GE Industrial Solutions Entellisys User Manual

GE
Entellisys™ Low Voltage Switchgear
Integrator’s Guide
DEH-232
Warnings, Cautions, and Notes as used in this publication
Warnings
Warning notices are also used for situations in which inattention or lack of equipment knowledge could cause either personal injury or damage to equipment.
Cautions
CAUTION: Caution notices are used for situations in which equipment might be damaged if care is not taken.
Notes
NOTE: Notes call attention to information that is especially significant to understanding and operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein does not cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described in here that are not present in all hardware and software systems. GE Consumer & Industrial assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Consumer & Industrial makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.
Entellisys™, EntelliGuard™, and FlexLogic™ are trademarks of the General Electric Company.
Modbus RTU is a registered trademark of AEG Schneider Automation.
©Copyright 2005 General Electric All Rights Reserved
How to contact us
Please have your Entellisys System Summary # and Sub # ready when calling. This information can be found on the Entellisys HMI on the System Health screen by clicking the Job Info button.
Post Sales Service GE Switchgear 510 Agency Road West Burlington, IA 52655
Phone (toll free): 1-888-437-3765
Additional information:
www.entellisys.com/support

Contents

1 Integrator’s Guide
1.1 Modbus® protocol implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1.2 Physical layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1.3 Data link layer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.1.4 CRC-16 Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.5 Supported function codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.1.5.1 Function Code 03H/04H – Read Actual Values or Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.1.5.2 Function Code 05H – Execute Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1.5.3 Function Code 06H – Store Single Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.1.5.4 Function Code 10H – Store Multiple Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.1.5.5 Exception responses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.1.6 File transfers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.1.6.1 Obtaining CPU files using Modbus protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.1.6.2 Modbus password operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.2 Interfacing to the Alarm Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Contents 5
6 Contents

1 Integrator’s Guide

1.1 Modbus® protocol implementation

1.1.1 Introduction

The CPU supports a number of communications protocols to allow connection to the HMI computer, as well as other equipment which includes personal computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus basic protocol supported. Modbus is available via ethernet as specified by the Modbus/TCP specification. Note that:
The CPU always acts as a slave device, meaning that it never initiates communications; it only listens and responds to requests issued by a master computer.
For Modbus, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitoring, programming, and control functions using read and write register commands.
The CPU will support a maximum of 8 concurrent Modbus sessions. Four sessions are reserved for use by HMI computers. A remote device that attempts to connect when all sessions are in use will receive a response message indicating the number of maximum connections has been exceeded. If a remote device does not make a request within 30 seconds, the session will be timed out and made available to the next device that establishes a session.
®
RTU protocol is the most

1.1.2 Physical layer

The Modbus RTU protocol is hardware-independent so that the physical layer can be any of a variety of standard hardware configurations. The CPU includes a faceplate (front panel) 100BaseT Ethernet port. Data flow is auto-configuring full or half-duplex. Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop bit, and possibly 1 parity bit. This produces a 10 or 11 bit data frame. The master device in any system must know the address of the slave device with which it is to communicate. In the case of ModbusTCP communications, the CPU will not act on a request from a master if the address in the request does not match the CPU’s slave address. A single setting selects the slave address used for ModbusTCP. The default slave address for a CPU is 1.
Modbus® protocol implementation 7

1.1.3 Data link layer

Communications takes place in packets, which are groups of asynchronously framed byte data. The master transmits a packet to the slave and the slave responds with a packet. The end of a packet is marked by ‘dead-time’ on the communications line. The following describes general format for both transmit and receive packets. For exact details on packet formatting, see the subsequent sections describing each function code.
MODBUS PACKET FORMAT
DESCRIPTION SIZE
SLAVE ADDRESS 1 byte
FUNCTION CODE 1 byte
DATA N b ytes
CRC 2 bytes
DEAD TIME 3.5 bytes transmission time
SLAVE ADDRESS
This is the address of the slave device that is intended to receive the packet sent by the master and perform the desired action. Only the addressed slave will respond to a packet that starts with its address. Note that since Modbus/TCP also relies on a correct IP address to receive the packet, and each CPU responds as a single device, it is generally not necessary to change the Modbus address of the device.
FUNCTION CODE
This is one of the supported function codes of the unit which tells the slave what action to perform. See Supported function codes on page 10
for complete details. An exception response from the slave is indicated by setting the high order bit of the function code in the response packet. See Exception responses on page 15
for further details.
DATA
This will be a variable number of bytes depending on the function code. This may include actual values, settings, or addresses sent by the master to the slave or by the slave to the master.
CRC
This is a two byte error checking code. The RTU version of Modbus includes a 16-bit cyclic redundancy check (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet thus preventing any erroneous operations. See CRC-16 Algorithm on page 9
for a description of how to calculate the CRC.
Integrator’s Guide8

1.1.4 CRC-16 Algorithm

The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one continuous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial (11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, most significant byte first. The resulting packet including CRC, when divided by the same polynomial at the receiver, will give a zero remainder if no transmission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
CRC-16 ALGORITHM
SYMBOLS --> data transfer
A 16-bit working register
Alow low order byte of A
Ahigh high order byte of A
CRC 16-bit CRC-16 result
i,j loop counters
(+) logical EXCLUSIVE-OR operator
N total number of data bytes
Di i-th data byte (i = 0 to N-1)
G 16-bit characteristic polynomial = 1010000000000001 (binary) with
MSbit dropped and bit order reversed
shr (x) right shift operator (th LSbit of x is shifted into a carry flag, a ‘0’ is
shifted into the MSbit of x, all other bits are shifted right one location)
ALGORITHM:
1. FFFF (hex) --> A
2. 0 --> i
3. 0 --> j
4. Di (+) Alow --> Alow
5. j + 1 --> j
6. shr (A)
7. Is there a carry? No: go to 8 Yes: G (+) A --> A and continue.
8. Is j = 8? No: go to 5 Yes: continue
9. i + 1 --> i
10. Is i = N? No: go to 3 Yes: continue
11. A --> CRC
Modbus® protocol implementation 9

1.1.5 Supported function codes

Modbus officially defines function codes from 1 to 127 though only a small subset is generally needed. The CPU supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.
1.1.5.1 Function Code 03H/04H – Read Actual Values or Settings
This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay. Data registers are always 16 bit (two byte) values transmitted with high order byte first. The maximum number of registers that can be read in a single packet is 125. See the MODBUS MEMORY MAP table on page 17 for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h, the CPU interpretation allows either function code to be used for reading one or more consecutive data registers. The data starting address will determine the type of data being read. Function codes 03h and 04h are therefore identical. The following table shows the format of the master and slave packets. The example shows a master device requesting 3 register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the values 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively.
FUNCTION CODE MODBUS DEFINITION CPU DEFINITION
HEX DEC
03 3 Read Holding Registers Read Actual Values or Settings
04 4 Read Holding Registers Read Actual Values or Settings
05 5 Force Single Coil Execute Operation
06 6 Preset Single Register Store Single Setting
10 16 Preset Multiple Registers Store Multiple Settings
Master and Slave Device Packet Transmission Example
MASTER TRANSMISSION
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 04
DATA STARTING ADDR - hi 40
DATA STARTING ADDR - lo 50
NUMBER OF REGISTERS - hi 00
NUMBER OF REGISTERS - lo 03
CRC - lo A7 DATA #2 - lo A7
CRC - hi 4A DATA #3 - hi 4A
Integrator’s Guide10
SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 04
BYTE COUNT 06
DATA #1 - h i 00
DATA #1 - lo 28
DATA #2 - h i 01
DATA #2 - lo 2C
DATA #3 - h i 00
DATA #3 - lo 00
CRC - lo 0D
CRC - hi 60
1.1.5.2 Function Code 05H – Execute Operation
This function code allows the master to perform various operations in the CPU.
The following table shows the format of the master and slave packets. The example shows a master device requesting the slave device 11H (17 dec) to perform a reset. The hi and lo CODE VALUE bytes always have the values ‘FF’ and ‘00’ respectively and are a remnant of the original Modbus definition of this function code.
Master and Slave Device Packet Transmission Example
MASTER TRANSMISSION
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 05
OPERATION CODE - hi 00
OPERATION CODE - lo 01
CODE VALUE - hi FF
CODE VALUE - lo 00
CRC - lo DF
CRC - hi 6A
Modbus® protocol implementation 11
SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 05
OPERATION CODE - hi 00
OPERATION CODE - lo 01
CODE VALUE - hi FF
CODE VALUE - lo 00
CRC - lo DF
CRC - hi 6A
Integrator’s Guide12
1.1.5.3 Function Code 06H – Store Single Setting
This function code allows the master to modify the contents of a single setting register in a CPU. Setting registers are always 16-bit (two byte) values transmitted high-order byte first . The following table shows the format of the master and slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device 11h (17 dec).
Master and Slave Device Packet Transmission Example
MASTER TRANSMISSION
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 06
DATA STARTING ADDR - hi 40
DATA STARTING ADDR - lo 51
DATA - hi 00
DATA - lo C8
CRC - lo CE
CRC - hi DD
SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 06
DATA STARTING ADDR - hi 40
DATA STARTING ADDR - lo 51
DATA - hi 00
DATA - lo C8
CRC - lo CE
CRC - hi DD
Modbus® protocol implementation 13
1.1.5.4 Function Code 10H – Store Multiple Settings
This function code allows the master to modify the contents of a one or more consecutive setting registers in a CPU. Setting registers are 16-bit (two byte) values transmitted high-order byte first. The maximum number of setting registers that can be stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to slave device 11h (17 dec).
Master and Slave Device Packet Transmission Example
MASTER TRANSMISSION
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 10
DATA STARTING ADDR-hi 40
DATA STARTING ADDR-lo 51
NUMBER OF SETTINGS-hi 00
NUMBER OF SETTINGS-lo 02
BYTE COUNT 04
DATA #1 - h i 00
DATA #1 - lo C8
DATA #2 - h i 00
DATA #2 - lo 01
CRC – lo 12
CRC – hi 62
Integrator’s Guide14
SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 10
DATA STARTING ADDR - hi 40
DATA STARTING ADDR - lo 51
NUMBER OF SETTINGS - hi 00
NUMBER OF SETTINGS - lo 02
CRC - lo 07
CRC - hi 64
1.1.5.5 Exception responses
Programming or operation errors usually happen because of illegal data in a packet . These errors result in an exception response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order bit of the function code set to 1. The following table shows the format of the master and slave packets. The example shows a master device sending the unsupported function code 39h to slave device 11.
Master and Slave Device Packet Transmission Example
MASTER TRANSMISSION
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE 39
CRC - low order byte CD
CRC - high order byte F2
SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11
FUNCTION CODE B9
ERROR CODE 01
CRC - low order byte 93
CRC - high order byte 95
Modbus® protocol implementation 15

