Flowserve Automax Aviator User Manual

Automax Valve Automation Systems
Installation, Operation and Maintenance Instructions
LML0002-1 (AUTO-32) 3/03 Page 1 of 2 © 2003, Flowserve Corporation, Printed in U.S.A.
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr. Flow Control Division Springville, Utah 84663-3004 Cookeville, TN 38501 www.flowserve.com Phone: 801 489 8611 Phone: 931 432 4021
Mechanical Installation
Electrical Connections
The Aviator™ features three (3) 1⁄2" NPT conduit entries. The switches and pilot solenoid are wired to a printed circuit board to simplify customer wiring connections. A wiring diagram is included under the lid. Simply make desired connections to the circuit board using the attached screw terminal blocks. Secure a grounding wire under the green grounding screw. Make sure the solenoid control voltage is the same as the solenoid electrical rating.
For hazardous locations, U.L. and National Electric codes require an approved sealing fitting within 18 inches of the switch enclosure. Sealing fittings are not required for Division 2 non-incendive applications. Open conduit entries must be closed after installation using a close-up plug approved for hazardous locations. Conduit and plugs must engage a full five (5) threads.
Spool and Tubing Configuration
1. For spring return actuators, a 4-way spool valve is provided with port #2 plugged. For double acting actuators, the same valve is provided with no plugs. Make sure the correct spool is selected before installing tubing. (Note: the APS2 module can be supplied on spring return actuators to purge the spring chamber with supply air.)
2. Make sure all air pressure is removed before installing tubing.
3. Attach tubing according to Figures 1 or 2 below, depending upon application. Attach supply tubing to Port 1 and use 3 and 5 exhaust.
4. To prolong actuator life use only clean, dry plant air. Lubricated air is not required, although it is recommended particularly for high cycle applications.
Automax Aviator
Caution
To prevent ignition of hazardous
atmospheres, keep cover bolts tight
while circuits are live. Disconnect
supply circuit before opening.
Figure 1 DA Actuator
Figure 2 SR Actuator
Figure 3 Cam Adjustment
Switch Setting
1. Rotate actuator to desired position.
2. Loosen five captive cover screws and remove lid, turning slightly while lifting.
3. To adjust the limits, lift or depress cam against spring to disengage splines and turn cam until switch activates / deactivates as desired (Figure 3).
4. Release cam, assuring that the splines are engaged.
5. Clean base and lid flanges and replace lid on base. Make sure wires are NOT caught between flanges, and tighten captive screws.
DEMKO 02 ATEX 130947 0518
Flameproof: II 2 G EEx d IIB T4-T6
DEMKO 02 ATEX 0218321
Non-Incendive: II 3 G EEx nC II T4-T6
Tamb = -25°C; T6 +55°C, T5 +70°C, T4 = 80°C
Automax Valve Automation Systems
Installation, Operation and Maintenance Instructions
LML0002-1 (AUTO-32) 3/03 Page 2 of 2 © 2003, Flowserve Corporation, Printed in U.S.A.
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr. Flow Control Division Springville, Utah 84663-3004 Cookeville, TN 38501 www.flowserve.com Phone: 801 489 8611 Phone: 931 432 4021
Item Part # Description Qty.
1 XM0268 Housing Base 1 2 X00903
1
/8" Muffler 1 3 X00878 Spool Valve 1 4 X00838 10-32 x 1
1
/8SHCS 3 5 1079352 Breather 2 6 X00892 O-Ring 2 7 X00814 O-Ring 1 8 X00779 O-Ring 3 9 X00837
1
/
8
x 2 Tubing 1 10A Varies 2 Watt Solenoid Pilot 2 11A 100158 4-40 x 1 PHS 1 12A X00893 O-Ring 1 13A XM0276 Manifold Block 1 10B Varies .67 Watt Solenoid Pilot 1 11B X00895 O-Ring 1 12B X00894 O-Ring 1 13B XM0292 Manifold Block 1
Item Part # Description Qty.
14 100167 8-32 x
1
/
2
PHS 4
15 X00410
1
/
8
" Tube Fittings 2 16 X00410G Gasket 2 17 Varies Switch Card 1 18 105915 #6-32 x
1
/
4
PHS 2 19 103627 Ground Screw 1 20 105626 Cup Washer 1 21 X00801
5
/
16
-18 bolts 5 22 XM0269 Housing Cover 1 23 X00663 Rotor 1 24 X00677 O-Ring 1 25 X00662 Dome 1 26 X00676 #10-24 x
1
/
2
PHS 4 27 Varies Shaft Assembly 1 28 103603 O-Ring 2 29 101810 Snap Ring 1
Lubrication
All Aviator™ spool valves are pre-lubricated and will operate dry (with no additional lubrication). The use of lubricated air will not interfere with the Aviator’s functioning.
If air lubrication is used, the oils listed below are popular, easily obtainable fluids that are recommended for use with the Aviator™ Spool valve: Gulf Harmony 47, Mobil DTE Medium, Shell Tellus 29, Texaco Rondo B, Sohivis 47 and Sunnis 921. Many other lubricants are acceptable providing they do not contain detergents that will attack Nitrile or Viton Seals.
Bill of Material