FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Diaphragm Linear Actuator - FlowAct
Diaphragm actuators take the form of a flexible diaphragm, placed between
two casings. The upper section of the two chambers is designed pressure
tight, the lower chamber holds a spring opposing the force generated within
the pressure chamber of the actuator. The controlled air supply is connected
to the pressure tight chamber, and an increase or decrease of the air pressure
results in a positioning force of the stem. This kind of actuator is called single
acting with spring return positioning force for linear motion. The linear motion
/ stroke is limited by a stroke range from 10 - 100 mm and a positioning force
range from 500 - 60.000 N dependent on the actuator size. The actuator parts are
designed so that the actuator can be assembled in two fail safe positions, close
or open. Simplicity of design reduces maintenance and parts inventory costs. It
is ideally suited for flow and pressure control of liquid and gas media in oil and
gas, power, chemical and petrochemical processing and related industries. The
FlowAct is manufactured to ISO 9001 standards.
The following instructions are designed to assist in unpacking, installing and
performing maintenance as required on Flowserve FlowAct diaphragm linear
actuators. This instruction manual does not include specific product design data.
Such data can be found on the actuator’s serial plate or specification documents;
additionally, dimensional information can be found in the FlowAct technical
bulletin. Procure needed documents as necessary before you begin any work
on the valve.
Figure 1: FlowAct - Actuator, Spring close
User Instructions cannot deal with all possible situations and installation options.
It is required that only trained and qualified technicians are authorized to adjust,
repair or work on diaphragm linear actuators, positioners and other accessories.
Review this bulletin prior to installing, operating or performing any maintenance
on the actuator. Additional Installation, Operation, and Maintenance Instructions
(IOMs) cover other features (such as positioners and other accessories).
To avoid possible injury to personnel or damage to actuator parts, WARNING andNOTICE indicators must be strictly followed. Modifying this product, substituting
non-factory parts or using maintenance procedures other than outlined could
drastically affect performance and be hazardous to personnel and equipment and
may void existing warranties. This manual should be used in conjunction with
applicable local and national laws. Failure to comply with User Instructions will
render the manufacturer’s guarantee and liability null and void. Unless otherwise
agreed, the manufacturer’s general terms and conditions of sale shall apply.
Read the user instructions carefully before use.
Keep for future reference.
Figure 2: FlowAct - Actuator, Spring opens
Contents
1 Scope of Manual37 Storage413 Troubleshooting12 - 13
2 Intended Use38 Unpacking4 - 514 Operating the Handwheel13
• Air supply max. 6 bar or as indicated on the type plate
• Protection class IP 54, with air purging IP 64
• Without or with attachments like:
- top mounted handwheel
- top mounted adjustable stroke limitation - max. 39 kN
- side-mounted handwheel - max. 39 kN
- central-mounted handwheel
components to match each application. There are two fail safe
positions, close or open without or with attachments.
The FlowAct is designed in compliance with EN 1349:2009
- Industrial Process Control Valves (DIN EN 1349 and VDE
0409-1349).
The FlowAct actuator is designed for use in MODERATE and
WORLDWIDE environmental conditions, standard ambient temperature range -40°C to +80°C (-40°F to 176°F). A special version is available with conditions up toup to -60°C, air humidity
up to 93% non-condensing, air pollution up to 300 µg/m3, (unless restricted by the accessories).
The product offering may include optional ancillary equipment,
such as positioners, air-filter regulators, solenoid valves, limit
switches or boosters. Digital, I/P, or pneumatic positioners
can be mounted direct or with a mounting bracket. Refer to
the relevant manufacturer‘s user instructions for information
regarding other ancillary equipment.
3 Product Identification
• Comes with or without ancillary equipment
2 Intended Use
WARNING
rated for specific application conditions. Before installation, check the serial number and / or the tag number to ensure that the valve and actuator being installed are correct
for the intended application. Do not use the valve assembly outside of its rated design limits. Exceeding the design
limits may cause hazardous conditions including leakage
of the process media or rupture of the pressure boundary
resulting in possible process loss, equipment or environmental damage, or serious personal injury or death.
Specific product design data can be found on the actuators
serial plate, data sheet and the calculation sheet (in acc. to the
IEC 60534-7:2010).
The FlowAct handles a wide variety of general service applications.
Diaphragm linear actuators are
pressure vessels designed and
Each FlowAct diaphragm linear actuator comes with an attached serial plate which includes key information specifically
for each actuator:
Figure 3: Serial Plate (Example)
The same serial number shown on the plate will appear on all
FlowAct data sheets, dimensional drawings, bills of material,
and spare parts lists. Other information located on the serial
plate is self-explanatory for the FlowAct actuator.
You can download .pdf versions of the FlowAct documentation including a sales brochure, technical bulletin and user
instructions at www.flowserve.com. It is the user’s responsibility to keep this and related documentation on file and accessible for the FlowAct product.
The FlowAct consists of the actuator, yoke and attachments
and accessories. The actuator is designed with a high level
of interchangeability allowing the user to assemble the greatest possible number of variations from a minimum number of
4 FlowAct Modification
FlowAct linear actuators are generally delivered as tested and
assembled units.
flowserve.com
3
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Unauthorized modification of the FlowAct diaphragm linear actuator voids the product test
certification and product warranties, could drastically affect product performance and could be
hazardous to personnel and equipment.
NOTICE
in compliance with all test routines, guidelines and engineering standards.
Before FlowAct re-installation, all necessary tests must be repeated and recorded
5 Safety
Safety terms - WARNING and NOTICE - are used to highlight
specific dangers and / or provide additional information
that may not be readily apparent in the User Instructions.
