The following important highlighted information appears
throughout this document to warn of potential hazards or
to call attention to information that clarifies a procedure.
Carefully read all instructions and become familiar with
the devices before trying to install, operate, service or
maintain this equipment.
Indicates a hazardous situation that, if not avoided, will
result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could
result in death or serious injury.
Failure to comply with these instructions may result in
product damage.
TRADEMARKS
EntelliGuard® WavePro®
Power Break® Power +®
MicroVersaTrip® EPIC®
ProTrip®
WARRANTY
This document is based on information available at the
time of its publication. While efforts have been made to
ensure accuracy, the information contained herein does
not cover all details or variations in hardware and
software, nor does it provide for every possible
contingency in connection with installation, operation,
and maintenance. Features may be described herein that
are not present in all hardware and software systems. GE
Industrial Solutions assumes no obligation of notice to
holders of this document with respect to changes
subsequently made. GE Industrial Solutions makes no
representation or warranty, expressed, implied, or
statutory, with respect to, and assumes no responsibility
for the accuracy, completeness, sufficiency, or usefulness
of the information contained herein. No warrantees of
merchantability or fitness for purpose shall apply.
Contact your local sales office if further information is
required concerning any aspect of EntelliGuard G, AKR,
Power Break, Power Break II and WavePro circuit breaker
operation or maintenance.
Indicates important information that must be
remembered and aids in job performance.
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
SECTION 1. General Information ................................................................................................................................................................ 1
Front Panel Display ............................................................................................................................................................................................................................ 1
Menu Access .......................................................................................................................................................................................................................................... 2
GTU Order Code ................................................................................................................................................................................................................................... 4
Installing the Setup Software .................................................................................................................................................................................................. 4
System Requirements ............................................................................................................................................................................................................ 4
Long Time Protection ........................................................................................................................................................................................................................ 7
Long Time Pickup ........................................................................................................................................................................................................................... 7
Long Time Delay ............................................................................................................................................................................................................................. 7
Thermal Long Time Overcurrent ............................................................................................................................................................................................ 7
Fuse Shaped Steep Long Time Overcurrent .................................................................................................................................................................... 8
Short Time Protection ....................................................................................................................................................................................................................... 9
Short Time Pickup .......................................................................................................................................................................................................................... 9
Short Time Delay ......................................................................................................................................................................................................................... 10
Short Time Slope .......................................................................................................................................................................................................................... 10
WaveForm Recognition vs. Peak Sensing ...................................................................................................................................................................... 11
Reduced Energy Let Through (RELT) ................................................................................................................................................................................. 11
Current Alarm................................................................................................................................................................................................................................ 13
Zone Selective Interlocking ......................................................................................................................................................................................................... 14
Making Current Release (MCR) ............................................................................................................................................................................................. 16
High Set Instantaneous Protection (HSIOC) .................................................................................................................................................................. 16
Voltage Unbalance ..................................................................................................................................................................................................................... 17
Current Unbalance ..................................................................................................................................................................................................................... 17
Zero Voltage Trip ......................................................................................................................................................................................................................... 17
Power Reversal Relay................................................................................................................................................................................................................ 18
Power Direction Setup......................................................................................................................................................................................................... 18
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
SECTION 3. Setting up the Trip Unit ....................................................................................................................................................... 22
Fan/Command Close Control ................................................................................................................................................................................................ 19
Bell Alarm Accessory ....................................................................................................................................................................................................................... 20
Bell Alarm with Lock-out Accessory Configuration Setup (applies to Power Break II and WavePro Trip Units only) ............. 20
Bell Alarm Operation – EntelliGuard G breakers ......................................................................................................................................................... 20
Digital Input Relays .......................................................................................................................................................................................................................... 21
Long Time Pickup .............................................................................................................................................................................................................................. 22
Long Time Delay ................................................................................................................................................................................................................................ 22
Short Time Pickup ............................................................................................................................................................................................................................. 22
Short Time Delay ............................................................................................................................................................................................................................... 22
Short Time Slope ............................................................................................................................................................................................................................... 23
Zone Selective Interlocking Setup ............................................................................................................................................................................................ 26
Zone Selective Interlock Short Time (ST) Setup ................................................................................................................................................................. 27
Zone Selective Interlock Ground Fault Setup ..................................................................................................................................................................... 27
Voltage Unbalance Relay ............................................................................................................................................................................................................. 27
Zero Voltage Tripping ..................................................................................................................................................................................................................... 28
Current Unbalance Relay.............................................................................................................................................................................................................. 28
Power Reversal................................................................................................................................................................................................................................... 29
Output Relay – Group 1 ................................................................................................................................................................................................................. 29
Output Relay – Group 2 ................................................................................................................................................................................................................. 29
Output Relay – Group 3 ................................................................................................................................................................................................................. 29
Output Relay – Group 4 and 5 .................................................................................................................................................................................................... 30
Output Relay – Group 6 ................................................................................................................................................................................................................. 30
Output Relay – Group 7 ................................................................................................................................................................................................................. 30
Output Relay – Groups 9, 10 and 11 ....................................................................................................................................................................................... 31
Digital Input Configuration .......................................................................................................................................................................................................... 31
Current Alarms ................................................................................................................................................................................................................................... 31
Neutral Pole (EntelliGuard G only) ............................................................................................................................................................................................ 32
Bell Alarm Lockout (PBII and WavePro only) ....................................................................................................................................................................... 32
Bell Alarm .............................................................................................................................................................................................................................................. 32
Power Demand Interval ................................................................................................................................................................................................................. 33
PT Voltage ............................................................................................................................................................................................................................................. 33
Power Direction ................................................................................................................................................................................................................................. 33
Frequency ............................................................................................................................................................................................................................................. 34
SECTION 7. Trip Unit Integration ............................................................................................................................................................. 45
SECTION 8. Serial Communication ......................................................................................................................................................... 48
Date and Time .................................................................................................................................................................................................................................... 34
Language ............................................................................................................................................................................................................................................. 34
Current Metering Display ............................................................................................................................................................................................................. 36
External CT Current Metering Display (EntelliGuard G only) ...................................................................................................................................... 36
Voltage Metering Display ............................................................................................................................................................................................................. 36
Power Metering Display: PH –PH .............................................................................................................................................................................................. 37
Power Metering Display—PH—N .............................................................................................................................................................................................. 37
Energy Metering Display ............................................................................................................................................................................................................... 37
Frequency Metering Display ....................................................................................................................................................................................................... 37
Power Factor Metering Display ................................................................................................................................................................................................. 37
Settings Status Screen................................................................................................................................................................................................................... 38
Pickup Status Messages ............................................................................................................................................................................................................... 38
Breaker Status Indications .......................................................................................................................................................................................................... 39
RELT Status Indications ................................................................................................................................................................................................................. 40
Communication Settings .............................................................................................................................................................................................................. 41
Long Time Trip Event Messages ............................................................................................................................................................................................... 42
Short Time Trip Event Messages .............................................................................................................................................................................................. 42
Modbus Baud Rate and Port Configuration .................................................................................................................................................................. 48
Modbus Function Codes .......................................................................................................................................................................................................... 49
Modbus RTU Message Format ............................................................................................................................................................................................. 50
EntelliGuard Trip Unit Function Code ..................................................................................................................................................................................... 50