1.1.6 File transfers

1.1.6.1 Obtaining CPU files using Modbus protocol
The CPU has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of files from the unit. The Modbus registers that implement file transfer are found in the “Modbus File Transfer (Read/Write)” and “Modbus File Transfer (Read Only)” modules, starting at address 030Eh in the Modbus Memory Map. To read a file from the CPU, use the following steps:
1. Write the filename to the “Name of file to read” register using a write multiple registers
command. If the name is shorter than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case sensitive.
2. Repeatedly read all the registers in “Modbus File Transfer (Read Only)” using a read multiple
registers command. It is not necessary to read the entire data block, since the CPU will remember which was the last register read. The “position” register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have read so far. The “size of...” register indicates the number of bytes of data remaining to read, to a maximum of 244.
3. Keep reading until the “size of...” register is smaller than the number of bytes you are
transferring. This condition indicates end of file. Discard any bytes you have read beyond the indicated block size.
4. If you need to re-try a block, read only the “size of...” and “block of data”, without reading the
position. The file pointer is only incremented when you read the position register, so the same data block will be returned as was read in the previous operation. On the next read, check to see if the position is where you expect it to be, and discard the previous block if it is not (this condition would indicate that the CPU did not process your original read request). The CPU retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus connections.
a. Obtaining files from the CPU using other protocols
All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for example, TFTP).
b. Reading event recorder files
To read the entire event recorder contents in ASCII format (the only available format), use the following filename:
•EVT.TXT
c. Reading fault report files
The file name for fault report data is faultReport#####.txt . The ##### refers to the fault report record number. This number is identical to the event record number associated with the fault report. A request for a non-existent fault report file will yield file with no data below the header.
d. Reading waveform capture files
Waveform records comply with COMTRADE 1999 format (IEEE Std C37.111-1999). The file names as required by the standard for waveform capture data are wfc#####.dat and wfc#####.cfg. The ##### refers to the waveform record number. Note that this number is not the same as the event number cited in the case of the fault report above. If an event has a waveform capture associated with it, the waveform number will be shown in the WF Number field as indicated in the header of the event log.
Integrator’s Guide16
1.1.6.2 Modbus password operation
The COMMAND password is set up at memory location 0458h. Storing a value of “0” removes COMMAND password protection. When reading the password setting, the encrypted value (zero if no password is set) is returned. COMMAND security is required to change the COMMAND password.
Similarly, the SETTING password is set up at memory location 045Ah. To gain COMMAND level security access, the COMMAND password must be entered at memory location 045Ch. To gain SETTING level security access, the SETTING password must be entered at memory location 045Eh. The entered SETTING password must match the current SETTING password setting, or must be zero, to change settings or download firmware.
COMMAND and SETTING passwords each have a 30-minute timer. Each timer starts when you enter the particular password, and is restarted whenever you “use” it. For example, writing a setting restarts the SETTING password timer and writing a command register or forcing a coil restarts the COMMAND password timer. The value read at memory location 0460h can be used to confirm whether a COMMAND password is enabled or disabled (0 for Disabled). The value read at memory location 0461h can be used to confirm whether a SETTING password is enabled or disabled.
COMMAND or SETTING password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be reentered after disconnecting and reconnecting on TCP/IP.
Modbus® protocol implementation 17