WARNING directions must be strictly followed.
follow HPE standards. (Nonreturnable packaging may contain
up to 90% recyclable materials.)
7 Storage
Maximum storage time for diaphragm linear
actuators is 2 years at 25 °C.
NOTICE
Upon arrival on site, store the FlowAct actuator on a solid base
in a cool, dry closed room. Until its installation, the actuator
must be protected from the weather, dirt and other potentially
harmful influences.
Do not remove the protective covers from the air supply connection of the actuator or from the instrument and accessories until the actuator is ready for installation at the site.
Rubber becomes brittle, lubricants become
resinous, see also ISO 2230.
WARNING
death and substantial property damage can occur if proper
precautions are not taken.
NOTICE indicates practices or provides
NOTICE
additional technical information.
or
WARNING indicates that
severe personal injury,
Grey fields indicate safety-related informations.
6 Packaging and Transport
Pay close attention to shipping marks and
transport pictograms.
Careful packing, loading and transport arrangements are required to prevent products from being damaged during transport. Standard packaging includes a cardboard box, with or
without a wooden pallet base as needed. Special packaging
may include a wooden box. Packaging may use cardboard,
plastic wrap, foam, or paper as packing material. Filling material may be a carton type or paper.
8 Unpacking
Hoisting and lifting are inherently dangerous
activities and require safe rigging and proper
training to mitigate hazards. Use standard industry safety practices, personal protection,
and warranted lifting devices.
WARNING
tuator. Do not allow the actuator assembly to rotate during
removal. Do not stand under suspended loads. Failure to
do so can cause serious personal injury and damage the
actuator or nearby equipment.
NOTICE
low the sling to touch the stem, travel indicator or peripheral
equipment. Observe the maximum permitted carrying capacity.
1. Check the packing list against materials received to
ensure all components and accessories are present.
Be aware that the center of gravity may be
above or beside the lifting point. Do not al-
Crushing hazard ! Arrange rigging to prevent tipping of the ac-
Shipping marks display product and package dimensions and
weight (for further information request Packaging and Sending Instructions, Form L 002). Packing guidelines for export
4
2. Place and hook a double-leg sling (if necessary a tripleleg sling) into the lifting rings mounted on the actuator.
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
3. You can alternatively place a sling around the actuator
case just above the yoke.
4. Upon removing the actuator from the packaging, we
recommend that you:
• Promptly touch up any damage to the paint that of-
fers corrosion protection.
• Contact your shipper immediately to report any
damage.
• Call your Flowserve representative if you experience
any problems.
Do not remove the protective covers from the
air supply connection of the actuator or from the
instrument ports of the actuator and accessories
until the actuator is ready for installation at the site.
Figure 4: Triple-Leg Sling (Example)
9 Installation
The actuator must be installed and commissioned by qualified staff - personnel who are familiar with the installation, commissioning and
operation of this product and possess the relevant qualifications in their field of activity.
Prior to installation of the actuator, we require, that you check the following conditions to reduce the risk of malfunction and
safety related incidents.
No.CheckPossible malfunction or safety related incident
1Confirm that the nominal / operational data on the
serial plate matches the operational data of the
facility.
An operational mismatch can cause considerable damage to
the actuator or may lead to a failure at the facility.
Table 1: Basic safety massages for installing the actuator (continued on next page 6)
5
flowserve.com
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
No.CheckPossible malfunction or safety related incident
2Confirm that the ambient temperature is not elevated
permanent above 160 °F (70 °C)(unless restricted by
the accessories).
3Confirm that the air supply and instrument signal
lines are dry and clear of dirt and oil.
4Confirm that the actuator and valve can be installed in
an upright position.
5Confirm that the yoke and needed parts are available
for mounting on the valve.
6Confirm that the valve stem and connecting parts
match.
7Confirm the actuator has enough overhead clearance
to disassemble the valve from the pipeline.
A sustained exceeding of the permissible ambient temperature
of 18 °F (10 °C) may halves the lifetime of non-metallic components, such as diaphragms, O-rings and scraper rings.
At a minimum, the instrument air must conform to ISA- 7.0.011996 (ISO 8573-1 Compressed Air - Class 2) requirement or
those of the accessory manufacturer.
Non-upright positioning may result in premature wear.
Yoke - connection dimensions see page 7
Yoke - connection dimensions see page 7.
Minimum clearance zone see page 8
8If there is an unused air connection ensure that it is
properly sealed (see page 7).
9Confirm removal of all hazards and ensure appropriate
protective measures are in place.
10Confirm the valve / actuator is grounded in order to
prevent an electrical discharge.
11Throttling control valves are typically equipped with
a pneumatic actuator and valve positioner. Refer to
the appropriate positioner manual for connections
and maximum air supplies.
The venting chamber of the pneumatic actuator is always
equipped with a venting plug. The pneumatic actuator types
253, 503 and 701 have two air connectors joining the pressure-tight actuator housing. One of this air connectors is used
to control the actuator depending on the mounted accessories.
The remaining connector on the actuator (S) or on the yoke (T)
must be appropriately sealed. This feature is not applicable for
type 1502 and 3002.
none
Noncompliance may result in electrical discharges.
The air supply must be limited to less than 87 psig (6 bar)
per the actuator serial plate. An air filter regulator should be
installed to ensure that the supply pressure to the pneumatic
actuator does not exceed the air supply pressure indicated on
the serial plate.
Table 1: Basic safety massages for installing the actuator
After these requirements are confirmed the actuator can be installed and connected to the valve.