Function Code 03H ..................................................................................................................................................................................................................... 51
Function Code 04H ..................................................................................................................................................................................................................... 51
Function Code 05H ..................................................................................................................................................................................................................... 51
Function Code 06H ..................................................................................................................................................................................................................... 52
Function Code 10H ..................................................................................................................................................................................................................... 52
Function Code 20H ..................................................................................................................................................................................................................... 53
Step 1: Set up the Serial Port on the Master Device .................................................................................................................................................. 53
Step 2: Configure the Communication Settings on the Trip Unit: Baud Rate, Parity, Stop Bits, Modbus Slave Address/ID 54
Step 3: Supply 24VDC to the Trip Unit, and Connect the Trip Unit to the Computer ............................................................................... 54
Step 4: Configure the Master’s Communication Parameters ............................................................................................................................... 54
Step 5: Attempt to Communicate with the Device .................................................................................................................................................... 54
Profibus System Concept.............................................................................................................................................................................................................. 55
Communication Setup and Station Addresses ................................................................................................................................................................. 55
Profibus GTU DP Cyclic Data ....................................................................................................................................................................................................... 56
Battery Function ................................................................................................................................................................................................................................ 58
Rating Plug Removal and Replacement ............................................................................................................................................................................... 59
Other General Troubleshooting Issues ............................................................................................................................................................................. 61
Trip Unit Removal and Replacement ...................................................................................................................................................................................... 63
Power Break I and Power Break II Insulated Case Circuit Breakers ................................................................................................................. 63
Trip Unit Removal ................................................................................................................................................................................................................... 63
Trip Unit Reinstallation ......................................................................................................................................................................................................... 64
AKR (225 A to 5000 A Frames) Circuit Breakers ........................................................................................................................................................... 64
EntelliGuard G Circuit Breaker Installation ..................................................................................................................................................................... 65
Trip Unit Removal (Figure 13-4 through Figure 13-7).......................................................................................................................................... 65
Trip Unit Reinstallation ......................................................................................................................................................................................................... 65
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
TABLE OF FIGURES
Figure 1-1: EntelliGuard G Trip Units .............................................................................................................................................................................................. 1
Figure 1-2: Power Break II and WavePro Trip Units ............................................................................................................................................................... 2
Figure 1-3: Power Break I, AK, AKR, Conversion Kit Trip Units .......................................................................................................................................... 2
Figure 1-4: EntelliGuard G Trip Units .............................................................................................................................................................................................. 2
Figure 1-5: Trip Unit Keypad and Functions ............................................................................................................................................................................... 2
Figure 2-1: Long Time Pickup Settings .......................................................................................................................................................................................... 7
Figure 2-2: Long Time Delay Settings ............................................................................................................................................................................................ 7
Figure 2-3: Short Time Pickup Time Current Curve................................................................................................................................................................. 9
Figure 2-4: Short Time Delay ........................................................................................................................................................................................................... 10
Figure 2-6: Voltage Conditioner Plate Wiring — Wye ......................................................................................................................................................... 18
Figure 2-7: Voltage Conditioner Plate Wiring — Delta ....................................................................................................................................................... 19
Figure 3-1: Short Time Slope ........................................................................................................................................................................................................... 23
Figure 3-3: Ground Fault Sum Slope, Option 3 ...................................................................................................................................................................... 25
Figure 7-1: RELT Connection when Using Positive Feedback from EntelliGuard TU Trip Unit ...................................................................... 45
Figure 7-2: RELT Connection Without Positive Feedback from EntelliGuard TU Trip Unit .............................................................................. 45
Figure 7-4: Incorrect and Correct TIM1 Wiring ...................................................................................................................................................................... 46
Figure 7-5: Six Trip Units Connected in Parallel to a Single Downstream TIM1 Input Pair ............................................................................. 47
Figure 7-6: TIM1 Zone Wiring Diagram ...................................................................................................................................................................................... 47
Figure 8-1: RS-232 and RS-485 Connections ......................................................................................................................................................................... 49
Figure 8-2: Wiring for Shield Grounding .................................................................................................................................................................................... 50
Figure 9-1: Profibus Communication Network ...................................................................................................................................................................... 55
Figure 11-1: Trip Unit with Rating Plug Removed................................................................................................................................................................. 59
Figure 13-1: Removing the Old Trip Unit ................................................................................................................................................................................... 64
Figure 13-2: Circuit Breaker without Trip Unit ........................................................................................................................................................................ 64
Figure 13-3: Installing the New Trip Unit ................................................................................................................................................................................... 65
Figure 13-4: Trip Unit Removal Sequence, Step A ................................................................................................................................................................ 65
Figure 13-5: Trip Unit Removal Sequence, Step B ................................................................................................................................................................ 65
Figure 13-6: Trip Unit Removal Sequence, Step C ................................................................................................................................................................ 65
Figure 13-7: Trip Unit Removal Sequence, Step D ............................................................................................................................................................... 65
Table 2-1: Nominal Time Delays for Thermal Shaped Long Time Bands ....................................................................................................................8
Table 2-2: Nominal Clearing Times for Fuse Shaped Long Time Bands ......................................................................................................................9
Table 2-3: Short Time Commit Times ........................................................................................................................................................................................... 10
Table 2-4: Short Time Settings by Breaker Type and Frame ........................................................................................................................................... 10
Table 2-5: Short Time Delay Settings ........................................................................................................................................................................................... 10
Table 2-6: Maximum Instantaneous for Power Break I, Power Break II, WavePro and AKR Trip Units .................................................... 11
Table 2-7: Instantaneous Thresholds for Power Break I, Power Break II, WavePro and AKR Trip Units .................................................. 12
Table 2-10: Voltage Unbalance Settings ................................................................................................................................................................................... 17
Table 2-11: Current Unbalance Settings.................................................................................................................................................................................... 17
Table 2-12: Under Voltage Settings .............................................................................................................................................................................................. 17
Table 2-13: Over Voltage Settings ................................................................................................................................................................................................. 18
Table 2-14: Power Reversal Settings ........................................................................................................................................................................................... 18
Table 8-1: Function Code 03H Example ..................................................................................................................................................................................... 51
Table 8-2: Modbus Packet Format for Function Code 03H .............................................................................................................................................. 51
Table 8-3: Modbus Packet Format for Function Code 04H .............................................................................................................................................. 51
Table 8-4: Modbus Packet Format for Function Code 05H .............................................................................................................................................. 52
Table 8-5: Modbus Packet Format for Function Code 06H .............................................................................................................................................. 52
Table 8-6: Modbus Packet Format for Function Code 10H .............................................................................................................................................. 52
Table 8-7: Modbus Packet Format for Function Code 20 ................................................................................................................................................. 53
Table 8-8: Slave Responses to Errors .......................................................................................................................................................................................... 53
Table A-8: Frame Rating (amperes) Digit 3 for TYPE A Conversion Kits ..................................................................................................................... 67
Table A-20: PowerBreak I & II Digits 6 & 7 ................................................................................................................................................................................ 70
Table A-21: EntelliGuard G ANSI and UL Low-cost ACB Digits 6 & 7 .......................................................................................................................... 70
Table A-22: CVCB MTU IEC Medium Voltage OC Protection Digits 6 & 7 .................................................................................................................. 70
Table A-23: Zone Selective Interlocking Digit 8 ..................................................................................................................................................................... 70
Table A-24: Advanced Features and Communications Col. 9 ....................................................................................................................................... 71
Table A-26: Original or Replacement Trip Unit Col. 11 ....................................................................................................................................................... 71
Table B-1: EntelliGuard G ACB Rating Plug Nomenclature .............................................................................................................................................. 72
Table C-4: Discrete Inputs from GTU ........................................................................................................................................................................................... 89
Table D-1: ST Band Comparisons.................................................................................................................................................................................................. 90
Table E-1: GTU-C Power Break I and AKR Trip Units ........................................................................................................................................................... 91
Table E-2: GTU-D PowerBreak II and WavePro ...................................................................................................................................................................... 91
Table E-4: Pin Out for Legacy Breakers ..................................................................................................................................................................................... 93
Table E-5: Pin Out for GTUTK20 Test Kit..................................................................................................................................................................................... 94
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
General Information
SECTION 1. GENERAL INFORMATION
WARNING
(EntelliGuard G only)
Pin Connector on back of all trip
The EntelliGuard TU Trip Unit is an electronic device that
interfaces with a circuit breaker. It monitors current and/or
voltage and trips the breaker in the event of an overcurrent or voltage related condition. It also provides
protective relay functions, advanced metering, diagnostic
features, and communications. The Trip Unit can be
removed or replaced in the field by de-energizing and
removing the cover of the circuit breaker.
The Trip Unit drives the circuit breaker flux shifter to
provide the electromechanical tripping function. A user
interface is provided on the front panel to allow adjustment
of the Trip Unit’s parameters.
EntelliGuard TU Trip Unit has been designed to be plug and
play compatible with previous generation trip units,
MicroVersa Trip, MVT RMS-9, EPIC, MVT Plus, MVT PM,
Power+, and ProTrip. In addition to trip unit upgrades,
Figure 1-1: EntelliGuard G Trip Units
40 Pin Connector on top
conversion kits are offered to upgrade ANSI type legacy
breakers.
FRONT PANEL DISPLAY
The Trip Unit includes a graphical Liquid Crystal Display
(LCD). The front panel is similar to those shown in
Figure 1-1 through Figure 1-5.
When the trip unit is energized the LCD normally displays a
menu of navigation options. If the trip unit is powered from
an external DC supply, a backlight is provided and remains
on. If the trip unit is powered from the circuit breaker’s
Current Transformers alone there is no backlight, but the
navigation menu is available as long as current flow is at
least 20% of the breaker’s sensor rating. If the display is
blank, pressing any key will turn on the menu using battery
power.
Catalog Number
LCD Screen
Navigation Panel
unit types, see images below for
specifics by breaker.
BOX SIZE AND CONNECTOR CONFIGURATION COMMONALITY DOES NOT SUGGEST INTERCHANGEABILITY BETWEEN
POWERBREAK II AND WAVEPRO OR POWERBREAK 1 AND AKR. THE OPTIONS ON THESE TRIP UNITS ARE DIFFERENT AND
WILL CAUSE THEM TO BEHAVE AND OPERATE
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
General Information
WARNING
IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Failure to comply with these instructions could result
in death or serious injury.