1.2 Interfacing to the Alarm Handler

The set of registers beginning at 0648h provides the means to interface to each CPU’s Alarm Handler functionality. Each pair of 32-bit values represent the current state (read only) and the acknowledge setting (read/write) for each alarm type. Each value represents the states for all of the circuit breakers in the system as denoted in Format Code F722, one bit for each. A 1 in the bit field position for a given circuit breaker in the state register indicates that the alarm condition is currently active, while a 0 indicates the condition is not currently active.
When a condition passes from inactive to active, the corresponding ACK bit in the next register will be set to 1. At this point an external program may acknowledge the alarm by writing a 0 to that bit location. It is important for the external program to first read the ACK register and mask the new value such that the states represented by the other bits remain intact. The following state table describes how the HMI interfaces with the CPU to update its indicators.
Figure 1-1 Alarm state transition diagram
Start
System Initialization
ACK: 0
Status: 0
HMI Color:
Green
HMI
ACK
Alarm Condition
Condition
Goes Normal
Occurs
HMI
ACK
ACK: 0
Status: 1
HMI Color:
Solid
Red
ACK: 1
Status: 0
HMI Color:
Yellow
ACK: 1
Status: 1
HMI Color:
Blinking
Red
Condition
Goes Normal
Condition
Recurs
Alarm State Transition Diagram
Integrator’s Guide18
Modbus Memory Map
NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the Range and/or Step imply a greater precision. In these cases, it is necessary to divide the returned value by 10 for a step of "0.1" or "0.5"; by 100 for a step of ".01"; and so on. Similarly, it is necessary to multiply by these factors prior to writing a settings value. This note does not apply to any step value greater than 1 (a step of "10" does not require a multiplier, for example). This note also does not apply to values returned in floating point format. See the format codes at the end of the map for more information.
NOTE: Discrete I/O output state registers (Contact Output x State – register range from x9180 to x91FF and Contact Output States – register range from xB256 to 0xB25D) contain correct information only when FlexLogic Active register (x0034) contains value 1 (yes).
Addr Register Name Range Units Step Format Factory Default
Product Information (Read Only)
0000 Product Type
0001 Serial Number 0009 External Ethernet MAC Address 000C Reserved (3 items) 000F CPU Hardware Version 0010 CPU Firmware Version 0011 CPU Firmware Boot Code Version 0012 Build Date 0026 Synchronizer Board Status 0027 Synchronizer Board Frequency Setting 0028 Last Energy Clear Date 002A Last CPU Commissioned Date 002C Expected Node Protocol Version 002D Summary Number 0033 Line Up 0034 FlexLogic Active 0035 Reserved (203 items)
0 to 2
---
---
--­0 to 655.35 0 to 655.35 0 to 655.35
---
0 to 1
50 to 60
0 to 4294967295
0 to 4294967295
0 to 655.35
---
0 to 99
0 to 1
---
--- 1 F716
--- --- F203 "0"
--- --- F072 0
--- --- F001 0
--- 0.01 F001 100
--- 0.01 F001 100
--- 0.01 F001 100
--- --- F200 "0"
--- 1 F102 0 (Disabled) Hz 10 F001 60
--- 1 F050 0
--- 1 F050 0
--- 0.01 F001 0
--- --- F205 "0"
--- 1 F001 1
--- 1 F126 0 (No)
--- --- F001 0
0 (Low Voltage
Switchgear)
Installation (Read/Write Setting)
0100 CPU ID 0101 CPU Commissioned 0102 CPU Name 0116 System Frequency 0117 Phase Rotation 0118 Reserved (232 items)
Clock (Read/Write Command)
0200 RTC Set Time
Clock (Read Only)
0202 Date Time Changed 0204 Reserved (8 items)
0 to 1 0 to 1
---
50 to 60
0 to 1
---
0 to 4294967295
0 to 4294967295
---
--- 1 F717 0 (CPU A)
--- 1 F102 0 (Disabled)
--- --- F200 "UNNAMED" Hz 10 F001 60
--- 1 F106 0 (ABC)
--- --- F001 0
--- 1 F050 0
--- 1 F050 0
--- --- F001 0
19
Communications (Read/Write Setting)
0210 External Ethernet IP Address 0212 External Ethernet IP Subnet Mask 0214 External Ethernet Gateway IP Address 0216 Reserved (205 items)
0 to 4294967295
0 to 4294963200
0 to 4294967295
Event Recorder (Read Only)
0308 Events Since Last Clear 030A Number of Available Events 030C Event Recorder Last Cleared Date
0 to 4294967295
0 to 4294967295
0 to 4294967295
Modbus File Transfer (Read/Write)
030E Name of file to read
Modbus File Transfer (Read Only)
0336 Character position of current block within file 0338 Size of currently-available data block 0339 Block of data from requested file (122 items)
0 to 4294967295
Modbus File Transfer Area 2 (Read/Write)
03B3 Name of file to read
Modbus File Transfer Area 2 (Read Only)
03DB Character position of current block within file
03DD Size of currently-available data block
03DE Block of data from requested file (122 items)
0 to 4294967295
1 to 254
---
0 to 65535 0 to 65535
---
0 to 65535 0 to 65535
--- 1 F003 3232235876
--- 1 F003 4294967040
--- 1 F003 0
--- 1 F001 1
--- 1 F003 0
--- 1 F003 0
--- 1 F050 0
--- --- F204 (none)
--- 1 F003 0
--- 1 F001 0
--- 1 F001 0
--- --- F204 (none)
--- 1 F003 0
--- 1 F001 0
--- 1 F001 0
Passwords (Read/Write)
045C Command Password Entry
045E Setting Password Entry
0 to 4294967295
0 to 4294967295
--- 1 F003 0
--- 1 F003 0
Passwords (Read Only)
0460 Command Password Status 0461 Setting Password Status
0 to 1 0 to 1
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
Zone Manager (Read Only)
04E4 Current Topology State
0 to 255
--- 1 F001 0
Zone Manager (Read/Write Setting)
04E5 Maintenance Mode Setting
0 to 1
--- 1 F102 0 (Disabled)
Zone Manager (Read Only)
04E6 Current Zone1 Topology 04E7 Current Zone2 Topology 04E8 Current Zone3 Topology 04E9 Current Zone4 Topology 04EA Zone Manager Reserved (22 items)
0 to 255 0 to 255 0 to 255 0 to 255
0 to 65535
--- 1 F001 1
--- 1 F001 1
--- 1 F001 1
--- 1 F001 1
--- 1 F001 1
Event Recorder Commands (Read/Write Command)
0500 Event Recorder Clear Command
0 to 1
--- 1 F126 0 (No)
Energy Commands (Read/Write Command)
0501 Energy Clear Command
Demand (Read/Write Setting)
0504 Demand Subinterval Length 0505 Demand Subintervals Per Interval
20
0 to 1
1 to 60 1 to 15
--- 1 F126 0 (No)
--- 1 F001 1
--- 1 F001 1
Demand (Read/Write Command)
0506 Demand Reset All Command
0 to 1
--- 1 F126 0 (No)
Demand (Read Only)
0507 Number Of Demand Resets All 0509 Last Demand Reset All DateTime
0 to 4294963200
0 to 4294967295
--- 1 F003 0
--- 1 F050 0
Demand (Read/Write Command)
050B Demand Log Clear All Command
0 to 1
--- 1 F126 0 (No)
Demand (Read Only)
050C Demand Log Last Cleared All Date
050E Demand Reserved (10 items)
0 to 4294967295
0 to 65535
--- 1 F050 0
--- 1 F001 0
Waveform Capture (Read Only)
0518 Number WF Records Available
0 to 65535
--- 1 F001 0
Waveform Capture (Read/Write Command)
0519 Waveform Clear Command
0 to 1
--- 1 F126 0 (No)
Waveform Capture (Read Only)
051A Waveform Last Clear Date
0 to 4294967295
--- 1 F050 0
Waveform Capture (Read/Write Command)
051C Waveform Trigger Command
0 to 1
--- 1 F126 0 (No)
Waveform Capture (Read/Write Setting)
051D Waveform Trigger Mode
051E Waveform Trigger Position
Waveform Capture (Read Only)
051F Waveforms Since Last Clear 0523 Reserved (8 items)
0 to 4294967295
Preventive Maintenance (Read/Write Setting)
052B Load Life Rating 800A 052C Load Life Rating 1600A 052D Load Life Rating 2000A
052E Load Life Rating 3200A 052F Load Life Rating 4000A 0530 Load Life Rating 5000A 0531 Mechanical_Life_Rating_800A 0532 Mechanical_Life_Rating_1600A 0533 Mechanical_Life_Rating_2000A 0534 Mechanical_Life_Rating_3200A 0535 Mechanical_Life_Rating_4000A 0536 Mechanical_Life_Rating_5000A 0537 Load Life Max Current 800A 0538 Load Life Max Current 1600A
0539 Load Life Max Current 2000A 053A Load Life Max Current 3200A 053B Load Life Max Current 4000A 053C Load Life Max Current 5000A
0 to 1
0 to 119
0 to 65535
0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535
1 to 50 1 to 50 1 to 50 1 to 50 1 to 50 1 to 50
--- 1 F118 0 (Automatic Overwrite)
Half
Cycles
F001 60
1
--- 1 F003 0
--- 1 F001 0
--- 1 F001 2800
--- 1 F001 1200
--- 1 F001 1000
--- 1 F001 600
--- 1 F001 500
--- 1 F001 400
--- 1 F001 12500
--- 1 F001 4000
--- 1 F001 4000
--- 1 F001 1500
--- 1 F001 1500
--- 1 F001 1500
--- 1 F001 15
--- 1 F001 15
--- 1 F001 15
--- 1 F001 13
--- 1 F001 9
--- 1 F001 7
21
Hardware Information (Read Only)
053D Flash Lifetime
Source Vectors (Read/Write Setting)
0600 Expected Nodes x State
0602 Source Node Identifier LED x State
0604 Node Setting Changed x State
Source Vectors (Read Only)
0630 Nodes Communicating x State
0632 Nodes Commissioned x State
0634 Duplicate Nodes x State
0636 Node Internal Diagnostics x State
0638 Node System Diagnostics x State 063A Node Hardware Diagnostics x State 063C Node Reflected CPU Diagnostics x State
063E Breaker Contact Position x State
0640 Breaker Primary Connection x State
0642 Breaker Lockout x State
0644 Summations Suspended x State
0646 Breaker Tripped x State
0648 Undervoltage Trip Alarm State
1 to 10
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
--- 1 F001 1
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
Source Vectors (All Ack Vectors are Read/Write Setting; All State Vectors are Read Only)
064A Undervoltage Trip Alarm Ack 064C Undervoltage Alarm State
064E Undervoltage Alarm Ack
0650 Overvoltage Trip Alarm State
0652 Overvoltage Trip Alarm Ack
0654 Overvoltage Alarm State
0656 Overvoltage Alarm Ack
0658 Phase Loss Trip Alarm State 065A Phase Loss Trip Alarm Ack 065C Phase Loss Alarm State
065E Phase Loss Alarm Ack
0660 Reverse Power Trip Alarm State
0662 Reverse Power Trip Alarm Ack
0664 Reverse Power Alarm State
0666 Reverse Power Alarm Ack
0668 High Current Alarm State 066A High Current Alarm Ack 066C Underfrequency Trip Alarm State
066E Underfrequency Trip Alarm Ack
0670 Underfrequency Alarm State
0672 Underfrequency Alarm Ack
0674 Overfrequency Trip Alarm State
0676 Overfrequency Trip Alarm Ack
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
22
0678 Overfrequency Alarm State 067A Overfrequency Alarm Ack 067C High Resistance Ground Fault Alarm State
067E High Resistance Ground Fault Alarm Ack
0680 Breaker Open Failed Alarm State
0682 Breaker Open Failed Alarm Ack
0684 Long Time Overcurrent Trip Alarm State
0686 Long Time Overcurrent Trip Alarm Ack
0688 Short Time Overcurrent Trip Alarm State 068A Short Time Overcurrent Trip Alarm Ack 068C Ground Fault Trip Alarm State
068E Ground Fault Trip Alarm Ack
0690 Ground Fault Alarm State
0692 Ground Fault Alarm Ack
0694 Analog IOC Trip Alarm State
0696 Analog IOC Trip Alarm Ack
0698 IOC Trip Alarm State 069A IOC Trip Alarm Ack 069C Node Control Power Lost State
069E Node Control Power Lost Ack 06A0 Node Communication Lost State 06A2 Node Communication Lost Ack 06A4 Breaker Load Life 50 State 06A6 Breaker Load Life 50 Ack 06A8 Breaker Load Life 75 State 06AA Breaker Load Life 75 Ack 06AC Breaker Load Life 90 State
06AE Breaker Load Life 90 Ack 06B0 Breaker Accum Service Alarm State 06B2 Breaker Accum Service Alarm Ack 06B4 Breaker Mechanical Life 12 5 State 06B6 Breaker Mechanical Life 12 5 Ack 06B8 Breaker Mechanical Life 25 State 06BA Breaker Mechanical Life 25 Ack 06BC Breaker Mechanical Life 37 5 State
06BE Breaker Mechanical Life 37 5 Ack 06C0 Breaker Mechanical Life 50 State 06C2 Breaker Mechanical Life 50 Ack 06C4 Breaker Mechanical Life 62 5 State 06C6 Breaker Mechanical Life 62 5 Ack 06C8 Breaker Mechanical Life 75 State 06CA Breaker Mechanical Life 75 Ack 06CC Breaker Mechanical Life 87 5 State
