The voltage of the frequency converter is dangerous whenever it is connected to mains. Incorrect installation of the motor or frequency
converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this
manual as well as local and national rules and safety regulations.
1.1.2. Safety Instructions
•Make sure the frequency converter is properly connected to earth.
•Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power.
•Protect users against supply voltage.
•Protect the motor against overloading according to national and local regulations.
•The earth leakage current exceeds 3.5 mA.
•The [OFF] key is not a safety switch. It does not disconnect the frequency converter from mains.
1.1.3. Software Version and Approvals
1
Software Version
Programming Guide
AF-60 LPറ Micro Drive
This Programming Guide can be used for all AF-60 LPറ Micro Drive frequency drives with software version
2.1x.
The software version number can be read in
parameter 15-43.
1.1.4. General Warning
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected (such as external DC bus power supplies).
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
Before touching any potentially live parts of the frequency converter, wait at least 4 minutes for all sizes.
Shorter time is allowed only if indicated on the nameplate for the specific unit.
3
1
AF-60 LP™ Micro Drive Programming Guide
Leakage Current
The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection
must be ensured by means of a min. 10mm² Cu or an addtional PE wire - with the same cable cross section as the Mains wiring - must be
terminated separately.
Residual Current Device
This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an
RCD of Type B (time delayed) shall be used on the supply side of this product.
Protective earthing of the frequency converter and the use of RCDs must always follow national and local regulations.
Motor overload protection is possible by setting Parameter 1-90 Motor thermal protection to the value Electronic overload trip. For the North
American market: Electronic overload functions provide class 20 motor overload protection, in accordance with NEC.
Installation in high altitudes:
For altitudes above 2 km, please contact GE .
1.1.5. IT Mains
IT Mains
Installation on isolated mains source, i.e. IT mains.
Max. supply voltage allowed when connected to mains: 440 V.
As an option, GE offers line filters for improved harmonics performance.
1.1.6. Avoid unintended Start
While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the drive
Keypad.
•Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start of any motors.
•To avoid unintended start, always activate the [OFF] key before changing parameters.
1.1.7. Disposal Instruction
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
1.1.8. Before Commencing Repair Work
1.
Disconnect AF-60 LPറ Micro Drive from mains (and external DC supply, if present.)
2.Wait for 4 minutes for discharge of the DC-link.
3.Disconnect DC bus terminals and brake terminals (if present)
4.Remove motor cable
4
2. Introduction
2.1.1. Drive Identification
AF-60 LP™ Micro Drive Programming Guide
Below is an example of the frequency converter nameplate sticker. This sticker is located on the top of each frequency converter and shows the ratings, serial
number, warnings catalog number, and other relevant data for each unit. See following tables for details, how to read the Type code string.
130BA505
Illustration 2.1: This example shows the identification sticker.
2.1.2. AF-60 LP Micro Drive Model Number System Diagram
2
5
2
AF-60 LP™ Micro Drive Programming Guide
2.1.3. Symbols
Symbols used in this Programming Guide.
NB!
Indicates something to be noted by the reader.
Indicates a general warning.
Indicates a high-voltage warning.
*Indicates default setting
2.1.4. Abbreviations and Standards
Abbreviations:Terms:SI-units:I-P units:
AWGAmerican wire gauge
Auto TuneAutomatic Motor Tuning
rC
I
LIM
rF
FCFrequency Converter
FrequencyHzHz
kHzKilohertz
LCPLocal Control Panel
mAMilliampere
msMillisecond
minMinute
MCTMotion Control Tool
M-TYPEMotor Type Dependent
NmNewton Metresin-lbs
I
M,N
f
M,N
P
M,N
U
M,N
par.Parameter
PELVProtective Extra Low Voltage
PressurePa = N/m²psi, psf, ft of water
I
INV
RPMRevolutions Per Minute
SRSize Related
Temperature˚C˚F
T
LIM
Acceleration
Celsius
CurrentAAmp
Current limit
EnergyJ = N·mft-lb, Btu
Fahrenheit
Nominal motor current
Nominal motor frequency
Nominal motor power
Nominal motor voltage
PowerWBtu/hr, hp
Rated Inverter Output Current
Timess,hr
Torque limit
VoltageVV
m/s
2
ft/s
2
Table 2.2: Abbreviation and Standards table .
6
3. Programming
3.1. How to Programme
3.1.1. Programming with DCT-10 Set-up Software
AF-60 LP™ Micro Drive Programming Guide
The frequency converter can be programmed from a PC via RS485 com-port by installing the DCT-10 Set-up Software.