Primary Current flow:
+24 VDC control power
Internal battery power
NOTICE
If 24 VDC supply drops below 22V, expect the
backlight of the trip unit to dim or shut off. In order to
ensure this does not happen, have a reliable,
consistent source of 24VDC.
BIM
RELT
ZSI
WFR
ELECTRICAL REQUIREMENTS
Ensure only qualified personnel install, operate, service
and maintain all electrical equipment.
EQUIPMENT INTERFACES
PowerBreak I, PowerBreak II, WavePro, AK, AKR, Conversion
Kits (for GE and other manufacturer breakers) and
EntelliGuard G Circuit Breakers.
Trip units do not require direct connections to the
equipment. All trip unit connections external to the breaker
are made through the circuit breaker secondary
disconnect.
PowerBreak I, PowerBreak II, WavePro, AKR and
EntelliGuard G Trip Units are powered from three different
sources:
•
sufficient power to energize the LCD when at least 20%
of the sensor's ampere rating is flowing.
•
the circuit breaker’s secondary disconnect, or from the
GTUTK20 test kit, or from the portable battery pack,
(TVPBP and TVPBPACC). Each GTU draws 90mA
maximum.
•
when any keypad key is pressed. Battery power
automatically turns off 20 sec after the last keypad
press. The battery power supply is disabled when any
current over 20% of the sensor rating is sensed through
the current sensors. Breaker status (open/closed) is not
reported under battery power.
Functions that require external 24 VDC:
• Communication (Modbus and Profibus)
• Zone Selective Interlocking—(Instantaneous only)
• WaveForm Capture
• Event log with time stamp
• Backlight
• Advanced Metering
• Relaying
• Input/output Contacts
• RELT – Reduced Energy Let Through
Breaker current sensors provide
. This is supplied externally, via
: Powers the unit temporarily
The following trip unit interfaces are available at the
secondary disconnect:
• Serial Communications (RS-485)
• Zone Selective Interlocking digital input and output
• Digital Inputs (2)
• Relay Outputs (2)
• Fan control digital output (5000A WavePro and AKR)
• Remote Close digital output (EntelliGuard G with
Command Close Coils)
• Potential Transformer analog voltage Input
• Zero Sequence Current Transformer analog input
• 4th Pole Iron Core/Rogowski (neutral sensor) analog
input
The front panel test kit port provides an interface to the
GTUTK20 digital test kit. See DEH-4568A for additional
detail.
In addition, the MVT portable battery pack (TVPBP) can also
be used on the GTU using the TVPBPACC adaptor cable.
DEFINITIONS
: Breaker Interface Module (only on EntelliGuard G). This
is a non-volatile memory device on the circuit breaker that
defines the breaker’s configuration to the trip unit. The BIM
stores configuration information on the breaker sensor
rating, it’s interrupting capacity, and the agency
requirements (UL, IEC, ANSI) the breaker meets.
: Reduced Energy Let Through. A second
instantaneous trip function that can be temporarily
engaged during maintenance procedures to ensure the
breaker trips as quickly as possible to limit arc flash
damage.
: Zone Selective Interlocking: A wired signaling scheme
between cascaded breakers that enhances coordination
and can improve protection without impacting selectivity.
Available on Short Time, Ground Fault and Instantaneous.
: Wave Form Recognition is the algorithm used in the
EntelliGuard G adjustable selective instantaneous trip
element to discern between unfettered fault current and
3
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
General Information
WFC
Close and Latch Rating
HSIOC
In: Trip Plug Rating in amperes. This is the current rating of
Icw: Short Time Withstand Rating of a particular circuit
I
RMS
Making Current Release (MCR)
X
xlCT: Multiples of current sensor rating (non-dimensional)
GTU
Order Code
Representation
Digit 9
Advanced Features &
the high peak, low energy let-through current allowed by a
Table 1-1: GTU Nomenclature
current limiting fuse or circuit breaker while in the process
of melting or tripping. This algorithm allows the adjustable
selective instantaneous to be set low and yet be selective
in high prospective fault current systems. WFR allows
circuit breakers to trip instantaneously for faults within
their zone of protection while maintaining instantaneous
clearing times in the 3-3.5 cycle range, depending on
circuit breaker type, facilitating maximum arc flash
mitigation possible with no sacrifice in selectivity.
: Waveform Capture – an optional feature that
captures an oscillographic record of system current and
voltage at the moment the breaker trip unit is triggered.
Digit 1 and 2 EntelliGuard Trip Unit Form
Digit 3 Frame Rating (Amperes) Short
Circuit/Withstand
Digit 4 and 5 Sensor Rating (Amperes)
Digit 6 and 7 Overcurrent and Ground Fault
Protection Packages
Digit 8 Zone Selective Interlocking
Communications
Digit 10 Manual/Auto Trip Reset
circuit breaker can close into and successfully latch.
: High Set Instantaneous Overcurrent, also known as
an instantaneous Override. A fixed instantaneous
function that operates if the breaker experiences a fault
: the maximum fault current a
Digit 11 Original or Replacement Trip Unit
Digits 12, 13,
RESERVED (Future)
14, and 15
SETUP SOFTWARE
exceeding its Short Time Rating (Icw).
The EntelliGuard Setup Software provides a graphical user
the rating plug installed in the trip unit. This is the
maximum Long Time pick up a trip unit can have with a
specific plug installed. A sensor can be applied with plugs
between 37.5% or 40% to 100% of the sensor rating. Plugs
interface (GUI) to configure and monitor the operation of
EntelliGuard Trip Unit functions. The software allows you to
save setting files offline to be loaded or compared with
current settings. It provides a means of creating
documentation regarding all the trip unit settings.
are labeled in amperes.
The software also provides a tool to extract and view
breaker in amperes. The withstand rating is defined
differently within different standards, but it is always the
value of current that a circuit breaker can withstand for the
captured waveforms from EntelliGuard trip units equipped
with optional the Waveform Capture feature. This feature
also provides a means of determining harmonic content of
the power system.
maximum Short Time Delay before interrupting.
The EntelliGuard Setup software is available at no charge
: True RMS current measurement through a phase
: This is an instantaneous
override that will trip the circuit breaker if it is closed into a
fault exceeding the breaker’s close and latch rating.
: X is a multiplier that may be applied in front of any rating
value to denote a fraction of that rating. Ex: The Long Time
Pickup is may be set at 0.5X of In.
: Shorthand/abbreviation for EntelliGuard TU Trip Unit
GTU ORDER CODE
from either the GE EntelliGuard CD or the GE Industrial
Solutions web-site.
In on-line mode the tool is connected over communication
networks - Serial or Ethernet, you can communicate with
an EntelliGuard device in real-time.
In off-line (Disconnected) mode, a settings file can be
created for eventual downloading to the device.
Installing the Setup Software
The following minimum requirements must be met for the
EntelliGuard Setup software to operate on your computer.
Below is the breakdown of what each column of the GTU
order code represents. For specific possibilities see
Appendix A: GTU Nomenclature. Also, find the Rating Plug
order code in Appendix B: Rating Plug Nomenclature.
• Microsoft Windows™ 2000/XP/Vista/7 is installed and
running properly.
• Minimum of 20 mb of hard disk space.
• Minimum 256 mb of RAM (512 mb recommended)
• RS-232 and/or Ethernet communication port.
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
General Information
Installation Procedure
WAVEFORM CAPTURE
Follow the procedure below to install the EntelliGuard
Setup software in to your system.
• Click on the Setup Icon
• The First Screen will be the welcome screen as shown
below. Opt [Next] to proceed further
•The Next will be the "License Agreement" screen. Opt
[Next] to proceed further.
•The Next screen will show the system path where the
setup is getting installed by default. One can change
the desired system path for the setup program by
clicking on [Browse].
•The system will perform installation in the specified
location after checking for appropriate requirements.
This may take 10 to 15 seconds. Once Installation is
completed user will be prompted with a screen that
has a [Finish] option.
Upon successful installation of the EntelliGuard you can
view the application in either of two places
• As an Application short cut Icon on the desktop
• In Start > Programs > EntelliGuard TU >
EntelliGuard Setup
One can use either of the above to start up the application
on which, the Main Screen of the EntelliGuard Setup will be
launched.
For further, detailed instructions on how to add a site and
add a device via serial communication or Ethernet
communication, check the help section on the software.
RATING PLUGS & THE UNIVERSAL RATING PLUG
The EntelliGuard TU trip system is composed of trip units
and trip unit rating plugs along with the sensors and wiring
provided in the circuit breaker to support the trip. Rating
plugs are used to lower the Long Time adjustment range of
the sensor provided in the circuit breaker.