6
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
62
~ M
Stroke
50
62
10
11
14
2 x M8
T Internal Air Supply
Yoke - connection dimensions (mm)
S
External Air Supply
VDI/VDE 3847
interface
45
T
G
Supply
HY
Ø B
Ø D
Additional interface for MULTI function yoke onlyAdditional internal air supply for IAS and MULTI-yoke only
14
2 x M8
50
Air
Actuator Size
2505007001500 3000
G 3/8 (Plug acc. to DIN 908 & O-ring 10x2 mm - if appl.)
T
G 1/4 (Plug acc. to DIN 906 - if applicable, G 1/2 - DVGW)
Packing Design -> adjustable -> Ø B = 65 mm, M = 105 mm, G = M12, Ø D = 95 mm and HY = 20 mm only !
Packing Design -> spring loadet -> Ø B = 82 mm, M = 170 mm, G = M12 only !
Table 2: Basic safety massages for installing the actuator
1)
, VariCool
flowserve.com
7
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Minimum Clearance Zone
~ 180 mm
for actuator
~ 7.1 inch
Removal space
~ H
valve
Height of
~ R
Face to face
Figure 5: Overhead clearance drawing
~ R~ H
Actuator Size
250mm135195290-335595
500mm180195330-460870
700mm205205345-600925
1500mm275-415685800-
3000mm275-4156851140-
without
accessories
Table 3: Overhead clearance dimensions / drawing
accessories
direct mounted
accessories
NAMUR -
mounted
dimensions
side mounted
hand wheel
with
without
hand wheel
10 Assembly on valve
structions using only original equipment manufacturer
The FlowAct diaphragm linear actuator is allowed to be assembled and reassembled only
by qualified staff - personnel who are familiar
with assembling, reassembling, installation and
commissioning of this product, and possess the
relevant qualifications in their field of activity.
8
When performing repairs, personnel are to follow these in-
(OEM) spare parts and recommended special tools to ensure
the reliability of the FlowAct diaphragm linear actuator.
Only Flowserve trained and authorized personnel are allowed
to repair (disassemble and reassemble) the FlowAct in hazardous areas.
Actuators for oil and grease-less service or oxygen service
may only be disassembled and reassembled in clean rooms
(ISO 14644- ISO 8, US FED STD 209 E - M 6.5, or equivalent).
max
with
top mounted
hand wheel
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
WARNING
Diaphragm linear actuators are pressure vessels.
Improper opening of the actuator can result in bodily injury.
Actuator assembly procedure
1. Fix the valve on the assembly table.
NOTICE
mounting position !
2. Lubricate all threads with a suitable, approved lubricant (see Section 16).
3. Mount the actuator / yoke and yoke lock nut (76) onto
the valve bonnet.
4. Finger tighten and fix the yoke lock nut; turn clockwise
(see Section 15).
NOTICE
The orientation of the valve must be
in accordance with the appropriate
The legs of the yoke should be parallel to the flow direction !
14. The valve is ready for the mounting of the accessories.
Actuator
344
249
240
76
345
113
5. If the fail safe position at air failure moves the stem
into closing position then must the actuator connected
with the air supply to move the stem into the open
(retracted) position (in most cases).
WARNING
tween the yoke legs while the valve is in operation.
6. Mount the lock nut (113) and lower coupling (345)
onto the valve stem.
7. Justify the plug against the seat.
8. Adjust the distance between the lower coupling (345)
ant the upper coupling (249) with the aid of an adapter
in stroke height (Figure 7).
9. Disconnect the air supply so that the actuator moves
to the close position.
10. Mount the cap screws (240).
11. Lock the lock nut (113). Secure the upper coupling
(249) against turn unwanted with a wrench.
12. Adjust the stroke indicator scale so that the zero mark
is in conjunction with the stroke indicator.
13. Perform three full strokes and check if the stroke indicator scale correspond with the end positions.
Stroke
Figure 7: Stroke adjusting
9
flowserve.com
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Reassemble the valve into the pipe
1. Remove the protective flange covers and coating from
the control valve; clean the flange gasket surface.
NOTICE
graphite gaskets. Review a current chemical resistance list before applying.
Unsuitable cleaning agents can damage and cause leakage in PTFE and
11 Valve Quick-Check
Apply appropriate personal protective equipment when working on the control valve to
prevent hazards arising from the operation.
Protect yourself against freezing, burns and
cuts by wearing appropriate protective clothing, gloves and eye protection.
2. Install the valve so that the actuator is in an upright position whenever possible. Vertical installation permits
easier actuator maintenance.
3. Install and connect the control valve to the pipeline.
Locate gaskets in the center of the body flanges and
secure nuts and bolts.
4. Connect the air supply and instrument signal lines.
Do not over-tighten packing.
Sudden exposure of the control valve to full
working pressure and temperature may cause
stress cracks.
Prior to valve operation, we require, that you check the following conditions to reduce the risk of malfunction and safety
related incidents.
No.Important informationPossible malfunction or safety related incident
1
Avoid critical operating conditions where excessive noise
or vibration levels might occur.
2
Avoid frequent system start-ups and shutdowns.Critical operating conditions, which can damage the
3
Keep the operating medium free of foreign particles.Installing a suitable strainer upstream of the control valve
4
Instrument air must conform to ISA 7.0.01-1996 (with a dew
point at least 18 °F (10 °C) below ambient temperature, particle size below 1 µm and oil content not to exceed 1 ppm)
5
6
Do not touch the body and bonnet ! The temperature of the operating medium is transferred to the
surface of the linear actuator.
