GE Industrial Solutions CAR1612FP User Manual

Page 1
GE Energy
CAR1612FP series rectifier
Features
Universal input with PFC
Constant power characteristic
2 front panel LED 1-input
LED 2-[output, fault, over temp]
Remote ON/OFF control of the 12Vdc output
Remote sense on the 12Vdc output
No minimum load requirements
Redundant parallel operation
Active load sharing (single wire)
Applications
12Vdc distributed power architectures
Datacom applications
Mid to high-end Servers
Enterprise Networking
Network Attached Storage
Telecom Access Nodes
Routers/Switches
Hot Pluggable
Efficiency: typically 94.5% @ 50% load
Standby orderable either as 3.3Vdc or 5Vdc
Auto recoverable OC & OT protection
Digital status & control: I
EN/IEC/UL60950-1 2
EMI: class B FCC docket 20780 part 15, EN55022
Meets EN6100 immunity and transient standards
Shock & vibration: NEBS GR-63-CORE, level 3
Data Sheet
2
C and PMBus serial bus
nd
edition; UL, CSA and VDE
Broadband Switches
ATE Equipment
Description
The CAR1612FP series of Front-End rectifiers provide highly efficient isolated power from worldwide input mains in a compact 1U industry standard form factor in an unprecedented power density of 19W/in for datacom applications such as enterprise networking, mid to high-end servers, and storage equipment, where mid to light load efficiency is of key importance given the nature of the power consumption of the end application.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future growth. The industry standard PMBus compliant I
2
C communications buss offers a full range of control and monitoring capabilities. The SMBAlert signal pin alerts customers automatically of any state change within the power supply.
November 1, 2012 ©2012 General Electric Company. All rights reserved.
3
. These rectifiers are ideal
Page 2
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter Device Symbol Min Max Unit
Input Voltage: Continuous All VIN 0 264 Vac
Operating Ambient Temperature All TA -10 601 °C
Storage Temperature All Tstg -40 85 °C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested) All 1500 Vac
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter Device Symbol Min Typ Max Unit
Operational Range All VIN 85 110/230 264 Vac
F
Frequency Range (ETSI 300-132-1 recommendation) All
Main Output Turn_OFF All
Maximum Input Current VIN= 100Vac
(VO= V
, IO=I
O, set
) VIN= 180Vac
O, max
Cold Start Inrush Current
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
All I
All I
IN
V
IN
IN
IN
Efficiency [230Vac / 110Vac] 100% load (T
=25C, V
amb
= 12Vdc, IO=I
out
) [230Vac / 110Vac] 50% load
O, max
All
[230Vac / 110Vac] 20% load Power Factor (Vin=230Vac, I
O=IO, max
) Holdup time2 Vin= 230Vac (Vout= 12V
, Tamb 25C, IO=I
dc
) Vin= 100Vac
O, max
Early warning prior to loss of DC output below regulation
Ride through
Leakage Current (Vin= 250Vac, Fin = 60Hz)
All
PF 0.99
All T
All
All
All
2 ms
T 10 ms
I
IN
Isolation Input/Output
Input/Frame 1500 V
All
Output/Frame 100 V
12Vdc MAIN OUTPUT
Parameter Device Symbol Min Typ Max Unit
Output Power High Line Operation 180 – 264 Vac
Low Line Operation 90 – 132 Vac 0 - 1200 W Set point All Overall regulation (load, temperature, aging) Ripple and noise3 Turn-ON overshoot Turn-ON delay
All W
All All
V
All All
out
T 2 sec
47 50/60 63 Hz
80 V
14.3
10.5
40 A
Aac
peak
ac
92.5 / 89
94.5 / 91
%
92.4 / 88
12 15
ms
3 mArms
3000 V
0 - 1600 W
11.9 12.00 12.1 V
ac
ac
dc
dc
-3 +3 % 120 mV
p-p
+3 %
1
Derated above 50C at 2.5%/C
2
12V output can decay down to 10.8V
3
Measured across a 10µf tantalum and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 2