The EntelliGuard TU trip rating plugs are unique in that they
can be used with multiple trip units and circuit breakers
within a specific sensor range, rather than only with a
single specific sensor. The trip rating plug catalog number
identifies the rating as well as the minimum and maximum
sensor rating the plug may be used with. Appendix B lists
trip-rating plugs available for each sensor and their part
numbers and the two-digit codes used within the trip rating
plug catalog numbers to identify sensor current ratings.
ANSI and UL circuit breaker types use a fixed rating plug
with a marked ampere rating. Trip units use the current
sensors installed in the breaker.
A total of eight cycles are captured:
• Four pre-trigger.
• Four post-trigger.
24 VDC external power is required for waveform capture.
When waveform capture is executed, the following
channels will be captured simultaneously: Phase A current,
Phase B Current, Phase C Current, Phase N Current, Phase
L1 voltage, Phase L2 voltage, Phase L3 voltage.
WFC captures 48 samples per cycle, per phase, at 50 hz
and 40 samples per cycle at 60 hz – the same data it used
for its protection algorithms. The GE Setup Software
contains full Waveform retrieval and viewer capability. GE
offers the software free via web download. There is a
function in the software that allows you to clear captured
waveforms. The GTU stores only one waveform record at a
time.
There are COMTRADE format viewers available to interpret
the file downloaded from the trip unit, but the GE Setup
Software is able to display the waveform graphically.
Viewing the waveform capture is described in the setup
software. Currently, the software must be in
communication with the trip unit prior to and during the
event in order for the event to be captured. After the
capture the software will show a file is available. The user
then uses the software to request the file, which is
extracted from the trip unit. At that point the file can be
saved off for external use, or it can be opened for viewing
in the program’s waveform viewer.
Harmonic content is calculated from the waveform data by
the Setup Software. There is no harmonic content
calculation performed by the trip unit – the data is
extracted from the data set by the GE Setup software.
1. While a waveform capture data (in COMMTRADE format) is
in memory, a new event will overwrite the capture data
in memory. Whether the waveform capture is disabled
or not, no other event is entertained. Unless and until
the waveform is read and cleared by master by issuing
appropriate commands, any read of waveform capture
data will return the same first waveform, even if other
events have occurred in between.
2. When the Modbus master is reading captured waveform
data and a valid Event (trigger) occurs (for which the
waveform could be captured): This new event is
ignored. Since the trip unit already has an event
captured and hence responding for the same event,
trip unit will ignore the latest event (trigger). The trip
unit will start capturing the new waveform only after
Master has read the complete waveform AND issued a
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
General Information
Event
Waveform Capture Setpoint
Manual trigger over
communications
ON, OFF
Inst)
Protective relays
ON, OFF
Current alarm 1
ON, OFF
Current alarm 2
ON, OFF
NOTICE
SOFTWARE REVISION 08.00.23 AND GREATER:
displayed on the LCD.
command to clear the waveform data in trip unit
memory.
Table 1-2: Trigger WaveForm Capture Events
Over current (GF, ST, LT,
Event Logging
The trip unit keeps a log of the last 10 events:
• Over current trips
• Protective relay trips
• Shunt trip (PBII and Global EntelliGuard G Trip Units Only)
• Under voltage Release trip (PBII and Global EntelliGuard
G Trip Units Only)
• BIM Trip Unit Mismatch - Breaker Interface Module
(EntelliGuard G only)
If a BIM read fails the trip unit will not open the breaker,
instead it will modify its internal configuration to match the
AIC rating of the least capable breaker in the family. The
trip unit will periodically read the BIM after that, and on a
successful match the original settings will be restored.
While the BIM error persists a BIM Err message will be
ON, OFF
The following information is stored with each event:
• RMS currents
• Phase
• Type of trip
• Trip counter
• Time and date stamps (Trips are logged under self
power without time stamp. Events with time stamps are
only logged when +24 VDC control power is available.)
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
SECTION 2. PROTECTION
OVERCURRENT PROTECTION FUNCTIONS
The Trip Unit provides the following over current
protections:
response of a thermal magnetic circuit breaker. And
available i
4
t option adds 22 bands that simulate the
overcurrent response of fuses. The EntelliGuard circuit
breaker is able to use all 44 bands. Power Break I, Power
Break II, WavePro and AKR circuit breakers use the 19
lower thermal CB-type bands and the 22 fuse-type bands.
• Long Time (L)
Figure 2-2: Long Time Delay Settings
• Short Time (S)
• Instantaneous (I, H=high range)
• Reduced Energy Let Through Instantaneous (RELT)
• Ground Fault Internal Summation (G)
• Ground Fault CT External Summation (C, EntelliGuard G
only)
• Instantaneous Override (HSIOC)
• Making Current Release (MCR)
LONG TIME PROTECTION
Long Time Pickup
This setpoint establishes the breaker's nominal ampere
rating, xLT, as a fraction of the rating plug value, xIn:
xLT = LT multiplier x xIn
The adjustment range for long time pickup settings is 0.50
to 1.00 times xIn in steps of 0.05. The pickup value has a
10% tolerance. The band is drawn at 1/(1+10%) and 1/110%). The actual long time pickup is increased by 12% over
the nominal so that 100% nominal current may be carried
indefinitely. So a 1000 A setting is placed at 1120 A with the
minimum pickup drawn (left side of band) is 1088A, and the
maximum pickup (right side of band) is drawn at 1244A.
Figure 2-1 shows the Long Time pickup setting.
Figure 2-1: Long Time Pickup Settings
Thermal Long Time Overcurrent
2
The thermal I
T shape is similar to the typical curve of a
thermal magnetic circuit breaker and matches the shape
of many overcurrent devices used in industry today. The
typical shape and range of settings may be seen in Figure
2-2. The range of time delays is shown in Table 2-1 at
various multiples of nominal (100%) current setting. Drawn
bands also include a mechanical constant time to account
for circuit breaker operating and clearing time, which
causes the slight widening of the band evident at the lower
(right) end of the faster (lower) bands.
Long Time Delay
The trip unit provides up to 44 long time delay bands (only
on trip unit models starting with “J”). Not all circuit breakers
have all bands available. There are 22 bands using a
logarithmic type curve resembling the overcurrent
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
X =
1.5
1.5 6 6
7.2
7.2
10
10
Commit
Clear
Commit
Clear
Commit
Clear
Commit
Clear
Min CB
4.25
8.04
0.20
0.33
0.14
0.24
0.072
0.137
C-2
12.7
24.1
0.60
0.94
0.42
0.66
0.21
0.35
C-3
25.5
48.1
1.21
1.84
0.83
1.28
0.43
0.67
C-4
34.0
64.1
1.61
2.45
1.11
1.70
0.57
0.89
C-5
51.0
96.2
2.41
3.66
1.67
2.53
0.86
1.32
C-6
67.9
128
3.21
4.87
2.22
3.37
1.15
1.75
C-7
84.9
160
4.02
6.08
2.78
4.20
1.43
2.18
C-8
102
192
4.82
7.29
3.33
5.03
1.72
2.61
C-9
119
224
5.62
8.49
3.89
5.87
2.01
3.03
C-10
136
256
6.43
9.70
4.44
6.70
2.29
3.46
C-11
153
289
7.23
10.9
5.00
7.54
2.58
3.89
C-12
170
321
8.04
12.1
5.56
8.37
2.87
4.32
C-13
204
385
9.64
14.5
6.67
10.0
3.44
5.18
C-14
238
449
11.2
17.0
7.78
11.7
4.01
6.04
C-15
272
513
12.9
19.4
8.89
13.4
4.59
6.90
C-16
306
577
14.5
21.8
10.0
15.0
5.16
7.76
C-17
340
641
16.1
24.2
11.1
16.7
5.73
8.61
C-18
374
705
17.7
26.6
12.2
18.4
6.30
9.47
Max CB
408
769
19.3
29.1
13.3
20.0
6.88
10.3
Thermal Memory
The Long Time and Short Time pick up algorithm also includes a cooling cycle that keeps track of current if it oscillates in
and out of pick up range. This Thermal Memory is also active in case the circuit breaker trips on Long Time or Short Time to
account for residual heating in conductors. If a circuit breaker is closed soon after a Long Time trip or Short Time trip, a
subsequent trip may happen faster than indicated by the time current curve due to the residual cable Thermal Memory
effect. In trips without control power, the Thermal Memory is powered from the trip battery. The cooling algorithm requires
up to 14 minutes to fully reset to zero.
Table 2-1 shows the nominal clearing and commit times for X multipliers of nominal pickup.
Table 2-1: Nominal Time Delays for Thermal Shaped Long Time Bands
• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.
• Actual Long Time pickup is 112% of nominal pickup.
Fuse Shaped Steep Long Time Overcurrent
The optional steeper fuse characteristic is a straight line K=I
4
t shape for application in systems where fuses and circuit
breakers are used together. Twenty-two different time bands are available in each trip unit. Figure displays minimum and
maximum bands. Table 2-2 displays the nominal time delays for each of the 22 bands at various multiples of nominal
current pickup.