Critical operating conditions can cause excessive or hazardous levels of vibration or noise.
Impermissible continuous operation of a control valve
under critical conditions can damage the valve.
control valve, may be encountered during system start-up
or shut down.
can prevent foreign particles from damaging the valve.
Contaminated instrument air can damage the accessories
and diaphragm linear actuator or cause them to fail.
Excessive hot surface temperatures can put you at risk for
burns.
Frigid surface temperatures can put you at risk for
freezing.
Impermissible levels of vibration can cause hearing
loss, vascular and nerve damage and damage to joints
and bones. Use hearing protection when noise levels
exceed 80 dB(A).
10
7
Incorrect maintenance can result in the emission
of hot, cryogenic, and / or toxic operating media.
Table 5: Basic safety massages for operating the valve
Incorrect maintenance can put you at risk for heat
related burns, freezing, acid burns or poisoning.
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
WARNING
while the valve is in operation.
Prior to start-up, we strongly recommend that you:
1. Stroke the valve and compare the plug position
indicator on the stem clamp to the stroke indicator
plate. The plug should change position in a smooth,
linear fashion.
NOTICE
such as PTFE. If over tightened, excessive friction may
impair smooth control.
2. Adjust instrument signals to ensure a full stroke.
Due to risk of crushing hazard, do
not work between the yoke legs
Graphite packing commonly creates
more friction than other materials,
12 Actuator Maintenance
Maintenance intervals and service life of an actuator is unique
to local environmental conditions at the site. The intervals
specified in the User Instructions are recommendations and
serve only as a guide. Under difficult operating conditions,
maintenance may be more frequent. We strongly recom-
3. Check the packing box bolting to ensure the correct
adjustment.
NOTICE
that may impede plug movement.
4. Continuously increase load until operation parameters
are reached.
5. Minor relaxation of the flange bolting is possible after
initial assembly. Retorque the bonnet flange bolting
if necessary before installation or following an initial
temperature excursion to ensure the bonnet gaskets
do not leak.
(See User Instructions - Control Valve).
mend a site survey followed by a documented procedure for
performing the maintenance work. Maintenance personnel
should perform and log the work accordingly. The data collected can be used as a basis for dynamically determining the
maintenance intervals and activities.
Over tightening can cause excessive
packing wear and high stem friction
Recommended Maintenance Actions
No.
1Visual inspection of
2Visual inspection of
3Visual inspection of
4Operation test
Recommended maintenance actions using the Logix digital positioner with ValveSight diagnostic solution software
5Visual inspection of
diagnostic interface
6Check health parameter
of actuator
7Check health parameter
of positioner
Service
the actuator
the tightness
Preventive maintenance
of the diaphragm
case bolting
Inter-
val
Bi-
weekly
Bi-
weekly
Yearly No actionRetighten case bolting if
Weekly No action -
Warn-
ing
Warn-
ing
GoodAdequateInadequate
No actionClean actuator stem with a
soft cloth
No actionRetighten leaky air supply,
case bolting
Dependent upon results of previous maintenance (see numbers 1 and 2 above) or a
minimum of once every 10 years
diaphragm leaks.
No actionPerform 3 full strokes using air supply; check for leakage
Take action per warningOverhaul or replace required part per
valve is healthy
No action -
actuator is
healthy
No action positioner
healthy
is
Check and retighten air
supply
Start step testOverhaul or replace positioner after
Valve Condition
Repair or replace actuator according to
product life cycle
Replace leaky air supply, diaphragm,
O-ring immediately
Remove from service and replace
case bolting, diaphragm immediately if external leakage persists or
if bolting is damaged
alarm
Overhaul or replace actuator after
alarm
alarm
Table 6: Service activities check list
11
flowserve.com
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Prior to valve maintenance it is required that you check the following conditions to reduce the risk of malfunction and safety
related incidents.
No.
1Check for signs of leakage through the case bolting
and end flanges.
2Check if all nuts and bolts are securely fastened.
3Check valve for smooth, full-stroke operation. Un-
steady stem movement could indicate an internal
valve problem.
WARNING
from all moving parts when operating the control valve can
cause serious injury.
1. Clear all dirt and / or foreign material from the shaft
and control valve.
2. If leakage is detected, retighten the bolting.
3. Activities on the valve, see separate document.
CheckPossible malfunction or safety related incident
Table 7: Basic safety massages for maintenance the valve
Crushing hazard ! Failure to keep
hands, hair, and clothing away
Tighten the case bolting nuts. See Section 14: Disassembly and
Reassembly for instructions. Also see Section 15.
Avoid critical operating conditions if excess noise or
vibration levels occur during operation.
Internal valve failure requires an immediate overhaul or actuator replacement by qualified stuff.
6. Make sure all accessory brackets and bolting are
securely fastened.
7. Check control valve health parameters:
• Characteristic curves of the valve with flow
• Upstream pressure
• Downstream pressure
4. Make sure all nuts and bolts are securely fastened.
5. If possible, stroke the valve and check for smooth,
full-stroke operation. Unsteady stem movement could
indicate an internal valve problem.
into the control room.
NOTICE
differ by more than 5%, maintenance may be required.
Monitor trim and bonnet components. If nominal and actual values
13 Troubleshooting
Contact customer service department or contract partner for any fault or defect found, otherwise
the manufacturer‘s guarantee shall be rendered null and void and the manufacturer released from
any responsibility. If the user performs the repairs, these User Instructions must be adhered to and
carried out in a competent manner. Original Equipment Manufacturer spare parts must be used to
make the repair.