This software can be downloaded from the GE Web site: www.geelectrical.com/drives
3.1.2. Programming with the Keypad
The Keypad is divided into four functional groups:
1.Numeric display.
2.Menu key.
3.Navigation keys.
4.Operation keys and indicator lights (LEDs).
NB!
Parameters should be changed in numerical order. Certain parameter values are affected by preceding changes.
3
Illustration 3.1: Keypad with potentiometer
The display:
A number of information can be read from the display.
Set-up number shows the active set-up and the edit set-up. If the same set-
up acts as both active and edit set-up, only that set-up number is shown
(factory setting).
When active and edit set-up differ, both numbers are shown in the display
(Setup 12). The number flashing, indicates the edit set-up.
Illustration 3.3: Indicating Set-up
7
3
AF-60 LP™ Micro Drive Programming Guide
The small digits to the left are the selected parameter number.
Illustration 3.4: Indicating selected par. no.
The large digits in the middle of the display show the value of the selected
parameter.
Illustration 3.5: Indicating value of selected par.
The right side of the display shows the unit of the selected parameter. This
can be either Hz, A, V, kW, HP, %, s or RPM.
Illustration 3.6: Indicating unit of selected par.
Motor direction is shown to the bottom left of the display - indicated by a
small arrow pointing either clockwise or counterclockwise.
Illustration 3.7: Indicating motor direction
Use the [MENU] key to select one of the following menus:
Status Menu:
The Status Menu is either in Readout Mode or Hand Mode. In Readout Mode the value of the currently selected readout parameter is shown in the display.
In Hand Mode the local Keypad reference is displayed.
Quick Menu:
Displays Quick Menu parameters and their settings. Parameters in the Quick Menu can be accessed and edited from here. Most applications can be run by setting
the parameters in the Quick Menus.
Main Menu:
Displays Main Menu parameters and their settings. All parameters can be accessed and edited here. A parameter overview is found later in this manual.
Indicator lights:
•Green LED: The frequency converter is on.
•Yellow LED: Indicates a warning. Please see section Troubleshooting
•Flashing red LED: Indicates an alarm. Please see section Troubleshooting
8
AF-60 LP™ Micro Drive Programming Guide
Navigation Keys:
[Back]: For moving to the previous step or layer in the navigation structure.
Arrows [Ⴃ] [Ⴍ]: For maneuvering between parameter groups, parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes to parameter settings.
Operation Keys:
A yellow light above the operation keys indicates the active key.
[Hand ]: Starts the motor and enables control of the frequency converter via the Keypad.
[Off/Reset]: The motor stops except in alarm mode. In that case the motor will be reset.
[Auto ]: The frequency converter is controlled either via control terminals or serial communication.
[Potentiometer] Keypad: The potentiometer works in two ways depending on the mode in which the frequency converter is running.
In Auto Mode the potentiometer acts as an extra programmable analog input.
In Hand Mode the potentiometer controls local reference.
3.2. Status Menu
After power up the Status Menu is active. Use the [MENU] key to toggle be-
tween Status, Quick Menu and Main Menu.
Arrows [Ⴃ] and [Ⴍ] toggles between the choices in each menu.
3
The display indicates the status mode with a small arrow above “Status”.
Illustration 3.8: Indicating Status mode
3.3. Quick Menu
The Quick Menu gives easy access to the most frequently used parameters.
1.To enter the Quick Menu, press [MENU] key until indicator in display is placed above Quick Menu.
2.
Use [Ⴃ] [Ⴍ] to select either QM1 or QM2, then press [OK].
3.
Use [Ⴃ] [Ⴍ] to browse through the parameters in the Quick Menu.
4.Press [OK] to select a parameter.
5.
Use [Ⴃ] [Ⴍ] to change the value of a parameter setting.
6.Press [OK] to accept the change.
7.To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
Illustration 3.9: Indicating Quick Menu mode
9
3
3.4. Main Menu
The Main Menu gives access to all parameters.
1.To enter the Main Menu, press [MENU] key until indicator in display
is placed above Main Menu.
2.
Use [Ⴃ] [Ⴍ] to browse through the parameter groups.
3.Press [OK] to select a parameter group.
4.
Use [Ⴃ] [Ⴍ] to browse through the parameters in the specific group.
5.Press [OK] to select the parameter.
6.
Use [Ⴃ] [Ⴍ] to set/change the parameter value.
7.Press [OK] to accept the value.
8.To exit, press either [Back] twice to enter Quick Menu, or press
[Menu] once to enter Status.
