GEH5643 Installation Instructions R03
Spectra Series™ Power Panelboards
Circuit Breakers and Modules
WARNING: Danger of electrical shock or injury.
OFF
Turn switchboard before workin
ment or removing any component. Do
e not remove circuit other component until the power is turned OFF.
ower ahead of the panelboard or
inside the
rotective devices or an
General
These instructions apply to the following catalog numbers:
• Circuit breaker modules AMC6QD and AMC4QD
• Circuit breaker frames TQD and THQD
Installation
1. Phase balancing for two-pole devices in three-phase
systems. To balance the panelboard load, remove the
screws on the appropriate bus clip, reposition the bus clip as shown in Figure 1, then install and tighten the screws to 27–32 in-lb.
Protective Cap
or Insulating
Tape
Stud Post
Figure 2. Removing the caps or tape from the stud posts of the
breaker module.
#10-32 x 3/4"
Hex-Head
Screw
Filler
Support
A & C Phase As Received
A & B Phase
B & C Phase
Figure 1. Repositioning the bus clip to balance the load.
2. Prepare the module. Remove the protective caps or insulating tape only from the tops of the stud posts to which the circuit breaker is to be attached, as shown in Figure 2. Fasten the filler supports, as shown in Figure 3, with #10-32 x to 15–20 in-lb.
3
/4" hex-head screws tightened
Figure 3. Fastening the filler supports in position.
3. Install the circuit breaker. Place the ON side of the breaker over the stud posts, as shown in Figure 4. Fasten the breaker to the module with screws with conical washers and #10-32 x 2 After all screws are in place, tighten the to 40–50 in-lb and the #10-32 screws to 25–30 in-lb.
For double-branch devices, repeat this procedure for the other breaker. Any combination of TQD or THQD circuit breakers may be used.
1
/4-20 x 3/4"
3
/4" screws.
1
/4-20 screws
#10-32 Screw
pp
1
/4-20 Screw &
Conical Washer
Stud
Post
Filler
ort
Su
Latch
Latch Lock
Screw
Figure 4. Installing the breaker on the module.
4. Position the module. Loosen the latch lock screws and fully retract the latches. Line up the guide fingers on both ends of the module with the notches in the panelboard interior rails, as shown in Figure 5. Allow no space between units.
5. Install the module. Latch one side of the circuit breaker module. Release the rail latch. Pivot the module onto the bus bars and engage the second latch. Release the rail latch. Tighten the rail latch screws to 25 in.-lbs, as shown in Figure 6.
Figure 6. Installing the breaker module.
6. Wire the circuits. Refer to the label on the circuit breaker for the proper tightening torque. levels
7. Filler plate kits. Install filler plate kits, as listed in Table 1.
Filler Plate
Cat. No. Module Type
AFP3QDD AMC6QD AFP2QDD AMC4QD
Table 1. Filler plate kit for each breaker module type.
Figure 5. Positioning the breaker module.
Latch
Latch Lock
Screw
Attention – Procedure for Aluminum Terminations
1. Strip the insulation, being careful to not nick the wire.
2. Clean the wire strands with a wire brush.
3. Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or PENETROX A13.
4. Insert the conductor and tighten the connector screw to the torque indicated on the rating label.