DefectNo.Possible CausesRemedy
Stem does not move1.1• No energy supply (pneumatic air)
to actuator and accessories (positioner, air filter regulator, solenoid
valve, limit switch, and/ or special
accessories)
• Pneumatic actuators:
Check supply for leaks
Check air pressure (usually 6 bar; 88 psig)
12
1.2• Mounted accessories do not work• See User Instructions for accessory manufacturer
1.3• Pneumatic actuator is defective• Contact customer service department or contract
partner
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
DefectNo.Possible CausesRemedy
Jerky stem movement2.1• Damaged stem• Contact customer service department or contract
partner
2.2• Actuator not powerful enough• Compare actuator specifications on the serial
plate with operation specifications of the facility. If
incompatible, contact customer service department
or contract partner
Stem travel less than full stroke
(0 to 100 %)
No limit switch signal4.1• Power supply to limit switch
Unstable positioner5.1• Defective positioner• See user instruction of the positioner manufacturer
14 Operation of the handwheel
WARNING
during regular operation. Actuation is only permitted with
separated air supply !
1. The handwheel is always in the neutral position in the
delivery condition.
2. The handwheel are designed to act against the fail
safety position of the actuator. That means in the
case of an pneumatic actuator design with restoring
springs.
3.1• Air supply pressure too low• Provide air at the pressure stated on the serial plate
(European production only).
3.2• Pneumatic actuators:
Improper handwheel position
3.3• Improperly adjusted or defective
positioner
3.4• Foreign particles in valve seat or
damaged trim
interrupted
4.2• Limit switch out of adjustment• Readjust limit switch operating distance; see limit
Table 8: Trouble-shooting
Due to risk of crushing hazard,
do not work with the handwheel
3. All handwheel designs are immediately ready for use,
4. Check the progress of the stroke adjustment on the
5. If normal operation is to be resumed, the handwheel
• Move handwheel to limit position , otherwise
contact factory for information.
• Readjust positioner to positioner manufacturer‘s
specification
• Contact customer service department or contract
partner
• Check power supply
(connections, circuit breakers, voltage)
switch data sheet
NOTICE
out the actuator the handwheel has no function.
except the lateral handwheel for the 1502 and 3002
actuator. In the event of fail safe position - spring-to-
open (retracted) - before using, the handwheel must
turned counterclockwise up to contact the drive pin the
coupling and subsequently locked.
stroke indicator scale.
must be turned always to the neutral position.
When adjusting, then the handwheel
press against the spring force - with-
15 Disassembly and Reassembly
The FlowAct linear actuator is allowed to be disassembled and reassembled only by qualified staff
- personnel who are familiar with disassembling, reassembling, installation and commissioning
of this product, and possess the relevant qualifications in their field of activity.
flowserve.com
13
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
When performing repairs, personnel are to follow these
instructions using only original equipment manufacturer
(OEM) spare parts and recommended special tools to ensure
the reliability of the FlowAct linear actuator.
Only Flowserve trained and authorized personnel are allowed
WARNING
Prior to disassemble and reassemble, we require, that you check the following conditions to reduce the risk of malfunction
and safety related incidents.
No.Important informationPossible malfunction or safety related incident
1Disregarding these instructions may bring serious or
harmful consequences.
2
Always observe system safety instructions
when preparing for and performing the repair
procedure.
Pneumatic actuator are pressure vessels.
Improper opening of the actuator can result in bodily injury.
to repair (disassemble and reassemble) the FlowAct in hazard
areas.
Actuators and valves for oil and grease-less service or oxygen
service only be disassembled and reassembled in clean rooms
(ISO 14644- ISO 8, US FED STD 209 E - M 6.5, or equivalent).
Failure to comply with these user instructions will render
the manufacturer‘s guarantee and liability null and void.
Unless otherwise agreed, the manufacturer‘s general
terms and conditions of sale shall apply.
Potential hazards and their sources are under the operator‘s
influence. The operator must observe national and international environmental regulations for control valve removal
from the pipe and cleaning. Permissible exposure limits
must be maintained, appropriate personal protective equipment must be used and service personnel must be properly
instructed in performing the repair procedure.
3Make sure the pipeline is depressurized an in
ambient state, also a suitable rigging (e.g.
Endless Sling) and securing devices (e.g. Vee Trough
with Stands / Vise) are readily available.
4Confirm that you have the required spare parts at the site.Not having the full complement of parts, accessories and
5
6Review the serial plate information to identify the actua-
7Check all parts for damage such as scoring, deformities,
Confirm that you have the required tools avail-
able to manage the disassembly and reassembly
(Special Tools on request !).
tor. The serial number and the part numbers needed are
required when ordering spare parts.
corrosion or overexpansion.
Table 9: Basic safety massages for repairing the actuator
Remove the valve / actuator from the pipeline in a depressurized and ambient state. Failure to do so can cause serious personal injury.
The control valve is not equipped with integral stands,
therefore guard against the valve from tipping over. Bodily
injuries can be the result. Use appropriate clamps, blocking or other stabilizing support. Attachment to overhead
crane can ensure stability.
tools can slow or stop repair work.
Improper tools and / or improper use of tools can result
in personal injury or damage to the parts.
A serial plate used for product identification is attached on
every valve / actuator (See Section 3: Product Identification).
If in doubt, replace faulty parts.
Never reuse gaskets.
After these requirements are confirmed the pneumatic actuator can be maintained and repaired.
14
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Disassemble the actuator from
the valve:
WARNING
Improper opening of the actuator
can result in bodily injury.