AF-60 LP™ Micro Drive Programming Guide
Illustration 3.10: Indicating Main Menu mode
10
AF-60 LP™ Micro Drive Programming Guide
4. Parameter Descriptions
4.1. Parameter group 0: Operation/Display
0-03 Regional Settings
Option:Function:
In order to meet the needs for different default settings in different parts of the world, par. 0-03, Regional Settings, is
implemented in the frequency converter. The selected setting influences the default setting of the motor nominal
frequency.
[0 ]InternationalSets default of par. 1-23, Motor Frequency, to 50 Hz, shows par. 1-20 in kW.
*
[1]
0-04 Operating State at Power-up (Hand Mode)
Option:Function:
USSets default of par. 1-23, Motor Frequency, to 60 Hz, shows par. 1-20 in HP.
NB!
This parameter cannot be adjusted while motor runs.
This parameter controls whether or not the frequency converter should start running the motor when powering up
after a power down in Hand mode.
NB!
If Keypad with potentiometer is mounted, reference is set according to actual potentiometer value.
4
[0]ResumeFrequency converter starts in same Hand or Off State as when powered off.
Local reference is stored and used after power-up.
*
[1]
[2]Forced Stop, Ref=0Frequency converter powers up in Off State meaning that motor is stopped after power up.
Forced Stop, Ref=OldFrequency converter powers up in Off State meaning that motor is stopped after power up.
Local reference is stored and used after power-up.
Local reference is set to 0. Thus motor will not start running before local reference has been increased.
4.1.1. 0-1* Set-up Handling
User defined parameters and miscellaneous external inputs (eg. bus, Keypad, analog/digital inputs, feedback, etc.) controls the functionality of the frequency
converter.
A complete set of all parameters controlling the frequency converter is called a set-up. The frequency converter contains 2 set-ups, Set-up1 and Set-up 2.
Furthermore, a fixed set of factory settings can be copied into one or more set-ups.
Some of the advantages of having more than one set-up in the frequency converter are
•Run motor in one set-up (Active Set-up) while updating parameters in another set-up (Edit Set-up)
•Connect various motors (one at a time) to frequency converter. Motor data for various motors can be placed in different set-ups.
•Rapidly change settings of frequency converter and/or motor while motor is running (eg. ramp time or preset references) via bus or digital inputs.
The Active Set-up can be set as Multi Set-up where the active set-up is selected via input on a digital input terminal and/or via the bus control word.
NB!
FactorySet-up cannot be used as Active Set-up.
0-10 Active Set-up
Option:Function:
Active Set-up controls the motor.
Shifts between set-ups can only happen when
11
AF-60 LP™ Micro Drive Programming Guide
•the motor is coasted
OR
•the set-ups between which the shift happens are linked to each other (see par. 0-12, Linked Set-ups).
If changing between set-ups that are not linked, the change will not happen before motor is coasted.
NB!
The motor is only considered stopped when it is coasted.
4
[1 ]
*
[2]Set-up 2Set-up 2 is active.
[9]Multi Set-upSelect the active set-up via digital input and/or bus, see par. 5-1* choice [23].
Set-up 1Set-up 1 is active.
0-11 Edit Set-up
Option:Function:
The Edit Set-up is for updating parameters in the frequency converter from either Keypad or bus. It can be identical
or different from the Active Set-up.
All set-ups can be edited during operation, independently of the active set-up.
*
[1 ]
[2]Set-up 2Update parameters in Set-up 2.
[9]Active Set-upUpdate parameters in set-up selected as Active Set-up (see par. 0-10).
Set-up 1Update parameters in Set-up 1.
0-12 Link Set-ups
Option:Function:
The link ensures synchronizing of the “not changeable during operation” parameter values enabling shift from one
set-up to another during operation.
If the set-ups are not linked, a change between them is not possible while the motor is running. Thus the set-up change
does not occur until the motor is coasted.
[0]Not linkedLeaves parameters unchanged in both set-ups and cannot be changed while motor runs.
[1 ]
*
LinkedCopy parameters “not changeable during operation” parameter values into presently selected Edit Set-up.
NB!
This parameter cannot be changed while motor runs.
4.1.2. 0-31 Custom Readout Min Scale
0-31 Custom Readout Min Scale
Range:Function:
0.00* [0.00 – 9999.00 ]
It is possible to create a customized readout related to the output frequency of the unit. The value entered in par. 0-31
will be shown at 0 Hz. The readout can be shown in the LCP display when in Status Mode or it can be read in par. 16-09
4.1.3. 0-32 Custom Readout Max Scale
0-32 Custom Readout Max Scale
Range:Function:
100.0* [0.00 – 9999.00]
It is possible to create a customized readout related to the output frequency of the unit. The value entered in par. 0-32
will be shown at the frequency programmed in par. 4-14 Motor Speed High Limit. The readout can be shown in the LCP
display when in Status Mode or it can be read in par. 16-09
4.1.4. 0-4* Keypad
The frequency converter can operate in the following three modes: Hand, Off and Auto.