06CE Breaker Mechanical Life 87 5 Ack 06D0 Breaker Mechanical Life 100 State
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
23
06D2 Breaker Mechanical Life 100 Ack 06D4 Bus Differential Trip Alarm State 06D6 Bus Differential Trip Alarm Ack 06D8 Bus Differential Alarm State 06DA Bus Differential Alarm Ack 06DC Multi Source Ground Fault Trip Alarm State 06DE Multi Source Ground Fault Trip Alarm Ack
06E0 Multi Source Ground Fault Alarm State
06E2 Multi Source Ground Fault Alarm Ack
06E4 Hardware Synch Card Lost State
06E6 Hardware Synch Card Lost Ack
06E8 Reserved
06EA Compartment ID Button Missing Alarm State
06EC Reserved
06EE Compartment ID Button Missing Alarm Ack
06F0 Control Alarm State
06F2 Control Alarm Ack
06F4 Redundant CPU Node Comm Loss State
06F6 Redundant CPU Node Comm Loss Ack
06F8 Redundant CPU Hardware Synch Loss State
06FA Redundant CPU Hardware Synch Loss Ack
06FC Discrete IO Misconfigured State
06FE Discrete IO Misconfigured Ack
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
--- 1 F722 0
Voltage (Read Only) (30 modules)
1000 Phase AG Voltage RMS
1002 Phase BG Voltage RMS
1004 Phase CG Voltage RMS
1006 Phase AB or AC Voltage RMS
1008 Phase BC or BA Voltage RMS 100A Phase CA or CB Voltage RMS 100C Reserved (50 items)
103E 107C 10BA
10F8
1136
1174 11B2
11F0
122E 126C 12AA
12E8
1326
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
---
V 0.001 F060 0 V 0.001 F060 0 V 0.001 F060 0 V 0.001 F060 0 V 0.001 F060 0 V 0.001 F060 0
--- --- F001 0
24
1364 13A2
13E0
141E 145C 149A 14D8
1516
1554
1592 15D0
160E 164C 168A 16C8
1706
...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Current (Read Only) (30 modules)
1800 Phase A Current RMS
1802 Phase B Current RMS
1804 Phase C Current RMS
1806 Neutral Current RMS
1808 Ground Current RMS 180A Reserved (28 items)
1826 184C
1872
1898
18BE
18E4 190A
1930
1956 197C 19A2 19C8
19EE 1A14 1A3A 1A60 1A86 1AAC 1AD2
1AF8
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
---
A 0.001 F060 0 A 0.001 F060 0 A 0.001 F060 0 A 0.001 F060 0 A 0.001 F060 0
--- --- F001 0
25
1B1E 1B44 1B6A 1B90 1BB6
1BDC
1C02 1C28
1C4E
...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Power (Read Only) (30 modules)
1D00 Three Phase Real Power
1D02 Phase A Real Power
1D04 Phase B Real Power
1D06 Phase C Real Power
1D08 Three Phase Reactive Power
1D0A Phase A Reactive Power
1D0C Phase B Reactive Power
1D0E Phase C Reactive Power
1D10 Three Phase Apparent Power
1D12 Phase A Apparent Power
1D14 Phase B Apparent Power
1D16 Phase C Apparent Power 1D18 Three Phase Power Factor
1D19 Phase A Power Factor 1D1A Phase B Power Factor 1D1B Phase C Power Factor 1D1C Reserved (4 items) 1D20 1D40 1D60 1D80 1DA0 1DC0 1DE0
1E00
1E20
1E40
1E60
1E80
1EA0
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-0.999 to 1
-0.999 to 1
-0.999 to 1
-0.999 to 1
---
W 0.001 F060 0
W 0.001 F060 0
W 0.001 F060 0
W 0.001 F060 0
var 0.001 F060 0
var 0.001 F060 0
var 0.001 F060 0
var 0.001 F060 0
VA 0.001 F060 0
VA 0.001 F060 0
VA 0.001 F060 0
VA 0.001 F060 0
--- 0.001 F013 0
--- 0.001 F013 0
--- 0.001 F013 0
--- 0.001 F013 0
--- --- F001 0
26
1EC0
1EE0
1F00
1F20
1F40
1F60
1F80
1FA0
1FC0
1FE0
2000
2020
2040
2060
2080 20A0
...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Energy (Read Only Non-Volatile) (30 modules)
2100 Positive Watthour
2102 Phase A Positive Watthour
2104 Phase B Positive Watthour
2106 Phase C Positive Watthour
2108 Negative Watthour
210A Phase A Negative Watthour
210C Phase B Negative Watthour
210E Phase C Negative Watthour
2110 Positive Varhour
2112 Phase A Positive Varhour
2114 Phase B Positive Varhour
2116 Phase C Positive Varhour
2118 Negative Varhour
211A Phase A Negative Varhour
211C Phase B Negative Varhour
211E Phase C Negative Varhour
2120 Vahour
2122 Phase A Vahour
2124 Phase B Vahour
2126 Phase C Vahour
2128 Reserved (8 items)
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
0 to
100000 00000 00
---
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
Wh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
varh 0.001 F060 0
vah 0.001 F060 0
vah 0.001 F060 0
vah 0.001 F060 0
vah 0.001 F060 0
--- --- F001 0
27
2130
2160
2190 21C0
21F0
2220
2250
2280 22B0
22E0
2310
2340
2370 23A0 23D0
2400
2430
2460
2490 24C0
24F0
2520
2550
2580 25B0
25E0
2610
2640
2670
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Source Harmonic Analysis (Read Only) (30 modules)
26A0 SRC x Phase A Voltage THD 26A1 SRC x Phase B Voltage THD 26A2 SRC x Phase C Voltage THD 26A3 SRC x Phase A Current THD 26A4 SRC x Phase B Current THD 26A5 SRC x Phase C Current THD 26A6 SRC x Phase N Current THD 26A7 SRC x Phase A K Factor 26A8 SRC x Phase B K Factor 26A9 SRC x Phase C K Factor 26AA SRC x Phase N K Factor 26AB SRC x Harmonic Analysis Reserved (5 items) --- --- --- F001 0 26B0
...Repeated for module number 2
0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1
0 to 1 0 to 6553.5 0 to 6553.5 0 to 6553.5 0 to 6553.5
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.001 F001 0
--- 0.1 F001 10
--- 0.1 F001 10
--- 0.1 F001 10
--- 0.1 F001 10
28
26C0 26D0
26E0 26F0 2700 2710 2720 2730 2740 2750 2760 2770 2780
2790 27A0 27B0 27C0 27D0
27E0
27F0
2800
2810
2820
2830
2840
2850
2860
2870
...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Source Demand Peaks (Read Only Non-Volatile) (30 modules)
2880 SRC x Maximum kW
2882 SRC x Maximum kW DateTime
2884 SRC x Maximum kvar
2886 SRC x Maximum kvar DateTime
2888 SRC x Maximum kVA
288A SRC x Maximum kVA DateTime 288C SRC x Source Demand Reserved (5 items) --- --- --- F001 0
2891 28A2 28B3 28C4 28D5
28E6
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7
-1000000000000
to 100000 00000 00
0 to 4294967295
-1000000000000
to 100000 00000 00
0 to 4294967295
-1000000000000
to 100000 00000 00
0 to 4294967295
W 0.001 F060 0
--- 1 F050 0
var 0.001 F060 0
--- 1 F050 0 VA 0.001 F060 0
--- 1 F050 0
29
28F7
2908
2919 292A 293B 294C 295D
296E
297F
2990 29A1 29B2 29C3 29D4
29E5
29F6 2A07 2A18 2A29 2A3A 2A4B 2A5C 2A6D
...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Power Peaks (Read Only Non-Volatile) (30 modules)
2A80 SRC x Three Phase Power Factor Min 2A81 SRC x Three Phase Power Factor Min Date 2A83 SRC x Phase A Power Factor Min 2A84 SRC x Phase A Power Factor Min Date 2A86 SRC x Phase B Power Factor Min 2A87 SRC x Phase B Power Factor Min Date 2A89 SRC x Phase C Power Factor Min 2A8A SRC x Phase C Power Factor Min Date 2A8C SRC x Three Phase Power Factor Max 2A8D SRC x Three Phase Power Factor Max Date
2A8F SRC x Phase A Power Factor Max 2A90 SRC x Phase A Power Factor Max Date 2A92 SRC x Phase B Power Factor Max 2A93 SRC x Phase B Power Factor Max Date 2A95 SRC x Phase C Power Factor Max 2A96 SRC x Phase C Power Factor Max Date 2A98 SRC x Last Clear Energy Date 2A9A SRC x Last Commissioned Date 2A9C SRC x Power Peak Reserved (50 items)
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
-0.999 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 0.001 F013 0
--- 1 F050 0
--- 1 F050 0
--- 1 F050 0
--- --- F001 0
30
2ACE 2B1C 2B6A 2BB8 2C06 2C54 2CA2
2CF0 2D3E 2D8C
2DDA
2E28
2E76
2EC4
2F12
2F60
2FAE
2FFC 304A
3098
30E6
3134
3182 31D0
321E 326C 32BA
3308
3356
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Source Demand (Read Only) (30 modules)
35AC SRC x Previous Internal kW
35AE SRC x Previous Interval kvar
35B0 SRC x Previous Interval kVA
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
-1000000000000
to 100000 00000 00
W 0.001 F060 0
var 0.001 F060 0
VA 0.001 F060 0
Source Demand (Read Only Non-Volatile) (30 modules)
35B2 SRC x Last Reset DateTime 35B4 SRC x Number Of Demand Resets
0 to 4294967295
0 to 4294967295
--- 1 F050 0
--- 1 F003 0
Source Demand (Read/Write Command) (30 modules)
35B6 SRC x Demand Reset 35B7 SRC x Demand Log Clear Command
0 to 1 0 to 1
--- 1 F126 0 (No)
--- 1 F126 0 (No)
Source Demand (Read Only Non-Volatile) (30 modules)
35B8 SRC x Demand Log Last Cleared Date
0 to 4294967295
--- 1 F050 0
31
Source Demand (Read Only) (30 modules)
35BA SRC x Demand Log Records Since Last Clear 35BC SRC x Demand Log Interval Records Available
35BE SRCx Source Demand Reserved (10 items) 35C8
35E4
3600 361C
3638
3654
3670 368C 36A8 36C4
36E0
36FC
3718
3734
3750 376C
3788 37A4 37C0 37DC
37F8
3814
3830 384C
3868
3884 38A0 38BC 38D8
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
0 to 4294967295
0 to 4294967295
0 to 4294967295
--- 1 F003 0
--- 1 F003 0
--- 1 F001 0
Source Status (Read Only) (30 modules)
5000 SRC x Node ID
5001 Reserved (3 items)
5004 SRC x Frame Rating
5005 SRC x CT Rating
5006 SRC x Breaker Type
5007 SRC x NodeProt Protection Config
5008 SRC x Node Firmware Version
5009 SRC x Hardware Version 500A SRC x Message Protocol Version
0 to 29
--­0 to 65535 0 to 65535
0 to 1
0 to 65535
0 to 655.35
0 to 255
0 to 655.35
--- 1 F001 0
--- --- F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F715 0 (UL)
--- 1 F705 0
--- 0.01 F001 0
--- 1 F001 0
--- 0.01 F001 0
32
500B SRC x Product Type
500C SRC x NodeProt Rating Switch 500D SRC x NodeProt LT Setting
500E SRC x NodeProt IOC Threshold Setting 500F SRC x NodeProt Ground Fault Setting 5010 SRC x NodeProt Short Time Setting 5011 SRC x Node Internal Diagnostics 5012 SRC x Node System Diagnostics 1 5013 SRC x Node System Diagnostics 2 5014 SRC x Node Hardware Diagnostics 5015 SRC x Node Physical Status 5016 SRC x Node Logic and Trip Status 5017 SRC x Node Last Trip Sequence Number
5019 SRC x Reflected CPU Diagnostics 501A SRC x Reflected CPU 0 Command 501B SRC x Reflected CPU 1 Command 501C SRC x Fan Status 501D SRC x CT Rating Node Report
501E SRC x Node Serial Number
5024 SRC x Node Status Reserved (43 items)
504F
509E 50ED 513C 518B 51DA
5229
5278 52C7
5316
5365 53B4
5403
5452 54A1
54F0
553F
558E
55DD
562C 567B 56CA
5719
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24
0 to 2
0 to 65535 0 to 655.35 0 to 655.35
0 to 1
0 to 1 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535
0 to 4294967295
0 to 65535 0 to 65535 0 to 65535
0 to 1 0 to 65535
---
0 to 1
--- 1 F716
0 (Low Voltage
Switchgear)
--- 1 F001 0
--- 0.01 F001 0
--- 0.01 F001 0
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F701 0
--- 1 F702 0
--- 1 F703 0
--- 1 F704 0
--- 1 F708 0
--- 1 F709 0
--- 1 F003 0
--- 1 F706 0
--- 1 F707 0
--- 1 F707 0
--- 1 F108 0 (Off)
--- 1 F001 0
--- --- F205 (none)
--- 1 F001 0
33
5768
57B7
5806 5855
58A4
58F3
...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Source Settings (Read/Write Setting) (30 modules)
5C8A SRC x Node Commissioned
0 to 1
Source Settings (Read Only) (30 modules)
5C8B SRC x PT Source Node Identifier
0 to 29
Source Settings (Read/Write Setting) (30 modules)
5C8C SRC x Breaker Connection 5C8D SRC x IOC Enabled
5C8E SRC x IOC Pickup Setting Multiplier
5C8F SRC x Ground Fault Protection Switch 5C90 SRC x Short Time Protection Switch 5C91 SRC x Short Time Pickup Setting 5C92 SRC x Short Time I2T Curve 5C93 SRC x Short Time Delay Band Setting 5C94 SRC x Long Time Delay Band Setting 5C95 SRC x Ground Fault Protection Alarm Select 5C96 SRC x Ground Fault Protection I2T Curve 5C97 SRC x Ground Fault Protection Pickup Setting
5C98
SRC x Ground Fault Protection Delay Band Setting
5C99 SRC x PT Rating 5C9A SRC x UV Trip Enable 5C9B SRC x UV Trip Curve Type 5C9C SRC x UV Trip Pickup Setting 5C9D SRC x UV Trip Time Delay