Page 3
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
12Vdc MAIN OUTPUT (continued)
Parameter Device Symbol Min Typ Max Unit
Remote ON/OFF delay time Turn-ON rise time (10 – 90% of V
)
out
Transient response 50% step [10%-60%, 50% - 100%] (dI/dt – 1A/µs, recovery 300µs)
Programmable range (hardware4 & software) 10.8 13.2 Overvoltage protection, latched
All
V
out
(recovery by cycling OFF/ON via hardware or software) Output current Vin = HL
V Current limit, Hiccup (programmable level) 110 130 % of FL
= LL
in
I
out
Active current share -5 +5 % of FL
AUXILIARY OUTPUT
Parameter Device Symbol Min Typ Max Unit
Set point All
Overall regulation (load, temperature, aging) All -5 +5 %
V
out
Ripple and noise All 50 mVp-p
Output current All Overload protection - Overvoltage protection
I
out
Isolation Output/Frame All 100
Environmental, Reliability
Parameter Min Typ Max Units Notes
Ambient Temperature Operating Altitude Operating Power Derating
Storage Altitude non-operating
Overload Protection shutdown restart
Humidity Operating Storage
Shock and Vibration acceleration 6 Grms NEBS GR-63-CORE, Level 3, 20 -2000Hz, minimum 30 minutes
Earthquake Rating 4
Reliability 25C
50C
200,000 Hrs Full load, demonstrated MTBF
5
-10
-40
125
110
30
95
10
320,000
100,000
70
2250
2.5
85
8200
95
6
%/°C
°C
Air inlet from sea level to 5,000 feet.
m
7400 ft 51°C to 70C (60C max where TUV/VDE is required)
°C m
30,000 ft
°C
Relative humidity, non-condensing
%
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and tested to meet NEBS specifications.
Full load, MTBF per Bellcore RPP
Hrs
Full load, MTBF per Bellcore RPP
Hrs
40 ms 50 ms
-5 +5 %V
V
dc
13.8 14.8 15.8
0
134 100
3.3 / 5.0 V
0 1 A
V
dc
A
dc
dc
dc
1.1 2.6 Adc
V
dc
out
4
V
=10.8 + (V
out
5
Designed to start at an ambient down to -40°C; meet spec after 30 min warm up period, may not meet operational limits below -10°C.
6
60C max where TUV/VDE is required
* 0.96) where 0 < V
prog
< 2.5. Unit stays at 13.2V when 2.5 < V
prog
< 3. Unit stays at 12V when V
prog
> 3V or no-connect.
prog
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 3
Page 4
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
EMC
Parameter Criteria Standard Level Test
AC input Conducted emissions EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
Radiated emissions** EN55022 A* 30 10000MHz
Voltage dips EN61000-4-11 B -30%, 10ms
B -60%, 100ms
B -100%, 5sec
Voltage surge EN61000-4-5 A 4kV, 1.2/50µs, common mode
A 2kV, 1.2/50µs, differential mode
immunity Fast transients EN61000-4-4 B 5/50ns, 2kV (common mode)
Enclosure immunity Conducted RF fields EN61000-4-6 A 130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields EN61000-4-3 A 10V/m, 80-1000MHz, 80% AM
ENV 50140 A
ESD EN61000-4-2 B 4kV contact, 8kV air
* Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
**
Radiated emissions compliance is contingent upon the final system configuration.
Status and Control
Details of analog controls are provided in this data sheet under Signal Definitions. GE Energy will provide separate application notes on the I2C protocol. Contact your local GE Energy representative for details.
1 (TTL HI level) turns ON the 12Vdc output, while a Logic 0 (TTL LO level) turns OFF the 12Vdc output.
A turn OFF command either through this signal (Remote ON/OFF) or firmware commanded would turn OFF the 12V output.
Enable: This is a short signal pin that controls the
Signal Definitions
All signals and outputs are referenced to Output return. These include ‘Vstb return’ and ‘Signal return’.