1. Disconnect the air supply from the actuator and / or
assembled accessories.
2. Disassemble the accessories from the actuator as necessary.
3. If is mounted a handwheel-side disassemble this first
(see pages 37 - 38).
4. Realize the fail safe position of the actuator. The coupling
parts must be free of positioning force.
Crushing hazard ! The
Actuators are pressure vessels.
WARNING
actuator stem is under
spring load. Never disconnect the air supply during
next steps, the stem will extends very quickly.
• If the actuator stem is extended, drive it into re-
tracted position by connecting air supply.
344
249
Actuator
240
76
345
113
Valve
• If the actuator stem is retracted no further action
is required.
• If the valve type is a three way valve drive the stem
into center position by connecting and control air
supply.
5. Keep upper coupling (249) from turning by secure with
a wrench. Turn the lock nut (113) clockwise to loosen.
6. Turn the cap screws (240) counterclockwise to loosen.
7. Turn the yoke lock nut (76) counterclockwise to loosen.
8. Disconnect the air supply from the actuator if applicable.
9. Lift off the actuator safely.
10. Place the actuator on an assembly table and fix the
yoke for disassembly.
The modular design of the actuators enables a wide variety
of variants. Following therefore is always described the
individual module and not the entire actuator. We ask for your
understanding.
flowserve.com
15
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Reassemble the Actuator onto
the valve:
1. Mount the actuator onto the bonnet and tighten the
yoke lock nut (76) clockwise.
The legs of the yoke should be parallel
NOTICE
to the flow direction.
2. Move the actuator to the open position.
3. Screw in the lock nut (113) onto the valve stem so it
is screwed all the way and lower coupling (345) three
turns and move the actuator into the closed position.
The plug must be aligned onto the
NOTICE
seat. The cushioning effect of the bel-
lows can be prevented by tightening the packing follower.
4. Move the actuator back into the open position and
adjust the distance between the lower coupling (345)
and upper coupling (249) by adjusting the stroke length.
Valve sizeStroke
+ 0,5
15 - 251/2“ - 1“10
15 - 501/2“ - 2“20
65 - 1003“ - 4“40
125 - 1506“60
1)
200 - 300
8“ - 12“ 1)80
40016“100
Table 11: Stroke adjustment length ( 1) depends on the valve
series)
mm 0.394
+ 0,5
mm 0.787
+ 0,5
mm 1.574
+ 0,8
mm 2.362
+ 0,8
mm 3.150
+ 0,8
mm 3.937
+ 0.02
+ 0.02
+ 0.02
+ 0.03
+ 0.03
+ 0.03
in.
in.
in.
in.
in.
in.
9. Check handwheel-side for correct limit position, if
applicable.
10. Reassemble the accessory on the valve as necessary,
see relevant accessory User Instruction.
11. Perform three full strokes and check the free movement
of the actuator.
12. For installation the valve into the pipeline and further
steps see User Instructions for applicable valve types.
13. Log the maintenance interval and the work performed.
Actuator
344
249
240
76
345
113
16
5. Move the actuator to the close position and install the
cap screws (240).
6. Lock the lock nut (113). Keep upper coupling (249)
from turning by securing with a wrench.
7. If a handwheel-side was mounted reassemble as next
(see pages 37 - 38).
The handwheel-side always presses
NOTICE
on the coupling, depending on the
safety position when actuated. The lever arms must be
positioned so that this condition is given.
8. Place the handwheel-side on the yoke and straighten
it, mount the washer (140) and hex bolt (150) and
tighten it, if applicable.
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Disassembly instruction of the actuator subassembly
NOTICE
1. Fix the actuator on the assembly table, if this is not
already happened.
2. Loosen the lock nut (344) counterclockwise and disassemble the upper coupling (249) and lock nut clockwise (see page 15).
3. Disassemble the short hexagon bolts (335), plain washers (337), hexagon nuts (351) and ring nuts (209).
4. Pull off the protection sleeve (339).
springs inside.
5. Lubricate the threads and loosen the long hexagon bolts
(336), plain washers (337) and hexagon nuts (351) uniformly in a clockwise sequence as the springs expand.
Limit disassembly only to necessary components.
WARNING
Risk of injury by jumping out parts ! Pre-loaded
Reassembly instruction of the actuator subassembly
NOTICE
13. Lubricate the new O-ring (275), new scraper ring (273)
with an appropriate lubricant and install into the guide
bushing (253).
14. Lubricate the new O-ring (272) with an appropriate
lubricant.
15. Lower the thrust washer (255), diaphragm (225), O-
onto the stem (211).
16. Lubricate the thread of the stem (211) with an appropriate lubricant and install and finger tighten the special nut (348).
The diaphragm plate should be positioned to the diaphragm with the aid
18
NOTICE
8.8 or higher, as well as washers and nuts.
6. Lift off the diaphragm casing (203), distance plate
(231) and spring adjusting plate (326).
7. Remove the actuator springs (229).
8. Carefully remove the diaphragm-stem unit (211 - 349).
9. Remove the scraper ring (273) and O-ring (275).
10. Secure the diaphragm-stem unit into the Special Tool.
11. Loosen the special nut (348) counterclockwise and
remove the lock washer (349), spacer bushing (228),
diaphragm plate (227), diaphragm (225), O-ring (272)
and thrust washer (255).
12. Check stressed surface areas for damage such as scoring and deformities. Use a brass brush or similar tool to
clean bolting. Check for corrosion or any other damage.
We recommend using threaded bolts
meeting standards from ISO 898-1,
17. Turn the special nut (348) clockwise using a suitable
torque wrench.