5C9E SRC x UV Trip Phase Requirement
5C9F SRC x UV Block Voltage Enable 5CA0 SRC x UV Trip Block Volt Setting
5CA1 SRC x UV Trip Open or Trip Setting
5CA2 SRC x UV Alarm Enable 5CA3 SRC x UV Alarm Curve Type 5CA4 SRC x UV Alarm Pickup Setting 5CA5 SRC x UV Alarm Time Delay 5CA6 SRC x UV Alarm Phase Requirement 5CA7 SRC x UV Alarm Block Volt Enable 5CA8 SRC x UV Alarm Block Volt Setting 5CA9 Reserved1 (5 items) 5CAE SRC x OV Trip Enable 5CAF SRC x OV Trip Pickup Setting
0 to 1 0 to 1
1.5 to 15 0 to 1 0 to 1
1.5 to 9 0 to 1 0 to 6 0 to 3 0 to 1 0 to 1
0.2 to 0.6
0 to 6
0 to 6 0 to 1 0 to 1
50 to 95
0.5 to 600 1 to 3 0 to 1
5 to 75
0 to 1
0 to 1 0 to 1
50 to 95
0.5 to 600 1 to 3 0 to 1
5 to 75
0 to 65535
0 to 1
105 to 125
--- 1 F102 0 (Disabled)
--- 1 F001 0
--- 1 F712 0 (Forward)
--- 1 F718 1 (Enabled)
--- 0.5 F001 60
--- 1 F102 0 (Disabled)
--- 1 F102 1 (Enabled)
--- 0.5 F001 50
--- 1 F102 0 (Disabled)
--- 1 F713 2 (BAND 3)
--- 1 F711 1 (BAND 2)
--- 1 F714 0 (Trip)
--- 1 F102 1 (Enabled)
--- 0.01 F001 24
--- 1 F713 2 (BAND 3)
--- 1 F719 0 (None)
--- 1 F102 0 (Disabled)
--- 1 F726 1 (Constant time curve)
--- 1 F001 50
--- 0.5 F001 300
--- 1 F001 1
--- 1 F102 0 (Disabled)
--- 1 F001 5
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F102 0 (Disabled)
--- 1 F726 1 (Constant time curve)
--- 1 F001 50
--- 0.5 F001 150
--- 1 F001 1
--- 1 F102 0 (Disabled)
--- 1 F001 5
--- 1 F001 0
--- 1 F102 0 (Disabled)
--- 1 F001 120
34
5CB0 SRC x OV Trip Time Delay 5CB1 SRC x OV Trip Phase Requirement
5CB2 SRC x OV Trip Open or Trip Setting
5CB3 SRC x OV Alarm Enable 5CB4 SRC x OV Alarm Pickup Threshold 5CB5 SRC x OV Alarm Time Delay 5CB6 SRC x OV Alarm Phase Requirement 5CB9 Reserved2 (7 items) 5CBE SRC x PL Trip Enable 5CBF SRC x PL Trip Pickup Setting 5CC0 SRC x PL Trip Time Delay 5CC1 SRC x PL Trip Block Volt Enable
5CC2 SRC x PL Open or Trip Setting
5CC3 SRC x PL Alarm Enable 5CC4 SRC x PL Alarm Pickup Setting 5CC5 SRC x PL Alarm Time Delay 5CC6 SRC x PL Alarm Block Volt Enable
0.5 to 600 1 to 3
0 to 1
0 to 1
105 to 125
0.5 to 600 1 to 3
0 to 65535
0 to 1
8 to 50
0.5 to 600 0 to 1
0 to 1
0 to 1
8 to 50
0.5 to 600 0 to 1
--- 0.5 F001 300
--- 1 F001 1
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F102 0 (Disabled)
--- 1 F001 120
--- 0.5 F001 150
--- 1 F001 1
--- 1 F001 0
--- 1 F102 0 (Disabled)
--- 1 F001 8
--- 0.5 F001 300
--- 1 F102 0 (Disabled)
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F102 0 (Disabled)
--- 1 F001 8
--- 0.5 F001 150
--- 1 F102 0 (Disabled)
Source Settings (Read Only) (30 modules)
5CC7 SRC x PL Trip Voltage Setting 5CC8 SRC x PL Alarm Blocking Voltage Setting
5 to 5 5 to 5
Source Settings (Read/Write Setting) (30 modules)
5CC9 Reserved3 (3 items) 5CCC SRC x Rev Power Trip Enable
5CCD SRC x Rev Power Trip Pickup Setting
5CCE SRC x Rev Power Trip Time Delay 5CCF SRC x Rev Power Alarm Enable 5CD0 SRC x Rev Power Alarm Pickup Setting 5CD1 SRC x Rev Power Alarm Time Delay
5CD2 SRC x Rev Power Trip or Open
5CD3 Reserved4 (4 items) 5CD7 SRC x High Curr Alarm Enable 5CD8 SRC x High Curr Alarm Pickup Setting 5CD9 SRC x High Curr Alarm Time Delay
5CDA Reserved5 (5 items)
5CDF SRC x Total Breaker Operations
5CE0 SRC x Total Breaker No Load Operations 5CE1 SRC x Total Breaker Load Operations 5CE2 SRC x Total Breaker Fault Operations 5CE3 SRC x Breaker Percent Load Life
0 to 65535
0 to 1
10 to 990
0.5 to 600 0 to 1
10 to 990
0.5 to 600
0 to 1
0 to 65535
0 to 1
50 to 200
1 to 15 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535
0 to 655.35
--- 1 F001 5
--- 1 F001 5
--- 1 F001 0
--- 1 F102 0 (Disabled)
--- 10 F001 990
--- 0.5 F001 300
--- 1 F102 0 (Disabled)
--- 10 F001 990
--- 0.5 F001 150
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F001 0
--- 1 F102 0 (Disabled)
--- 5 F001 200
--- 1 F001 15
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 0.01 F001 0
Source Settings (Read Only) (30 modules)
5CE4 SRC x Percent Mechanical Life
0 to 655.35
Source Settings (Read/Write Setting) (30 modules)
5CE5 SRC x Time Date Last Breaker Operation
0 to 4294967295
--- 0.01 F001 0
--- 1 F050 0
35
5CE7 SRC x Time Date Initial Energization
0 to 4294967295
Source Settings (Read Only) (30 modules)
5CE9 SRC_X_Breaker_Service_Hours
0 to 4294967295
Source Settings (Read/Write Setting) (30 modules)
5CEB Reserved6 (5 items)
5CF0 SRC x UF Trip Enable 5CF1 SRC x UF Trip Pickup Setting 5CF2 SRC x UF Trip Time Delay 5CF3 SRC x UF Trip Blocking Voltage Enable
5CF4 SRC x UF Trip or Open setting
5CF5 SRC x UF Alarm Enable 5CF6 SRC x UF Alarm Pickup Setting 5CF7 SRC x UF Alarm Time Delay 5CF8 SRC x UF Alarm Blocking Voltage Enable
5CF9 SRC x OF Trip Enable 5CFA SRC x OF Trip Pickup Setting 5CFB SRC x OF Trip Time Delay 5CFC SRC x OF Trip Blocking Voltage Enable
5CFD SRC x OF Trip or Open setting
5CFE SRC x OF Alarm Enable
5CFF SRC x OF Alarm Pickup Setting 5D00 SRC x OF Alarm Time Delay 5D01 SRC x OF Alarm Blocking Voltage Enable 5D02 SRC x HRGF Enable 5D03 SRC x HRGF Pickup 5D04 SRC x HRGF Delay 5D05 SRC x HRGF Ground Resistance 5D06 SRC x HRGF CT Rating 5D07 SRC x Settings Reserved (41 items) 5D30
5DD6
5E7C
5F22
5FC8
606E
6114 61BA
6260
6306 63AC
6452
64F8
659E
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15
0 to 65535
0 to 1
45 to 60
0.1 to 600 0 to 1
0 to 1
0 to 1
45 to 60
0.1 to 600 0 to 1 0 to 1
50 to 70
0.1 to 600 0 to 1
0 to 1
0 to 1
50 to 70
0.1 to 600 0 to 1 0 to 1
2 to 10
0.5 to 5 5 to 500 10 to 10
0 to 65535
--- 1 F050 0
--- 1 F003 0
--- 1 F001 0
--- 1 F102 0 (Disabled)
--- 0.1 F001 450
--- 0.1 F001 300
--- 1 F102 0 (Disabled)
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F102 0 (Disabled)
--- 0.1 F001 450
--- 0.1 F001 150
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 0.1 F001 500
--- 0.1 F001 300
--- 1 F102 0 (Disabled)
--- 1 F727
1 (Trip and activate
lockout)
--- 1 F102 0 (Disabled)
--- 0.1 F001 500
--- 0.1 F001 150
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 0.1 F001 20
--- 0.1 F001 5
--- 1 F001 5
--- 1 F001 10
--- 1 F001 0
36
6644 66EA 6790 6836
68DC
6982 6A28 6ACE 6B74 6C1A 6CC0 6D66
6E0C
6EB2
6F58
...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Source Commands (Read/Write Command) (30 modules)
7000 SRC x Open Breaker
7001 SRC x Close Breaker
7002 SRC x Trip Breaker
7003 SRC x Clear Energy
7004 Reserved --- --- --- F001 0
7005 SRC x Remote Lockout Enable
7006 SRC x Remote Lockout Reset
7007 SRC x ATO Mode Enabled
7008 SRC x Command Reserved (42 items)
7032
7064
7096 70C8
70FA 712C
715E
7190 71C2
71F4
7226
7258 728A 72BC
72EE
7320
7352
7384
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19
0 to 1 0 to 1 0 to 1 0 to 1
0 to 1 0 to 1 0 to 1
0 to 65535
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F126 0 (No)
--- 1 F001 0
37
73B6
73E8 741A 744C
747E 74B0
74E2
7514
7546
7578 75AA
...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
Contact Input Configuration (Read/Write Setting) (2 modules)
75DC Board x I/O Direction High 75DE Board x I/O Direction Low
75E0
...Repeated for module number 2
0 to 4294967295
0 to 4294967295
--- 1 F737 0
--- 1 F736 0
SynchCheck Settings (Read/Write Setting) (6 modules)
7F97 Synch Check Enable
7F98 Synch Chech V1 Source
7F99 Synch Check V2 Source
7F9A Synch Check Max Volt Diff
7F9B Synch Check Max Phase Diff
7F9C Synch Check Max Freq Diff 7F9D Synch Check Dead Max V1
7F9E Synch Check Live Min V1
7F9F Synch Check Dead MaxV2
7FA0 Synch Check Live Min V2
7FA1 Synch Check Dead Source Select
0 to 1 0 to 29 0 to 29 0 to 90 0 to 60
0 to 2 5 to 50
50 to 100
5 to 50
50 to 100
0 to 5
--- 1 F102 0 (Disabled)
--- 1 F001 0
--- 1 F001 0
--- 0.5 F001 0
--- 1 F001 0
--- 0.1 F001 0
--- 1 F001 5
--- 1 F001 50
--- 1 F001 5
--- 1 F001 50
--- 1 F176 0 (None)
SynchCheck Settings (Read Only) (6 modules)
7FA2 SynchCheck Status 7FA3 Synch Check Reserved (9 items)
7FAC
7FC1
7FD6
7FEB 8000
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6
0 to 65535 0 to 65535
Discrete I/O Configuration (Read Only)
8015 Boards Detected 8016 Boards Used 8017 Total I/O Points Available 8018 Contact Input Count 8019 Contact Output Count
0 to 8
0 to 8
0 to 65535
0 to 128 0 to 128
Discrete I/O Configuration (Read/Write Setting)
801A Boards Expected 801B Discrete I/O Configuration Reserved (15 items)
38
0 to 2
0 to 65535
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
--- 1 F001 0
Force Contact Inputs (Read/Write Setting)
8700 Force Contact Input x State (128 items)
Force Contact Outputs (Read/Write Setting)
8780 Force Contact Output x State (128 items)
Expanded Digital I/O states (Read Only)
9100 Contact Input x State (128 items) 9180 Contact Output x State (128 items)
Options (Read Only)
9379 Options Authentication State 937A Options Timestamp 937C Options Bit Vectors 937D Options Expanded Metering Count
Options (Read/Write Setting)
937E
Options Expanded Metering Node x State Enable
Options (Read Only)
9380 Options Demand Metering Count
Options (Read/Write Setting)
9381
Options Demand Metering Node x State Enable
Options (Read Only)
9383 Options Harmonics Metering Count
0 to 2
0 to 3
0 to 1 0 to 1
0 to 2
0 to 4294967295
0 to 65535
0 to 30
0 to 4294967295
0 to 30
0 to 4294967295
0 to 30
--- 1 F144 0 (Disabled)
--- 1 F131 0 (Disabled)
--- 1 F108 0 (Off)
--- 1 F108 0 (Off)
--- 1 F738 0
--- 1 F050 0
--- 1 F728 0
--- 1 F001 0
--- 1 F722 0
--- 1 F001 0
--- 1 F722 0
--- 1 F001 0
Options (Read/Write Setting)
9384
Options Harmonics Metering Node x State Enable
0 to 4294967295
--- 1 F722 0
Options (Read Only)
9386 Options Voltage Relay Count
0 to 30
--- 1 F001 0
Options (Read/Write Setting)
9387 Options Voltage Relay Node x State Enable
0 to 4294967295
--- 1 F722 0
Options (Read Only)
9389 Options High Current Relay Count
0 to 30
--- 1 F001 0
Options (Read/Write Setting)
938A
Option High Current Relay Node x State Enable
0 to 4294967295
--- 1 F722 0
Options (Read Only)
938C Options Freq and Rev Pwr Relay Count
0 to 30
--- 1 F001 0
Options (Read/Write Setting)
938D Option Freq and Rev Pwr Relay Node x Enable
0 to 4294967295
--- 1 F722 0
Virtual Input Commands (Read/Write Command) (32 modules)
AC00 Virtual Input x State AC01 AC02 AC03 AC04 AC05
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6
0 to 1
--- 1 F108 0 (Off)
39
AC06 AC07 AC08 AC09 AC0A AC0B AC0C
AC0D
AC0E AC0F AC10 AC11 AC12 AC13 AC14 AC15 AC16 AC17 AC18 AC19 AC1A AC1B AC1C
AC1D
AC1E AC1F
...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30 ...Repeated for module number 31 ...Repeated for module number 32
Digital I/O States (Read Only)
B200 Virtual Input States (2 items) B202 Reserved (30 items) B220 Virtual Output States (8 items) B228 Reserved (30 items) B246 Contact Input States (8 items)
B24E Reserved (8 items) B256 Contact Output States (8 items)
B25E Reserved (162 items)
0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
--- 1 F500 0
Flexlogic Status (Read Only)
B320 Flexlogic Status Message
Breaker Control (Read/Write Setting) (30 modules)
B400 Breaker Control x Open Flux Shifter B401 Breaker Control x Open Shunt Trip B402 Breaker Control x Trip Flux Shifter B403 Breaker Control x Trip Shunt Trip B404 Breaker Control x Close
40
0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535
---
--- --- F200 (none)
--- 1 F300 0
--- 1 F300 0
--- 1 F300 0
--- 1 F300 0
--- 1 F300 0