Hand: The frequency converter is locally operated and does not allow any remote control. By activating Hand a start signal is given.
OFF: The frequency converter stops with a normal stop ramp. When Off is chosen the frequency converter can only be started by pressing either Hand or Auto
on the Keypad.
12
Auto: In Auto-mode the frequency converter can be remote controlled (bus/digital).
0-40 [Hand ] Key on Keypad
Option:Function:
[0]DisabledHand key has no function.
[1 ]
*
EnabledHand key is functional.
0-41 [Off/Reset] Key on Keypad
Option:Function:
[0]Disable Off/ResetOff/reset key has no function.
*
[1 ]
[2]Enable Reset OnlyReset only. Stop (Off) function is disabled.
Enable Off/ResetStop signal and reset of any faults.
0-42 [Auto ] Key on Keypad
Option:Function:
[0]DisabledAuto key has no function.
[1 ]
*
EnabledAuto key is functional.
4.1.5. 0-5* Copy/Save
AF-60 LP™ Micro Drive Programming Guide
4
0-50 Keypad Copy
Option:Function:
The detachable Keypad of the frequency converter can be used for storing setups, and thus for transferring data when
moving parameter settings from one frequency converter to another.
NB!
Keypad Copy can only be activated from the Keypad and ONLY when the motor is coasted.
[1]All to KeypadCopy all setups from the frequency converter into the Keypad.
[2]All from KeypadCopy all setups from Keypad to frequency converter.
[3]Size indep. from Keypad Copy non motor size dependent data from Keypad to frequency converter
0-51 Set-up Copy
Option:Function:
Use this function to copy a set-up content into the Edit Set-up.
In order to be able to make a set-up copy ensure that
•the motor is coasted
•par. 0-10, Active Set-up, is set to either Set-up 1 [1] or Set-up 2 [2]
NB!
The keyboard/parameter database are blocked while Set-up Copy is running.
[0 ]
*
[1]Copy from Set-up 1Copy from Set-up 1 to edit set-up chosen in par. 0-11, Edit Set-up.
[2]Copy from Set-up 2Copy from Set-up 2 to edit set-up chosen in par. 0-11, Edit Set-up.
[9]Copy from Factory Set-upCopy from Factory Settings to edit set-up chosen in par. 0-11, Edit set-up.
No CopyCopy function is inactive
4.1.6. 0-6* Password
0-60 (Main) Menu Password
Range:Function:
Use password for protection against unintended change of sensitive parameters, eg. motor parameters.
Password protected parameters can always be read, but cannot be edited without entering the password.
13
AF-60 LP™ Micro Drive Programming Guide
4
0* [0 - 999]
NB!
Pressing buttons [MENU], [OK] and down will unlock the password. This will automatically enter the parameter editing screen in Quick Menu or Main Menu.
Enter the password for access to Main Menu via the [Main Menu] key. Select the number that should allow for changing
other parameter values. 0 means there is no password.
14
4.2. Parameter Group 1: Load/Motor
1-00 Configuration Mode
Option:Function:
Use this parameter for selecting the application control principle to be used when a Remote Reference is active.
NB!
Changing this parameter will reset parameters 3-00, 3-02 and 3-03 to their default values.
NB!
This parameter cannot be adjusted while motor runs.
AF-60 LP™ Micro Drive Programming Guide
[0 ]
*
[3]Process Closed LoopEnables process closed loop control. See par. group 7-3* for further information on PI-controller.
Speed Open LoopFor normal speed control (References).
When running in process closed loop, par. 4-10 Motor Speed Direction must be set to Clockwise [0]
1-01 Motor Control Principle
Option:Function:
[0]U/fIs used for parallel connected motors and/or special motor applications. The U/f settings are set in parameters 1-55
and 1-56.
NB!
When running U/f control slip- and load compensations are not included.
[1]
*
Advanced Vector Con-
trol
Normal running mode, including slip- and load compensations.
1-03 Torque Characteristics
Option:Function:
With more torque characteristics it is possible to run low energy consuming, as well as high torque applications.
*
[0 ]
[2]Energy SavingsThis function automatically optimizes energy consumption in centrifugal pump and fan applications. See par. 14-41
This parameter is only relevant when parameter 1-00 Configuration Mode is set to Process Closed Loop [3]. The pa-
rame ter is use d for dete rmining the refer ence or setpoint h andling w hen changing from Auto Mode to Hand Mo de on
the Keypad.