Drawn bands also include a constant time component, which accounts for the slight widening evident in the time current
curve at the lower (right) end of the faster (lower) time bands.
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
X =
1.5
1.5 6 6
7.2
7.2
10
10
Commit
Clear
Commit
Clear
Commit
Clear
Commit
Clear
Min F
0.67
1.54
0.025
0.085
0.025
0.085
0.025
0.085
F-2
2.0
4.40
0.025
0.085
0.025
0.085
0.025
0.085
F-3
3.6
7.98
0.025
0.085
0.025
0.085
0.025
0.085
F-4
5.6
12.5
0.025
0.085
0.025
0.085
0.025
0.085
F-5
8.1
18.0
0.032
0.100
0.025
0.085
0.025
0.085
F-6
11.2
25.0
0.044
0.13
0.025
0.085
0.025
0.085
F-7
15.1
33.8
0.059
0.16
0.028
0.094
0.025
0.085
F-8
20.0
44.7
0.078
0.20
0.038
0.114
0.025
0.085
F-9
26.1
58.4
0.102
0.26
0.049
0.14
0.025
0.085
F-10
33.8
75.4
0.13
0.32
0.064
0.17
0.025
0.085
F-11
43.3
96.8
0.17
0.41
0.082
0.21
0.025
0.085
F-12
55.3
123
0.22
0.51
0.104
0.26
0.028
0.092
F-13
70.2
157
0.27
0.64
0.13
0.33
0.036
0.109
F-14
88.9
198
0.35
0.81
0.17
0.40
0.045
0.13
F-15
112
251
0.44
1.01
0.21
0.50
0.057
0.16
F-16
141
316
0.55
1.26
0.27
0.62
0.072
0.19
F-17
178
397
0.69
1.58
0.34
0.78
0.090
0.23
F-18
224
499
0.87
1.98
0.42
0.97
0.113
0.28
Max-F
280
626
1.10
2.48
0.53
1.21
0.142
0.35
Table 2-2: Nominal Clearing Times for Fuse Shaped Long Time Bands
• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.
• Actual Long Time pickup is 112% of nominal pickup.
SHORT TIME PROTECTION
Figure 2-3: Short Time Pickup Time Current Curve
Short Time Pickup
The Short Time Pickup function establishes the current at
which short time trip is activated. Short Time Pickup is with
a multiple of the Long Time Pickup and the choices of
pickup settings are from 1.5 to 12.0 times the Long Time
setting, xLT, in steps of 0.5 xLT.
The maximum pickup depends on breaker type and frame
as shown in Table 2-3, below:
The Short Time Pickup value tolerance band is
approximately -9% to +11% of the set point based on a
10% current sensing accuracy with the pickup calculated
with 1/ (1+Tolerance). The time current curve of short time
pickup is shown in Figure 2-3.
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
Time Band
60 Hz
ANSI, UL489
50 Hz
ANSI, UL489
1
0.025 sec
0.030 sec
2
0.033 sec
0.040 sec
3
0.042 sec
0.050 sec
4
0.058 sec
0.060 sec
5
0.092 sec
0.090 sec
6
0.117 sec
0.120 sec
7
0.158 sec
0.160 sec
8
0.183 sec
0.180 sec
9
0.217 sec
0.220 sec
10
0.350 sec
0.350 sec
11
0.417 sec
0.420 sec
12
0.517 sec
0.520 sec
13
0.617 sec
0.620 sec
14
0.717 sec
0.720 sec
15
0.817 sec
0.820 sec
16
0.917 sec
0.920 sec
17
0.933 sec
0.940 sec
Breaker
Available Settings
conversion kits
AKR and WavePro 5000A
frame
OFF, 1.5 to 7, steps of 0.5
and 2
EntelliGuard G Frame 3
OFF, 1.5 to 10, steps of 0.5
Band
Time Delay
Commit Time
EntelliGuard G
50 Hz
60 Hz
Clear
60 Hz
Clear
50 Hz
1
Min.
0.030
0.025
0.080
0.085
2
2nd
0.040
0.033
0.088
0.093 3 3rd
0.050
0.042
0.097
0.102 4 4th
0.060
0.058
0.113
0.118
5
5th
0.110
0.092
0.147
0.152
6
6th
0.130
0.117
0.172
0.177 7 7th
0.180
0.158
0.213
0.218 8 8th
0.210
0.183
0.238
0.243
9
9th
0.240
0.217
0.272
0.277
10
10th
0.280
0.350
0.405
0.410
11
Max.
0.340
0.417
0.472
0.477
Slope OFF
Slope = 3
Slope = 1
Table 2-3: Short Time Commit Times
Figure 2-4: Short Time Delay
Short Time Slope
Table 2-4: Short Time Settings by Breaker Type and
Frame
The slope setting modifies the initial portion of the ST delay
band in the familiar “hockey stick” configuration. A setting
Power Break I, Power
Break II, WavePro, AKR
OFF, 1.5 to 9, steps of 0.5
of OFF puts the constant time band in effect, with no slope.
Slope settings of 1, 2, or 3 put progressively higher slope
values in effect. If the fault exceeds the sloped section of
the curve, the constant time band setting takes effect.
EntelliGuard G Frame 1
OFF, 1.5 to 12, steps of 0.5
Short Time Delay
The Short Time Delay setting consists of both a slope
setting and a fixed delay band setting. The slope and delay
are independently selectable. The slope setting consists of
2
T slopes (minimum (1), intermediate (2) and
three I
maximum (3)) and fixed delay. The fixed delay bands
consist of 11 constant time bands. The width of the bands
varies by circuit breaker and with frequency. See Table 2-4.
On all ANSI and IEC breakers, the Short Time can be
disabled by setting the Short Time Delay to “OFF”. Note that
if Instantaneous is set to “OFF” Short Time cannot be
turned off.
Table 2-5: Short Time Delay Settings
Band Setting
Time
• Short Time slope is forced to OFF when optional LT Fuse (i4t) curves are
in use.
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
Frame
(A)
ANSI (X In)
UL (X In)
With ST
W/O ST
With ST
W/O ST
800
15
10
15
10
1,600
15
10
15
10
2,000
15
10
15
10
2,500
13
10
3,000
13
10
3,200
13
10
4000 9 9 9 9
5000 7 7
INSTANTANEOUS PROTECTION
Adjustable Selective Instantaneous over current protection
causes an undelayed breaker trip when the chosen current
level and proper waveform is reached.
The pickup value may be set in steps of 0.5 xIn from 2.0 xIn
to 15 xIn and steps of 1 xIn from 15 xIn to a maximum of
30 xIn. Greater than 15xIn is available only in trips provided
with the “Extended Range Instantaneous” option on ANSI
EntelliGuard G circuit breakers.
The maximum possible setting depends on the trip unit
instantaneous option provided, the circuit breaker’s
withstand capability and whether or not ST has been
enabled.
When Instantaneous pickup is set above 15X without ST on,
ST pickup is automatically switched on Default delay is
automatically switched on at a minimum delay setting,
unless otherwise set by the user. This is only applicable to
EntelliGuard G.
Table 2-6: Maximum Instantaneous for Power Break I,
Power Break II, WavePro and AKR Trip Units
or current limiting circuit breaker while interrupting in a
current limiting manner. This allows the trip setting to be
set much lower than optimally peak sensing trips and
hence sensitive to lower arcing fault currents that could be
causing an arc flash event.
Reduced Energy Let Through (RELT)
The EntelliGuard TU trip unit’s RELT capability provides the
ultimate in user flexibility for wiring and controlling an
alternate Instantaneous setting for temporary use to
reduce personnel hazard.
All versions of the EntelliGuard TU trip units are available
with Reduced Energy Let-Through (RELT) Instantaneous
protection. This optional feature allows the trip unit’s
Instantaneous Protection pickup threshold to be
temporarily set lower when personnel are in close
proximity to the circuit breaker. In the event of a fault, the
trip unit will respond sooner, minimizing damaging arc
flash energy. Once personnel are safely clear of the area,
RELT is disengaged, returning the system to its normal
Instantaneous settings. The RELT setting is independent of
the normal adjustable selective Instantaneous. Even if the
normal instantaneous is not enabled, by turning on RELT
the instantaneous will then be enabled.
The Instantaneous pickup accuracy is +10%. On certain
ANSI trip units with the user-selectable switchable
instantaneous over current an additional value of OFF
appears at the end of the listing of numerical values. Note
that if Short Time Delay is set to off, you will not be able to
also turn off Instantaneous.
When Instantaneous pickup is set above the maximum
allowed for the CB without ST on, ST pickup is automatically
switched on at a default delay is automatically switched on
at a minimum delay setting.