B405 Breaker Control x Lockout B406 Breaker Control x Lockout Reset B407 Reserved (18 items) B419 B432 B44B B464 B47D B496 B4AF B4C8
B4E1 B4FA B513 B52C B545
B55E B577 B590 B5A9 B5C2
B5DB
B5F4 B60D B626
B63F B658 B671 B68A B6A3 B6BC B6D5
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
ZSI Option Settings (Read/Write Setting)
B784 ZSI Option B785 ZSI Option Reserved
0 to 65535 0 to 65535 0 to 65535
0 to 2
0 to 65535
--- 1 F300 0
--- 1 F300 0
--- 1 F001 0
--- 1 F732 0 (ST ZSI)
--- 1 F001 0
ZSI Zone Enables (Read/Write Setting) (4 modules)
B786 ZSI Zone x Enabled B787 ZSI Zone Enable Reserved (14 items) B795 B7A4 B7B3
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4
0 to 65535
0 to 1
--- 1 F126 0 (No)
--- 1 F001 0
41
ZSI ST Tier Settings (Read/Write Setting) (30 modules)
B7C2 SRC x ST ZSI Zone 1 Tier Settings (16 items) B7D2 SRC x ST ZSI Zone 2 Tier Settings (16 items)
B7E2 SRC x ST ZSI Zone 3 Tier Settings (16 items)
B7F2 SRC x ST ZSI Zone 4 Tier Settings (16 items) B802 ZSI Tier Settings reserved (16 items) B812 B862 B8B2 B902 B952 B9A2
B9F2 BA42 BA92 BAE2 BB32 BB82
BBD2
BC22 BC72 BCC2 BD12 BD62
BDB2
BE02
BE52 BEA2
BEF2
BF42
BF92
BFE2 C032 C082 C0D2
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
0 to 3 0 to 3 0 to 3 0 to 3
0 to 65635
ZSI GF Tier Settings (Read/Write Setting) (30 modules)
C122 SRC x GF ZSI Zone 1 Tier Settings (16 items) C132 SRC x GF ZSI Zone 2 Tier Settings (16 items) C142 SRC x GF ZSI Zone 3 Tier Settings (16 items) C152 SRC x GF ZSI Zone 4 Tier Settings (16 items) C162 SRC x GF ZSI Tier Settings reserved (16 items) C172 C1C2
...Repeated for module number 2 ...Repeated for module number 3
0 to 3 0 to 3 0 to 3 0 to 3
0 to 65535
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F001 0
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F001 0
42
C212 C262 C2B2 C302 C352 C3A2
C3F2 C442 C492
C4E2 C532 C582 C5D2 C622 C672 C6C2 C712 C762 C7B2 C802 C852 C8A2
C8F2 C942 C992
C9E2 CA32
...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30
ZSI MSGF Tier Settings (Read/Write Setting) (4 modules)
CA82 MSGF ZSI Zone 1 GRPx Tier Settings (16 items) CA92 MSGF ZSI Zone 2 GRP x Tier Settings (16 items) CAA2 MSGF ZSI Zone 3 GRP x Tier Settings (16 items) CAB2 MSGF ZSI Zone 4 GRP x Tier Settings (16 items) CAC2 MSGF ZSI Reserved (16 items)
CAD2
CB22 CB72
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4
0 to 3 0 to 3 0 to 3 0 to 3
0 to 65535
Zone x MSGF Settings (Read/Write Setting) (4 modules)
CBC2 Zone x MSGF Trip Pickup Setting (16 items)
CBD2 Zone x MSGF Alarm Pickup Setting (16 items)
CBE2
CBF2
CC02 Zone x MSGF Trip I2T Curve (16 items)
Zone x MSGF Trip Delay Band Setting (16 items)
Zone x MSGF Alarm Delay Band Setting (16 items)
30 to 1200 30 to 1200
0 to 6
0 to 6
0 to 1
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F733 0 (ZSI Tier 0)
--- 1 F001 0
--- 1 F001 1200
--- 1 F001 1200
--- 1 F735 2 (BAND 3)
--- 1 F735 2 (BAND 3)
--- 1 F102 0 (Disabled)
43
CC12 Zone x MSGF Alarm I2T Curve (16 items) CC22 Zone x MSGF Trip Enabled (16 items) CC32 Zone x MSGF Alarm Enabled (16 items) CC42 Zone x MSGF Backup Enabled (16 items)
CC52
Zone x MSGF Backup Time Date Enabled (16 items)
CC62 Zone x MSGF Trip or Open
CC63 Zone x MSGF Reserved (16 items) CC73 CD24
CDD5
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4
0 to 1 0 to 1 0 to 1 0 to 1
0 to 1
0 to 1
0 to 65535
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F727
--- 1 F001 0
Zone x BD Settings (Read/Write Setting) (4 modules)
CE8A Zone x BD Trip Pickup Setting (16 items) CE9A Zone x BD Alarm Pickup Setting (16 items) CEAA Zone x BD Trip Pickup Setting2 (16 items) CEBA Zone x BD Alarm Pickup Setting2 (16 items) CECA Zone x BD Trip Delay Band Setting (16 items)
CEDA
Zone x BD Alarm Delay Band Setting (16 items)
CEEA Zone x BD Trip Delay Band Setting2 (16 items)
CEFA
Zone x BD Alarm Delay Band Setting2 (16 items)
CF0A Zone x BD Trip Enabled (16 items) CF1A Zone x BD Alarm Enabled (16 items) CF2A Zone x BD Backup Enabled (16 items)
CF3A
Zone x BD Backup Time Delta Enabled (16 items)
CF4A Zone x BD Trip or Open
CF4B Zone x BD Reserved (16 items) CF5B D02C
D0FD
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4
30 to 2200 0 30 to 2200 0 30 to 2200 0 30 to 2200 0
0 to 6
0 to 6
0 to 6
0 to 6
0 to 1 0 to 1 0 to 1
0 to 1
0 to 1
0 to 65535
--- 1 F001 1200
--- 1 F001 1200
--- 1 F001 1200
--- 1 F001 1200
--- 1 F735 2 (BAND 3)
--- 1 F735 2 (BAND 3)
--- 1 F735 2 (BAND 3)
--- 1 F735 2 (BAND 3)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F727
--- 1 F001 0
Zone x Summation Settings (Read/Write Setting) (2 modules)
D1D2
D1E2
Zone x Summation MSGF Trip Delay Band Setting (16 items)
Zone x Summation MSGF Alarm Delay Band Setting (16 items)
D1F2 Zone x Summation MSGF Trip I2T (16 items)
D202
D212
D222
D232
Zone x Summation MSGF Alarm I2T Curve (16 items)
Zone x Summation MSGF Trip Enabled (16 items)
Zone x Summation MSGF Alarm Enabled (16 items)
Zone x Summation MSGF Trip Pickup Setting (16 items)
D242 Zone x Summation MSGF Alarm Pickup
0 to 6
0 to 6
0 to 1
0 to 1
0 to 1
0 to 1
30 to 1200
30 to 1200
--- 1 F735 2 (BAND 3)
--- 1 F735 2 (BAND 3)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F102 0 (Disabled)
--- 1 F001 1200
--- 1 F001 1200
0 (Open and don't
activate lockout)
0 (Open and don't
activate lockout)
44
Setting (16 items)
D252 Zone x Summation MSGF Trip or Open
D253 Zone x Summation Reserved (32 items) D273
...Repeated for module number 2
0 to 1
0 to 65535
Alarm Flex Logic (Read/Write Setting) (16 modules)
D314 Alarm x Flex Logic D315 Alarm Flex Logic Reserved D316 D318 D31A D31C D31E D320 D322 D324 D326 D328 D32A D32C D32E D330 D332
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16
0 to 65535 0 to 65535
Contact Inputs (Read/Write Setting) (128 modules)
D334 Contact Input x Name D348 Contact Input x Events D349 Contact Input x Debounce Time D34A Contact Input x Reserved (4 items) D34E D368 D382 D39C D3B6
D3D0
D3EA D404 D41E D438 D452 D46C D486 D4A0
D4BA
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16
0 to 1 0 to 4
0 to 65535
---
--- 1 F727
--- 1 F001 0
--- 1 F300 0
--- 1 F001 0
--- --- F200 "Contact Input 1 "
--- 1 F102 1 (Enabled)
--- 1 F734 0 (Disabled)
--- 1 F001 0
0 (Open and don't
activate lockout)
45
D4D4
D4EE D508 D522 D53C D556 D570 D58A D5A4 D5BE
D5D8
D5F2 D60C D626 D640 D65A D674 D68E D6A8 D6C2
D6DC
D6F6 D710 D72A D744 D75E D778 D792
D7AC
D7C6 D7E0 D7FA D814 D82E D848 D862 D87C D896 D8B0
D8CA
D8E4 D8FE
...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30 ...Repeated for module number 31 ...Repeated for module number 32 ...Repeated for module number 33 ...Repeated for module number 34 ...Repeated for module number 35 ...Repeated for module number 36 ...Repeated for module number 37 ...Repeated for module number 38 ...Repeated for module number 39 ...Repeated for module number 40 ...Repeated for module number 41 ...Repeated for module number 42 ...Repeated for module number 43 ...Repeated for module number 44 ...Repeated for module number 45 ...Repeated for module number 46 ...Repeated for module number 47 ...Repeated for module number 48 ...Repeated for module number 49 ...Repeated for module number 50 ...Repeated for module number 51 ...Repeated for module number 52 ...Repeated for module number 53 ...Repeated for module number 54 ...Repeated for module number 55 ...Repeated for module number 56 ...Repeated for module number 57 ...Repeated for module number 58
46
D918 D932 D94C D966 D980 D99A D9B4 D9CE D9E8 DA02
DA1C
DA36 DA50
DA6A
DA84 DA9E
DAB8 DAD2 DAEC
DB06 DB20
DB3A
DB54 DB6E DB88
DBA2 DBBC DBD6
DBF0
DC0A
DC24 DC3E DC58 DC72
DC8C DCA6 DCC0 DCDA
DCF4
DD0E DD28 DD42
...Repeated for module number 59 ...Repeated for module number 60 ...Repeated for module number 61 ...Repeated for module number 62 ...Repeated for module number 63 ...Repeated for module number 64 ...Repeated for module number 65 ...Repeated for module number 66 ...Repeated for module number 67 ...Repeated for module number 68 ...Repeated for module number 69 ...Repeated for module number 70 ...Repeated for module number 71 ...Repeated for module number 72 ...Repeated for module number 73 ...Repeated for module number 74 ...Repeated for module number 75 ...Repeated for module number 76 ...Repeated for module number 77 ...Repeated for module number 78 ...Repeated for module number 79 ...Repeated for module number 80 ...Repeated for module number 81 ...Repeated for module number 82 ...Repeated for module number 83 ...Repeated for module number 84 ...Repeated for module number 85 ...Repeated for module number 86 ...Repeated for module number 87 ...Repeated for module number 88 ...Repeated for module number 89 ...Repeated for module number 90 ...Repeated for module number 91 ...Repeated for module number 92 ...Repeated for module number 93 ...Repeated for module number 94 ...Repeated for module number 95 ...Repeated for module number 96 ...Repeated for module number 97 ...Repeated for module number 98 ...Repeated for module number 99 ...Repeated for module number 100
47
DD5C DD76 DD90 DDAA DDC4 DDDE DDF8
DE12 DE2C DE46 DE60 DE7A DE94 DEAE DEC8 DEE2 DEFC DF16 DF30 DF4A DF64 DF7E DF98 DFB2
DFCC
DFE6
E000
E01A
...Repeated for module number 101 ...Repeated for module number 102 ...Repeated for module number 103 ...Repeated for module number 104 ...Repeated for module number 105 ...Repeated for module number 106 ...Repeated for module number 107 ...Repeated for module number 108 ...Repeated for module number 109 ...Repeated for module number 110 ...Repeated for module number 111 ...Repeated for module number 112 ...Repeated for module number 113 ...Repeated for module number 114 ...Repeated for module number 115 ...Repeated for module number 116 ...Repeated for module number 117 ...Repeated for module number 118 ...Repeated for module number 119 ...Repeated for module number 120 ...Repeated for module number 121 ...Repeated for module number 122 ...Repeated for module number 123 ...Repeated for module number 124 ...Repeated for module number 125 ...Repeated for module number 126 ...Repeated for module number 127 ...Repeated for module number 128
Contact Outputs (Read/Write Setting) (128 modules)
E034 Contact Output x Name
E048 Contact Output x Operation
E049 Contact Output x Sealin
E04A Contact Output x Events
E04B Contact Outputs Reserved (7 items)
E052
E070
E08E E0AC E0CA
E0E8
E106
E124
E142
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10
--­0 to 65535 0 to 65535
0 to 1
0 to 65535
--- --- F200 "Contact Output 1 "
--- 1 F300 0
--- 1 F300 0
--- 1 F102 1 (Enabled)
--- 1 F001 0
48
E160 E17E
E19C E1BA E1D8
E1F6
E214
E232
E250
E26E
E28C E2AA
E2C8
E2E6
E304
E322
E340
E35E
E37C
E39A
E3B8 E3D6
E3F4
E412
E430
E44E
E46C
E48A
E4A8
E4C6
E4E4
E502
E520
E53E
E55C
E57A
E598
E5B6 E5D4
E5F2
E610
E62E
...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30 ...Repeated for module number 31 ...Repeated for module number 32 ...Repeated for module number 33 ...Repeated for module number 34 ...Repeated for module number 35 ...Repeated for module number 36 ...Repeated for module number 37 ...Repeated for module number 38 ...Repeated for module number 39 ...Repeated for module number 40 ...Repeated for module number 41 ...Repeated for module number 42 ...Repeated for module number 43 ...Repeated for module number 44 ...Repeated for module number 45 ...Repeated for module number 46 ...Repeated for module number 47 ...Repeated for module number 48 ...Repeated for module number 49 ...Repeated for module number 50 ...Repeated for module number 51 ...Repeated for module number 52