18. Loosen and remove the diaphragm-stem unit (211-
349) from the Special Tool. Lubricate the actuator
stem with an appropriate lubricant.
19. Carefully lower the diaphragm-stem unit (211- 349)
into the diaphragm casing.
NOTICE
Mark align.
20. Install and align the actuator springs (229).
21. Install and positioning the spring adjusting plate (326)
such that the drilling, mark and air connection match.
22. Install the distance plate (231) and diaphragm casing
(203), positioning the casing such that the drilling,
mark and air connections match.
23. Lubricate the threats of the long hexagon bolts (336)
with an appropriate lubricant then compress the springs
Position the diaphragm-stem unit
such that the air connection and the
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
uniformly in a clockwise sequence by tightening the long
hexagon bolts (336), plain washers (337) and hexagon
nuts (351). Alternative method see NOTICE step 5.
24. Install the short hexagon bolts (335), hexagon nuts (351)
as well as the hexagon bolts (335) and ring nuts (209).
25. Tighten the nuts (351) using a crosswise pattern in
four steps.
26. Install the protection sleeve (339).
27. Reassemble the yoke and coupling parts, perform three
full strokes then check the tightening of the casing bolting.
Item #
Part
WWEU
2026.1Diaphragm Casing
2036.2Diaphragm Casing
2096.6Ring Nut
2116.12Stem
2256.16Diaphragm
2276.15Diaphragm Plate
2286.13Spacer Bushing
2296.21Actuator Spring
2316.22Distance Plate
2536.8Guide Bushing
2546.80Plain Bearing
2556.18Thrust Washer
2586.26Vent Plug
2726.17O-Ring
2736.11Scraper Ring
2756.10O-Ring
3266.23Spring Adjusting Plate
3356.3.1Hexagon Bolt - short
3366.3.2Hexagon Bolt - long
3376.5Plain Washer
3396.25Protection Sleeve
3486.20Special Nut
3496.19Lock Washer
3516.4Hexagon Nut
28. Log the maintenance interval and the work performed.
29. The actuator subassembly is ready to be mounted on
the valve and the accessories attached.
336
335
337
203
258
231
326
229
202
253
254
351
339
275
273
Table 13: Actuator parts
Figure 10: Actuator parts
19
flowserve.com
Actuator without attachments
Spring-to-open
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Disassembly instruction of the actuator subassembly
NOTICE
1. Fix the actuator on the assembly table, if this is not
already happened.
2. Loosen the lock nut (344) counterclockwise and disassemble the upper coupling (249) and lock nut clockwise (see page 15).
3. Disassemble the hexagon bolts (335), plain washers
(337), hexagon nuts (351) and ring nuts (209).
4. Pull off the protection sleeve (339).
springs inside.
5. Lubricate the threads and loosen the long hexagon bolts
(336), plain washers (337) and hexagon nuts (351) uniformly in a clockwise sequence as the springs expand.
NOTICE
8.8 or higher, as well as washers and nuts.
6. Lift off the diaphragm casing (203).
Limit disassembly only to necessary components.
WARNING
We recommend using threaded bolts
meeting standards from ISO 898-1,
Risk of injury by jumping out parts ! Pre-loaded
Reassembly instruction of the actuator subassembly
NOTICE
14. Lubricate the new O-ring (275), new scraper ring (273)
with an appropriate lubricant and install into the guide
bushing (253).
15. Lubricate the new O-ring (272) with an appropriate
lubricant.
16. Lower the spacer bushing (228), diaphragm plate
onto the stem (211).
17. Lubricate the thread of the stem (211) with an appropriate lubricant and install and finger tighten the special nut (348).
18. Turn the special nut (348) clockwise using a suitable
torque wrench.
19. Loosen and remove the diaphragm-stem unit (211-
349) from the Special Tool. Lubricate the actuator
stem with an appropriate lubricant.
20. Install and positioning the spring adjusting plate (326)
such that the drilling and air connection match.
7. Carefully remove the diaphragm-stem unit (211 - 349).
8. Remove the actuator springs (229).
9. Remove the spring adjusting plate (326).
10. Remove the scraper ring (273) and O-ring (275).
11. Secure the diaphragm-stem unit into the Special Tool.
12. Loosen the special nut (348) counterclockwise and
remove the lock washer (349), thrust washer (255), Oring (272), diaphragm (225), diaphragm plate (227),
and spacer bushing (228).
13. Check stressed surface areas for damage such as
scoring and deformities. Use a brass brush or similar
tool to clean bolting. Check for corrosion or any other
damage.
21. Install and align the actuator springs (229).
22. Carefully lower the diaphragm-stem unit (211- 349)
into the diaphragm casing.
23. Install the diaphragm casing (203), positioning the
casing such that the air connections are aligned.
24. Lubricate the threats of the long hexagon bolts (336)
with an appropriate lubricant then compress the springs
uniformly in a clockwise sequence by tightening the long
hexagon bolts (336), plain washers (337) and hexagon
nuts (351). Alternative method see NOTICE step 5.
25. Install the short hexagon bolts (335), hexagon nuts (351)
as well as the hexagon bolts (335) and ring nuts (209).
26. Tighten the nuts (351) using a crosswise pattern in
four steps.
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
27. Install the protection sleeve (339).
28. Reassemble the yoke and coupling parts, perform three
full strokes then check the tightening of the casing bolting.
29. Log the maintenance interval and the work performed.
30. The actuator subassembly is ready to be mounted on
the valve and the accessories attached.