WaveForm Recognition vs. Peak Sensing
WFR is the standard algorithm used in the normal
instantaneous trip function for all CB versions except
Power Break I. The WFR algorithm is specially designed to
optimize selectivity while achieving fast instantaneous
tripping of the circuit breaker. The algorithm’s
measurements act as a proxy for measuring energy and
hence are able to discern a fault current from a peak-letthrough current allowed to flow by a current limiting fuse
The pickup value may be set in steps of 0.5 xIn from 1.5 xIn
to 15 xIn or the maximum allowed instantaneous pickup
for the particular circuit breaker type, rating and size. The
RELT Instantaneous pick up clears fault current in 50
milliseconds or less. The maximum setting depends on the
trip unit catalog number, breaker type and frame, and
whether or not ST is enabled. See Table 8.
Clearing times for the various instantaneous functions vary
by circuit breaker. The RELT function clearing time is 0.042
seconds for EntelliGuard G at 60Hz and 0.05 seconds at
50Hz. The adjustable selective instantaneous is 0.05 and
0.06 seconds at 60 and 50 Hertz respectively. For Power
Break II, AKR, and WavePro circuit breakers the clearing
times are 0.05 and 0.058 seconds for RELT and selective
instantaneous respectively at 60 Hz. Power Break does not
offer the selective Adjustable Instantaneous or RELT
function. Instantaneous clears in 0.05 seconds for Power
Break versions of the EntelliGuard TU trip unit.
When the RELT option is configured in an EntelliGuard TU
Trip Unit Digital Input 1 and Digital Output 1 are
automatically and permanently configured to function with
RELT. RELT is a factory installed option—it cannot be
“turned on” if it is not purchased as an option. The Digital
Output will be energized whenever RELT protection is
engaged. The Digital Input can be wired to one or more
external contacts, such as a light curtain, to engage RELT
when someone is within range of the equipment.
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
NOTICE
for reliable communication regarding RELT status.
Breaker
Frame Size
(A)
Instantaneous
Threshold with
Short Time (× IN)
Instantaneous
Threshold without
Short Time (× IN)
800
Off, 2 to 15
Off, 2 to 10
1600
Off, 2 to 15
Off, 2 to 10
2000
Off, 2 to 15
Off, 2 to 10
3200
Off, 2 to 13
Off, 2 to 10
4000
Off, 2 to 9
Off, 2 to 9
5000
Off, 2 to 7
Off, 2 to 7
NOTICE
RELT can also be controlled remotely over Modbus
Communications. RELT Status is also provided via Modbus
register. Separate Modbus commands are required to
engage and disengage RELT.
Whenever RELT is engaged the trip unit’s LCD display will
flash an obvious “RELT ON” warning.
Once engaged, all trigger sources (remote via Modbus and
externally wired digital input) must be cleared before RELT
will disengage. RELT will stay engaged for 15 seconds after
the last trigger is cleared to give personnel time to clear the
area.
Due to Lock-Out-Tag-Out (LOTO), RELT cannot be turned on
Fault CT are desired, order both from the factory because
after delivery these options cannot be changed.
Ground Fault Summation
This protection element operates continuously on the four
current sensor inputs to the trip unit. On four pole breakers,
the fourth pole is built into the circuit breaker. On 3 pole
th
breakers the 4
pole is connected to a neutral sensor
typically mounted in the cable section via the secondary
disconnect. In applications that do not require a neutral
th
sensor, this 4
pole connection must be shorted at the
secondary disconnect to avoid nuisance tripping due to
extraneous noise pickup.
or off from the trip unit LCD.
RELT capability may be provided on a trip unit with or
without 24VDC control power.
When 24 VDC/AC is provided to the RELT input (input 1), the
trip unit will use the set RELT Instantaneous trip setting.
Without control power connected to the trip unit
permanently, indication that the trip unit is in the RELT
mode may not appear on the main screen. The trip unit
must be permanently connected to 24VDC control power
A RELT Switch Kit (catalog #GTURSK) can also be purchased
to add a RELT switch to existing breakers. The kit includes
the selector switch, LED bulb, NO/NC contacts, 8 feet of
wire with spade connectors. The LED Bulb burden is 0.84
watts and the color of the switch is blue.
Table 2-7: Instantaneous Thresholds for Power Break I,
Power Break II, WavePro and AKR Trip Units
POWERBREAK, AK, AKR, WAVEPRO AND CONVERSION
KITS:
Ground Fault Sum is used for single source and multiple
source Ground Fault schemes.
ENTELLIGUARD G
GF Sum is used for single source ground fault only. For
multiple source ground fault see “Ground Fault CT,”
below.
Ground Fault CT
This protection element is available only on the
EntelliGuard G. It is typically utilized for multi-source
Ground Fault (MSGF) applications in ANSI/UL applications
where sensor data must be shared among multiple trip
units on systems with multiple sources connected in
parallel. Contact your local sales office or the Burlington
factory for details on GE’s recommended MSGF
implementation. When GF CT is specified in a breaker, a
special “interposing CT” is installed in the breaker that is
wired between the breaker’s secondary disconnect and the
trip unit’s CT inputs. The full scale output of this CT is
1.54mA at 100% of external sensor.
• RELT instantaneous allows the minimum threshold to go to 1.5X.
GROUND FAULT PROTECTION
The Trip Unit provides two types of ground fault protection:
Ground Fault Summation and Ground Fault CT. These
protections are independent. A related GF alarm function is
available for both types of GF protection, and share the
same pickup level, band choices and tolerances as the GF
trip functions. If both Ground Fault Summation and Ground
The GF pickup value tolerance band is 15% of the set point.
The ground fault pickup settings are listed in Table 2-8 as
multiples of xCT the current sensor rating, in steps of 0.01
xCT. The maximum GF pickup value is limited to 1200 A per
UL standard.
Multiple Ground fault curves are also available: Definite
2
t slope, l4t and a double break special selective
time, l
ground fault with dual l
2
t slopes. The pickup in all is drawn
with a 10% tolerance and the bands are drawn with a 15%
current tolerance. In the case of the double break selective
ground fault the first slope is 10% tolerance, the second is
15%. See DES-093A for ground fault curve shapes.
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
0.20–0.60 (max of 1200
A) (increment of 0.01)
with OFF as a selection
when GF or GF Alarm
0.01) with OFF as a
selection when GF or GF
Alarm Switchable is
GF/ALARM
Pickup
4000 0.20–0.30 (increment of
0.01 with OFF as a
selection when GF or GF
Alarm Switchable is
GF/ALARM
Pickup
5000 0.20–0.24 (increment of
0.01) with OFF as a
selection when GF or GF
Alarm Switchable is
GF/ALARM
Pickup
6000 0.2 (1200 A) with OFF as
a selection when GF or
GF Alarm Switchable is
Ground-Fault Delay
This function sets the delay before the breaker trips when
the ground-fault pickup current has been detected.
The Ground Fault Delay setting consists of a selection
between two I
2
T slopes: an optional steeper fuse slope, and
fixed delay only. One of fourteen fixed time bands is also
selected. The fixed delay bands are listed in Table 2-9.
The Ground Fault Delay settings consist of two user
settings. The Time Delay band and the Ground Fault
protective function curve shape. The time delay bands
consist of up to 14 definite time response bands. Table 2-8
lists the available time delay bands for the various circuit
breakers. There are four ground fault protective functions
shapes that may be selected. Definite time (OFF), l
4
t slope and a double break special selective ground fault
l
with dual l
2
t slopes.
2
t slope,
The Ground Fault Delay band may be set to off based on
trip unit configuration. Note that “switchable Ground Fault”
is not UL listed.
• Power Break I, Power Break II, WavePro and AKR time band width is 60
msec.
• EntelliGuard G 60 Hz time band width is 0.055 sec.
• EntelliGuard G 50 Hz time band width is 0.060 sec.
ALARMS
Ground Fault Alarms
The Ground Fault alarm DOES NOT issue a trip event. If
tripping on ground fault is required order LSI
not LSIGA.
Instead it can turn on a digital output if an output is
configured for it. It will always turn on an indication in the
Modbus register map. The output can be used to turn on a
light or other signal but it WILL NOT GENERATE A TRIP
EVENT.
All GTUs with a Ground Fault trip can also send a signal
after the trip event that a GF occurred.
Current Alarm
The trip unit provides two current alarms. These alarms will
trigger an alert when current consumption exceeds their
setpoints. This is useful for implementing load shedding
processes, and serves as an alert to impending Long Time
pickup. The alert can be signaled either via
communications or via digital output. The Current Alarms’
ON/OFF pickup settings are 0.5 to 1.0 xIn in steps of 0.05.
The trip unit does not allow the current alarm OFF setpoint
to be set above the ON setpoint.