49
E64C
E66A
E688
E6A6
E6C4
E6E2
E700
E71E
E73C
E75A
E778
E796
E7B4 E7D2
E7F0
E80E
E82C
E84A
E868
E886
E8A4
E8C2
E8E0
E8FE
E91C
E93A
E958
E976
E994
E9B2 E9D0
E9EE EA0C EA2A
EA48
EA66
EA84 EAA2 EAC0 EADE EAFC EB1A
...Repeated for module number 53 ...Repeated for module number 54 ...Repeated for module number 55 ...Repeated for module number 56 ...Repeated for module number 57 ...Repeated for module number 58 ...Repeated for module number 59 ...Repeated for module number 60 ...Repeated for module number 61 ...Repeated for module number 62 ...Repeated for module number 63 ...Repeated for module number 64 ...Repeated for module number 65 ...Repeated for module number 66 ...Repeated for module number 67 ...Repeated for module number 68 ...Repeated for module number 69 ...Repeated for module number 70 ...Repeated for module number 71 ...Repeated for module number 72 ...Repeated for module number 73 ...Repeated for module number 74 ...Repeated for module number 75 ...Repeated for module number 76 ...Repeated for module number 77 ...Repeated for module number 78 ...Repeated for module number 79 ...Repeated for module number 80 ...Repeated for module number 81 ...Repeated for module number 82 ...Repeated for module number 83 ...Repeated for module number 84 ...Repeated for module number 85 ...Repeated for module number 86 ...Repeated for module number 87 ...Repeated for module number 88 ...Repeated for module number 89 ...Repeated for module number 90 ...Repeated for module number 91 ...Repeated for module number 92 ...Repeated for module number 93 ...Repeated for module number 94
50
EB38
EB56
EB74
EB92 EBB0 EBCE EBEC EC0A
EC28
EC46
EC64
EC82 ECA0 ECBE
ECDC
ECFA ED18 ED36 ED54 ED72 ED90 EDAE
EDCC
EDEA
EE08
EE26
EE44
EE62
EE80
EE9E EEBC EEDA
EEF8
EF16
...Repeated for module number 95 ...Repeated for module number 96 ...Repeated for module number 97 ...Repeated for module number 98 ...Repeated for module number 99 ...Repeated for module number 100 ...Repeated for module number 101 ...Repeated for module number 102 ...Repeated for module number 103 ...Repeated for module number 104 ...Repeated for module number 105 ...Repeated for module number 106 ...Repeated for module number 107 ...Repeated for module number 108 ...Repeated for module number 109 ...Repeated for module number 110 ...Repeated for module number 111 ...Repeated for module number 112 ...Repeated for module number 113 ...Repeated for module number 114 ...Repeated for module number 115 ...Repeated for module number 116 ...Repeated for module number 117 ...Repeated for module number 118 ...Repeated for module number 119 ...Repeated for module number 120 ...Repeated for module number 121 ...Repeated for module number 122 ...Repeated for module number 123 ...Repeated for module number 124 ...Repeated for module number 125 ...Repeated for module number 126 ...Repeated for module number 127 ...Repeated for module number 128
Virtual Outputs (Read/Write Setting) (128 modules)
EF34 Virtual Output x Name
EF48 Virtual Output x Events
EF49 Virtual Output x Reserved (2 items)
EF4B
EF62
EF79
EF90
EFA7
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6
0 to 1
---
---
--- --- F200 "Virtual Output 1 "
--- 1 F102 0 (Disabled)
--- --- F001 0
51
EFBE EFD5
EFEC
F003
F01A
F031
F048
F05F
F076 F08D
F0A4 F0BB F0D2
F0E9
F100
F117
F12E
F145
F15C
F173
F18A
F1A1
F1B8
F1CF
F1E6 F1FD
F214
F22B
F242
F259
F270
F287
F29E
F2B5 F2CC
F2E3
F2FA
F311
F328
F33F
F356 F36D
...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30 ...Repeated for module number 31 ...Repeated for module number 32 ...Repeated for module number 33 ...Repeated for module number 34 ...Repeated for module number 35 ...Repeated for module number 36 ...Repeated for module number 37 ...Repeated for module number 38 ...Repeated for module number 39 ...Repeated for module number 40 ...Repeated for module number 41 ...Repeated for module number 42 ...Repeated for module number 43 ...Repeated for module number 44 ...Repeated for module number 45 ...Repeated for module number 46 ...Repeated for module number 47 ...Repeated for module number 48
52
F384
F39B
F3B2
F3C9
F3E0
F3F7
F40E
F425
F43C
F453
F46A
F481
F498
F4AF
F4C6
F4DD
F4F4
F50B
F522
F539
F550
F567
F57E
F595 F5AC
F5C3 F5DA
F5F1
F608
F61F
F636 F64D
F664
F67B
F692
F6A9
F6C0 F6D7
F6EE
F705
F71C
F733
...Repeated for module number 49 ...Repeated for module number 50 ...Repeated for module number 51 ...Repeated for module number 52 ...Repeated for module number 53 ...Repeated for module number 54 ...Repeated for module number 55 ...Repeated for module number 56 ...Repeated for module number 57 ...Repeated for module number 58 ...Repeated for module number 59 ...Repeated for module number 60 ...Repeated for module number 61 ...Repeated for module number 62 ...Repeated for module number 63 ...Repeated for module number 64 ...Repeated for module number 65 ...Repeated for module number 66 ...Repeated for module number 67 ...Repeated for module number 68 ...Repeated for module number 69 ...Repeated for module number 70 ...Repeated for module number 71 ...Repeated for module number 72 ...Repeated for module number 73 ...Repeated for module number 74 ...Repeated for module number 75 ...Repeated for module number 76 ...Repeated for module number 77 ...Repeated for module number 78 ...Repeated for module number 79 ...Repeated for module number 80 ...Repeated for module number 81 ...Repeated for module number 82 ...Repeated for module number 83 ...Repeated for module number 84 ...Repeated for module number 85 ...Repeated for module number 86 ...Repeated for module number 87 ...Repeated for module number 88 ...Repeated for module number 89 ...Repeated for module number 90
53
F74A
F761
F778
F78F
F7A6 F7BD F7D4
F7EB
F802
F819
F830
F847
F85E
F875
F88C
F8A3 F8BA F8D1
F8E8
F8FF
F916 F92D
F944
F95B
F972
F989
F9A0
F9B7
F9CE
F9E5
F9FC
FA13 FA2A
FA41
FA58
FA6F
FA86 FA9D
...Repeated for module number 91 ...Repeated for module number 92 ...Repeated for module number 93 ...Repeated for module number 94 ...Repeated for module number 95 ...Repeated for module number 96 ...Repeated for module number 97 ...Repeated for module number 98 ...Repeated for module number 99 ...Repeated for module number 100 ...Repeated for module number 101 ...Repeated for module number 102 ...Repeated for module number 103 ...Repeated for module number 104 ...Repeated for module number 105 ...Repeated for module number 106 ...Repeated for module number 107 ...Repeated for module number 108 ...Repeated for module number 109 ...Repeated for module number 110 ...Repeated for module number 111 ...Repeated for module number 112 ...Repeated for module number 113 ...Repeated for module number 114 ...Repeated for module number 115 ...Repeated for module number 116 ...Repeated for module number 117 ...Repeated for module number 118 ...Repeated for module number 119 ...Repeated for module number 120 ...Repeated for module number 121 ...Repeated for module number 122 ...Repeated for module number 123 ...Repeated for module number 124 ...Repeated for module number 125 ...Repeated for module number 126 ...Repeated for module number 127 ...Repeated for module number 128
54
Virtual Inputs (Read/Write Setting) (32 modules)
FAB4 Virtual Input x Function FAB5 Virtual Input x Name --- --- --- F200 "Virtual Input 1 " FAC9 Virtual Input x Programmed Type FACA Virtual Input x Events FACB Virtual Input x Reserved (3 items) --- --- --- F001 0 FACE
FAE8
FB02 FB1C
FB36
FB50 FB6A
FB84
FB9E FBB8 FBD2 FBEC
FC06
FC20 FC3A
FC54
FC6E
FC88 FCA2 FCBC FCD6
FCF0 FD0A FD24 FD3E FD58 FD72 FD8C FDA6 FDC0
FDDA
...Repeated for module number 2 ...Repeated for module number 3 ...Repeated for module number 4 ...Repeated for module number 5 ...Repeated for module number 6 ...Repeated for module number 7 ...Repeated for module number 8 ...Repeated for module number 9 ...Repeated for module number 10 ...Repeated for module number 11 ...Repeated for module number 12 ...Repeated for module number 13 ...Repeated for module number 14 ...Repeated for module number 15 ...Repeated for module number 16 ...Repeated for module number 17 ...Repeated for module number 18 ...Repeated for module number 19 ...Repeated for module number 20 ...Repeated for module number 21 ...Repeated for module number 22 ...Repeated for module number 23 ...Repeated for module number 24 ...Repeated for module number 25 ...Repeated for module number 26 ...Repeated for module number 27 ...Repeated for module number 28 ...Repeated for module number 29 ...Repeated for module number 30 ...Repeated for module number 31 ...Repeated for module number 32
0 to 1
0 to 1 0 to 1
--- 1 F102 0 (Disabled)
--- 1 F127 0 (Latched)
--- 1 F102 0 (Disabled)
55
Modbus Memory Map Format Codes
Format Name Format Type/Bitmask Format Definition
F001 UINT16 UNSIGNED 16 BIT INTEGER F003 UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register. Low order word is stored in the second register.
F013 POWER_FACTOR POWER FACTOR (SIGNED 16 BIT INTEGER)
Positive values indicate lagging power factor; negative values indicate leading.
F050 UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January 1, 1970. F060 FLOATING_POINT IEEE FLOATING POINT (32 bits) F072 HEX6 6 BYTES - 12 ASCII DIGITS F102 ENUMERATION DISABLED/ENABLED
0 Disabled
1 Enabled F106 ENUMERATION PHASE ROTATION
0 ABC
1 ACB F108 ENUMERATION OFF/ON
0 Off
1 On F118 ENUMERATION WAVEFORM CAPTURE MODE
0 Automatic Overwrite
1 Protected F126 ENUMERATION NO/YES CHOICE
0 No
1 Yes F127 ENUMERATION LATCHED OR SELF-RESETTING
0 Latched
1 Self-Reset F131 ENUMERATION FORCED CONTACT OUTPUT STATE
0 Disabled
1 Energized
2 De-energized
3 Freeze F144 ENUMERATION FORCED CONTACT INPUT STATE
0 Disabled
1 Open
2 Closed F176 ENUMERATION SYNCHROCHECK DEAD SOURCE SELECT
0 None
1 LV1 and DV2
2 DV1 and LV2
3 DV1 or DV2
4 DV1 xor DV2
5 DV1 and DV2 F200 TEXT40 40 CHARACTER ASCII TEXT
20 registers -16 Bits: 1st Char MSB, 2nd Char. LSB
56
F203 TEXT16 16 CHARACTER ASCII TEXT F204 TEXT80 80 CHARACTER ASCII TEXT F205 TEXT12 12 CHARACTER ASCII TEXT F300 UINT16 FLEXLOGIC BASE TYPE (6 bit type)
The flexlogic BASE type is 6 bits and is combined with a 9 bit descriptor and 1 bit for protection element to form a 16 bit value. The combined bits are of the form : PTTTTTTDDDDDDDDD where P bit if set, indicates that the flexlogic type is associated with a protection element state and T represents bits for the BASE type, and D represents bits for the descriptor. The values in square brackets indicate the base type with P prefix [PTTTTTT] and the values in round brackets
indicate the descriptor range. [0] Off(0) this is boolean FALSE value [0] On (1)This is boolean TRUE value [2] CONTACT INPUTS (1 - 96) [3] CONTACT INPUTS OFF (1-96) [4] VIRTUAL INPUTS (1-64) [6] VIRTUAL OUTPUTS (1-64) [10] CONTACT OUTPUTS VOLTAGE DETECTED ( 1-64) [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64) [12] CONTACT OUTPUTS CURRENT DETECTED (1-64) [13] CONTACT OUTPUTS CURRENT OFF DETECTED (1-64) [14] REMOTE INPUTS (1-32) [28] INSERT (Via Keypad only) [32] END [34] NOT (1 INPUT) [36] 2 INPUT XOR (0) [38] LATCH SET/RESET (2 INPUTS) [40] OR (2-16 INPUTS) [42] AND (2-16 INPUTS) [44] NOR (2-16 INPUTS) [46] NAND (2-16 INPUTS) [48] TIMER (1-32) [50] ASSIGN VIRTUAL OUTPUT (1 - 64) [52] SELF-TEST ERROR (See F141 for range) [56] ACTIVE SETTING GROUP (1-8) [62] MISCELLANEOUS EVENTS (See F146 for range)