Input Signals
Voltage programming (V
signal can vary the output voltage ± 10% from 10.8Vdc to
13.2Vdc. The equation of this signal is:
V
= 10.8 + (V
out
* 0.96) 0 < V
prog
If 2.5 < Vprog < 3, the output is 13.2V. If Vprog is > 3V or left open the programming signal is ignored and the unit output is set at the setpoint of 12Vdc.
Load share (Ishare): This is a single wire analog signal
that is generated and acted upon automatically by power supplies connected in parallel. The Ishare pins should be tied together for power supplies if active current share among the power supplies is desired. No resistors or capacitors should get connected to this pin.
Remote ON/OFF: Controls the presence of the main
12Vdc output voltage. This is an open collector, TTL level control signal. This signal needs to be pulled HI externally through a resistor. Maximum collector voltage is 12Vdc and the maximum sink current is 4mA. A Logic
): An analog voltage on this
prog
< 2.5
prog
presence of the 12Vdc main output. This pin should be connected to ‘output return’ on the system side of the output connector. The purpose of this pin is to ensure that the output turns ON after engagement of the power blades and turns OFF prior to disengagement of the power blades.
Write protect (WP): This signal protects the contents of
the EEPROM from accidental over writing. When left open the EEPROM is write protected. A LO (TTL compatible) permits writing to the EEPROM. This signal is pulled HI internally by the power supply.
Output signals
Output current monitor (Imon): A voltage level
proportional to the delivered output current is present on this pin. 134A = 3V, 100A = 2.25V; accuracy: ± 10%.
AC OK: A TTL compatible status signal representing
whether the input voltage is within the anticipated range. This signal needs to be pulled HI externally through a resistor. Maximum sink current 4mA and the max voltage is 12Vdc. Open collector (HI) on this signal indicates that the input voltage is applied within the specified input range.
DC OK: A TTL compatible status signal representing
whether the output voltage is present. This signal needs
A* 0.15 30MHz
0 – 2 KHz
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 4
Page 5
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
to be pulled HI externally through a resistor. Maximum sink current 4mA and the max voltage is 12Vdc. Open collector (HI) on this signal indicates that the output voltage is present.
Over temp warning: A TTL compatible status signal
representing whether an over temperature exists. This signal needs to be pulled HI externally through a resistor. Maximum sink current 4mA and the max voltage is 12Vdc. Open collector (HI) on this signal indicates that temperatures are normal.
If an over temperature should occur, this signal would pull LO for approximately 10 seconds prior to shutting down the power supply. The unit would restart if internal temperatures recover within normal operational levels. At that time the signal reverts back to its open collector (HI) state.
Fault: A TTL compatible status signal representing
whether a Fault occurred. This signal needs to be pulled HI externally through a resistor. Maximum sink current 4mA and the max voltage is 12Vdc. Open collector (HI) on this signal indicates that no Fault is present.
This signal activates for OTP, OVP, OCP, AC fault or No output.
PS Present: This pin is connected to ‘output return’ within
the power supply. Its intent is to indicate to the system that a power supply is present. This signal may need to be pulled HI externally through a resistor.
Interrupt (SMBAlert): A TTL compatible status signal,
representing the SMBusAlert# feature of the PMBus compatible i needs to be pulled HI externally through a resistor. Maximum sink current 4mA and the pull up resistor should be tied to 3.3Vdc. Open collector (HI) on this signal indicates that no Interrupt has been triggered.
2
C protocol in the power supply. This signal
Serial Bus Communications
The I²C interface facilitates the monitoring and control of various operating parameters within the unit and transmits these on demand over an industry standard I²C Serial bus.
All signals are referenced to ‘Signal Return’.
Device addressing: The microcontroller (MCU) and the
EEPROM have the following addresses:
Device Address Address Bit Assignments
MCU 0xBx 1 0 1 1 A2 A1 A0 R/W
(Most to Least Significant)
EEPROM 0xAx 1 0 1 0 A2 A1 A0 R/W
Address lines (A2, A1, A0): These signal pins allow up to
eight (8) modules to be addressed on a single I²C bus. The pins are pulled HI internal to the power supply. For a logic LO these pins should be connected to ‘Output Return’
Serial Clock (SCL): The clock pulses on this line are
generated by the host that initiates communications across the I²C Serial bus. This signal is pulled up internally to 3.3V by a 10k resistor. The end user should add additional pull up resistance as necessary to ensure that rise and fall time timing and the maximum sink current is in compliance to the I²C specifications.