If the highest measured phase current goes above the
Current Alarm ON setpoint and remains above the setpoint
for more than 60 seconds the alarm will be triggered. If the
current falls below the Current Alarm OFF setpoint for more
than 60 seconds while the Current Alarm is active, the
alarm condition will be cleared.
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
Unrestrained, normal mode ST setpoints: If
Restrained settings:
The serial register indicating the state of the Current Alarm
will assume a value 1 when the alarm is triggered, and a
value of zero if the alarm is cleared. If a digital output is
mapped to the Current Alarm, it will be open if the alarm is
clear, and closed if the Current Alarm is active. The alarm
indications do not latch; they follow the state of the Current
alarm.
enters pickup, the normal or unrestrained GF pickup
setpoints will be effect.
If the Zone Selective Input goes off while the restrained
settings are in effect, they will remain in effect for 50
milliseconds. After that, the unrestrained settings will go
into effect.
ZONE SELECTIVE INTERLOCKING
Zone -selective interlocking coordinates breakers so that
the downstream breaker is allowed the first opportunity to
clear a fault or overload event.
The optional Zone Selective Interlocking (ZSI) function
operates with a group of series-connected breakers. ZSI is
achieved with the use of the TIM1 module or an equivalent
GE qualified and recommended device.
There are two sets of settings in a breaker used in a Zone
Selective Interlocking system. The normal or “unrestrained”
setpoints are the main over current protection setpoints. A
second set of ZSI or “restrained” setpoints are included for
each interlocked protection element – GF, ST, and
Instantaneous.
If a protection element, such as Ground Fault, goes into
pickup and the Zone Selective Interlock input is active, the
“restrained” or ZSI settings will be in effect. If the Zone
Selective Interlock input is not active when the GF element
the trip unit enters Short Time pickup and the
ZSI input is OFF, these settings are in effect. In
a ZSI configuration these settings are
optimized for protection of the cable/bus
directly below the breaker, and not for
selectivity with downstream breakers.
If the trip unit enters
Short Time Pickup and the ZSI input is ON,
these settings are in effect. This setting is
intended to provide selectivity with the
downstream breaker, so it will typically be set
longer, to give the downstream breaker a
chance to clear the fault.
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
In Power Break II and Spectra MicroEntelliGuard Circuit
Breakers the "T" option only enables instantaneous ZSI
as an output to interlock with upstream circuit breakers
such as a GE WavePro, AK, AKR, Conversion Kits or new
EntelliGuard G (ANSI or UL489). The T option requires 24
VDC external power. The T option does not modify IOC
timing on PowerBreak I, PowerBreak II and Spectra
MicroEntelliGuard circuit breakers.
Figure 2-5: Restrained ZSI Settings
ZSI Option
Two Zone- Selective-Interlocking options may be
purchased with each trip. Option "Z" or option "T". Option Z
allows the user access to short time or ground fault ZSI.
The user may enable or disable either or both. The "T"
option adds Instantaneous ZSI capability. Instantaneous
ZSI may be enabled or disabled by the user at any time.
Use of the short time or GF ZSI in a CB requires that the
user set two different delay and slope bands for ground
fault or short time depending on which he has enabled.
The upstream breaker uses the ST ZSI and/or GF ZSI delay
bands and slope, and/or transition to a delay
Instantaneous if it receives a downstream ZSI signal.
The desired ZSI (ST and/or GF and/or Instantaneous) must
be selected in order for the downstream breaker to issue a
ZSI signal, and the upstream breaker to act upon this
signal. If the ZSI setting is set to OFF no ZSI output signal is
generated.
The ST ZSI Delay Bands are independent and have the
same bands available. Slope settings may also be
interlocked.
The GF ZSI Delay Bands are independent and have the
same bands available. Slope settings may also be
interlocked.
15
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
EntelliGuard G (ANSI and UL489):
AKR, WavePro and Conversion Kits:
NOTICE
SOFTWARE REVISION 08.00.23 AND GREATER:
displayed on the LCD.
If the GTU’s internally stored BIM ID (Breaker Serial
Number) is ZERO:
Instantaneous ZSI is either enabled or disabled. There are
no settings to modify the action of Inst ZSI.
the traditional mechanical rejection methodology used on
other GE circuit breakers.
INST ZSI timing is as follows::
•
An additional 2.5
cycles (ignore inst for 3 cycles after seeing input and trip
th
on the 7
•
cycles (ignore inst for 4.5 cycles after seeing input and
trip on the 9
half cycle)
th
half cycle.)
An additional 4
INTERRUPTION PROTECTION
Making Current Release (MCR)
Every EntelliGuard G circuit breaker uses a making current
release. The making current release varies per circuit
breaker Envelope and is related to the circuit breaker’s
close and latch rating.
The MCR pickup is activated at the time the circuit breaker
closes and for six cycles thereafter. When the six cycles are
over, the threshold changes to the HSIOC pickup setting.
High Set Instantaneous Protection (HSIOC)
HSIOC is also known as Override Pickup. Some of the trip
units on EntelliGuard G circuit breakers may be provided
with an override instantaneous trip.
Whether such a trip is provided or not depends on the
circuit breaker within which the trip is installed. If the circuit
breaker’s withstand lcw is equal to the short circuit rating
then the trip will not have an override pickup. If the
withstand rating is lower than the short circuit rating then
the trip will enable override protection of the circuit breaker
at the short time withstand rating level.
In UL 489 circuit breakers the HSIOC setting is nominally at
107% of the Icw for the circuit breaker. Taking tolerance
into account, the override’s minimum trip is at 100% of the
circuit breaker’s Icw.
In UL 1066 (ANSI) circuit breakers the HSIOC setting is also
at 107% Icw if the adjustable selective instantaneous is ON.
If the adjustable selective instantaneous is OFF then the
HSIOC nominal pick up is at 98% of the circuit breaker’s Icw
and, considering tolerance, the minimum pickup is at 91%
of the circuit breaker’s Icw.
The BIM contains information that describes the breaker
configuration to the trip unit. The trip unit extracts
information on Sensor Rating, Interruption Rating, and pole
configuration from the BIM. This is a one-time event that
occurs when a new trip unit is first powered up in a
breaker. Every time the trip unit powers up in the breaker
from that point forward, it compares information in the BIM
to the information it initially read and stored. If the
information does not match the trip unit will immediately
trip the breaker and set a BIM Error Flag, and record a BIM
error trip event. In effect, the trip unit “marries” the breaker.
If a BIM read fails the trip unit will not open the breaker,
instead it will modify its internal configuration to match the
AIC rating of the least capable breaker in the family. The
trip unit will periodically read the BIM after that, and on a
successful match the original settings will be restored.
While the BIM error persists a BIM Err message will be
The “Universal Trip Unit” can be used as a replacement for
any trip unit. The Protection and Advanced Features of the
Universal trip unit should match the configuration of the
trip unit being replaced to maintain the same functionality.
The Universal trip unit is programmed with minimum
values for all protection, and it will automatically read the
BIM values from the first breaker it is installed in. This will
force the Universal Trip Unit to assume the configuration of
the trip unit it is replacing. Once this process is complete,
the Universal Trip Unit cannot be moved to another
breaker – it “marries” the breaker.
BIM Transaction Details
On power up the trip unit immediately queries the BIM for
local breaker configuration information.
• Upon power-up the trip unit reads BIM ID
• Since there is no match:
Power Break I, WavePro and AKR circuit breakers do not
employ an override function. Power Break II circuit
breakers use a mechanical override function.
Breaker Interface Module (BIM)
The EntelliGuard G Breaker uses a Breaker Interface
Module which is internally connected to the EntelliGuard G
Trip Unit. This allows the breaker to electronically reject an
incorrect trip unit being inserted into a breaker, instead of
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
If the GTU BIM ID (Breaker Serial Number) is NON-ZERO
BIM Remarry Sequence:
Item
Option
Voltage unbalance
pickup
Adjustable from 10% to 50%
in increments of 1%.
disables this function.
Item
Option
pickup
in increments of 1%.
disables this function.
Item
Option
pickup
increments of 1%.
Under voltage
Adjustable from 1 sec to 15 sec in
Voltage Unbalance
• Upon power-up the trip unit reads BIM ID
• If there is no match:
o Breaker trips Note: Software Revision 08.00.23
and great, If a BIM read fails the trip unit will not
trip the breaker, instead it will modify its internal
configuration to match the AIC rating of the least
capable breaker in the family. The trip unit will
periodically read the BIM after that, and on a
successful match the original settings will be
restored. While the BIM error persists a BIM Err
message will be displayed on the LCD.
o GTU shows BIM ID Mismatch Error
o GTU registers a BIM Trip Event
Under certain circumstances, it is possible to reconfigure a
trip unit so that it can be installed in a different circuit
breaker. This involves “divorcing” the BIM and trip unit so
that the trip unit can be “married” to a different circuit
breaker.
1. Install the trip unit on the target breaker. On power up
the breaker will be tripped due to BIM error.
