating under usual
service conditions, shall be capable of operating the number
of times specified in Table F-1. The operating conditions and
conditions such as encountered in motor starting
applications. Industry standards have been established for
the minimum performance that is indicated in Table F-1.
With adequate maintenance, GE breakers can be expected to
exceed the standards.
Number of
Operations
Current
Switching*
2800
800
800
400
400
400
Number of
Operations
No-Load
Closing and
Opening*
(1) (2) (3) (4)
(5) (6) and (7)
9700
3200
3200
1100
1100
1100
Number of
Operations
In-Rush
Current
Switching*
(3) (4) (5) (6))
(7) (9) and (10)
1400
400
400
—
—
—
the permissible effect of such operations upon the breaker are
given in the following lettered paragraphs. For each column,
all paragraphs listed in the column heading must be given
consideration.
72
Entellisys Low Voltage Switchgear
Appendix F. Circuit Breaker Repetitive Duty Data
This standard applies to all parts of a circuit breaker that
function during normal operation. It does not apply to other
parts, such as overcurrent tripping devices, that function only
during infrequent abnormal circuit conditions.
1. Servicing consists of adjusting, cleaning, lubricating,
tightening, etc., as recommended by the manufacturer.
When current is interrupted, dressing of contacts may
be required as well. The operations listed are on the
basis of servicing at intervals of 6 months or less.
2. When closing and opening no-load.
3. With rated control voltage applied.
4. Frequency of operation not to exceed 20 in 10 minutes
or 30 in an hour. Rectifiers or other auxiliary devices
may further limit the frequency of operation.
5. Servicing at no greater intervals than shown in Column
2 of Table F-1.
6. No functional parts should have been replaced during
the listed operations.
7. The circuit breaker should be in a condition to carry its
rated continuous current at rated maximum voltage and
perform at least one opening operation at rated shortcircuit current. After completion of this series of
operations, functional part replacement and general
servicing may be necessary.
8. When closing and opening current up to the continuous
current rating of the circuit breaker at voltages up to
the rated maximum voltage and at 85% power factor or
higher.
9. When closing currents up to 600% and opening currents
up to 100% (80% power factor or higher) of the
continuous current rating of the circuit breaker at
voltages up to the rated maximum voltage.
When closing currents up to 600% and opening currents
up to 600% (50% power factor or less) of the continuous
current rating of the circuit breaker at voltages up to
rated maximum voltage, the number of operations
shown shall be reduced to 10% of the number listed.
10. If a fault operation occurs before the completion of the
listed operations, servicing is recommended and
possible functional part replacements may be necessary,
depending on previous accumulated duty, fault
magnitude, and expected future operations.
Appendix G. Fuses for EGF-08/16 and FRE Elements
NEMA
Fuse Class
600V, 60 Hz 08 16 Rating Fuse Cat. No.
“J”
“L”
Welder Limiter x
Special — x 2500 A4BQ2500GE
*Mounting adapter required.
Ampere Fuse Size Fuse Cat. No’s
Rating Min. Max. Gould Shawmut
3200
4000
5000
A4BY4000-55BA
Breaker Type
x
x
x
x
x
x
x
x
x
x
—
x
---
EGF
—
--x
x
x
x
x
x
x
x
x
x
x
x
Ampere
Table G-1. Fuses for Integrally Fused EntelliGuard Breakers
2000A
2000A
2000A
4000A
5000A
5000A
Table G-2. Fuses for Roll-out Fuse Carriages
73
300*
350*
400*
450
500
600
800
1000
1200
1600
2000
800
1600
2000
Gould
Shawmut
A4J300
A4J350
A4J400
A4J450
A4J500
A4J600
A4BY800
A4BY1000BG
A4BY1200BG
A4BY1600BG
A4BY2000
A4BX800
A4BX1600BG
A4BX2000
A4BY2000-55BA
A4BQ2500-55BA
A4BY3000-55BA
A4BY5000-55BA
g
GE Consumer & Industrial
General Electric Company
510 Agency Road, West Burlington, IA 52655