GE Industrial Solutions EntelliGuard TU Rating Plugs User Manual

GE Energy
Industrial Solutions
DEH-41318 Installation Instructions
EntelliGuard® TU Rating Plugs
For Power Break®, Power Break® II, AKR, WavePro®,
®
EntelliGuard
Function
EntelliGuard TU Trip Units are designed with UL-Listed interchangeable rating plugs. These rating plugs change the per-unit (1X) continuous current rating of the breaker. A circuit breaker frame equipped with a suitable rating plug has a long-time trip value equal to the ampere rating marked on the rating plug. For example, a breaker frame with a 1600 A sensor and an 800 A rating plug has an 800 A continuous current (long-time) rating.
The available rating plugs for the AKR , Power Break, WavePro and EntelliGuard families are listed in Table 1. Not all sensors listed in Table 2 are available in all circuit breakers.
Table 1. Rating plug catalog numbers
GTP0060U0101 GTP1100U1225 GTP0080U0101 GTP1200U1232 GTP0100U0103 GTP1500U1640 GTP0125U0103 GTP1600U1640 GTP0150U0104 GTP1900U2050 GTP0200U0204 GTP2000U2050 GTP0225U0306 GTP2200U2550 GTP0250U0407 GTP2400U2564 GTP0300U0408 GTP2500U2564 GTP0350U0408 GTP3000U3064 GTP0400U0410 GTP3200U3264 GTP0450U0612 GTP3600U4064 GTP0500U0613 GTP4000U4064 GTP0600U0616 GTP5000U5064 GTP0700U0816 GTP6000U6064 GTP0750U0820 GTP1600K4040* GTP0800U0820 GTP2000K4040* GTP0900U1020 GTP3000K4040* GTP1000U1025 GTP4000K4040*
* For use with ITE 4000A conversion kits ONLY
G / microEntelliGuardTM Circuit Breakers and Trip Unit Conversion Kits
Front Label
Figure 1. Front of rating plug, showing label
The front label, shown in Figure 1, is visible when the rating plug is installed. The items listed are:
Rating Plug Amps (X) The rating plug continuous
Catalog Number GTP1100U1225
In this example: GTP = EntelliGuard TU trip unit rating plug
1100 = The rating plug continuous current in amperes U = Universal Trip Plug (Use K for ITE 400A sensor
conversion kit)
12 = Smallest sensor that accepts this plug (1200A) 25 = Largest sensor that accepts this plug (2500A)
Table 2. Catalog number sensor rating designations
Sensor Designation Sensor Rating
01 150A 02 200A 03 225A 04 400A 06 600A 07 630A 08 800A 10 1000A 12 1200A 13 1250A 16 1600A 20 2000A 25 2500A 30 3000A 32 3200A 40 4000A 50 5000A 60 6000A 64 6400A
current in amperes
UL Label
The UL label is mounted on the side of the rating plug and is not visible when the rating plug is installed. The label lists the circuit breaker frames that will accept that rating plug.
Installation
Before installing a rating plug into an EntelliGuard TU trip unit, inspect the plug for damage, then follow these steps:
1. Verify that the rating plug catalog number matches the desired continuous current rating and is suitable for the circuit breaker’s sensor based on the minimum and maximum sensor rating defined on the rating plug’s catalog number.
2. Hold the rating plug between the thumb and forefinger, then push it into the trip unit. Proper engagement is verified by an audible and tactile click.
CAUTION: Do not attempt to push the rating plug into the trip unit if there is resistance.
plug. Grasp the tabs of the rating plug with the tool, as illustrated in Figure 2. Be careful to hold the tabs and not the front cover, as the rating plug could be damaged otherwise. Gently pry the rating plug out by pulling away from the trip unit. A left–right wriggling motion assists the removal. Insure that the tabs are held securely until the Rating Plug is completely removed.
Removal
The rating plug is seated firmly in the trip unit. As illustrated in Figure 1, there are tabs at the sides of the rating plug for removal. A rating plug removal tool, catalog number TRTOOL, also known as an integrated circuit (DIP) extractor, is required to remove the rating
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com © 2010 General Electric Company
Figure 2. Rating plug removal
NOTE: Protection to the breaker is maintained at the
minimum rating plug value for a particular sensor when the rating plug is removed.
imagination at work
DEH-41318 Rev. 5 (07/10 M45)