2. BIM mismatch will be indicated.
3. Press Right + Left + Up simultaneously.
4. “BIM OK” will flash in the upper left corner of the LCD
display if marry succeeded
5. “BIM ERROR” will show if the marry failed.
Upon execution of the procedure, GTU will upload the data
if the breaker is open and the following data in the BIM
matches the GTU data programmed in the factory:
This function compares the highest or lowest phase
voltage with the average of all three phases and initiates a
trip if the difference exceeds the set point.
Table 2-10: Voltage Unbalance Settings
Voltage unbalance
delay setting
Current Unbalance
This function compares the current in the highest or lowest
phase with the average of all three phases and initiates a
trip if the difference exceeds the set point.
Table 2-11: Current Unbalance Settings
Current unbalance
Current unbalance
delay setting
Undervoltage Relay
This function measures the voltage in all phases and
initiates a trip if any phase voltage drops below the set
point. This internal trip unit relay feature operates
independently of any separately installed undervoltage
Relay Accessory on the circuit breaker.
Table 2-12: Under Voltage Settings
Adjustable from 1 sec to
15 sec in increments of 1 sec.
Setting this value to OFF
Adjustable from 10% to 50%
Adjustable from 1 sec to
15 sec in increments of 1 sec.
Setting this value to OFF
• Sensor
• Standard (UL/ANSI/IEC)
• MCR
• HSIOC
• Breaker interruption rating (Frame)
If there is no match, BIM Data mismatch error will show.
Otherwise, continue normal operation.
PROTECTIVE RELAYS
The protection relay can be set to cause either a trip or an
alarm. If the PR Enable on the LCD is set to ON, a trip will be
generated, if set to OFF an alarm will be generated. The
alarms can provide external indication by using the digital
output contacts. See “Output Relays,” below, about output
contact behavior.
“Trip on Zero Volts” is a setpoint that defines the operation
of the UVR relay on a “dead bus”. It determines whether the
protective relay UVR trip unit function trips or not when all
three phase voltages drop to zero.
Overvoltage Relay
This function measures the voltage in all phases and
initiates a trip if any phase voltage exceeds the setpoint.
See Table 2-13.
Adjustable from 50% to 90% in
increments of 1 sec. Setting this value
to OFF disables this function.
17
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
Item
Option
pickup
increments of 1%.
to OFF disables this function.
Item
Option
pickup
increments of 10 kW.
to zero (0) will disable this function.
Table 2-13: Over Voltage Settings
Power Direction Setup
Over voltage
Over voltage
delay
Power Reversal Relay
Adjustable from 110% to 150% in
Adjustable from 1 sec to 15 sec in
increments of 1 sec. Setting this value
This function selects the normal power flow direction for
the breaker. Set this parameter to match the direction of
current flow through the breaker during normal operating
conditions. This direction setup also affects the sign of the
normal power metering displays.
Potential Transformer Voltage
This function measures the direction of power flow through
the breaker and initiates a trip if a sufficient magnitude of
reverse power is detected.
Table 2-14: Power Reversal Settings
Power reversal
Adjustable from 10 kW to 990 kW in
Enter the primary voltage rating of the potential
transformer. The range of values is 120 V to 600 V, with an
increment of 1V. The voltage input coming into the trip unit
must be wired into using voltage conditioners which steps
the voltage down to an acceptable voltage level. See below
for voltage conditioner plate wiring diagrams.
Power reversal
delay
Adjustable from 1 sec to 15 sec in
increments of 1 sec. Setting this value
Figure 2-6: Voltage Conditioner Plate Wiring — Wye
DEH-4567B EntelliGuard TU Trip Units: UL/ANSI Models
Protection
NOTICE
voltage and power metering values.
30 VDC/25 VAC max, 1 A.
Figure 2-7: Voltage Conditioner Plate Wiring — Delta
An incorrect PT voltage set point will result in incorrect
Potential Transformer Connection
Select the appropriate potential transformer connection,
either line-to-line (Ph-Ph) or line-to-neutral (Ph-N). See “PT
Connection,” below, for more details.
OUTPUT RELAYS
The number of outputs available varies by breaker. These
are relay contact outputs to the secondary disconnect.
Each output can be configured per Table 2-15.
The contacts are rated for
Power Break I, Power Break II, WavePro, AK, AKR and
Conversion Kit Trip Units have one output relay.
EntelliGuard G Trip Units have two output relays. The relay
output can be assigned to the following functions:
• Group 1 – GF Sum and GF CT alarm only. Does not latch.
The trip units must have the specific option (as an example
protective relay must be enabled in order for protective
function to actuate the relay) enabled in order to actuate
the relay.
Fan/Command Close Control
EntelliGuard trip units include an output dedicated to
controlling either an external breaker cooling fan (5000A
WavePro and AKR breakers only) or a remote close
accessory (EntelliGuard G breakers only). Breaker
documentation provides wiring information.
For WavePro and AKR breakers, the trip unit automatically
calculates cooling requirements and activates the fan
control output to maintain the breaker’s operating
temperature.
For EntelliGuard G breakers, the remote close command is
available via Modbus command. Issuing command 111 will
EntelliGuard TU Trip Units: UL/ANSI Models DEH-4567B
Protection
Group #
Function
Summary Description
1
activated.
2
INST, LT, ST)
7
Reduced
(RELT)
Output relay contact closes when
3
relays
relay contact closes.
4
Current
Exceeding current alarm pick-up
5
alarm 2
turns closes the relay contact.
set via communication).
operate the command close coil accessory on the circuit
breaker (remotely closes the breaker).
Table 2-15: Output Configuration
• UVR, Protective Relay
• Over Current, Protective Relay
• Shunt Trip, UVR, Over Current
GF alarm Turns on when GF alarm is
Overcurrent
trip (GF,
Energy LetThrough
Protective
alarm 1
Current
*Health
6
status
BELL ALARM ACCESSORY
Bell Alarm with Lock-out Accessory Configuration Setup
(applies to Power Break II and WavePro Trip Units only)
This defines the types of signals (protection trip, Shunt trip,
Shunt Trip with Lockout, or Under Voltage Release trip) that
activates the Bell Alarm-Alarm Only and Bell Alarm with
Lockout accessories on the Power Break II breaker only.
The customer may enable or disable a different path to
activate these accessories from the different types of trip
signals.
The following settings can be set on the LCD or through
communication for PBII and WavePro breakers:
• Disabled
• Shunt Trip
• UVR Trip
• Over Current Trip
Over-voltage trip turns ON the
relay.
the RELT pickup is enabled.
When protective relay trips the
turns closes the relay contact.
Exceeding current alarm pick-up
Relay contact will be closed or
opened depending on the Health
contact setting. (Either normally
open (NO) or normally closed (NC)
• Shunt, UVR, Protective Relay
• Shunt, Over Current, Protective Relay
• UVR, Over Current, Protective Relay
• Shunt, UVR, Over Current, Protective Relay
Settings Description
The following are descriptions of the effects of each
accessory switch when it is enabled:
• If Bell Alarm or Bell Alarm with Lockout is set to Shunt
Trip, an opening generated by a Shunt Trip will cause
the Bell Alarm contacts to change state.
• If Bell Alarm with Lock-out is set to over current trip, a
fault generated by LT, ST, GF, and/or Instantaneous will
cause the Bell Alarm contacts to change state.
Bell Alarm Operation – EntelliGuard G breakers
The EntelliGuard G breaker has a mechanical lockout built
into the breaker’s trip mechanism. The lockout actuator is
always triggered when the flux shifter actuator “trips” the
circuit breaker. The breaker’s mechanical lockout is not
actuated if the breaker is “opened” using the front panel
pushbuttons, or an optional shunt trip accessory.
There are two modes of operation for the Lockout button in
UL & ANSI applications – MANUAL and AUTOMATIC. The trip
unit’s Lockout button configuration is fixed based on the
catalog number of the trip unit. MANUAL or AUTO operation
is fixed at the factory, and cannot be changed. Do not
attempt to rotate the knob as it will damage the locking
mechanism.
In MANUAL mode the breaker’s lockout actuator is allowed
to travel to its “triggered” position. As the lockout trigger
extends from the breaker mechanism following a flux
shifter operation, it pushes the knob on the front of the trip
unit out. At this point the breaker mechanism is “locked
out” and cannot be closed until the mechanical lockout is
manually reset. Reset is accomplished by pushing in the
button on the trip unit until the breaker lockout is reset.
In AUTOMATIC mode the breaker’s mechanical lockout
actuator is physically restrained from traveling to its
“triggered” position by the fixed knob on the trip unit. In
other words, the mechanical lockout is fired when the flux
shifter operates, but the trip unit’s knob “automatically
resets” the lockout so that the breaker can be reclosed
without manual intervention.
Loading...
+ 76 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.