DEH-41318 Installation Instructions
EntelliGuard® TU Rating Plugs
For Power Break®, Power Break® II, AKR, WavePro®,
®
EntelliGuard
Function
EntelliGuard TU Trip Units are designed with UL-Listed
interchangeable rating plugs. These rating plugs
change the per-unit (1X) continuous current rating of
the breaker. A circuit breaker frame equipped with a
suitable rating plug has a long-time trip value equal
to the ampere rating marked on the rating plug. For
example, a breaker frame with a 1600 A sensor and
an 800 A rating plug has an 800 A continuous current
(long-time) rating.
The available rating plugs for the AKR , Power Break,
WavePro and EntelliGuard families are listed in Table 1.
Not all sensors listed in Table 2 are available in all circuit
breakers.
Table 1. Rating plug catalog numbers
GTP0060U0101 GTP1100U1225
GTP0080U0101 GTP1200U1232
GTP0100U0103 GTP1500U1640
GTP0125U0103 GTP1600U1640
GTP0150U0104 GTP1900U2050
GTP0200U0204 GTP2000U2050
GTP0225U0306 GTP2200U2550
GTP0250U0407 GTP2400U2564
GTP0300U0408 GTP2500U2564
GTP0350U0408 GTP3000U3064
GTP0400U0410 GTP3200U3264
GTP0450U0612 GTP3600U4064
GTP0500U0613 GTP4000U4064
GTP0600U0616 GTP5000U5064
GTP0700U0816 GTP6000U6064
GTP0750U0820 GTP1600K4040*
GTP0800U0820 GTP2000K4040*
GTP0900U1020 GTP3000K4040*
GTP1000U1025 GTP4000K4040*
* For use with ITE 4000A conversion kits ONLY
G / microEntelliGuardTM Circuit Breakers and Trip Unit Conversion Kits
Front Label
Figure 1. Front of rating plug, showing label
The front label, shown in Figure 1, is visible when the
rating plug is installed. The items listed are:
Rating Plug Amps (X) The rating plug continuous
Catalog Number GTP1100U1225
In this example:
GTP = EntelliGuard TU trip unit rating plug
1100 = The rating plug continuous current in amperes
U = Universal Trip Plug (Use K for ITE 400A sensor
conversion kit)
12 = Smallest sensor that accepts this plug (1200A)
25 = Largest sensor that accepts this plug (2500A)
Table 2. Catalog number sensor rating designations
Sensor Designation Sensor Rating
01 150A
02 200A
03 225A
04 400A
06 600A
07 630A
08 800A
10 1000A
12 1200A
13 1250A
16 1600A
20 2000A
25 2500A
30 3000A
32 3200A
40 4000A
50 5000A
60 6000A
64 6400A
current in amperes
UL Label
The UL label is mounted on the side of the rating plug
and is not visible when the rating plug is installed. The
label lists the circuit breaker frames that will accept
that rating plug.
Installation
Before installing a rating plug into an EntelliGuard TU trip
unit, inspect the plug for damage, then follow these steps:
1. Verify that the rating plug catalog number matches
the desired continuous current rating and is suitable
for the circuit breaker’s sensor based on the
minimum and maximum sensor rating defined on
the rating plug’s catalog number.
2. Hold the rating plug between the thumb and
forefinger, then push it into the trip unit. Proper
engagement is verified by an audible and tactile click.
CAUTION: Do not attempt to push the rating plug into
the trip unit if there is resistance.
plug. Grasp the tabs of the rating plug with the tool,
as illustrated in Figure 2. Be careful to hold the tabs
and not the front cover, as the rating plug could be
damaged otherwise. Gently pry the rating plug out by
pulling away from the trip unit. A left–right wriggling
motion assists the removal. Insure that the tabs are held
securely until the Rating Plug is completely removed.
Removal
The rating plug is seated firmly in the trip unit. As
illustrated in Figure 1, there are tabs at the sides of
the rating plug for removal. A rating plug removal tool,
catalog number TRTOOL, also known as an integrated
circuit (DIP) extractor, is required to remove the rating
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and
microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they
provide for every possible contingency that may be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062
www.geelectrical.com
© 2010 General Electric Company
Figure 2. Rating plug removal
NOTE: Protection to the breaker is maintained at the
minimum rating plug value for a particular sensor when
the rating plug is removed.
imagination at work
DEH-41318 Rev. 5 (07/10 M45)