[0]Speed Open LoopIn Hand Mode the drive always runs in Open Loop configuration regardless of setting in par. 1-00 Configuration
Mode. Local potentiometer (if present) or Arrow up/down determines output frequency limited by Motor Speed High/
Low Limit (parameters 4-14 and 4-12).
[2]
*
As configuration in par.
1-00
If par. 1-00 Configuration Mode is set to Open Loop [1] function is as described above.
If par. 1-00 is set to Process Closed Loop [3] changing from Auto mode to Hand mode results in a setpoint change via
local potentiometer or Arrow up/down. The change is limited by Reference Max/Min (parameters 3-02 and 3-03).
4
4.2.1. 1-2* Motor Data
Enter the correct motor nameplate data (power, voltage, frequency, current and speed).
Run Auto Tune, see par. 1-29.
Factory settings for advanced motor data, par. 1-3*, are automatically calculated.
NB!
Parameters in parameter group 1.2* cannot be adjusted while motor runs.
15
AF-60 LP™ Micro Drive Programming Guide
4
1-20 Motor Power [kW]/[HP] (P
m.n
)
Option:Function:
Enter motor power from nameplate data.
Two sizes down, one size up from nominal AF-60 LPറ rating.
[1]0.09 kW/0.12 HP
[2]0.12 kW/0.16 HP
[3]0.18kW/0.25 HP
[4]0.25 kW/0.33 HP
[5]0.37kW/0.50 HP
[6]0.55 kW/0.75 HP
[7]0.75 kW/1.00 HP
[8]1.10 kW/1.50 HP
[9]1.50 kW/2.00 HP
[10]2.20 kW/3.00 HP
[11]3.00 kW/4.00 HP
[12]3.70 kW/5.00 HP
[13]4.00 kW/5.40 HP
[14]5.50 kW/7.50 HP
[15]7.50 kW/10.0 HP
[16]11.00 kW/15.00 HP
NB!
Changing this parameter affects par. 1-22 to 1-25, 1-30, 1-33 and 1-35.
1-22 Motor Voltage (U
m.n
)
Range:Function:
230/400 V [50 - 999 V]Enter motor voltage from nameplate data.
1-23 Motor Frequency (f
m.n
)
Range:Function:
60 Hz* [20-400 Hz]
1-24 Motor Current (I
m.n
Enter motor frequency from nameplate data.
)
Range:Function:
M-type dependent* [0.01 - 26.00 A]
1-25 Motor Nominal Speed (n
Enter motor current from nameplate data.
)
m.n
Range:Function:
M-type Dependent* [100 - 9999 RPM]
Enter motor nominal speed from nameplate data.
1-29 Auto Tune
Option:Function:
Use Auto Tune to optimize motor performance.
NB!
This parameter cannot be changed while motor runs.
16
1.Stop the frequency converter – make sure motor is at standstill
2.Choose [2] Enable Auto Tune
3.Apply start signal
– Via Keypad: Press Hand
AF-60 LP™ Micro Drive Programming Guide
- Or in Remote On mode: Apply start signal on terminal 18
[0]
*
[2]Enable Auto TuneAuto Tune function starts running.
OffAuto Tune function is disabled.
NB!
To gain optimum tuning of frequency converter, run Auto Tune on a cold motor.
4.2.2. 1-3* Adv. Motor Data
Adjust advanced motor data using one of these methods:
1.Run Auto Tune on cold motor. Frequency converter measures value from motor.
2.Enter X
3.Use R
NB!
These parameters cannot be changed while motor runs.
value manually. Obtain value from motor supplier.
1
, X1, and X2default setting. Frequency converter establishes setting based on motor nameplate data.
s
4
1-30 Stator Resistance (Rs)
Range:Function:
Depending on motor data* [Ohm]
Set stator resistance value.
1-33 Stator Leakage Reactance (X1)
Range:Function:
Depending on motor data* [Ohm]
Set stator leakage reactance of motor.
1-35 Main Reactance (X2)
Range:Function:
Depending on motor data* [Ohm]
Set motor main reactance.
4.2.3. 1-5* Load Independent Setting
This parameter group is for setting the load independent motor settings.
1-50 Motor Magnetization at Zero Speed
Range:Function:
This parameter enables different thermal load on motor when running at low speed.
*
[ 0 - 300%]
100 %
1-52 Min. Speed Normal Magnetizing [Hz]
Range:Function:
Enter a percentage of rated magnetizing current. If setting is too low, motor shaft torque may be reduced.
Use this parameter along with par. 1-50, Motor Magnetizing at Zero Speed.