Serial Data (SDA): This line is a bi-directional data line. .
This signal is pulled up internally to 3.3V by a 10k resistor. The end user should add additional pull up resistance as necessary to ensure that rise and fall time timing and the maximum sink current is in compliance to the I²C specifications.
EEPROM
The microcontroller has 96 bytes of EEPROM memory available for the system host.
Another separate EEPROM IC will provide another 128 bytes of memory with write protect feature. Minimum information to be included in this separate EEPROM: model number, revision, date code, serial number etc.
See the communications protocol for further information.
Communications Protocol
The I²C protocol is described in detail by the I2C and PMBus Serial Communications Protocol for the CAR Family of Power Supplies application note.
LEDs
Two LEDs are located on the front faceplate. The AC_OK LED provides visual indication of the INPUT signal function. When the LED is ON GREEN the power supply input is within normal design limits.
The second LED DC/FLT provides visual indication of three different states of the power supply. When the LED is GREEN then there are no faults and the DC output is present. When the LED is AMBER then a fault condition exists but the power supply still provides output power. When the LED is RED then a fault condition exists and the power supply does not provide output power.
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 5
Page 6
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
Alarm Table
LED Indicator Monitoring Signals
LED1
Test Condition
1 Normal Operation
2 Low or NO INPUT Off
3 OVP
4 Over Current
5 Temp Alarm Warning
6 Fault Over Temp
7 Remote ON/OFF
Note: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.
AC
Green Green
Green Red
Green Red
Green Orange
Green Red
Green Red
Tri-Color LED2
DC / FLT
Red
FAULT DC OK INPUT OK TEMP OK
High High High High
Low Low Low High
Low Low High High
Low Low High High
High High High Low
Low Low High Low
Low Low High High
Outline Drawing
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 6
Page 7
GE Energy
CAR1612FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A
Connector Pin Assignments
Input Mating Connector: IEC320, C20 type
Output Connector: FCI Berg P/N: 51732-021 or equivalent
Mating connector: 51762-10802400ABLF (right angle mount)
Pin Function Pin Function Pin Function Pin Function
A1 Vstb [3.3V] B1 Fault C1 ISHARE D1 VProg
A2 Vstb [3.3V] Return B2 I Monitor (IMON) C2 N/C D2 OVP Test Point
A3 Signal Return B3 Enable: “0” –ON “1” -OFF C3 Over Temp Warning D3 Remote ON/OFF
A4 Write Protect (WP) B4 PS Present C4 I2C Address (A0) D4 DC OK
A5 Remote Sense (+) B5 SDA (I2C bus) C5 I2C Address (A1) D5 AC OK
A6 Remote Sense (-) B6 SCL (I2C bus) C6 I2C Address (A2) D6 SMBAlert
P1 - P4 Output Return P5 – P8 +12Vout
Ordering Information
Please contact your GE Energy Sales Representative for pricing, availability and optional features.
PRODUCT DESCRIPTION PART NUMBER
1600W Front-End +12Vout Front-End, 3.3Vaux, with bezel and PMBus interface CAR1612FPBXXZ01A
1600W Front-End +12Vout Front-End, 5Vaux, with bezel and PMBus interface CAR1612FPBX5Z01A
1600W Front-End +12Vout Front-End, reverse airflow,, with bezel and PMBus interface CAR1612FPBRXZ01A
Contact Us
For more information, call us at
USA/Canada:
+1 888 546 3243, or +1 972 244 9288
Asia-Pacific:
+86.021.54279977*808
Europe, Middle-East and Africa:
+49.89.878067-280
India:
+91.80.28411633
November 1, 2012 ©2012 General Electric Company. All rights reserved. Page 7