GE 4700E, 4800E Instruction Manual

GE Energy
Masoneilan* Products
4700E/4800E Electropneumatic Positioners
ATEX Instruction Manual
Corrosion resistant positioner
• Integrated 4000 Series I/P transducer
• Optional high-flow capacity
2 – 9
ATEX Instruction Manual GEA19513 – 03/2012 4700E and 4800E Series Electropneumatic Positioners
CONTENTS
WARNING ____________________________________________________________________________________________________________ 3 INSTRUMENT OPERATION _______________________________________________________________________________________________ 3
1. NUMBERING SYSTEM _____________________________________________________________________________________________ 4
2. TECHNICAL DATA ________________________________________________________________________________________________ 4
2.1. Performances _____________________________________________________________________________________________ 4
2.2. Schematic ________________________________________________________________________________________________ 4
3. ATEX INTRINSIC SAFETY MARKING and nL TYPE FOR MODEL 4000 I/P CONVERTER __________________________________________ 5
4. ATEX EXPLOSIONPROOF MARKING FOR MODEL 4000 I/P CONVERTER _____________________________________________________ 5
5. ELECTRICAL CONNECTIONS and CONDUIT ENTRY _____________________________________________________________________ 6
5.1. Current signal ____________________________________________________________________________________________ 6
5.2. Maximum Power __________________________________________________________________________________________ 6
5.3. Intrinsic Safety entity parameters ____________________________________________________________________________ 6
5.4. Conduit entry in flameproof application _______________________________________________________________________ 6
6. ASSEMBLY OF A 4700E OR 4800E POSITIONER ON A VALVE ______________________________________________________________ 7
7. PNEUMATIC CONNECTION OF POSITIONER 4700 E / 4800 E _____________________________________________________________ 7
8. INSTALLATION and START UP ______________________________________________________________________________________ 7
8.1. Installation _______________________________________________________________________________________________ 7
8.2. Start up __________________________________________________________________________________________________ 7
9. CALIBRATION OF THE 4700 E/4800 E POSITIONER _____________________________________________________________________ 8
10. MAINTENANCE SERVICE __________________________________________________________________________________________ 8
10.1. General rules _____________________________________________________________________________________________ 8
10.2. Before maintenance activity ________________________________________________________________________________ 8
10.3. During maintenance activity ________________________________________________________________________________ 8
10.4. After maintenance activity __________________________________________________________________________________ 9
11. SPECIAL CONDITIONS OF USE ______________________________________________________________________________________ 9
11.1. For Intrinsic Safety and Flameproof __________________________________________________________________________ 9
11.2. For Intrinsic Safety ________________________________________________________________________________________ 9
11.3. For Flameproof____________________________________________________________________________________________ 9
3 – 9
ATEX Instruction Manual GEA19513 – 03/2012 4700E and 4800E Series Electropneumatic Positioners
WARNING
BEFORE installing, using or carrying out any maintenance tasks associated with this instrument, READ THE INSTRUCTIONS CAREFULLY.
These instruments comply with the essential safety requirements of the European Directive ATEX 94/9/CE. It is certified to be used in Gas or Dust explosive atmospheres, groups IIA, IIB, IIC or IIIC:
Category II 1GD – zones 0, 1, 2, 20, 21 and 22 for the protection mode "ia" Category II 3G – zone 2 for the protection mode "nA & nL" Category II 2GD – zones 1, 2, 21 and 22 for the protection mode "d".
They also comply with the essential safety requirements of the European Directive EMC 89/336/CE as amended, for use within an industrial environment.
It is the end user's responsibility to:
Verify material compatibility with the application Ensure proper use of fall protection when working at heights, per Safe Site Work Practices Ensure use of proper Personal Protective Equipment Take the appropriate actions to ensure that site personnel who are performing installation, commissioning and
maintenance have been trained in proper site procedures for working with and around equipment, per Safe Site Work Practices
Products certified as explosion proof equipment MUST BE: a) Installed, put into service, used and maintained in compliance with European and/or national and local
regulations and in accordance with the recommendations contained in the relevant standards concerning potentially explosive atmospheres.
b) Used only in situations those comply with the certification conditions shown in this document and after
verification of their compatibility with the zone of intended use and the permitted maximum ambient temperature.
c) Installed, put into service and maintained by qualified and competent professionals who have been trained in
proper site procedures for for instrumentation used in areas with potentially explosive atmosphere and for working with and around equipment, per Safe Site Work Practices.
Under certain operating conditions, the use of damaged instruments could cause a degradation of the performances of the system which may lead to personal injury or death.
Use only genuine replacement parts, which are provided by the manufacturer, to guarantee that the products comply with the essential safety requirements of the European Directives mentioned above.
INSTRUMENT OPERATION
4700E/4800E apparatus: electro pneumatic positioner (force balanced principle) with integrated current to pressure
converter (4000 I/P Converter). It controls the position of the plug of a control valve to a 4-20 mA control signal. Feedback is obtained by means of a cam.
4800E is a positioner with a high flow pneumatic block.