17
AF-60 LP™ Micro Drive Programming Guide
4
0.0 Hz* [0.0 - 10.0 Hz]
Set frequency required for normal magnetizing current. If frequency is set lower than motor slip frequency, par. 1-50,
Motor Magnetizing at Zero Speed is inactive.
1-55 U/f Characteristic - U
Range:Function:
This parameter is an array parameter [0-5] and is only functional when par. 1-01, Motor Control Principle is set to U/
f [0].
0.0 V
*
[0.0 - 999.9 V]
Enter voltage at each frequency point to manually form a U/f characteristic matching motor. Frequency points are
defined in par. 1-56, U/f characteristics - F.
1-56 U/f Characteristic - F
Range:Function:
This parameter is an array parameter [0-5] and is only functional when par. 1-01, Motor Control Principle is set to U/f
[0].
0.0 Hz
*
[0.0 - 1000.0 Hz]
Enter frequency points to manually form a U/f characteristic matching motor. Voltage at each point is defined in par.
1-55, U/f Characteristic - U.
Make a U/f characteristic based on 6 definable voltages and frequencies, see below figure.
Simplify U/f characteristics by merging 2 or more points (voltages and frequencies), respectively, are set equal.
Illustration 4.1: Fig. 1 U/f characteristics
NB!
For par. 1-56 the following applies
[0] ู [1] ู [2] ู [3] ู [4] ู [5]
4.2.4. 1-6* Load Dependent setting
Parameters for adjusting the load dependent motor settings.
1-60 Low Speed Load Compensation
Range:Function:
Use this parameter to gain optimum U/f characteristic when running at low speed.
100 %* [0-199 %]
Enter percentage in relation to load when motor runs at low speed.
18
Change-over point is automatically calculated based on motor size.
1-61 High Speed Load Compensation
Range:Function:
Use this parameter to obtain optimum load compensation when running at high speed.
100 %
*
[0 - 199 %]
Enter percentage to compensate in relation to load when motor runs at high speed.
Change-over point is automatically calculated based on motor size.
AF-60 LP™ Micro Drive Programming Guide
4
1-62 Slip Compensation
Range:Function:
100 %* [-400 - 399 %]
Compensation for load dependent motor slip.
Slip compensation is calculated automatically based on rated motor speed, n
and the 4 pole 1800 RPM motor has an actual nameplate RPM of 1750 RPM, then 50 RPM is added to the output
frequency by the drive.
NB!
This function is only active when par. 1-00, Configuration Mode, is set to Speed Open Loop [0], and when par. 1-01,
Motor Control Principle, is set to Advanced Vector Control [1].
. Example: if par. 1-62 is set to 100%
M,N
1-63 Slip Compensation Time
Range:Function:
0.10 s [0.05 - 5.00 s]Enter slip compensation reaction speed. A high value results in slow reaction whereas a low value results in quick
reaction.
If low-frequency resonance problems arise, use longer time setting.
4.2.5. 1-7* Start Adjustments
Considering the need for various start functions in different applications, it is possible to select a number of functions in this parameter group.
1-71 Start Delay
Range:Function:
The start delay defines the time to pass from a start command is given until the motor starts accelerating.
Setting start delay to 0.0 sec. disables Start Function, [1-72], when start command is given.
0.0 s
*
[0.0 - 10.0 s]
Enter the time delay required before commencing acceleration.
Par. 1-72 Start Function is active during Start delay time .
1-72 Start Function
Option:Function:
[0]DC Hold/Delay TimeMotor is energized with DC holding current (par. 2-00) during start delay time.
19
AF-60 LP™ Micro Drive Programming Guide
[1]DC Brake/Delay TimeMotor is energized with DC braking current (par. 2-01) during start delay time.
[2]
*
1-73 Start Mode
Option:Function:
Coast/Delay TimeDrive is coasted during start delay time ( Driveoff).
The Start Mode parameter is used to catch a spinning motor after eg. mains drop-out.
This function is not suitable for hoisting applications.
4
[0]
*
[1]EnabledFrequency converter enabled to catch spinning motor.
DisabledCatch a spinning load disabled.
NB!
When catch a spinning load is enabled par. 1-71, Start Delay, and par. 1-72, Start Function, have no function.
4.2.6. 1-8* Stop Adjustments
To meet the need for various stop functions in different application these parameters offer some special stop features for the motor.
1-80 Function at Stop
Option:Function:
The selected function at stop is active in following situations:
•Stop command is given and output speed is ramped down to Min. Speed for Activating Functions at Stop.
•Start command is removed (standby), and output speed is ramped down to Min. Speed for Activating Functions
at Stop.
•DC-brake command is given, and DC-brake time has passed
•While running and calculated output speed is below Min. Speed for Activating Functions at Stop.