Item #
Part
WWEU
2026.1Diaphragm Casing
2036.2Diaphragm Casing
2096.6Ring Nut
2116.12Stem
2256.16Diaphragm
2276.15Diaphragm Plate
2286.13Spacer Bushing
2296.21Actuator Spring
2536.8Guide Bushing
2546.80Plain Bearing
2556.18Thrust Washer
2586.26Vent Plug
2726.17O-Ring
2736.11Scraper Ring
2756.10O-Ring
3266.23Spring Adjusting Plate
3356.3.1Hexagon Bolt - short
3366.3.2Hexagon Bolt - long
3376.5Plain Washer
3396.25Protection Sleeve
3486.20Special Nut
3496.19Lock Washer
3516.4Hexagon Nut
209
348
349
255
225
227
228
211
336
335
337
203
272
229
326
202
253
254
258
351
339
275
273
Table 14: Actuator parts
Figure 11: Actuator parts
21
flowserve.com
Actuator with attachments
Spring-to-close
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
Disassembly instruction of the actuator subassembly
NOTICE
1. Fix the actuator on the assembly table, if this is not
already happened.
2. Disassemble the attachments first (see page 16).
3. Loosen the lock nut (344) clockwise and disassemble
the upper coupling (249) and lock nut (see page 15).
4. Disassemble the hexagon bolts (335), plain washers
(337), hexagon nuts (351) and ring nuts (209).
5. Pull off the protection sleeve (339).
springs inside.
6. Lubricate the threads and loosen the long hexagon bolts
(336), plain washers (337) and hexagon nuts (351) uniformly in a clockwise sequence as the springs expand.
Limit disassembly only to necessary components.
WARNING
Risk of injury by jumping out parts ! Pre-loaded
Reassembly instruction of the actuator subassembly
NOTICE
14. Lubricate the new O-rings (275), new scraper rings
(273) with an appropriate lubricant and install into the
guide bushing (253 and 390).
15. Lubricate the new O-ring (272) with an appropriate lubricant.
16. Lower the thrust washer (255), diaphragm (225), O-
onto the stem (211).
17. Lubricate the thread of the stem (211) with an appropriate lubricant and install and finger tighten the special stem (348).
NOTICE
of the Positioning Template. Mark the position.
18. Turn clockwise the special stem (348) using a suitable
torque wrench.
The diaphragm plate should be positioned to the diaphragm with the aid
22
NOTICE
8.8 or higher, as well as washers and nuts.
7. Lift off the diaphragm casing (203) and spring adjusting plate (326).
8. Remove the actuator springs (229).
9. Carefully remove the diaphragm-stem unit (211 - 349).
10. Remove the scraper rings (273) and O-rings (275).
11. Secure the diaphragm-stem unit into the Special Tool.
12. Loosen the special stem (348) counterclockwise and
remove the lock washer (349), spacer bushing (228),
diaphragm plate (227), diaphragm (225), O-ring (272)
and thrust washer (255).
13. Check stressed surface areas for damage such as scoring
and deformities. Use a brass brush or similar tool to clean
bolting. Check for corrosion or any other damage.
We recommend using threaded bolts
meeting standards from ISO 898-1,
19. Loosen and remove the diaphragm-stem unit (211
- 349) from the Special Tool. Lubricate the actuator
stems with an appropriate lubricant.
20. Carefully lower the diaphragm-stem unit (211 - 349)
into the diaphragm casing.
NOTICE
Mark align.
21. Install and align the actuator springs (229).
22. Install and positioning the spring adjusting plate (326)
such that the drilling, mark and air connection match.
23. Install the diaphragm casing (203), positioning the casing
such that the drilling, mark and air connections match.
24. Lubricate the threats of the long hexagon bolts (336)
with an appropriate lubricant and load the springs uniformly in a clockwise sequence by tightening the long
hexagon bolts (336), plain washers (337) and hexagon
nuts (351). Alternative method see NOTICE step 6.
Position the diaphragm-stem unit
such that the air connection and the
FlowAct Diaphragm Linear Actuator FCD VLENIMFACTA4 10/16
25. Install the short hexagon bolts (335), hexagon nuts (351)
as well as the hexagon bolts (335) and ring nuts (209).
26. Tighten the nuts (351) using a crosswise pattern in
four steps.
27. Install the protection sleeve (339).
28. Reassemble the yoke and coupling parts, perform three
full strokes then check the tightening of the casing bolting.
Item #
Part
WWEU
2026.1Diaphragm Casing
2036.2Diaphragm Casing
2096.6Ring Nut
2116.12Stem
2256.16Diaphragm
2276.15Diaphragm Plate
2286.13Spacer Bushing
2296.21Actuator Spring
2316.22Distance Plate
2536.8Guide Bushing
2546.80Plain Bearing (2x)
2556.18Thrust Washer
2586.26Vent Plug
2726.17O-Ring
2736.11Scraper Ring (2x)
2756.10O-Ring (2x)
2766.9O-Ring
3266.23Spring Adjusting Plate
3356.3.1Hexagon Bolt - short
3366.3.2Hexagon Bolt - long
3376.5Plain Washer
3396.25Protection Sleeve
3486.29Stem
3496.19Lock Washer
3516.4Hexagon Nut
3906.24Guide Bushing
29. Log the maintenance interval and the work performed.
30. The actuator subassembly is ready for the reassemble
of the attachments - see page 16 - and accessories.
336
335
337
202
276
390
254
258
326
229
202
276
253
254
351
339
275
273
Table 15: Actuator parts
Figure 12: Actuator parts
23
flowserve.com
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.