[64-127] ELEMENT STATES (Refer to Memory Map Element States Section)
F500 UINT16 PACKED BITFIELD
First register indicates I/O state with bits 0(MSB)-15(LSB) corresponding to I/0
state 1-16. Second register indicates I/O state with bits 0-15 corresponding to I/0
state 17-32 (if required). Third register indicates I/O state with bits 0-15
corresponding to I/0 state 33-48 (if required). Fourth register indicates I/O state
with bits 0-15 corresponding to I/0 state 49-64 (if required). The number of
registers required is determined by the specific data item.
A bit value of 0 = Off, 1 = On
F701 BITFIELD SRCx Node Internal Diagnostics Bit Mask
0 Power-on Self Test Error Detected 1 Built-In-Test Error Detected 2 Invalid Data Detected 3 Jamb sync occurred over threshold 4 Invalid node configuration detected 5 Invalid CRC check of node firmware
57
6 IButton Missing 7 EEPROM Configuration Invalid 8 Not Used 9 Not Used 10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15 Not Used
F702 BITFIELD SRCx Node System Diagnostics 1
0 Node not receiving a broadcast message from CPU A 1 Node not receiving a broadcast message from CPU B 2 No link pulse from CPU A 3 No link pulse from CPU B 4 Invalid system frequency received from CPU A 5 Invalid system frequency received from CPU B 6 Invalid IOC pickup setting multiplier received from CPU A 7 Invalid IOC pickup setting multiplier received from CPU B 8 Invalid ST setting received from CPU A 9 Invalid ST setting received from CPU B 10 Invalid GF setting received from CPU A 11 Invalid GF setting received from CPU B 12 Invalid command received from CPU A 13 Invalid command received from CPU B 14 CPU A command not completed due to arbitration 15 CPU B command not completed due to arbitration
F703 BITFIELD SRCx Node System Diagnostics 2
0 CPU A command timed out 1 CPU B command timed out 2 Node synch not locked 3 Unknown Message Received on Port 0 4 Unknown Message Received on Port 1 5 Not Used 6 Not Used 7 Not Used 8 Not Used 9 Not Used 10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15 Not Used
F704 BITFIELD SRCx Node Hardware Diagnostics
0 Secondary Control Power 1 Not Used 2 Not Used 3 Not Used 4 AD AIOC Failure 5 Node Not Calibrated 6 Not Used
58
7 Not Used 8 Not Used 9 Control_Power1_Status 10 Control_Power2_Status 11 App Flash CRC Fail 12 Boot Flash CRC Fail 13 Option Box Failure 14 Not Used 15 Not Used
F705 BITFIELD SRCx NodeProt Protection Function Configuration
0 Ground Fault Protection Enabled 1 Instantaneous Overcurrent Protection Enabled 2 Short Time Protection Enabled 3 Switchable ST/IOC Protection Enabled/Disabled 4 Switchable GF 5 Not Used 6 Not Used 7 Not Used 8 Not Used 9 Not Used 10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15 Not Used
F706 BITFIELD SRCx Reflected CPU Diagnostics
0 CPU A is using the hardware clock 1 CPU A is not receiving data from one or more nodes 2 CPU A Identifier 3 CPU A Running Flex Logic 4 CPU B Running Flex Logic 5 Not Used 6 Not Used 7 Not Used 8 CPU B is using the hardware clock 9 CPU B is not receiving data from one or more nodes 10 CPU B Identifier 11 CPU A Running Flex Logic 12 CPU B Running Flex Logic 13 Not Used 14 Not Used 15 Not Used
F707 BITFIELD SRCx Reflected CPU Commands
0 No Op 1 Open 2 Close 3 Trip 4 Network Interlock 5 Reset Interlock 6 Light LED 7 ATO Mode
59
8 Start Firmware Download 9 Switch Firmware 10 Cancel Firmware Download 11 Ignore CPU Message 12 Firmware Packet Present 13 Flux Shifter Open 14 Flux Shifter Trip 15 Not Used
F708 BITFIELD SRCx Node Physical Status
0 Breaker Contacts Open 1 Breaker Contacts Closed 2 Lockout 3 Closing Spring Charged 4 Primary Connected 5 Primary Disconnected 6 Secondary Connected 7 Door Interlock 8 Analog IOC 9 Not Used 10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15 Not Used
F709 BITFIELD SRCx Node Logic and Trip Status
0 Synchronization Source Bit 0 1 Synchronization Source Bit 1 2 Download Source Bit 0 3 Download Source Bit 1 4 Download Complete 5 Test Mode 6 GF Suspend 7 Not Used 8 Trip Flag 9 Trip due to LT 10 Trip due to ST 11 Trip due to GF 12 Trip due to IOC 13 Phase Indicator Bit 0 14 Phase Indicator Bit 1 15 Not Used
F711 ENUMERATION SRCx Long Time Delay Band Setting
0 BAND 1 1 BAND 2 2 BAND 3 3 BAND 4
F712 ENUMERATION SRCx Breaker Connection
0 Forward 1 Reverse
F713 ENUMERATION Delay Band Settings
0 BAND 1
60
1 BAND 2 2 BAND 3 3 BAND 4 4 BAND 5 5 BAND 6 6 BAND 7
F714 ENUMERATION SRCx Ground Fault Protection or Alarm Select
0 Trip 1 Alarm
F715 ENUMERATION UL or ANSI
0 UL 1 ANSI
F716 ENUMERATION Product Type
0 Low Voltage Switchgear 1 Medium Voltage Switchgear 2 Paralleling Switchgear
F717 ENUMERATION CPU Identifier
0 CPU A 1 CPU B
F718 ENUMERATION IOC Protection Type
0 Disabled 1 Enabled
F719 ENUMERATION SRCx PT Wiring
0 None 1 PT Rating 600V Delta 2 PT Rating 600V Wye 3 PT Rating 480V Delta 4 PT Rating 480V Wye 5 PT Rating 240V Delta 6 PT Rating 208V Wye
F722 UINT32 Node 0-29 Bit Field Vector
0 Bit field representing a 0 or 1 for Node 0 1 Bit field representing a 0 or 1 for Node 1 2 Bit field representing a 0 or 1 for Node 2 3 Bit field representing a 0 or 1 for Node 3 4 Bit field representing a 0 or 1 for Node 4 5 Bit field representing a 0 or 1 for Node 5 6 Bit field representing a 0 or 1 for Node 6 7 Bit field representing a 0 or 1 for Node 7 8 Bit field representing a 0 or 1 for Node 8 9 Bit field representing a 0 or 1 for Node 9 10 Bit field representing a 0 or 1 for Node 10 11 Bit field representing a 0 or 1 for Node 11 12 Bit field representing a 0 or 1 for Node 12 13 Bit field representing a 0 or 1 for Node 13 14 Bit field representing a 0 or 1 for Node 14 15 Bit field representing a 0 or 1 for Node 15 16 Bit field representing a 0 or 1 for Node 16 17 Bit field representing a 0 or 1 for Node 17 18 Bit field representing a 0 or 1 for Node 18 19 Bit field representing a 0 or 1 for Node 19 20 Bit field representing a 0 or 1 for Node 20
61
21 Bit field representing a 0 or 1 for Node 21 22 Bit field representing a 0 or 1 for Node 22 23 Bit field representing a 0 or 1 for Node 23 24 Bit field representing a 0 or 1 for Node 24 25 Bit field representing a 0 or 1 for Node 25 26 Bit field representing a 0 or 1 for Node 26 27 Bit field representing a 0 or 1 for Node 27 28 Bit field representing a 0 or 1 for Node 28 29 Bit field representing a 0 or 1 for Node 29 30 Not Used 31 Not Used
F726 ENUMERATION SRCX curve type
0 Inverse time curve 1 Constant time curve
F727 ENUMERATION SRCX Trip or Open setting
0 Open and don't activate lockout 1 Trip and activate lockout
F728 BITFIELD Option Bit Vectors F732 ENUMERATION ZSI Option
0 ST ZSI 1 GF ZSI 2 ST and GF ZSI
F733 ENUMERATION ZSI Zone Tier Settings
0 ZSI Tier 0 1 ZSI Tier 1 2 ZSI Tier 2 3 ZSI Tier 3
F734 ENUMERATION Contact IO Debounce values
0 Disabled 1 Enabled_00016 2 Enabled_00104 3 Enabled_04088 4 Enabled_32760
F735 ENUMERATION Multipoint delay band settings
0 BAND 1 1 BAND 2 2 BAND 3 3 BAND 4 4 BAND 5 5 BAND 6 6 BAND 7
F736 UINT32 Contact Input Configuration Low Vector
0 0 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 1 1 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 2 2 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 3 3 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 4 4 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 5 5 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 6 6 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 7 7 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 8 8 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 9 9 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
62
10 10 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 11 11 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 12 12 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 13 13 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 14 14 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 15 15 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 16 16 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 17 17 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 18 18 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 19 19 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 20 20 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 21 21 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 22 22 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 23 23 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 24 24 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 25 25 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 26 26 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 27 27 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 28 28 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 29 29 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 30 30 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 31 31 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
F737 UINT32 Contact Input Configuration High Vector
0 32 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 1 33 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 2 34 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 3 35 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 4 36 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 5 37 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 6 38 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 7 39 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 8 40 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 9 41 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 10 42 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 11 43 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 12 44 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 13 45 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 14 46 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 15 47 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 16 48 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 17 49 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 18 50 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 19 51 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 20 52 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 21 53 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 22 54 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 23 55 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 24 56 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 25 57 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 26 58 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 27 59 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 28 60 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
63
29 61 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 30 62 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output 31 63 - I/O x + (bit number) Input, 1 - I/O x + (bit number) Output
F738 ENUMERATION Option String Authentication Status
0 New and Old Both Option strings Invalid 1 Using Valid New Option String 2 Using Valid Old Option String
64
Loading...