*
[0]
[1]DC holdThe motor is energized with a DC current. See par. 2-00 DC Hold Current for more information.
1-82 Min. Speed For Function at Stop [Hz]
Range:Function:
0.0 Hz* [0.0 - 20.0 Hz]
CoastThe drive is coasted.
Set the speed at which to activate par. 1-80 Function at Stop.
4.2.7. 1-9* Motor Temperature
With an estimated motor temperature monitor the frequency converter is able to estimate motor temperature without having a thermistor mounted. It is thus
possible to receive a warning or an alarm, if motor temperature exceeds upper operational limit.
1-90 Motor Thermal Protection
Option:Function:
Using Electronic Overload the motor temperature is calculated based on frequency, speed and time. GE recommends
using The Electronic Overload function, if a thermistor is not present.
NB!
Electronic Overload calculation is based on motor data from group 1-2*.
[0]
*
[1]Thermistor WarningA thermistor connected to either digital or analog input gives a warning if upper limit of motor temperature range is
[2]Thermistor TripA thermistor connected to either digital or analog input gives an alarm and makes the frequency converter trip if upper
No ProtectionDisables temperature monitoring.
exceeded, (see par. 1-93, Thermistor Resource).
limit of motor temperature range is exceeded, (see par. 1-93, Thermistor Resource.
20
AF-60 LP™ Micro Drive Programming Guide
[3]Electronic Overload
Warning
[4]Electronic Overload Trip If 90% of calculated upper limit of motor temperature range is exceeded, an alarm occurs and frequency converter
NB!
When the Electronic Overload function has been selected the drive will store the recorded temperature at power down and this temperature will resume at
power up regardless of the elapsed time. Changing par. 1-90 back to [0] No Protection will reset the recorded temperature.
If calculated upper limit of motor temperature range is exceeded, a warning occurs.
trips.
1-93 Thermistor Resource
Option:Function:
Select the thermistor input terminal.
*
[0]
[1]Analog Input 53Connect thermistor to analog input terminal 53.
[6]Digital input 29Connect thermistor to digital input terminal 29.
NoneNo thermistor is connected.
NB!
Analog input 53 cannot be selected for other purposes when selected as thermistor resource.
While this input functions as thermistor input, it will not respond to the function chosen in par. 5-13, Digital Input 29.
The value of par. 5-13 remains however unchanged in parameter database while function is inactive.
Input Digital/
Analog
Digital10 V<800 ohm - >2.9k ohm
Analog10 V<800 ohm - >2.9k ohm
Supply VoltageThreshold Cut-out
Values
4
21
4
4.3. Parameter Group 2: Brakes
4.3.1. 2-** Brakes
4.3.2. 2-0* DC-Brake
The purpose of DC-brake function is to brake a rotating motor by applying DC-current to the motor.
2-00 DC Hold Current
Range:Function:
This parameter either holds the motor (holding torque) or pre-heats the motor.
The parameter is active if DC Hold has been selected in either par. 1-72 Start Function or par. 1-80 Function at Stop.
*
[0 - 100%]
50%
NB!
Avoid 100% current too long as it may overheat the motor.
2-01 DC Brake Current
Range:Function:
50 %* [0 - 150%]
Enter a value for holding current as a percentage of the rated motor current set in par. 1-24 Motor Current. 100% DC
holding current corresponds to I
Set DC-current needed to brake rotating motor.
Activate DC-brake in one of the four following ways:
1.DC-brake command, see par. 5-1* choice [5]
2.DC Cut-in function, see par. 2-04
3.DC-brake selected as start function, see par. 1-72
4.DC-brake in connection with Flying Start, par. 1-73.
M,N
.
AF-60 LP™ Micro Drive Programming Guide
2-02 DC-Braking Time
Range:Function:
DC-braking time defines the period during which DC-brake current is applied to the motor.
10.0 s
*
[0.0 - 60 s]
NB!
If DC-brake is activated as start function, DC-brake time is defined by start delay time.
Set the time DC-braking current, set in par. 2-01, must be applied.
2-04 DC-Brake Cut-in Speed
Range:Function:
0.0 Hz* [0.0 - 400.0 Hz]
Set DC-brake cut-in speed to activate DC braking current, set in par. 2-01, when ramping down.
When set to 0 the function is off.
22
4.3.3. 2-1* Brake Energy Function
Use the parameters in this group for selecting dynamic braking parameters.
2-10 Brake Function
Option:Function:
Resistor Brake:
The resistor brake limits voltage in the intermediate circuit when the motor acts as generator. Without brake resis-
tor, the frequency converter eventually trips.
The resistor brake consumes surplus energy resulting from motor braking. A frequency converter with brake stops a
motor faster than without a brake, which is used in many applications. Requires connection of external brake resistor.
An alternative to the resistor brake is the AC brake.
NB!
Resistor brake is only functional in frequency converters with integrated dynamic brake. An external resistor must
be connected.
AC Brake:
The AC brake consumes surplus energy by creating power loss in the motor.
It is important to keep in mind that an increase in power loss causes motor temperature to rise.
[0]
*
[1]Resistor BrakeResistor brake is active.
[2]AC BrakeAC brake is active.
OffNo brake function.
AF-60 LP™ Micro Drive Programming Guide
4
2-11 Brake Resistor (Ohm)
Range:Function:
5 ű* [5 - 5000 ű]
Set brake resistor value.
2-16 AC Brake, Max Current
Range:Function:
100.0 %* [0.0 - 150.0 %]
Enter max. permissible current for AC-braking to avoid overheating of motor.
100% equals motor current set in par. 1-24.
2-17 Over-Voltage Control
Option:Function:
Use Over-voltage Control (OVC) to reduce the risk of the frequency converter tripping due to an over voltage on the
DC link caused by generative power from the load.
An over-voltage occurs eg. if the ramp down time is set too short compared to the actual load inertia.
[0]
*
[1]Enabled, not at stopOVC is running unless a stop signal is active.
[2]EnabledOVC is running, also when a stop signal is active.
NB!
If Resistor Brake has been chosen in par. 2-10 Brake Function the OVC is not active even though enabled in this parameter.
DisabledThe OVC is not active/required.
4.3.4. 2-2* Mechanical Brake
For hoisting applications an electro-magnetic brake is required. The brake is controlled by a relay, which releases the brake when activated.
The brake activates if frequency converter trips or a coast command is given. Furthermore, it activates when motor speed is ramped down below the speed set
in par. 2-22, Active Brake Speed.
23
4
2-20 Release Brake Current
Range:Function:
0.00 A* [0.00 - 100 A]
Select motor current at which mechanical brake releases.
2-22 Activating Mechanical Brake
Range:Function:
If the motor is stopped using ramp, the mechanical brake is activated when motor speed is less than Active Brake
Speed.
Motor is ramped down to stop in the following situations:
•A start command is removed (stand by)
•A stop command is activated
•Quick-stop is activated (Q-stop ramp is used)
AF-60 LP™ Micro Drive Programming Guide
If start delay time has passed, and motor current is below Release brake current, frequency converter
trips.
0 Hz
*
[0 - 400 Hz]
Select motor speed at which mechanical brake activates when ramping down.
Mechanical brake automatically activates if frequency converter trips or reports an alarm.
24
AF-60 LP™ Micro Drive Programming Guide
4.4. Parameter Group 3: Reference/Ramps
4.4.1. 3-** Reference/Ramps
Parameters for reference handling, definition of limitations, and configuration of the frequency converter's reaction to changes
4.4.2. 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-00 Reference Range
Option:Function:
Select the range of reference and feedback signals. Values can be both positive and negative, unless par. 1-00,
Configuration Mode, is set to Process Closed Loop [3]. In that case only positive values are allowed.
[0]
*
[1]-Max - +MaxRanges can have both positive and negative values.
Min - MaxReference setpoint ranges can have positive values only.
Select this if running in Process Closed Loop.
3-02 Minimum Reference
Range:Function:
0.00* [-4999 - 4999]
Enter value for minimum reference.
The sum of all internal and external references are clamped (limited) to the minimum reference value, par. 3-02.
3-03 Maximum Reference
Range:Function:
Maximum Reference is adjustable in the range Minimum Reference - 4999.
50.00
*
[-4999 - 4999]
Enter value for Maximum Reference.
The sum of all internal and external references are clamped (limited) to the maximum reference value, par. 3-03.
4.4.3. 3-1* References
Parameters for setting up the reference sources. Select the preset references for the corresponding digital inputs in parameter group 5.1*, Digital Inputs.
4
3-10* Preset Reference
Option:Function:
Each parameter set-up contains 8 preset references which are selectable via 3 digital inputs or bus.
Table 4.1: Par. 5-1* selection [16], [17] and [18]
-100.00 - 100.00%Enter the different preset references using array programming.
*
[0.00]
Normally, 100% = value set in par. 3-03, Maximum Reference.
However, there are exceptions if par. 3-00 is set to Min - Max, [0].
Example 1:
[18]
Bit2
0000
0011
0102
0113
1004
1015
1106
1117
[17]
Bit1
[16]
Bit0
Preset reference no.
25
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.